HVAC DESIGN SOLUTIONS

ENGINEERING SOFTWARE

WETSIDE DESIGN
Essential
EssentialDesign
DesignPrograms
Programs
with
withAccurate
AccurateSizing
SizingCalculations
Calculations
help
helpto
toStreamline
StreamlineYour
YourDesign
Design
Copyright 2008 HVAC Design Solutions

Overview

Wetside Design from HVAC Design


Solutions is a package of software programs
for many of the HVAC Designers sizing
tasks:
Hydronic System Sizing -Optimum Sizes
Pump Head Calcs (Primary, Secondary, &
Condenser Water Pumps)
Heating Water Expansion Tank Sizing
Chilled Water Expansion Tank Sizing
Coil Psychrometrics & Coil GPM Calcs
Extensive Help Files, and Extras
Copyright 2008 HVAC Design Solutions

Streamline Your Design

Reduce your dependence on


Reference Books, Charts, Graphs,
and Rules of Thumb.
Eliminate many of the usual HVAC
Design Tasks
Reduce common errors and mistakes
Create an easy-to-follow, step-bystep Procedure for Wetside Design
Software Package contains most of
for all projects.
the sizing calculations and
procedures for typical projects

Copyright 2008 HVAC Design Solutions

Extensive Calculation Programs


CONTENTS
PROJECT INFORMATION

JUMP TO FILE

Any One of these


programs is worth the cost
of the Entire Package!
INDEXP.xls

BASIC PROJECT INPUT SHEET


BUILDING INFORMATION REQUEST LETTER #1
BUILDING INFORMATION REQUEST LETTER #2
CEILING SPACE INFORMATION REQUEST FORM
HEAT/COOL LOAD DESIGN CRITERIA

WET SIDE DESIGN

INDEXP.xls#PROJ.INFO!D2

Bldginfo.xls#'Bldg. Info.'!E11

Bldginfo.xls#'Bldg. Info. 2'!D11

Bldginfo.xls#'Ceiling Space'!D11

LOADCAL.XLS#'Design Criteria'!C5

INDEX2W.xls#INDEX!C10

Quick Links to
all calculation
programs

PIPE SIZING - OPTIMUM ECONOMIC SIZES - SINGLE PIPES

INDEX2W.xls#PIPECALC!H10

PIPE SIZING SCHEDULE - HYDRONIC PIPE SYSTEMS

INDEX2W.xls#PIPESIZE!A13

PRELIMINARY PUMP HEAD CALCULATIONS

INDEX2W.xls#'PUMP-HD.-PRELIM.'!C3

VAV - REHEAT COIL LOAD CALCULATIONS

INDEX2W.xls#'VAV REHEAT'!C6

AIR HANDLING UNIT - PRELIM. COOLING COIL CALCS

INDEX2W.xls#'AHU-COOL. COIL'!H6

AIR HANDLING UNIT - PRELIM. HEATING COIL CALCS

INDEX2W.xls#'AHU-HTG.COIL'!H6

PUMP PRESSURE DROP CALCS - COOLING WATER

INDEX2C.xls#INDEX!C9

PRIMARY PUMP HEAD CALCULATIONS - CHILLED WATER

INDEX2C.xls#'PUMP-CHW-PRIM.'!F15

SECONDARY PUMP HEAD CALCULATIONS - CHILLED WATER

INDEX2C.xls#'PUMP-CHW-SEC.'!F15

PUMP HEAD CALCULATIONS DIAGRAM - CHILLED WATER

INDEX2C.xls#'PUMP-DIAG.'!C2

CONDENSER WATER PUMP HEAD CALCS - COOLING TOWER

INDEX2C.xls#'PUMP-COOL.TOWER'!F15

CHILLED WATER EXPANSION TANK CALCULATIONS

INDEX2C.xls#'EXPTANK-CHW'!B9

PUMP PRESSURE DROP CALCS - HEATING WATER

INDEX2H.xls#INDEX!C9

PRIMARY PUMP HEAD CALCULATIONS - HEATING WATER

INDEX2H.xls#'PUMP-HHW-PRIM.'!F15

SECONDARY PUMP HEAD CALCULATIONS - HEATING WATER

INDEX2H.xls#'PUMP-HHW-SEC.'!F15

PUMP HEAD CALCULATIONS DIAGRAM

INDEX2H.xls#'PUMP-DIAG.'!B2

HEATING WATER EXPANSION TANK CALCULATIONS

INDEX2H.xls#'EXPTANK-HHW'!B9

Copyright 2008 HVAC Design Solutions

Typical Project Startup


"YOUR COMPANY NAME"

BASIC PROJECT INFORMATION

HELP

Begin with Basic Project


Information input

PROJECT NAME :

OAKPARK OFFICE BLDG. 3

PROJECT NUMBER :

134-08

PROJECT LOCATION :
DATE :
TYPE OF BUILDING :

Information automatically
transfers to all programs

CHICAGO, IL
05/06/08
OFFICE

SUMMER OUTDOOR DESIGN DRY BULB TEMP. (DEG. F):

91.0

WINTER OUTDOOR DESIGN DRY BULB TEMP. (DEG. F):

-6.0

INDOOR DESIGN TEMP. - SUMMER (DEG. F) :

75.0

INDOOR DESIGN TEMP. - WINTER (DEG. F) :

70.0

PROJECT ELEVATION (FEET) :

670

PROJECT MANAGER :

BILL REECE

PROJECT ENGINEER :
CLIENT :
CLIENT CONTACT NAME:

Design Conditions are


used in many calculations

JIM EDMOND
ADS ARCHITECTS
JOHN GOREMANN

Copyright 2008 HVAC Design Solutions

Hydronic Pipe Sizing-Optimum Sizes


PIPE SIZING SCHEDULE - OPTIMUM ECONOMICAL SIZES
* NORMAL PIPE SIZING BASED ON:
VELOCITY NOT EXCEEDING 4 FT/SEC. UP TO 2" PIPE
VELOCITY NOT EXCEEDING 10 FT/SEC. FOR LARGER THAN 2" PIPE
PRESSURE DROP BETWEEN 1 AND 5 FT/100 FT.
1/2" TO 3" SIZES ARE COPPER, 4" AND LARGER SIZES ARE STEEL

PIPE SECTION

FLOW RATE
(GPM)

NORMAL
SIZE *
(INCH)

PRINT

PROJECT NAME:
TEST PROJECT #1
PROJECT NUMBER:
1444-07
DATE:
12/19/07
CAUTION: VELOCITY EXCEEDS 10 FT./SEC. - MAY CAUSE NOISE AND EROS
CAUTION: VELOCITY IS LESS THAN 2 FT./SEC. - MAY CAUSE AIR TRAPPING
CAUTION: EXCESSIVE PRESSURE DROP - MAY INCREASE PUMP HORSEPO

NORMAL
VELOCITY
(FT/SEC)

NORMAL
PRESS.
DROP
(FT/100 FT)

LOW FIRST
COST SIZE
(INCH)

LOW FIRST
COST VEL.
(FT/SEC)

FROM

TO

164.0

4.4

1.8

2 1/2

152.0

4.4

1.8

2 1/2

141.5

7.1

5.5

2 1/2

138.0

7.1

5.5

2 1/2

10.1

136.8

7.1

5.5

2 1/2

10.1

121.0

5.9

4.0

2 1/2

96.0

4.7

2.6

5.2

5.1

1 1/2

4.5

5.7

1 1/4

3.1

3.4

8
9
48.5
Quick
and
Easy
Input
9
10
22.3
10

11

12.8

11

12

6.3

3/4
0

LOW FIRST
COST PD
(FT/100 FT)

11.7
20.0
Alternate
11.7
20.0
Pipe
Sizes
10.1
13.0

LOW
LOW
OPERATING OPERATING
COST SIZE
COST VEL.
(INCH)
(FT/SEC)
4

4.4

4.4

4.0

13.0

4.0

13.0

4.0

8.4

8.5

3.3

10.4

17.0

4.7

5.2

5.1

2.4

1 1/4

6.4

13.0

2.6

4.7

9.0

1 1/2

2.2

10.0

1 1/4

1.5

0.0

0.0

10.0
3/4
Most4.0Economical
Pipe 4.0
0.0
0.0
0
0.0
Sizes to meet Sizing Criteria
(Velocity and Pressure Drop)

Copyright 2008 HVAC Design Solutions

Warning Flags for


Alternate Sizes
6

Preliminary Pump Head Calcs


PRELIMINARY PUMP HEAD CALCULATIONS
PUMP CAPACITY (GPM):

164

MAX. PRESSURE DROP (ft./100 ft.):

4.0

MAIN PIPE SIZE (in.):

PRINT

PROJECT NAME:

HELP

TEST PROJECT #1

Preliminary Pump
1444-07Head Calcs, for
DATE:preliminary Pump
12/19/2007
HP requirements
PROJECT NUMBER:

APPROX. HP:

PRESS. DROP PIPE PRESS.


(ft./100 ft.)
DROP (ft.)

5.4

PIPE SIZE

TOTAL PIPE
LENGTH (ft.)

1/2

4.0

0.0

ELL - 90 DEG.

12

18

10.3

3/4

30

4.0

1.2

ELL - 45 DEG.

0.0

4.0

0.0

THRU TEE

3.9

1 1/4

15

4.0

0.6

BRANCH TEE

1.1

1 1/2

25

4.0

1.0

GLOBE VALVE

6.6

25

4.0

1.0

GATE VALVE

0.0

ANGLE VALVE

2 1/2
0
3.0
Quick
and Easy
Input

FITTING OR
VALVE TYPE

NO. OF FITTINGS NO. OF FITTINGS NO. OF FITTINGS FITTING PRESS.


UP TO 2"
2" TO 4"
4" to 10"
DROP (ft)

0
0
Approximate
Fitting0.2
0
0
0.0
and Valve
counts

130

3.0

3.9

SWING CHECK
VALVE

2.3

62

3.0

1.9

LIFT CHECK
VALVE

0.0

2.5

0.0

CONTROL
VALVE

5.3

Copyright 2008 HVAC Design Solutions

Primary Pump Head Calcs - #1


Typical Project Example for
Primary Pump Head Calcs

PRIMARY PUMPS
Copyright 2008 HVAC Design Solutions

Primary Pump Head Calcs - #2


PUMP HEAD CALCULATION - CHILLED WATER - PRIMARY
* PRESSURE DROP BASED ON:
VELOCITY NOT EXCEEDING 5 FT/SEC. UP TO 2" PIPE
VELOCITY NOT EXCEEDING 10 FT/SEC. FOR LARGER THAN 2" PIPE
PRESSURE DROP BETWEEN 1 AND 5 FT/100 FT.
APPROXIMATE PUMP BHP:
(CALCULATED DURING INPUT)

2.5
SIZE
(IN.)

ITEM
LENGTH (FT.)
PUMP ACCESSORIES:

RESET/CLEAR
AVERAGE
NUMBER OF
GPM
FITTINGS (EACH SIZE)

RunningPROJECT
TotalNAME:
of
PROJECT NUMBER:
Approx.DATE:
Pump BHP
9

TEST PROJECT #1
1444-06
2/19/2006

CAUTION : ABOVE OR BELOW NORMAL VELOCITY

VELOCITY
(FT./SEC.)

