Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Technical Data
HRV design guide
EEDEN14-205
Ventilation
Technical Data
HRV design guide
EEDEN14-205
TABLE OF CONTENTS
HRV design guide
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
HRV Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Interlocked operation with VRV & Sky Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Energy Saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FRESH-UP operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Element (HEP element) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Easy Installation and service maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Optional accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unique Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reducing operating sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centralized piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cautions in installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical wiring procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
11
13
14
16
17
18
Optional accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
19
26
Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
31
22
25
34
35
44
52
Nomenclature
i n a og l i i c t se a er l d i t t Van Re VH
V
500
VE
Ventilation
Air
Mounted type
50
GB
V1
Ventilation
Outdoor Air Treatment Type
Mounted type
Nominal Air Flow Rate (50 : 500m /h, 80 : 750m /h, 100 : 950m /h)
3
Check with your sales representative if the unit is sold in your country.
HRV Features
2-1
Simultaneous ON / OFF with the indoor unit by the indoor unit remote control.
HRV independent operation during air conditioning off season by the indoor unit remote control.
Fan speed changeover by the indoor unit remote control: High / Low, Ultra-High / High, Ultra-High / Low
Precooling / heating control function setting to delay the start of ventilation during air conditioner start-up to realize the high energy saving
efficiency.
Filter sign display notifies the time for cleaning the filter
1
2
NOTE
Type
Indoor
unit
Indoor
unit
HRV
Structure
Remote
Control
Features
HRV
Connectable
Indoor unit
Remote
Control
(HC0228)
(HC0229)
Other types
Daikins HRV
FAN mode
Remote
Control
No falling of dust
OFF
Dust
(HC0006)
Dust does not fall off from the air filter because the air supply fan
of the interlocked indoor unit remains activated even when the
HRV is operated independently.
(HC0005)
Installation Examples
Direct duct connection system
(HC0007)
(HC0008)
HRV Features
2-2
Energy Saving
By heat recovery operation
Approx. 24 % reduction
of heating / cooling load
HRV unit recovers the thermal energy during cooling / heating operation of air
conditioner. HRV reduces the cooling / heating load drastically and enhances the
heating / cooling efficiency.
Exhaust Air
Return Air
Outdoor Air
Supply Air
Heat Exchanger Element
(Heat Recovery)
By setting to automatic
ventilation mode
(HC0230)
Proper use of Heat recovery ventilation and normal ventilation saves energy.
When the cooling operation is required in winter, use of heat recovery ventilation is not
efficient because the outdoor air temperature is normally lower than that of the indoor.
Thus, the proper use of ventilation mode enhances the heating / cooling efficiency.
Automatic Ventilation mode changeover
Approx. 6% reduction
of heating / cooling load
Operation
Sensor of ventilation
Cooling
Difference between
indoor / outdoor temp.
Decision of mode
(Which is more
energy efficient?)
Return Air
Outdoor Air
Supply Air
Heat Exchanger Element
(Heat Recovery)
(HC0231)
Automatic
Changeover
Return Air
Outdoor Air
Supply Air
Heat Exchanger Element
(Heat Recovery)
Approx. 2% reduction
of heating / cooling load
(HC0232)
The load is reduced at startup of the air conditioner by the following control.
Before the working hour, the room air is clean.
Therefore, the startup of HRV can be delayed.
Working hour ends
9:00
18:00
Air conditioner ON
OFF
HRV
OFF
ON
Cooling / Heating
load is reduced
The nighttime free cooling works at night when the air conditioner is off, reducing the
cooling load in the morning when the air conditioner is turned on.
Approx. 5% reduction on
cooling load
CO2 sensor demand control
By measuring indoor air quality comfort is guaranteed at all times, while the unit is
switched off when possible, preventing over ventilation
Approx. 3% saving by
preventing over ventilation
Total
40% reduction
of heating / cooling
load
Reduction of
heating / cooling
load (%)
24%
Normal
operation
HRV
independent
operation
32%
Interlocked
operation
NOTE
The total heating / cooling load may vary depending on the climate or the other environmental conditions.
40%
Energy saving
options installed/
(HC0233)
enabled
HRV Features
2-2
Energy Saving
Efficient Outdoor Air Introduction with Heat Exchanger and Cooling / Heating Operation
Indoor unit with outdoor air treatment
Using outdoor air, the temperature can
be brought near room temperature with
minimal cooling capacity through the use
of outdoor air.
100
80
heat recovery
+
humidifying
2-2-2
60
Effect of
humidification
20
3
2
2-2-1
Effect of heating
Effect of full heat exchange
5
10
15
20
25
30
Dry bulb temperature (CDB)
35
40
The VRV
outdoor unit
HRV (VKM)
Link connection
HRV Features
2-2
Energy Saving
2-2-3
1
2
The nighttime free cooling is an energy-conserving function which works at night when the air conditioners is off, reducing the cooling load in the
morning when the air conditioner is turned on. This is mainly for rooms that contain office equipment, which raises the room temperature.
Nighttime free cooling only works during cooling and when connected to Building Multi or VRV systems.
Nighttime free cooling is set to off in the factory settings; so request your dealer to turn it on if you intend to use it.
40
(a)
30
20
(b)
OFF
(c)
ON
(e)
OFF
(d)
Operation image
22:00
24:00
(time)
Following morning
Conditions
2
the indoor temperature is higher than the air conditioning setting and
If the above conditions are not satisfied, reevaluation is made every 60 minutes.
NOTE
The Nighttime free cooling operation works when the HRV unit is off. Therefore, it is not possible to stop the night purge operation, though the
forced off is input from the optional controllers for centralized control.
Test run
After completing the installation of the system, check again to make sure that no error was made in wiring or switch setting on the printed
circuit boards of the HRV units.
Then, turn on the power of the HRV units. Refer to the manual of the remote controller of each unit (remote controller for air conditioner, central control
unit, etc.) for conducting a trial operation.
HRV Features
2-3
FRESH-UP operation
Both the excessive supply mode and the excessive exhaust mode are selectable.
This function creates a more comfortable air environment.
Detail
Supply Fresh-up
(Excessive outdoor air supply)
Exhaust Fresh-up
(Excessive Exhaust air supply)
Major
effects
Application
Offices, etc.
