Sei sulla pagina 1di 35

PASOLINK V4 LCT Training Manual

NEC Cooperation

CONTENTS
Part1
Part2
Part3

LCT
LCTCONNECTION
CONNECTION

ALL
ALLMENUS
MENUS

ITEMS
ITEMSMEANING
MEANINGIN
INMENUS
MENUS
&&HOW
HOWTO
TOUSE
USEIT
IT

PASOLINK Introduction

TARGETS
KNOW HOW TO LOGIN LCT
KNOW ITEMS MEANING IN MENUS
KNOW HOW TO USE ITEMS IN MENUS

PASOLINK Introduction

LCT CONNECTION (1)

The Pasolink equipment can be configured controlled and


monitored locally using the Local Craft Terminal (LCT). Using the
LCT it is possible to monitor the local Indoor Unit and related Out
Door Unit

A personal computer can be used as the LCT and terminal software


like windows Hyper terminal can be used to communicate with the
IDU.

The terminal software, communications parameters should be set


as follows
Bits per second
9600
Data bits 8
Parity
None
Stop bits 2
Flow Control
Hardware
Emulation VT100 Video Terminal
Transmission
Add CR/LE at end of line: yes
Local
Echo: No
(Send line ends with line feeds: yes)*
(Echo typed characters locally: No)* Receiving
CR : No
Return to the right edge : Yes
Force incoming data to 7-bit ASCII: No
(Append line feed to incoming line feeds :no)*
(Force incoming data to 7-bit ASCII: No)*
(Wrap lines that exceed terminal width: Yes)*
* Settings for Windows Hyper Terminal

PASOLINK Introduction

LCT CONNECTION (2)

The Remote Pasolink equipment (opposite station ) can be


configured controlled and monitored from the local IDU using the
Local Craft Terminal (LCT). Connect the LCT to the NMS/RA port.
Using the LCT it is possible to monitor the Remote Indoor Unit and
related Out Door Unit
Remote configuring/monitoring is not possible when the PM
card is mounted or during HBER alarm condition.
A personal computer can be used as the LCT and terminal
software like windows Hyper terminal can be used to communicate
with the IDU.
The terminal software, communications parameters should be set
as follows:

Bits per second


9600
Data bits 8
Parity
None
Stop bits 2
Flow Control
Hardware
Emulation VT100 Video Terminal
Transmission
Add CR/LE at end of line: yes
Local
Echo: No
(Send line ends with line feeds: yes)*
(Echo typed characters locally: No)* Receiving
CR : No
Return to the right edge : Yes
Force incoming data to 7-bit ASCII: No
(Append line feed to incoming line feeds :no)*
(Force incoming data to 7-bit ASCII: No)*
(Wrap lines that exceed terminal width: Yes)*
* Settings for Windows Hyper Terminal

PASOLINK Introduction

HYPER-TERMINAL SETTING

PASOLINK Introduction

LCT--MENUS

(1+0)

5.CAS
6.CRC

99.Exit

TX power :*.**
RX level :*.**

Manufactured date
Software version
Bit rate
Option module
Manufactured date

Sub band

Start frequency
Shift frequency
PASOLINKSerial
Introduction
number

ODU

Software version
Bit rate
RF band

ODU

Monitoring

1. Monitoring voltage
2. Monitoring voltage (con mode)
3. Alarm/Status
4. Inventory
00. Menu
99. Exit

4.Framing

00.Menu

IDU

Maintenance

(1+1)

3.Flow ctrl

7.Collion Report

IDU

4.Exit

1. MAINT
2. FE loop back ctrl 1-16
3. NE loop back ctrl 1-16
4. BER ALM >> AIS
5. CW
6. Power mute
7. ATPC manual ctrl
00. Menu
99. Exit
1. to 5. same as 1+0
6. Power mute1
7. Power mute2
8. TX SW ctrl
9. RX SW ctrl
10. ATPC manual ctrl
00. & 99. same as 1+0

1. Port1 setting
2. Port2 setting
3. FE link down
00. Menu
99. Exit

2.Mode

Alarm Table

3.Monitoring

1. System configuration
2. LAN setting
3. Channel usage error
00. Menu
99. Exit

1.Thoughtput

Port setting

2.Maintenance

Maintenance

1.Setting

1. ATPC/MTPC
2. MTPC TX power
3. ATPC TX power range
4. ODU ALM mode
5. RX threshold
00. Menu
99. Exit

LAN setting

Next Item

Password Change:

TX power ctrl

Setting

Password:

1.Bit rate (16x2MB)


2. AIS RCVD alarm/status
3. AIS SEND alarm/status
4. TX/RX frequency
5. TX power ctrl
6. Main channel usage 1-16
7. BER alarm threshold
8. Frame ID
9. WS channel usage
10. DSC1
11. DSC2
12. DEM invert
13. Alarm table
14. Next items
00. Menu
99. Exit

