Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 1 of 87
WIP-SIPS-PCS-001
08/02/08
First Issue
RM
PCS
GP
PCS
GP
ENG
Date
Revision
Description of Revision
Prepared by
Checked by
Approved by
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 2 of 87
REVISION RECORDING
Date
Revision
Description of Revision
Prepared by
Checked by
Approved by
08/02/08
First Issue
RM
PCS
GP
PCS
GP
ENG
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 3 of 87
TABLE OF CONTENTS
1.
INTRODUCTION.......................................................................................................................4
2.
RESPONSIBILITY ....................................................................................................................4
3.
SCOPE......................................................................................................................................4
4.
5.
FORMULA ................................................................................................................................6
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
DM WATER SYSTEM.............................................................................................................77
25.
26.
27.
28.
29.
30.
31.
REFERENCE ..........................................................................................................................87
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 4 of 87
1.
INTRODUCTION
This guideline generally outlines the methods for designing the process systems.
2.
RESPONSIBILITY
The design engineer shall be responsible for carrying out the Process system design. The
respective lead engineer shall counter check the correctness of calculations and design.
3.
SCOPE
This guideline covers the following subjects in detail:
1)
Formulas
2)
Material of construction
3)
Storage tank selection and sizing
4)
Vessel selection and sizing
5)
Pump selection and sizing
6)
Line sizing and selection
7)
Control valve selection and sizing
8)
Compressor selection
9)
Safety valve relief load calculation and selection
10) Raw water / service water / potable water system design
11) Cooling water system design
12) Chilled water / chilled brine system design
13) DM water system design
14) Steam & condensate system design
15) Service and Instrument air system design
16) Nitrogen generation / storage system design
17) Oxygen storage and system design
18) Diesel / Fuel oil / LSHS storage and handling system design
19) Flare system design and selection
20) Chemicals storage and handling system design
21) Process control
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 5 of 87
4.
PHYSICAL PROPERTIES
Property
Heat
Capacity
Units
Water
Organic
Liquids
Steam
Air
Organic
Vapors
KJ/kg C
4.2
1.0 - 2.5
2.0
1.0
2.0 - 4.0
Btu/lb F
1.0
0.239 - 0.598
0.479
0.239
0.479 - 0.958
kg/m
1000
700 - 1500
1.29@STP
lb/ft
62.29
43.6 - 94.4
0.08@STP
KJ/kg
1200 - 2100
200 - 1000
Btu/lb
516 - 903
86 - 430
W/m C
0.55 - 0.70
0.10 - 0.20
0.025 - 0.070
0.025 - 0.05
0.02 - 0.06
Btu/h ft F
0.32 - 0.40
0.057 - 0.116
0.0144 - 0.040
0.014 - 0.029
0.116 - 0.35
cP
1.8 @ 0C
**See Below
0.01 - 0.03
0.02 - 0.05
0.01 - 0.03
10-1000
1.0
0.7
0.7 - 0.8
Density
Latent Heat
Thermal
Cond.
Viscosity
0.57 @ 50C
0.28 @ 100C
0.14 @ 200C
Prandtl
Number
1 - 15
L (TC T ) 0.3
Gas density can be calculated by:
G =
MW P
Z R T
Tbp = P 10 9
0.25
Tbp in C ; P in MPa
Density of Metals
Metal
Density
(kg/m)
Aluminum
3500
Carbon Steel
7800
Galvanized Iron
6000
Stainless Steel
8000
Titanium
4000
FRP
2000
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 6 of 87
5.
FORMULA
5.1
Volume
Surface area
Sphere
D/ 6
Hemi-head
D / 12
D/ 2
S.E.head
D / 24
1.084D
Ellipsoidal head
D l / 6
0.08467D
0.9286D
F & D head
2R K / 3
R ( 1+ l2/ R (2 l/R))
Cone
D l / 12
Dl / 2cos
Truncated cone
( l (D + D d + d) ) / 12
30 Truncated cone
0.227(D d)
1.57(D d)
Cylinder
D l / 4
Dl
.
Where
l = Height of cone, depth of head or length of cylinder
= one- half apex angle of cone
D = Large diameter of cone / diameter of head or cylinder
R = Radius
r = Knuckle radius of F & D head
L = Crown radius of F & D head
h = Partial depth of horizontal cylinder
K,C = Coefficients
d = Small diameter of truncated cone
V = Volume
K=
L
2r
L L
1 + 1
R
R
R R
e = 1
l2
R2
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 7 of 87
5.2
V1 = L R 2
sin( ) cos( )
57.3
h
cos( ) = 1 R
= Degrees{ A cos()}
Volume of Head (V2) (both heads)
V2 = 2 0.215 h (3R h )
Total Volume (V)
V = V1 + V2
5.3
V1 =
D2h
V2 = 0.215 h (3R D )
Total Volume (V)
V = V1 + V2
5.4
A1 = R 2 ( Ar cos(1 h / R) ) L
Wetted area of heads (A2) (heads are assumed to be hemispherical) (two heads)
RH
A2 = 2R 2 1
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 8 of 87
5.5
5.6
= Ql / (Ql + Q g )
h = l + g (1 )
h = l + g (1 )
Where Q
l
g
h
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 9 of 87
6.
6.1
Insulation
Thickness (mm)
25
40
50
65
80
Nominal Pipe
Size
90
100
115
125
140
150
165
180
190
200
1/2
68
230
456
723
760
61
205
409
653
760
48
150
302
491
707
760
45
134
269
439
635
760
42
122
244
398
579
760
40
111
221
361
526
710
760
37
100
195
319
465
629
760
35
86
164
265
386
524
676
760
34
79
147
236
343
465
599
745
760
10
33
75
136
216
312
422
544
676
760
12
32
72
129
203
292
393
506
629
760
14
32
70
125
196
281
379
487
605
731
760
16
32
68
121
188
268
360
462
573
692
760
18
31
67
117
181
258
345
442
548
661
760
20
31
66
114
176
249
333
426
527
635
750
760
Over 24 and
flat surface
31
64
110
167
236
314
400
494
594
701
760
To obtain the correct insulation thickness, read across from the correct pipe diameter to a
tabulated process temperature that is greater or equal to the actual temperatures. Read up for
the insulation thickness. For example a 16 diameter pipe operating at 190C will require 80
mm of insulation.
6.2
INSULATION MATERIAL
Up to 343C (650F), magnesia is most used
From 871C to 1037C (1600F 1900F) a mixture of asbestos and diatomaceous
earth is used
Ceramic refractories are used for higher temperatures
Cryogenic equipment -129C (-200F) employs insulation with fine pores in which air is
trapped
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 10 of 87
7.
MATERIALS OF CONSTRUCTION
Material
Carbon Steel
Stainless Steel
Titanium
Advantage
Low cost, easy to fabricate, abundant,
most common material. Resists most
alkaline environments well.
Relatively low cost, still easy to fabricate.
Resist a wider variety of environments than
carbon steel. Available is many different
types.
Moderate cost, still easy to fabricate.
Resistance is better over a wider range of
concentrations and temperatures
compared to stainless steel.
Very good resistance to chlorides (widely
used in seawater applications). Strength
allows it to be fabricated at smaller
thicknesses.
Disadvantage
Very poor resistance to acids
and stronger alkaline streams.
More brittle than other
materials, especially at low
temperatures.
No resistance to chlorides and
resistance decreases
significantly at higher
temperatures.
Little resistance to chlorides,
and resistance at higher
temperatures could be
improved.
While the material is
moderately expensive,
fabrication is difficult. Much of
cost will be in welding labor.
Pd stabilized
Titanium
Nickel
Hastelloy Alloy
Graphite
Tantalum
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 11 of 87
8.
Type
Model
Applicable Range
Remarks
Equations of state
for high pressure
hydrocarbon
applications
Platform
Separation
Equations of state
for high pressure
hydrocarbon
applications
Transportation of
oil and gas by
pipeline
Equations of state
for high pressure
hydrocarbon
applications
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Braun K-10
(BK10)
Suited for
vacuum
and low
pressure
applications
Applicable
range is 133 o
800 K. Can be
used up to
o
1100 K
REFINERY
Low Pressure
applications (up
to several atm)
eg: Vacuum
tower & crude
tower
Petroleum
Correlation Models
Chao-Seader
(CHAO-SEA)
Grayson
Chao-Seader
(CHAO-SEA)
Medium
Pressure
applications (up
to several tens of
atm) Coker Main
Fractionator
FCC Main
Fractionator
200-533 K
200-700 K
200-533 K
Petroleum
Correlation Models
Equation Of State
Models
Grayson
200-700 K
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 12 of 87
Hydrogen Rich
Applications eg:
Reformer,
Hydrofiner,
Hydrotreaters &
HydroDesulfurisers
Petroleum
Correlation Models
Equation Of State
Models
Equation Of State
Models
Grayson
200-700 K
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng Robinson
MHV2 equation
of state
(PRMHV2)
Accurate up
to 150 bar
All
Temperatures
Peng Robinson
Wong-Sandler
Equation Of
State (PRWS)
Accurate up
to 150 bar
All
Temperatures
Predictive
Soave-RedlichKwong (PSRK)
All
Pressures
All
Temperatures
Redlich Kwong
MHV2 equation
of state
(RKSMHV2)
Accurate up
to 150 bar
All
Temperatures
Redlich Kwong
Wong-Sandler
Equation Of
State (RKSWS)
Accurate up
to 150 bar
All
Temperatures
Chao-Seader
(CHAO-SEA)
200-533 K
Grayson
200-700 K
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
GAS PROCESSING
Hydrocarbon
separations Demethanizer C3splitter
Cryogenic gas
processing
Gas Dehydration
with glycols
Equation Of State
Models
Equation Of State
Models
Flexible and
Predictive Equation
of State Model
PETROCHEMICALS
Ethylene Plant
Main
Fractionator
Petroleum
Correlation Models
Ethylene Plant
Light
Hydrocarbon
Equation Of State
Models
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 13 of 87
Separation Train
Ethylene Plant
Quench Tower
Aromatics (eg:
BTX Extraction)
Substituted
hydrocarbons,
VCM Plant &
Acrylo Nitrile
Plant
Ether Production
eg: MTBE,
ETBE, TAME
Equation Of State
Models
Liquid Activity
Coefficients
Equation Of State
Models
Liquid Activity
Coefficients(very
sensitive to
parameters)
Equation Of State
Models
Ethyl Benzene
and Styrene
Plants
Liquid Activity
Coefficients
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
NRTL
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
UNIFAC
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
UNIQUAC
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
NRTL
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
UNIFAC
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
UNIQUAC
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
Peng-Robinson
(PENG-ROB)
All
Pressures
All
Temperatures
Redlich-KwongSoave (RKSOAVE)
All
Pressures
All
Temperatures
NRTL
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
UNIFAC
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
UNIQUAC
Low
pressures
up to 10
atm.
