Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Published2008.4
Table of Contents
1.
Introduction................................................................... 1
2.
3.
4.
5.
6.
7.
8.
2.1
Front-panel ......................................................................................................................................... 2
2.2
3.2
Setpoints ........................................................................................................................................... 35
4.2
Controls ............................................................................................................................................ 36
4.3
Description ....................................................................................................................................... 37
5.2
Preparation ....................................................................................................................................... 43
6.2
6.3
6.4
Report ...................................................................... 48
7.1
7.2
7.3
Others ............................................................................................................................................... 48
Appendix .................................................................... 49
Diagram lists
Figure 1 Front-panel Plan.................................................................................................................... 2
Figure 2 Backboard Plug-in & Terminal Diagram .............................................................................. 5
Figure 3 Menu Structure Diagram..................................................................................................... 13
Figure 4 Typical Interface Structure ................................................................................................. 14
Figure 5 Wring Display Interface (Default) ...................................................................................... 15
Figure 6 State Report Interface ......................................................................................................... 16
Figure 7 Lockout/blocking Logic Diagram ....................................................................................... 17
Figure 8 Action Report Interface ...................................................................................................... 19
Figure 9 Curve Display Interface ...................................................................................................... 20
Figure 10 Manual Transfer Interface ................................................................................................. 24
Figure 11 Semi-auto Parallel Transfer Interface (1st Step) ................................................................ 24
Figure 12 Semi-auto Parallel Transfer Interface (Success) ............................................................... 25
Figure 13 DI Debug Interface ........................................................................................................... 28
Figure 14 Regulate Precision Interface ............................................................................................. 29
Figure 15 GPS Port Monitoring Interface ......................................................................................... 30
Figure 16 Advanced Function Interface ............................................................................................ 31
Figure 17 Communication Setting Interface ..................................................................................... 32
Figure 18 Shortcut Key Setting Interface .......................................................................................... 33
1. Introduction
Based on the first and second generation device, a third generation MFC2000-3A high-speed bus
power transfer device is developed. The new device with back-plugin and fieldbus backboard structure
employs 4U cabinet and 320X240 LCD display. Master CPU module adopts 32-bit SCM plus DSP. All
the features endow the device with improved technical performance, high reliability and friendly HMI
and so on..
2. Hardware Configuration
MFC2000-3A device has the following hardware mainly
Front-panel
2.1 Front-panel
This panel covers LCD display, control keys, shortcut keys, status indicators and 232 communication
port.
direction keys are used to move the cursor up/down/left/right to the desired
2
message;
Key1~4The concrete functions are listed in the right shortcut bar. Users can also self-define
their separate functions as they need.
Key 5Also called Help key. Press it, menu-related topics will be displayed; in default menu,
current device running status will be indicated.
RUNThe LED flashes slowly when the device runs normally, it flashes fast when the device is
blockedthe LED will be blacked out when the device is in debugging state or CPU doesnt
work.
TRBLOCK Transfer Blocking Indicator. The LED illuminates when the device is in
lockout/blocking status, no transfer is permitted.
ACTThe LED illuminates when the device has finished the transfer operation just now and it
extinguish after resetting.
WORKThe status indicator illuminates when the work power source works.
STANDBYThe status indicator illuminates when the standby power source works.
REMOTEIts on when the device is in remote operation mode, otherwise, in local mode.
Power ModuleEMPW400
Convert DC220V or DC110Vvoltage into small voltage +5V15V and +24V for device
internal use. The tailor-made voltage delay circuit can ensure no misoperation during the process
of power-on and power-off. The power source is for AC/DC both.
AI ModuleMAI400
AC Input module.Isolate and transform the secondary output current (CT) and voltage (VT)
DI ModuleEMDI400
Digital Input module.Send the Digital inputs (dry contacts) from console, protection circuit and
other control devices to CPU after undergoing relay isolation and photoelectric isolation.
Output ModuleEMDO400,EMDO401
Group and send close/trip commands from CPU to output relay after photoelectric isolation and
Test ModuleEMTEST400
It includes analog CB, control button and signal indicators so on, even without practical
operations, users can still test the performance of internal input & output circuit. The special
6
hardware switch supplied can cut off the test circuit in normal operation condition, while connect
it when testing.
GNDground.
