RECORD DRAWINGS

NET ACCESS MMU


9 WING DRIVE
CEDAR KNOLLS, NJ

Prepared By:
Mike Konzelman
Sales Engineer
800 Shrewsbury Ave.
Tinton Falls, NJ 07724
Ph: (732) 741-3866
Fax: (732) 741-3866
E-mail:
MikeK@Warshauer.com

Warshauer Generator Division


Project: 79-9422-B
Prepared By: Mike Konzelman

NET ACCESS MMU


CEDAR KNOLLS, N.J.
Submittal Contents Listing
Bill of Material.

1-4

MD 600 Data Sheets ...

5-8

MD 600 Alternator Data Sheet .

MD 600 Footprint Drawing .....

10

Digital Controller Brochure ..

11 - 14

Run Relay Data Sheet .

15

Voltage Regulator Data Sheet

16 - 17

Single Line Drawing .

18

Engine Schematic Drawing .

19 - 20

Engine Wiring Drawing .

21 - 23

Operator Interface: Schematic Diagram

24

Operator Interface: Wiring Diagram ..

25

PM-SC Brochure ..

26 - 29

System Controller Schematic Diagram .

30 - 31

System Controller Wiring Diagram .

32 - 33

PM-SC / DCP Interconnect ..

34

PM-SC Installation Drawing .

35

Paralleling Switch Brochure .

36

Redundant Controller Brochure ..

37 - 38

Redundant Controller Wiring

39

Redundant Controller Interface

40

Circuit Breaker Data Sheets ....

41 - 46

Block Heater Data Sheet

47

Strip Heater Data Sheet

48

Battery Data Sheet ...

49

Battery Heater Data Sheet

50

Battery Charger ..

51 - 52

Flexible Exhaust Connector .

53

Unit Mounted Load Center

54

Remote Annunciator Panel Brochure ..

55 - 56

Remote Annunciator Panel Owners Manual

57 - 67

Remote Emergency Stop Switch

68 - 69

Spring Isolator Data Sheet . .

70 - 71

Gen-Link Software Owners Manual

72 - 77

Generator Warranty Data Sheet

78

Start-Up Checklist ....

79 - 82

ii

800 Shrewsbury Avenue, Tinton Falls, NJ 07724 Phone: 732.741.6400

Fax: 732.741.3866

NET ACCESS MMU


CEDAR KNOLLS, NJ
We are pleased to offer the following GENERAC MPS package for your consideration:

SUMMARY
For this project, we are providing an option to meet the power requirements of the base design.
Please see below for summary of this option.
Description
1800 KW MPS: Modular
Power System consisting of
3 paralleled gen sets, 3
each @ 600 kW.

Benefits
Redundancy- N+1
redundancy to life
safety load
Reduced Lead Time12-14 Weeks Lead
Time
Flexibility- Smaller
units offer rooftop
mounting, lower
transport cost
Scalability- System
expandable to
accommodate
additional loads and
future growth

Cost

Page 1 of 4

Quoted materials and services per the described systems include:


1800 KW MPS
GENERATORS
Quantity: 3 Units
3 @ 800 kW GENERAC, Diesel Fired, Parallel units.
60 HZ, 277/480 VAC, 3 Phase
MPS-Digital Control Panel
2 Year Limited Factory Warranty

ADDITIONAL ACCESSORIES AND SERVICES (Included in quote total for each system above)
Power Manager Digital Control Platform configured for Generac Modular Power System's Paralleling
Controller (PM-PC) shipped loose for job site installation, by others.
Redundant Controller: shipped loose for job site installation, by others.
Alternator strip heater
Engine run relay.
Start-Up during normal business hours
1 hour factory testing at .8 power factor.
Freight included to job site via open-top truck; Off-loading by others.

See Bill of Material for complete details and specs.


BILL OF MATERIAL
GENERAC POWER SYSTEMS, INC.
Bill of Material for: NET ACCESS MMU
Qty. 3 Turbo charged, after cooled, diesel fired, engine driven generators, paralleled to
provide 1800 kW of power, consisting of the following features and accessories:
3:MD0800K3622D18GPNLC, 800 kW Rating, synchronous alternator, wired for 277/480 VAC, 3 Phase,
60 HZ.
- PowerManager Digital Control Platform configured for Generac Modular
Power System's Paralleling Controller (PM-PC)
PowerManager Digital Control Platform configured for Generac Modular
Power System's Paralleling Controller (PM-PC)
- 32 bit microprocessor structured with:
real time clock, 47 inputs, 32 outputs, 2- RS232 ports, 2- RS485
ports, RJ45 modem port, CANBus port
- 0.25% digital voltage regulator with:
3 phase RMS sensing, Soft start voltage ramping - adjustable, Loss
of sensing protection - adjustable, Negative power limit - adjustable,
Hi/lo voltage limit - adjustable, V/F slope and gain - adjustable,
Fault protection, Encapsulated and sealed
- 0.25% digital frequency regulation with;
Soft start ramping - adjustable, Gain - adjustable, Overshoot limit - adjustable,
- On board PLC for customer configuration with:

Page 2 of 4

(24) Digital inputs, (43) Analog inputs, (24) digital open collector
outputs - 30vdc, (16) Timers, (16) Counters
- Programmable touch screen engine control and monitoring module with:
Auto/Manual/off key switch, Alarm LED, Not in Auto LED,
Audible alarm, Emergency stop switch,
30 page readout including:
Oil pressure and optional oil temperature, Coolant temperature
and level, Fuel level (where applicable), Engine speed, DC
battery voltage, Run time hours, Generator voltages, Amps,
Frequency, Power, Power factor
Alarm Status:
Low or high AC voltage, Low or high battery voltage, Low or
High frequency, Pre-low or low oil pressure, Pre-high or high oil
temperature (optional), Low water level and temperature, Prehigh or high engine temperature, High, low and critical low fuel
levels (where applicable), Overcrank, Over and under speed,
Unit not in "Automatic Mode"
* 1000 amp paralleling contactor
- Electronic governor isochronous: Steady state regulation +/-0.25%
- 1000 amp, UL listed, mainline circuit breaker installed
- 110AH, 925 CCA, group 31 - battery w/rack-installed
- 10AMP battery charger-installed
- Battery charging alternator
- Battery cables
- Battery tray
- Fuel shut-off solenoid valve
- Solenoid activated starter motor
- Fuel filter and water separator
- Air cleaner and oil filter with internal bypass
- Oil and antifreeze
- Oil and radiator drain extensions
- 2 Pieces standard flexible exhaust connector
- Block heater 5000W 240V
- 2 Owners manuals
- UL2200 Listed
- 2 year standard warranty, factory limited
PowerManager Digital Control Platform configured for System Controller
(PM-SC)
- 32 bit microprocessor structured with:
Real time clock, 47 inputs, 32 outputs, 2- RS232 ports, 2- RS485
ports, RJ45 modem port, CANBus port
- On board ILC for customer configuration with:
(24) Digital inputs, (43) Analog inputs, (24) digital open collector
outputs - 30vdc, (16) Timers, (16) Counters
- Programmable touch screen system control monitoring module with:
Utility status via ATS 2-wire start
Individual generator status via digital communications with PM-PC

