Total redundancy
CPU, Power, I/O, Network
Redundancy / MasterLogic-100R
Experion PKS
Experion PKS
MasterLogic - 100R
CPU Redundancg
GM2 - FDIA
GM2 - FDIA
I/O Redundancy
Redundant I/O and Switched I/O (non redundant) System
Configuration
Optional : Input Triplexing to improve reliability (2 out of 3 voting)
Fault detection by output feedback and automatic power
shutdown at the faulted unit
Redundancy I/O
Switched I/O
(non-redundant)
Redundancy I/O
GM2-FRIC
GM2-B04E
GM2-B08E
GM2-B12E
GM2-FRIC
GM2-B08E
GM2-B12E
GM2-FRIC
GM2-B04E
GM2-B08E
GM2-B12E
Snet
Fast Ethernet
G3L - RBRA
GM3-BO8R
G3L - RBRA
GM3-BO8R
G3L - RBRA
GM3-BO8R
G3L - RBRA
GM3-BO8R
G3L - RBRA
GM3-BO8R
G3L - RBRA
GM3-BO8R
Redundancy / MasterLogic-100R
Features
Scalable & Modular
Total redundancy
l Redundant CPU Bumpless switching occurs when the master CPU fails and system control is transferred to the standby CPU without
interrupting the operation of the process under control.
Redundant I/O Both the master and standby CPU control I/Os simultaneously. Synchronization between master and standby CPU ensures
data & program consistency.
Optional input triplexing for enhanced reliability - Both master and standby CPU compare input data read from redundant I/O base and an
additional switched I/O base and does a 2 out of 3 voting.
Redundant Network
- with Experion PKS / SCADA / HMI
- I/O interface cables
General Specifications
No.
Item
Specification
Operating temperature
0 ~ 55
Standard
Storage temperature
-25 ~ 70
Operating Humidity
5 ~ 95%RH, non-condensing
Storage humidity
5 ~ 95%RH, non-condensing
Vibration
Occasional vibration
Frequency
Acceleration
Amplitude
Sweep count
10 f 57 Hz
0.075 mm
10 times in each
57 f
9.8
IEC61131-2
direction for X, Y, Z
150 Hz
{1G}
Continuous vibration
Shocks
Frequency
Acceleration
Amplitude
10 f 57 Hz
0.035 mm
57 f 150 Hz
4.9 {0.5G}
IEC61131-2
Noise immunity
Square wave
impulse noise
1,500 V
Electrostatic
discharge
Radiated
electromagnetic
field
Fast transient
burst noise
IEC61131-2, IEC61000-4-3
Severity Level
All power
modules
Digital I/Os
( Ue 24 V)
Voltage
2 kV
1 kV
0.25 kV
Atmosphere
Up to 2,000m
10
Pollution degree
2 or lower
11
Cooling method
Self-cooling
IEC61131-2, IEC61000-4-4
Redundancy / MasterLogic-100R
Performance Specifications
Item
Description
Control Method
Program Language
IL (Instruction List)
SFC (Sequential Function Chart)
Operator
Number of
Standard Function
Instructions
13
Operator
0.12 s/instruction
Processing
Standard Function
0.12 s/step
Speed
0.12 s/step
I/O Points
Max. 256Kbyte (Stand-by operation is delayed according to its used size: 2ms/1Kbyte)
Timer
Counter
Operation Mode
Data Retention
180
Scan (Cyclic)
180
Time-driven Task
32
Program
16
Types
Internal Task
16
Initialization Task
2 (_INIT, _H_INIT)