AI ModuleMAI400
UaUbUcUnAuxiliary bus 3-phase voltage. UaUb and Uc for line voltage Ua, Ub
Uc and Un for phase voltage.
UgzUgz*Work power voltage (auxiliary branch or VT voltage), which can be line voltage
or phase voltage.
UbyUby*Standby power voltage, which can be phase-to-phase voltage or phase-to ground
voltage.
Urs1Urs1*Urs2Urs2*Reserved.
DI ModuleEMDI400
When these protections work, the transfer system will be blocked. Pickup mode is closed
short-pulse.
( 50ms). This signal is valid only when the setting Control Mode is set as Remote.
Disconnected, it is Parallel Transfer; Connected, its Sequential Transfer (when setting Remote
Tran Group is set as Par Seq) or Simultaneous Transfer (when setting Remote Tran Group is
set as Par Sim). This signal is valid only when the setting Control Mode is set as Remote.
TranExit(XC-8)Contact for Enable/Disable transfer manually. Disconnected, transfer is
enabled; connected, transfer function is disabled. When the transfer function is disabled, an alarm
signal will be sent to operators. The pickup mode is long-holding.
RSV1(XC-9)Reserved.
COMMON(XC-16)Common terminal.
TrExit (XG1-7XG1-8)Make contact. When the device is in the following situations, the
signal will be sent and the device cannot undertake transfer operation. If any of the following
situations is not met, the signal will be cleared and the device is allowed to transfer without
resetting.
Transfer methods , including Fast Transfer, Lead Phase TransferLead Time Transfer
Residual Voltage Transfer and Fixed Time Transfer are all disabled.
BSS (XG2-1XG2-2)Make contact. Signals for breaker status abnormity. Under the
9
following conditions, the device will block the transfer function and send the signals.
Abnormal situations: Work breaker and standby breaker are closed or open together, or VT
isolating switch is open..
SSUVB (XG2-3XG2-4)Make contact. Signals for Standby-Source-Under-Voltage-Blocking.
When standby power voltage is lower than setting SSUV Vol Amp and the setting SSUVB is
enabled, the contact is closed. It will be kept until the problem is solved and the standby power
voltage gets right.
NoteWhen standby VT is taken out of service for maintenance, operators can disable the
Standby-Source-Under-Voltage-Blocking function through setting menu. In this case, the
device can transfer normally when the standby power source has power, if power is lost, the
device can only implement Residual Voltage Transfer and Fixed Time Transfer.
VTFL (XG2-5XG2-6)Make contact. When VT fuse loss is detected, transfer function is
blocked and the signal is sent. It will be kept until the problem is solved and the device is reset.
Fault (XG2-7XG2-8)Make contact. It will block the transfer function and send the signal
when fault is detected in self-check process. In fault report, operators can find out the detailed
information about the fault. It will be kept until the problem is solved and the device is reset.
AAP (XG2-9XG2-10)Make contact. When transfer is initiated, this contact is closed to
initiate the after-accelerated protection of branch protection. Contact closing duration is transfer
time + 500ms.
PSCBO(XF2-1XF2-2)Make contact. If the Single-Circuit-Breaker Close Operation is
permitted, the signal is sent.
RSV1RSV2RSV3RSV4(XF2-3XF2-4, XF2-5XF2-6, XF2-7XF2-8, XF2-9
XF2-10)Make contact. Reserved for future use.
DO Module 1EMDO401
DO Module2EMDO400
CloseStb-L (XE2-1 XE2-2) Standby power LV side close Output. This contact is
current-self-holding mode.
TripStb (XE2-3XE2-4)Standby power trip output. Pickup mode is the same as above.
DEBUGDebug Port. Connected with 232 port .Basically, users can not use it.
DEBUGDebug Port.Connected with 232 port .Basically, users can not use it.
PrintPort1Printer interface.
Test ModuleEMTEST400
For the convenience of on-site testthe device is equipped with a test module.
NoteAfter the test, switches K1~K6 must be turned off and switch K7 is on. Or operators can
plug out the module.
Panel indicators and switches in test module
11
12
Status barIts on the bottom of the whole screen, mainly to show the running status and time
etc. The icons and their meaning in the status bar are shown below:
The master CPU is send oscillagraphic curves to slave CPU.
The communication between master CPU and slave CPU is interrupted.
The number 1,2,3 means running mode 1mode 2 and mode 3 separately.