No component
should be close
to its critical
temperature.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 14 of 87
9.
RECEIVER
Kiker line
BL
Kiker line
AL
AR
BR
Bypass line
Kicker line
Balance line
Drain line
Major barrel
4 6
10
10
12
12
6 8
16
14
6 10
16
16
8 12
18
18
10 12
20
20
10 16
24
24
12 18
28
28
16 20
10
32
30
16 24
10
36
32
16 24
10
36
36
18 28
12
40
38
20 28
12
42
40
20 32
12
44
42
20 36
16
46
48
24 36
18
52
56
32 40
20
60
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 15 of 87
Approx.
maximum
tool length
(m)
(Note 2)
Approx.
maximum
tool weight
(kg)
(Note 3)
AL
BL
AR
BR
2.8
60
2.8
0.5
2.8
2.8
2.8
90
2.8
1.5
2.8
2.8
3.9
170
4.1
1.5
3.9
3.9
10
4.3
300
4.3
1.5
4.3
4.3
12
4.3
365
4.3
1.5
4.3
4.3
14
4.8
380
4.8
1.5
4.8
4.8
16
5.1
700
5.1
1.5
5.1
5.1
18
5.1
810
5.1
1.5
5.1
5.1
20
5.1
840
5.1
1.5
5.1
5.1
24
5.7
1600
5.7
1.5
5.7
5.7
28
5.8
2000
5.8
1.5
5.8
5.8
30
6.0
2000
6.0
1.5
6.0
6.0
32
6.6
2270
6.6
1.5
6.6
6.6
36
6.6
3560
6.6
1.5
5.3
6.6
38
6.6
3600
6.6
1.5
5.5
6.6
40
6.6
4090
6.6
1.5
5.5
6.6
42
6.6
4550
6.6
1.5
6.4
6.6
48
6.6
Note 4
6.6
1.5
6.6
6.6
56
6.6
Note 4
6.6
1.5
6.6
6.6
Pipeline
diameter
Launcher
Receiver
NOTES:
1) Refer the figure above for details
2) The lengths are extreme figures. To be checked with supplier for accurate dimensions
3) The weight is indicative for the pig only, excluding the weight of lifting/loading trolley
4) To be checked with supplier
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 16 of 87
10.
10.1
PUMP SELECTION
Service
Very high head at low flow
Metering small flows (< 1 m/h)
Viscous fluid (> 1000 cP)
Non-Newtonian fluid
Suspension of crystals or fragile solids
Entrained gas (> 2 vol%)
10.2
Type of Pump
Reciprocating
Reciprocating (plunger or diaphragm)
Rotary gear or screw
Screw
Rotary lobe
Rotary or diaphragm
Centrifugal pumps:
Single stage for 3.4 - 1134 m/h (15 - 5000 GPM) & 152 m maximum head
Multi Stage for 4.6 - 2500 m/h (20 - 11,000 GPM) & 1675 m maximum head
Efficiencies of 45% at 23 m/h (100 GPM), 70% at 113 m/h (500 GPM), 80% at 2270 m/h
(10,000 GPM).
Axial pumps can be used for flows of 4.6 - 22680 m/h (20 - 100,000 GPM)
Expect heads up to 12 m and efficiencies of about 65-85%
Rotary pumps can be used for flows of 0.23 - 1134 m/h (1 - 5000 GPM)
Expect heads up to 15,200 m (50,000 ft) and efficiencies of about 50 - 80%
Reciprocating pumps can be used for 2.3 - 22680 m/h (10 - 100,000 GPM)
Expect heads up to 300,000 m (1,000,000 ft).
Efficiencies:70% at 7.46 kW (10 hp), 85% at 37.3 kW (50 hp) and 90% at 373 kW (500 hp)
Q2 = Q1
D2
D1
D
H 2 = H 1 2
D1
D
BHP2 = BHP1 2
D1
Speed change
Q2 = Q1
N2
N1
N
H 2 = H 1 2
N1
N
BHP2 = BHP1 2
N1
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 17 of 87
D
N
H 2 = H 1 2 2
D
1 N1
D
N
BHP2 = BHP1 2 2
D1 N 1
10.3
Alternate for centrifugal pump (rotary pump) to be considered when fluid viscosity is above
220 cSt (or 2500 SSU). Small pumps become impractical above 220 cSt.
Generally centrifugal pumps are limited to about 4000 SSU max. viscosity
Correction factors to head, capacity and efficiency should be applied when viscosity is
above 70 SSU.
Viscosity correction calculation:
Viscous capacity (gpm) Qvis = Qwater* Cq
Viscous head (ft)
Hvis = Hwater* Ch
Viscous efficiency
Evis = Ewater* Ce
Correction factors (Cq,Ch,Ce)
10.5
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 18 of 87
T =
At shut-off
T =
(BHP
fromcurve
0.000252 Q H Sg ) 42.4
Q 8.33 Sg Cp
(BHP
at shutoff
) 42.4
W Cp
Q = 29.8 K d 2 P
Sg
Where Q = gpm, K = orifice disc coef =0.65, d = orifice dia (inch),
P = pres. drop (psi), Sg = Specific Gravity
10.6
NPSHr (m)
1.5
1.8
2.1 2.4
2.7 3.0
3.0 3.7
NPSHr (m)
3.7 4.3
4.3 6.1
6.1 7.3
7.6
10.7
10.8
Centerline
Elevation (m)
0.76
0.91
Centerline
Elevation (m)
1.1
1.4
Efficiency (%)
50 75%
60 80%
70 82%
Efficiency (%)
20 40%
30 50%
35 65%
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 19 of 87
10.9
Motor Rating
1.25 x BkW
1.15 x BkW
1.10 x BkW
Efficiency (%)
33
37
45
Efficiency (%)
58
64
Pump suction
Pump discharge
0 - 57 m/h
57 - 159 m/h
> 159 m/h
Pressure drop
0.23 - 0.68 bar/km
Pressure drop
Higher velocity is considered for bigger pipes and for higher operating pressures.
10.12 MULTIPLYING FACTOR FOR EQUIVALENT LENGTH
Pipe dia
up to 3"
4"
6"
8" and above
30
1.9
2.2
2.7
3.4
150
1.2
1.3
1.4
1.6
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 20 of 87
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 21 of 87
0-5%
10%
15%
20%
25%
0.294
0.468
0.658
0.875
0.950
0.059
0.094
0.132
0.175
0.200
Hso
Hd
dPv
dPo
dPf
dPs
Qm in
Qm
Qn
Qd
Where:
dPv = Control valve pressure drop at maximum flow Qm
dPo = Control valve pressure drop at full open condition at design flow Qd
H3
Pa
dPf2
dPf1
H1
PS
H2
Pd
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 22 of 87
Where: Pa
Pb
Pv
Ps
Pd
Sg
dPf1
dPf2
H1
H2
H3
= Pa + H1 H2 dPf1
= Pb + H3 H2 + dPf2
= Pd Ps
= DP *10.2 / Sg
(barg)
(barg)
(bar)
(m)
General considerations:
1) RVP is lower than the True vapor pressure (TVP or Absolute vapor pressure) of
hydrocarbon liquids. Correction chart is used to find out TVP from RVP at operating
temperature. TVP is used for pump calculations
2) Calculated NPSHa - 1 m (less 1 m) should be given in the process datasheet. The
difference between vendor NPSHr and datasheet NPSHa should not be less than 1 m.
3) In absence of data pump suction elevation can be considered as 0.6 m for smaller pumps
and 1.0 m for larger pumps (> 200 m/h).
4) In absence of data take 0.1 bar line loss for suction piping or 0.05 bar for smaller pumps.
5) Spare single stage pumps in service over 260C and spare multistage pumps in service
over 200C must be kept warm for quick start-up, by providing a bypass around check
valve. Needle valve to be provided for the bypass.
6) Pumping capacity over design: Column overhead pumps
20%
Product and transfer pumps 10%
Design pressure of pump = Design pressure of suction vessel (PSV set) + Max. suction static
head + Max. pump differential pressure
Pump Power calculation
Power estimates for pumping liquids
BkW = { Flow (m/h) x Head (m) x Sp.Gr. } / {367 x Efficiency}
BHP = { Flow (US gpm) x Head (ft) x Sp. Gr. } / {3960 x Efficiency}
**Efficiency expressed as a fraction in these relations
An equation developed for efficiency based on the GPSA Engineering Data Book is:
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 23 of 87
Service
Sour water drain
Intermittent
Utilities
For pump speeds above 100 rpm multiply the above volumes by (Pump rpm / 100).
b) Calculation of line shock pressure due to valve closure
The magnitude of line shock can be calculated by the following formula:
P=
Where,P
Vp
Sg
V
v
G
Sg V P (V v)
144 g
= Increase in pressure due to shock (psi)
= Velocity of pressure wave propagation in pipe (approx 4000 ft/s in small
pipes)
= Specific gravity of liquid (lb/ft)
= Velocity of liquid in pipe before valve closure (ft/s)
= Velocity of liquid in pipe at an interval equivalent to the time that a
pressure wave will travel up the pipe and back after the valve starts
closing (ft/s)
= Acceleration of gravity, 32 (ft/s)
Example:A 3" line 1000 ft long is carrying water at a pressure of 250 psi and at a velocity of 10 ft/s is
suddenly shut-off by a valve closing in 0.3 sec. Assuming that the velocity of the pressure
wave in the pipe is approx 4000 ft/s, it would take 0.5 sec for the wave to travel up the pipe
and back. This is slower than the time required for the valve to close and consequently v (the
velocity thro the valve after the pressure wave has made one complete cycle) is equal to zero.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 24 of 87
R P2 ((0.005 L) T )
A = 0.004
(P2 P1 )
Where,
Example:
In a 3"-40 sch line 1000 ft long water @ 230 gpm at 10 ft/s is flowing at 250 psi. Fric. Drop is
4.5 psi/100ft. Valve closure time is 0.3 sec.
P1 = 250 - (4.5*1000/100) = 205 psi
P2 = 250 * 1.5 = 375 psi
A = 0.004 * 230 * 375 * (0.005 * 1000 - 0.3) / (375-205) = 9.5 gallons.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 25 of 87
11.