Air supply
Air exhaust
HRV
Normal
ventilation fan
HRV
Air supply
Air exhaust
Example
Sick area
Floor area
Portion of fresh
up operation
ex. <Hospital>
ex. <Office>
(HC0010)
Centralized
control system
Independent system
Centralized
control system
Independent system
(HC0009)
Fan speed
Low
Normal
High
Low
Ultra-high
High
Ventilation air flow
setting
Fan speed
Low
Normal
High
Low
Ultra-high
High
Switch on the PCB (H / M / L)
L
M
H
Fresh-up operation
Off
On
Off
On
Off
On
Off
On
Terminal between J1
and JC
(Fresh-up by external
command)
Open
Short-circuit
Open
Short-circuit
Open
Short-circuit
Open
Short-circuit
Terminal between J1
and JC (Fresh-up by
external command)
Open
Short-circuit
Open
Short-circuit
open
Short-circuit
Fan operation
Fresh-up
Fresh-up
Supply air setting
Exhaust air setting
Supply side
Exhaust side
Supply side
Exhaust side
Low
Low
Low
Low
High
Low
Low
High
High
High
High
High
Ultra-high
High
High
Ultra-high
Low
Low
Low
Low
High
Low
Low
High
Ultra-high
Ultra-high
Ultra-high
Ultra-high
Ultra-high
High
High
Ultra-high
Fan operation
Supply side
Low
High
High
Ultra-high
Low
High
Ultra-high
Ultra-high
Exhaust side
Supply side
Low
Low
Low
Low
High
High
High
High
Low
Low
Low
Low
Ultra-high
Ultra-high
High
High
Fan operation
Exhaust side
Low
High
High
Ultra-high
Low
High
Ultra-high
Ultra-high
Supply side
Exhaust side
Supply side
Exhaust side
Low
High
High
Ultra-high
Ultra-high
Low
Low
High
High
Ultra-high
Low
Low
High
High
Ultra-high
Low
High
High
Ultra-high
Ultra-high
Ultra-high
High
High
Ultra-high
HRV Features
2-4
Material
1
2
The heat exchanger element adopts a new paper of high permeability. The material recovers exhaust humidity at a speed of 2 times of the previous
model.
The material is flame-retardant for safety.
The fungiproof design also keeps the air clean.
Structure
The heat exchanger element is designed without moving parts for higher durability and reliability.
The supply air passage and the exhaust air passage are arranged in right angle to prevent the supply and exhaust air from getting mixed.
Permeation mechanism
Highly
humid air
Porous particle
(Absorbent)
water Vapor
FA/FB series
Moisture
absorption
Diffusion
Moisture
release
HRV Features
2-5
EA
SA
EA
RA
OA
RA
OA
(HC0234)
1
2
(HC0235)
Service Maintenance
Switch Box
Access door
Maintenance cover
(HC0235)
2-6
HRV Features
2-7
2-7-1
The VRV
outdoor unit
2
HRV (VKM)
HRV (VKM)
HRV (VKM)
Indoor unit
remote control
2-7-2
Conventional
system
P56
P56
P56
P56
P56
HRV Humidifier
Outdoor (1,000 CMH)
unit
New system
P56
P56
P56
10
The VRV
outdoor unit
P56
One fewer
unit!
VKM
Installation
3-1
The air suction and discharge grille may give out operating
sound higher by 8 to 11 phons than of the HRV units body.
When installing this unit in a quiet place, take measures to
reduce operating sound.
3-1-1
OA
RA
EA
SA
Air suction /
discharge
grille
operating sound.
Note:
When using a sound-insulating sheet, it is necessary to have the
entire body of the unit covered with it. Note, however, that some
models do not allow the use of a sound-insulating sheet because it
may badly affect the ventilation of their radiation heat.
(HC0054)
OA
RA
EA
SA
Flexible duct
Apply sound-insulating
material to the SA duct.
Note:
Air supply
and exhaust
grille
3-1-3
Flexible duct
Apply sound-insulating material here
for effective operating sound reduction.
3-1-2
(HC0058)
(HC0055)
(HC0059)
3. To reduce the air flow sound heard from the air discharge outlet
(suction inlet) of an attic-installed duct type model, use a small
diameter flexible duct, which excels in sound absorptivity, for
greater sound reduction effect.
1 Branched duct (for letting air flow through two ducts to slow
Fig.5
hanging strength
See Precautions for installing and handling the unit on pages
77 and 87.
2. Take the following sound reduction measures. (Fig.2)
Fig.2
(HC0060)
2 Flexible duct
(HC0057)
11
Installation
3-1
3-1-4
Caution
1
3
1. Be sure to connect a flexible duct (2 m) to an outlet of the main body in the indoor air supply side.
2. Do not connect a spiral duct and an alminium bellows directly to the outlet of the main body.
*A silencer is effective especially when using the flexible duct at the same time.
3-1-5
Main body
6 m long
Main body
Silencer
Main body
Main body
Silencer
Flexible duct 2 m
Flexible duct 2 m
Flexible duct 6 m
Flexible duct 6 m
Spiral duct 4 m
Spiral duct 4 m
5 Mounting a silencer
6 Spiral duct 6 m
No measures taken
(dB)
Main body
Main body
Main body
Silencer
Spiral duct 4 m
Spiral duct 6 m
Flexible duct 2
m
Spiral duct 6 m
Suction /
discharge gri
(HC0061)
Note:
Measure the noise at 1.5 m below the air supply grille. Operating noise conforms to JIS standard and the value is converted in terms of the anechoic
chamber.
3-1-6
Notes for duct work is written on the HRV units as indicated below.
When connecting a spiral duct or an aluminum bellows, sound at the air discharge outlet is higher by 8~11 phon than the main body operating
sound.
When using this unit in a quiet place, take a remedy for sound by connecting an optional flexible duct at the outlet of the indoor air suction side of
the main body.
12
Installation
3-2
Centralized piping
Direction of
air flow
(Indoor side)
OA
Discharge grille
EA
HRV units (No. 1 unit)
(Outdoor side)
Discharge grille
HRV units (No. 2 unit)
OA
OA
(Outdoor side)
(Outdoor side)
(Indoor side)
(Indoor side)
OA
RA
EA
SA
OA
RA
EA
HRV units
(No. 1 unit)
Discharge grille
Discharge grille
HRV units (No. 1 unit)
Air suction
grille
Air suction
grille
Discharge grille
Discharge grille
Air suction
grille
:Damper opened
:Damper closed
(HC0063)
(HC0064)
13
Installation
3-3
Cautions
When a smoke back flow prevention damper is
installed
1
3
Use suspension bolts for installation. Confirm that the place for
installation can stand the weight of the unit. If not, reinforce the place
with beams, etc. and install the suspension bolts.
If the strength of the place for installation is not sufficient, the place
resonates to the vibration of the unit and abnormal noise may be
transmitted.
Fan
Centralized duct
(Vertical hole)
Steel plate of
0.8 mm thick or more
Inspection hole
(450450 or more)
(HC0066)
Fan
Centralized duct
(Vertical hole)
Cross sectional area :
Less than 250 cm2
Steel plate of
0.8 mm thick or more
5. Air filters are provided on the air intake side and exhaust
air side. Be sure to install these filters.
Air filter cleans the air and prevents clogging of the element, and must
be installed properly.
2 m or more
Rigid mounting
Caution
Installing a 2 m exhaust duct in a centralized duct involves difficulty in
construction and maintenance, and is not practised generally. In
actual installation a smoke back flow prevention damper is used (field
supply).
Fill mortar
(HC0065)
Conditions:
14
Installation
3-3
Cautions
RH
cy
en
=<
i
fic
ef %
py B
al g
th olin
n
o
E c
in
OA
SA
RA
Note:
If the outdoor discharge air exceeds 95% RH, please preheat the
outdoor suction air before it goes through the heat exchanger.
1)
1
3
Temperature efficiency A%
Dry bulb temperature (CDB)
(HC0067)
100
Not
available
90
Example
Ceiling
80
Indoor conditions
25CDB, 60% RH
22CDB, 50% RH
22CDB, 60% RH
70
Available
60
HRV units
body
50
Vibration
isolating rubber
(HC0070)
40
30
20
40
cy
en
ici
f
f
e %
lpy C
tha ating
n
E he
in
5%
RH
<= 9
RA
(In heating)
OA
EA
Sa
tur
ati
on
cu
rve
2)
Such operation may cause frost to form in the body and dirty ceiling may
result.