The device is in blocking status.
Master CPU is implementing transfer operation.
Functions in the shortcut bar correspond with hotkeys (shortcut keys) in the panel. Different
interfaces have different shortcut icons as well as different hotkey functions.
Press any key except Reset and Help to enter Main menu interface.
Generally, Wiring display interface is the suggested default interface.
MFC2000-3A device displays system diagram in graphics stamped with related measured parameters.
In the following diagram, except some real-time measured quantities, the position status of work breaker,
standby breaker and VT isolating switch also are displayed practically.
Note: Standby frequency displayed is either work frequency (fgz) or standby frequency (fby) which
depends on the work breaker status. When the work breaker is closed, standby frequency (fby) is
adopted; when it is open, work frequency (fgz) is adopted.
3.2.1
Main Menu
Enter default interface automatically after the startup, press Cancel key to enter Main menu
interface, see figure 4. Press , , and keys to get to relevant submenu, and then press
OK key or relevant hotkeys to enter the submenu. Press Cancel to return to default interface.
3.2.2
Measure
15
WiringDisp
Wiring(connection) display interface.See Figure 5.
PhaseDisp
Display the relationship between bus voltage and work voltage/standby LV voltage in phase, from
which users can find out the phase angle change between the two voltages easily.
ListDisp
Display the values of measured quantities and DI quantities in table.
3.2.3
Report
Under this submenu, there are 6 items: StateRPT, ActRPT, AbnEvent, RunRecord,
DIRecord and StatiRPT.
Press , , or keys to find the relevant item and then press OK to enter the submenu.
StateRPT
Just as shown in figure 6, transfer blocking/lockout situations and reasons are displayed here.
16
Fault
BSS
Non-Self-Reset
blocking
Realy
VTFL
Transfer
blocking
AftTran
SSUVB
Self-Reset
blocking
ExtTran
Disable
Transfer
IntTran
Methods
Figure7 shows the lockout/blocking logic. Transfer blocking/lockout is a general blocking status.
When any of the following situations occurs, the device enters blocking status and cannot implement
transfer function. The situations include:
1) Relay: relay blocking
2) VTFL: Abbreviation of VT fuse-lose blocking
3) AftTran: Abbreviation of after transfer blocking
4) VTIS: if the VT Isolating switch is open, transfer is blocked.
5) BSS: Abbreviation of breakers same status blocking
6) SSUVB: Abbreviation of standby-source under-voltage blocking
7) Fault: Device fault blocking.
7) ExtTran: External transfer blocking.
8) IntTran: Internal transfer blocking.
9) Methods: All transfer methods blocking.
The above lockout/blocking reasons can be classified as: self-reset lockout/blocking and
non-self-reset lockout/blocking. Self-reset lockout/blocking means when the lockout condition is cleared,
the device can recover to running status automatically; Non-self-reset lockout/blocking means the device
17
can return to running status only by manual reset after lockout condition is cleared.
Self-reset lockout/blocking
SSUVB: when the setting SSUVB is set as Enable, and standby source voltage is lower than
the setting SSUV Vol Amp, the device blocks the transfer.
NoteWhen the setting SSUVB is set as Disable, although the voltage is lower than the
setting SSUV Vol Amp, the transfer function is not blocked, but only Residual-voltage
Transfer or Fixed Time Transfer can be adopted.
ExtTran: if digital input contact TranExit is closed, the transfer function is blocked. If the
contact is open, the device recover running status.
IntTran: if the setting Transfer is set as Disable, the transfer function is blocked.
Methods: All transfer methods are disabledWhen the setting Fast Tran, DIP Lead Phase
Tran, DIP Lead Time Tran, ResVol Tran and Fixed Time Tran are all disabled, the
transfer function is blocked.
Non-self-reset lockout/blocking
FaultWhen device faults are detected in the self-check process, the transfer function is
blocked.
BSSWhen work breaker and standby breaker both are closed or open , the transfer function is
blocked.
RelayWhen external digital input RLYBlock is closed, the transfer function is blocked.
VTFLWhen VT fuse loss is detected through analyzing voltage, the transfer will be blocked.
AftTranOne transfer has been implemented just now, the function will be blocked. Only after
resetting device manually, it can return to running status.