Page 3 of 4

- Generator bus status via digital communications


ATS operation via programmable permissive signal
Proportional load sharing via digital communications with PM-PC
Programmable ATS load shed initiation
- Alarm and event logging
- System communications via GenLink software
- Internal modem
- System controller housed in separate NEMA 1 enclosure.

REMOTE ANNUNCIATOR PANEL


Qty. 1: 21 Light, Remote Annunciator: Surface Mount (shipped loose for job site mounting, by others)
- Generator remote start capabilities
- 12/24 Volt DC input
- Solid-state LED lamps
- Annunciation of:
Generator Run, Pre-Low Oil Pressure, Battery Charger AC Fail.,
Pre-High Water Temp, Low Battery Voltage, Pre-Low Water Temp,
High Battery Voltage, Pre-Low Fuel, RPM Sensor Loss,
Low Oil Pressure, Overcrank, High Water Temp / Low Water Level,
Overspeed, Emergency Stop, Generator Power, Not in Auto,
System Ready, Line Power, Communication OK and Spare Light

Page 4 of 4

NET ACCESS MMU:


TYPICAL FOR 3

MD600

For Modular Power System (MPS)

Standby Power Rating


600KW 60 Hz

Prime Power Rating (1)


547KW 60 Hz
Power Matched

GENERAC 22.0DTA ENGINE


Turbocharged / Aftercooled
Tier II Compliant
EPA Cert. DWX-NRC1-06-06

PowerManager Digital Control Platform

FEATURES

(1) Prime power unit not available at this time.

INNOVATIVE DESIGN & PROTOTYPE TESTING are key


components of GENERAC'S success in "IMPROVING POWER BY
DESIGN." But it doesn't stop there. Total commitment to component
testing, reliability testing, environmental testing, destruction and life
testing, plus testing to applicable CSA, NEMA, EGSA, and other
standards, allows you to choose GENERAC POWER SYSTEMS
with the confidence that these systems will provide superior
performance.





system, while allowing the PM-DCP, with its onboard PLC, to be


customized to meet any application requirement. The system is
available on single unit gas, diesel or bi-fuel installations as well
as Modular Paralleling Systems (MPS) from 350 kW - 3000 kW.
SINGLE SOURCE SERVICE RESPONSE from Generac's dealer
network provides parts and service know-how for the entire unit,
from the engine to the smallest electronic component. You are never
on your own when you own a GENERAC POWER SYSTEM.

PARALLELING SYSTEM FEATURES:


AUTO SYNCHRONIZATION
ISOCHRONOUS LOAD SHARING
REVERSE POWER PROTECTION
MAXIMUM POWER PROTECTION
ELECTRICALLY OPERATED MECHANICALLY HELD

ECONOMICAL DIESEL POWER. Low cost operation due to


modern diesel engine technology. Better fuel utilization plus lower
cost per gallon provide real savings.
LONGER ENGINE LIFE. Generac heavy-duty diesels provide long
and reliable operating life.

TRANSFER SYSTEM
REDUNDANT OPERATION AND INCREASED RELIABILITY
UL2200 LISTED

GENERAC TRANSFER SWITCHES, POWERMANAGER AND


ACCESSORIES. Long life and reliability is synonymous with
GENERAC POWER SYSTEMS. One reason for this confidence
is that the GENERAC product line includes its own transfer
systems, accessories, and PowerManager controls for total system
compatibility.


POWERMANAGER DIGITAL CONTROL PLATFORM. The
PowerManager Digital Control Platform (PM-DCP) is a powerful
control system built around a 32-bit, industrial microprocessor.
Standard factory programming controls the entire engine/generator

APPLICATION
& ENGINEERING DATA

MD600 MPS

GENERATOR SPECIFICATIONS

ENGINE SPECIFICATIONS

TYPE.............................................................Marathon MagnaMax PMG


150C Rating Marathon 572RSL4028...........................................610kW
SHORT CIRCUIT RATIO.................................................................0.653
SYNCHRONOUS REACTANCE.................................................2.680 pu
NEGATIVE SEQUENCE REACTANCE......................................0.213 pu
ZERO SEQUENCE REACTANCE..............................................0.051 pu
TRANSIENT REACTANCE........................................................0.144 pu
SUBTRANSIENT REACTANCE.................................................0.121 pu
OVERSPEED..........................................................................2250 RPM
PHASE SEQUENCE........................................................................ ABC
VOLTAGE BALANCE........................................................................0.2%
THD.....................................................................................................5%
TIF......................................................................................................<50
VOLTAGE DIP FULL LOAD APPLICATION....................................12.5%
VOLTAGE OVERSHOOT LOAD REJECT.........................................15%
MOTOR STARTING CHARACTERISTICS................... (See Chart pg. 3)
GENERATOR EFFICIENCY
95% @ 1.0 pf Full Load 480 volt
93% @ 0.8 pf Full Load 480 volt
BEARINGS (PRELUBED AND SEALED)..............................................1
COUPLING......................................................................Direct Flex Disk
LOAD CAPACITY (STANDBY)........................................................100%

