KHU-10-YE_-EFE-EA_-000

CLIENT:

NWPGCL NORTH-WEST POWER GENERATION COMPANY LTD

PROJECT:

KHULNA 150MW PEAKING POWER PLANT PROJECT (Package 1A)


CALCULATION REPORT

RELAY ADJUSTMENT AND COORDINATION REPORT

2
1

2012-08-03
2012-07-11

Design
Information and comments

AOX
AOX

DBC
DBC

REV

DATE

DESCRIPTION

EDITED

CHECKED

KHU-10-YE_-EFE-EA_-000 - RELAY ADJUSTMENT AND COORDINATION REPORT

Domingo
Beato
2012.08.03
13:41:35
+02'00'

MIR
MIR

Ana Martinez-Vara de
Rey
por ausencia
2012.08.03 14:10:22
+02'00'

APPROVED

Project:

KHULNA 150MW PEAKING POWER PLANT


PROJECT (Package 1A)

Title:

Relay Adjustment And Coordination Report

EAI Document No:

448-10-F-E-01000

KKS Document No:

KHU-10-YE_-EFE-EA_-000

Purpose of issue:

Design

Prepared:

Reviewed:

Approved:

Issue: 2

Date: 2012-08-03

Alicia Rosa
Lucena
2012.08.03
13:37:25 +02'00'

AOX

DBC

Domingo Beato
2012.08.03
13:42:32 +02'00'

MIR

Ana MartinezVara de Rey


por ausencia
2012.08.03
14:10:37 +02'00'

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is to be used solely for the Project and the purpose for which it is furnished.
It may not be disclosed to others for a different use without the written permission of Empresarios Agrupados Internacional,S.A.

EMPRESARIOS AGRUPADOS INTERNACIONAL, S.A.


Magallanes, 3

28015 Madrid - Espaa

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page I

CLASSIFICATION
Contains information for the design of structures, systems or components: Yes
Design verification : Not applicable

Head of OU/Supervisor

Verifier Level 1

No
Level 2

CONTROL OF MODIFICATIONS
Issue

1
2

Modifications

First Issue
As indicated by vertical line in the margin

PRELIMINARY OR PENDING INFORMATION


Issue

Paragraphs

Subject

Status

Internal

No. copies/Format

DISTRIBUTION
External

MIR, DBC, AOX, AGD

1 pdf

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page i

CONTENTS
Page No.

1.

PURPOSE ............................................................................................................... 1-1

2.

LIST OF DATA ......................................................................................................... 2-1


2.1

DATA ........................................................................................................... 2-1

3.

HYPOTHESIS .......................................................................................................... 3-1

4.

RESULTS ................................................................................................................ 4-1

5.

4.1

MEDIUM VOLTAGE BOARDS (10BBA11/12) ............................................ 4-1

4.2

415 V STATION BOARDS (10BFA11/12) AND ESSENTIAL


DISTRIBUTION BOARDS (10BMA11/12) ................................................. 4-10

REFERENCE DOCUMENTS ................................................................................... 5-1

APPENDIX A COORDINATION CURVES ...................................................................... 5-2

00139289

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

1.

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 1-1

PURPOSE
The purpose of this study is the coordination and setting of the protection relays for
the transformers, cables, busbars, motors and other loads in the 6.6 kV and 415 V
systems.
This study affects all phase and ground overcurrent protection, motor protection and
minimum voltage detection relays.

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

2.

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-1

LIST OF DATA
2.1

DATA

2.1.1

Maximum symmetrical short-circuit currents

6.6 kV System:
-

Contribution of Unit Auxiliary transformer:

Is =19.5kA

Minimum phase to ground short-circuit current:

600A

415 V System:
-

Contribution of transformers:
Contribution through the power centre transformer 10BFT11 and
10BFT12: 42.5 kA

Short-circuit on Power Centres (most unfavourable):


10BFA11/ 10BFA12 (coupled busbars,most unfavorable case): 58.5 kA
10BMA11/12 (coupled busbars,most unfavorable case): 56 kA

2.1.2

MV (6.6 kV) System Motor Data

2.1.2.1

Gas compressor (10EKH10/20AP001)

Manufacturer:

SIEMENS AG

Rated power

3400 kW

Rated current

340 A

Locked rotor current

5.4 x 340 = 1836A

Acceleration time:
Rated voltage:

7 seconds

80% Rated voltage:

14 seconds

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

Issue 2

EA No.: 448-10-F-E-01000

Page 2-2

Maximum permissible time with locked rotor:


Rated voltage:

18/16seconds

80% Rated voltage:

26/29 seconds

Maximum of successive complete starts:


Hot:

Cold:

2.1.2.2

KKS No.: KHU-10-YE_-EFE-EA_-000

Electric fire pump (10XGA10AP002)

Rated power

315 kW

2.1.3

Transformers Data

2.1.3.1

Unit Auxiliary Transformer (10BBT10)

Power:

15 MVA ONAN

Rated voltage:

15 kV 5% 2.5% / 6.9 kV

Ground

through ground resistor (600 A)

Connection type:

Dyn11

2.1.3.2

Start up Transformer (SFC) (10MBJ10)

Rated power:

6.6 MVA (primary) /


5 MVA (secondary) 1.6 MVA (tertiary)

Rated voltage:

6.6 kV / 1.8 kV (secondary) 433V (tertiary)

Maximum start-up power:

4938kVA (4MW) (secondary)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

2.1.3.3

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-3

Station Transformers (10BFT11/12)

Rated power:

2500 kVA

Rated voltage:

6.6 kV 5% 2.5% / 0.433 kV

Ground:

Rigid to ground

Zcc:

7.5% (2500 kVA base)

2.1.3.4

Lighting transformers (10BNT10 and 10BLT10)

Rated power:

200 kVA

Rated voltage:

415 / 415 240 V

Connection type:

Dyn1

Ground:

Rigid to ground

2.1.4

Other Data

2.1.4.1

Current Transformers

In MV, all current transformers shall be 5P10 (at In the error is 1% and at 10 In it is
5%), except the following, which is 5P20 (at In the error is 1% and at 20 In it is 5%):
for incoming busbar from auxiliary transformers and coupling between MV busbars.
In LV, all current transformers shall be 5P10 (at In the error is 1% and at 10 In it is
5%).
2.1.4.2

Feeders consumption

Electrical heater

200 kW

Turbine crane for GT area

45 kW

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

2.1.4.3

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-4

Diesel Generator

Alternator rated power:

1250 kVA

Rated voltage:

415 V

Power factor:

0.8

In emergency operation, the diesel generator shall be earthed directly.