Motor
Motor
Motor mount
Vibration isolating
rubber
(HC0071)
Caution
When the outdoor air infiltrates into the ceiling and the temperature
and humidity in the ceiling become high, insulate the metal part of the
unit.
Temperature efficiency A%
Dry bulb temperature (CDB)
(HC0069)
15
Installation
3-4
Cautions in installation
1
3
A place such as machinery plant and chemical plant where gas, which
contains noxious gas or corrosive components of materials such as
acid, alkali, organic solvent and paint, is generated. Place where
combustible gas leakage is likely.
Such gas can cause fire.
g as
3-5
Installation
gas
(HC0072)
VAM150-1000FA
Metal suspension bracket
Nut
Washer
(HC0073)
Double nut
40C
VAM1500,2000FA
Metal suspension bracket
(HC0074)
Nut
Washer
Double
nut
Carbon
black
(HC0076)
Note:
(HC0075)
3P034927-2B
16
Remove the clamp (at two locations) for securing the unit in transit,
if it prevents installation work. (Be sure to screw in the removed
mounting screw on the body side to prevent air leakage.)
Installation
3-6
Duct Work
3 - 6 - 1Caution
150 + 50
200
1
3
(HC0077)
(HC0080)
Image picture
Fig. 1
Indoor
External
wall
Outdoor
Mortar
Insulator
(Field supply)
1 / 100 1 / 50
Slope: Over 1 / 50
Aluminum tape
150
100
Body
Hood
(Field supply)
(HC0079)
Spiral duct
Spiral duct
(HC0081)
<e.g.>
Duct diameter
100 + 50
Caulking material
(Sealing material)
Hole diameter
150
17
Installation
3-7
Before obtaining access to terminal devices, all power supply circuits must be interrupted.
Connection of Wiring
1
3
Connection of wiring
A circuit breaker capable of shutting down supply to the entire system must be installed.
A single switch can be used to supply power to units on the same system. However, branch switches and branch circuit breakers must be
selected carefully.
Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
Be sure to give the electric grounding (earth) connection.
VRV
outdoor unit
Power supply
Transmission
wiring
Main
switch
Switch
Fuse
VRV
Indoor unit
HRV
VRV
Indoor unit
HRV
Remote control
(HC0082)
Model
FXYCP150FA
Transmission wiring
Wire
Size
Wire
Size
15A
H05VV-U3G
FXYCP250FA
FXYCP350FA
FXYCP500FA
FXYCP650FA
FXYCP800FA
FXYCP1000FA
FXYCP1500FA
FXYCP2000FA
(HC0083)
18
Optional accessories
4-1
4-1-1
Features
4-1-2
3
1
4
CO2 measurement is done with air inside the unit, not in the room
When the unit is switched on, it will operate 20 min. in High fan speed to allow CO2 measurement of air in the room and not inside the unit
CO2 sensor is
installed inside
the unit with
power supply
from the unit
4-1-3
Category
IDA 1 - High indoor air quality
IDA 2 - Medium indoor air quality
IDA 3 - Moderate indoor air quality
IDA 4 - Low indoor air quality
Source: EN13779
Effects of CO2 level on adults at good health:
- normal outdoor level: 350-450 ppm
- acceptable levels: < 600 ppm
19
Optional accessories
4-1
4-1-4
4-1- 4-1
1
4
Critical values
From the moment a set critical value in terms of PPM is surpassed, the fans will start a dedicated program
Both fans (supply & exhaust) will run in the programmed speed of the response program
Use of same fan curves of initial set-up
4-1- 4-2
1.
2.
Field setting
Mode
Switch
Position
19 (29)
05
Response program
18 (28)
a) 01 (Linear)*
b) 03 (Tap A)
c) 04 (Tap B)**
19 (29)
a) 01 (0)*
b) 02 (+200)
c) 03 (+400)
d) 04 (+600)
e) 05 (-200)
f) 06 (-400)
g) 07 (-600)
* = factory pre-defined
** = for VAM-FB only
Example: In field setting mode 19 (29) with setting switch Nr 7 in position 05 the complete range of factory defined trigger values is shifted as follows:
Trigger Values
CO2 (PPM)
Trigger Values
CO2 (PPM)
Factory-defined
Personalized
1450
1250
1300
1100
1150
20
Setting pos. 05
950
1000
800
850
650
700
500
550
350
400
200
Optional accessories
4-1
4-1-4
4-1- 4-1
2.
Start
Judgment
Calculation of CO2 concentration
Operation pattern (*) at medium or low CO2 concentration
1
4
Linear (min.)
Tap
20min. High Speed
20min. High Speed
Every 30 min.
Every 20 min.
1-time PPM measurement
Average of 6 PPM
measurements (every 5
min.)
Below 700 PPM
Tap A: Below 850 PPM continuously in L speed
continuously in L speed Tab B: Below 850 PPM unit will stop**
Example
Coming from 750, a PPM of 900 is measured
In Linear
The fans will operate 20 minutes in H, then 10 minutes in L
Then a new judgment is done (= after 30 min.)
In Tap A
The fans will shift from L to H for 20 minutes
Then a new judgment is done
In Tap B (VAM-FB only)
Ventilation is Off and no CO2 measurement till next judgment
Trigger Values
CO2 (PPM)
Linear (min.)
Tap
Tap A
Tap B
NOTE
The response is always step by step, even if suddenly a very high increase of PPM is measured
Trigger Values
CO2 (PPM)
Linear (min.)
Tap
Tap A
Tap B
Suddenly
very high
increase
of CO2
stop
stop
stop
stop
21
Optional accessories
4-2
4-2-1
Components
1. KRP50-2 PCB (1)
Components
See the right for components.
(16)
2 PCS.
Fixing Screw
Fixing Board
(HC0114)
Tie wrap(1)
3 PCS.
Clamp
Installation
(5)
(HC0113)
Fixing Screw
Manual(1)
PCB Support
(Attached to
Adapter PCB)
Installation guide
1 The KRP50-2 can be connected to HRV units as follows to send
the operation signal (pilot lamp etc.) to remote locations.
Electric wiring is as follows.
For Remote contact
KRP50-2A90
Switch Box
Power supply
(1 220 ~ 240 V)
Pilot lamp
(Operation display)
J1 J2 JC
3P connector
2P connector
1
2
X9A SS1
X10A
F1 F2
X11A
P1 P2
HRV unit
KRP50-2
P1 P2
Applicable adapter
Adapter name
(HC0253-1)
For Humidifier
J1 J2 JC
YC
1
Float
switch
A
B
3P connector
2P connector
X9A SS1
X10A
F1 F2
X11A
P1 P2
Y2
HRV unit
KRP50-2
Humidifier
Humidity Controller
(Field supplied)
P1 P2
Remote control
for HRV unit
(HC0115-1)
22
Kit name
(1)
KRP50-2
(2)
KRP2A21
4P055444
Power supply
( 1 100 V or 200 V)
SV
Lid
Fixing Screw
Optional accessories
4-2
Zone control
Per group
Remote control
=RQHFRQWUROIRU);<&.9(XQLWVFRQWUROJURXSVRIDQG
([
.53$[NLW
%5&&[NLW
To outdoor unit
0D[JURXSV
NOTES
0D[XQLWV
0D[XQLWV
Indoor unit
8QLHGFRQWURORIDPD[JURXSVRIDPD[LQGRRUXQLWVHDFK%XWWKHPD[RILQGRRUXQLWVLV
1.