INPUT LOSS AIS RCVD


AIS SEND OUTPUT LOSS
WS INPUT LOSS WS AIS
RCVD WS AIS SEND
WS OUTPUT LOSS LAN
INTFC ALM TX CLK LOSS
RX CLK LOSS FSYNC
ALM
HIGH BER ALM LOW BER
ALM BER ALM
MOD ALM
DEM ALM
OPR ALM
TX PWR ALM RX LEV
ALM APC 1 ALM
APC2 ALM
IF INPUT ALM MAINT
TX SEL
RX S EL
MDP CPU ALM

INPUT LOSS 1-16


CHANNEL USAGE ERROR 1-16
AIS RCVD 1-16
AIS SEND 1-16
OUTPUT LOSS 1-16
LAN INTFC ALM
WS INPUT LOSS
WS AIS RCVD WS AIS SEND
WS OUTPUT LOSS
TX CLK LOSS
RX CLK LOSS
FSYNC ALM
HIGH BER ALM
LOW BER ALM BER ALM
MOD ALM
DEM ALM
MDP CPU ALM

TX PWR ALM
RX LEV ALM
APC 1 ALM
APC2 ALM
IF INPUT ALM
MUTE
TX FREQ CH
RX FREQ CH

LCT MAIN MENU

Connect the LCT PC to the IDU LA Port or


RA port using a RS232-C cable. Open the
communication software ( eg. HyperTerminal).
Press the CTRL and D keys at the
same time

Password :********
Change Password? (No:0/Yes:1) :1
New Password :********
New Password (Re-enter) : * * * * * * * *
1. Setting
2. Maintenance
3. Monitoring
99. Exit
Select Function No. :

LCT MAIN MENU


LCT main menu has the following main functions.
Setting: Local configuration of IDU and ODU
Maintenance: IDU and ODU maintenance
functions
Monitoring: Pasolink Alarm / Status Monitoring
function

From the LCT main menu and sub-menus


select 99. EXIT to close the LCT program.

From the sub menus, select 00.Menu to


display the LCT main menu

After data is entered to cancel or go back to


higher level menu, press ESC

PASOLINK Introduction

SETTING MENU

SETTING menu is used to


Configure/setup the Pasolink IDU and
ODU locally.
Current setting for each menu item is
shown in brackets.

1. Setting
2. Maintenance
3. Monitoring
4. Exit
Select Function No:

Press 1 and Enter

Note: The Items shown on the Setting menu


depends on the optional hardware mounted and
the configuration.

Setting
1. Bit rate
(1 6x2MB)
2. AIS RCVD alarm/status (alarm)
3. AIS SEND alarm/status (alarm)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used: UUNN NNNN UUNN
NNNN)
7. BER alarm threshold
(10-3)
8. Frame ID (1)
9. WS channel usage
(on)
1 0.DSC1
(232)
11 .DSC2
(232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00.Menu
99.Exit
Select Item No. :

PASOLINK Introduction

BIT RATE SETTING


1. Bit rate (transmission capacity)
Press 1 and Enter
Setting
1. Bit rate (1 6x2MB)
(4x2MB) Bit rate (2x2:0 /
2. AIS RCVD alarm/status
(alarm)
4x2:1 / 8x2:2 / 16x2:3) : 2
3. AIS SEND alarm/status
(alarm)
Changing the bit rate will cause
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
temporary communication
6. Main channel usage 1 - 16 (used: UUNN
loss until the bit rate of the
NNNN UUNN NNNN)
opposite site is changed.
7. BER alarm threshold (10-3)
8. Frame ID
(1)
The buzzer may be issued until
9. WS channel usage (on)
then.
1 0.DSC1 (232)
11 .DSC2 (232)
Press any key to continue ... Press
12.DEM invert
(off)
ESC key to quit
13.Alarm table
14.Next items
Two types of IDUs:
00.Menu
Fixed bit rate(4x2MB) : the bit rate is automatically detected
99.Exit
and set in IDU.
Select Item No. :
Variable bit rate : the selection is 2MBx2, 2MBx4, 2MBx8 or
2MBx16 . Enter the number corresponding to the bit rate
required and press the ENTER key

Note: The IDU has two type of 2Mb input


connections. 75 ohm unbalance or
120 ohm balanced .
PASOLINK Introduction

10

ALARM INDICATION SIGNAL (AIS)


SETTING

Setting
2. AIS RCVD alarm/status (status)
1. Bit rate (1 6x2MB)
Press 2 and Enter
2. AIS RCVD alarm/status (status)
AIS RCVD alarm/status
Press
3
and
Enter
3. AIS SEND alarm/status (status)
(status:0 /alarm :1)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
3. AIS SEND alarm/status (alarm)
6. Main channel usage 1 - 16 (used: UUNN
NNNN UUNN NNNN)
AIS SEND alarm/status
7. BER alarm threshold (10-3)
(status:0 /alarm :1 )
8. Frame ID
(1)
9. WS channel usage (on)
Note:
1 0.DSC1 (232)
When AIS SEND is set to alarm , and AIS is sent out
11 .DSC2 (232)
the front panel IDU alarm LED lights. When AIS
12.DEM invert
(off)
SEND is set to status and AIS is sent out, no
13.Alarm table
alarm indication is initiated.
14.Next items
00. Menu
When AIS RCVD is set to alarm , on reception of AIS
99. Exit
the front panel IDU alarm LED lights. When AIS
Select Item No. :
RCVD is set to status on reception of AIS no
alarm indication is initiated.
PASOLINK Introduction