EQUIVALENT
LENGTH
(FT.)

PRESS.
DROP -EACH
(FT/100 FT.) *

LOSS FOR
SIZE
(FT. HD.)

PUMP FLEX. CONNECTIONS

22

2.6

1.14

CHECK VALVE - LIFT CHECK

84

2.6

2.18

CHECK VALVE - SWING CHECK

0.00

CHECK VALVE - SILENT CHECK

N/A

N/A

0.00

BALANCING VALVE (80% OPEN)

SHUT-OFF VALVE - BUTTERFLY

SHUT-OFF VALVE - GATE

HELP

Easy Input of
N/A
N/A
System
Components
and GPM
Quantities
N/A
N/A
0

TOTAL
LOSS
(FT. HD.)

4.00
2.00
0.00

Copyright 2008 HVAC Design Solutions

Primary Pump Head Calcs - #3


BRANCH TEE - DIVERTING FLOW OR CONVERGING FLOW
(FLOW TURNS 90 DEGREES)
SIZE
TEE #1
3
GPM "IN"
TEE #1
GPM "OUT"
TEE #2
3
GPM "IN"
TEE #2
GPM "OUT"
In
TEE #3
3
GPM "IN"
TEE #3
GPM "OUT"
Out
TEE #4
3
GPM "IN"
TEE #4
GPM "OUT"
TEE #5
3
GPM "IN"
TEE
#5
GPM
"OUT"
Out
TEE #6
0
GPM "IN"
TEE #6
GPM "OUT"
In
TEE #7
0
GPM "IN"
TEE #7
GPM "OUT"
TEE #8
0
GPM "IN"
TEE #8
GPM "OUT"
TEE #9
0
GPM "IN"
TEE #9
GPM "OUT"
TEE #10
0
GPM "IN"
TEE #10
GPM "OUT"

GPM
160
120
120
160
120
160
120
120
120
120
0
0
0
0
0
0
0
0
0
0

VEL.
8

EQ. LEN.
21.39

FT/100 FT.
7

1.50

16.91

0.68

16.91

0.68

16.91

0.68

16.91

0.68

THRU TEE - CONVERGING FLOW


(FLOW STRAIGHT THRU)
TEE #1
TEE #1
TEE #2
TEE #2
In
Out
TEE #3
TEE #3
TEE #4
TEE #4
TEE #5
TEE #5

GPM
120
160
120
160
0
0
0
0
0
0

VEL.
6

EQ. LEN.
8.9

FT/100 FT.
4

0.36

8.9

0.36

0.00

0.00

0.00

Easy Input of System


Components and
GPM Quantities
SIZE
3
3
0
0
0

GPM "IN"
GPM "OUT"
GPM "IN"
GPM "OUT"
GPM "IN"
GPM "OUT"
GPM "IN"
GPM "OUT"
GPM "IN"
GPM "OUT"

Built-in Fitting
Coefficients
0

0.00

0.00

0.00

0.00

0.00

4.20

Copyright 2008 HVAC Design Solutions

10

Primary Pump Head Calcs - #4


CHILLER EQUIPMENT:

VEL.

EQ. LEN.

FT/100 FT.

N/A

N/A

0.60

0.00

0.00

ISOLATION VALVE - ANGLE

0.00

ISOLATION VALVE - BALL

0.00

Y-TYPE STRAINER

CHILLER AUTOMATIC ISOLATION VALVE


(AUTOMATIC GLOBE VALVE)
0

130.5

2.6

3.39

CHILLER FLEX. CONNECTION

22

2.6

1.14

ISOLATION VALVE - BUTTERFLY

ISOLATION VALVE - GATE

ISOLATION VALVE - GLOBE

N/A
0.80
Allowance
forN/AItems at
Chiller or Boiler

5.94
CHILLER PRESSURE DROP (FROM MANUFACTURER, IF KNOWN) :
GENERIC CHILLER PRESSURE DROP (IF NOT AVAIL. FROM MFG'R.) :
CHILLER TONS :
100
CHILLER GPM :
120

Generic Values Built-in


(Conservative) if Mfgrs.
Data Unknown

AIR CONTROL AND FLOW METERS:


AIR SEPARATOR PRESSURE DROP (FROM MANUFACTURER, IF KNOWN) :

GENERIC AIR SEPARATOR PRESSURE DROP - WITH STRAINER (IF NOT AVAIL. FROM MFG'R.) :
SIZE : 2 0
GPM :
160

Copyright 2008 HVAC Design Solutions

4.20
4.20
0

11.05

11

Primary Pump Head Calcs - #5


PIPE LOSSES (MEASURE "OUT & BACK" TO PUMP) :
SIZE
NUMBER
LENGTH (FT.)
(IN.)
COPPER PIPE :
0
1/2
N/A
COPPER PIPE :
0
3/4
N/A
COPPER PIPE :
0
1
N/A
COPPER PIPE :
0
1 1/4
N/A
COPPER PIPE :
0
1 1/2
N/A
COPPER PIPE :
0
2
N/A
COPPER PIPE :
0
2 1/2
N/A
COPPER PIPE :
150
3
N/A
COPPER PIPE :
0
4
N/A

GPM

VELOCITY
(FT./SEC.)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
8.0
0.0

EQ. LEN.