Error Task
1 (_ERR_SYS)
Self-diagnostic Function
Restart Mode
16
Redundancy System
Redundancy / MasterLogic-100R
GMR-B08E
GMR-B12E
GM2-B04E
GM2-B08E
GM2-B12E
GM3-B08R
GM3-B08S
Communication Modules
FEnet
G3L-EUTB
G3L-EUFB
G3L-EU5B
Snet I/F module
G3L-CUEA
Max I/O: 7,680 points, Program Memory: 512KB, Data Memory: 512KB
Max I/O: 7,680 points, Program Memory: 2MB, Data Memory: 512KB
CPU Interface module
2-slot for I/O interface & communication modules (total 4 slots)
4-slot for I/O interface & communication modules (total 6 slots)
A+B
On
On
Off
Off
Key
A+B
A SEL
B SEL
A SEL
Off
Off
On
Off
LED
B SEL
Off
Off
Off
On
CPU-A
On
Off
On
Off
CPU-B
Off
On
Off
On
Operation Setup
Redundant operation
Single operation (CPU-A)
Single operation(CPU-B)
Operation
Mode
Redundant operation mode (Master: CPU-A)
Redundant operation mode (Master: CPU-B)
Single operation (CPU-A)
Single operation (CPU-B)
POWER
I/F or COMM
I/F or COMM
I/F or COMM
CPU
I/F or COMM
CPU
DIFE
I/F or COMM
I/F or COMM
5
I/O
I/O
I/O
I/O
GM2 - FRIC
FDIA
4
GM2 - FRIC
FDIA
3
I/O
POWER
CPU
2
I/O
CPU
DIFE
FDIA
I/O
I/O
I/O
I/O
Terminal
Resistance
Slot 0
POWER
I/O
POWER
FRIC
I/O
FRIC
FDIA
POWER
POWER
COMM
I/O
CPU
FDIA
DIFE
1
I/O
I/O
POWER
Terminal
Resistance
I/O
CPU
FDIA
FDIA
POWER
POWER
Terminal
Resistance
Slot 0
B side
I/F or COMM
POWER
I/F or COMM
A side
POWER
I/F or COMM
I/F or COMM
CPU
CPU
DIFE
B side
I/F or COMM
POWER
I/F or COMM
A side
I/O
I/O
I/O
I/O
I/O
FRIC
I/O
Slot 0
I/O
I/O
POWER
FRIC
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
Slot 0
I/O
I/O
I/O
I/O
POWER
FRIC
FRIC
I/O
I/O
POWER
POWER
Slot 0
I/O
Terminal
Resistance
Terminal
Resistance
Redundancy / MasterLogic-100R
System Configuration
Max No. of Base Boards: 16 (Base number: 0 ~ 15)
Max No. of I/O Modules: 120modules
Max No. of I/O Points: 3,840points (with 32-point modules)
7,680points (with 64-point modules)
32,000points (in Network System Configuration)
I/O
I/O
I/O
I/O
POWER
FDIA
Expansion Cable
G2C-E
FRIC
I/O
I/O
COMM
I/O
I/O
Base Number
FRIC
I/O
I/O
I/O
I/O
I/O
FRIC
COMM
CPU
COMM
CPU
FDIA
I/O
POWER
POWER
(GMR-B08E)
Slot 0
Switched
I/O
Base #2
I/O
I/O
POWER
(GMR-B08E)
POWER
Slot 0
Switched
I/O
Base #1
DIFE
COMM
COMM
FRIC
(GMR-B04M)
COMM
CPU
Redundant
Base #0
POWER
I/O
I/O
I/O
I/O
Terminal
resistance
FRIC
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
(GM2-B08E)
I/O
Redundant
I/O
Base( A) #4
I/O
Slot 0
I/O
(GM2-B08E)
POWER
Redundant
I/O
Base( A) #3
POWER
Slot 0
FRIC
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
FRIC
(GM2-B08E)
I/O
Redundant
I/O
Base( A) #4
POWER
Slot 0
I/O
(GM2-B08E)
I/O
Redundant
I/O
Base( A) #3
POWER
Slot 0
FRIC
Terminal
Resistance
Terminal
resistance
input is needed
Network A
Network B
Master Logic - 100R
Redundancy
G3L-FURA
G3L-FURA
GM3-RBRA
GM2-B08R
GM3-RBRA
GM2-B08R