MAKE..........................................................................................Daewoo
MODEL........................................................................................ p222LE
CYLINDERS..................................................................................... V 12
DISPLACEMENT - liter/(cu. in.)............................................. 22.0 (1338)
BORE - mm/(in.)...................................................................... 128 (5.04)
STROKE - mm/(in.) ................................................................ 142 (5.59)
COMPRESSION RATIO.................................................................15.0:1
INTAKE AIR....................................Turbocharged/Aftercooled (Air-to-Air)
NUMBER OF MAIN BEARINGS............................................................7
CONNECTING RODS..................................................... I-Beam Section
CYLINDER HEAD........................ Individual Cylinder Heads/Two Valves
PISTONS....................................................... Open Chamber/Oil Cooled
CRANKSHAFT....................................................Counter Weighted Type

LOAD CAPACITY (PRIME)..............................................................110%

CONTROL SYSTEM PM-PC (See Note 4)


The Generac PowerManager Generator Control is mounted at the
generator set and monitors all engine and alternator parameters:
High/Low Battery
High/Low Frequency
High Oil Temp
Pre-alarm Hi Oil Temp
Low Oil Pressure
Pre-alarm Lo Oil Pressure
Low Coolant Level
Overcrank
High Coolant Level
Pre-alarm Hi Coolant
Low Coolant Level
Critical Low Fuel
Overspeed/Underspeed
Over/Under Voltage
Sensor Failures
High/Lo Fuel
The instrumentation screen displays the following:
AC volts
AC amps
Frequency
kW
Power Factor
Coolant Temp
Coolant level
Run-time Hours
Fuel level(%)
Battery Voltage
Oil Pressure
Engine Speed
Serial communication to the PowerManager System Controller via
RS485 connection
Programmable
Built in synchronizer for paralleling control and protection
Digital Voltage Regulator for precise control
Three pole 1000 amp paralleling switch
Rated 600 volts
UL recognized device
Electrically operated Mechanically held
Built in ARC supression
Mainline circuit breaker
mounted in series with paralleling switch
Generator Connection Box
mounted on right side (facing rear) 12" x 22" x 36"
access from side, top, bottom to paralleling switch

VALVE TRAIN
LIFTER TYPE...................................................................................Solid
HARDENED VALVE SEATS............................................................... Yes
ENGINE GOVERNOR
ELECTRONIC / ISOCHRONOUS............... Barber Colman / Generac
STEADY STATE FREQUENCY REGULATION........................0.25%
LUBRICATION SYSTEM
TYPE OF OIL PUMP........................................................................Gear
OIL FILTER.................................................................Full Flow Cartridge
CRANKCASE CAPACITY - liter(gal.)........................................ 42 (11.1)
COOLING SYSTEM
TYPE OF SYSTEM............................................. Pres. Closed Recovery
WATER PUMP.............................................Centrifugal Type, Belt Driven
TYPE OF FAN.............................................................................. Pusher
NUMBER OF FAN BLADES...................................................................7
DIAMETER OF FAN - mm/(in.) . ................................................ 915 (36)
COOLANT HEATER..........................................................240V (4000W)
FUEL SYSTEM
FUEL.............................................................................No. 2 Diesel Fuel

(Fuel should conform to ASTM Spec.)
FUEL FILTER.............................................................Full Flow Cartridge
FUEL INJECTION PUMP............................................. Bosch P Type x 1
FUEL PUMP............................................................... Bosch/Piston Type
INJECTORS..................................................................Bosch Multi-Hole
FUEL LINE (Supply)................................................................. 1/2"FNPT
FUEL RETURN LINE............................................................... 1/2"FNPT
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR............................... 45 Amps at 24V
STARTER MOTOR............................................................ 6.6 kW at 24V
RECOMMENDED BATTERY (SERIES STRING)...... 2 x 12V X 700 CCA 27F
GROUND POLARITY.................................................................Negative

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). Prime (Unlimited Running Time): Applicable for supplying electric power in lieu of commercially purchased power. Prime power is the maximum power available at variable
load. A 10% overload capacity is available for 1 hour in 12 hours. (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271). Prime power is not available at this time for MPS units.

MD600 MPS

OPERATING DATA


GENERATOR OUTPUT VOLTAGE/KW60Hz
277/480V, 3-phase, 0.8 pf NOTE: Consult your Generac
dealer for additional voltages.
600V, 3-phase, 0.8 pf

EXHAUST
Exhaust flow at rated output

60 Hz - m3/min. (cfm)
Maximum recommended back pressure

kPa (" Hg)
Exhaust temperature at rated output
o

C (oF)
Exhaust outlet size

Rated AMP
903
722

480V
2100
3500

Load
150 kW
300 kW
gal./hr.
14.4
23.4
in.
48

COOLING
Coolant capacity
System - lit./gal.

Engine - lit./gal.

Radiator - lit./gal.
Coolant flow/min.
60 Hz - lit./gal.
Heat rejection to coolant
60 Hz - BTU/hr.
Radiator air flow
60 Hz - m3/min. (cfm)
o
Max. operating air temp to radiator
C (oF)
o
Max. operating ambient temp
C (oF)
Max. external pressure drop

after radiator
in. H2O

COMBUSTION AIR REQUIREMENTS
Flow at rated power
60 Hz - m3/min. (cfm)

ENGINE
Rated RPM
HP at rated kWe (gross)
Piston speed
BMEP

MD600

KW

600

600

MOTOR STARTING KVA


Locked rotor kVA at 35% instantaneous voltage dip

with standard alternator; 60 Hz-kVA
with alternate alternator; 60 Hz-kVA
* see note 1
FUEL
Fuel consumption60 Hz

* see note 3
Fuel pump lift

STANDBY

450 kW
36.6

600kW
46.2

131 (34.6)
36 (9.5)
95 (25.0)
1098 (290)
1,740,000
665 (23,500)
60 (140) * see note #5
50 (122) * see note #5
0.5
55.5 (1959)

182 (6419)
5.1 (1.5)
704 (1300)
2 - 8" ANSI Flange (Dual Exhaust) or 1 - 10" ANSI Flange (Single Exhaust)

60 Hz
60 Hz
60 Hz - m/sec. (ft./min)
60 Hz - psi

1800
864
8.5 (1677)
284

POWER ADJUSTMENTS FOR AMBIENT CONDITIONS



* see note 6
Temperature

-4.5% for every 10o C above - Co

-2.5% for every 10oF above - Fo
Altitude

-0.8% for every 100 m above - m

-2.5% for every 1000 ft. above - ft.