18
ActRPT
24
samples per cycle will be recorded from100ms before initiating to 200ms after initiating, and then, 12
samples per cycle will be recorded for 2 seconds (time from 200ms to 2.2S), afterwards, one effective
value per 10ms is kept for 2.7 seconds.
For Uma, df, Uma, dq, Uma, fm and Uma, df,,dq curve display. One effective value per
10ms will be recorded within 5S, (time from 100ms before initiating to 4.9s after initiating).
In Figure 9, press CHOS CURV hotkey to get a dialog box. Press , and OK keys to
select or cancel a curve display. Only one curve can be displayed one time. After selection, press
Cancel key to return to curve display interface.
19
Note: for convenience of display, the wave of df is magnified 60 times and current wave is magnified
20 times.
Initiating time.
Transfer methodFast, Lead angle, Lead time, Residual voltage transfer and so on
Time, frequency difference, phase difference, bus 3-phase voltage and branch current when
the device is initiated.
Time, frequency difference, phase difference, bus 3-phase voltage and branch current when
tripping command is issued.
Time, frequency difference, phase difference, bus 3-phase voltage and branch current when
breaker is tripped.
Time, frequency difference, phase difference, bus 3-phase voltage and branch current when
closing command is issued.
Time, frequency difference, phase difference, bus 3-phase voltage and branch current when
breaker is closed.
20
These three interfaces and operation are similar, thus we will only take AbnEvent(Abnormal Event)
interface as an example
Users can view latest 72 abnormal events at most. Each screen can display 9 records with event
number, event date and event description etc.
Abnormal events include following types :
(shown on device)
SSUV
Standby-Source Under-Voltage
SSV Normal
BKS Open.E
BKS Closed.E
BKS Closed.CW
BKS Closed.CS
BKS Open.TS
BKS Open.SCBO
VTIS Open
VTFL
VT Fuse-Loss
Device Fault
Abnormal Init
Abnormal Initiated
(shown on device)
Electrify
Electrify Device
Device Reset
Remote Reset
Comm Reset
Communication Reset
21
Modify Setting
Ext Disable Tran
Modify Presicion
Ext Enalbe SCBO
Note: External means operation through digital input contacts, which are controlled by DCS or
console; Internal means operation through device panel, such as Setting interface and so on.
DI(Digital Input) records are corresponding with DI terminals.
StatiRPT
3.2.4 Setting
Setting menu has five screens totally which can be displayed through hotkey operation.
Setting modification procedure
Input the correct password and press OK key to get a dialog box prompting that the
password is correct, and then press any key to cancel the box.
Press and key or PAGE Up or PAGE DOWN key to get to the wanted item.
Press VALU PLU1or VALU RDU1 to change the number and then press OK to
confirm the operation.
3.2.5 Clear
In this menu, you can clear the reports and take Clear Run Record as an example to show the
procedure.
Press CNFM CLER in the shortcut bar to confirm the operation and clear records.
3.2.6 ManTran
Manual transfer, which is bidirectional, can be classified as local and remote manual transfer. Local
manual transfer means to implement transfer operation in the device itself(through ManTran
interface to operate);remote transfer means the operation is implemented in console or DCS system.
Transfer mode includes: Auto parallel transfer, Semi-auto parallel transfer, Sequential transfer and
Simultaneous transfer.
Local semi-auto parallel transfer
Take the transfer from work to standby as an example.
Preparation
Set Local ManTran Mode in Settings submenu as SAuto Parallel(Note: SAuto is the
abbreviation of Semi-auto)
Operation
23
Press EXEC ACT hotkey to close standby breaker, shown in Figure 11. After the
implementation, a successful closing operation message is displayed, if it failed, the transfer is
disabled.
Press EXEC ACT key to trip work breaker, shown in Figure 12.
24
in status bar.
Operation
Press EXEC ACT button. The device will close the standby breaker and trip work breaker at
the same time automatically.
Preparation
Set Control mode in Setting submenu as Remote
25
Operation
Press the button of Manual Initiate in console or DCS system, the standby breaker is closed
automatically.
After confirmation of the closing operation, operator will trip work breaker manually.
Then the LED indicators TRBLOCK and ACT are illuminated, the transfer process is
over.
Preparation
Operation
Press button of Manual Initiate in console or DCS system, the device will issue commands
to close standby breaker and trip work breaker at the same time automatically.
Then the LED indicators TRBLOCK and ACT are illuminated, the transfer process is
over.