The KRP2A61 62 51 52 53 enables operation by remote control (ON/OFF control, temperature setting,
operation display, error display). With it, the following system can be built. Note however that the adapter cannot
be used with other optional controllers for centralized control.
1
Individual indoor units connected to the centralized line cannot be displayed individually.
5HPRWHFRQWUROLQSXWWHUPLQDOERDUG;0
&RQQHFWVFRQWUROLQSXWIURPUHPRWHKRVW
computer monitor panel, timer, etc. ).
'LVSOD\RXWSXWWHUPLQDOERDUG;0
&RQQHFWVRSHUDWLRQDQGHUURURXWSXWWRDUHPRWHSRLQWKRVWFRPSXWHU
PRQLWRUSDQHOHWF1RUPDORSHUDWLRQ::PDOIXQFWLRQ::
7RGLVSOD\DOOFRQWUROXQLWVDVXQLHG]RQHVHWWR=RQH
(Factory set)
1PA63641-1M
23
3
4
Optional accessories
4-2
Electrical wiring
First wire between the indoor and outdoor units, then to the separate
power sources, and between the indoor units and the remote
controls. Then, check wiring is correct. (If wanting group control
by remote control, check transmission wiring.) For details, see the
installation manual of the indoor and outdoor units.
Next, wire between the wiring adapter for electrical appendices (1)
and the indoor units. For details, see Wiring to indoor units.
Finally, wire between external units such as the host computer
monitor panel, and make the necessary settings. For details, see
Wiring to external units (host computer monitor panel).
Note
Max. 16 units
Max. 16 units
1.
X/8A/X35A
PC board assy
Remote control
Remote control
:LULQJVSHFLFDWLRQV
Wiring ... Sheathed wire (2-wire)
Gauge ... 0.75 ~ 1.25 mm2
Length ... Max. 1000 m
( IMPORTANT)
Keep transmission wiring at least
50 mm away from power supply
wiring to avoid malfunctions.
Remote control
NON
VOLT
Input B
Input A
Wiring adapter
KRP2A61 62 51 52
Input A
Factory set: 0
position
:LULQJVSHFLFDWLRQV
Wiring ... Sheathed wire
Gauge ... 0.18 ~ 1.25 mm2
Length ... Max. 150 m
( IMPORTANT)
Keep transmission wiring at least 50 mm
away from power supply wiring to avoid
malfunctions
Wiring adapter
KRP2A61 62 51 52
Input B
2.
Position
Function
Individual display
(input ignored)
CONTROL MODE
Adapter
PCB
Max. 64 groups
Remote control
acceptance / rejection
Central priority
Remote control
rejection
Function
Remote control
acceptance only (No
operation by the remote
location)
Operation + stop by
remote control acceptable
(No operation by the
remote control)
Operation + remote
control accepted
Position
Contents of input A
Stop for ON while
operating, Operate for ON
while stopping
Stop + remote
control rejection
3.
Temperature
setting (C)
Resistance (:
Temperature
setting (C)
73.8
|
77.8
25
0.0
|
3.4
16
82.4
|
85.8
26
5.0
|
11.6
17
91.0
|
94.0
27
13.8
|
20.0
18
99.4
|
102.2
28
22.4
|
28.4
19
108.6
|
110.4
29
31.0
|
36.4
20
117.2
|
119.2
30
39.4
|
44.8
21
125.8
|
127.4
31
48.2
|
52.8
22
134.2
|
140.0
32
56.6
|
61.2
23
65.2
|
69.4
24
Wiring adapter
KRP2A61 62 51 52
Temperature setting corresponds to resistance values in the range of 0 to
135 :. Their relationship is as shown below.
Resistance (:
Note
( IMPORTANT)
Keep transmission wiring at least
50 mm away from power supply
wiring to avoid malfunctions.
:LULQJUHVLVWDQFHLQFOXGHGLQDERYHJXUHV
4.
:LULQJVSHFLFDWLRQV
Wiring ... Sheathed wire
Gauge ... 1.25 ~ 2.00 mm2
Length ... Max. 70 m
Forced thermostat OFF command
Operation display
Error display
Wiring adapter
KRP2A61 62 51 52
DC24V
AC24V
AC220
~240V
Operation output terminals (W1 and W2) and malfunction output terminals
(W3 and W4) are non-voltage constant contact output. (Allowed electric
current per contact is between 10 mA and 3A.)
Normal operation
output (Ry 1) ON
when the unit is
operating normally
Note
Ry1 only ON
Ry2 only ON
Both Ry1
and Ry2
OFF
Malfunction output
(Ry2) ON when the
unit stops because of
malfunction or when
a malfunction of
transmission occurs
between the adapter
and the indoor unit.
Output
System
All zones
OFF
1PA63642-1C
Note
Zone
control
Power source
Function of Input B
Note
Input B is for forced-OFF. When ON, stop + remote control is rejected, and input A
is ignored. When OFF, even if A is ON, the contents of when input A is ON are not
achieved. Input A must therefore be re-input.
Last command
priority
Remote control
rejected
Function
Position
Function
Position
Remote control
rejection
Operation + remote
control accepted
Stop + remote
control rejection
Contents when
input A is OFF
In zone control, operation is displayed as long as one indoor unit is running. When in
the last command priority mode, some units are not operation while ON.
In such case, even if input A is ON, the unit and all other units in the same zone
will stop.
When operating with dual momentry inputs from A and B
(Use a momentary input of 200 mili-sec or longer.)
Central priority
Remote control
acceptance only (No
operation by the remote
location)
Remote control
acceptance / rejection
Operation + stop by
remote control acceptable
(No operation by the
remote control)
Doing constant input A with position 7 ~ A, it will be forced OFF function (input A
is ignored)
Constant input cannot use for input B with position B.
Note
24
Optional accessories
4-3
KDDM24B50
Applicable model
Nominal pipe diameter
KDDM24B100
VAM500FB
VAM650FB
200 mm
200 mm
VAM800FB, VAM1000FB,
VAM1500FB, VAM2000FB
250 mm
Approx. 6 dB
4
Installation procedure
Body of silencer
Caution
Flange
(HC0212)
Dimensions
2. Remove the duct coupling of
the air inlet provided on the
body of HRV units.
KDDM24B50
KDDM24B100
A
Duct coupling
19
(HC0213)
M4 hole
6 hole
(HC0245)
Flange
KDDM24B50
320
340
206
210
KDDM24B100
380
480
250
260
HRV units
(HC0214)
Flange
Silencer
Duct coupling
HRV units
(HC0215)
Silencer
Aluminum
tape
Duct
HRV units
(HC0216)
25
Optional accessories
4-4
4-4-1
1
4
When operating the HRV units at or below 10C of the outdoor air temperature, use preheater (field supplied) to preheat outdoor air.
