Turndown Misconceptions
As simple as the concept of turndown may seem, it
has led to considerable misunderstanding in the
HVAC industry, and especially with regard to VAV
laboratory ventilation applications. For instance, if a
specific air terminal has a maximum to minimum
airflow range from 3200 cfm down to 400 cfm, it
would have a turndown ratio of 8-to-1. If another air
terminal has the same maximum airflow of 3200 cfm
but a minimum airflow of 200 cfm, its turndown ratio
would be 16-to-1 or twice that of the 8-to-1 unit. A
common but erroneous assumption is that the 16-to-1
unit provides twice the airflow range that the 8-to-1
unit can provide. Figure 1 shows a graphic
Siemens Industry, Inc.
Document No. 149-978
16 : 1
TURNDOWN
8:1
TURNDOWN
1.
2.
3.
The internal work surface is a few inches wider than the sash
opening width. This extra area (although small) should also
be considered when determining a fume hood's minimum
airflow. In addition, some fume hoods may have a working
area deeper than 24 inches and if so, this should be
considered when determining the minimum airflow.
Siemens Industry, Inc.
Document No. 149-978
4.
5.
Table 1. Air Driven Laboratory Rooms with Fume Hoods - Supply Airflow Turndown Ratios.
Laboratory Room
Size:
(Length)
(Width)
(Height)
R
O
O
M
Floor Area
Excess
Room
Exhaust
Airflow
For
Negative
Pressure
Total Fume
Hood Exhaust
VAV Fume
Hoods in
Room
4
Total
Miscellaneous
Room
Exhaust
Total
Room
Exhaust
5
6
8
Foot Widths
Room
Minimum
Air
Changes
Per Hour
Room
Supply
Airflow
Room
Supply
Turndown
Ratio
Room Volume
4'
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
6.
5'
6'
8'
Length: 25 ft
Width: 10 ft
Height: 9 ft
1
1
12
Area:
250 ft
Vol.:
2250 ft
250
cfm
1
2
2
2
2
3
Length: 25 ft
Width: 20 ft
Height: 9 ft
3
3
12
Area:
500 ft
Vol.:
4500 ft
350
cfm
3
4
4
4
4
Length: 25 ft
Width: 30 ft
Height: 9 ft
5
5
5
12
Area:
750 ft
Vol.:
6750 ft
450
cfm
5
6
6
6
6
Min.
cfm. 6
150
200
250
350
300
400
500
700
450
600
750
1050
600
800
1000
1400
750
1000
1250
1750
900
1200
1500
2100
Max.
7
cfm
750
1000
1250
1750
1500
2000
2500
3500
2250
3000
3750
5250
3000
4000
5000
7000
3750
5000
6250
8750
4500
6000
7500
10500
200 cfm
(2 Bench
Snorkels)
400 cfm
(4 Bench
Snorkels)
600 cfm
(6 Bench
Snorkels)
Min.
8
cfm
350
400
450
550
500
600
700
900
850
1000
1150
1450
1000
1200
1400
1800
1350
1600
1850
2350
1500
1800
2100
2700
Max.
9
cfm
950
1200
1450
1950
1700
2200
2700
3700
2650
3400
4150
5650
3400
4400
5400
7400
4350
5600
6850
9350
5100
6600
8100
11100
9.3
10.7
12.0
14.7
13.3
16.0
18.7
24.0
11.3
13.3
15.3
19.3
13.3
16.0
18.7
24.0
12.0
14.2
16.4
20.9
13.3
16.0
18.7
24.0
Min.
10
cfm
100
150
200
300
250
350
450
650
500
650
800
1100
650
850
1050
1450
900
1150
1400
1900
1050
1350
1650
2250
Max.
11
cfm
700
950
1200
1700
1450
1950
2450
3450
2300
3050
3800
5300
3050
4050
5050
7050
3900
5150
6400
8900
4650
6150
7650
10650
7.0 : 1
6.3 : 1
6.0 : 1
5.7 : 1
5.8 : 1
5.6 : 1
5.4 : 1
5.3 : 1
4.6..:..1
4.7 : 1
4.8 : 1
4.8 : 1
4.7 : 1
4.8 : 1
4.8 : 1
4.9 : 1
4.3 : 1
4.5 : 1
4.6 : 1
4.7 : 1
4.4 : 1
4.6 : 1
4.6 : 1
4.7 : 1
NFPA 45 and Standard ANSI/AIHA Z9.5 requires that VAV fume hoods maintain a minimum exhaust airflow of 25 cfm per square feet of internal hood work surface area.
7.
Maximum exhaust airflow is based upon a vertical sash fume hood with an average face velocity of 100 fpm and a 30-inch maximum sash opening height.
8.
Total Room Minimum Exhaust is the sum of the Total Fume Hood Minimum Exhaust plus the Constant Volume Room Exhaust.
9.
Total Room Maximum Exhaust is the sum of the Total Fume Hood Maximum Exhaust plus the Constant Volume Room Exhaust.
10. Room Minimum Supply Airflow is the Total Room Exhaust minus the Excess Room Exhaust Airflow For Negative Pressure.
11. Room Maximum Supply Airflow is the Total Room Exhaust minus the Excess Room Exhaust Airflow For Negative Pressure.
12. The amount of Excess Room Exhaust Airflow For Negative Pressure is the approximate amount needed to maintain 0.010 inches of negative pressure for the size of room.
Page 4 of 8
Page 5 of 8
Conclusion
This paper provided an in-depth analysis of many
VAV laboratory airflow control situations in
conjunction with the applicable standards
requirements and good design practices to establish
the actual turndown ratios typically needed for
laboratory airflow control applications. In virtually
every instance, it has been shown that high
turndown ratios (more than 8-to-1) are not required.
The following statements summarize the results of
this analysis:
Page 7 of 8