TWO WAY BEAM-SLAB

INPUTS
Case

Long direction (L)

13.500 ft

Short direction (S)

11.000 ft

L.L

40.00 psf

Floor finishe (F.F)

20.00 psf

Additional(partition)load

50.00 psf

f'c

3.0 ksi

fy

60.0 ksi

Provided thickness (h)

6.0 in

DESIGN BY:
Abid Moin Uddin
EMAIL:
Engr.abid@rocketmail.com

Depth check (With respect of maximum Moment):


Maximum Steel ratio
d

Slab thickness (h)

3.788 in

Required depth (t)

SLAB THICKNESS IS OK
Partition wall load calculator

Shear Check:

Wall Height

9.00 ft

Wall Length

10.00 ft

Wall Thickness
Partition wall load

Concrete Strength ( Vc)


Stress (Vu)

SLAB THICKNESS IS OK

5.0 in
30.30 psf

Steel Calculation:
As(+M): (alt ckd)

0.815

Total D.L

145.00 psf

Total factored load (W)

238.00 psf

As(-M): (ext.top)
As (minimum)

RESUL

Negetive Moment:
-M.short

2001.994 lb-ft

Slab Thickness

-M.long

1322.150 lb-ft

As(+M): (alt ckd)

Max. (-M) moment

2001.994 lb-ft

As(-M):(ext.top)+alt.ckd
As(-M):(ext.top)-alt.ckd

Positive Moment:

Alt. Ckd

+M.s.dl

802.391 lb-ft

+M.s.ll

360.239 lb-ft

10mm @

+M.l.dl

535.572 lb-ft

12mm @

+M.l.ll

243.648 lb-ft

16mm @

+M.s(total)

1162.631 lb-ft

20mm @

+M.l (total)

779.220 lb-ft

Max. (+M) moment

1162.631 lb-ft

Choose alt.ckd.
12 mm
Maximum spacing (2*h)

O WAY BEAM-SLAB DESIGN

:
Uddin

@rocketmail.com

h respect of maximum Moment):

12 mm =0.175in2

0.0155
1.71 in
2.71 in

LAB THICKNESS IS OK

5 in
10 in

5 in

4.93 kips
1.09 kips

LAB THICKNESS IS OK
0.052 in2
0.091 in2

Case-2

0.200 in2

RESULTS:
6.0 in

Case-3
STATUS: (SLAB THICKNESS):

0.200 in2

DEFLECTION

OK

0.200 in2

MOMENT

OK

-0.009 in2

SHEAR

OK

Alt. Ckd

Ext. Top
7.26 in c/c alt.ckd

10mm @

-0.072 -~ 1 nos

10.50 in c/c alt.ckd

12mm @

-0.051 -~ 1 nos

18.66 in c/c alt.ckd

16mm @

-0.028 -~ 1 nos

29.16 in c/c alt.ckd

20mm @

-0.018 -~ 1 nos

Case-4
Case-5
Case-6
Case-7
Case-8

Choose alt.ckd.
5.0 in c/c alt.ckd
12 in

Case-9

CASE
m

4
0.815

Cs.neg 0.06952

Here red
border
indicating
the
support
edge.

Cl.neg

0.03048

Cs.dl

0.03811

Cl.dl

0.01689

Cs.ll

0.04652

Cl.ll

0.02089

ONE WAY SLAB DESIGN


Input Data :
Yield Strength of Steel,fy =
Concrete Compressive Strength, f'c =
Concrete Unit Weight =
Span Length, L =

60000

psi

4000
150
6

psi
pcf
ft

Load Calculation :
Self Weight =
Thickness of Lime Concrete =
Load of Lime Concrete =
Load of Plaster =
Load of Floor Finish =
Live Load =
Total Factored Load =

2.For One End Continuous =


75
2
20
5
20
40
208

psf
in
psf
psf
psf
psf
psf

Moment Calculation :
Coefficient :
0.11 Interior , M1 (-ve) =
Interior =
0.042 Exterior , M2 (-ve) =
Exterior =
0.071 Midspan , M3 (+ve) =
Midspan =

Calculation of Thickness of Sla


Minimum Slab Thickness
Criteria :
4
1. For Simply Supported =

823.68
314.496
531.648

3. For Both End Continuous =


4.For Cantilever =
Selected Thickness,h =
For different Concrete unit weight,Thickness
For other than 60G bar, Thickness =
Provide Thickness, h =
Effective Depth, d =

Check For Depth :


lb-ft
lb-ft
lb-ft

Maximum Moment =
Maximum Steel Ratio, max =
R=
Required Depth , d =

OK

Calculation of Steel Area :


Minimum Steel Area:
For 60G bar =
For 40G bar =
For >60G bar =
For Interior (-ve) Moment :
Assume , a =
Required, a =
Steel Area, As =
Selected Steel Area, As =
#
Use
3
Maximum Spacing, Smax =

#
Provide
For Exterior (-ve) Moment
Steel Area, As =
Selected Steel Area, As =
#
Use
#
Provide

3
:

3
3

@
@

@
@

0.1296
0.144
0.1296

in2
in3
in4

0.411
0.056143
0.038177
0.1296

in
in
in2
in2
" C/C
in
" C/C

10.22135
12
10.22135
0.014577
0.1296
10.22135

10.22135

in2
in2
" C/C
" C/C

For Midspan (+ve) Moment:


Steel Area, As =
Selected Steel Area, As =
Use
#
3
Provide
#
3
For Binder :
Selected Steel Area, As =
Use
#
3

on of Thickness of Slab :

ess

ply Supported =

End Continuous =

3.6

in

in

h End Continuous =
2.571429
ilever =
7.2
=
7.2
unit weight,Thickness
7.2
ar, Thickness =
7.2
=
6

in
in
in
in
in
in
in

heck For Depth :


823.68
0.02138
1040.081
0.938046

lb-ft

in2
in2

@
@

0.024642
0.1296
10.22135
10.22135

" C/C
" C/C

0.1296
10.22135

" C/C

psi
in

OK

oment:

As =

As =

in2