2.1.5

Protection Relays Data

2.1.5.1

Phase and ground Protection relay type SEPAM series 20 from


Schneider Electric.

It is used to protect the following elements:

Outgoings from Medium voltage busbars to start up transformer (S20),


10BFT11/12 station transformers (S20), electric fire pump (S20), outgoings to
gas booster compressor (M20) and in medium voltage busbars (minimum
voltage, B21).

The characteristics of the relay are listed below:

Rated phase current (IN):

1 to 6250 A

Base current (Ib):

(0.4 1.3) x IN

Rated residual current (INO):

1 to 6250 A

Phase sensor:

1 or 5 A

Rated primary phase-to-neutral voltage (Vnp):

220 V to 250 kV

Thermal overload unit:


-

Initial heat rise (Es0):

0 to 100%

Tripping set point (Es2):

50 to 300%

Heat rise constant (T1):

1 to 120 min

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-5

Cooling constant (T2):

5 to 600 min

Accounting for negative sequence component (K):

0 2.25 4.5 9

Excessive starting time and locked rotor unit:

Set point (IS):

50% Ib Is 500% Ib

Excessive starting time delay (ST):

0.5 300 sec

Locked rotor time delay (LT):

0.05 300 sec

Phase overcurrent unit:


-

Tripping curve:

Definite time (DT). Time dependent: Standard inv.


(SIT), Very inv. (VIT or LTI), Extremely inv. (EIT) and
ultra inv. (UIT), IEC curves, IEEE curves and IAC
curves

Set point (IS):

Definite time:

0.1 IN Is 24 IN (A)

Time dependent:

0.1 IN Is 2.4 IN (A)

Definite time:

0.05 300 sec

Time dependent:

0.1 12.5 sec or TMS

Time delay (T):

Negative sequence/unbalance unit:


-

Curve:

Definite, IDMT

Set point (IS):

Definite time:

10% Ib Is 500% Ib

IDMT:

10% Ib Is 50% Ib

Definite time:

0.1 300 sec

IDMT:

0.1 1 sec

Time delay (T):

Earth fault unit:


-

Tripping curve:

Definite time (DT). Time dependent: Standard inv. (SIT),


Very inv. (VIT or LTI), Extremely Inv. (EIT) and ultra inv.
(UIT)

Set point (ISO):

Sum of CTs: Definite time:

0.1 INO ISO 15 INO (A)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-6

Sum of CTs: Time dependent:

0.1 INO ISO INO (A)

With CSH sensor: Definite time: 2A rating 0.2A to 30A


20A rating 2A to 300A

Time delay setting:

With CSH sensor: IDMT:

2A rating: 0.2A to 2A
20A rating: 2A to 20A

Definite time:

inst., 0.05 300 sec

Time dependent:

0.1 12.5 sec or TMS

For Iso< 0.4Ino, the minimum time delaty is 300ms. If a shorter time delay
is needed, use the CT+ CSH30.

Starts per hour unit:


-

Period of time (P):

1 6 hours

Total number of starts (Nt):

1 60

Number of consecutive starts (Nh, Nc):

1 Nt

Time delay between starts (T):

0 90 mn

Phase-to-neutral undervoltage unit B21 (27S):


-

Set point:

5% Vnp Vs 100% Vnp

Time delay:

50 ms to 300 sec

Note:
2.1.5.2

Functions that are not specified are not used in this project.
Phase and ground protection relay type SEPAM series 60 from
Schneider Electric

It is used to protect the following elements:

Medium voltage busbars supply lines and Medium Voltage couplings (S60), MV
switchgear 10BBA11/10BBA12 Synchronization (MCS025).

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-7

The characteristics of the relay are listed below:

Rated phase current (IN):

1 to 6250 A

Base current (Ib):

(0.2 1.3) x IN

Rated residual current (INO):

1 to 6250 A

Phase sensor:

1 or 5 A

Rated primary phase-to-neutral voltage (Vnp):

220 V to 250 kV

Phase overcurrent unit:


-

Tripping curve:

Definite time (DT). Time dependent: Standard inv.


(SIT), Very inv. (VIT or LTI), Extremely inv. (EIT) and
ultra inv. (UIT).

Set point (Is):

Definite time:

0.05 IN Is 24 IN (A)

Time dependent:

0.05 IN Is 2.4 IN (A)

Definite time:

0.05 300 sec

Time dependent:

0.1 12.5 sec at 10Is

Earth fault unit:


-

Tripping curve:

Definite time (DT). Time dependent: Standard inv.


(SIT), Very inv. (VIT or LTI) Extremely Inv. (EIT) and
ultra inv. (UIT)

Set point (ISO):

Definite time:

0.1 INO ISO 15 INO (A)

Time dependent:

0.1 INO ISO INO (A)

Definite time:

inst., 0.05 300 sec

Time dependent:

0.1 12.5 sec at 10Is

Time delay (T):

Time delay (TO):

Undervoltage unit (L-L) or (L-N):


-

Set point:

5% Vnp Vs 100% Vnp

Time delay:

50 ms to 300 sec

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-8

MCS025 synchro-check module:


-

Measured voltages: Phase to phase / phase-to-neutral

Rated primary phase-to-phase voltage:

Unp sync1 (Vnp sync1 = Unp sync1/3): 220 V to 250 kV

Unp sync2 (Vnp sync2 = Unp sync2/3): 220 V to 250 kV

Rated secondary phase-to-phase voltage:

Uns sync1:

90 V to 120 V (Phase to phase)


90 V to 230 V (Phase-to-neutral)

Uns sync2 :

90 V to 120 V (Phase to phase)


90 V to 230 V (Phase-to-neutral)

Synchro-check setpoints

dUs set point: 3% to 30% of Vnp sync1

dfs set point:

dPhi set point: Del 5 al 80

Us high set point:

70% to 110% Vnp sync1

Us low set point:

10% to 70% Vnp sync1

Others settings:

Note:

0,05 a 0,5 Hz

Lead time:

0 a 0,5 s

Operating modes: no-voltage conditions for which coupling is allowed

Dead1 AND Live2

Live1 AND Dead2

Dead1 XOR Dead2

Dead1 OR Dead2

Dead1 AND Dead2

Functions that are not specified are not used in this project.