These two transfer methods are similar except the setting Remote Tran Group. Take the sequential
transfer from work to standby as an example.
Preparation
Set Control Mode in Setting submenu as Remote.
26
Operation
Press the button of Manual Initiate in console or DCS system, the work breaker is tripped
first and then the standby breaker is closed automatically.
Then the LED indicators TRBLOCK and ACT are illuminated, the transfer process is
over.
3.2.7 DUBUG
There are five items under this submenu: Simulate, SCBO, DI Debug, Precision and Watch
Comm.
Press , , or key to get to the wanted option and press OK key to enter related
interface.
Note: when the device is in debugging status, RUN LED indicator will stop flashing. Remote
resetting command and communication resetting command play no role.
Simulate
Transfer simulation is bidirectional and it used to examine trip-close circuit before the device is
placed into operation.
The process is
Input the correct password and press OK key, in this case, a dialog box will appear
indicating the password is correct, and then press any key to return it.
Press CNFM EXEC hotkey. If the circuit works well, it will return to Tran Success,
otherwise, return to Tran Failure.
27
SCBO
The function of this interface is the simulation of Single-Circuit-Breaker operation. Only one breaker
is involved in SCB Operation each time. The operation process is similar with it of transfer simulation.
DI Debug
It is used to check whether the external Digital Input circuit works well. See the following figure,
White dot means closed, blue dot means open..
Precision
Just as shown in Figure14the function of this interface is to compensate the difference between the
measured value and the real value of voltage, current and phase difference etc, caused by transmission
disturbance or measurement circuit error.
The second row data is benchmark value, the third row is real value. Precision regulation enables the
real value to close to benchmark value.
28
There are two regulation modes: Auto and Manual. Press the hotkey SWTH MODE to choose
regulation mode.
Auto regulation
1. when adjusting, AI inputs should be supplied with rated voltage and current ( phase voltage
is 63.5vline voltage is 110v and current is 5.00A). Work voltage and standby voltage are in
phase.
2. Input the correct password and press OK key.
3. Choose Auto mode.
4. Press OK key. Through the calculation of inner software, the device will adjust the
coefficient automatically.
5. Finish massage will be displayed in the screen after the adjustment.
Manual regulation
1. when adjusting, AI terminals should be supplied with rated voltage and current ( phase
voltage is 63.5vline voltage is 110v and current is 5.00A). Work voltage and standby voltage
are in phase.
2. Input the correct password and then press OK
3. Choose Manual mode.
4. Move the cursor to the wanted value and set the value through VALU PLU1 and VALU
29
RDU1 hotkeys.
Note.dq1 compensates the error caused by measuring the phase difference between
standby branch and bus; dq2 compensates the error caused by measuring the phase
difference between work branch and bus. If these two precisions are to be adjusted, they
should be done in the related status.
Watch Comm
The function of this interface is to watch the communication between the device and external devices.
Its port could be 485 port1, 485 port2, GPS port or inner SPI.
wanted port. Press STOP/BEGN WATH hotkey to stop the process or start the process. Press CLER
SCRN hotkey to clear the screen.
The monitoring interface is divided into two parts. The upper part is to display message received and
the lower part is for message sent. Each message is displayed in two lines, the symbol > means the
displayed message is the current sending/receiving message.
GPS monitoring interface is different from others. When the device receives GPS signals, GPS level
number will be shown in the upper message zone. If the number increases continuously, it means the
GPS port works well; if the number doesnt change, that means the port fails.
30
Advanced function
If operators input super-password (0100) when entering Debug submenu, the shortcut bar will show
ADVS FUCT option. On the option with two items: Reserve and IniEERAM. Reserve interface
is used to set reserved output and signals; IniEERAM interface is used to initialize EERAM, which is
to recover settings and precisions to factory default.
NoteThis advanced function is used for factory debugging, thus users had better not use it,
and otherwise, if the device fails due to this reason, Wiscom do not take any responsibility!
3.2.8 SetSystem
This submenu has seven options: Clock, Password, Comm, Shortcut, DefScrn and
Language.
Press , , and key to get to the wanted option, and press OK to enter the related
interface.
Clock
Set time of device in this interface.
Password
The procedure is as follows
31
Move cursor to New PSW box and input the new password.
Note: 0100 is the super password, thus 0100 is not recommended here.