11.1
11.2
TYPE OF ROOF
U.S. environmental protection agency requires the following for storage of hydrocarbon in
petroleum refineries:
1) Hydrocarbons with a natural vapor pressure of 1.5 psia (0.103 bara) or less at storage
temperature may be stored in a freely vented fixed roof tank
2) Hydrocarbons with a natural vapor pressure between 1.5 psia to 11.0 psia (0.103 bara to
0.76 bara) at storage temperature may be stored in floating roof tanks
3) Hydrocarbons with a natural vapor pressure in excess of 11.0 psia (0.76 bara) at storage
temperature should be stored in a fixed roof tank with a vapor recovery or refrigeration
system.
4) The flammability of the stored material, regulations governing the emission of the vapor to
the atmosphere together with cost of the product lost due to evaporation, should be
considered.
11.3
11.4
HOLDUP TIME
1)
2)
3)
4)
Holdup time is 5 minutes for half full reflux drums and gas/liquid separators
Design for a 5-10 minute holdup for drums feeding another column
For drums feeding a furnace, a holdup of 30 minutes is a good estimate
Knockout drum in front of compressors should be designed for a holdup of 10 times the
liquid volume passing per minute.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 26 of 87
11.5
VELOCITY CRITERIA
1) Liquid/Liquid separators should be designed for settling velocities of 2-3 inch/min (0.00085
m/s to 0.0013 m/s)
2) Gas velocities in gas/liquid separators
Velocity = k
( V
1)
Where k =
A 6 (150 mm) mesh pad thickness is very popular for such vessels
3) For positive pressure separations, disengagement spaces of 6-18 (150 mm to 450 mm)
before the mesh pad and 12 inches (300 mm) after the pad are generally suitable
11.6
DESIGN CONDITIONS
1) The design pressure for atmospheric storage tanks is +100 mmWC (or full of water) / -50
mmWC
2) Design pressure is 10% or 0.69 bar to 1.7 bar above the maximum operating pressure,
whichever is greater, as applicable
3) The maximum operating pressure is taken as 1.7 bar (25 psi) above the normal operation
pressure, as applicable
4) For vacuum operations, design pressures are 1 barg (15 psig) to full vacuum
5) For systems with maximum operating temperature (MOT) between -30C and 345C,
design temperatures is typically MOT + 15C (to 25C as applicable). Above this range the
margin increases
6) Minimum design temperature is 0C to 5C less than the minimum operating temperature
7) Minimum wall thicknesses for maintaining tank structure are:
6.4 mm (0.25 in) for 1.07 m (42 in) diameter and under
8.1 mm (0.32 in) for 1.07 m - 1.52 m (42-60 in) diameter
9.7 mm (0.38 in) for diameters over 1.52 m (60 in)
8) Allowable working stresses are taken as 1/4 of the ultimate strength of the material
11.7
MECHANICAL DESIGN
1) Thickness calculation based on pressure and radius is given by:
(Pressure) * (outer Radius)
Thickness =
(Allowable stress) * (Weld Efficiency) 0.6 (Pressure)
Where : pressure = psig, radius = inch, stress = psi, corrosion allowance = inch
** Weld efficiency can usually be taken as 0.85 for initial design work
2) Guidelines for corrosion allowances are as follows: 0.35 in (9 mm) for known corrosive
fluids, 0.15 in (4 mm) for non-corrosive fluids, and 0.06 in (1.5 mm) for steam drums and air
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 27 of 87
receivers
3) Generally 1.5 mm to 3.0 mm is considered as the minimum corrosion allowance (CA) for
Carbon Steel equipment/piping while Nil corrosion allowance is considered for Stainless
Steel and non-metallic equipment/piping
11.8
W=
3600 W '
e
A =W
Z T / M
245 P1
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 28 of 87
12.
HEAT EXCHANGERS
Some of the important design tips for heat exchanger design are:
1) Fluids that are corrosive, fouling, scaling, high pressure drop or under high pressure are
usually placed in tube side
2) Hot, viscous and condensing fluids are typically placed on the shell side
3) Pressure drops are about 1.5 psi (0.1 bar) for boiling/vaporization and 3-10 psi (0.2-0.7 bar)
for other services
4) The minimum approach temperature for shell and tube exchangers is about 20F (10 C)
for fluids and 10F (5C) for refrigerants.
5) Cooling tower water is typically available at a maximum temperature of 90F (30C) and
should be returned to the tower no higher than 115F (45C)
6) Double pipe heat exchangers may be a good choice for areas from 100 to 200 ft2 (9.3-18.6
m2)
7) Spiral heat exchangers are often used to slurry interchangers and other services containing
solids
8) Plate heat exchanger with gaskets can be used up to 320F (160C) and are often used for
interchanging duties due to their high efficiencies and ability to "cross" temperatures.
9) For the heat exchanger equation, Q = UAF (LMTD), use F = 0.9 when charts for the LMTD
correction factor are not available
10) Shell and Tube heat transfer coefficient for estimation purposes can be found in many
reference books
11) Most commonly used tubes are (19 mm) outer diameter on a 1 triangular spacing at 16
ft (4.9 m) long
12) A 1 ft (300 mm) shell will contain about 100 ft2 (9.3 m2)
A 2 ft (600 mm) shell will contain about 400 ft2 (37.2 m2)
A 3 ft (900 mm) shell will contain about 1100 ft2 (102 m2)
13) Typical velocities in the tubes should be 3-10 ft/s (1-3 m/s) for liquids and 30-100 ft/s (9-30
m/s) for gases
12.1
DESIGN MARGINE
The following design margins shall be adopted as applicable:
1) Heat exchangers shall be designed with 10% margin on area while using the normal heat
duty.
2) While designing heat exchangers, 10% margin on normal duty shall be considered and the
exchanger shall be designed with minimum over design factor (say 2% to 5%) on area.
3) If the design duty (10% to 15% over design factor) is used for sizing the heat exchangers,
then the exchanger shall be designed with minimum over design factor (say 2% to 5%) on
area.
12.2
EVAPORATORS
1) When the boiling point rise is appreciable, the economic number of effects in series with
forward feed is 4-6.
2) When the boiling point rise is small, minimum cost is obtained with 8-10 effect in series.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 29 of 87
12.3
TEMA X
TEMA G
TEMA H
TEMA J21
TEMA J12
TEMA E
TEMA K
ACU
2) Baffle cut orientation; parallel, perpendicular and 45 with reference to shell nozzle
Parallel
0
45
Perpendicular
90
3) Tube length : Length up to the tangent point of the outermost tube for U-tubes. The length
in the tube sheets should be included. Effective area is excluding the tube sheet.
U-tube exchanger
Vertical
code
0
code
1
code
2
Code 0, normal
Code 1, in front of
Code 2, behind U
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 30 of 87
6) Shell side inlet nozzle location: Normally it is assumed to be at the tube channel end.
Distance from tangent point to last baffle: Generally the last baffle is placed at the at the
tangent point of the U-tube
7) Tube arrangement
Triangular Pitch
Rotated Square
Pitch
Rotated
Triangular Pitch
Square Pitch
Flow
30
45
Pitch
Pitch
60
Pitch
90
Pitch
8) Impingement device: An impingement plate will be added if the inlet nozzle pV value is
greater than TEMA standards (1500 lb/ft s or 2232 kg/m s)
9) Adding a shell in parallel: If pressure drop limitations are not met at the maximum shell
diameter permitted, a unit can be added in parallel.
10) Adding a shell in series: If a pure counter flow exchanger has been selected, a shell can be
added in series only if the required heat duty can not be achieved at the maximum
permitted shell diameter. For multi-tube pass exchangers shells in series can be added if
the F-factor is less than 0.7
11) Temperature cross: When the outlet temp of the cold fluid is higher than the outlet temp of
hot fluid, it is called the temperature cross. For small exchangers, temperature cross does
not have much effect on the type of shells. But for large exchangers shells in series to be
used.
12) Baffle design: Baffle window cut should be between 17% to 35%. Baffle spacing should be
20% to 100% of shell ID. For no-tube-in-window exchangers, the ratio of window velocity to
cross-flow velocity should normally be 2 to 3. For double segmental baffles (for low pres
drop service), baffle spacing should not be too small to avoid ineffective shell side flow
patterns.
13) No-tube-in-windows baffle cut design: The baffle cut shall be limited between 15 - 30% of
shell diameter
14) Baffle cut out of window: The portion of the baffle which is continuous into the window acts
as a sealing strip in the window to force the fluid into the bundle. Continuous baffles should
be considered for pull-through floating heads.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 31 of 87
12.4
Window
Baffle
1) B-stream : Main cross flow stream through the bundle. B should be at least 60% of the total
flow for turbulent flow and 40% for laminar flow. If the baffle spacing is too narrow, more
flow will be forced into the A, C and E streams, thereby decreasing the heat transfer.
2) C-stream : Bundle to shell cross flow bypass stream. C should not normally exceed 10%.
Additional sealing strips can be incorporated to decrease this flow fraction. Although this
stream is partially effective for heat transfer, a high C-stream flow fraction, especially for
pure cross flow shells ("X"), can lead to a severe delta correction to the mean temp
difference
3) F-stream : Tube pass partition bypass stream. F should not normally exceed 10%.
Additional seal rods can be incorporated to decrease this flow fraction. Although this stream
is partially effective for heat transfer, a high C-stream flow fraction, is not recommended. To
block the F-stream flow fraction, program assumes one seal rod of a diameter equal to the
tube diameter for each 6 tube rows of cross flow in the exchanger
4) A-stream : Tube-to-baffle hole leakage stream. A-stream is large in narrow baffle spacing
where large TEMA clearances apply. However, the A-stream is fairly effective thermally. It
will decrease for multi-segmental baffles. Fouling layers might seal this A-stream. The
design should be examined by giving a zero tube-to-baffle clearance and the built-up
fouling layer thickness for a safe design from a pres drop stand point.
5) E-stream : Baffle-to-shell leakage stream. E-stream is highly ineffective thermally because
it does not contact the heat transfer surface; but, since it mixes poorly with the other
streams, it can cause distortions of the temp profile. If E-stream is more than 15%, double
segmental baffle or other modifications should be tested. If E-stream causes (ST program
only) low delta correction factor (< 0.8), corrective action is required.