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

2.1.5.3

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-9

Overcurrent protection relay RV-IMA from Arteche

It is used to protect the following elements:

Neutral of the station transformers and of the start-up transformer (51G)

The characteristics of the relay are listed below:

Functions:
-

Earth fault protection relay with harmonic filter (50/51N)

Measurement rated current:


SETTING RANGE

RATED
CURRENT

Instant Unit

Time Unit

5A

0.5 60 A

1A

STEPS

CURRENT

0.5 12 A

0.1 A

Phase and earth

0.25 15 A

0.25 3 A

0.01 A

Phase and earth

0.25 A

0.05 3 A

0.05 1 A

0.01 A

Phase and earth

0.1 A

0.02 1.5 A

0.02 0.3 A

0.01 A

Phase and earth

0.01 A

0.004 0.035 A

0.004 0.02 A

0.001 A

Earth

0.01 A

0.005 0.1 A

0.005 0.03 A

0.001 A

Earth

Precision:
-

Measurement:

5%

Defined times:

5% or 0.03 seconds

2.1.5.4

Overcurrent protection relay RV-ITN from Arteche

It is used to protect the following elements:

Differential from gas booster compressor (87)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-10

The characteristics of the relay are listed below:

Functions:
-

(51N)

Measurement rated current:


SETTING RANGE

RATED
CURRENT

Instant Unit

Time Unit

5A

0.5 60 A

1A

STEPS

CURRENT

0.5 12 A

0.1 A

Phase and earth

0.25 15 A

0.25 3 A

0.01 A

Phase and earth

0.25 A

0.05 3 A

0.05 1 A

0.01 A

Phase and earth

0.1 A

0.02 1.5 A

0.02 0.3 A

0.01 A

Phase and earth

Precision:
-

Measurement:

5%

Defined times:

5% or 0.03 seconds

2.1.5.5

F-650 Relay from GE

It is used to protect the following elements:

Low voltage: 415 V Station boards (10BFA11/12) incomings and coupling and
essential distribution board (10BMA11/12) coupling.

The characteristics of the relay are listed below:

Curves: Inverse, very inverse and extremely inverse, etc., as per IEEE

Phase range (In): 1 or 5A

Earth range (In): 1 or 5A

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-11

The characteristics are as follows:

Function 51PH, 51PL, 51N and 51G phase and earth time overcurrent:
-

Start level: 0.05 to 160 A, in steps of 0.01 A

Precision: + 0.5% or + 10 mA from 0.05 to 10 A; + 1.5% for higher values

Curve dial: 0.00 to 900.00 in steps of 0.01 s

Precision of timing devices: + 3.5% of operating time or + 30 ms


(whichever is longer) for I > 1.03 times the start-up level.

Function 50PH, 50PL, 50N and 50G instantaneous phase and earth
over-current.
-

Start level: 0.05 to 160 A, in 0.01 A steps

Precision: + 0.5% or + 10 A from 0.05 to 10 A; + 1.5% for higher values

Timing device: 0.00 to 900 s in 0.01 s steps

Operating time: 20 ms at 3 x pickup

Precision of timing devices: + 3% of operating time or + 30 ms (whichever


is longer).

Function 50SG, sensitive earth instantaneous overcurrent:


-

Pickup level: 0.005 to 16.00 a in steps of 0.001 A

Level accuracy: 1.5% of the reading 1 mA from 0.005 to 16 A

Trip delay: 0.00 to 90.00 s in steps of 0.01 s

Function 27, minimum voltage.


-

Start level: 3 to 300 V, in 1 V steps

Ressetting value: 97% of start level

Ressetting time: Instantaneous

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-12

Function 25, synchrocheck:


-

Dead/live levels for line and bus: 0.00 to 300.00 in steps of 0.01 V
Maximum voltage difference: 2.00 to 300.00 V in steps of 0.01 V
Maximum angle difference: 2.0 to 80.0 in steps of 0.1
Maximum frequency slip: 10 to 5000 mHz in steps of 10 mHz
Synchronism time: 0.01 to 600.00 s in steps of 0.015
Angle accuracy: 2

Dead source function:


None
(DL-DB) Dead line - Dead Bus
(LL-DB) Live line - Dead Bus
(DL-LB) Dead line - Live Bus

2.1.5.6

Protection relay Entelliguard GTE from GE

It is used to protect the following elements:

Low voltage: overcurrent protection for feeders and mccs.

The characteristics of the relay are as listed below:

Four poles

Rated current (In):

Long time protection LT-LTD:


-

Pick-up setting (Ir):

400-630-800-2000 A

(0.2-1) In being In the rated current of the


circuit breaker:

Primary setting (Ie): 1-0.975-0.9625-0.95-0.45-0.4 x In

Secondary setting (Ir):


0.55-0.5 x Ie

1-0.95-0.9-0.85-0.8-0.75-0.7-0.65-0.6-

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-13

10%

Accuracy (current):

Time setting: 22 bands

Short time protection ST-STD:

Pick-up setting (Im): (1.5 - 12) Ir in steps of 0.5

Accuracy (current):

Time setting: 17 bands (from 30 to 940miliseconds60 to 1000


miliseconds),

10%

Earth protection GF(residual connection):


-

Pick-up setting (If):

(0.2 - 1) In in steps of 0.01

Accuracy (current):

15%

Time setting: 14 bands (from 50 to 840miliseconds110 to 900


miliseconds),

Neutral setting (for relays with 4 poles):


-

2.1.5.7

0%, 50% or 100% x phase settings (LT, ST and I)


Synchronism Check Relay MLJ from GE (25)

It is used to protect the following elements:

Essential distribution boards (10BMA11/12) incomings and couplings

The characteristics of the relay are listed below:

Voltage difference (difference vector module, V, volts)


-

Range from 2 to 90 in 0.5 steps

Angle difference (, degrees)


-

Range from 2 to 60 in steps of 1

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

Range: from 10 to 180 in steps of 1

Range: from 40 to 245 in steps of 1

Range: from 10 to 180 in steps of 1

Enable condition: dead line and dead bus (DLDB ON-OFF)