11

TX/RX FREQUENCY SETTING


Setting
1. Bit rate
(1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
Press 4 and Enter
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used: UUNN
NNNN UUNN NNNN)
7. BER alarm threshold
(10-3)
8. Frame ID (1)
9. WS channel usage
(on)
1 0.DSC1
(232)
11 .DSC2
(232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. :

4. TX/RX Frequency (4ch)


TX/RX frequency (0-255ch):1
1+0 or 1+1 Hot Standby Configuration
4. TX/RX Frequency
( No.1:4ch/No.2:10ch)
1. No.1 TX/RX Frequency (4ch)
2. No.2 TX/RX Frequency (10ch)
1+1 Twin Path Configuration

This menu item is used to configure the ODU transmit and


receive frequencies. The ODU frequency band
information is shown in the label attached to it.

PASOLINK Introduction

12

TX POWER CONTROL (1)


Setting
1. Bit rate
(1 6x2MB)
2. AIS RCVD alarm/status (status)
Press 5 and Enter
3. AIS SEND alarm/status (status)
TX power ctrl (ATPC)
4. TX/RX frequency
(4ch)
5. TX power ctrl (ATPC)
1. ATPC/MTPC
(ATPC)
6. Main channel usage 1 - 16 (used: UUNN NNNN
2. MTPC TX power
(0dB)
UUNN NNNN)
7. BER alarm threshold (10-3)
3. ATPC TX power range (MAX : 0dB / MIN : -30dB)
8. Frame ID
(1)
4. ODU ALM mode
(hold)
9. WS channel usage
(on)
5.
RX
threshold
(-55dBm)
1 0.DSC1
(232)
11 .DSC2
(232)
00. Menu
12.DEM invert
(off)
99. Exit
13.Alarm table
Select
Item No.
14.Next items
00. Menu
99. Exit

1. ATPC/MTPC (ATPC)
ATPC/MTPC (MTPC:0 /
ATPC:1) :0

2.MTPC TX power (0dB)


MTPC TX power (-30 to
0dB) :-5

Select Item No. :

MTPC TX PWR defines the ODU output power in MTPC mode.


The value entered is the attenuation level in dB from
the maximum ODU output power.

3. ATPC TX power range (MAX :0


to /MIN:-15 dB):-5
Min power(-30 to -5dB):-20

ATPC/MTPC MODE SELECTION


This menu item select the TX PWR Control
mode to be used.

ATPC range defines the maximum and minimum transmission power


during the ATPC operation.

PASOLINK Introduction

13

TX POWER CONTROL (2)


Press 5 and Enter
4. ODU ALM mode (hold)
Setting
1. Bit rate
(1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used: UUNN
NNNN UUNN NNNN)
7. BER alarm threshold (10-3)
8. Frame ID (1)
9. WS channel usage
(on)
1 0.DSC1
(232)
11 .DSC2
(232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. : 5

From the TX power ctrl menu, select


[5] and press Enter.

TX power ctrl (ATPC)


1. ATPC/MTPC
(ATPC)
2. MTPC TX power
(0dB)
3. ATPC TX power range (MAX : 0dB / MIN :
-30dB)
4. ODU ALM mode
(hold)
5. RX threshold
(-55dBm)
00. Menu
99. Exit
Select Item No.: 4
5. RX threshold

(-55dBm)

RX threshold(-80 to -30 55dBm)


RX THRESHOLD
When the monitored RX signal level falls
below this level, a control signal is
sent to the opposite station to
initiate the ATPC function

PASOLINK Introduction

ODU ALM mode (MAX:


0/min:1/hold:hold:2):1

ODU ALARM MODE


This menu item defines the ODU
transmit power level when
ATPC control
communication between IDU
and ODU fails. In MTPC
mode this setting is ignored

MAX: Power is controlled to ATPC


Max level
MIN : Power is controlled to ATPC
Min level
HOLD: Power is maintained at
current level
14