40
104
1067
3500

Notes:

1. Motor starting kVA adds directly for each generator on the bus. With Generacs PowerManager Digital Control Platform, the load is
shared proportionally.
2. Maximum distance between generator sets is determined by the voltage drop of the power conductors and the maximum distance
allowed for the RS485 connection. If the distance between units exceeds 500 feet, consult your Generac representative for wire and
communication recommendations.
3. Fuel consumption like motor starting kVA is additive. Each generator will proportionally share the load and the fuel consumption will be
based on the percentage of load shared.
4. A complete MPS system requires a PowerManager Paralleling Controller (PM-PC), a PowerManager System Controller (PM-SC),
and switch(es) from Generac Power Systems GTS line of digitally controlled transfer switches. In addition, Generac Power Systems
Genlink Communications Software provides remote monitoring and user interface with the Power Manager Digital Control Platform.
5. Values given are maximum temperatures to which power adjustment factors can be applied. Consult your Generac representative if
operating conditions exceed these maximums.
6. Consult Factory for high altitude cooling options.

STANDARD ENGINE & SAFETY FEATURES
















High Coolant Temperature Automatic Shutdown


Low Coolant Level Automatic Shutdown
Low Oil Pressure Automatic Shutdown
Overspeed Automatic Shutdown (Solid-state)
Crank Limiter (Solid-state)
Oil Drain Extension
Radiator Drain
Factory-Installed Cool Flow Radiator
Radiator Duct Adapter On Open Genset
Closed Coolant System
UV/Ozone Resistant Hoses
Rubber-Booted Engine Electrical Connections
Stainless Steel Flexible Exhaust Connection
Battery Charge Alternator
Battery Cables

MD600 MPS

Battery Tray
24 Volt, Solenoid-activated Starter Motor
Air Cleaner
Fan Guard
Control Console
Isochronous Governor
Jacket water heater
Autosynchronizer
Isochronous Load Sharing Module
Reverse Power Protection Relay
Dead Bus Sensing
Sync Check Relay
Main Line Circuit Breaker
2 Year Warranty

POWERMANAGER DIGITAL CONTROL PLATFORM


The PowerManager Paralleling Controller (PM-PC) is a fully programmable, integrated digital generator control console using a 32-bit industrial
microprocessor to handle all control, monitoring, input/output genset functions. The open architecture used allows customizing the controls to meet any
customer requirement, yet maintaining the simplicity of operating 'as is' with the factory default programming. (see Generac bulletin #0168840SBY)

GENERATOR CONNECTIONS
1. 4 Wire load connections from Paralleling Switch to optional connection box bus or transfer switch bus. Paralleling Switch has 4 lugs per phase
each lug will accept 4/0 to 350MCM aluminum or copper conductor.
2. 2 wire shielded cable (RS485) to PowerManager System Control.
3. 2 wire twisted pair from transfer switch (when multiple transfer switches are used). Can also go to the PowerManager System Controller
4. 120Volt 15 amp input circuit for battery charger.
5. 240Volt 20 amp input for coolant heater.

OPTIONS
OPTIONAL FUEL ACCESSORIES
Base Tank Low Fuel Alarms
Secondary Fuel Filters, Heaters and Water Alarms
UL Listed Fuel Tanks / Daytanks
Electric Fuel Transfer Pump System
OPTIONAL ELECTRICAL ACCESSORIES
10A Dual Rate Battery Charger
Battery, 24 Volt
Battery Warmer
500MCM Lugs on Paralleling Switch (4 lugs per phase)
OPTIONAL ALTERNATOR ACCESSORIES

Alternator Heater
OPTIONAL EXHAUST ACCESSORIES
Critical, Residential or Industrial Exhaust Silencers
Installed Low-Profile Critical Muffler (available on sound
attenuated enclosure
Single Exhaust System (available on open genset)
GENERAC POWERMANAGER SYSTEM CONTROLLER
FOR COORDINATION OF GENERATOR(S) AND TRANSFER
SWITCHE(ES)
See Spec 0169060SBY For Additional Information














ADDITIONAL OPTIONAL EQUIPMENT


20 Light Remote Annunciator
Remote Relay Panels
Oil Heater
5 Year Warranties
GenLink Communications Software
OPTIONAL ENCLOSURES
Weather Protective
Sound Attenuated
Aluminum

Distributed by:

Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.

Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com
2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0168810SBY rev B / Printed in U.S.A. 09/04/09

NET ACCESS MMU: TYPICAL FOR 3


Alternator
Data

Alternator Rating:
kW
kVA
600---------------------------750
Part # .....................................0G6303 (K2)
Type .....................................Brushless/PMG
Connections ..........................Series Wye
Efficiency @ 1.0 Power Factor
kW Load
Efficiency
150 kW ........................91.4
300 kW ........................92.6
450 kW ........................94.1
600 kW ........................94.2
600kW @ 0.8 pf ..........92.7

600 kW

Waveform Distortion................................. <5%


Telephone Influence Factor...................... <50
Synchronous Speed ................................. 1800 rpm
Maximum Overspeed ............................... 3300 rpm
Number of Bearings ................................. 1-Sealed Ball
Insulation System .................................... Class H
Excitation System.........Wound Field + Perm Mag
300% Current Limited

Temperature Rise vs. kW Output ( 0.8 PF ):


kW
Temperature Rise C
471
80
560
105
600
125

Machine Parameters @ Max kW Rating:


Transient S C Time Constant........... 1.7 ms
Subtransient Reactance................... 0.146
Transient Reactance ........................ 0.190
Synchronous Reactance .................. 1.970
Negative Sequence Reactance ....... .0.18
Zero Sequence Reactance .............. 0.042
Short Circuit Ratio ............................ 0.35
Excitation Voltage ............................ 20-80V
Excitation Current @ Rated kW ....... 3.2A -0.8pf
Lamination Type............................... WEG