0
0
0
0
0
0
0
0
0
0
0
0
0
0
160
150
0
0
0
STEEL PIPE :
0
1/2
N/A
0
0.0
0
STEEL PIPE :
0
3/4
N/A
0
0.0
0
STEEL PIPE :
0
1
N/A
0
0.0
0
STEEL PIPE :
0
1 1/4
N/A
0
0.0
0
STEEL PIPE :
0
1 1/2
N/A
0
0.0
0
STEEL PIPE :
0
2
N/A
0
0.0
0
STEEL PIPE :
0
2 1/2
N/A
0
0.0
0
STEEL PIPE :
0
3
N/A
0
0.0
0
SUB-TOTAL
PRESSURE
STEEL PIPE :
0
4
N/A
0
0.0 DROP (FT.
0 HEAD) :
STEEL PIPE :
0
5
N/A
0
0.0
0
GLYCOL
PRESSURE
DROP0CORRECTION
ON 50 DEGREE
F WATER
:
STEEL PIPE
:
6 (IF ANY) - BASED
N/A
0
0.0 TEMPERATURE
0

Adjustments for
Glycol (if applicable)
and/or Safety Factor

PERCENT GLYCOL, BY WEIGHT :

PRESS.
DROP
(FT/100 FT.) *
0.0
0.0
0.0
0.0
0.0
0.0
0.0
7.0
0.0

Imput Length of
Longest Run Piping
(Measured Out &
0.0
0.00
Back to Pump)
0.0
0.00
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

TOTAL
LOSS
(FT. HD.)

10.50

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Final, Totalized Primary


55.25
Pump Head (Ft.) for the
System

GLYCOL CORRECTION FACTOR :

CORRECTED SUB-TOTAL PRESSURE DROP (FT. HEAD) :


PRESSURE DROP SAFETY FACTOR (IF ANY) - RECOMMEND 5% = 1.05

LOSS FOR
SIZE
(FT. HD.)
0.00
0.00
0.00
0.00
0.00
0.00
0.00
10.50
0.00

1
55.25

1.05

TOTAL PUMP PRESSURE DROP (FT. HEAD):

58.01

Copyright 2008 HVAC Design Solutions

12

Primary Pump Head Calcs - #6


PUMP HEAD CALCULATION - CHILLED WATER - PRIMARY
2007 hvacdes igns olutions .com
* PRESSURE DROP BASED ON:
VELOCITY NOT EXCEEDING 5 FT/SEC. UP TO 2" PIPE
VELOCITY NOT EXCEEDING 10 FT/SEC. FOR LARGER THAN 2" PIPE
PRESSURE DROP BETWEEN 1 AND 5 FT/100 FT.

PROJECT NAME:
PROJECT NUMBER:
DATE:
9

APPROXIMATE PUMP BHP:

TEST PROJECT #1
1444-06
2/19/2006

CAUTION: ABOVE OR BELOW NORMAL VELOCITY

2.5

(CALCULATED DURING INPUT)


ITEM
NAME
LENGTH (FT.)

(IN.)

EQUIVALENT
(FT.)

PRESS.
(FT/100 FT.)

LOSS FOR
(FT. HD.)

PUMP FLEX. CONNECTIONS

120

CHECK VALV E - LIFT CHECK

120

22

2.6

1.14

84

2.6

BALANCING VALVE (80% OPEN)

2.18

160

N/A

N/A

SHUT-OFF VALVE - BUTTERFLY

4.00

160

N/A

N/A

TRIPLE DUTY VALVE -STRAIGHT

2.00

120

N/A

N/A

TRIPLE DUTY VALVE -ANGLE

1.20

N/A

N/A

0.00

FITTINGS

AVERAGE
(EACH SIZE) (FT./SEC.)

STANDARD 90 DEG. ELBOW


3
5
160.0
8
9.3
7
3.26
STANDARD 90 DEG. ELBOW
12
0
0.0
0
0
0
0.00
THRU TEE - DIVERTING FLOW
3
GPM "IN"
160.0
8
1.86
7
0.13
TEE #2
3
GPM "IN"
160.0
8
1.86
7
0.13
TEE #3
3
GPM "IN"
160.0
8
1.86
7
0.13
TEE #4
3
GPM "IN"
120.0
6
0.89
4
0.04
TEE #5
3
GPM "IN"
120.0
6
0.89
4
0.04
TEE #10
0
GPM "OUT"
0.0
0
0
0
0.00
BRANCH TEE - DIVERTING FLOW OR
3 CONVERGING
GPM "IN"
FLOW 160.0
8
21.39
7
1.50
TEE #2
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #3
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #4
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #5
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #10
0
GPM "OUT"
0.0
0
0
0
0.00
THRU TEE - CONVERGING FLOW
3
GPM "IN"
120
6.0
8.90
4
0.36
TEE #2
3
GPM "IN"
120
6.0
8.90
4
0.36
TEE #10
0
GPM "OUT"
0
0.0
0.00
0
0.00
ISOLATION VALVE - BUTTERFLY
3
2
120
5.0
N/A
N/A
0.60
Y-TYPE STRAINER
3
1
120
5.0
N/A
N/A
0.80
(AUTOMATIC GLOBE VALVE)
3
1
120
5.0
130.50
3
3.39
CHILLER FLEX. CONNECTION
3
2
120
5.0
22.00
3
1.14
GENERIC CHILLER PRESSURE DROP (IF NOT AVAIL. FROM
CHILLER
MFG'R.)
TONS
:
100.0
:
CHILLER GPM :
120
4.20
GENERIC AIR SEPARATOR PRESSURE DROP - WITH STRAINER
SIZE (IF
:
NOT AVAIL.
0.0
FROM
GPM
MFG'R.)
:
:
160
11.05
GENERIC AIR SEPARATOR PRESSURE DROP - WITHOUT STRAINER
SIZE :
(IF NOT
0.0 AVAIL. FROM
GPM :MFG'R.) : 0
0.00
GENERIC FLOW METER PRESSURE DROP (IF NOT AVAIL. FROM
SIZE : MFG'R.)0.0
:
GPM :
160
3.50
GENERIC SUCTION DIFFUSER PRESSURE DROP (IF NOT AVAIL.
SIZE :FROM MFG'R.)
0.0
:
GPM :
120
0.90
COPPER PIPE :
150
3
N/A
160.0
8.0
150
7.0
10.50
COPPER PIPE :
0
4
N/A
0.0
0.0
0
0.0
0.00
SUB-TOTAL PRESSURE DROP (FT. HEAD) :
PERCENT GLYCOL, BY WEIGHT :
0
GLYCOL CORRECTION FACTOR :
1
CORRECTED SUB-TOTAL PRESSURE DROP (FT. HEAD) :
PRESSURE DROP SAFETY FACTOR (IF ANY) - RECOMMEND 5% = 1.05 1.05
1.05
TOTAL PUMP PRESSURE DROP (FT. HEAD):