MAIN CHANNEL USAGE


Setting
1. Bit rate
(1 6x2MB)
2. AIS RCVD alarm/status (status)
Main channel usage 1-16
3. AIS SEND alarm/status (status)
( 1:used
2:not used 3:not used 4: not used 5:N/A
6:N/A
7:N/A
4. TX/RX frequency
(4ch) Press 6 and Enter
8:N/A 9:N/A 10:N/A
11:N/A 12:N/A 13:N/A
14:N/A
5. TX power ctrl
(ATPC)
15:N/A 16:N/A )
6. Main channel usage 1 - 16 (used: UNNN
#### #### ####)
Select channel No. :2
7. BER alarm threshold (10-3)
Channel 2 (used: 0/not used;1):0
8. Frame ID (1)
Select the channel number and select:
9. WS channel usage
(on)
1 0.DSC1
(232)
0 and Enter to use the channel for E1 transmission
11 .DSC2
(232)
1 and Enter not to use the channel for E1 transmission.
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
N/A indicates the channels that are not available for E1 transmission due to
99. Exit
10/100 Base-T LAN assignment or hardware restrictions
Select Item No. : 5
#: Indicates the channels that are restricted by hardware limitations, bit rate setting or selected for LAN signal transmission. U:
Indicates when the channel is used for E1 transmission. N: Indicates when the channel is not used. Inhibits alarm.
The variable bit rate type IDUs are either 16MB/s or 32Mb/s rate. In 16Mb/s type the selection is 2MBx2, 2MBx4 or 2MBx8 and 32Mb/s
type the selection is 2MBx2, 2MBx4, 2MBx8 or 2MBx16. The display will show the rate selection accordingly.

PASOLINK Introduction

15

BER ALM POINT & FRAME ID

7. BER alarm threshold (10-4)


BER alarm threshold (10-3:0 / 104:1 / 10-5:2 / 10-6:3) :
Press 7 and Enter

BER ALARM THRESHOLD


When excessive BER is detected, the
IDU insert AIS into the data
streams sent to the MUX
equipment. Threshold value for
AIS insertion can be selected
as 1 x 10-3, 1 x 10-4, 1 x 10-5
or 1 x10-6.

8. Frame ID(2)
Input ID No. (0-7): 1
Setting
1. Bit rate
(1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used: UNNN
#### #### ####)
7. BER alarm threshold (10-3)
8. Frame ID (1)
9. WS channel usage
(on)
1 0.DSC1
(232)
11 .DSC2
(232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. : 5
PASOLINK Introduction

Press 8 and Enter


FRAME ID
Select item No.This item defines the
Frame ID of the
transmit/receive signal. The
Frame ID is used at the receive
station to identify the correct
receive signal.
As a signal with a different Frame ID
cannot be received, the Frame
ID of the opposite station
should be set to the same ID
number.
In the (1+1) Hot standby system, both
No.1 and No.2 channels should
have the same Frame ID. The
number of Frame IDs, which
can be set, is eight (ID0 to ID7).

DSC ASSIGNMENT
Setting
1. Bit rate (1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used:
UNNN #### #### ####)
7. BER alarm threshold (10-3)
8. Frame ID
(1)
9. WS channel usage (on)
1 0.DSC1 (232)
11 .DSC2 (232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. : 5

10. DSC1 (232)

11. DSC2 (232)

DSC1( 232:0 / 64k: 1 ): 0

DSC2( 232:0 / 422:1 /


485(TERM):/485 ( NON
TERM): :3):0

Press 10 and Enter


Press 11 and Enter

DSC2 can be used as a 9.6Kbps


interface with RS232C / RS
422 / RS485 interface
selectable.

Pasolink V4 uses six service channels in its radio overhead


frame as shown in the table.

DSC1 default setting is 9.6Kbps


RS232C interface. A 64Kbps
G703 interface card or V11
interface card are available
as an option.
PASOLINK Introduction

17

WS CHANNEL USAGE & DEM


INVERT
Setting
1. Bit rate (1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used:
UNNN #### #### ####)
7. BER alarm threshold (10-3)
8. Frame ID
(1)
9. WS channel usage (on)
1 0.DSC1 (232)
11 .DSC2 (232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. : 5

WS CHANNEL USAGE
The WS option is applicable only on the 16x2 MB system with WS
INTFC mounted. In this case if WS E1 channel is not used, set
this to not use inhibit alarms.
When the WS INTFC module (optional) is not mounted, this menu item
is not displayed.
9. WS channel usage (not used)
WS Channel usage (used:0 / not used:1) : 0
12.DEM invert (off)
DEM invert (off:0 / on:1) :
DEM INVERT
When the ODU receive signal is down converted the signal sent
to the IDU may have a normal or inverted spectrum.

Note: 8GHz 728MHz shift-E7426B / E9747B,F


7GHz 161MHz shift-G6583A,B / G6584A,B
7GHz 154MHz shift-G6583E,F / G6584E,F

For the listed ODUs select DEM invert ON

8GHz all Types G6585,G6586,G3362,G3363


PASOLINK Introduction

18

ALARM TABLE
Setting
1. Bit rate (1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used:
UUNN NNNN UUNN NNNN)
7. BER alarm threshold (10-3)
8. Frame ID
(1)
9. WS channel usage (on)
1 0.DSC1 (232)
11 .DSC2 (232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. : 5
This menu item defines the external relay
outputs. The alarms are sent out
through four relays(1 +0) or six
relays(1 +1). Multiple alarms can be
assigned to any relay and alarms can
be assigned to multiple relays.