GM3-RBRA
GM2-B08R
GM3-RBRA
GM2-B08R
GM3-RBRA
GM2-B08R
GM3-RBRA
GM2-B08R
GM3-RBRA
GM2-B08R
Network A & B
A System is connected to
B System is connected to
Station Number
Network Redundancy
Separated
A Network only
B Network only
A system = N
B system = N (Equal to A)
Cable Redundancy
Concurrent
A + B Netwrok
B + A Network
A system = N
B system = N+1
Connected
internally
Network A
Network Redundancy
A System
B System
Network B
POWER
CPU
DIFE
CPU
POWER
G3L-RBRA (Slave)
I/O
I/O
I/O
I/O
I/O
I/O
POWER
POWER
I/O
I/O
I/O
I/O
I/O
I/O
POWER
POWER
G3L-RBRA (Slave)
I/O
I/O
I/O
I/O
I/O
I/O
Cable Redundancy
GM3-B08R
A System
B System
POWER
CPU
DIFE
CPU
POWER
G3L-RBRA (Master)
I/O
I/O
I/O
I/O
I/O
I/O
POWER
POWER
I/O
I/O
I/O
I/O
I/O
I/O
POWER
POWER
G3L-RBRA (Slave)
I/O
I/O
I/O
I/O
I/O
I/O
I/O
POWER
GM3-B08R
POWER
I/O
POWER
POWER
GM3-B08R
GM3-B08S
* Only digital I/O, analog I/O, TC, RTD modules can be installed in remote I/O base. PID, LPCA & HSC modules shall be installed
only in switched I/O or redundant I/O base.
* Remote I/O base [GM3-B08R] can be further extended up to 3 stages using GM3-B08S I/O base (see diagram)
* Max # of remote I/O stations that can be connected to a remote I/O driver module G3L-FURA depends on the I/O configuration in
the remote I/O base. Each G3L-FURA module can be configured for a max 32 contiguous block of output (DO,AO) modules, 32
contiguous block of input modules (AI, DI, TC, RTD) (receive). The following table shows various combinations:
Specifications
Item
Transmission method
Max. distance
Driver module
Receiver module
Max. expansion stage number
Current Consumption
I/F module
Differential Transmission
100m (total length of CH1 plus Ch2)
GM2-FDIA
GM2-FRIC
8 per driver module
GM2-FDIA: 500mA, GM2-FRIC: 600mA
Remark
Main base
Expansion base
1MLR-PA1A
I/F or COMM
I/F or COMM
I/F or COMM
1MLR-PA1A
1MLR-PA1A(B)
I/F or COMM
B side
1MLR-PA1A(A)
I/F or COMM
I/F or COMM
1MLR-PA1A
I/F or COMM
A side
1MLR-PA1A
I/F or COMM
I/F or COMM
1MLR-PA1A
1MLR-PA1A(B)
I/F or COMM
B side
1MLR-PA1A(A)
I/F or COMM
1MLR-PA1A
A side
I/F or COMM
GMR-B02M
Operation S/W
Base number setting S/W
END S/W
Operation LED
Failure LED
Input/Output Module
Features
16-, 32-, and 64-point I/O modules
Photocoupler insulation
Operation check by LED display
Terminal and connector type
DC Input
Part number
G3I-D22A
Input point
16points
G3I-D22C
AC Input
G3I-D24A
G3I-D28A
G3I-A12A
G3I-A14A
G3I-A24A
32points
64points
16points
32points
32points
DC 12/24V
5/11mA
AC 100~120V (50/60Hz)
On voltage/current
9.5V/4mA or more
AC 80V/6mA or more
AC 150V/4.5mA or more
Off voltage/current
DC 6V/1.0mA or less
AC 30V/3mA or less
AC 50V/3.0mA or less
Response time
Off -> On
10ms or less
On -> Off
10ms or less
3/7mA
15ms or less
25ms or less
Common
8points/COM