After Input is complete, press Compile


& Print Button for full System Report

Copyright 2008 HVAC Design Solutions

LOSS
TOTAL

10.53
3.26

0.46

4.20

0.71

5.94
4.20
11.05
3.50
0.90
10.50
55.25
55.25
58.01

13

Coil Psychrometrics Calcs


AIR HANDLING UNIT - PRELIMINARY COOLING COIL LOAD CALCULATIONS
OA DESIGN DB =
OA DESIGN WB =
DESIGN ROOM TEMP. =

91
74
75

PROJECT ELEVATION =
CHILLED WATER DELTA-T =

670
10

RESET/CLEAR

RETURN AIR ENTERING AIR

PROJECT NAME:

TEST PROJECT #1

PROJECT NUMBER:

1456-07

DATE:

06/21/07

AHU

COOLING

SUPPLY

MINIMUM

LEAVING AIR

COOLING

CHILLED

FLOOR

CFM PER

NUMBER

LOAD *

AIR TEMP.

OUTSIDE AIR

QUANTITY

TEMP.

ENTHALPY

ENTHALPY

ENTHALPY

ENTHALPY

COIL LOAD

WATER

AREA

SQ. FT.

(MBH)

(F)

(CFM)

(CFM)

(F)

(BTU/LB.)

(BTU/LB.)

(BTU/LB.)

(BTU/LB.)

(MBH)

(GPM)

(SQ. FT)

12.5
18.2
46.3
244.8
42.0
121.7
24.5
205.9
105.5
33.6
19.5
150.3

54.0
54.0
54.0
54.0
54.0
54.0
54.0
54.0
54.0
54.0
54.0
54.0

150
320
1550
5500
1480
2640
450
5120
2200
1250
250
2850

590
859
2186
11556
1983
5745
1157
9720
4980
1586
921
7095
0
0
0
0

78.0
78.0
78.0
78.0
78.0
78.0
78.0
78.0
78.0
78.0
78.0
78.0
0.0
0.0
0.0
0.0

37.7
37.7
37.7
37.7
37.7
37.7
37.7
37.7
37.7
37.7
37.7
37.7
0.0
0.0
0.0
0.0

30.2
30.2
30.2
30.2
30.2
30.2
30.2
30.2
30.2
30.2
30.2
30.2
0.0
0.0
0.0
0.0

32.1
33.0
35.5
33.8
35.8
33.6
33.1
34.2
33.5
36.1
32.2
33.2
0.0
0.0
0.0
0.0

21.7
21.7
21.7
21.7
21.7
21.7
21.7
21.7
21.7
21.7
21.7
21.7
0.0
0.0
0.0
0.0

26.1
41.1
126.6
586.9
117.2
289.6
55.7
509.2
248.2
95.8
41.2
344.7
0.0
0.0
0.0
0.0

5.2
8.2
25.3
117.4
23.4
57.9
11.1
101.8
49.6
19.2
8.2
68.9
0.0
0.0
0.0
0.0

400
650
2000
12950
1820
4800
820
11200
4280
1500
700
6200

1
2
3
4
5
6
7
8
9
10
11
12

SUPPLY AIR RETURN AIR OUTSIDE AIR

PRINT

HELP

Psychrometric Calculations Assist with


Preliminary Equipment Selection,
Preliminary Pump Sizing, Etc.

Copyright 2008 HVAC Design Solutions

1.5
1.3
1.1
0.9
1.1
1.2
1.4
0.9
1.2
1.1
1.3
1.1
0.0
0.0
0.0
0.0

14

Heating Water Expansion Tank


EXPANSION TANK SIZING - HEATING WATER
MINIMUM WATER TEMP. (DEG. F):

40

PROJECT NAME:

HEATING WATER TEMP. (DEG. F):

200

PROJECT NUMBER:

PROJECT ELEVATION (ft.)

670

PRINT

TOTAL PIPE
LENGTH (ft.)

GALLONS PER
FOOT

PIPE GALLONS

0.0121

0.0

PIPE SIZE
1/2

DATE:

120

0.0251

3.0

60

0.0429

2.6

BOILER MBH

0.0653

1 1/2

# HEATING COILS
75

0.0924

# HEAT EXCHANGERS
224

0.1610

450
18
1

TEST PROJECT #1
1444-07

Heating Water and Chilled


Water Expansion Tank
Sizing Programs
12/19/2007

3/4

1 1/4

HELP

337.5

0.0

COIL
GALLONS
36.0

6.9

EXCHANGER
GALLONS
15.0

36.1

TOTAL CONTENT (gal.)

490.2

GLYCOL % (IF APPLICABLE)

10

(PERCENT BY VOLUME) ENTER 0 IF NO GLYCOL IN SYSTEM

EXPANSION FACTOR

0.03510

(BASED ON HEATING WATER TEMP. MINUS MINIMUM WATER TEMP.)

