Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Freq
Amp
18
19
20
21
22
23
24
25
48
48
48
48
50
53
22.54
22.28
14.75
21.35
19.87
20.94
1
2
3
4
5
6
40
36
41
36
31
35
8.08
9.13
7.16
7.02
7.29
3.84
Input
Motor
Output
Motor
Load
Power
12.16
14.64
torque
72
88
voltage
396
399
Power
10
12.59
factor
80
91
6.84
46
399
6.53
47
700.1
12.55
12.38
14.33
80
82
78
398
404
409
11.55
13.16
13.2
82
80
92
799.9
644.1
684.1
3.11
3.46
2.72
2.08
2.25
1.32
35
42
30
55
53
27
335
303
340
249
202
238
3.08
2.95
2.02
2.27
35
44
39
43
148.4
233.3
401.6
389.6
W/h
706.3
615.5
8
14
15
16
17
10
11
13
40
28.5
28.5
28.5
28.5
10
24
30
20.95
15.08
16.39
19.21
15.81
12.94
16.3
11.29
9.54
5.43
5.38
6.93
5.77
1.88
5.45
3.57
152
110
81
102
106
80
119
68
337
244
243
243
245
98
209
257
8.22
4.58
5.52
5.77
5.03
1.26
4.34
3.24
142
111
86
92
120
88
121
78
1250
618.4
154.6
145.1
488.9
721.8
77.25
684.6
With this double drive system design, one additional main drive motor which is same
HP to existing main drive motor will be added into the production line main conveyor
chain. The existing main drive motor is 20HP. Hence, an additional 20HP will be
added.
To run both main drive motors with 20HP respectively, the existing inverter which
provides 15kW output is not sufficient to run two units of 20HP motor
simultaneously. Therefore, inverter must be sized properly based on its connected
motors.
I. The total HP of the connected motors to the inverter is 40HP.
II. Referring to NEC Table 430.250 the full load current for one 20HP main drive
motor is 27Amp.
III. Adding up both main drive motors the total of full load current will draw from
inverter is 54Amp.
IV. The estimate output power from inverter during full load is as below:
Pic 1: double drive system prototype with one unit inverter to run two units of motor
Pic 2: The speed of both motors is tested using one conveyor chain in different
frequency values
Initially, both motors are running in low frequency, the conveyor chain is driven
normally. The gap between upper and bottom layer conveyor chain is wide as shown
in picture 3. Both motor amperes are measured using clamp meter and the value is
0.3Amp respectively as shown in picture 4. Adding up both motor amperes should be
0.6 Amp. The inverter ampere reading is 0.8Amp as shown in picture 5. This is due to
the decimal error in clamp meter where causing the ampere between motors and
inverter has slight different.
Pic 6: motor on the left hand side is running slower than motor on the right one
5. Design Constraint
Double main drive system will initially run in the same speed for both motor if the
mechanical structure for the machine is well tuned. After running for some time, the
conveyor chain will elongate due to continuous heating and cooling process. Then, the
chain will start jerking; one motor will run slightly faster than other. The mechanical
part should do alignment to balance up the load between motors by changing the
sprocket ratio. However, this condition is continuous, meaning that every time when
chain start jerking a new sprocket has to replace to slow down the faster motor.
To reduce further on the chain elongation issue, the double drive conveyor chain
comes with one tensional load and one spring to absorb the elongation as shown in
picture 7. However, this system will potentially be more worsen. The tensional load
will absorb the chain elongation effect by lowering down the dead load and the spring
will pull back further to tighten back the chain if the chain elongated. But, tensional
load will react faster than spring system to absorb the elongation part. If the tensional
load is after the faster motor (A), then the conveyor chain will become loosen even
faster at the bottom part as shown in picture 7. Spring has little reaction of elongation
on this situation. Then the situation will happen where the conveyor chain on spring
system part become tighten and on the tensional load will become loosen. Hence, the
load in the whole conveyor chain will no longer be even.
Pic 7: Side effect if one motor run slightly faster than other in spring and tensional
load system
If one main drive motor was burned and repaired by rewinding, the performance of
both motors will not be the same, the rewinding motor will have lower efficiency and
the speed may not be the same anymore. Hence, it may cause load uneven issue too.
6. Future Study
To eliminate the design constraint, the double drive system concept has to be changed.
Instead of providing same speed to both motors, the new design is by using two units
of inverter to run two units of main drive motors.
Both inverters will communicate with each other on the load factor, torque and speed.
To link up both inverters, master-slave design should implement. One inverter will act
as master that providing frequency to main drive motor and provide torque and load
factor data to slave inverter. Slave inverter will base on the signal provided and adjust
the frequency provide to the downstream main drive motor.
Hence, master inverter will make sure its downstream main drive motor running in
constant torque and speed while slave inverter will vary the torque and speed to
support master main drive motor.