-

Range: from 40 to 245 in steps of 1

Busbar voltage absence level (dead bus: DB, volts)


-

Range: enabled or disabled

Busbar voltage presence level (live bus: LB, volts)


-

Range from 10 to 180 in steps of 1

Line voltage absence level (dead line: DL, volts)


-

Range: enabled or disabled

Line voltage presence level (live line: LL, volts)


-

Range from 0.1 to 99 in steps of 0.1

Enable synchronism unit (25 ON-OFF)


-

Range from 0.1 to 99 in steps of 0.1

Threshold voltage for sub-voltage monitoring (27V, volts)


-

Range from 10 to 500 in steps of 10

Enable sub-voltage monitoring (sup 27 ON-OFF)


-

Page 2-14

Manual mode timing (t man, seconds)


-

EA No.: 448-10-F-E-01000

Continuous mode timing (t cont, seconds)


-

Issue 2

Frequency difference of (slipping), F, mHz)


-

KKS No.: KHU-10-YE_-EFE-EA_-000

Range: enabled or disabled

Enable condition: dead line with live bus (DLLB ON-OFF)


-

Range: enabled or disabled

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

EA No.: 448-10-F-E-01000

Page 2-15

Range: enabled or disabled

Unit number:
-

Issue 2

Enable condition: live line with dead bus (LLDB ON-OFF)


-

KKS No.: KHU-10-YE_-EFE-EA_-000

Range: from 1 to 255

Serial port speed (kilobauds)


-

Range: from 0.3 to 38.4

2.1.5.8

Feeders outgoings from 10BMA11/12: GE type Relay

2.1.5.8.1

FE 250 SMR1 used in the incoming to 110VDC BATTERY CHARGER


1/2 and HVAC ELECTRICAL PANELBOARD ELECTRICAL ROOM

Rated current (In):

Long time protection (LT):

80-125-100-160-250 A

Pick-up setting (Ir):

(0.625-1) In in 16 steps

Pick-up band:

1.05-1.2x Ir

Short time protection (ST):


-

Pick-up setting (Im):

(2-13) Ir in 10 steps

Pick-up band:

Im 20%Im

2.1.5.8.2

FE LTMD 160 GE used in the incoming to By-pass transformer and


Switching station 132kV bldg emergency feeder

Rated current (In):

Thermal protection:

100 125 - 160 A

Pick-up setting (Ir):

(0.8-1) In

Pick-up band:

1.05-1.3 x Ir

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 2-16

Magnetic protection:
-

Pick-up setting (Im):

(5-10) In

Pick-up band:

Im 20%Im

2.1.5.9

Relay MIFII N of GE used in normal and emergency lighting


transformers (10BLT10/10BNT10) neutral protection

The characteristics of the relay are listed below

Function 50G1/50G2: Instantaneous ground overcurrent protection


-

Startup level: 0.1 to 30.00 x In in steps of 0.1In of the current transformer


primary

Time delay: 0-600.00 seconds in steps of 0.01s

2.1.5.10

Undervoltage relay (27) MIV II from GE

It is used to protect the following elements:

415V station boards


(10BMA11/12)

(10BFA11/12)

and

Essential

distribution

boards

The characteristics of the relay are listed below:

Start voltage:
-

Range 0: 10 to 250 V in steps of 0.1 V

Range 1: 2 to 60 V in steps of 0.1 V

Timing: 0-600 s in steps of 0.01 seconds

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

3.

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 3-1

HYPOTHESIS
3.1
The minimum inverse time margin for the maximum fault current
between electronic relays in the MV system shall be greater than or equal to 250 ms.
Time corresponding to breaker ...........................................

65 ms

Timing errors ......................................................................

85 ms

Relay reset .........................................................................

50 ms

Safety interval ....................................................................

50 ms

Total .................................................

250 ms

3.2
In order to ensure an adequate level of selectiveness, the precision of
the various relays and of the current transformers is taken into account.
3.3
The symmetrical current supplied to the Gas booster compressor shortcircuit taken into consideration for protection purposes is 20% higher than the locked
rotor current of the Gas booster compressor.

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-1

RESULTS
4.1

MEDIUM VOLTAGE BOARDS (10BBA11/12)

4.1.1

Relay type SEPAM series 20 (M20)

KKS

10EKH10/20AP001

Service

Gas booster
compressor

Transform. ratio
T.I.
Phase

Ground

630/1
5P10

CSH200

Rated
Base Sensor
phase
current rating
current
Ib
INO
IN
630

391

Termal overload
Unit
(***)
Es2 Es0 T1

T2

100

126

21

Excessive
starting time and
locked rotor unit
K

Is

2.25 200

F (50/51)-1
Phase overcurrent
Unit
(setting A)

Phase overcurrent
Unit
(setting B)

Negative
sequence/unbalance
Unit

ST

LT

Curve

ISF1A

TF1A Curve ISF1B

TF1B

Curve

ISi

TF1

20

DT

3635

Inst

11.5

DT

40

0.5

SIT

391

Starts per hour


unit

Earth fault unit

Curve ISO
DT

TO

P Nt Nh Nc Ta

15 0.1 1

LEGEND:
The phase sensors will be set at 1 A

Accounting for negative sequence component constant

ISF1A

Phase current set point (A), F (50/51)-1, group of setting A

Rated phase current (A)

Is

Set point (% Ib)

ISF1B

Phase current set point (A), F (50/51)-1, group of setting B

Ib

Base current (A)

ST

Excessive starting time delay (sec)

TF1A

Phase current time delay (sec), F (50/51)-1, group of setting A

INO

Sensor rating (A)

LT

Locked rotor time delay (sec)

TF1B

Phase current time delay (sec), F (50/51)-1, group of setting B

Es0

Initial heat rise (%)

Curve

ISI

Negative sequence set point (% Ib)

Es2

Tripping set point (%)

T1

Heat rise constant (min)

Tripping curve: definite time (DT), Standard inv. (SIT), very


inv. (VIT), extremely inv. (EIT) and ultra inv. (UIT).
The curves are IEC curves

T2
(***)

IN

TFI

Negative sequence time delay (sec)

Iso

Earth fault set point (A)