This kit is required to have ON / OFF delay control when preheater is used. (Initial setting is required.)
Cautions
For electric heater, safety devices and installation location, follow the standards or regulations of each country.
Use nonflammable duct for the electric heater. Be sure to keep 2 m or more between the heater and HRV unit for safety.
For the HRV units, use a different power supply from that of the electric heater and install a circuit breaker for each.
Setting mode
Setting position
19
03 or 04
ON
OFF
HRV
heat
cool
on
FAN
OFF
on
EH
OFF
10 sec delay
26
Optional accessories
4-4
Installation example
Return Air
Exhaust Air
HRV
Outdoor Air
Preheater
(Field supply)
Supply Air
Adapter
BRP4A50
Temperature thermostat (Field supply)
(Heater ON when the temperature is at or below 10C)
Temperature thermostat (Field supply)
(Heater OFF when the temperature is at or more than 5C)
Power supply (Field supply)
Relay box
(HC0223)
Wiring
Electric heater (EH)
NFB2
52H
Power
supply
for
electric
heater
Bimetal
switch
(85C)
Temperature
fuse (120C)
52H
Power
supply
for HRV units
Preheater
X9A
X10A
BRP4A50
TH3
TH4
Temperature thermo.
(ON when the temperature is at or below 10C)
Symbol
52H
EH
TH3
TH4
(Option)
HRV
(printed circuit board
Temperature thermo.
(OFF when the temperature is at or more than 5C)
Part
Relay
Electric heater (Bimetal switch, Temperature fuse, Thermal cut out etc. (built in)
Temperature thermostat (ON when the temperature is at or below 10C)
Temperature thermostat (OFF when the temperature is at or more than 5C)
(HC0224)
Installation Place
Install a relay box at site
Duct
Duct (front of EH)
Duct (behind EH)
Field supply
Field supply
Field supply
Field supply
Note:
Make sure to install TH3 and TH4 for safety.
Test run
After completing the installation of the system, check again to make sure that no error was made in wiring or switch setting on the printed circuit
boards of the HRV units.
Then, turn on the power of the HRV units. Refer to the manual of the remote control of each unit (remote control for air conditioner, central control unit,
etc.) for conducting a trial operation.
27
Optional accessories
4-4
1
4
Fixing Screw
2 pcs.
Clamp
2 pcs.
Installation
Install the Heater control kit to the outside of switch box for HRV unit as shown below.
Fixing Screw
Heater Control kit
Switch Box
Lid
Fixing Screw
28
Optional accessories
4-4
Switch box
ADAPTER PCB: (KRP50-2)
3
1
4
TERMINAL
WIRING
INSIDE DETAIL
29
Optional accessories
4-4
6FUHZV
Installation
<VKM-GB (M) V1>
Before installation (box cover is unnecessary)
$VVHPEOHPDLQNLWDQG[LQJSODWHDVVKRZQEHORZ
Fixing plate
,QVWDOOWKHKHDWHUFRQWURONLWWRWKHLQVLGHRIVZLWFKER[
DVVKRZQEHORZ
6FUHZV
6ZLWFKER[
7DNHRIIWKHVFUHZVRQWKHWHUPLQDOSODWH
7XUQXSWKHWHUPLQDOSODWHDVVKRZQEHORZ
6FUHZV
Clamp
<VAM-FB>
Before installation
$VVHPEOHPDLQNLWDQG[LQJSODWHDVVKRZQEHORZ
7DNHRII$SODWHIURPPDLQNLW
$SODWH
$SODWH
7DNHRQWKH[LQJSODWHDQG$SODWHDVVKRZQEHORZ
Fixing plate
6ZLWFKER[
Clamp
Clamp
,QWKHFDVHRI9$0)%DVVKRZQEHORZ
,QVWDOOWKHKHDWHUFRQWURONLWWRWKHRXWVLGHRIXQLW
6HHWKH,167$//$7,210$18$/RI+HDW5HFODLP9HQWLODWRU
IRU9$0)%
Maintenance cover
6FUHZ
&RQQHFW;RISULQWFLUFXLWERDUG
Box cover
6FUHZ
<<Cautions>>
7KHLQLWLDOVHWWLQJLVUHTXLUHGE\UHPRWHFRQWUROIRULQGRRUXQLWRU
+HDW5HFODLP9HQWLODWRUXQLW
6HHWKH,167$//$7,210$18$/RI+HDW5HFODLP9HQWLODWRU
(Local setting)
(OHFWULFKHDWHUVHWWLQJ212))GHOD\>@
7KHLQLWLDOVHWWLQJLVQHFHVVDU\IRUVDIHW\
Loop
6DPHIRUHDFK9$0)%
Clamp
6FUHZV
7KHEDFNVLGHRI
WHUPLQDOSODWH
&ODPSVQRWWRORRVHWKLVZLUH
Terminal plate
&RQQHFW;RISULQWFLUFXLWERDUG
Terminal plate
Installation example
(OHFWULFKHDWHU
(Field Supply)
7HPSHUDWXUHWKHUPR
(Field supply)
21ZKHQWKHWHPSHUDWXUHLVDWRU
EHORZ&
Wiring
3RZHUVXSSO\
for electric
KHDWHU
Fuse
2m or more
7HPSHUDWXUHWKHUPR
(Field supply)
2))ZKHQWKHWHPSHUDWXUHLVDWRU
PRUHWKDQ&
3RZHUVXSSO\
Relay box (Field supply)
Heater
(OHFWULFKHDWHU(+
7KHUPDO
cut out
<<Cautions>>
)RUHOHFWULFKHDWHUVDIHW\GHYLFHVDQGLQVWDOODWLRQORFDWLRQ
IROORZWKHVWDQGDUGVRUUHJXODWLRQVRIHDFKFRXQWU\
8VHQRQDPPDEOHGXFWIRUWKHHOHFWULFKHDWHU
%HVXUHWRNHHSPRUPRUHEHWZHHQWKHKHDWHUDQG+HDW
5HFODLP9HQWLODWRUXQLWIRUVDIHW\
)RUWKH+HDW5HFODLP9HQWLODWRUXQLWVXVHDGLIIHUHQWSRZHU
VXSSO\IURPWKDWRIWKHHOHFWULFKHDWHUDQGLQVWDOODFLUFXLW
EUHDNHUIRUHDFK
Remote control
IRU+HDW5HFODLP9HQWLODWRUXQLW7KHLQLWLDO
VHWWLQJLVUHTXLUHGE\UHPRWHFRQWURO
3RZHUVXSSO\IRU+HDW
Reclaim Ventilator
Field supply
7KHUPDOIXVH
Field supply
%LPHWDOVZLWFK
Field supply
Duct
Installation Place
: Magnetic Contactor
Part
K1M
: (OHFWULFKHDWHU%LPHWDOVZLWFK7KHUPDOIXVH
7KHUPDOFXWRXWHWFEXLOWLQ
Field supply
Symbol
EH
'XFWEHKLQG(+
Setting position
: 7HPSHUDWXUHWKHUPR
21ZKHQWKHWHPSHUDWXUHLVDWRUEHORZ&
6HWWLQJVZLWFK
1R
7+
3P343420E
Setting mode
: 7HPSHUDWXUHWKHUPR
2))ZKHQWKHWHPSHUDWXUHLVDWRUPRUHWKDQ&
Heater setting
7+
Initial Setting
Make sure to set remote control of Heat Reclaim Ventilator at initial setting as
VKRZQLQWKHULJKWWDEOHIRU212))GHOD\
30
Control systems
5-1
b
g
BEFORE USE:
GENERAL DESCRIPTION OF SYSTEM
For a maximum of 64 groups of indoor unit unified operation/stop can be performed. When using 2 central remote
controls, unified operation is possible with up to a maximum of 128 groups of indoor units. It can be used to set
operation modes by ZONE: ON/OFF operation, operation controlled by timer ON/OFF control possible/ impossible; as
well as, to set operating state: temperature setting,etc.