1point/COM
8points/COM
32points/COM
8points/COM
1point/COM
5points/COM
20points/COM
Operating indicator
8points/COM
8points/COM
5points/COM
LED
Insulation method
Current consumption (DC5V)
AC 200~240V (50/60Hz)
11mA (AC110V/60Hz)
Photocoupler insulation
70mA
140mA
150mA
70mA
140mA
140mA
G3I-A12A
G3I-D22C
G3I-A14A
G3I-D24A
G3I-A24A
G3I-D28A
Input/Output Module
Specifications for Output modules
Output type
Relay output
Part number
G3Q-RY2A G3Q-RY4A
G3Q-TR2A
G3Q-TR4A/B
G3Q-TR8A/B
G3Q-SS2A
G3Q-SS4A
Output point
16points
16points
32points
64points
16points
32points
DC 12/24V, AC110/220V
Rated load
1point
2A
1A
2A
0.5A
0.1A
2A
current
1common
8A/COM
5A/COM
5A/COM
3A/COM
3A/COM, 2A/COM
5A/COM
Response
Off -> On
10ms or less
2ms or less
time
On -> Off
12ms or less
2ms or less
Common
32points
8points/COM
Transistor output
Triac output
DC 12/24V
8points/COM
16points/COM
Operating indicator
AC 100~240V (50/60Hz)
1A
0.5cycle+1ms or less
0.5cycle+1ms or less
32points/COM
8points/COM
LED
Insulation method
Photocoupler
Surge absorber
Varistor
110mA
220mA
DC 24V
Clamp diode
120mA
220mA, 280mA
Varistor, CR absorber
300mA, 280mA
370mA
690mA
G3Q-RY4A
G3Q-TR2A
G3Q-TR8A/8B
G3Q-SS2A
G3Q-SS4A
G3Q-TR4A/4B
G3L-EUTB
G3L-EUFB*1)
G3L-EU5B
Network
10BASE-5, AUI
Support protocol
TCP/IP, UDP/IP
Service
Command service
Application
Communication data
Number of channels
16 channels
Usage
Communication between MasterLogic PLC and other devices (PC), High-speed link between MasterLogic PLCs
Rnet Module
Features
Transmission speed: 1Mbps, transmission distance: 750m (Electric)
High-speed link capacity: Max. 61,440 points
Convenient to configure various multi-drop network systems with remote I/O modules
Specifications
Item
Transmission speed
1Mbps
Encoding type
Manchester Biphase-L
Max. 750m
Max. 5.25km
( 6 repeaters)
Transmission medium
Number of nodes
64
Communication method
High-speed link
64 blocks
60 words
1Mbps
Cable
3km
Function of signal,
Regeneration,
regeneration
Reshaping
CRC 16
Specifications
Optical cable
Terminal resistance
110
Operation Mode
Operation Mode
Remark
SoftMaster-100R mode
Dedicated protocol
User-defined protocol
Test mode
Self-diagnosis
Specifications
Item
G3L-CUEA
Interface
Comm. Mode
Data form
RS-232C, RS-422/485
Dedicated
SoftMaster-100R
Program download, upload and remote control using SoftMaster protocol (RS-232C, 1:1)
User-defined
Communication using user-defined protocol by Frame Editor (Interface with other PLCs)
Start bit
1 *2)
Data bit
7 or 8 *2)
Stop bit
1*2) or 2
Parity bit
Channel selection
By mode switch
Synchronization
Asynchronous
Transmission speed
300/600/1,200/2,400/4,800/9,600/19,200/38,400/76,800 *1)
Network configuration
Modem communication
Transmission
RS-232C
RS-422/485
Diagnostic function
31)
500m
Loop-back test mode