Instantaneous Voltage Dip in kVA @ % Dip


Voltage

10% 15%

20%

480 Volt

450

1000 1250 1750 2100

700

25%

30%

35%

Available Options:
Alternator Heater

100,000

ALTERNATOR DECREMENT CURVE


3 Phase
Therm Limit
Test Parameters
kW Rating 600
Voltage
480
Power Factor 0.4

Short Circuit Amps

10,000

Control Panel Cutoff

1,000

100

0175550SSB

10

Se conds

10/11/07 R1

0.1

100
0.01

10
10

NET ACCESS MMU: TYPICAL FOR 3

INSTALLATION DRAWING
FOR

NET ACCESS MMU:


TYPICAL FOR 3

PM-DCP

FEATURES

PowerManager Digital Control Platform

Touch Screen Information Panel


Additional Standard Features Parallel Control
PowerManager Parallel Control (PM-PC)
Paralleling Control (Synchronizing)

Totally Integrated Control. The Generac PowerManager


Digital control Platform is a fully integrated and multipurpose family
of controllers for Generac's single and Modular Power Systems
(MPS). The PowerManager Digital Control Platform (PM-DCP), is
configured as the PowerManager Genset Controller (PM-GC) for
stand-alone gensets, the PowerManager Parallel Controller (PMPC) for gensets in a Modular Power System configuration, and
the PowerManager System Controller (PM-SC) for the systematic
control of the Modular Power Systems.

Standard Features System Control


PowerManager System Control (PM-SC)
Built-In PLC Logic Eliminates The Need For External

Standard Features as a Single Unit Control


PowerManager Generator Control (PM-GC)
Engine Protective Functions












Reverse Power
Loss Of Synchronization Between Gensets
Load And VAR Sharing

Digital Engine Governor Control


Digital Voltage Regulator
Touch Screen
Multiple Programmable Outputs And Inputs
PLC Logic And Programming
Remote Display Capability
Communication Via Modbus Or CANBus
Alarm And Event Logging With Real Time Stamping
Built-In Diagnostics
Spare Analog And Digital Inputs And Outputs
Software Update Via Remote Computer
Built-In Modem And Dial-Out Capability
Dial-Out Capabilities

11

Controllers Under Most Conditions


Touch Screen For Local Control And Engine / Generator
Information
Remote Display And Programming Via Laptop
Internal Built-In Modem
Communication Between Gensets Via Standard Modbus
Protocol
Programmable I/O Channel Properties
Alarm And Event Logging With Real Time Stamping
Parameter Logging And Trending
Built-In Diagnostics
Selective Load Sharing
Spare Analog And Digital Inputs And Outputs
Software Updated Via Remote Communication
Dial-Out Capability
Separate Enclosure (24" x 30" x 9") NEMA 1

PM-DCP

Voltage Regulation GC, PC**

Ports

Digital Control
Three Phase Sensing
Variable V/F Slope Settings And Adjustable Gains
Negative Power Limit
Soft Start Ramping
Loss Of Sensing Protection
Components Encapsulated For Total Protection
RMS Sensing
Paralleling Function On PM-PC
Fault Protection (I2T Function) Optional
High Voltage Limit
Low Voltage Limit
Maximum Power Limit
0.5% Voltage Regulation
0.1% Stability
Adjustable Via GenLink

2 - RS485
2 - RS232
1 - RJ45 Modem
CANBus

PLC (Built-In Programmable Logic Controller)


Boolean Logic Programming (Ladder)
16 Timers
16 Counters
Counter Reset
Programmable In GenLink
Custom Configurable For Non-Standard Options

Governor GC, PC**


Soft Start Ramping (Multiple Steps)
Synchronizing Function PM-PC Only
Overshoot Limit And Control
Fully Adjustable Gain (PID)

Display (Touch Screen)**


Interactive RS485 Interface To CPU
30 Pages Available With 10 Items Per Page
Touch Screen Parameter Page Changes
Amps Per Phase - Generator
Amps Per Phase - Utility
Line To Line And Line To Neutral Volts - Utility And Gen
Frequency
RPM
Engine Coolant Temperature
Engine Oil Pressure
Engine Oil Temperature
Battery Voltage
Power Factor
kW
kVAR
Shutdown Messages
Diagnostics
Maintenance Information
Hourmeter

Connections*
28 - Digital Outputs (Open Callector 30v 200 mA)
4 - Analog Outputs (0 - 5 Volts)
24 - Digital Inputs Maximum
6 - Isolated Digital Inputs
17 - Analog Inputs Maximum

Qualification Testing
Life Test In Environmental Chamber
Temperature Rating -40 C to +70 C
Humidity 2% to 95%
Vibration Tested And Protected
Accelerated TEsting MTBF >50,000 Hr.

Codes And Standards


UL2200
CSA
NFPA 110 (Software Programmable For Level 1 or 2)
NFPA 70
IEC801 Radiated Emissions, Susceptibility And Surge
Immunity

Engine Shutdown Messages (Touch Screen)**


Low Oil Pressure
Low Coolant Level
High Coolant Temperature
Sender Failure
Oil Temperature
Overspeed, Underspeed User Definable (Within

Overcurrent And Short Circuit Protection GC, PC**


Protection Against Phase To Phase And Phase To
Neutral Short Circuits. (I2T Algorithm) Optional

Flexibility
Standby Controller PM-GC
Paralleling Controller PM-PC
PowerManager System Controller PM-SC
Common Control Platform Via GenLink Software
Same Hardware = Less Service Stock

Control Panel And Touch Screen**


Auto / Manual / Off Keyswitch
Alarm LED
Not In Auto LED
Alarm Acknowledge Button
Audible Alarm
Emergency Stop

* Actual number may vary due to configuration of genset options


** Applies to these specific controllers, otherwise to all controllers

12

PM-DCP

Typical GenLink Screen For PLC

Typical Screens From Touch Screen Panel On Genset

Main Processor Assembly


Factory Sealed In A Die Cast Aluminum Tamper
Resistant Enclosure
No Internal Adjustments Or Controls
Watertight Output And Input Connections
5 - 30 Volts Input Power
Motorola 32 Bit Processor
Built-In Protection From Voltage Spikes
Built-In Diagnostics
4 - 20 mA Sender Input
-40 C to +70 C Temperature Range
Multi-Layer Circuit Board Technology With Surface
Mount Components
Shown With Cover Removed (Back Side)