EXPANDED WATER VOLUME (gal.)

20.8

HEIGHT OF SYSTEM (ft.)

45

RELIEF VALVE SETTING (psi)

30

ACCEPTANCE FACTOR

0.06

TANK VOLUME (gal.)

353.8

Built-in Water Volumes,


Expansion Factors,
Acceptance Factors, and
Expansion Formulas

24.6

(SYSTEM PRESSURE)

CAUTION: RELIEF VALVE SETTING MUST BE LARGER THAN


REQUIRED SYSTEM PRESSURE

30
27

0.94
ACCEPTANCE VOLUME MUST EXCEED EXPANDED WATER VOLUME (gal.)

Copyright 2008 HVAC Design Solutions

15

Project Information Request Letters


BUILDING MECHANICAL INFORMATION REQUEST
PROJECT NAME:

TEST PROJECT #1

PROJECT NUMBER:

1456-07

HELP
DATE:

06/21/07

BUILDING MECHANICAL ROOM INFORMATION REQUEST FORM


PROJECT NAME:

TEST PROJECT #1

DATE:

HELP

06/21/07

PROJECT NUMBER: 1456-07

REQUESTED BY:

Please provide the following information, to expedite our design of your project. It is very important that
you respond as soon as possible, with as accurate information as you have available, so we can
calculate the correct air conditioning requirements and make accurate equipment selections.
A. Please provide the number of people, heat output or amperage and voltage of equipment, and any
other element that might effect the HVAC load in the following areas:

REQUESTED BY:

ROOM NAME/NUMBER:
NUMBER OF PEOPLE
PEOPLE ACTIVITY LEVEL: (S) - Seated Office; (M) - Moderate Office; (W) - Walking or
Standing; (B) - Bench Work; (H) Heavy Work

1. All Offices
2. Conference Rooms
3. Photocopy machine rooms
4. Lounge and/or lunch rooms
5. Electrical equipment rooms
6. Computer Rooms
7. Procedure Rooms

Programming
Information Request
Forms for Owner or
Architect Input

HEAT PRODUCING EQUIPMENT (Please Indicate Quantity Below)


PC Stations

Laser Printers

Photocopy Machines

Fax Machines

Microwaves

TV Sets or Monitors

Refrigerators (Small S, Large L)

Vending Machines

Coffee Makers
Special Lighting (Total Watts to Room)

8. Other specialty rooms

Special Equipment (Total Watts to Room)

The above information should include: PC Stations, Laser Printers, Fax Machines, Photocopy
Machines, Microwaves, Vending Machines, Refrigerators, Coffee Makers, Special Lighting, etc. If
available, this information should contain: quantity, location, BTU/hr, wattage, amperage, voltage,
heat output to the space, operating cycle time, etc.

Exposed Motors in Room (Horsepower)

NO HEAT PRODUCING EQUIPMENT IN THIS ROOM

B. Please indicate any special HVAC requirements such as areas requiring:


1. 24 Hour Air Conditioning
2. Relative Humidity Controls

SPECIAL OPERATING CONDITIONS


24 Hour Air Conditioning Required

Copyright 2008 HVAC Design Solutions

16

Mechanical Peer Review Software


Coordination Between Disciplines
Contents:
A
B
C
D
E
F
G
H
A

(Click on hyperlink to jump to the sheet checklist)

Preliminary Review of Plans and Specifications


Demolition Plans
Arc hitect and/or Owner Coordination
Structural Coordination
Mechanical Coordination
Plumbing Coordination
Civil Engineering Coordination
Electrical Coordination

Preliminary Review of Plans and Specifications


1 Quickly review all Drawings in the Construction Document set, including Architectural,
Structural, Civil, Landscaping, Mechanical, Plumbing, Fire Protection, Electrical, Food
Service, and any other discipline. Spend not more than one minute per sheet, average.
2 Make a list of any apparent discrepancies or questions while reviewing the set, and add
flags to sheets where there are significant questions.
3 Quickly review the Specifications by reading through the Table of Contents for
Mechanical and Plumbing work. Check the Table of Contents against the actual
Specification sections to verify all sections have been included. Make a list of questions
that may come up during the cursory review.
4 Review Architectural T itle Sheet, or first sheet in the set, and make a list of the Project
Square Footage, Building Occupancy Type, Building Construction Type, Governing
Codes, Index of Drawings, and any other information that relates to Mechanical or
Plumbing work.
5 Check for consistent appearance of Title Blocks, Drawing Scales, North Arrows,
Professional Stamps, Company Logos, Sheet Numbers, Sheet Titles, Issue Dates, and
Issue Revisions on all sheets.
Demolition Plans
1 Verify that Demolition Symbols (cross-hatching, etc.) are clear and complete, and are
coordinated with other disciplines.
2 Verify there are notes regarding potential hazardous materials (asbestos, lead paint,
etc.), and coordinate with Architect or other Prime Consultant and Owner.