C1 C2 C3 C4 C5 C6
1.INPUT LOSS
OUT OUT --- --- --- --2.AIS RCVD
--- --- --- --- --- --3.AIS SEND
--- --- --- --- --- --4.OUTPUT LOSS
--- --- OUT OUT --- --5.TX CLK LOSS
OUT --- --- --- --- --- --larm table 2/3
C1 C2 C3 C4 C5 C6
9.FSYNC ALM1
--- --- OUT --- --- --11.HIGH BER ALM1 --- --- OUT --- --- --12.HIGH BER ALM2 --- --- --- OUT --- --13.LOW BER ALM1
--- --- --- --- --- --15.BER ALM
--- --- OUT --- OUT --17.MOD ALM1
OUT --- --- --- --- --19.DEM ALM1
--- --- OUT --- --- --21.OPR ALM1
OUT --- OUT --- --- --23.TX PWR ALM
OUT --- --- --- --- --25.RX LEV ALM1
--- --- OUT --- --- --------33.MAINT
MASK MASK MASK MASK MASK OUT

PASOLINK Introduction

19

NEXT ITEMS MENU


Setting
1. Bit rate (1 6x2MB)
2. AIS RCVD alarm/status (status)
3. AIS SEND alarm/status (status)
4. TX/RX frequency
(4ch)
5. TX power ctrl
(ATPC)
6. Main channel usage 1 - 16 (used:
UUNN NNNN UUNN NNNN)
7. BER alarm threshold (10-3)
8. Frame ID
(1)
9. WS channel usage (on)
1 0.DSC1 (232)
11 .DSC2 (232)
12.DEM invert
(off)
13.Alarm table
14.Next items
00. Menu
99. Exit
Select Item No. : 5

Press 14 and Enter


Next item
1.System configuration
2. LAN setting
3. Channel usage error
00. Menu
99. Exit
Select Item No. : 5

Press 3 and Enter


1.

Press 1 and Enter


1. System Configuration (Hot
standby)
System configuration (1+0
expandable: 0 / Hot standby:
1/ Twin path: 2)
System Configuration menu item
appears only in (1+1) systems.

Channel usage error (not report)

Channel usage error (report: 0 / not report :1); 0


When a main channel or WS channel is selected as not
used, and the 2MB or WS interface detects a 2MB
signal at the input, This item defines whether to report
or not to report this condition as an alarm event.

(1+0) expandable configuration is selected when in an (1+1) hardware configuration only one channel IDU
and ODU is equipped or used. Other channel alarms are inhibited.
(1+1) Hot standby only one channel is transmitted at a time but receive from both channels and select one.
(1+1) Twin Path both channels transmit andPASOLINK
use two different
frequencies.
Introduction
20

NEXT ITEMS MENU-LAN


SETTING
1.Thoughtput

Port setting

LAN setting

1. Port1 setting
2. Port2 setting
3. FE link down
00. Menu
99. Exit

3.Flow ctrl
4.Framing
5.CAS
6.CRC
7.Collion Report
00.Menu

0. Disable
1.

2M

2.

4M

3.

8M

4.

16M

5.

32M

99.Exit

Throughout = 2MB Framing = OFF


1.Thoughtput
2.Mode
3.Flow ctrl
4.Framing
5.Collion Report
00.Menu
99.Exit

Throughout > 2MB

Mode Setting

Port setting

Next item
1.System configuration
2. LAN setting
3. Channel usage error
00. Menu
99. Exit
Select Item No. : 5

2.Mode

Throughput setting

Throughout = 2MB Framing = ON

0. AUTONEG (Auto-MDI/MDIX)
1.10M-Half (MDI)
2.10M-Full (MDI)
3.100M-Half (MDI)
4.100M Full (MDI)
5 .10M-Half (MDIX)
6.10M-Full (MDIX)
7.100M-Half (MDIX)
8.100M Full (MDIX)
00. Menu
99. Exit

Port setting

1.Thoughtput
2.Mode
3.Flow ctrl
4.Collion Report
00.Menu
99.Exit

PASOLINK Introduction

21

Applicable Traffic Channels - 1

PASOLINK Introduction

22

Applicable Traffic Channels - 2

PASOLINK Introduction

23

LAN PORT SETTING (1)


1. LAN setting
1.Port1 setting (2M)
2.Port2 setting (disable)
3.FE link down (enable)
00. Menu
99. Exit
Select item No. :

Press 1 or 2 and Enter

Select the rate for each LAN


Ports, Depending on
the selection the No.
of channels for E1
data are decided. See
the table in the next
page.

1. Throughput (disable)
Throughput (disable:0 / 2M:1 / 4M:2 / 8M:3 / 16M:4 / 32M:5) :1

1. Port 1 setting

1. Throughput
(2M)
2 .Mode
(AUTONEG(AUTO-MDI/MDIX))
3. Flow ctrl (off)
4. Framing (on)
5. CAS
(on)
6. CRC
(on)
7. Collision report (report)
00. Menu
99. Exit

3. Flow Ctrl (off)


Flow ctrl (off: 0/ on:1):1

Select whether to use flow control or not

4. Framing (off)
Framing ( off : 0 / on : 1 ) :

Select whether to use Framing or not. Applies only


when 2M is selected as throughput for the Port.