F-stream seal rods: Allocate one seal rod of the tube diameter for each 6 rows in cross flow
in the exchanger
Sealing strips: These are metal strip or rod placed between the shell and the bundle which
has the effect of forcing the bundle bypass C-stream back into the bundle.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 32 of 87
12.5
Clearance
Slot area
Length
Thermal correction factor "F" = (TUBE) x (BAFFLES) x (F/G) x (HOT/COLD); where TUBE is
the uncorrected F-factor based on the no of tube passes, shell style and temp BAFFLES is the
correction when there are few baffles. (F/G) is the correction for thermal leakage through
longitudinal baffle for TEMA "F","G","H" shells.
(HOT/COLD) is the correction for nonconstant overall h.t.coeff due to diff in the h.t.coeff at the
hot and cold ends.
Effective MTD = (LMTD) x F x (DELTA): where DELTA is the profile distortion due to the Eand C-stream leakage
12.6
12.7
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 33 of 87
12.8
Main pipe
H
Liquid Driving
Head (Static
Head)
C
F
E
Nozzle pipe
Header pipe
Main pipe
1) For horizontal thermosiphon reboilers, most recirculating type feed systems can be
designed with kettle type since the height of the outlet piping entering the column is above
the liquid level in the column as shown in figure.
2) For thermosiphon reboiler systems for which the reboiler outlet piping enters the distillation
column at a height below the liquid level in the trap-out tray as shown in figure the piping
should be checked to ensure that the liquid level does not cover the exit nozzle.
3) For horizontal thermosiphon reboiler designs, the reboiler exit weight fraction should be
limited to 0.5 to avoid tube wall dry out.
4) For an effective design, most of the available loop pressure drop is used across the
reboiler. As a rule of thumb, this should be around 60 - 70%. However, the inlet and outlet
piping design may change this requirement.
Vapor+Liquid
Vapor+
Liquid
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 34 of 87
13.
13.1
13.2
TRAY COLUMNS/TOWERS
1) The most economic number of trays is usually about twice the minimum number of trays
2) The minimum number of trays is determined with the Fenske-Underwood Equation
3) Typically, 10% more trays than calculated are specified for a tower
4) Tray spacings should be from 18 to 24 (450 to 600 mm), with accessibility in mind
5) Peak tray efficiencies usually occur at linear vapor velocities of 2 ft/s (0.6 m/s) at moderate
pressures, or 6 ft/s (1.8 m/s) under vacuum conditions.
6) Pressure drop per tray is of the order of 3 of water or 0.1 psi (0.007 bar)
7) Tray efficiencies for distillation of light hydrocarbons and aqueous solutions are usually in
the range of 60-90% while gas absorption and stripping typically have efficiencies closer to
10-20%
8) Sieve tray holes are 0.25 to 0.50 in. diameter with the total hole area being about 10% of
the total active tray area
9) Valve trays typically have 1.5 diameter holes each with a lifting cap. 12-14 caps/square
foot of tray is a good benchmark. Valve trays usually cost less than sieve trays
10) The most common weir heights are 2 and 3 (50 to 80 mm) and the weir length is typically
75% of the tray diameter
11) For towers that are at least 3 ft (0.9 m) in diameter, 4 ft (1.2 m) should be added to the top
for vapor release and 6 ft (1.8 m) should be added to the bottom to account for the liquid
level and reboiler return
12) Limit tower heights to 175 ft (53 m) due to wind load and foundation considerations
13) The Length/Diameter ratio of a tower should be no more than 30 and preferably below 20
14) Liquid redistributors are needed every 5-10 tower diameters with pall rings but at least
every 20 feet (6.1 m). The number of liquid streams should be 3-5 /ft in towers larger than
3 ft dia, and more numerous in smaller towers
15) A rough estimate of reboiler duty as a function of tower diameter is given by:
Q = 0.5 D for pressure distillation
Q = 0.3 D for atmospheric distillation
Q = 0.15 D for vacuum distillation
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 35 of 87
REFLUX DRUMS
1) The most economic reflux ratio usually is between 1.2 Rmin and 1.5 Rmin
2) Reflux pumps should be at least 25% over designed
3) Reflux drums are almost always horizontally mounted and designed for a 5 min holdup at
half of the drum's capacity. A take off pot for second liquid phase such as water in
hydrocarbon systems, is sized for a linear velocity of that phase of 0.5 ft/s (0.15 m/s) with
minimum diameter of 16 (400 mm)
13.4
PACKED TOWERS
1) Packed towers almost always have lower pressure drop than comparable tray towers
2) Packing is often retrofitted into existing tray towers to increase capacity or separation
3) For gas flow rates of 500 ft/min (14.2 m/min) use 1 in (2.5 cm) packing, for gas flows of
2000 ft/min (56.6 m/min) or more, use 2 in (5 cm) packing
4) Ratio of tower diameter to packing diameter should usually be at least 15
5) Due to the possibility of deformation, plastic packing should be limited to an unsupported
depth of 10-15 ft (3-4 m) while metallic packing can withstand 20-25 ft (6-7.6 m)
6) Liquid distributor should be placed every 5-10 tower diameters (along the length) for pall
rings and every 20 ft (6.5 m) for other types of random packing
7) For redistribution, there should be 8-12 streams per sq. foot of tower area for tower larger
than 3 feet in diameter. They should be even more numerous in smaller towers
8) Packed columns should operate near 70% flooding
9) Height Equivalent to Theoretical Stage (HETS) for vapor-liquid contacting is 1.3-1.8 ft (0.40.56 m) for 1 in pall rings and 2.5-3.0 ft (0.76-0.90 m) for 2 in pall rings
13.5
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 36 of 87
14.
1) Fans should be used to raise pressure about 3% (12 or 300 mm water), blowers to raise to
less than 2.75 barg (40 psig), and compressors to higher pressures
2) The theoretical reversible adiabatic power is estimated by:
Power = m Z R T1
[( P2 / P1 ) a] 1
a
where:
T1 = Inlet temperature; R = gas constant; Z1 = Compressibility; m = molar flow rate
a = (k 1) / k
k = Cp / Cv
T2 = T1 ( P2 / P1 ) a
T2 = Outlet temperature for adiabatic reversible flow
3) Exit temperatures should not exceed 204C (400F)
4) For diatomic gases (Cp/Cv = 1.4) this corresponds to a compression ratio of about 4
5) Compression ratios should be about the same in each stage for a multistage unit,
P
Ratio = n
P1
1/ n
with n stages.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 37 of 87
k Pd k
BHP = 0.0857 (Z av ) (Z s )
k 1 P 1
s
Where BHP = Brake horsepower per stage
Qg = Volume of gas (MMscfd)
Ts = Suction temperature (R)
Zs = Suction compressibility factor
Zd = Discharge compressibility factor
Zav = (Zs + Zd) / 2
E
= Efficiency %
High speed reciprocating units use 70%
Low speed reciprocating units use 78%
Centrifugal units
- use 75%
K = Ratio of specific heat, Cp/Cv
Ps = Suction pressure of stage (psia)
Pd = Discharge pressure of stage (psia)
1
k
14.1
k 1
k
Q g Ts
E
VACUUM PUMPS
1) Reciprocating piston vacuum pumps are generally capable of vacuum to 1 torr (1 mmHg
absolute)
2) Rotary piston types can achieve vacuums of 0.001 torr
3) Single stage Jet ejectors are capable of vacuums up to 100 torr, 2-stages to 10 torr, 3stages to 1 torr, and 5-stages to 0.05 torr
4) A three stage ejector requires about 100 lb steam/lb air (100 kg steam/kg air) to maintain a
pressure of 1 torr
5) Air leakage into vacuum equipment can be approximated as follows:
Leakage = k V 2 / 3
Where k = 0.20 for P >90 torr, 0.08 for 3 < P < 20 torr, and 0.025 for P < 1 torr
V = equipment volume (ft)
Leakage = air leakage into equipment (lb/h)
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 38 of 87
15.
15.1
15.2
15.3
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 39 of 87
1)
2)
3)
4)
5)
6)
7)
8)
Blocked outlet
Gas blow by case
Inadvertent valve opening
Reflux failure
Tube rupture
Fire case
Reverse flow
Thermal relief case.
Q = 21000 F A 0.82
Where adequate drainage & firefighting equipment do not exist, the following equation should
be used:
Q = 34500 F A 0.82
Where q = Average unit heat absorption (Btu/h/ft of wetted surface)
Q = Total heat absorption (input) to the wetted surface (Btu/h)
F = Environmental factor (Values for various type of installation are given in
Table 5 in API 521 page 25)
A = Total wetted surface (ft)
The discharge area for pressure relief devices on vessels containing super critical fluids, gases
or vapors exposed to open fires can be estimated by using the following equation.
A=
F'=
F ' A'
P1
(T T1 )1.25
T
1
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 40 of 87
T1 = ( P1 / Pn ) Tn
Where Pn = Normal operating gas pressure (psia)
Tn = Normal operating gas temperature (R)
Air Coolers
For air coolers heat absorption equation becomes
Q = 21000 F A1.0
Total bare tube area to be considered instead of finned area, since fins are burned out in the
first few minutes of fire.
Water spray nozzles are some times mounted below the tubes in case of fire. API 520
recommends a minimum of 0.05 - 0.2 gpm/ft water spray rate.
15.3.3 Inadvertent Valve Opening
CV =
W
N 6 FP Y X P1 1
Y =1
X
3 FK X K
N 6 = Constant (27)
FP = Geometric factor
Y = Downstream pressure (bara)
X = Ratio of pressure drop
P1 = Upstream pressure (bara)
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 41 of 87
Cold fluid blocked in and continuous heat input from hot fluid. Two conditions can occur:
Cold fluid remains liquid and expands
WL = B Q / c
Cold fluid vaporizes
WV =
(T1 Tbp )
(T1 Tav )
Q/ L
API
3 to 34.9
35 to 50.9
51 to 63.9
64 to 78.9
Expansion Coef.
0.0004
0.0005
0.0006
0.0007
Fluid
Oil
Oil
Oil
Water
API
79 to 88.9
89 to 93.9
=>94
Expansion Coef.
0.0008
0.00085
0.0009
0.0001
WL = 2 1.256 d 2 C (P
Where WL = Relieving rate. (kg/h)
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 42 of 87
q L = 41.8 d 2
P1 P2
Sg
qV = 385 d 2 P1
M
Z T
SETTLE-OUT PRESSURE
In high pressure oil & gas handling facilities the compressor suction KO drum has to be
designed based on settle-out pressure. In case of compressor trip the suction and discharge
shutdown valves will close and the gas from high pressure discharge side will flow through the
recycle control valve to the suction side. A new settle-out condition is reached.