* 1) RS-232C: 300~38,400bps, RS-422/485: 300~76,800bps, In case of MODBUS communication, baud rate is 2,400~38,400bps
* 2) Default value
Specifications
Item
Analog Input
G3F-AD4A
G3F-AD3A
G3F-AD4B
DC -5~5V
DC -1~5V
DC 1~5V
DC 0~10V
DC 1~5V
Current
DC -20~20mA
DC 4~20mA
Voltage/Current select
Voltage
Digital output
Resolution
Program
0~16,000 -8,000~8,000
0~4,000
DC 1~5V
1.0mV (1/4,000)
0.25mV (1/1,6000)
DC 0~10V
2.5mV (1/4,000)
DC -5~5V
0.625mV (1/16,000)
DC -10~10V
1.25mV (1/16,000)
DC -20~20mA
2.5
DC 4~20mA
(1/16,000)
Accuracy
(1/4,000)
0.5% (Full scale)
DC 4~20mA
3ms/Ch
Voltage
5ms/Ch
0~16,000 -8,000~8,000
(1/16,000)
0.3% at 25
3ms/Ch
15V
Current
25mA
16 Channels
8 Channels
Offset/gain
Available
Not available
Insulation method
Between input termical and PLC power supply: Photocoupler, Between channels: No insulation
Current consumption
670mA
Configuration
500mA
16 Channels
540mA
Specifications
Item
G3F-DA4V *
Digital Input
Analog Output
DC -10~10V
DC 0~10V
DC -5~5V
Resolution
Output Range
Accuracy
G3F-DA3V
~ 1
~ 1
Resolution (1/16,000)
Output Range
Resolution(1/4,000)
DC -5~5V
0.625mV
DC -10~10V
2.5mV
DC 10~10V
1.25mV
0.5%
15ms/16Ch
+15V
16 Channels
8 Channels
Offset/gain
Available
Not available
Insulation
Between output terminal and PLC power supply: Photocoupler, Between channels: No insulation
Current consumption
200mA
600mA
15ms/8Ch
-10V
-5V
1V
Gain
0V
0V
3V
Configuration
(Full Scale)
Specifications
Item
G3F-DA4I
G3F-DA3I
Digital Input
(0~16,000, -8,000~8,000)
(0~4,000)
Analog Output
Resolution
Accuracy
or less
(1/16,000)
(1/4,000)
0.5% (Full Scale)
15ms/16Ch
DC 24mA
15ms/8Ch
16 Channels
8 Channels
Offset/gain
Available
Not available
Insulation
Between output terminal and PLC power supply: Photocoupler, Between channels: No insulation
DC 24V (220mA)
Current consumption
200mA
70mA
Example
Configuration
Offset
Gain
Output range
4mA
12mA
4~20mA
8mA
12mA
8~16mA
Thermocouple Module
Features
5 thermocouple types available (KS, JIS, ANSI, DIN, BS)
Automatic reference junction compensation
Open wire detection in every channel
Specifications
Item
G3F - TC4A
Thermocouple
TC input point
16 Channels
Digital output
BS specification
Measuring temperature
Measuring voltage
range ( )
range ( )
NiCr-Ni
NiCr-NiAl
-200.0~1200.0
-5,891~48,828
Fe-CuNi
-200.0~800.0
-7,890~45,498
NiCr-CuNi
-150.0~600.0
-7,279~45,085
Cu-CuNi
-200.0~400.0
-5,603~20,869
PtRh30-PtRh6
-400.0~1,800.0
786~13,585
PtRh13-Pt
0.0~1,750.0
0~21,006
PtRh-Pt
PtRh10-Pt
0.0~1,750.0
0~18,612
Automatic compensation
50ms/Channel
Every channel
Accuracy
Current consumption
DIN specification
450mA
Configuration
RTD Module
Features
Open wire detection in every channel
8-channel connection: G3F-RD3A
Specifications
Item
G3F-RD3A
Connectable RTD
Input channel
8 Channels