5. CAS (off)

Applies when Port throughput is set to 2MB with Framing ON. If CAS is ON
LAN data is also sent in TS16. IF CAS is off then LAN data is not sent in
TS16. PASOLINK Introduction
24

CSC( off: 0/ on: 1)

LAN PORT SETTING (2)


1. LAN setting
1.Port1 setting (2M)
2.Port2 setting (disable)
3.FE link down (enable)
00. Menu
99. Exit
Select item No. :

Press 1 or 2 and Enter


Applies when Port throughput is
set to 2MB with Framing
ON.
6. CRC (off)
CRC( off: 0/ on: 1)

1. Port 1 setting
1. Throughput
(2M)
2 .Mode
(AUTONEG(AUTO-MDI/MDIX))
3. Flow ctrl (off)
4. Framing (on)
5. CAS
(on)
6. CRC
(on)
7. Collision report (report)
00. Menu
99. Exit

3. FE link down (disable)


FE link down (disable :0 / enable :1):

2. Mode

(10M-HALF(MDI))

Mode AUTONEG (AUTO -MDI/MDIX) :0


7. Collision report (report)
Collision Report( report :0 / not report : 1)

10M-HALF(MDI) :1 / 10M-FULL(MDI) :2
100M-HALF(MDI) :3 / 100M-FULL(MDI) :4
10M-HALF(MDIX) :5 / 10M-FULL(MDIX) :6
1 00M-HALF(MDIX):7 / 1 00M-FULL(MDIX):8
Select No. :2

PASOLINK Introduction

25

MAINTENANCE
1. Setting
2. Maintenance
3. Monitoring
4. Exit
Select Function No:
To display the Maintenance menu, press
[2] and [Enter] from the LCT main
menu.
The first item in the maintenance menu shows
the status of the maintenance mode
(Normal or MAINT).
The Maintenance Menu is used to carry out
the following functions.
Maintenance ON/OFF
Far end loop back
Near end loop back
Transmit CW carrier
Stop Transmission (Mute)
BER AIS insertion ON/OFF
TX and RX manual switching(1+1)
Manual ATPC control

Maintenance
1. MAINT
(NORM)
2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
4. BER ALM >> AIS
(on)
5. CW
(off)
6. Power mute1
(off)
7. Power mute2
(off)
8. TX SW ctrl
(AUTO)
9. RX SW ctrl
(AUTO)
10. ATPC manual ctrl
(off)
00. Menu
99. Exit
The maintenance items 7, 8, and 9 applies to (1+ 1) configuration
If TX power control mode is MTPC menu item 10 is not displayed
MAINT (Normal:0 / MAINT:1) : 0
When the maintenance mode is on, or any of the maintenance
control items are on, the front panel MAINT LED (amber)
lights.
PASOLINK
Introduction
26

FE LOOP-BACK
Maintenance
1. MAINT
(NORM)
2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
4. BER ALM >> AIS
(on)
5. CW
(off)
6. Power mute1
(off)
7. Power mute2
(off)
8. TX SW ctrl
(AUTO)
9. RX SW ctrl
(AUTO)
10. ATPC manual ctrl
(off)
00. Menu
99. Exit

2. FE loop back ctrl 1-16


(1:off 2:off 3:off 4:off 5:off 6:off 7:off 8:off 9:off 10:off 11:off
12:off 13:off 14:off 15:off 16:off)
Select channel No. : 1
Channel 1 (off: 0 / on: 1): 0
Press:
[1] and [Enter] to switch Loopback on
[0] and [Enter] to switch Loopback of
2. FE loop back ctrl 1-16 ( ctrl:*--# --z---- ---- )
(ans : *--- ---- ---- ---- )
This menu is used to create a Far End loopback at the main
interface of the opposite station IDU.
Press [2] and [Enter] from the Maintenance Menu to display the
FE Loopback control menu.
The FE Loopback status of channels 1 to 16 are displayed.
Select the channel No: to be controlled and press Enter.

* An asterisk on the cont line indicates that the loopback control is sent to the selected channel
* An asterisk on the ans line indicates that the loopback control was successfully carried out on the selected channel
z A z on the cont line indicates that the loopback control was initiated from the opposite station IDU
# E1 channel is inhibited by hardware restrictions or LAN signal transmission usage
PASOLINK Introduction

27

NE LOOP-BACK
Maintenance
1. MAINT
(NORM)
2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
4. BER ALM >> AIS
(on)
5. CW
(off)
6. Power mute1
(off)
7. Power mute2
(off)
8. TX SW ctrl
(AUTO)
9. RX SW ctrl
(AUTO)
10. ATPC manual ctrl
(off)
00. Menu
99. Exit

3. NE loop back ctrl 1-16


(1:off 2:off 3:off 4:off 5:off 6:off 7:off 8:off 9:off 10:off 1 1:off
12:off 13:off 14:off 15:off 16:off) Select channel No. : 1
Channel 1 (off:0 / on:1) : 0
NEAR END LOOPBACK CONTROL
From this menu, it is possible to create a near end loopback at the
main interface of the local station IDU.
Press [3] and [Enter] from the Maintenance Menu to display the NE
Loopback control
The NE Loopback status of channels 1 to 16 are displayed. Select
the channel No: to be controlled and press Enter.