The settle-out pressure is calculated by the following formula:
( P V ) + ( P2 V2 )
Ps = 1 1
V1 + V2
Where Ps
P1
P2
V1
V2
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 43 of 87
16.
PIPE SIZING
The major criteria for line sizing are velocity and pressure drop
1) Liquid lines should be sized for a velocity of (5+D/3) ft/s and a pressure drop of 2.0 psi/100
ft of pipe at pump discharge. At the pump suction, size for (1.3+D/6) ft/s and a pressure
drop of 0.4 psi/100 ft of pipe.
**D = pipe diameter (inch)
2) Steam or gas lines can be sized for 20D ft/s and pressure drops of 0.5 psi/100 ft of pipe
3) Limits on superheated, dry steam or gas line should be 61 m/s (200 ft/s) and a pressure
drop of 0.1 bar/100 m (0.5 psi/100 ft) of pipe. Saturated steam lines should be limited to 37
m/s (120 ft/s) to avoid erosion.
4) For turbulent flow in commercial steel pipes, use the following:
M 0.2
20000 D
Where:P = Frictional pressure drop (psi/100 ft)
M = Mass flow (lb/h)
= Viscosity (cP)
= Density (lb/ft)
D = ID of pipe (inch)
For smooth heat exchanger steel tubes replace 20000 with 23000
P =
5) For two phase flow, an estimate often used is Lockhart and Martinelli. First, the pressure
drops are calculated as if each phase exist alone in the pipe, then
0.5
P
X = L
PG
Now the total pressure drop can be calculated by one of the following:
PTOTAL = YL PL or YG PG
Where
YL = 4.6 X 1.78 + 12.5 X 0.68 + 0.65
YG = X 2 YL
6) Control valves require at least 0.7 bar (10 psi) pressure drop for sufficient control
7) Flange ratings include 10, 20, 40, 103, and 175 bar (150, 300, 600, 1500, and 2500 psig)
8) Globe valves are most commonly used for gases and when tight shutoff is required. Gate
valves are common for most other services.
9) Screwed fitting are generally used for line sizes 2 inches and smaller. Larger connections
should utilize flanges or welding to eliminate leakage.
10) Pipe Schedule Number = 1000 P/S (approximate) where P is the internal pressure rating in
psig and S is the allowable working stress of the material is psi. Schedule 40 is the most
common.
11) About 15% margin in flow should be considered in general for line sizing
12) For fuel oil and heating oil, lines to be sized for 25% margin on flow
13) Pump suction lines should be checked for NPSH requirement. More critical if the liquid is at
its saturation temperature
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 44 of 87
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 45 of 87
Recommended Velocity and Pressure Drop for Process Liquids (not Water)
SL. NO.
Type of Service
Recommended Velocity
(m/s)
1.5 - 4.5
1.2 - 1.5
---
3.0 - 4.5
1.8 - 3.0
1.5 - 2.5
-------
1.
General recommendation
2.
0.6 - 1.8
1.2 - 2.4
1.1
2.2
6.
Laminar flow
Turbulent flow
Liquid density (kg/m)
320
800
1600
Pump suction
Boiling liquid
Non-boiling liquid
Pump discharge (m/h)
< 57
57 - 159
> 159
Liquid flow on gravity
1.8 - 2.4
2.4 - 3.0
3.0 - 4.5
0.9 2.4
13.5
9.0
4.5
0.9
7.
1.2 - 1.8
---
3.
4.
5.
8.
9.
Outlet to reboilers
10.
1.0
0.9
0.3 - 1.2
0.33
0.9 - 1.8
1.1
11.
1.2 - 1.8
---
12.
Refrigerant liquid
0.6 - 1.2
0.9
13.
0.18
---
NOTE :
The velocity higher than 3.0 m/sec for any line should be used only after due consideration for
velocity limitations.
Type of Service
Steam Headers : Saturated
Superheated
Recommended Velocity
(m/s)
60 (max)
75 (max)
30 - 50
0.57
1.1
2.2
3.4
---
35 - 100
6.8
35 - 100
6.8
---
3.4
---
1.1
3.8 - 4.6
---
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 46 of 87
2.
Pipe diameter
< 1
2
4
6
8
10
12
16
20 and above
Pump suction
0.6 - 0.9
0.9 - 1.3
1.5 - 2.0
2.0 - 2.7
2.4 - 3.0
3.0 - 3.6
3.0 - 4.3
3.0 - 4.6
3.0 - 4.8
1.2 - 2.1
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
---
3.
Pump discharge
1.5 - 3.0
---
4.
2.4 - 4.5
---
5.
0.9 - 1.5
---
6.
Process water
Cooling water
(once thro, brackish/sea)
Cooling water
(circulating, clean)
Water drain lines (gravity flow)
0.6 - 1.5
5.5
3.6 - 4.9
4.5
1.5 - 3.0
5.0
1.2 - 2.1
---
SL. NO.
Type of Service
General service
1.
7.
8.
9.
Type of Service
Recommended
Maximum Velocity
(m/s)
2.
3.
4.
5.
Phenolic water
Concentrated H2SO4
Salt water
Caustic solution (low temp.)
Stainless steel pipe with
CO2 -rich amine liquid
Cement pipe with salt water
Coal Tar enamel lined pipe with salt water
Plastic pipe or rubber lined pipe with
Liquid in general
Liquid with suspended solids
0.9
1.2
1.8
1.2
3.0
4.5
4.5
3.0
0.9 (min. velocity)
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 47 of 87
Recommended Velocity
(m/s)
-------------
0.22
0.34
0.68
1.3
3.4
4.5
38 - 60
18 - 30
12 - 15
0.11 - 0.22
0.45 - 1.1
0.45 - 1.1
Compressor suction
---
1.1
Compressor discharge
---
2.2
Refrigerant suction
5.0 - 11.0
---
Refrigerant discharge
11.0 - 18.0
---
---
1.1
Continuous operation:
P 20 bar g
20 < P 50 bar g
50 < P 80 bar g
80 < P 120 bar g
P > 120 bar g
6,000
7,500
(2)
10,000
15,000
20,000
10,000 (2)
15,000
25,000
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 48 of 87
17.
SELECTION OF VALVES
Some of the most common types of valves are:
17.1
GATE VALVES
Best suited control: Quick opening
Recommended uses:
1. Fully open/closed, non-throttling
2. Infrequent operation
3. Minimal fluid trapping in line
Applications: Oil, gas, air, slurries, heavy liquids, steam, non-condensing gases, and corrosive
liquids
Advantages
High Capacity
Tight shut-off
Low cost
Little resistance to flow
17.2
Disadvantages
Poor control
Cavitate at low pressure drops
Cannot be used for throttling
GLOBE VALVES
Best suited control: Linear and equal percentage
Recommended uses:
1. Throttling service/flow regulation
2. Frequent operation
Applications: Liquids, vapors, gases, corrosive substances, slurries
Advantages
Efficient throttling
Accurate flow control
Available in multiple ports
17.3
Disadvantages
High pressure drop
More expensive than other valves
BALL VALVES
Best suited control: Quick opening, linear
Recommended uses:
1. Fully open/closed, limited-throttling
2. Higher temperature fluids
Applications: Most liquids, high temperatures, slurries
Advantages
High Capacity
Tight sealing with low torque
Low cost
Low leakage and maintenance
Disadvantages
Poor control
Prone to Cavitation
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 49 of 87
17.4
BUTTERFLY VALVES
Best suited control: Linear, equal percentage
Recommended uses:
1. Fully open/closed or throttling services
2. Frequent operation
3. Minimal fluid trapping in line
Applications: Liquids, gases, slurries, liquids with suspended solids
Advantages
High Capacity
Good flow control
Low cost and maintenance
Low pressure drop
17.5
Disadvantages
High torque required for control
Prone to Cavitation at lower flows
OTHER VALVES
1) Another type of valve commonly used in conjunction with other valves is called a check
valve. Check valves are designed to restrict the flow to one direction. If the flow reverses
direction, the check valve closes.
2) Relief valves are used to regulate the operating pressure of incompressible flow.
3) Safety valves are used to release excess pressure in gases or compressible fluids.
17.6
CONTROL VALVES
Control valves are of three types based on how the valve travel or stroke (openness) relates to
the flow:
Equal Percentage: equal increments of valve travel produce an equal percentage in flow
change
Linear: valve travel is directly proportional to the valve stoke
Quick opening: large increase in flow with a small change in valve stroke
17.7
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 50 of 87
17.8
P = P1 P2
Cf =
P
PVC
NORMAL FLOW
CRITICAL FLOW
P < C f Pcritical
P C f Pcritical
C v = 1.16 Q
FOR LIQUID
G
P
C v = 1.16 Q
G
C f Pcritical
2
P = P1 P2
G=
g
@ STP
AIR
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 51 of 87
NORMAL FLOW
CRITICAL FLOW
P < 0.5 C f P1
P 0.5 C f P1
FOR GAS
Cv =
SATURATED
STEAM
SUPERHEATED
STEAM
Q
G T
295 P ( P1 + P2 )
Cv =
Cv =
Cv =
72.4 W
Cv =
P ( P1 + P2 )
72.4 W (1 + 0.00126 Ts )
P ( P1 + P2 )
Q G T
257 C f P1
Cv =
83.7 W
C f P1
83.7 W (1 + 0.00126 Ts )
C f P1
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 52 of 87
17.9
IF REQUIRED
3/4"
3/4"
1) For control valve diameter < 4" in continuous service, complete manifold
(block+bypass) shall be provided
2) For control valve diameter > 4" the need for installation of block & bypass valve
and handwheel around the control valve shall be defined for case by case
3) Bypass valves are globe valves for size <8" or butterfly valves for size >6"
Dia. Block
& By-pass
Valve Size
= 1
= 1
10
10
10
10
12
12
12
14
14
12
14
= 2
= 3
= 4
= 6
= 8
= 10
= 12
= 14
= 16
10
12
14
16
16
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 53 of 87
150#
300#
600#
900#
1500#
2500#
3/4"
3/4"
COULD BE SDV
TRAIN B
3/4"
3/4"
1) Double valving will be provided if the operating pressure is higher or equal than 75 barg
and for piping rating > 600#
2) Type of valve and isolation by spacer or spectacle blind must be as per the standard practice
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 54 of 87
Valve upstream,
downstream PSV
Ball valve FB ( )
BDV Ball valve FB ( )
ESDV Ball valve FB (
)
Valve upstream,
downstream PSV
Ball valve FB (
BDV Ball Valve
FB ( )
ESDV Ball valve
FB ( )
Glycol
Same criteria as
hydrocarbon
services if operating
temperature is
170 oC, the type of
ball valve will be
revised.
2 Butterfly
valve
Machinery suction:
Ball valve FB (
> 2 Butterfly
valve
for sea
water.
INJECTION
WATER
P > 150 bar
Ball valve ( )
3/4"
2"
BYPASS
< 2 Gate
valve
2 Gate
valve or
diaphragm valve
for sea water
Sea Water,
Cooling Water &
Hot Water
D
2"
LC
BYPASS
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 55 of 87
SP
3/4"
300 min
1/2"
2"
DO
DRAIN
UTILITY INJECTION
Injection dia =3/4"
MIN
CHEMICAL LINE
Top or Side
connection
Rem ovable
UTILITY INJECTION
Injection dia > 3/4"
UTILITY LINE
3/4"
FLOW
Process Class
3/4"
Utility Class
PSV INSTALLATION
TO FLARE HEADER
3/4"
LO
SP
3/4"
SPEC
BREAK
LO
V
LO
3/4"
600 min
LO
V
SPEC
BREAK
LO
V
PSV
SPEC
BREAK
PSV
SPEC
BREAK
PSV
LC
NOTES:
1) Distance between PSV and reducer is minimum
2) Downstream block valve is installed flange to flange (if the builtup back pressure is high this
valve is installed downstream the reducer)
3) The minimum distance of 600 mm is required in case of cold depressurisation to avoid icing of
the ball valve
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 56 of 87
UC
3/4"
UC
3/4"
3/4"
3/4"
3/4"
NOTES:
1) "Y" type strainer are installed for lines <6"
and "T" type strained are installed for lines >4"
2) For water services the pump drains are
collected in a tray which is routed to open drain
3) A bypass around the pump non-return valve
shall be installed if the pump operating temp is
>80C for spare pump heating or for draining
the spare pump discharge side
4) Utility connection (UC) is required only for
hydrocarbon services
COLLECTED
DRAIN
Level
instr. drain
PROCESS LINE
Level
instr. drain
COLLECTED
DRAIN
COLLECTED
DRAIN
2"
D
2"
3/4"
SPEC
BREAK
3/4"
SPEC
BREAK
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 57 of 87
18.
FLARE SYSTEM
Generally there are two types of flares:
Ground flare (in case of more land area available)
Elevated flare (common practice)
Burning pit, an excavated pit of 5 ft depth, with a burner inserted in a wall. These are not
generally
used because of excessive smoke. Location - at least 500 ft from process and
storage area and from any roadway.
Flares can be designed for smokeless operation. Two types of smokeless flares are:
Steam sparged flare
Air assisted flare
The flare system shall be any one or combination of the following:
HP flare system
LP flare system
The general philosophy for LP and HP flare system in an Oil & Gas facility are:
1) Relieving devices with set pressure <= 10 barg are connected to the LP flare system.
2) Relieving devices with set pressure > 10 barg are connected to the HP flare system.
Relief devices can not relieve the design relief rate, when the back pressure is more than
certain limit, as stated below:
1) Back pressure for conventional safety valves shall be < 10% of set pressure.
2) Back pressure for balanced bellows safety valves shall be < 50% of set pressure.
3) Back pressure for pilot operated safety valves shall be < 90% of set pressure.
18.1
ELEVATED FLARE
Elevated flares consists of a stack (guyed, self-supporting or with a supporting structure) with a
burner tip, pilot burners and associated fuel system, igniter and miscellaneous auxiliaries.
Recommended distances of the flare stack from other equipments are:
1) >200 ft (61 m) to a separator/floating roof tank which could be ignited by an occasional
falling spark
2) > 400 ft (122 m) to any other equipment
3) > 500 ft (152 m) to any equipment having an elevation within 125-150 ft of the elevation of
the flare tip
Flare stack diameter is generally sized on a velocity basis, although pressure drop should be
checked. Diameter of the flare stack is to be not less than that of the flare tip. Flare tip shall be
sized for Mach 0.2 to 0.4 at max emergency load. The higher limit is to be used with fuels with
high burning velocities. For example, small amounts of H2 in a hydrocarbon fuel increases the
burning velocity and permits higher gas velocities in the tip without flame blow off. Minimum
velocity at full capacity should be 100 fps. Too low a tip velocity can actually cause heat and
corrosion damage.
Flare stack height is generally designed based on the radiant heat intensity generated by the
flame. A check should also be made on the max ground concentration level if toxic and
corrosive pollutants are present in the stream.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 58 of 87
Some heat intensity levels which have been employed in design are:
1) 3.16 kW/m (1000 Btu/h ft): storage tanks containing volatile materials and control rooms
or areas where personnel must remain at their posts.
2) 4.73 kW/m (1500 Btu/h ft): used by some companies for acceptable intensity in operating
areas where operators wearing normal clothing were likely to perform their duties and
where general area radiant shielding exists.
3) 6.31 kW/m (2000 Btu/h ft): in open areas where no shelter is available and only escape is
required.
4) 15.77 kW/m (5000 Btu/h ft): on structures and in operating areas where operators are not
likely to perform their duties and where shelter from radiant heat is available, e.g. behind
equipment.
Elevated Flare Flash Back Protection
Protection shall be provided against flash back from the flare tip to the flare header and
blowdown drum. For this purpose gas purging in connection with sealing devices are
recommended. Two methods of sealing are : (a) Molecular seal, (b) Liquid seal
Liquid Seal
A liquid seal is often provided in the flare stack either at the base of the stack itself or in a
separate seal drum. The preferred liquid is water although oil may also be used. In sizing a
seal drum, first determine the maximum pressure on the flare side. The minimum seal length
provided by the water discharge pipe is then specified for 200% of maximum operating
pressure of the drum or 10 ft, whichever is greater.
The drum diameter is set to provide sufficient vapor/liquid disengaging area, with the vapor
velocity V limited to Vc.
(D d )
V = 0.157
d
V = velocity (ft/s) D = density of entrained liquid, (lb/ft)
The height of vapor space in a vertical drum should be approx 2 - 3 times the drum diameter. If
a horizontal vessel is used a minimum dia of 3 ft is recommended for this purpose. A seal drum
design pressure of 50 psig is suggested to protect the drum from pressure surges, as with the
blowdown drum. However if continuous gas purging is not used, the seal drum design pressure
should be 150 psig in order to withstand the overpressure due to explosion. Gunite lining is
normally used for corrosion control.
Pipe Seal
Pipe seal usually consisting of a loop or trap built into the base of the flare stack or the flare
line inlet connection, are designed to be filled with water to prevent flashback into the flare
headers. The slop of the inlet is designed to provide a volume of water below the normal
sealing water level equivalent to the volume of 10 ft of the inlet line. Although the 10 ft volume
basis is arbitrary, it should provide adequate sealing against flashback. Depth of the water seal
is usually held to about 12 in since greater depths can cause gas pulsations. Seal water level is
maintained by a continuous flow of water at about 20 gpm.
Smokeless Operation
A diluents such as steam, air or water may be used to improve flame characteristics i.e. reduce
smoke and luminosity. Steam is preferred to compressed air because of cost. Steam can be
injected into the flare stack below the burner tip. Steam required for smokeless operation can
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 59 of 87
WS = WHC 0.68
M = Gas MW
When unsaturated hydrocarbons are present (which are more difficult to burn) following steam
rates shall be used :
Steam
rate (kg
steam /
kg gas)
0.25
For no spoke
operation
---
For reduced
luminosity
---
10
0.35
---
---
20
0.6
---
---
30
0.75
---
---
35
0.88
1.55
---
40
1.75
2.75
50
1.2
2.15
3.2
60
1.45
2.55
3.65
65
1.55
2.75
3.85
% unsaturates
No smoke operation
Smokeless operation is usually specified for only 10 - 30% of the max flare load.
Ignition
The number of pilot units (with remote ignition) required per flare is largely a function of wind
conditions. If the prevailing wind is strong, then one pilot unit may be adequate. Standard flare
tip includes three pilot units uniformly distributed around the top of the flare.
Smokeless operation
1) The stack itself will be of carbon steel. The foot of the stack (below the main seal) is
cement filled
2) The bottom of the stack and inlet are to be gunite-lined from the cement fill to a height of 6'0" above
the sealing water level. Dip leg and bottom of flare stack are to be insulated
and steam traced to a
height of 6'-0" above sealing water level (to vaporize condensed
hydrocarbons)
3) The top 10' of flare stack and pilot assembly to be type SS-310. If steam is injected in to the
flare stack, below the burner tip, the entire tip assembly will be of heat-resisting alloy
4) Sometimes, when a gas stream has a continuous high level of H2S, there is an economic
advantage to providing a separate flare, header and seal drum for the H2S rich stream
Noise
The roar of combustion is the one source of noise that cannot be avoided with elevated flares.
At moderate release rates this source generally does not cause problem, but if the roar
remains objectionable, the moderate (and most frequent) release can be burned in a ground
flare, keeping the elevated flare for emergencies.
In smokeless flares, generally steam is used which increases the combustion roar. In this case
the noise can be reduced to some extent by using a multipoint steam nozzle.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 60 of 87
18.2
GROUND FLARE
Ground flare is similar to an elevated flare, but without any supporting structure. It requires 76
152 m (250 - 500 ft) sterile distance. A ground flare may be either single tip or multi-jet type.
The former is no longer recommended. All new installations are multi-jet type. A multi-jet
ground flare is designed for burning gas at nearly atmospheric pressure. The gas is supplied
by a manifold of parallel burner lines which lead to a number of vertically discharging 1"
diameter burners. Solid rods acting as flame holders are mounted above the outlet of the
burners parallel to the burner lines, their main function being to prevent the flame from riding
up to the top of flare.
The flames are surrounded by a refractory lined stack. The stack acts as a chimney, drawing
air in to the combustion zone. The stack in turn is surrounded by a windbreak to reduce wind
effects and luminosity at ground level.
The use of a ground flare requires a clear distance of about 500 ft from any processing unit or
storage facility and not less than 200 ft from property line fence.