It can display the operation state such as operation modes and preset temperature by group.
Furthermore, the unit can be connected with an external key system or host computer monitor panel to enable forced
ON/OFF input (no-voltage normally open contactor).
(This unit cannot be used concurrently with the adapter for electrical appendices [optional accessory].)
c Group No. 1 00
b Central remote control
a Host computer monitor panel, etc.
g Forced ON/OFF command
d Group No. 1 15
e Group No. 2 00
f Group No. 4 15
h
(Stops with command from either central remote control)
A maximum of 64 groups
j Group No. 5 15
i Group No. 5 00
m A maximum of 128 groups
k Group No. 6 00
l Group No. 8 15
C
e
e
(HC0145)
31
Control systems
5-1
1
5
b Indoor unit
b
c Remote control
A maximum of 16 units
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
32
Control systems
5-1
OPTIONAL ACCESSORIES
You can perform the normal operation, take off the malfunction contact point and unified operation/stop by contact point, all by
connecting this unit with the unification adapter for computerized control. For further details, ask your DAIKIN dealer.
b
a
(1)
(2)
With two central remote controls, centralized control (indoor units) is possible from different locations.
Note:
For control alignment and settings for double central remote control, contact your DAIKIN dealer.
(HC0173)
33
Control systems
5-2
The control systems introduced here is for the HRV unit adopting the high speed and high performance transmission system (DIII-NET), the same as
the VRV systems and SkyAir series,
Control system
Basic method to
operate HRV unit
(Operation by
exclusive remote
control for HRV
unit)
Malfunction display
Manual
Ventilation
mode
changeover
Operation / Stop
Schedule timer
Description of system
Contol system
Independent
Purposes and
applications
Function
Controller
Automatic
Description of system
HRV unit
Interlocked operation
Initial setting
required
HRV unit
*1
*2
[Schedule timer]
[Central remote
control]
Up to 64 groups of
the units can be
controlled
individually by one
central remote
control.
Indoor unit
Remote control
for indoor unit
HRV unit
Remote control
for HRV unit
Indoor unit
HRV unit
Maximum number
of groups: 64 units
A maximum of
16 groups can be
controlled of
On / Off by one
unified On / Off
controller.
(Note)
Up to 4 unified ON /
OFF controllers can
be installed in one
system.
Centralized control
[Unified On / Off
controller]
(HC0018)
1. A remote control for HRV unit can be connected as the 2nd remote control. In addition to air volume control, selection of ventilation mode and
Fresh up mode is available.
2. In case of installing Indoor unit remote control only, initial setting is required for the setting of above function. However, in case of installing both
indoor unit remote control and HRV unit remote control, initial setting is not required.
34
Control systems
5-3
Basic patterns
5-3-1
Independent system
Control
system
Description of system
BRC301B61
Liquid crystal remote control
Remote
control
for HRV unit
Group control
Single-group interlocked operation
Direct duct connection system
HRV unit
Remote
control
for HRV unit
BRC301B61
Liquid crystal remote control
HRV unit
HRV unit
HRV unit
Remote
control
for HRV unit
Indoor unit
Remote
control
for HRV unit
Remote
control
for indoor unit
Indoor unit
Remote
control
for HRV unit
HRV unit
HRV unit
Remote
control
for indoor unit
35
1
5
Control systems
5-3
Basic patterns
Function
BRC301B61
ON / OFF
Ventilation mode (Auto / Heat Exchange / Bypass)
Ventilating rate (High / Low)
Fresh up mode (On / Off)
ON / OFF
Ventilation mode (Auto / Heat Exchange / Bypass)
Ventilating rate (High / Low)
Fresh up mode (On / Off)
Timer setting (On / Off)
Indication of filter cleaning signal
Digital indication of malfunction
BRC301B61
Cautions
page
39
41
(HC0019)
36
Control systems
5-3
Basic patterns
5-3-1
Control
system
Optional accessories
required
Description of system
Indoor unit
Indoor unit
DST301B61
Schedule timer
[Schedule Timer]
Collective / Individual control
HRV unit
Indoor unit
HRV unit
Remote control
for indoor unit
Unified On / Off
controller or
Schedule timer
or Adapter PCB
for remote
control
Remote control for HRV unit
Indoor unit
Centralized control system
KRP2A61
Adapter PCB for remote
control
(One adapter PCB
should be installed in
either the HRV unit or the
indoor unit.)
KRP2A61
Adapter PCB for remote
control (not possible to
use together with other
central control)
* One of the above control
should be installed in indoor
unit.
(However, only KRP2A61
can also be installed in HRV
unit.)
HRV unit
Zone 1
DCS302B61
Central remote control
Indoor unit
Zone 2
HRV unit
Central
remote
control
Indoor unit
HRV unit
37
1
5
Control systems
5-3
Basic patterns
Function
Cautions
page
41
41
(HC0020)
38
Control systems
5-3
Basic patterns
5-3-2
Independent system
Information
SS1
F1 F2
H (Ultra-High)
X11A
M (High)
X10A
L (Low)
P1 P2
SS1
Factory setting
HRV unit
Up to 500 m maximum.
(HC0022)
P1 P2
Remote control for HRV unit
(HC0021)
39
Control systems
5-3
Basic patterns
5-3-2
Independent system
1
5
J1 J2 JC
SS1
X9A
X10A
P1 P2
HRV unit
P1 P2
Main
Remote control
for HRV unit
Point
The wiring to the remote controls must be branched from the
unit as shown in the diagram.
(Though the crossover between the master and slave
remote controls is acceptable, the work to put two wires into
the remote control takes time.)
F1 F2
X11A
P1 P2
Sub
Remote control
for HRV unit
(HC0023)
Note
1. The maximum allowable total length of wires to the remote
control is 500 m.
2. Simple remote controls cannot be used for control with two
remote controls.
Group control
Purpose and functions
J1 J2 JC
X9A SS1
F1 F2
J1 J2 JC
X11A
X9A SS1
X10A
X10A
P1 P2
HRV unit
Point
F1 F2
X11A
J1 J2 JC
X9A SS1
F1 F2
X11A
X10A
P1 P2
HRV unit
P1 P2
HRV unit
P1 P2
Remote control
for HRV unit
(HC0024)
Note
1. The maximum allowable total length of wires to the remote
control is 500 m.
2. One liquid crystal remote control is always required.
3. Simple remote controls cannot be used for control with two
remote controls.