PASOLINK Introduction

28

BER ALM & CW


Maintenance
1. MAINT
(NORM)
2. FE loop back ctrl 1-16 (ctrl:---- ---- -------)
(ans :---- ---- ---- ----)
3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
4. BER ALM >> AIS
(on)
5. CW
(off)
6. Power mute1
(off)
7. Power mute2
(off)
8. TX SW ctrl
(AUTO)
9. RX SW ctrl
(AUTO)
10. ATPC manual ctrl
(off)
00. Menu
99. Exit
5. CW (off)
CW(off:0 / on:1)

:1

4.BER AIS on/off (on)


BER AIS on/off (off:0 / on:1) 1
BER ALM >> AISBER AIS
From this maintenance menu item, it is possible to
disable BER AIS insertion for all channels.
Press [4] and [Enter] from the Maintenance Menu to
display the BER ALM AIS control.
Press: [0] and [Enter] to disable BER AIS insertion
[1] and [Enter] to enable BER AIS insertion
CW
From this menu item, it is possible to transmit an unmodulated carrier.
To display the CW control, press [5] and [Enter] from
the maintenance menu. MOD CW control is
displayed.
Press: [1] and [Enter] to transmit a CW carrier
[0] and [Enter] stop transmitting a CW carrier

PASOLINK Introduction

29

OTHER MAINT FUNCTIONS


Maintenance
1. MAINT
(NORM)
2. FE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
3. NE loop back ctrl 1-16 (ctrl:---- ---- ---- ----)
(ans :---- ---- ---- ----)
4. BER ALM >> AIS
(on)
5. CW
(off)
6. Power mute1
(off)
7. Power mute2
(off)
8. TX SW ctrl
(AUTO)
9. RX SW ctrl
(AUTO)
10. ATPC manual ctrl
(off)
00. Menu
99. Exit

ATPC manual ctrl (off)


ATPC manual ctrl (off:0 / on:1) :1 ATPC current
(-5dB)
ATPC current (-30 to 0dB) :-10

6.Power mute (off) Power


mute (off:0 / on: 1) : 0
POWER MUTE1 OR 2(1+1)
From this maintenance menu item, it is possible to
switch off the ODU output power.
Press [6] and [Enter] from the Maintenance Menu
to display the Power Mute control.
Press: [0] and [Enter] to select mute off
[1] and [Enter] to select mute on
Maintenance menu reappear to select any other
maintenance item
ATPC manual ctrl
From this menu item, it is possible to change the ATPC set
TX power manually.
To display the ATPC manual ctrl, press [10] and [Enter]
from the maintenance menu.
Press: [1] and [Enter] to select ATPC manual control
Enter the attenuation required to get the TX power required.

PASOLINK Introduction

30

MONITORING
1. Setting
2. Maintenance
3. Monitoring
4. Exit
Select Function No:
Press [3] and [Enter] from the
LCT main Menu to display
the Monitoring menu.
The monitoring menu is used to
monitor the equipment for
preventive maintenance
purposes. This menu
provides monitoring of the
Transmit and Receive signal
levels. Equipment status and
alarm can also be monitored
from this menu. Inventory list
provides details of the
modules in the equipment

Monitoring

1. Monitoring voltage
2. Monitoring voltage
(continuous mode)
3. Alarm/Status
4. Inventory
00. Menu

Monitoring voltage
TX power1 :4.10V (< -5dB)
RX level1 :2.37V ( -61dBm)
TX power2 :*.**
RX level2 :*.**

DATA (Monitoring voltages)


Measured input / TX output
2. Monitoring voltage (continuous
RF signal levels are
mode) Time stamp
displayed. The metering
(1min:0 / 1sec:1):1
range for each
Press any key to start...
measurement is given in
the table above. TX
output power is given as
the detector voltage and
METER READING OF ODU PARAMETERS
attenuation used in dB.
Transmitter Power
0 to 4.6 V DC
RX signal level is given
Receiving Level
0.8 to 4.4V DC
as AGC voltage and in
dBm
(Depend on the Transmitter Power and the
Receiving Signal level )

PASOLINK Introduction

31

ALARM/STATUS MONITORING
Monitoring
1. Monitoring voltage
2. Monitoring voltage
(continuous mode)
3. Alarm/Status
4. Inventory
00. Menu
Select item No. : 3

Press 3 and ENTER

3. Monitoring of alarm/status 2/2


MOD ALM
(alarm:-/-)
DEM ALM
(alarm:-/-)
OPR ALM )
(alarm:-/-)
MDP CPU ALM (alarm:-/*)
ODU
TX PWR ALM (alarm:-/-)
RX LEV ALM ) (alarm:-/-)
APC1 ALM
(alarm:-/-)
APC2 ALM
(alarm:-/-)
IF INPUT ALM (alarm:-/-)
MUTE
(on)
TX/RX FREQ CH

Monitoring of alarm/status 1/2


IDU
INPUT LOSS 1-16
(alarm:---- ---- ---- ----)
CHANNEL USAGE ERROR 1-16 (alarm:---- ---- ---- ----)
AIS RCVD 1-16
(alarm:---- ---- ---- ----)
AIS SEND 1-16
(alarm:---- ---- ---- ----)
OUTPUT LOSS 1-16
(alarm:---- ---- ---- ----)
TX CLK LOSS
(alarm:-/-)
RX CLK LOSS
(alarm:-/-)
FSYNC ALM
(alarm:-/-)
HIGH BER ALM
( alarm:-/-)
LOW BER ALM
(alarm:-/-)
BER ALM
(alarm:-/-)
Press any key to continue
Monitoring of alarm/status 2/2

The IDU and ODU alarms and status


information can be viewed form this
menu item. Alarm condition is
indicated by * and normal
condition by -.

(1ch )
PASOLINK Introduction

32

ALARMS

IF Input ALM
IF input level in the ODU below (approximately)63dBm.
STATUS INFORMATION
MUTE
ODU output mute on/off status
TX/RX Frequency CH
Channel number corresponding to the ODU
transmit/receiver frequency
IDU Alarms
Input loss 1 16
In the 2MB interface, loss of 2MB input signal
detected. Alarm indicated for each channel.
Channel Usage Error 1 -16 In the 2MB
interface,2MB channel# is to
Used and a signal is detected at the input
AIS RCVD 1-16
In the 2MB interface, AIS (all1) received from
MUX equipment or Back-to-back 2MB
connection. Alarm indicated for each
channel.

AIS Send 1-16


In the 2MB interface, AIS sent to MUX equipment or
back-to-back 2MB connection. Alarm indicated
for each channel.
Output loss 1 -16
In the 2MB interface, loss of received 2MB signal from
the demodulator side. Alarm indicated for each
channel.
LAN INTFC ALM
When the WS channel usage is set to not used and
there is a 2MB signal at the input
WS input loss
In the optional WS interface card, loss of WS input
signal
WS Channel Usage Error
When the WS channel usage is set to not used and
signal is detected at the WS input.
WS AIS RCVD
In the optional WS interface card, AIS detected in the
WS input signal.
WS AIS send
In the optional WS interface card, AIS is sent out as the
WS

PASOLINK Introduction

33

ALARMS

WS output loss
In the optional WS interface card, Receive WS
signal not detected from the demodulator.
TX CLK loss
Loss of TX clock, in the 2 MB interface.
RX CLK loss
Loss of RX clock in the 2 MB interface.
FSYNC ALM
Loss of RX frame synchronization at the RX DPU.
HIGH BER ALM
When the receive BER is > 10-3
LOW BER ALM
When the receive BER is > 10-6
BER ALM
BER alarm point for inserting AIS. Alarm trigger
point can be selectable from (10-3, 10-4,
10-5 and 10-6)

MOD ALM
Modulator 850 MHz PLL oscillator loop unlock
condition.
DEM ALM
RX carrier not synchronized or lost.
OPR ALM
Communication error between ODU and IDU
ODU ALARMS
TX Power ALM
Transmitter output power decreased by 3 to 5 dB
RX Level ALM
Receive level below squelch level
APC1 ALM
ODU 1st local oscillator APC unlock alarm
APC2 ALM
ODU 2st local oscillator APC unlock alarm

PASOLINK Introduction

34

INVENTORY
Monitoring
1. Monitoring voltage
2. Monitoring voltage
(continuous mode)
3. Alarm/Status
4. Inventory
00. Menu
Select item No. : 3

Press 4 and ENTER

No.1 ODU
Serial number
16352
Manufactured date
OCT/2005
Software version (ROM/RAM) (1.02/2.03)
Bit rate
17/34MB
RF band
13GHz High
Sub band
A
Start frequency
13020.500MHz
Shift frequency
266MHz
CH separation
1.750MHz

IDU
SW UNIT
Serial number
4023
Manufactured date
DEC/2005
Software version (ROM/RAM) (1.20/2.40)
Bit rate
2/4/8/16x2MB
Option module
PM CARD
Inventory 2/4
IDU
No.1 MD UNIT
Serial number
12650
Manufactured date
DEC/2005
Software version (ROM/RAM) (1.2/2.49)
No.2 MD UNIT

This menu item gives the IDU and ODU


module information as given in the
figure. The figure gives the inventory
information for a (1+1) configuration

PASOLINK Introduction