13

PM-DCP
KEY COMPONENTS
PM-GC
MP-PC
PM-SC

Single Units Only


Paralleled Units
Controller For Multiple Paralleled Units

OPERATION SEQUENCE FOR MPS

Power up sequence with single or multiple transfer


switches.
1. Utility fail or brownout occurs.
2. Transfer switch sends a signal via a two-wire start to the PM-SC.
3. The PM-SC the n sends a signal to each generator telling it to begin
the start sequence.
4. The Generator Controller on each genset will monitor power up frequency
and voltage. When the first generator reaches rated frequency and
voltage, the PM-PC will close the generator contactor to the bus. The
bus is now live.
5. The PM SC will monitor the rest of the generators and sequence them
to the bus as they reach their rated parameters. The PM-PC monitors
phase sequence, voltage and frequency and then determines when the
contactor closes, but the PM-SC provides an interrupt to sequence the
gensets and prevent two generators from closing at the same time.
6. When the appropriate number of gensets assigned to each transfer
switch are up and closed on the bus, the PM-SC then allows that transfer
switch to switch to the Emergency position.

7. If one generator does not start, programmable load shed contacts


will open or prevent a switch from closing, which will reduce the load,
then allow selected transfer switches to transfer to the emergency
position with the available generators.
8. If emergency power is required within 10 seconds, a separate
transfer switch for the critical loads is installed and powered from
the main bus. As soon as the bus is live, the transfer switch will
transfer and pick up the critical loads.
9. If a single genset is taken off line, the load shed contacts will drop
a pre-programmed load and keep the remaining loads alive.
10. When Utility returns, the PM-SC will transfer the load back to the
Utility side and then give disconnect commands to the generators
and after a cool-down period will give a shutdown command to all
generators.

Distributed by:

GENERAC POWER SYSTEMS, INC. P.O. BOX 8 WAUKESHA, WI 53187


262/544-4811 FA X 262/544-0770

Bulletin 0169060SBY / Printed in USA 01.04, rev. 02.07

2007 Generac Power systems, Inc. All rights reserved. All specifications subject to change without notice.

14

Engine-Run Relay

NET ACCESS MMU


TYPICAL FOR 3

For use with Generac PMDCP, H-100, E


panel or C panel control systems
10 Amp Contact Rating
12 or 24 Volt DC input
Contact open or closure on engine run

Contacts
Type

DPDT

Material

Silver

Rating

Wiring Diagram, Engine Run Relay with


C panel, E panel, H-100 Panel

UL
10A @ 240VAC
10A @ 30VDC

Coils
Input Voltage

24VDC

Resistance

400 Ohms

Nominal Power

1.5 W

Wiring Diagram, Engine Run Relay with


PMDCP

GENERAC POWER SYSTEMS, INC. P.O. BOX 8 WAUKESHA, WI 53187


262/544-4811 FA X 262/544-4851

Bulletin 0161920SBY / Printed in USA 6.98 rev: 01.06

All specifications subject to change without notice.

15

Gener
ac Standb
y Gener
ator
Generac
Standby
Generator
Automatic Voltage Regulator
NET ACCESS MMU
TYPICAL FOR 3
Excellent stability.
Responds in less than one cycle.
Less than 1% steady state regulation.
LED display indicates shutdown
conditions.
Handles direct or brushless excitation.
Adjustable gain and stability for custom
genset application.
Minimal start-up overshoot.

More Than Fast Response


Today's generator specifier must
have voltage regulation response
in mere hundredths of a second.
Steady state regulation must be
less than 1%, with an absolute
minimum of overshoot at start-up.
The Generac Standby Voltage
Regulator meets those critical
requirements. And measures up
to performance standards only
Generac regulators supply. We
offer critical power that is as close
to uninterrupted as possible with
our affordable, flexible regulator.

Reliable, Consistent
Regulation
You can count on less-than-onecycle response from your
Generac automatic voltage
regulator. Pulse-width modulation
controls the Silicon-Controlled
Rectifier, ensuring excellent
latching and no false triggering.
Bench testing can be performed
without applying a load.
Adjust for direct or brushless
excitation with the flip of a switch.
Gain and stability adjustments
allow you to customize for your
application.

16

Featured for Accurate


Monitoring and
Designed to Last
LED indicator lights monitor
excitation, sensing voltage, and
the SCR fire signal. Potential
generator failure conditions such
as loss of sensing or excitation
voltage or failed circuit reference
are reflected on the LED display
to alert the operator to problems.
Circuits are protected by a high
temperature-resistant varnish.
The Generac Automatic Voltage
Regulator is built for long-term
performance you can count on.

Automatic Voltage Regulator Specifications*


* Meets or exceeds all EGSA voltage regulator performance standards.

Response
Temperature Tracking (32 - 120oF)
Temperature Drift
Steady State Regulation
Droop (voltage over frequency)

Less than one cycle


0.41%
<1% for 40oC change
0.75% RMS conditionally
0 - 4 Volts/Hz
Selectable start 52 - 62 Hz (underfrequency pot)
Rate 4/8 V/Hz (jumper select)
100A @ 1 cycle peak
10A @ 50oC cont.
20A one minute forcing
4 Volts RMS (DPE)
Pulse width modulation
93%
10% conditionally
1 second
0% oscillation

Maximum Output Current to Field

Regulator Turn On
SCR Control
Maximum DPE Energy
Startup Overshoot
Startup Voltage Time
Stability (100A, 0.8 PF)
LED Indicators

Green - Excitation on
Red - SCR fire signal
Yellow - Sensing voltage present
40 - 240 Volts RMS
1 Ph 60 Hz., 190 - 240 Volts RMS
On board
5K pot
No load required
State variable
Stamped case
High temperature varnish

Excitation Voltage
Sensing Input
Field Flash
Panel Voltage Control
Bench Testing
Feedback Method
Heat Sink
Circuit Seal

User-Adjustable Settings
Voltage
Gain Response
Compensation
Droop
Excitation

20% @ regulator, 10% @ panel


x10 variation
5 - 52 Hz
4 Volts/Hz<62 to 52 Hz
Brushless or direct

Regulator Shutdown Conditions:


Loss of sensing voltage
Loss of excitation voltage
Loss of circuit reference

GENERAC POWER SYSTEMS, INC P.O. BOX 8 WAUKESHA, WI 53187


262/544-4811 FAX 262/544-4851
All specifications subject to change without notice.

Bulletin 050120000S / Printed in USA 4.97, 6.97, 9.99

17

18
18

NET ACCESS MMU

SAMPLE ONE-LINE DIAGRAM


FOR

600 kW

600 kW

600 kW

19

NET ACCESS MMU


TYPICAL FOR 3

20

NET ACCESS MMU


TYPICAL FOR 3

21

NET ACCESS MMU


TYPICAL FOR 3

22

NET ACCESS MMU


TYPICAL FOR 3

23

NET ACCESS MMU


TYPICAL FOR 3

NET ACCESS MMU


TYPICAL FOR 3

24

NET ACCESS MMU


TYPICAL FOR 3

25

NET ACCESS MMU

PM-SC

PowerManager System Controller

Models
4975 PM-SC in NEMA 1 Enclosure
5039 PM-SC in NEMA 3R Enclosure
5047 PM-SC in NEMA 3R Enclosure with
thermostatically controlled heater

PM-SC in NEMA 1 Enclosure

Controller Description
The PM-SC can coordinate up to fifteen MPS generators
and fully supports generators of different power outputs
(load is shared proportionate to generator size). The
System Controller also supports single and multiple
transfer configurations. The transfer switches can be from
any manufacturer provided they utilize a standard twowire start. The PM-SC supports load sequencing through
three permissive and three load-shed steps which can
be used to sequence numerous load circuits.

The Power Manager System Controller (PM-SC) is


a digital control box that acts as the master system
coordinator for Generacs Modular Power System (MPS).
The System Controller provides a single point of remote
communication to the system, facilitates the starting and
stopping of the generators, helps fine-tune the generator
load balancing, and manages priority loading and load
shedding. The System Controller utilizes an RS485 data
highway to communicate with each generator controller.
The generator controller on each unit controls all generator
operation including synchronizing and the primary load
balancing functions. The role of the System Controller
is simply to facilitate normal system sequencing and
data gathering.

The PM-SC is mounted in a NEMA 1 or NEMA 3R


wall-mounted enclosure and can be located anywhere
within 3000 feet of the generators, though it is often
most convenient to locate it with the transfer switch
equipment.

After gathering information from each of the generator


controllers the PM-SC can easily provide generator
information upstream to a building management system
or to Generacs Genlink operator interface software
provided with the equipment. The System Controller
supports multiple communication ports utilizing Modbus
protocol as well as a built-in modem.

26

PM-SC

System Functions

Key Features
Controls up to 15 paralleling generators
Touch-screen display for monitoring system and
individual generator status
Diagnostics capabilities at the touch-screen and
through Genlink software
Data logging and trending capabilities
Real time clock and calendar
Programmable exerciser
Remote monitoring using Modbus RTU protocol or
GenLink operator interface software
Standard internal modem
Priority loading (3) and load shedding (3) capability
Programmable spare I/O, 4 auxiliary inputs and 8
auxiliary outputs
Integral custom logic algorithm allows implementation
of an up to 47 rungs of PLC style logic
Three position key switch for operation mode
selection (Auto/Off/Manual)
Battery-backed DC controls with AC charger,
redundant 24VDC input available
EEPROM non-volatile memory assures settings are
not lost during loss of power
Fuse-protected 120VAC GFI convenience duplex
receptacle (5 amp max)
UL 508 Listed

The PM-SC:
Accepts a 2-wire start signal from multiple ATSs
Starts and stops generators via RS485
Fine-tunes the real and reactive generator load sharing
via RS485
Priority loads the system (3 levels)
Load sheds during generator failure (3 levels)
Central point of communication & control
RS232, RS485, and Modem
Modbus Protocol & GenLink Interface Software
Supports a system level remote annunciator and
common alarm output
Supports backup modes of operation
Human interaction (standard)
Redundant controls (optional)

Normal Sequence of Operation


1. The automatic transfer switches (ATSs) monitor the
utility voltage and provides a 2 wire generator start
contact to the PM-SC.
2. T
 he PM-SC then provides a start command to all
generators via RS485 communications.
3. Each generator will start independently.
4. The first generator that attains rated voltage and
frequency performs dead bus arbitration with the
PM-SC and then closes its internal paralleling switch
connecting to the generator bus.
5. If an emergency system load requiring a 10 second
start exists, the first unit to close onto the generator
bus will typically pick-up the emergency ATS
immediately.
6. D
 uring this time, the PM-SC inhibits the transfer of
the other ATSs via permissive relays.
7. The remaining generators will sync with the
generator bus and close their individual paralleling
switches.
8. As the generators are paralleled to the generator
bus, the PM-SC sequentially signals the remaining
ATSs to transfer onto the generator bus.
9. If a generator fails, load shed contacts are available
to disconnect selected loads. Load shedding can
be implemented at the transfer switches, with shunt
trip breakers, through building automation, and by
various other methods.

Optional & Backup Functionality


The MPS product line is designed to support operation
even if a failure occurs to the PM-SC or to the RS485
data highway. Standard back-up mode allows human
intervention to manually bring the generators online utilizing the capabilities built into the generator
controllers. Load is then sequenced manually by
actuating manual push buttons inside the System
Controller. An optional redundant load sequencing
controller is available for sites which desire fully
automatic backup operation.
In addition to basic functionality, the PM-SC is designed
to fully integrate with Generacs MTS digital transfer
switches or Generacs soft load transfer switch controller.
The System Controller also supports integration of
other optional functionality like generator capacity
management and site-specific custom logic.

10. When utility supply returns, the ATSs remove the 2


wire start causing the PM-SC to issue a command
to each generator control to disconnect from the
generator bus.
11. Each generator will operate for the cool-down period
and then shutdown.