If users forget their passwords, they can solve the problem as follows:
Move cursor to New PSW box and input the new password.
Comm
The function of this interface is to set device address, communication protocol and baud rate.
Shortcut(Hotkey)
Set shortcut keys(hotkeys) in the main menu interface.
PressSHT CUT4button
DefScrn
The function of this interface is to set default interface. At present the device supplies users with two
default interfaces---Wiring display and System information. Choose the wanted default interface and
press Ok key to save setting.
33
Language
In order to exploit international market, the new generation transfer device supports multi-languages.
Switch between Chinese and English is available.
3.2.9 Print
Print submenu has 6 options: ActReport, AbnEvent, RunRecord, DIRecord Statistic,
Setting.
Press , , and keys to choose the wanted option, and then press OK key to enter the
wanted interface, choose the object and print the content.
If want to print the waveform of action report, users are suggested to download the curves to PC
through MFC2000-3A management software and then print it.
34
4. Setting Report
All settings can be set in LCD display through the buttons according to the menu indication, but
before modification, operators must input correct 4-bit password. The factory default password is 1000
users can set their own password as they like.
4.1 Setpoints
Default values are the reference setpoints when the breaker close time is 65ms. Operators
should regulate them according to the on-site situation
Item
1
Name
Unit
Range
Default
Full Name
Mode1Mode2
Running Mode
10
11
12
13
14
15
UV Init Delay
None
Mode3
Mode1
020
20
Hz
0.020.50
0.50
0.520.0
15.0
0.015.00
0.50
Ms
1500
50
Ms
0120
Hz
0.12.0
1.5
0.560.0
30.0
Hz
0.15.0
5.0
-30-120
-90
Ms
1150
70
2060
2090
0.105.00
35
25
40
1.00
80
ms
200-500
200
2080
60
19
2080
60
20
0.020.0
0.5
Standby-Source
Under-voltage Voltage
Amplitude
Standby-Source
Under-voltage Delay
1st Loadshedding
Voltage
2nd Loadshedding
Voltage
1st Loadshedding Delay
21
0.020.0
9.0
22
23
24
Under-current Value
0.50-2.00
0.50
25
0.5-10.0
9.0
26
0-60
27
0.5-60.0
28
0-20
29
Hz
0.1-2.0
16
17
SSUV Delay
18
5090
0/30.0/60.0/
Compensation Delta
Phase Angle1
Compensation Delta
Phase Angle2
90.0/120.0
0/30.0/60.0/
90.0/120.0
60
30.0
20
1.5
Note:
D(Unit)=Degree
4.2 Controls
Item
Name
Range
Default
Control Mode
RemoteLocal
Remote
SeqSim
Seq
SeqSim
Seq
Auto Par
Seq Sim.
36
Full Name
AutoSemi-auto
Auto
Par Seq
UV Init
Enable, Disable
Enable
Under-voltage Initiating
Fast Tran
Enable, Disable
Enable
Fast Transfer
Enable, Disable
Disable
10
Enable, Disable
Enable
11
ResVol Tran
Enable, Disable
Enable
12
1st Loadshed
Enable, Disable
Disable
13
2nd Loadshed
Enable, Disable
Disable
14
SSUVB
Enable, Disable
Enable
Standby-Source
Under-voltage Blocking
15
Transfer
Enable, Disable
Enable
16
SCBO
Enable, Disable
Disable
17
Under-current CRTA
Enable, Disable
Disable
Single-Circuit-Breaker
Operation
Under-current Criteria
18
Enable, Disable
Disable
19
Enable, Disable
Disable
20
SCB SynClose
Enable, Disable
Disable
Single-Circuit-Breaker
Non-voltage Close
Operation
Single-Circuit-Breaker
Synchronization Close
Operation
Note:
Seq=Seqential
Sim=Simultaneous
Par=Parallel
SAuto=Semi-auto
4.3 Description
Running ModeThere are three setpoints, namely mode 1, mode 2 and mode 3.
ParTran Delta Vol, ParTran Delta Freq, ParTran Delta Phase and ParTran Trip DelayParTran
means Manual Parallel Transfer, the transfer method of which must be Fast Transfer. When
the voltage difference, frequency difference and phase difference between work power and
standby power are lower than their separate setpoints, the device will issue command to close
37
the standby(work) breaker, and after the ParTran Trip Delay time, it will trip the
work(standby) breaker.
SimTran Close DelayUnder simultaneous transfer mode, after the Trip command is issued,
the close command will be sent after this time delay.
Standby Close DelayAfter the command to close the standby high-voltage side breaker is
issued, the command to close the standby Low-voltage side breaker will be issued after this
delayed time.
FastTran Delta Freq and Delta PhaseUnder fast transfer, if the frequency difference and
phase difference between work power and standby power are lower than the two setpoints, the
device will issue Close command. These setpoints are decided by the residual voltage
characteristic and standby breaker closing performance. If users want a high transfer success
rate, the setpoints could be set larger. If users need a high motor security, then the setpoint
should be smaller.
DIP Tran Delta Freq: This is the prerequisite of Lead Phase Transfer. Default is 5HZ.
Lead Phase of DIPIf the frequency difference is lower than the setting DIP Tran Delta
Freq, and the phase angle difference is within this range, the device will issue closing
command. This setting is decided by the residual voltage characteristic and standby breaker
closing performance.
Lead Time of DIPIt depends on the total closing delay of standby breaker.
ResVol Tran Vol AmpUnder residual voltage transfer, if the bus voltage is lower than this
setpoint, the device will issue Close command. Default value is 25.
UV Init Vol Amp and UV Init Delay When the bus voltage is lower than the setpoint and the
duration exceeds the time delay, Under-voltage Initiated Transfer could be implemented.
Default values are 40 and 1s respectively.
SSUV Vol Amp and Delay When the standby source voltage is lower than the set amplitude
and duration exceeds the delayed time, at the same time, the setting SSUVB is enabled, the
device will block the transfer function. The default value is 80and 200ms separately.
1st Loadshed Vol and Delay, 2nd Loadshed Vol and Delay: Whether motors can be started up
successfully after the transfer, is mainly decided by standby transformer capacity, bus voltage
and the amount and capacity of all motors that will self-start. It is helpful to cut off some
38
insignificant motors in order to maintain the continuity of important load. Default values are
60%0.5s609.0s respectively
Comp Delta Phase 1To compensate the phase difference between standby voltage and bus
voltage. Default value is 0. For example, supposed bus voltage and standby voltage are in
phase, if UAN is adopted as standby voltage and bus voltage, then the initial phase angle is
0if UAN and UAB are adopted, the phase angle is -30; while if they are UAC and UAB,
then the phase angle is -60.
Comp Delta Phase 2To compensate the phase difference between work voltage and bus
voltage. Default value is 0.
Fixed Time DelayWhen Fixed Time Transfer is initiated, after this delay time, the device
will issue a Close command without voltage difference, current difference and phase
difference analysis. The default value is 9s.
SCB SynClose Delpha, SCB SynClose DelVol, SCB SynClose DelFreq Under
single-circuit-breaker synchronization close operation, if the phase difference, voltage
difference and frequency difference are smaller than these setpoints, Synchronization Close
operation is satisfied. The default values are 3020and 1.5Hz.
Control ModeWhen it is set as Remote, users can implement operations in console or DCS
system, and the local operations are prohibited. Vice versa. The default value is Remote.
Relay Init Tran ModeThis control word decides the transfer method initiated by external
protection. Default value is Seq.
UV Init Tran ModeThis control word decides the transfer mode initiated by Under-voltage.
Default value is Seq.
Local ManTran modeThis control word decides the local manual transfer mode. The default
value is Auto Par.
39
Remote ParTran ModeThis control word decides the remote manual parallel transfer mode
Auto or Semi-auto. Default value is Auto.
Remote Tran GroupWhen the control word is parallel /sequential, the remote manual transfer
can only be parallel or sequential transfer. When the control word is parallel /simultaneous,
the remote manual transfer can only be parallel or simultaneous transfer. Default value is Par
Seq.
UV InitThis word will decide whether the under-voltage initiated transfer is enabled. Default
value is Enable.
Fast TransferThis word will decide whether Fast Transfer is enabled. Default value is
Enable.
DIP Lead Phase TranIt will decide whether this kind of transfer is enabled, and the default
value is Disable.
DIP Lead Time TranIt will decide whether this kind of transfer is enabled, and the default
value is Enable.
ResVol TranIt will decide whether this kind of transfer is enabled, and the default value is
Enable.