Design Criteria
Large flow rates cannot be treated by a ground flare; John Zinc suggests a max. flow rate of
40000 - 60000 lb/h. To determine the diameter of a ground flare, the ESSO formula for multijet
flares can be used :
D = 0.826 Q
D = Stack dia (ft)
For stack diameters up to 25 ft, the stack length is usually made 32 ft. For larger diameters, the
stack height should be suitable increased. The bottom of the stack is elevated to allow air for
combustion to enter. Minimum clearance between bottom of stack and grade is either 6 ft or
0.3 D, whichever is greater.
Sealing Device
The same for elevated flare can be used. A special sealing device "two stage water seal for
use with integrated flare system" has also been developed for a combined elevated and ground
flare. The base of the elevated flare contains a seal drum with two dip legs. Gas is first sent
through the lower seal to ground flare. Up to the capacity of the ground flare, all gas is sent to
the ground flare, with increasing gas flows handled by varying the number of burners
operating. As the gas flow increases further the upper seal is broken and gas is sent to the
elevated flare.
Smokeless operation
Smokeless flaring - both ground & elevated flares can be operated under smokeless condition
by suitable injection of steam or air. However smokeless firing under all conditions is
uneconomic and smokeless operation is generally specified only for 10-30% of the maximum
flare load. Smoke production, depending upon MW and gas flow can be reduced in multi-jet
ground flares with steam or water injection. However a multi-jet ground flare is less smoky than
an elevated flare without steam injection.
Material of construction
Ground flares are generally constructed of fire brick or of a CS cylinder lined with about 8" of
refractory material.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 61 of 87
Noise
From available data and consequent extrapolations, it has been found that, in the absence of
combustion- drive pulsation, the grade level flare is likely to be about 10 dB quitter at the same
load than an elevated flare.
18.3
VENT STACK
If vapors from pressure relief valves may be directly discharged to atm, this can be done by
simply piping to a safe location (called as vent pipe) or by collecting these vapors via laterals
and headers and disposing of them together with other valve emissions to the atmosphere
through a common stack (called as vent stack).
Air dilution
The mass flux (in lb/h) when discharged directly to the atm may be expressed by the following
equation:
W
= 0.264 X / D
Wo
Where:X = distance from the jet nozzle (vent pipe end) (ft)
D = vent pipe (nozzle dia) (ft)
W = weight flow rate of vapor-air mixture at the distance X from the vent pipe
end (lb/h)
Wo = weight flow rate of the vapors discharged by the vent pipe (lb/h)
Based on this info, hydrocarbon vapors discharging from a safety valve into the atmosphere
will entrain sufficient air to be below their LEL at a distance approx 120 tail pipe diameters
away from the end of the vent. In order to supply the energy requirement for this amount of
mixing, it is necessary that the velocity of the discharged hydrocarbon vapors be more than
152 m/s as they leave the tail-pipe. When reduction of pipe size is required to maintain 152 m/s
or higher outlet velocity, the pipe end should be reduced for a length equal to 3 pipe diameters.
Location of vent stacks
1) At least 1.83 m (6 ft) above the highest adjacent structure or tower.
2) At least 3.66 m (12 ft) above the highest adjacent platform.
3) At least 4.57 m (15 ft) above grade.
4) At least 15.2 m (50 ft) or 120 pipe diameters, whichever is greater, away from the nearest
platform structure or tower when located at an elevation lower than the platform, structure
or tower.
5) At least 30.5 m (100 ft) or 120 pipe diameters, whichever is greater, away from the tops of
flue gas stacks or other ignition sources regardless of the atmospheric vent elevation.
Design Criteria
High discharge velocities are desirable in order to obtain good hydrocarbon-air mixing and
reach a concentration below 3% by weight within a reasonable distance from the stack.
Tip Diameter
The tip dia. is usually sized for an exit velocity of 500 fps at the max relief rate. Sonic velocity is
to be avoided.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 62 of 87
DO 2
4
WMAX
3600 d V U O MAX
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 63 of 87
18.4
Fluid
Phase
Gas
Phase
Two
Phase
TOTAL Spec
GS ECP 103
Service
SAIPEM Standard
Mach No.
V
(kg/m s)
Mach No.
V
(kg/m s)
0.7
0.5
Headers
0.7
0.7
0.25
< 50 000
Gci = 12.6 Po
M
((2 Z ) 1) To
N = 4 f
Le
D
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 64 of 87
section with dia D and resistance factor N can be converted to an equivalent diameter De
having a line resistance factor Ne equal to
D
Ne = N e
D
Any diameter may be selected as equivalent diameter (De), but the calculation of mass velocity
(G and Gci) must be referred to this diameter De.
The total resistance factor Nt of the entire header, referred to the equivalent diameter, De is the
sum of equivalent resistance factors Ne of the various sections of the header.
The pressure drop of the header can be found using Lappel chart with Nt and G/Gci calculated
with equivalent diameter De.
Compressible fluids & flashing liquids
For the sizing of a blow down header carrying saturated liquids flashing as the pressure drops,
the following equation may be used:
(N Va / 2) + V
P = P1 P2 = 7.26 w 2
D4
Where P1 = inlet pressure (psia)
P2 = outlet pressure (psia)
w = mass flow rate (liquid + gas) (lb/s)
N = number of velocity heads, as defined in Lapple method
Va = average specific volume (ft/lb)
D = pipe diameter (inch)
V = V2 V1 = increase in specific volume of fluid between inlet and outlet,
(ft/lb)
Suggested velocities and sonic flow
Sonic velocity may be calculated from the following formula (valid for ideal gas):
VS = 223
(Z k T )
M
Where Vs = sonic velocity (ft/s)
K = Cp/Cv at fluid temperature
MW = molecular weight
T = fluid temperature (R)
Z = compressibility factor (approx. 1 at low pressure)
Even if sufficient pressure is available, depending on the lowest set pressure of relief valve in
the system, it is not desirable to size the header so that the flow becomes sonic (high noise
level and pipe vibrations).
To prevent this, the value for the ratio (P2/Po) / (G/Gci) must be larger than 0.6 and preferable
not less than 1, P2 being the pressure in the downstream vessel.
The recommended range of values for flare headers and other piping when pressure drop is
not controlling are listed below:
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 65 of 87
Flare System
18.5
(P2/Po) / (G/Gci)
V / Vs
1 to 2
0.25 to 0.65
Flare headers
1 to 2
0.25 to 0.65
Flare stacks
2 to 3
0.20 to 0.40
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 66 of 87
Flare Gas
Relief Gas
Flare Gas
Relief Gas
FLARE KO
DRUM
FLARE KO DRUM
(Single pass)
Flare Gas
Relief Gas
Flare Gas
Relief Gas
FLARE KO DRUM
(Tw o pass)
FLARE KO DRUM
(Tw o pass)
15) For most of the oil & gas facility, high high level in flare KO drum initiates plant shutdown
system. Therefore, KO drum sizing should be done carefully to hold the emergency liquid
relief. KO drums are provided with the following equipment / accessories:
16) KO drum pump to evacuate the liquid for further processing. The KO drum pump shall be
sized to evacuate the liquid collected during emergency relief in 20 30 minutes.
17) KO drums are sometimes provided with boot to enhance the suction head to avoid NPSH
problem for the KO drum pump. The reason for providing boot are:
Flare headers are routed with slop towards the KO drum, and hence the KO drum is
located at ground level or lowest level in the plant. There would not be sufficient liquid
head for the pump for safe operation. To avoid cavitation in the pump and to boost the
NPSH, boots are provided from which the pump suction is taken.
The liquid collected in the KO drum are mostly at bubble point or flashing nature. This
creates cavitation problem in the pump. By adding a boot of sufficient height, the
suction static head and NPSH can be improved.
For satisfactory performance of any pump, the available NPSH should be >1 meter. In
cases, where the NPSH is lower than 1, which is a typical case for KO drum pump,
special pumps like canned pumps are selected.
18) KO drums are also provided with internal / external heaters. The reasons for the heater are:
To keep the liquid warm, to avoid freezing of the liquid or to reduce the viscosity of the
liquid.
Internal heaters are sometimes used to vaporize the light liquid collected in the KO
drum, so that they can be flared. For such cases pumps may not be provided for the
KO drum.
Generally electrical heaters are used in flare KO drum due to the remote location in the
plant and their rare operational requirement.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 67 of 87
19) Following procedure from API 521 shall be used for flare KO drum sizing:
Liquid particles will separate when:
the residence time of the vapour or gas is equal to or greater than the time required to
travel the available vertical height at the dropout velocity of the liquid particles
the vertical gas velocity is sufficiently low to permit the liquid dropout to fall
The dropout velocity of a particle in a stream is calculated using the following equation:
U C = 1.15 g D
Where Uc
g
D
l
v
C
( l v )
v C
v D 3 ( l v )
2
[ (
)]
[ (
- 0.0028 Log C Re 2
)]
[ (
+ 0.1225 Log C Re 2
)]
[ (
- 1.136 Log C Re 2
(The drag coefficient (C) can also be taken from Figure-20 on page 64 in API 521)
The liquid dropout time is calculated as:
= hv / U c
Where = dropout time (sec)
hv = vertical height available above liquid level in KO drum (m)
The actual vapour velocity is calculated as:
Uv =
Qv / 3600
( Av N b )
)]
+ 2.8091)
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 68 of 87
Lmin = U v N b
The selected KO drum length should be > Lmin
(Otherwise the above calculation to be repeated until the required KO drum length has
been arrived)
According to in-house KO sizing criteria, the gas flow area of KO drum shall meet one of
the following requirements of max:
max =
Q *max
Av min
Q *max = Qv max
v
l v
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 69 of 87
28
0.002
0.006
0.034
0.128
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 70 of 87
Purge gas rate required to prevent vacuum conditions after a hot gas flaring, can be calculated
by the following formula :
G = 60 VO
(1 (Ta / T ))
t
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 71 of 87
19.
CONSUMERS
N2
HOT OIL
MAKEUP
TC
PC
TRIM
COOLER
SURGE TANK
FC
HOT OIL
SUPPLY PUMP
TC
FIRED
HEATER
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 72 of 87
20.
Relative Size
2.4
15
1.0
25
0.55
Soft Water
Makeup
H2SO4
DOSING
TANK
CHEMICAL
DOSING
TANK
CONSUMERS
ID FAN
CELL-1
CELL-2
CELL-3
SCREENS
BLOWDOWN
EMERGENCY CW
PPUMPS
COOLING WATER
CIRCULATION PUMPS
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 73 of 87
General consideration
1) Water circulation rates are generally 2-4 gpm/ft (81-162 lit / min / m) and air velocities are
usually (1.5-2.0 m/s)
2) Countercurrent induced draft towers are the most common. These towers are capable of
cooling to within 2F (1.1C) of the wet bulb temperature. Approach of 5-10F (2.8-5.5C) is
more common
3) Evaporation losses are about 1% by mass of the circulation rate for every 10F (5.5C) of
cooling. Drift losses are around 0.25% of the circulation rate. A blow down of about 3% of
the circulation rate is needed to prevent salt and chemical treatment buildup
4) Cooling tower water is received from the tower between 80-90 F (27-32 C) and should be
returned between 115-125 F (45-52 C) depending on the size of the tower. Seawater
should be return no higher than 110 F (43 C)
5) Cooling water systems shall be designed for the conditions specified in the data /
requisition sheet, and in no case shall be designed for a working pressure of less than 7
barg
6) Provision shall be made for complete venting and draining of the system.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 74 of 87
21.
