Sei sulla pagina 1di 15

1

Oferta N TCO-0058-047/2014
Lima, 03 de Febrero de 2014
Seores
INGENIERIA ELECTRICA SAC
Lima
Atencin:
Srta. Sandra Gil
Referencia: COTIZACIN DE TABLEROS ELCTRICOS
Estimados Seores:
En atencin a su amable solicitud, sometemos a su consideracin nuestra oferta N
TCO-0058-047/14:
te
m
1

Can
t.
1

Descripcin
TABLERO DE CARGA DE BAJA TENSION, 480VAC,
60Hz, 3FASES, 3HILOS, 65KA, NEMA 4.
TAG: 405-LCL-001.
TABLERO DE ALUMBRADO, 400-230VAC, 60Hz,
3FASES, 4HILOS, 25KA, NEMA 4.
TAG: 405-DPJ-001.
TABLERO DE INSTRUMENTACION, 208-120VAC,
60Hz, 3FASES, 4HILOS, 22KA, NEMA 4.
TAG: 405-DPJ-001.
TRANSFORMADOR TIPO SECO 30KVA, 3FASES,
480/400-230V, NEMA 3R.
TAG: 405-XFL-001.
TRANSFORMADOR TIPO SECO15KVA, 3FASES,
480/208-120V, NEMA 3R.
TAG: 405-XFZ-001.

VENTA TOTAL US$

V.V.Unit
US$
18,880
.14

V.V.Total
US$
18,880
.14

4,783
.58

4,783.
58

3,218
.61

3,218.
61

3,504
.75

3,504.
75

2,521
.57

2,521.
57

VALOR

Los precios son vlidos por el total de la oferta.


Ver aclaraciones al final de la oferta.

32,908.65

2
Oferta N TCO-0058-047/2014

CONDICIONES COMERCIALES
PRECIOS:
VALIDEZ DE LA
OFERTA:
GARANTIA:
PLAZO DE
ENTREGA:
LUGAR DE
ENTREGA:
FORMA DE PAGO:

Los precios son en Dlares Americanos y no incluye IGV.


Incluye embalaje de madera.
30 das.
12 meses contados a partir de la fecha de entrega.
2 semanas para emisin de planos de aprobacin despus de
recibida la Orden de Compra y el pago del adelanto.
15 Semanas para fabricacin despus de recibido la
aprobacin de planos.
En Nuestros Almacenes.
50% con la orden de compra ms el IGV correspondiente.
Saldo Contra Entrega.
Otras Formas de Pago a tratar.
El pago se efectuar en US$ dlares o en moneda nacional al
valor venta del tipo de cambio promedio ponderado vigente a
la fecha de cancelacin segn R.C. No 007-91-EF/90.

3
Oferta N TCO-0058-047/2014

NOTAS
1. Los equipos de la presente oferta sern revisados y/o probados por nuestro
Dpto. de Control de Calidad y preferentemente en presencia de su
representante. De requerirse la asistencia de nuestro personal durante la
puesta en servicio o asesoramiento en sus instalaciones, ste servicio se
cotizar como un adicional.
2. La colocacin de su orden de implica la aceptacin de las condiciones aqu
indicadas, as como las Condiciones Generales de Ventas de Manufacturas
Elctricas que en anexo se adjunta.
3. El plazo de entrega se contabilizar tomando en cuenta los siguientes puntos:

Aceptacin por parte de Manufacturas Elctricas de una orden de


compra tcnica y comercialmente clarificada y dentro de la validez de la
oferta.
Pago del adelanto indicado en la Forma de Pago y que la aprobacin de
los planos, de ser requerida, se realice dentro del plazo sealado por
Manufacturas Elctricas, dependiendo de los requerimientos de cada
caso.

4. Para la elaboracin de la oferta se ha tomado en cuenta las especificaciones


del cliente y los diseos estndares propios de Manufacturas Elctricas.
Cualquier cambio posterior a la aceptacin de la Orden de Compra, que
obligue a cambiar los diseos afectar el precio y el plazo de entrega.
Esperamos que nuestra oferta les sea satisfactoria y est de acuerdo con sus
requisitos. Si necesitan alguna informacin adicional, no duden en contactarse con el
Ing.
Antonio
Carbajal,
Telef.
(511)
619-6200,
anexo
250,
Email:
acarbajal@manelsa.com.pe.
Muy Atentamente.

Ing. Antonio Carbajal


INGENIERO DE VENTAS

RM/.

Ing. Guillermo Gallo

JEFE TECNICO COMERCIAL

Ing. Roberto Contreras


GERENTE DE VENTAS

4
Oferta N TCO-0058-047/2014

ESPECIFICACIONES TECNICAS
CLIENTE:
REF. :

INGENIERIA ELECTRICA SAC


TABLEROS ELECTRICOS

tem 1
TABLERO DE CARGA DE BAJA TENSION, 480VAC, 60Hz,
3FASES, 3HILOS, 65KA, NEMA 4.
TAG: 405-LCL-001.
INTERIORES
El Interior del tablero es ensamblado con lmina de proteccin
de equipos y estn diseadas para la conexin de secuencia de
fases de equipos para el equilibrio de las cargas elctricas. Los
dispositivos pueden ser reemplazados sin perturbar las unidades
adyacentes o eliminar conexiones principales de autobuses.
Las barras colectoras estn dimensionadas de acuerdo con los
estndares UL para limitar el aumento de temperatura en
cualquier parte de conduccin de corriente a un mximo de 65
C por encima de 40 C de temperatura ambiente.
Terminales estndar son del tipo mecnico adecuado, ya sea
para conductores de cobre o aluminio y se instalan con las
disposiciones anti-giro apropiados.
CAJAS
Las cajas del tablero se construyen a partir de acero galvanizado
de calibre comercial. Cajas estndar cuentan con paredes
terminales extrables en blanco. Todas las cajas son de tamao
de alambre para proporcionar espacio de flexin como se
requiere por el NEC.
Pernos de montaje interiores incluyen dentro y fuera capacidad de ajuste para la
alineacin de la instalacin.

5
Oferta N TCO-0058-047/2014

6
Oferta N TCO-0058-047/2014
Caractersticas Tcnicas
Estructura
Dimensiones aprox.
Grado de Proteccin
Pintura
Sistema Elctrico
Tensin del Sistema
Barras Principales
Capacidad de
Interrupcin

: 1866.9 mm x 609.6 mm x 406.4 mm (altura x ancho x


profundidad)
: NEMA 4 (uso exterior)
: ANSI 61
: 480 V, 3 fases, 3 hilos, 60 Hz
: Ba Cu, 400 A, plateado.
: 65 kA sym.

Equipamiento
Interruptor Principal
1- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
HKD, 400 A frame, 150 A rating plug, 65 kAIC a 480 V, con unidad de
disparo Digitrip RMS 310 (funcin proteccin LSIG).
Incluye bobina de disparo a 110-240 Vac, contactos auxiliares 1NA/1NC y
elemento de bloqueo mecnico.
Arrancadores de motor
1- Arrancador directo FVNR Size 1, 1,5 kW/480 V, cada uno compuesto de:
1- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
HFD, 3x15 A, 65 kAIC a 480 V. Incluye bobina de disparo a 110-240
Vac, y elemento de bloqueo mecnico.
1- Contactor EATON FREEDOM CN 15, NEMA Sz 1, 27 A, bobina 120 V, 60
Hz.
Incluye bloque de contactos auxiliares 1NO+1NC.
1- Rel de sobrecarga EATON C440, NEMA Sz 1, 4-20 A.
Incluye mdulo de comunicacin PROFIBUS.
1- Transformador CPT 100 VA, 240-480/120 V, 60 Hz.
1- Lmpara de sealizacin RUN tipo LED, rojo, 120 V.
1- Lmpara de sealizacin STOP tipo LED, verde, 120 V.
1- Pulsador de mando START, verde, 1 NA.
Interruptores Derivados
1- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
HFD, 3x50 A, 65 kAIC a 480 V. Incluye bobina de disparo a 110-240 Vac, y
elemento de bloqueo mecnico.
1- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
HFD, 3x40 A, 65 kAIC a 480 V. Incluye bobina de disparo a 110-240 Vac, y

7
Oferta N TCO-0058-047/2014
elemento de bloqueo mecnico.
4- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
HFD, 3x15 A, 65 kAIC a 480 V. Incluye bobina de disparo a 110-240 Vac, y
elemento de bloqueo mecnico.
1- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
HFD, 2x20 A, 65 kAIC a 480 V. Incluye contactos auxiliares 1NA/1NC y
elemento de bloqueo mecnico.
Proteccin de falla a tierra
5- Rel de falla a tierra GE GFM-252, 1.5-65 A, autoalimentado.
5- Sensor de falla a tierra GE GFM.
5- Transformador CPT 100 VA, 240-480/120 V, 60 Hz.

8
Oferta N TCO-0058-047/2014
tem 2
TABLERO DE ALUMBRADO, 400-230VAC, 60Hz, 3FASES, 3HILOS,
20KA, NEMA 4.
TAG: 405-DPJ-001.
INTERIORES
El Interior del tablero es ensamblado con lmina de
proteccin de equipos y estn diseadas para la conexin de
secuencia de fases de equipos para el equilibrio de las cargas
elctricas. Los dispositivos pueden ser reemplazados sin
perturbar las unidades adyacentes o eliminar conexiones
principales de autobuses.
Las barras colectoras estn dimensionadas de acuerdo con los
estndares UL para limitar el aumento de temperatura en
cualquier parte de conduccin de corriente a un mximo de
65 C por encima de 40 C de temperatura ambiente.
Terminales estndar son del tipo mecnico adecuado, ya sea
para conductores de cobre o aluminio y se instalan con las
disposiciones anti-giro apropiados.
CAJAS
Las cajas del tablero se construyen a partir de acero
galvanizado de calibre comercial. Cajas estndar cuentan con
paredes terminales extrables en blanco. Todas las cajas son
de tamao de alambre para proporcionar espacio de flexin como se requiere por el
NEC.
Pernos de montaje interiores incluyen dentro y fuera capacidad de ajuste para la
alineacin de la instalacin.

9
Oferta N TCO-0058-047/2014
Caractersticas Tcnicas
Estructura
Dimensiones aprox.
Grado de Proteccin
Pintura
Sistema Elctrico
Tensin del Sistema
Barras Principales y
Neutra
Capacidad de
Interrupcin

: 914.4 mm x 609.6 mm x 152.4 mm (altura x ancho x


profundidad)
: NEMA 4 (uso exterior)
: ANSI 61
: 400-230 V, 3 fases, 4 hilos, 60 Hz
: Ba Cu, 100 A, estaadas.
: 25 kA sym.

Equipamiento
Interruptor Principal
1- Interruptor automtico de caja moldeada Series C, marca EATON, tipo
FD, 3x50 A, 35 kAIC a 480 V.
Incluye elemento de bloqueo mecnico.
Interruptores Derivados
13 Interruptor automtico de caja moldeada Series C, marca EATON, tipo
- HGHB, 1x20 A, 25 kAIC a 227 V.
Incluye elemento de bloqueo mecnico.
Interruptores Diferenciales
7- Interruptor diferencial mRCM, marca EATON, 2x25 Amp, 30 mA, tipo AC.

10
Oferta N TCO-0058-047/2014
tem 3
TABLERO DE INSTRUMENTACION, 208-120VAC, 60Hz, 3FASES,
3HILOS, 20KA, NEMA 4.
TAG: 405-DPJ-001.
INTERIORES
El Interior del tablero es ensamblado con lmina de
proteccin de equipos y estn diseadas para la conexin de
secuencia de fases de equipos para el equilibrio de las cargas
elctricas. Los dispositivos pueden ser reemplazados sin
perturbar las unidades adyacentes o eliminar conexiones
principales de autobuses.
Las barras colectoras estn dimensionadas de acuerdo con
los estndares UL para limitar el aumento de temperatura en
cualquier parte de conduccin de corriente a un mximo de
65 C por encima de 40 C de temperatura ambiente.
Terminales estndar son del tipo mecnico adecuado, ya sea
para conductores de cobre o aluminio y se instalan con las
disposiciones anti-giro apropiados.
CAJAS
Las cajas del tablero se construyen a partir de acero
galvanizado de calibre comercial. Cajas estndar cuentan con
paredes terminales extrables en blanco. Todas las cajas son
de tamao de alambre para proporcionar espacio de flexin como se requiere por el
NEC.
Pernos de montaje interiores incluyen dentro y fuera capacidad de ajuste para la
alineacin de la instalacin.

11
Oferta N TCO-0058-047/2014
Caractersticas Tcnicas
Estructura
Dimensiones aprox.
Grado de Proteccin
Pintura
Sistema Elctrico
Tensin del Sistema
Barras Principales y
Neutra
Capacidad de
Interrupcin

: 762 mm x 609.6 mm x 152.4 mm (altura x ancho x


profundidad)
: NEMA 4 (uso exterior)
: ANSI 61
: 208-120 V, 3 fases, 4 hilos, 60 Hz
: Ba Cu, 100 A, estaadas.
: 22 kA sym.

Equipamiento
Interruptor Principal
1- Interruptor automtico bolt-on Quicklag, marca EATON, tipo QBHW,
3x100 A, 22 kA a 240 V.
Incluye elemento de bloqueo mecnico.
Interruptores Derivados
1- Interruptor automtico bolt-on Quicklag,
A, 22 kA a 120 V.
Incluye elemento de bloqueo mecnico.
2- Interruptor automtico bolt-on Quicklag,
A, 22 kA a 120 V.
Incluye elemento de bloqueo mecnico.
1- Interruptor automtico bolt-on Quicklag,
A, 22 kA a 120 V.
Incluye elemento de bloqueo mecnico.
3- Interruptor automtico bolt-on Quicklag,
A, 22 kA a 120 V.
Incluye elemento de bloqueo mecnico.
3- Interruptor automtico bolt-on Quicklag,
A, 22 kA a 120 V.
Incluye elemento de bloqueo mecnico.

marca EATON, tipo QBHW, 1x35


marca EATON, tipo QBHW, 1x40
marca EATON, tipo QBHW, 1x50
marca EATON, tipo QBHW, 1x15
marca EATON, tipo QBHW, 1x20

Interruptores Diferenciales
6- Interruptor diferencial mRCM, marca EATON, 2x25 Amp, 30 mA, tipo AC.
3- Interruptor diferencial mRCM, marca EATON, 2x40 Amp, 30 mA, tipo AC.
1- Interruptor diferencial mRCM, marca EATON, 2x63 Amp, 30 mA, tipo AC.

12
Oferta N TCO-0058-047/2014
tem 4
TRANSFORMADOR TIPO SECO30KVA, 3FASES, 480/400-230V,
NEMA 3R.
TAG: 405-XFL-001.
Dry-type transformers rated 600V and
below are available in a wide variety
of types and ratings to provide
reliable
and
versatile
electrical
distribution for lighting and power
loads in industrial and commercial
applications.
The air cooled dry type construction
requires
no
special
vaults
for
installation. Maintenance requires
only periodic inspection of cable
connections and removal of any dust
accumulation.
Ratings
kVA...................................30
Phase ..............................Three Phase
Frequency:........................60 Hertz
Primary Voltage / BIL:.......480 Delta-10kV
Secondary Voltage / BIL. . .400Y/230-10kV
Conductor:.......................Copper
Temperature Rise ............150 above an average ambient of 30 C
Impedance:......................Factory Standard
Taps (approx)...................+2/-4@2.5%
Insulation System.............220 C
Characteristics
Indoor, NEMA 3R, Category C(Accessible to authorized personnel only)
ANSI 61 Paint color
AA self cooled only
UL Listed
For installation at or below 4300 meters

13
Oferta N TCO-0058-047/2014
tem 5
TRANSFORMADOR TIPO SECO 15KVA, 3FASES, 480/208-120V,
NEMA 3R.
TAG: 405-XFZ-001.
Dry-type transformers rated 600V and
below are available in a wide variety
of types and ratings to provide
reliable
and
versatile
electrical
distribution for lighting and power
loads in industrial and commercial
applications.
The air cooled dry type construction
requires
no
special
vaults
for
installation. Maintenance requires
only periodic inspection of cable
connections and removal of any dust
accumulation.
Ratings
kVA...................................15
Phase ..............................Three Phase
Frequency:........................60 Hertz
Primary Voltage / BIL:.......480 Delta-10kV
Secondary Voltage / BIL. . .208Y/120-10kV
Conductor:.......................Copper
Temperature Rise ............150 above an average ambient of 30 C
Impedance:......................Factory Standard
Taps (approx)...................+2/-4@2.5%
Insulation System.............220 C
Characteristics
Indoor, NEMA 3R, Category C(Accessible to authorized personnel only)
ANSI 61 Paint color
AA self cooled only
UL Listed
For installation at or below 4300 meters

14
Oferta N TCO-0058-047/2014

ACLARACIONES A LA OFERTA
1. El alcance de nuestro suministro comprende el equipamiento tal y como se
encuentra definido en la presente oferta, cualquier variacin favor consultar.
2. Los equipos contemplados en esta especificacin son apropiados para operar en
las condiciones ambientales y climticas en el lugar de su instalacin.
3. La elaboracin de la presente oferta est de acuerdo a las especificaciones
tcnicas del proyecto, diagramas unifilares y esquemticos enviados por el
cliente, con las siguientes excepciones:
No se incluye servicios de puesta en marcha de los tableros.
Para el tablero TAG: 405-LCL-001, se est considerando una barra principal
de 400 Amp esto debido a la seleccin del interruptor principal de frame
400 A y trip 150 A.
El interruptor diferencial considerado es de 30mA del tipo AC, bajo
fabricacin IEC.

15
Oferta N TCO-0058-047/2014
CONDICIONES GENERALES DE VENTA MANUFACTURAS ELECTRICAS S.A.
El presente documento define las condiciones comerciales de suministro de los productos fabricados por Manufacturas Elctricas S.A. Estas condiciones slo
pueden variar si expresamente se indicasen otras en las Condiciones Particulares de cada oferta (cotizacin).
A. Alcances:
Los trminos y condiciones de la oferta (cotizacin) slo son aplicables a los equipos ofertados, cualquier modificacin o adicin ser materia de una nueva
oferta (cotizacin).
La oferta (cotizacin) contenida en este documento refleja los trminos libremente negociados entre las partes. Una vez aceptada, constituir un contrato
valido y exigible entre ellas.
B. Pruebas:
Los precios en nuestras ofertas (cotizaciones) incluyen exclusivamente los servicios comprendidos dentro de los alcances de la garanta que se describe
posteriormente. No incluyen, por tanto, los servicios de asistencia tcnica, tales como pruebas de inspeccin, funcionamiento y ajustes de los suministros
despus de su instalacin por terceros, participacin de nuestros tcnicos durante la puesta en marcha de los suministros, presencia de nuestro personal en la
entrega de los suministros al cliente final. Estos y otros servicios se brindan previa aprobacin de la oferta (cotizacin) que para el efecto se presente a
solicitud del interesado.
El cliente se obliga, en los casos que sea requerido a asistir a las pruebas de equipos que sean necesarias. Siendo las pruebas parte integral del proceso
productivo, las fechas de dichas pruebas sern sealadas por MANUFACTURAS ELECTRICAS S.A. y coordinadas entre las partes dentro de los siete das
calendarios anteriores a su realizacin. La fecha una vez sealada para la ejecucin de las pruebas slo podr ser postergada por decisin de MANUFACTURAS
ELECTRICAS S.A. Los gastos que conlleve la participacin del cliente en las pruebas sern por cuenta del mismo.
Si el cliente no asiste a las pruebas, en Ia fecha indicada estas se realizaran igualmente, entregndole al cliente los respectivos protocolos de pruebas.
Para que estas pruebas se realicen nuevamente, el cliente deber coordinar con MANUFACTURAS ELECTRICAS S.A. las nuevas fechas asumiendo el cliente los
costos totales de las mismas.
El cliente despus de efectuar la inspeccin de los productos contratados y de levantadas las observaciones si fuese el caso, los aceptar en la planta de
Manufacturas Elctricas S.A., caso contrario aceptar la conformidad del protocolo de pruebas emitido por e Dpto. de Control de Calidad de la empresa.
C. Validez de la oferta (cotizacin):
30 das calendarios a partir de la emisin de la misma.
D. Garanta:
MANUFACTURAS ELCTRICAS S.A., garantiza sus productos por un periodo de 12 meses contados a partir de la fecha de entrega, respecto a que estn libres de
defectos en el diseo, materia prima y en la fabricacin, comprometindonos a reparar, modificar y/o reemplazar las partes o los equipos que se encuentren
defectuosos a su costo, a excepcin de los gastos de transporte, alojamiento y alimentacin de su personal, y transporte de los materiales y/o equipos cuando
las instalaciones del cliente se encuentren fuera de la provincia de Lima. Esta garanta est limitada a la reparacin, modificacin, y/o reemplazo de los
materiales y/o equipos, no siendo aceptadas ninguna otra responsabilidad econmica ni legal.
El cliente deber informar inmediatamente, dentro del plazo mximo de dos das calendario de producido o detectado el defecto que evidencia el producto, as
como brindar las facilidades necesarias para revisar el equipo sujeto a reclamo.
Esta garanta no es aplicable en los casos que los tableros no se ubiquen en ambientes apropiados ni se instalen adecuadamente, compatibles con el grado de
hermeticidad especificada y que los equipos hayan estado sujetos a una operacin, mantenimiento o almacenamiento inapropiados, u otros, fuera del servicio
o uso normal. Tampoco se aplicar esta garanta a aquellos productos que hayan sido modificados o manipulados sin una autorizacin expresa de
MANUFACTURAS ELECTRICAS S.A.
Para que se pueda hacer uso de Ia garanta el cliente no deber tener ninguna deuda vencida con MANUFACTURAS ELECTRICAS S.A.
E. Embalaje:
Los productos solicitados por el cliente son suministrados sin embalaje. Si el cliente solicitara que aquellos sean embalados deber asumir el costo de dicho
servicio.
F. Entrega:
Los equipos se entregarn en los plazos indicados en la oferta (cotizacin), en la planta de MANUFACTURAS ELECTRICAS S.A.; sin embargo, MANUFACTURAS
ELECTRICAS S.A. se reserva el derecho de revisar los plazos en funcin de las confirmaciones de fechas de entrega de sus proveedores de equipos importados y a
la carga que pueda tener su planta al momento de recibir la Orden de Compra y a las vacaciones colectivas de MANUFACTURAS ELECTRICAS S.A. que se toman
durante la ltima semana de Diciembre y la primera semana de Enero.
El cliente se obliga a retirar el bien fabricado dentro del tercer da laborable de recibida Ia comunicacin de MANUFACTURAS ELECTRICAS S.A., indicando que
dicho bien se encuentra a su disposicin. Ser requisito indispensable para el retiro del bien, el pago del integro del saldo vencido del valor de fabricacin
pactado entre las partes.
De no ser retirado el bien dentro del plazo estipulado MANUFACTURAS ELECTRICAS S.A. se reserva el derecho de cobrar al cliente los gastos de almacenaje,
guardiana y seguro hasta el da en que se produzca el retiro. Si se venciera el plazo establecido para el retiro y transcurriera un plazo mayor a XXX das
laborales, MANUFACTURAS ELECTRICAS S.A., se reserva el derecho de disponer el uso de los mismos, previa notificacin al cliente, sin necesidad de resolver el
contrato ni de obtener Ia autorizacin respectiva. En tal casos, MANUFACTURAS ELECTRICAS S.A. repondr los bienes utilizados dentro de los plazos pactados
inicialmente.
De superar el periodo de almacenaje los seis meses y a fin de poder garantizar el buen funcionamiento de las unidades producidas, MANUFACTURAS ELECTRICAS
S.A., dispondr realizar nuevamente las pruebas finales cuyo costo deber ser asumido por el cliente.
MANUFACTURAS ELECTRICAS S.A. no acepta penalidades por demora en la entrega derivadas de hechos no imputables directamente a su parte. Otras
penalidades, as como daos, perjuicios y lucro cesante, para ser exigibles deben haber sido previamente pactadas.
G. Resolucin del Contrato:
De conformidad con lo previsto en el artculo 1430 del Cdigo Civil, las partes acuerdan que el contrato podr ser resuelto por MANUFACTURAS ELECTRICAS S.A.
si se produce cualquiera de los siguientes incumplimientos por parte del cliente:
a) El cliente no retira el bien fabricado por encargo suyo dentro del tercer da laborable de recibida la comunicacin de MANUFACTURAS ELECTRICAS S.A.,
indicando que dicho bien se encuentra a su disposici6n.
b) El cliente no cancela el integro del saldo vencido, de la contraprestacin pactada por la fabricacin del bien dentro del plazo convenido.
La resolucin se producir de pleno derecho cuando, producido el incumplimiento, MANUFACTURAS ELECTRICAS S.A. comunique al cliente que invoca Ia
presente clusula resolutoria.
Producida Ia resolucin de pleno derecho, el cliente deber pagar a MANUFACTURAS ELECTRICAS S.A., una penalidad correspondiente al costo de anulacin del
contrato. Esta penalidad no limita el derecho de MANUFACTURAS ELECTRICAS S.A., de solicitar una indemnizacin por cualquier dao.
H. Artculos Suministrados por el Cliente:
La entrega de equipos o cualquier tipo de bien por parte del cliente a MANUFACTURAS ELECTRICAS S.A., para que esta ltima cotice el valor de eventuales
servicios, elabore presupuestos, para cualquier tipo de servicios, los instale en sus tableros, o cualquier otra causa, se sujetara a las siguientes condiciones:
a) La entrega no constituye a MANUFACTURAS ELECTRICAS S.A. depositario de dichos bienes o equipos, ni responsable por Ia prdida de los mismos. Dichos
bienes debern estar adecuadamente asegurados por el cliente.
b) El cliente se obliga a retirar los equipos o bienes que haya entregado a MANUFACTURAS ELECTRICAS S.A., apenas culmine el servicio pactado en relacin a los
mismos, o se realice Ia cotizacin para Ia cual dichos equipos o bienes fueron entregados.
La sola entrega de bienes o equipos a MANUFACTURAS ELECTRICAS S.A., constituye aceptacin plena por parte del cliente de los trminos indicados
anteriormente.
Roberto Contreras Mimbela
Gerente de Ventas

V7. Dic. 2012