40
Control systems
5-3
Basic patterns
5-3-3
The remote control for indoor unit can control the interlocked
operation with the HRV unit, and it can make an initial setting
of the ventilation flow rate, the ventilation mode changeover
and fresh-up operation. The HRV unit can independently be
operated, even if the indoor unit is not in operation.
F1 F2
X9A
Note
X11A
1
5
P1 P2
Indoor unit
SS1
F1 F2
X10A
P1 P2
J1 J2 JC
P1 P2
HRV unit
Remote control
Up to 500 m maximum
(HC0025)
F1 F2
J1 J2 JC
X9A
P1 P2
Indoor unit
Setting
Slave
Master
F1 F2
X11A
X10A
P1 P2
Note
1. The amount of fresh air to the indoor unit should be less
than 20% of the total air volume of the indoor unit. (If the
amount of fresh air is too much, the capacity of the indoor
unit may reduce and the operating sound might be higher.)
2. The HRV unit can be operated independently, if the fan of
indoor unit is in operation.
3. Since this is two remote control system (for Indoor unit and
HRV unit), the Master / Slave setting is required.
SS1
P1 P2
HRV unit
Up to 500 m
P1 P2
Remote control
for HRV unit
Remote control
for indoor unit
(HC0026)
41
Control systems
5-3
Basic patterns
5-3-3
1
5
Up to 1000 m maximum
B1 B2 BC W1 W2 W3 W4
KRP2A1
(Installed in
the HRV unit)
Cautions
F1 F2
F1 F2
J1 J2 JC
X9A SS1
X10A
P1 P2
P1 P2
Indoor unit
P1 P2
F1 F2
X11A
P1 P2
Indoor unit
HRV unit
P1 P2
F1 F2
P1 P2
Indoor unit
P1 P2
Note:
The central transmission line can be extended up to 1000 m
maximum.
42
Control systems
5-3
Basic patterns
5-3-4
Unified
On / Off
Power supply
F1 F2
J1 J2 JC
Cautions
1. It is necessary to assign a central group number to each
indoor unit and HRV unit.
2. The operation of HRV unit is not interlocked with the
operation of indoor unit under this control system. If you
like to have a interlocked operation, please consider other
control system.
F1 F2
SS1
X9A
X11A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
Remote control
for HRV unit
P1 P2
P1 P2
Remote control
for indoor unit
The initial setting is required by the remote control for indoor unit
or HRV unit.
No change is required (as per factory setting)
F1 F2
J1 J2 JC
F1 F2
SS1
X9A
X11A
X10A
P1 P2
P1 P2
Indoor unit
P1 P2
HRV unit
Remote control
for indoor unit
(HC0028)
Power supply
F1 F2
Zone 1
J1 J2 JC
SS1
X9A
X10A
P1 P2
Cautions
P1 P2
HRV unit
Indoor unit
P1 P2
J1 J2 JC
Zone 2
The initial setting is required by the remote control for indoor unit
or HRV unit.
For zone 1ON [17(27)802]
For zone 2Factory set (No change is required)
P1 P2
Remote control
for indoor unit
X9A
SS1
F1 F2
X11A
X10A
Remote control
for HRV unit
J1 J2 JC
X9A
SS1
F1 F2
X11A
X10A
P1 P2
P1 P2
HRV unit
HRV unit
P1 P2
F1 F2
X11A
Remote control
for HRV unit
43
Control systems
5-4
Applicable patterns
5-4-1
Additional functions
1
5
J1 J2 JC
X9A
SS1
F1 F2
X11A
X10A
P1 P2
Cautions
HRV unit
1. Install insect control wire net on the air intake and exhaust
openings. (If the power is disconnected when the damper is
open, the damper remains open and the insects may get
into the room.)
2. When you install the remote control, it is possible to have
normal operation after the electric power is supplied.
P1 P2
Remote control for indoor unit
(HC0030)
Monitor of operation (KRP1C4/BRP4A50A) [HRV unit operating pilot lamp (local supply)]
Purposes and functions
To monitor the operation of one HRV unit.
3P connector
1
2
3
2P connector
[KRP1C4/BRP4A50A
J1 J2 JC
X9A
SS1
F1 F2
X11A
X10A
P1 P2
HRV unit
P1 P2
Remote control for HRV unit
(HC0031)
44
Control systems
5-4
Applicable patterns
5-4-1
Additional functions
5
J1 J2 JC
SS1
X9A
F1 F2
X11A
X10A
P1 P2
HRV unit
P1 P2
Local wiring
Operation of HRV
unit
Fresh-up
Normal
Open circuit
Capacity of connecting
terminal
No-voltage normally
open contact for microcurrent 16 V, 10 mA
Note:
The connecting wiring between HRV unit and the terminal for
local connection can be extended up to 50 m maximum.
45
Control systems
5-4
Applicable patterns
5-4-1
Additional functions
1
5
F1 F2
Cautions
J1 J2 JC
X9A
Setting
Slave
Master
SS1
F1 F2
X11A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
P1 P2
Remote control
for indoor unit
Remote control
for HRV unit
Connecting line can
be extended up to
500 m.
(HC0033)
Cautions
1. When the system is under group control, the input from
outside controls the operation of ON / OFF collectively, if it
is installed in the one of the unit.
J1 J2 JC
X9A
SS1
F1 F2
X11A
X10A
P1 P2
HRV unit
P1 P2
Remote control
for HRV unit
(HC0034)
46
Control systems
5-4
Applicable patterns
5-4-2
F1 F2
J1 J2 JC
Cautions
1. It is not possible to set the On / Off and timer setting by
the remote control for HRV unit. Also it is not possible to
display the filter-sign and malfunction code neither on the
remote control for indoor unit nor on the remote control for
HRV unit.
2. Since this is two remote control system (for Indoor unit and
HR unit), the Master / Slave setting is required.
Remote control for
Indoor unit
HRV unit
Setting
Slave
Master
X11A
SS1
X9A
F1 F2
1
5
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
P1 P2
Remote control
for indoor unit
Remote control
for HRV unit
Connecting line can be
extended up to 500 m
maximum.
(HC0033)
To central control
Cautions
1. In case of Zone control, the operation / stop and the timer
setting cannot be done by the remote control for the HRV
unit. (The operation lamp blinks twice to indicate that the
operation is not possible.)
2. The remote control for the HRV unit cannot set the group
no. for centralized control. In this case, the remote control
for the indoor unit has to be connected once for this setting.
3. It is not possible to have Precool / preheat time setting
function.
F1 F2
J1 J2 JC
SW
X9A
F1 F2
X11A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
Remote control
for indoor unit
P1 P2
Remote control
for HRV unit
(HC0035)
47
Control systems
5-4
Applicable patterns
5-4-3
1
5
Power supply
Cautions
F1 F2
TeS1
D1
D2
F1 F2
J1 J2 JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
P1 P2
F1 F2
J1 J2 JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
P1 P2
(HC0036)
Cautions
1. The setting of group number for central control is not
required.