Digital output
Pt100: -200.0~600.0
JPt100: -200.0~600.0
(18.48~313.59 )
(17.14~317.28 )
Every channel
Accuracy
Current consumption
Value
Configuration
Specifications
Item
G3F-PIDB
32
PID constant
P value (P)
0.01~100.00(%)
I value (I)
0.0~3,000.0 (sec)
D value (D)
0.0~3,000.0 (sec)
0~16,000
0~16,000
0~16,000
0~16,000
Control operation
Control cycle
0.01~99.99s
Processing type
Output
LED Display
Points
32Points
DC12/24V
Voltage range
DC10.2~26.4V
0.1A/point, 1.5A/COM
Response time
2ms or less
Common
16 points/COM
RUN / STOP
RUN LED On
Current consumption
700mA
Specifications
Item
G3F-LPCA
Input
DC 4~20mA
DC 1~5V
Current
Voltage
0.5mV (1/8000)
(1/8000)
Insulation
Between input terminal and PLC power supply: Photocoupler, Between Channels: No insulation
Loop
Digital output
Output
Analog
Translstor output
Current output
DC 4~20mA
Resolution
1ms
1~100sec
(1/4000)
DC 24V
Voltage range
DC 20.4~26.4V
70mA
Response time
2ms
Common
4points/COM
Insulation
Between output terminal and PLC power supply: Photocoupler, Between loops: No insulation
Loop
Digital input
Accuracy
PID Specifications
Item
Common Specifications
Specifications
PID
P value (P)
constant
I value (I)
Item
Specifications
1~10000 (0.01~100.00%)
External
Voltage
DC 24V
Current
160mA
0~36000 (0.0~3600.0sec)
power supply
D value (D)
0~36000 (0.0~3600.0sec)
Current consumption
370mA
SV (Set Value)
Ripple voltage
50mVp-p or Iess
PV (Present Value)
MV (Manipulated Value)
0~4000
0~4000
Control loop
Control cycle
200ms
Processing type
Control operation
Specifications
Item
G3F-HSCA
Number of channel
Counter
Phase
input
Level
signal
Type
Voltage input
Counting range
A, B, Z (phase)
0~16,777,215
(Binary 24 bits)
Counting speed
50kpps
Up/down
1-phase input
Program or B phase
counter setting
2-phase input
Phase difference
Multiplication
2-phase input
External input
Limit switch
DC 24V
External output
Type
OUT1, OUT2
(Select: >, =, <)
Signal
Current consumption
Configuration
SoftMaster-100R Software
Features
Supports the international language (IEC61131-3)
- IL (Instruction List), LD (Ladder Diagram), SFC (Sequencial Function Chart)
Supports Windows 95, 98, ME, NT, 2000, XP
Simulation (DI/DO, AI/AO)
- Program test and debugging without PLC
Editing, monitoring, debugging using symbol and variable name
Automatic memory allocation
- Compiler sets a variable location automatically
Optimization (PLC code) by compiler method
User-defined function/function block support
Function (Type conversion, Arithmetic, Comparison, Array operation function)
Function block (Timer, Counter, etc)
System Requirement
Intel compatible PC (Intel Pentium CPU or later)
Windows 95,98,ME, NT, 2000, XP
Video adapter
Mouse/Printer compatible with Windows
128M RAM and 20M free hard disk space
System configuration