Copyright 2008 HVAC Design Solutions

Extensive Quality
Control Mechanical
Checklists are available
in a separate Mechanical
Peer Review Software
Package

Over (110) Pages of


Checklists and
Spreadsheets for a
thorough review of
Mechanical Construction
Documents
17

Mechanical Peer Review Software


A

Return to Table of Contents


Mechanical Piping Plans
1 Sum all Chilled Water Supply and Return quantities (GPMs) from coils back to service
connection or pumps. Pencil in quantities adjacent to pipes. Verify flow rates are listed
for all coils or equipment, and that Schedules for each device are complete. Check flow
direction Arrows for completeness and correct direction.
2
Sum
Heating
Supplychecklist)
and Return quantities (GPMs) same as Chilled Water.
Contents:
(Click on hyperlink
toalljump
to Water
the sheet
Pencil in quantities. Verify Schedule information is complete. Check flow direction
Arrows.
A Preliminary Review of Plans and 3Specifications
Check for provisions for Water Balancing on plans or on details of coil connections.
4 Check for Isolation Valves to allow servicing without shutting down and draining entire
B Legend and Symbols Sheet
systems.
C Schedule Sheets
5 Verify whether Direct-return or Reverse-return piping. Suggest Reverse-return for better
D Mechanical Demolition Plans
water balancing, if appropriate.
E Mechanical Ductwork Floor Plans6 Check provisions for Condensate Drains. Coordinate with Plumbing drawings for piping
and Approved Disposal methods.
F Mechanical Piping Plans
7 Check on provisions for Air Venting and Drainage on Coil Piping Details and plans.
G Mechanical Roof Plans
8 Check Thermostat locations (if thermostats are shown on Piping Plans) and verify all
heating and cooling elements have a corresponding Thermostat or Sensor Control.
H Mechanical Central Plant Plans
9 Spot-check pipe sizes against totalized water quantities. Use maximum of 4 ft. per 100 ft.
Clean Room and Fabrication Facilities
I
pipe friction, up to 5 pipe size, and maximum of 8 ft. per second Velocity for pipe 6 and
J Mechanical Piping Diagrams
larger.
K Mechanical Control Drawings 10 Check for provisions for Pipe Expansion Pipe Loops, adequate turns (less than 50 feet
of straight pipe), or expansion devices.
L Mechanical Detail Drawings
11 Check for restrictions to pipe movement against columns, against solid walls, drops or
rises to adjacent floors.
12 Verify that pipes are not run through Stairwells, Elevator Shafts, Columns, or Electrical
Rooms.
13 Compare Totalized water quantities with associated Pumps, and analyze diversity if totals
are not equal.
14 Verify that all pipes are sized.
15 Coordinate Pipe plans with Ductwork plans and identify any potential conflicts.

Mechanical Plan Review Items

Example of Quality
Control Check List
Items

Copyright 2008 HVAC Design Solutions

18

Calculation Documents
PUMP HEAD CALCULATION - CHILLED WATER - PRIMARY
2007 hvacdes igns olutions .com
* PRESSURE DROP BASED ON:
VELOCITY NOT EXCEEDING 5 FT/SEC. UP TO 2" PIPE
VELOCITY NOT EXCEEDING 10 FT/SEC. FOR LARGER THAN 2" PIPE
PRESSURE DROP BETWEEN 1 AND 5 FT/100 FT.

PROJECT NAME:
PROJECT NUMBER:
DATE:
9

APPROXIMATE PUMP BHP:

TEST PROJECT #1
1444-06
2/19/2006

CAUTION: ABOVE OR BELOW NORMAL VELOCITY

2.5

(CALCULATED DURING INPUT)


ITEM
NAME
LENGTH (FT.)

(IN.)

EQUIVALENT
(FT.)

PRESS.
(FT/100 FT.)

LOSS FOR
(FT. HD.)

PUMP FLEX. CONNECTIONS

120

CHECK VALV E - LIFT CHECK

120

22

2.6

1.14

84

2.6

BALANCING VALVE (80% OPEN)

2.18

160

N/A

N/A

SHUT-OFF VALVE - BUTTERFLY

4.00

160

N/A

N/A

TRIPLE DUTY VALVE -STRAIGHT

2.00

120

N/A

N/A

TRIPLE DUTY VALVE -ANGLE

1.20

N/A

N/A

0.00

FITTINGS

AVERAGE
(EACH SIZE) (FT./SEC.)

STANDARD 90 DEG. ELBOW


3
5
160.0
8
9.3
7
3.26
STANDARD 90 DEG. ELBOW
12
0
0.0
0
0
0
0.00
THRU TEE - DIVERTING FLOW
3
GPM "IN"
160.0
8
1.86
7
0.13
TEE #2
3
GPM "IN"
160.0
8
1.86
7
0.13
TEE #3
3
GPM "IN"
160.0
8
1.86
7
0.13
TEE #4
3
GPM "IN"
120.0
6
0.89
4
0.04
TEE #5
3
GPM "IN"
120.0
6
0.89
4
0.04
TEE #10
0
GPM "OUT"
0.0
0
0
0
0.00
BRANCH TEE - DIVERTING FLOW OR
3 CONVERGING
GPM "IN"
FLOW 160.0
8
21.39
7
1.50
TEE #2
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #3
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #4
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #5
3
GPM "IN"
120.0
6
16.91
4
0.68
TEE #10
0
GPM "OUT"
0.0
0
0
0
0.00
THRU TEE - CONVERGING FLOW
3
GPM "IN"
120
6.0
8.90
4
0.36
TEE #2
3
GPM "IN"
120
6.0
8.90
4
0.36
TEE #10
0
GPM "OUT"
0
0.0
0.00
0
0.00
ISOLATION VALVE - BUTTERFLY
3
2
120
5.0
N/A
N/A
0.60
Y-TYPE STRAINER
3
1
120
5.0
N/A
N/A
0.80
(AUTOMATIC GLOBE VALVE)
3
1
120
5.0
130.50
3
3.39
CHILLER FLEX. CONNECTION
3
2
120
5.0
22.00
3
1.14
GENERIC CHILLER PRESSURE DROP (IF NOT AVAIL. FROM
CHILLER
MFG'R.)
TONS
:
100.0
:
CHILLER GPM :
120
4.20
GENERIC AIR SEPARATOR PRESSURE DROP - WITH STRAINER
SIZE (IF
:
NOT AVAIL.
0.0
FROM
GPM
MFG'R.)
:
:
160
11.05
GENERIC AIR SEPARATOR PRESSURE DROP - WITHOUT STRAINER
SIZE :
(IF NOT
0.0 AVAIL. FROM
GPM :MFG'R.) : 0
0.00
GENERIC FLOW METER PRESSURE DROP (IF NOT AVAIL. FROM
SIZE : MFG'R.)0.0
:
GPM :
160
3.50
GENERIC SUCTION DIFFUSER PRESSURE DROP (IF NOT AVAIL.
SIZE :FROM MFG'R.)
0.0
:
GPM :
120
0.90
COPPER PIPE :
150
3
N/A
160.0
8.0
150
7.0
10.50
COPPER PIPE :
0
4
N/A
0.0
0.0
0
0.0
0.00
SUB-TOTAL PRESSURE DROP (FT. HEAD) :
PERCENT GLYCOL, BY WEIGHT :
0
GLYCOL CORRECTION FACTOR :
1
CORRECTED SUB-TOTAL PRESSURE DROP (FT. HEAD) :
PRESSURE DROP SAFETY FACTOR (IF ANY) - RECOMMEND 5% = 1.05 1.05
1.05
TOTAL PUMP PRESSURE DROP (FT. HEAD):