2. The HRV unit judges the ventilation mode, individually.
3. The power supply for the schedule timer can be supplied
from the PCB of the unit. (X18A for the indoor unit and
X11A for the HRV unit)
Schedule timer
Power supply
DC 16 V
D1
D2
TeS1
F1 F2
X18A
J1 J2 JC
SS1
X9A
F1 F2
X11A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
P1 P2
F1 F2
J1 J2 JC
SS1
X9A
F1 F2
X11A
X10A
P1 P2
Indoor unit
P1 P2
HRV unit
P1 P2
P1 P2
(HC0037)
48
Control systems
5-4
Applicable patterns
5-4-3
Cautions
1. Adapter PCB can be installed in any unit connected to the
central transmission line.
2. It cannot be used with other central control.
3. The setting of group number is not required.
4. The HRV unit judges the ventilation mode, individually.
B1 B2 BC
The initial setting is required by the remote control for the indoor
unit or HRV unit.
Collective zone interlock setting
......................................OFF (as per factory setting)
The setting of switch on the PCB
Voltage / no-voltage changeover switch(SS1)
......................................no-voltage
*
Remote control mode changeover switch (RS1) should be
selected.
1
5
W1 W2 W3 W4
F1 F2
J1 J2 JC
SS1
X9A
X18A
F1 F2
X11A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
Remote control
for HRV unit
P1 P2
F1 F2
P1 P2
J1 J2 JC
SS1
X9A
F1 F2
X11A
X10A
P1 P2
P1 P2
Indoor unit
HRV unit
P1 P2
(HC0038)
49
Control systems
5-4
Applicable patterns
5-4-3
1
5
Zone setting
(Collective operation for plural group)
Power
supply
RC1
RC2
[1-01]
RSA
[1-02]
[1-03]
[1-00]
R3
RSB
Central
transmission line
R1
[1-05]
[1-04]
Zone setting
(Individual operation
R5
C
R7
[1-08]
RSC
RC1
RC2
RSA - D
R1 - 9
RC1
RC2
RSA - D
R1 - 9
AA
*2
*3
*3
AA
AA
BB
CC
DD
AA
*2
*3
*3
AA
*1
Linked to
A/B
Linked to
A/B
Linked to
C/D
RC2
R1 - 9
(Connection required,
when setting)
RSA - D
Total
evaluation
*1. Independent operation for ventilation is possible, if collective zone interlock setting is ON with the indoor unit in the same zone.
*2. It is possible by the initial setting.
*3. Display of malfunction code only.
*4. The meaning of total evaluation
AA: Interlocked operation with energy saving and changeable of Ventilation mode / Air flow rate
BB: Interlocked operation with energy saving and no changeable of Ventilation mode / Air flow rate
CC: No interlocked operation with energy saving and changeable of Ventilation mode / Air flow rate
DD: No interlocked operation with energy saving and no changeable of Ventilation mode / Air flow rate
*5. Interlocked operation setting must not be done for individual zone. (Because there is no unit to combine in zone except 1unit.)
50
*4
RC1
Not required
(Setting required
only for
)
R1 - 9
Filter-sign
Malfunction code
Linked to
C/D
Collective by zone
(Connection required,
when setting)
Choise condition
Not required
(Setting required
only for
)
(Connection required,
when setting)
10
(HC0039)
Interlocked
operation with
Energy saving
RSA - D
Required (
)
Not Required
RC2
On Off
R9
Independent ventilation
Operation/stop
Operation / stop
RC1
Group number
setting for
central control
3
4
10
[1-10]
Interlocked
zone contol
Zone
setting
Individual
Collective
Unit No.
9
[1-09]
RSD
Setting
[1-07]
*5
CC
*5
DD
Control systems
5-4
Applicable patterns
5-4-4
<Part 1>
<Part 2>
F1 F2
F1 F2
J1 J2 JC
X9A
SS1
F1 F2
X11A
SS1
F1 F2
X11A
X10A
P1 P2
X17A
P1 P2
J1 J2 JC
X9A
X14A
X15A
X10A
Indoor unit
P1 P2
P1 P2
Indoor unit
HRV unit
HRV unit
P1 P2
Remote control
for indoor unit
No remote control
(HC0042)
(HC0041)
Reason
Reason
Because the signal through the transmission line is originated
from the remote control, there is no transmission signal to operate
the units, if the remote control is not installed.
51
Control systems
5-5
5-5-1
When carrying out a central connection, connect the central line to F1 and F2 only on the corresponding multiple type for building P-board. Do not
connect to F1 and F2 on the ventilation side. ( = Connect to the terminal block X3M.)
5
A1P
Note 1) JC
J2
Ventilation P-board F1
F2
A2P
T1
T2
Corresponding multiple F1
type for building P-board F2
P1 P2
F1
F2
Centralized units
P1 P2
P1
P2
Connection to central
line is prohibited.
In case of a central control, operation ON/OFF can be done separately by each zone. (In this case, zone interlocked setting must be kept as the
factory setting (17. 08. 01).)
Structure without a remote control cannot be accepted because the remote control group is controlled within a VKM-GA(M) model. (intelligent
Touch Controller, central control controller)
* Alteration of set temperature and independent ventilation operation cannot be performed from a central device.
52
Control systems
5-5
5-5-2
5-5- 2-1
(This is because the operation mode switches automatically depending on the outdoor conditions
regardless of the indoor temperature when set to "Automatic".)
1
5
5-5- 2-2
When bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit identical to the VRV indoor unit (master unit),
and use group-linked operation.
Outdoor unit for heat recovery
EA
OA
BS Unit
BS Unit
RA
SA
If above setting is not made, the detection of correct temperature is not available and automatic judgment on proper cooling or heating cannot be made
when the temperature in the ceiling gets higher than indoor temperature.
Poor heating or shortage of the amount of humidification may result.
If the indoor unit and this unit are installed with different BS system inevitably, always take following remedies (1) and (2).
1
RA (Exhaust and suction) of this unit is not taken directly from inside of the ceiling, connect the suction duct and suction grille to the fitting port of
RA duct to suck the indoor air.
EA
OA
BS Unit
Suction
grille
SA
RA
Do not make the selection of heating or cooling in automatic mode and it shall be made by manual selection from remote control or centralized
controller.
53
Control systems
5-5
5-5-2
5-5- 2-3
1
5
EA
OA
Suction
grille
SA
RA
b) Do not connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure, the unit might back up.
c) When it is connected to the suction side of indoor unit as a direct duct connection system, etc., since there is a possibility that the body thermo of
the indoor unit detects erroneously SA discharge from this unit as indoor air, use the remote sensor (Optional).
54
Control systems
5-5
5-5-3
5-5- 3-1
VKM sucks the air after OA has subjected to total heat exchange with RA, detects the air temperature by means of the thermistor for inlet air into DXcoil (R3T) to make a judgment on operation mode, cooling or heating and exercises the control on the capacity of air heat exchanger.
1
5
RA
OA
R2T
DX-Coil
Thermistor for
outdoor air
R3T
SA
EA
Humidifier
electronic
expansion
valve
R5T
55
The present publication is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
compiled the content of this publication to the best of its knowledge. No express
or implied warranty is given for the completeness, accuracy, reliability or fitness
for particular purpose of its content and the products and services presented
therein. Specifications are subject to change without prior notice. Daikin Europe
N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest
sense, arising from or related to the use and/or interpretation of this publication.
All content is copyrighted by Daikin Europe N.V..
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende