Generation,
Distribution, Use
of Electric Current
4. Power transmission and distribution in power supply systems
(introduction...)
4.1. Types of networks
4.2. International networks
4.3. Common voltage levels in the flow of electric energy
4.3.1. The importance of the voltage
4.3.2. Voltage levels of the elec-trotechnical networks
4.4. The importance of the electric current as dimensioning criterion for all
transmission elements
(introduction...)
4.4.1. Operating current
4.4.2. Short-circuit current
4.4.3. Environment
4.5. Common technical terms in the field of transmission and distribution
4.6. Lines and cables as transmission and distribution elements
4.6.1. Basic terms
4.6.2. Lines for heavy-current installations
4.6.3. Power cables
4.7. Switching and distributing plants and accessories for the transmission and
distribution of electric energy
4.7.1. Switching and distributing plants
4.7.2. Switches
4.7.3. Accessories
4.7.4. Insulating material (insulators)
4.8. Laying of lines and cables
4.8.1. General
4.8.2. Laying of lines
4.8.3. Laying of cables
4.8.4. Electric connections
Figure 7. Various types of networks as integral parts of the electric power transmission system - (1)
supergrids (extra-high voltage systems (2) medium-voltage system (3) low-voltage systems - 1 meshoperated network, 2 medium-voltage ring-operated network, 3 low-voltage distribution network (closed), 4
open network (multiple lump-loading), 5 star network, 6 feeding
Advantages and
disadvantages
simple circuit, clear
arrangement, very simple
protective system, very easy
planning, good utilization,
low costs, poor operational
reliability, poor voltage
maintenance, high losses
Examples of
application
small industrial
plants and local
networks of
small extent
lighting
installations
simple circuit
local networks
for long-distance
settlements,
extended factory
halls
Closed
system
of
ring layout
clear arrangement
factory plants,
medium-voltage
distribution
networks,
higher-level
supergrids
star layout
low-voltage
distribution
networks in big
industrial plants
meshed layout
local networks
for bigger and
large towns, lowvoltage networks
for big
companies
Figure 9. TN-C-network
- TN-S-network
PE protective conductor carrying no operating current.
electrically connected to the earthed network point (T). Such networks, which are internationally called
TT-networks, apply protective earthing (single earthing) using FI or FU protective circuits.
TT-network
The variety of the individual levels shall be demonstrated by means of an example of an installation
Figure 14. Example of possible voltage levels - 1 generator, 2 generator transformer, 3 substation
transformer, 4 distribution transformer, 5 consumers, 6 voltages in kV
To enable efficient transmission of high powers over large distance, the transmission voltages have become
higher and higher in the course of technological development.
4.4. The importance of the electric current as dimensioning criterion for all transmission
elements
Having dealt with the effects of the voltage on the physical dimensions of all electrotechnical transmission
elements, we now consider the effects of the electric current:
There are three objective factors of influence on the dimensioning.
The so-called instantaneous or asymmetric short-circuit current involves high electrodynamic loads for the
installation parts immediately on its occurence. The intensive magnetic fields generated as a consequence
of such current can physically destroy busbar installations, current transformer heads (insulator-type
transformer), switching devices etc. Conductor elements of overhead lines may also be affected.
- Sustained short-circuit current
The sustained short-circuit current occuring after the instantaneous short-circuit current has several times
the intensity of the operating current and, with a time lag after the short- circuit, results in heavy or extreme
heating of all components in the fault circuit. Mostly such current destroys the installation parts unless this
is prevented by adequate protective measures.
4.4.3. Environment
The thermal effects of the environment are important for the dimensioning of the installation with respect
to the cross sections of the transmission elements and to the protective elements to be used. High ambient
temperatures physically call for larger cross sections and low ambient temperatures permit smaller cross
sections than normally specified for the operating current. Mutual heating is taken into account in
installation engineering by providing for adequate distances of busbars, stranded conductors, lines and
cables between each other and between components and for air circulation.
Figure 16. Example of central potential equalization - 1 foundation earthing electrode, 2 heating tube
system, 3 drinking water pipe, 4 gas distribution pipe, 5 house connection box, 6 customers meter. 7
potential equalization line (connection point optional), 8 potential equalization bar (if necessary), 9 water
meter (conductively bridged, if the meter is built into a metallic pipe system), 10 structural design
Primary system
It serves the purpose of directly distributing the electric energy and includes all components directly
involved in the transmission of electric energy.
(Main) busbar
A conductor - bar or rope - to which several conductors or lines are connected.
Busbar section
A portion of busbars or busbar systems.
Each section comprises only one part of the switchboard sections.
Busbar system
Busbars with connected switchboard sections.
Distribution plant
Electrotechnical installation including accessories, such as actuators, transformers, measuring devices etc.,
the main purpose of which is to distribute electric energy to several outgoing lines.
Cubicle (cell)
is a construction of suitable material which stands on the floor and has a degree of protection at least at one
side but not at all sides.
Figure 19. Equivalent connection diagram of a line - RLeit. line resistance, RIso insulation resistance, XL
inductive reactance (inductance), XC capacitative reactacne (capacitance), Z consumer
- Ohmic line resistance RLeit
It depends on the length, material, cross section and temperature:
The conductor cross-section is to be selected so as not to exceed the admissible voltage and conduction
loss:
The inductance per conductor depends on the length of the line l, the conductor distance a and the
conductor radius r. It is calculated as follows:
L1 a r
H km mm mm
If it is a line with return line, the total inductance of the line is to be calculated using 2.1 for the length.
Because of the small conductor distance a of cables, the inductive reactance of cables is considerably
lower than that of overhead lines.
Examples:
Figure 20. Equivalent connection diagram of the capacitances of - a three-phase overhead line, CL
conductor-conductor capacitance, CE conductor-earth capacitance
The mutual capacitance of a three-phase overhead line is calculated as follows:
CB =CE + 3 CL
CB= mutual capacitance
CE = conductor-earth capacitance
CL = conductor-conductor capacitance
Charge current of the three-phase line
Table 3 Influence of circuit elements on the behaviour of lines with respect to different types of voltage and
current
Elements
Line
resistance
Insulation
resistance
Line
inductance
Line
capacitance
Low voltage
heating UV, PV
Direct current
Three-phase current
heating UV, PV
heating UV , PV
low corona
losses
self-inductance
effects only
when switching
on and off
with 2 three-phase
systems and operating
currents flowing in
opposite directions the
self-inductance effects are
compensated
line capacitance depends
on distance between each
of the three conductors, on
the insulation and
screening
capacitance
increases with
increasing line
length and
voltage