LOSS
TOTAL

10.53
3.26

0.46

4.20

After completing input and


calculations, Output and
Sizing Documents can be
printed for submittal to
building department
officials and for addition to
drawings and schedules

Copyright 2008 HVAC Design Solutions

0.71

5.94
4.20

11.05
3.50
0.90
10.50
55.25
55.25
58.01

19

Software Contents
PIPECALC

PIPE SIZING CALCULATOR- OPTIMAL ECONOMIC


SIZING

PUMP-CHW-PRIM.

PRIMARY CHILLED WATER PUMP HEAD


CALCULATIONS

PIPESIZE

PIPE SIZING SCHEDULE - OPTIMAL ECONOMIC


SIZING

PUMP-CHW-SEC.

SECONDARY CHILLED WATER PUMP HEAD


CALCULATIONS

PUMP HEAD CALCULATIONS DIAGRAM

PRELIMINARY PUMP HEAD CALCULATIONS

PUMP-DIAG.

VAV - REHEAT COIL LOAD CALCULATIONS

PUMP-COOL.TOWER

PUMP-HD.-PRELIM.
CONDENSER WATER (COOLING TOWER) PUMP
HEAD CALCULATIONS

VAV REHEAT

AHU-COOL. COIL

AHU - PRELIMINARY COOLING COIL LOAD


CALCULATIONS

AHU-HTG.COIL

AHU - PRELIMINARY HEATING COIL LOAD


CALCULATIONS

Bldg. Info.

BUILDING MECHANICAL INFORMATION REQUEST


FORM

EXPTANK-CHW

PUMP-HHW-PRIM.

PUMP-HHW-SEC.

Extensive Wetside
Programs to help
PRIMARY HEATING WATER PUMP HEAD
Streamline your
CALCULATIONS
Design Procedures
CHILLED WATER EXPANSION TANK
CALCULATIONS

SECONDARY HEATING WATER PUMP HEAD


CALCULATIONS

PUMP HEAD CALCULATIONS DIAGRAM

Bldg. Info. 2

BUILDING MECHANICAL ROOM INFORMATION


REQUEST FORM

CEILING SPACE INFORMATION REQUEST FORM

Ceiling Space

PUMP-DIAG.

EXPTANK-HHW

HEATING WATER EXPANSION TANK


CALCULATIONS

Copyright 2008 HVAC Design Solutions

20

Features and Benefits

Straightforward takeoff and input allows


easy calculation and sizing of Wetside
Systems.
Extensive procedures, formulas, charts,
and tables as prescribed by Mechanical
Codes and as recommended by ASHRAE
and Equipment Manufacturers have been
included and have been used to establish the
Accurate Wetside System Sizes.
Multiple Programs are included, covering
most of the typical Wetside Design Tasks for
most projects.
Copyright 2008 HVAC Design Solutions

21

Features and Benefits

Significantly reduces Reference


Material Dependence which can save a
great deal of time and effort.
Output in the form of Compliance
Documents or System Sizing
Summaries for submittal to appropriate
code enforcement officials or building
departments.
Extensive Help Files that are
hyperlinked to each program, form, or table.
Copyright 2008 HVAC Design Solutions

22

Pricing

Limited time Special Pricing available at


our website
www.hvacdesignsolutions.com
Wetside Design Package
Original Price: $225 US, Special Price:
$169 US
Mechanical Peer Review Package
Original Price: $275 US, Special Price:
$198 US
Copyright 2008 HVAC Design Solutions

23

Availability

Current Version: 2.12, with latest update


(08/24/2008) Free updates, as available.
To purchase Wetside Design or
Mechanical Peer Review, visit our website
at www.hvacdesignsolutions.com and go
to the Prices/Orders page
Software can be downloaded for
immediate installation (with password)
after purchase is confirmed
Copyright 2008 HVAC Design Solutions

24

System Requirements

OS: Windows 98, 2000, XP, 2003, Vista


Processor: Pentium or equivalent
Ram: 512MB (minimum recommended)
Disk Space: 100 MB (recommended)
Software: MS Word, MS Excel

Copyright 2008 HVAC Design Solutions

25

Thanks!

Thank you for taking your time to


review our Wetside Design software
packages
If you have any questions or
comments, you can e-mail to:
steveathvacdesignsolutions.com , or
supportathvacdesignsolutions.com
We also have an interactive demo of
our Wetside Design software that can
be delivered, on request, via e-mail.
Copyright 2008 HVAC Design Solutions