Cooling constant (min)

To

Earth fault time delay (sec)

The alarm set point, ES1, must be disabled or inhibitted (setting: 300%)

Nt

Total number of starts

NC

Number of consecutive cold starts

Nh

Number of consecutive hot starts

Ta

Time delay between starts (min)

Period of time (hr)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-2

Note 1

The protections units that are not indicated must be disabled

Note 2

Latching option(86) must be enabled

Note 3

Timer hold curve and Timer hold delay settings must remain in definite time and 0 miliseconds respectively, in phase overcurrent and earth fault units

Note 4

Harmonic 2 restraint setting must be disabled in earth fault unit

Note 5

Delay for locked rotor on start (LTS) setting must be disabled or inhibitted (setting: 300 sec), in excessive starting time and locked rotor unit

Note 6

As an explanation: Groups of settings A and B must be always active when using SEPAM M20

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.1.2

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-3

Relay type RV-ITN 51N (87) de arteche

Service

Toroidal
Transformer
ratio
(In/1)

Rated
current

Setting range (51N)


Instant unit (A)

Differential Gas booster


compressor from motor

40/1

1A

0.25
(Inst)

LEGEND
I n:

Toroidal transformer rated current (A)

Rated current (A)


Setting range: Instantaneous unit setting in A

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.1.3

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-4

Relay type SEPAM series 20 (S20)

KKS

10MBJ10
10BFT11/12
10XGA20AP001

Service

Transform.
Ratio
T.I.

F(50/51)-1

Rated
phase
current
IN

Sensor
rating
INO

Phase overcurrent
Unit
(setting A)

F(50/51)-2

Phase overcurrent
Unit
(setting B)

Earth fault
Unit

Phase overcurrent
Unit
(setting A)

Phase

Ground

Curve

ISF1A

TF1A

Curve

ISF1B

TF1B

Curve

ISF2A

TF2A

Curve

ISO

TO

Start up transformers

750/1

CSH200

750

SIT

722

DT

4619

0.1

DT

5280

inst

DT

10

Inst

MV/LV station transformers

300/1

CSH200

300

EIT

302

DT

1312

1.35

DT

4667

inst

DT

10

inst

Electric fire pump

60/1

CSH200

60

EIT

44

3.5

DT

455

inst

--

--

--

DT

10

inst

LEGEND:
The phase sensors will be set at 1 A
IN

Rated phase current (A)

ISF1A
ISF1B
ISF2A
TF1A
TF1B
TF2A
Iso
TO

Phase current set point (A), F (50/51)-1, group of setting A


Phase current set point (A), F (50/51)-1, group of setting B
Phase current set point (A), F (50/51)-2, group of setting A
Phase current time delay (sec), F (50/51)-1, group of setting A
Phase current time delay (sec), F (50/51)-1, group of setting B
Phase current time delay (sec), F (50/51)-2, group of setting A
Earth fault set point (A)
Earth fault time delay (sec)

INO

Sensor rating (A)

Curve

Tripping curve: Definite time (DT), Standard inv. (SIT),


very inv. (VIT), extremely inv. (EIT) and ultra inv. (UIT)
The curves are IEC curves

Note 1
Note 2
Note 3
Note 4
Note 5

The protection units that are not indicated must be disabled


Latching option (86) must be enabled
Timer hold curve and Timer hold delay settings must remain in definite time and 0 miliseconds respectively, in phase overcurrent and earth fault units
Harmonic 2 restraint setting must be disabled in earth fault unit
As an explanation: Groups of settings A and B must be always active when using SEPAM S20.

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.1.4

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-5

Relay type RV- IMA (51G) Arteche

Service

Single-phase overcurrent (50N)


Toroidal Transformer
Medium sensitivity current set
ratio
(In/1)
Delay type
Ie >>
tIe >>

MV/LV station
transformers Neutral

1000/1

DT

3A

1.3 sec

LEGEND
I n:

Toroidal transformer primary rated current (A)

Delay type:

Type of curve (defined time in this case)

Ie>>:

Instantaneous second earth threshold in times In (A)

tIe>>:

Time delayed second earth threshold (sec)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.1.5

Relay type SEPAM series 60 (S60)

4.1.5.1

Phase protection
Transform.
Ratio
T.I.

Service

Incoming to busbars 10BBA11 from Unit Auxilary Transformer


Incoming to busbars 10BBA12 from Auxilary Transformer
Coupling 10BBA11/12 Busbars

Phase
1600/1
1600/1
1600/1

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-6

Rated
Rated
phase residual
current current
IN
INO

Ground
3CT+CSH30 1600
3CT+CSH30 1600
3CT+CSH30 1600

1600
1600
1600

Phase overcurrent Unit

Earth Fault Unit

F(50/51)-1

F(50N/51N)-1*

Curve ISF1 TF1 Curve ISF2


TF2 Curve ISF3
TF3 Curve IS01 T01
SIT 1569 10
DT
6930 0.6
DT
7341 0.5
DT 215 0.6
SIT 1569 10
DT
6930 0.6
DT
7341 0.5
DT 215 0.6
SIT 1255 8.5
DT
5777 0.35
DT
6123 0.25
DT 185 0.35

LEGEND:
IN
INO
Curve

Note 1

The phase sensors will be set at 1 A


ISF1
Rated phase current (A)
ISF2
Rated residual current (A)
ISF3
Tripping curve: Definite time (DT), Standard inv.
ISO1
(SIT),
very inv. (VIT), extremely inv. (EIT) and ulta inv.
(UIT)
The curves are IEC curves
The protection units that are not indicated must be disabled

Phase current set point 1 (A), F (50/51)-1


Phase current set point 2 (A), F (50/51)-2
Phase current set point 3 (A), F (50/51)-3
Earth fault set point 1 , F (50N/51N)-1

TF1
TF2
TF3
TO1

Phase current time delay 1 (sec), F (50/51)-1


Phase current time delay 2 (sec), F (50/51)-2
Phase current time delay 3 (sec), F (50/51)-3
Earth fault time delay 1 (sec), F (50N/51N)-1

Note 2

Latching option (86) must be enabled

Note 3

Timer hold curve and Timer hold delay settings must remain in definite time and 0 miliseconds respectively, in
phase overcurrent unit.and in earth fault unit

Note 4*

Harmonic 2 restraint setting must be enabled in earth fault unit for coupling 10BBA11/12 Busbars, Incoming to busbars 10BBA12 from Auxilary Transformers and Incoming to busbars
10BBA11 from Unit Auxilary Transformers

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-7

4.1.6

Synchronism protection (25) for MV buses (10BBA11/12). Relay


MCS025 Synchro-check module of SEPAM S60

4.1.6.1

Incoming to MV Busbars 10BBA11/12 from Unit Auxiliary


transformer and from Auxiliary transformer (It corresponds to relay
section 4.1.5.1)

MCS025 Synchro-check module (Sepam S60)

FUNCTION

RANGE

SETTING

Unsync1

110V (phase-phase conection)

110V

Unsync2

110V (phase-phase conection)

110V

dUs

3% Unsync1 to 30%Unsync1

5%

dfs

0.05 - 0.5 Hz

0.1 Hz

5 to 50

15

Us high set point

70% Unsync1 to 110%Unsync1

90%

Us low set point

10% Unsync1 to 70%Unsync1

20%

Voltage checking

On /off

On

Dead1 and Live2


Live 1 and Dead 2
Dead1 XOR Dead2
Dead1 OR Dead2
Dead1 and Dead2

Live 1 and Dead 2

dPhis

Operationg mode with


no voltage

4.1.6.2

Coupling MV Busbars 10BBA11/12

MCS025 Synchro-check module (Sepam S60)

FUNCTION

RANGE

SETTING

Unsync1

110V (phase-phase
conection)

110V

Unsync2

110V (phase-phase
conection)

110V

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

FUNCTION

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-8

RANGE

SETTING

dUs

3% Unsync1 to
30%Unsync1

5%

dfs

0.05 - 0.5 Hz

0.1 Hz

5 to 50

15

Us high set point

70% Unsync1 to
110%Unsync1

90%

Us low set point

10% Unsync1 to
70%Unsync1

20%

Voltage checking

On /off

On

Dead1 and Live2


Live 1 and Dead 2
Dead1 XOR Dead2
Dead1 OR Dead2
Dead1 and Dead2

Dead1 OR Dead2

dPhis

Operationg mode with


no voltage

4.1.7

Minimum voltage protections for MV buses

4.1.7.1

Relay type SEPAM series 20 (B21 for measurement)

VOLTAGE
TRANSFORMATION
(Vnp // Uns/3)
6600/3 // 110/3
(connection phase-toneutral)

PHASE-TO-NEUTRAL UNDERVOLTAGE UNIT


(27)
SET POINT
Vs (V)

Tripping
curve

TIME DELAY
(ms)

70% Vnp

Definite

50

Vnp:

Rated primary phase-to-neutral voltage

Uns:

Rated secondary phase-to-phase voltage

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.1.7.2

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-9

Relay type SEPAM series 60 (S60 for incoming from Unit Auxiliary
transformer 10BBT10 and Auxiliary transformer)

(These settings complete the relay settings indicated in paragraph 4.1.5.1).

VOLTAGE
TRANSFORMATION
(Vnp // Uns/3)
6600/3 // 110/3
(connection phase-toneutral)

PHASE-TO-NEUTRAL UNDERVOLTAGE UNIT


(27)
SET POINT
Vs (V)

Tripping curve

TIME DELAY
(ms)

90% Vnp

Definite

50

Vnp: Rated primary phase-to-neutral voltage


Uns: Rated secondary phase-to-phase voltage
4.1.7.3

Timer auxiliary relay TDF-4 of Arteche

FUNCTION

IDENTIFICATION

DELAY

Trip of all MV motors

27T2

2 seconds

Transfer initiation

27T1

2.1 seconds

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-10

4.2

415 V STATION BOARDS (10BFA11/12) AND ESSENTIAL DISTRIBUTION BOARDS (10BMA11/12)

4.2.1

F650-type relay for busbars protection

For all F650 protections, the input type shall be RMS.


PHASE PROTECTION

Earth Protection
Instantaneous
Overcurrnet
(50PH)

Transf.
Ratio
CT (A)

Time Overcurrent (51PH)


Is

Ts (s)

Curve

Ii

Ti (s)

4000/1

2.8

IEC C

3.5

1.1

4000/1

0.7

3.1

IEC C

2.8

Essential switchgear 10BMA11/12 coupling

2000/1

0.72

1.85

IEC B

Incoming from essential distribution board 10BMA11 to emergency


diesel generator

2000/1

0.98

IEC B

SERVICE

Incoming to 415V station boards 10BFA11/12


415V station boards 10BFA11/12 coupling

Transf.
Ratio
CT (A)

Time Overcurrent (51N)


Ist

Tst (s)

Curve

4000/1

0.66

1.1

Definite
time

0.95

4000/1

0.62

0.95

Definite
time

2.25

0.49

2000/1

0.49

Definite
time

2.9

0.64

2000/1

1.25

0.64

Definite
time

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-11

LEGEND
Is:

Pickup level in Amps.

Ts:

Multiplying factor of the phase overcurrent protection curve in seconds.

Curve:

Type of curve of the phase overcurrent.

Ii:

Pickup level in Amps.

Ti:

Trip delay of the phase protection instantaneous overcurrent, in seconds.

Ist:

Pickup level in Amps.

Tst:

Trip delay of the earth protection overcurrent, in seconds

Curve:

Type of curve of the earth overcurrent

Note:

The protection units that are not indicated must be disabled.

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.2

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-12

CCMS: GE Relay Entelliguard GTE

KKS

Service

In
(A)

Settings
LT

ST

GF

Ie

Ir

LTD Band

Im

STDB Band*

If

GFDB Band**

10BFA11GS210

Gas compressors 10BJA30 MCC

400

1 xIn (400A)

1x Ie (400A)

C-5

4xIr

1 xIn

10BFA11GS220

10BJA11 MCC++

800

1 xIn (800A)

0.75x Ie (600A)

C-10

4xIr+

1 xIn+

10BFA11GS310

10BJA13 MCC++

800

1 xIn (800A)

0.65x Ie (520A)

C-15

4xIr

1 xIn

10BFA12GS210

10BJA12 MCC++

800

1 xIn (800A)

0.75x Ie (600A)

C-10

4xIr+

1 xIn+

10BFA12GS220

10BJA14 MCC++

800

1 xIn (800A)

0.75x Ie (600A)

C-10

4xIr+

1 xIn+

10BFA12GS410

10BJA15 MCC+++

800

1 xIn (800A)

0.5x Ie (400A)

C-15

4xIr

1 xIn

10BFA12GS420

10BJA16 MCC+++

800

1 xIn (800A)

0.65x Ie (520A)

C-10

4xIr

1 xIn

LEGEND
Ie
Ir
Im
If
*
**
Note 1:
Note 2:

LT main unit current set point (in times In)


LT secondary unit current set point (in times Ie)
ST unit current set point (in times Ir)
GF unit current set point (in times In)
STDB bands: I2t disable
GFDB bands: I2t disable
++: The neutral protection shall be adjusted to 50% x phase settings
+++: The neutral protection shall be adjusted to 100% x phase settings
+: The magnetic setting of feeders fed from mccs shall be 800A approximately as maximum

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.3

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-13

Feeders and BMAs: GE Relay Entelliguard GTE

KKS

Service

In
(A)

Settings
LT

ST

GF

Ie

Ir

LTD Band

Im

STDB Band*

If

GFDB Band**

10BFA11GS320

10BMA11++

2000

1xIn (2000A)

0.9x Ie (1800A)

C-7

3.5xIr

15

1 xIn

13

10BFA12GS310

10BMA12++

2000

1xIn (2000A)

0.9x Ie (1800A)

C-7

3.5xIr

15

1 xIn

13

10BFA11GS410

Electrical heater+++

400

1xIn (400A)

0.8x Ie (320A)

C-3

2.5xIr

0.2 xIn

10BFA11GS420

Turbine crane+++

400

0.45 xIn (180A)

0.55x Ie (99A)

C-22

11xIr

0.2 xIn

1 xIn (800A)

0.5x Ie (400A)

C-15 5.5xIr

1 xIn

11BTL10
10BFA12GS320

Alstom emergency system (to transfer switch)++ 800


10BLT10 Normal Lighting transformer+++

400

0.95xIn(380)

0.75x Ie (285A)

C-15 9.5xIr

10

0.2 xIn

10BNT10 Emergency Lighting transformer +++

400

0.95xIn(380)

0.75x Ie (285A)

C-15 9.5xIr

10

0.2 xIn

LEGEND
Ie
Ir

LT unit current set point (in times In)


LT unit current set point (in times Ie)

Im

ST unit current set point (in times Ir)

If

GF unit current set point (in times In)

STDB bands: I2t disable

**

GFDB bands: I2t disable

Note:

++: The neutral protection shall be adjusted to 50% x phase settings


+++: The neutral protection shall be adjusted to 100% x phase settings

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.4

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-14

Normal and emergency lighting transformer 10BNT10 and 10BLT10 neutral protection 50G1: GE relay MIF II N

Settings
Current transformer

600/1

Pickup value

Type of curve

DELAY
(s)

3.8

Definite time

0.35

Startup level: in In times of the current transformer primary

DELAY: Definite time delay in seconds

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.5

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-15

Feeders outgoings from 10BMA11/12:

Note: for setting of thermal and magnetic relay of the motors fed from 10BMA11/12, see section 4.2.8.
4.2.5.1

FE 250 SMR1 GE type Relay

Circuit Breaker/
Relay type

Service

FE 250A SMR1
FE 250A SMR1

Settings

In
(A)

LT

ST

Ir

Im

110VDC BATTERY CHARGER 1/2

250

0.85xIn=212.5

9xIr

HVAC ELECTRICAL PANELBOARD


ELECTRICAL ROOM

160

0.75xIn=120

6xIr

LEGEND
Ir

LT unit current set point (in times In)

Im

ST unit current set point (in times Ir)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.5.2

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-16

FE LTMD 160 GE type Relay

Circuit Breaker/
Relay type

Service

FE 160A LTMD
FE 160A LTMD

Settings

In
(A)

Thermal Ir

Magnetic Im

Ir

Im

By-pass tranformer

125

0.9xIn=112.5

10 xIn=1250

Switching station 132kV bldg emergency feeder

160

0.9xIn=144

5 xIn=800

LEGEND
Ir

Thermal unit current set point (in times In)

Im

Magnetic unit current set point (in times In)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-17

4.2.6

Minimum voltage protections (27) for LV buses

4.2.6.1

GE relay F-650: 415V station boards incomings (10BFA11/12


incomings)

(These settings complete the relay settings indicated in paragraph 4.2.1).

Minimum voltage protection (27)


Transf.
Ratio
VT(V)

Input mode

415/3/ 110/3
(connection phase-neutral)

Phase-to-ground

57

U:

Minimum voltage, in volts.

T:

Trip delay of the minimum voltage protection

4.2.6.2

415V station boards (10BFA11/12)

MIV II from GE relay


TIMED UNIT
VOLTAGE
TRANSFORMATION
415/3 // 110/3*

START VOLTAGE
(V)

DELAY
(S)

44.5

Relay connection: phase-neutral

Relay type (27T1, 27T2)


FUNCTION

IDENTIFICATION

DELAY

Low voltage transfer initiation

27T1

3 seconds

Motor trip

27T2

2 seconds

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.6.3

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-18

Essential distribution boards (10BMA11/12)

MIV II from GE relay


VOLTAGE
TRANSFORMATION

TIMED UNIT
START VOLTAGE
(V)

DELAY
(S)

44.5

415/3 // 110/3*

Relay connection: phase-neutral

Relay type (27T1)


FUNCTION

IDENTIFICATION

DELAY

27T1

4 seconds

TRANSFER INITIATION

4.2.7

Synchronism protection (25) for LV buses

4.2.7.1

F650 type relay: 415V station boards (10BFA11/12) incomings

Voltage transformer: 415/3 110/3

Relay connection: phase-to-neutral (Un=110 /3)


SETTING NAME

RANGE

STEP

SETTING

DEAD/LIVE LEVELS FOR LINE AND BUS

0 300 V

0.01 V

50 V

MAXIMUM VOLTAGE DIFFERENCE

2 300 V

0.01 V

6.4 V

2 80

0.1

15

0.01 600 s

0.01 s

2s

MAXIMUM FREQUENCY SLIP

10 - 5000 MHZ

10 MHZ

100 MHZ

DEAD SOURCE FUNCTION

NONE, DL-DB
LL-DB, DL-LB

--

LL DB

MAXIMUM ANGLE DIFFERENCE


SYNCHRONISM TIME

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

4.2.7.2

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-19

F650 type relay: 415V station boards (10BFA11/12) couplings

Voltage transformer: 415/3 110/3

Relay connection: phase- phase (Un=110 V)


SETTING NAME

RANGE

STEP

SETTING

DEAD/LIVE LEVELS FOR LINE AND BUS

0 300 V

0.01 V

88 V

MAXIMUM VOLTAGE DIFFERENCE

2 300 V

0.01 V

11 V

2 80

0.1

15

0.01 600 s

0.01 s

2s

MAXIMUM FREQUENCY SLIP

10 - 5000 MHZ

10 MHZ

100 MHZ

DEAD SOURCE FUNCTION

NONE, DL-DB
LL-DB, DL-LB

--

LL DB
DL LB

MAXIMUM ANGLE DIFFERENCE


SYNCHRONISM TIME

4.2.7.3

Synchronism protection (25) of synchronism check relay MLJ from


GE

4.2.7.3.1

Essential distribution boards (10BMA11/12) incomings and couplings

Voltage transformer: 415 / 3 - 110 / 3 V

Relay connection: phase- neutral (Un=110 / 3 V)


SETTING NAME

RANGE

STEP

SETTING

50/60 HZ

N.A.

50

0-1

FREQUENCY

1-1

DIFFERENCE BETWEEN VOLTAGES

2-90 V

0.5 V

6.5

1-2

DIFFERENCE BETWEEN ANGLES

2-60

15

1-3

DIFFERENCE BETWEEN FREQUENCIES

10-500 MHZ

10 MHZ

100

1-4

CONTINUOUS MODE TIMING

0.1-99.0 s

0.1 s

1-5

MANUAL MODE TIMING

0.1-99.0 s

0.1 s

10

2-1

VOLTAGE SUPERVISION ENABLING

OFF-ON

N.A.

ON

2-2

VOLTAGE SUPERVISION
VOLTAGE

10-180 V

1V

57

3-1

LINE VOLTAGE PRESENCE LEVEL (LIVE


LINE: LL, VOLTS)

40-245 V

1V

50 *

3-2

LINE VOLTAGE ABSENCE LEVEL (DEAD


LINE: DL VOLTS)

10-180 V

1V

30 *

THRESHOLD

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 4-20

SETTING NAME

RANGE

STEP

SETTING

3-3

BUSBAR VOLTAGE PRESENCE LEVEL


(LIVE BUS: LB, VOLTS)

40-245 V

1V

50 *

3-4

BUSBAR VOLTAGE ABSENCE LEVEL


(DEAD BUS: DB, VOLTS)

10-180 V

1V

30 *

4-1

SYNCHRONISM UNIT ENABLING

OFF-ON

N.A.

ON

4-2

CONDITION ENABLING: (DLDB) DEAD


LINE WITH DEAD BUS

OFF-ON

N.A.

OFF

4-3

CONDITION ENABLING: (DLLB) DEAD


LINE WITH LIVE BUS

OFF-ON

N.A.

ON

4-4

CONDITION ENABLING: (LLDB) LIVE LINE


WITH DEAD BUS

OFF-ON

N.A.

ON

5-1

CONFIGURATION
OUTPUT

OF

1ST

AUXILIARY

SEE TABLE 2

N.A.

5-2

CONFIGURATION
OUTPUT

OF

2ND

AUXILIARY

SEE TABLE 2

N.A.

Default values

4.2.8

Setting of thermal and magnetic relays for the phase protection


of the motors supplied from the motor control centres and
essential service switchgears 10BMA11/12

Protection against overloads

The thermal tap at 1.15 times the motor rated current is selected.

Protection against short-circuits

The magnetic element is set to 6.5 x 1.5 x 1.1 = 11 times the motor rated
current.

where:
6.5:

The ratio between the motor start current and the rated current

1.5:

Asymmetrical component

1.1:

Relay tolerance

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

5.

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page 5-1

REFERENCE DOCUMENTS
5.1

Industrial Power System Data Book G.E.

5.2

National Electric Code (NEC)

5.3

IEC 60076-5 and ANSI C57.12.00

5.4

IEC 60185. Current Transformers

5.5

G.E. Power Systems, Steam Turbine: Recommended Practices for


Protective Relaying, Electric Motors and Electric Control Circuits. GEI
90368F. September 1990.

5.6

IEC 947-2. Low-Voltage Switchgear and Control Gear. Part 2: Circuit


Breakers.

5.7

ANSI/IEEE C37.96 Guide for AC Motor Protection.

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

APPENDIX A
COORDINATION CURVES

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-i

CONTENTS
Pag.
1.

2.

MEDIUM VOLTAGE COORDINATION


1.1

PHASE PROTECTION COORDINATION.......................................... A-1

1.2

GROUND PROTECTION COORDINATION ...................................... A-2

LOW VOLTAGE COORDINATION


2.1

PHASE PROTECTION COORDINATION.......................................... A-3

2.2

GROUND PROTECTION COORDINATION ...................................... A-5

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-1

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-2

KHULNA 150MW PEAKING POWER PLANT


MEDIUM VOLTAGE GROUND PROTECTION COORDINATION

Aux
transformers
(by others)

1000
Unit
Auxiliary
Transf.

R2

R1
R4

10BBA11

R5

R7

R3
10BBA12

R6

Gas Booster
Electric Fire
Compressor
Station
pump
Start up transformer
Isolation
Highest
Transf.
transformer
motor

100

R7

R5

Gas Booster
Compressor

Station
transformer
Isolation
Transf.

R7
R2
10

Time (s)

R6

R1

R5

R3
R4
1

0,1

Icc phase to
ground in MV
system (600A)

0,01
1

10

100

1000

Current (A)

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-3

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-4

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-5

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page

KKS No.: KHU-10-YE_-EFE-EA_-000

Issue 2

EA No.: 448-10-F-E-01000

Page A-6

This document contains proprietary information of Empresarios Agrupados Internacional, S.A. and is subject to the restrictions set forth on the title page