Product List
Type
Type
Part Number
CPU Module
GMR-CPUA
Redundant CPU, Max I/O: 7,680points, Program memory: 512K, Data memory: 512
GMR-CPUB
Redundant CPU, Max I/O: 7,680points, Program memory: 2M, Data memory: 512
Redundancy
GMR-DIFA
GMR-PA1A
Power Supply
Redundant
GMR-PA2A
Module
Power Supply
GMR-PA1B
GMR-PA2B
Base
CPU
GMR-B02M
Main Base
GMR-B04M
Remote
GM3-B08R
I/O Base
GM3-B08S
Switched I/O
GMR-B08E
Expansion Base
GMR-B12E
GM2-B04E
GM2-B08E
GM2-B12E
I/O base Interface Module
&
Expansion Cable
Specification
GM2-FDIA
Switched &
GM2-FRIC
Redundant I/O
GM2-TERA
G3L-FURA
G3L-RBRA
G2C-E061
Switched &
G2C-E121
Redundant I/O
G2C-E201
G2C-E401
G2C-E601
G2C-E102
G2C-E202
Product List
Type
Type
Part Number
Specification
G3I-D22A
G3I-D22C
Digital
G3I-D24A
Input
G3I-D28A
G3I-A12A
G3I-A14A
G3I-A24A
DC Input Module
Module
AC Input Module
Digital
G3Q-RY2A
G3Q-RY4A
G3Q-TR2A
Transistor Output 16points (DC12/24V 2A, with surge absorber, sink type)
Output
G3Q-TR4A
Transistor Output 32points (DC12/24V 0.5A, with surge absorber, sink type)
Module
G3Q-TR4B
Transistor Output 32points (DC12/24V 0.5A, with surge absorber, source type)
G3Q-TR8A
Transistor Output 64points (DC12/24V 0.1A, with surge absorber, sink type)
G3Q-TR8B
Transistor Output 64points (DC12/24V 0.1A, with surge absorber, source type)
G3Q-SS2A
G3Q-SS4A
G3F-AD4A
G3F-AD4B
G3F-AD3A
G3F-DA4V
Module
G3F-DA4I
G3F-DA3V
G3F-DA3I
G3F-HSCA
G3F-TC4A
G3F-RD3A
G3F-PIDB
G3F-LPCA
Communication
Fast
G3L-EUTB
10/100BASE-TX, TP
Module
Ethernet
G3L-EUFB
Open type
(Pt100, JPt100))
G3L-EU5B
10BASE-5, AUI
G3L-CUEA
Interface Module
G3L-FUEA
Optical Converter
G0L-FOEA
Dimensions
Base
Power Module
GMR-B02M
GMR-B04M
GMR-B08E
GMR-B12E
GM3-B08R
GM3-B08S
GM2-B04E
GM2-B12E
424
564
480
620
480
480
284
424
526
439
579
495
635
495
495
299
493
549
Australia
Honeywell Ltd.
Phone : (61) 2-9353-4500
Fax : (61) 2-9353-7677
Japan
Honeywell Inc.
Phone : (81) 3-5440-1395
Fax : (81) 3-5440-1368
Singapore
Honeywell Pte Ltd.
Phone : (65) 6355-2828
Fax : (65) 6445-3033
China
Honeywell (Tianjin) Ltd. Beijing
Phone : (86-10) 8458-3280
Fax : (86-10) 8458-3102
South Korea
Honeywell Co., Ltd.
Phone : (82) 2-799-6114
Fax : (82) 2-792-9015
Thailand
Honeywell Systems Ltd.
Phone : (662) 693-3099
Fax : (662) 693-3085
Malaysia
Honeywell Engineering Sdn Bhd.
Phone : (603) 7958-4988
Fax : (603) 7958-8922
Taiwan
Honeywell Taiwan Ltd.
Phone : (886) 2-2245-1000
Fax : (886) 2-2245-3241
Indonesia
PT Honeywell Indonesia
Phone : (62) 21-535-8833
Fax : (62) 21-5367-1008
New Zealand
Honeywell Ltd.
Phone : (64-9) 623-5050
Fax : (64-9) 623-5060
India
Honeywell Automation India Ltd.
Phone : (91) 20-5603-9400
Fax : (91)-20-5603-9800
Philippines
Honeywell Systems Inc.
Phone : (63-2) 633-2830
Fax : (63-2) 638-4013
e-mail : MasterLogic@honeywell.com