REFRIGERATION SYSTEMS
1) A ton of refrigeration equals the removal of 12,000 Btu/h (12,700 kJ/h) of heat
2) For various refrigeration temperatures, the following are common refrigerants:
Temp (F)
Temp (C)
Refrigerant
0 to 50
-18 to -10
-50 to 0
-45 to -18
-150 to -50
-100 to -45
Ethane, Propane
3) Compression refrigeration with 100F condenser requires the following power @HP/ton at
various temperature levels:
1.24 at -6.7C;
1.75 at -17.8C;
3.1 at -40C; 5.2 at -62.2C
4) Below -62.2C, cascades of two or three refrigerants are used
5) In single stage compression, the compression ratio is limited to about 4
6) In multistage compression, economy is improved with inter-stage flashing and recycling,
so-called economizer operation
7) Absorption refrigeration (ammonia to -34.4C, lithium bromide to +7.2C) is economical
when waste steam is available at 12 psig or so
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 75 of 87
22.
COOLING
WATER
HOT WELL
CHILLER
UNIT
CONSUMERS
COLD WELL
=30%-40% of
vessel
diam eter
CHILLED WATER
TANK
BLOWDOWN
CHILLED WATER
PUMPS
CHILLED WATER
CIRCULATION PUMPS
General consideration
1) DM water is used as make-up water for the chilled water system
2) Chilled water supply temperature is approx 5C to 10C. Return temperature is 10C to
15C
3) The tank / pump / piping material of construction is Carbon Steel
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 76 of 87
23.
CONSUMERS
CHILLED BRINE
TANK
COOLING
WATER
CHILLER
UNIT
DRAIN
General consideration
1) 40% ethylene glycol solution is used as the brine solution
2) Chilled brine supply temperature is approx -15C to -5C. Return temperature is -10C to
0C
3) The tank / pump / piping material of construction is Carbon Steel and some times LTCS
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 77 of 87
24.
DM WATER SYSTEM
DM water is used as make up water for boiler feed water to generate steam. DM water is
some times used as Process water and diluents for acids and chemicals preparation.
DM WATER SYSTEM CONFIGURATION
ACTIVE CARBON
FILTER
SAND FILTER
SOFTENER
CATION
EXCHANGER
WEAK BASE
ANION
EXCHANGER
RAW
WATER
BLOWER
DEGASSER
BACK WASH
WATER
HCl
TANK
NaOH
TANK
DEGASSER PUMP
DRINKING
WATER
MIXED BED
EXCHANGER
STRONG BASE
ANION
EXCHANGER
DM WATER PACKAGE
DM WATER TANK
DM WATER
CONSUMERS
DM WATER PUMPS
HCl
TANK
ACID DRAIN
NaOH
TANK
Characteristics
Total hardness as CaCO3 max. (mg/lit)
pH value
Oxygen as O2 max. (mg/lit)
Fe+Cu+Ni max. (mg/lit)
Total solids, alkalinity
Silica
Oil
Organic matter
40 bar
60 bar
2
0.5
8.5 9.5
0.02
0.01
--0.02
----(1)
(1)
---------
Fire Tube
Boiler
<25 bar
2
(1)
----(1)
-----
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 78 of 87
25.
STEAM SYSTEM
Boilers generate steam either at saturated or at superheated conditions by burning the fuel.
Steam is used for power generation, heating, stripping, atomizing and is used as driving force
for turbines. The fuels used are (1) Solid fuels such as coal; (2) Liquid fuels such as fuel oil,
LSHS, diesel, naphtha, etc; (3) gaseous fuels such as hydrogen, natural gas, hydrocarbon
gas, etc.
The two types of boilers are (1) Fire tube boilers and (2) Water tube boilers.
Fire tube boilers: Water is boiled in a vessel inside the boiler and hot flue gas passes through
the tubes immersed in water.
Water tube boilers: Hot flue gas passes through the shell side and water passes through the
tubes from an overhead drum.
Boiler is supplied by vendors as a package which consists of:
Main boiler system with boiler/steam control system
Boiler Feed Water (BFW) system and BFW pumps
Fuel handling system & burner management system
Combustion air system & atomization system
Economizer for heating BFW using flue gas (optional)
Air pre-heater using flue gas (optional)
Boiler stack & flue gas monitoring system
Chemical dosing system
ATM
TC
PC
BOILER
CHEMICAL
DOSING
TANKS &
PUMPS
LP STEAM
CONSUMERS
LP STEAM
DESUPERHEATER
DM WATER
MAKEUP
PC
VENT STACK
DEAERATOR
LC
LLP
STEAM
HP/MP CONDENSATE
ATM
PC
PC
PC
FLASH VESSEL
LC
FUEL OIL
CONDENSATE VESSEL
BOILER
BLOWDOWN
CONDENSATE PUMPS
BFW PUMPS
CONDENSATE PUMPS
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 79 of 87
Characteristics
Total hardness as CaCO3 max. (mg/lit)
pH value
Oxygen as O2 max. (mg/lit)
Fe+Cu+Ni max. (mg/lit)
Total solids, alkalinity
Silica
Oil
Organic matter
40 bar
60 bar
2
0.5
8.5 9.5
0.02
0.01
--0.02
----(1)
(1)
---------
Fire Tube
Boiler
<25 bar
2
(1)
----(1)
-----
1.
2.
3.
4.
5.
6.
7.
8.
9.
20 bar
40 bar
60 bar
Fire Tube
Boiler
<25 bar
50-100
30-70
20-50
50-100
300
150
60
350
700
500
300
1200
75
30-50
0.1-1.0
--200
3000
40
20-40
0.1-0.5
--50
2000
20
15-30
0.05-0.3
----1200
<4
30-70
0.1-1.0
--50
3500
Characteristics
Sodium phosphate in terms of CaCO3
max. (mg/lit)
Caustic alkalinity in terms of CaCO3
max. (mg/lit)
Total alkalinity in terms of CaCO3 max.
(mg/lit)
Silica as SO2 max. (mg/lit)
Sodium sulphate as Na2SO3 (mg/lit)
Hydrazine as N2H4 (mg/lit)
Chloride as Cl max (mg/lit)
Suspended solids max. (mg/lit)
Dissolved solids max. (mg/lit)
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 80 of 87
26.
Capacity (m/h)
Pressure (bar)
From
To
From
To
100
30000
0.1
100
12000
0.8
12
100
12000
12.0
700
100
2400
0.8
13
100
2200
0.8
24
Centrifugal
600
300000
0.1
450
PC
INSTRUMENT AIR
CONSUMERS
ATM
INSTRUMENT
AIR RECEIVER
AFTERFILTER
PC
SERVICE AIR
CONSUMERS
DRIER BEDS
E LE C T R IC
H EA T ER
E LE C T R IC
H EA T ER
ATM AIR
PLANT AIR
RECEIVER
PRE-FILTER
COOLING
WATER
AIR DRIER
PACKAGE
1) Unless otherwise specified, the instrument air pressure in the air supply piping shall be 7
barg under normal operation and never less than 4.2 barg for proper operation of the
instruments
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 81 of 87
2) To prevent condensation in the supply piping or in the instruments, the dew point of the air
at operating pressure shall always be at least 10C lower than the lowest expected
ambient temperature for the air system at any location
3) To reduce the load on the air drier, the air from the compressors shall be cooled to a
temperature of 10 C maximum above the cooling medium inlet temperature
4) The quantity of solids in instrument air shall be less than 0.1 g/m and the diameter of the
particles shall not be more than 3 mm
5) Safety/relief valves shall be provided when required by statutory regulations, and/or by the
relation between maximum compressor discharge pressure and the maximum allowable
working pressure of vessels and piping
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 82 of 87
27.
NITROGEN
BUFFER
VESSEL
PC
PC
PSA
NH3
CYLINDERS
NITROGEN
COOLER/SEPARATOR/RE
GENERATION HEATER
AIR RECEIVER
BOOSTER COMPRESSOR
B ED S
H E A T LE SS A IR
D R IER B E D S
ATM AIR
M O IS T UR E
SEP A R A T OR
COOLING
WATER
M O IST UR E
SE P A R A T O R
PC
NITROGEN
CONSUMERS
NITROGEN
RECEIVER
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 83 of 87
28.
INCINERATOR SYSTEM
Waste organic and inorganic liquids/gases which can not be sent to flare or other disposal
systems, also where there is no other disposal system is available, are disposed by
incinerator.
VENT STACK
WASTE ORGANIC
CHEMICAL
MAIN COMBUSTION
CHAMBER
WASTE
LIQUID DAY
TANK
POST
COMBUSTION
CHAMBER
AIR
BLOWER
FUEL OIL
DAY TANK
DUPLEX
FILTER
FUEL OIL
PUMP
FUEL OIL
HEATER
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 84 of 87
29.
UREA
TANK
ALUM
TANK
CLEAR EFFLUENT
STREAMS
NEUTRALISING
TANK
AERATION TANK
LOCAL EFFLUENT
SLUDGE DRYING BEDS
Na2SO3
TANK
SECONDARY
CLARIFIER
LIME DOSING TANK
ACID EFFLUENT
TREATED EFFLUENT TO
DISPOSAL
pHIC
FINAL TREATED
EFFLUENT TANK
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 85 of 87
6) Velocities of less than 0.3 m/s shall be avoided in order to prevent a premature separation
and consequent accumulation of oil/sediment within the drainage network.
7) The maximum effluent temperature within any drainage network shall not exceed 45 C.
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 86 of 87
30.
PROCESS CONTROLS
Vent to
Flare
FG / N2
PC
LC
FC
1
FC
FC
TC
Top Product /
Distillate
FEED
TC
50
LC
MP Steam
FC
MP Cond.
Bottom s
Vent to
Flare
FC
PC
Process Gas to
Com pressor or FG
LC
LC
FC
Water
FC
Oil
Doc. N: WIP-SIPS-PCS-001
Rev.: A
Date: 08/02/08
Page 87 of 87
31.
REFERENCE
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)