1st Loadshed, 2nd LoadshedIt will decide whether this function is enabled, the default value is
Disable.
TransferWhen it is set as Disable, the transfer function is blocked. The default value is
Enable.
Value, then transfer initiated. Otherwise, transfer can not be initiated even the work breaker
is tripped and the device enters into the status of work fake open.
Fixed Time TranIt will decide whether this kind of transfer is enabled, the default value is
Disable.
SCB Non-Vol CloseThis setpoint will decide whether Non-voltage Close is permitted. The
default value is Disable.
SCB SynCloseThis setpoint will decide whether this Close method is permitted. The default
value is Disable.
41
When the device works normally, only one of the panel indicators WORK or STANDBY
will be illuminated; RUN indicator flashes slowly; REMOTE indicator is on and ACT
and TRBLOCK indicators are off.
Setting: All settings should be consistent with the values shown in setting submenu.
Status barThe clock should work correctly, running mode is consistent with the setpoint and
there should be no lockout icon.
42
Check whether cabinet terminal crews are fixed tightly and fuses are complete.
Turn on the power switch to monitor the +5V15V and +24V powers.
6.1.3 Settings
Press Reset button to check again whether the settings are set correctly.
Regulate voltage inputs to see whether the voltage, current, frequency and phase etc, are
displayed normally.
43
RLYInit. Press the button RLYInit in the debugger manually. If possible, operators can
directly simulate the action of generator-transformer protection and see the result.
RLYBlock. Press the button RLYBlock in the debugger. If possible, operators can directly
simulate the action of branch over-current protection or bus differential protection and see the
result.
ManInit. Press the button ManInit in the debugger. If possible, operate the transfer switch in
console or DCS control terminal directly.
ManMode. Press the button in the debugger. If possible, operate the transfer mode selection
switch in console or DCS control terminal directly.
VTIS. Press the VT isolating switch button in the debugger, if possible, open/close VT
isolating switch in bus directly.
Reset. Press the reset button in the debugger; if possible, operate the reset button in console or
DCS control terminal.
TranExit. Press the button in debugger to enable/disable the transfer function; if possible,
operate in console or DCS control terminal directly.
TripWork
CloseStb-H
CloseWork TripStb
Other outputs
CloseStb-L
44
Fail
TrBlock
TrExit
PWROff
BSS
SSUVB
VTFL
Fault
AAP
LC/RT
PSCBO
6.2.5 Print
Simulate an accident transfer
6.2.6 Completion
45
Implement the transfer from work source to standby source and from standby to work at least
one time separately.
If necessaryamend setpoints.
Confirm that the device is ready( without lockout and alarm indication)
46
6.4.1
Normal Transfer
Implement the transfer from work source to standby source and from standby to work at least
one time separately.
If necessaryamend setpoints.
47
7. Report
7.1 Mark in the above when the test item is finished.
7.2 Reports preparation
z
Appendix 1
Appendix 2
Appendix 3
Appendix 4
Appendix 5
7.3 Others
Client
Generator Unit #
Client representative
Date :
Telephone
Test person
48
segment #
8. Appendix
For the reason of screen size, we adopt abbreviation in some interface. The contrast table is as
flowing:
Abbreviation
Full Name
Tran
Transfer
ManTran
Manual Transfer
SysInfo
System Information
InitTime
Initiated Time
InitMeth
Initiated Method
TranDire
Transfer Direction
TranMeth
TranMethod
Stb
Standby
BLK
block
RLY
Relay
PSW
Password
BSS
TP
Trip
CL
Close
TWC
TSC
LimitT
Limit Time
RVFT
Cond
Condition
ResVol
Residual-voltage
LoadShed
Load Shedding
Int
Internal
Ext
External
Dis
Disable
Mod
Modify
AbnEvent
Abnormal Event
RPT
Report
RTID Time
AAP
49
Comm
Communication
DefScrn
Default Screen
Dev
Device
DISP
Display
PRNT
STAI
Statistic
STAE
State
CANL
Cancel
RPT
Report
SETT
Setting
PREC
Precision
WIRI
Wiring
PHAS
Phase
RCOD
Record
VALU
Value
PLU1
Plus 1
RDU1
Reduce 1
WATH
Watch
CNFM
Confirm
EXEC
Execute
ADVS FUNC
Advanced Function
50