27

PM-SC

Operating Specifications

Typical Screens From Touch Screen Panel

External Power
Supply Requirement....................... 120VAC single phase
Internal Power.......................................................24VDC
Output Ratings

Relay Contacts........................ 250VAC, 28VDC, 10A

Open Collector User Outputs................. 30V, 200mA
Environmental

Temperature............................................ 10 to +50 C

Humidity............................ 0 to 95% non-condensing

Packaging and Mounting


Enclosure Types Available.........NEMA 1 or NEMA 3R
Mounting....................................Wall Mount
Weight.......................................90 Lbs.
Dimensions................................30H x 24W x 9D
Finish.........................................Generac Gray RhinoCoat

Main Processor Assembly


Factory Sealed In A Die Cast Aluminum Tamper
Resistant Enclosure
No Internal Adjustments Or Controls
Watertight Output And Input Connections
5 - 30 Volts Input Power
Motorola 32 Bit Microprocessor
Built-In Protection From Voltage Spikes
Built-In Diagnostics
-40 C to +70 C Temperature Range
Multi-Layer Circuit Board Technology With Surface
Mount Components
Shown With Cover Removed (Back Side)
Plug-in/Plug-out Design

28

PM-SC

SINGLE TRANSFER
SWITCH CONFIGURATION

MULTIPLE TRANSFER
SWITCH CONFIGURATION

GENLINK PC/LAPTOP

GENLINK PC/LAPTOP

500 kW

500 kW

500 kW

RS485/232

500 kW

500 kW

500 kW

RS485/232

TRANSFER
SWITCH

TO
UTILITY

PERMISSIVE/LOAD SHED CIRCUITS

Load Shed
Capabilities
Included

229.2mm[9.0"]
203.2mm[8.0"]

Non-Vital
Load

11.1mm[ 0.4"]TYP.

PERMISSIVE/LOAD SHED CIRCUITS

Most
Critical
Load

Critical
Load

609.6mm[24.0"]
456.6mm[18.0"]

229.2mm[9.0"]
203.2mm[8.0"]

76.5mm[3.0"]

11.1mm[ 0.4"]TYP.

Critical
Load

609.6mm[24.0"]
456.6mm[18.0"]

798.0mm[31.4"]

762.0mm[30.0"]

WALL MOUNTING
BRACKETS

76.5mm[3.0"]

762.0mm[30.0"]

WALL MOUNTING
BRACKETS

PM-SC IN NEMA 1 ENCLOSURE

See installation drawings for details:


NEMA 1: 0E7619
NEMA 3R: 0H3175

Non-Vital
Load

856.5mm[33.7"]

856.5mm[33.7"]
798.0mm[31.4"]

TO
UTILITY

TRANSFER
SWITCH

PM-SC

TO
UTILITY

TRANSFER
SWITCH

PM-SC

TRANSFER
SWITCH

TO
UTILITY

NEMA 3R ENCLOSURE

Distributed by:

Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com
2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0182690SBY/Printed in U.S.A. 05.09

29

30
30

NET ACCESS MMU


TYPICAL FOR 3

31
31

NET ACCESS MMU


TYPICAL FOR 3

32

NET ACCESS MMU


TYPICAL FOR 3

33

NET ACCESS MMU


TYPICAL FOR 3

34
34
NET ACCESS MMU
TYPICAL FOR 3

35

DATE: 03/18/09

REVISION: H-4160-C

REVISION: H-4160-C
DATE: 03/18/09

NET ACCESS MMU


DRAWING #: 0E7619
TYPICAL FOR 3
POWER MGR-SC W/G PANEL

INSTALLATION DRAWINGS

GROUP G

SWITCH
RATING

MODEL NUMBER

SERIAL NUMBER

SYSTEM VOLTAGE

TYPE CODE

TRANSFER SYSTEM DATA

MAXIMUM VOLTS

MAXIMUM AMPS

GENERAC POWER SYSTEMS, INC.


WAUKESHA, WI.

P1

P2

P3

WHEN GENERATORS ARE RUN MANUALLY AND NOT UNDER


CONTROL OF THE PM-SC, PERMISSIVE RELAYS (P1, P2, P3)
CAN BE OPERATED USING THE PUSHBUTTONS ON TOP OF
THE RELAYS. SEE OWNER'S MANUAL.

DRAWING #: 0E7619

POWER MGR-SC W/G PANEL

INSTALLATION DRAWINGS

GROUP G

NET ACCESS MMU


TYPICAL FOR 3

MPS Paralleling Switch


Control Wiring

Copper Bus Generator Feed


S1B S1A AT2
M

AT1

A2

A1

DO NOT OPERATE WHILE THE SWITCH IS UNDER LOAD.


CLOSE
TRIP OPEN

SET MANUAL HANDLE ON "M" AND


OPERATE IN THE DIRECTION
PUSH THE "TRIP" WITH A SCREWDRIVER

Arc Chutes

LOAD BREAK SWITCH


RATED CURRENT
1000A
RATED VOLTAGE
480 VAC UL
600 VAC CSA

xxxxxx
XXXXX

MANUAL
CLOSE

Solenoid Actuated Mechanically Held


Switching Mechanism

OFF

TRIP

Copper Bus Load Terminals


(Lugs not shown)

DESCRIPTION

Generacs paralleling switch is an integral, plant-mounted paralleling device. This unit-mounted switch allows
Generacs Modular Power System (MPS) to parallel without external switchgear. Controlled by the gensets Power
Manager controller, these heavy duty switches are solenoid actuated, mechanically held, and serve as the customer
connection point for each MPS generator sets power output cabling.

SPECIFICATIONS

Manufactured by......................................................Generac Power Systems


Rating .....................................................................Continuous (100% Rated)
Contact Material......................................................Silver Plated Copper
Arc Chutes...............................................................Heavy Duty
Switching Mechanism..............................................Heavy Duty Solenoid Actuated - Mechanically Held
Life Test...................................................................20,000 Cycles Minimum
Approval..................................................................UL/CSA
Connections ...........................................................Bus Connection to Lugs
Features..................................................................Contacts may be inspected visually without switch disassembly
Contactor Rating

400 Amp

600 Amp

1000 Amp

Withstand Rating

35,000

42,000

65,000

Lug (Qty) Sizes*

(2) 250 mcm or


(1) 600 mcm/phase

(2) #1 to
500 mcm/phase

(4) #6 to
350 mcm/phase

Bus Size (inches)

1.57 x 0.20

1.38 x 0.59

2 x 0.59

*Contact your Generac Industrial Dealer for optional lug sizes.


Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com
2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0183530SSD/Printed in U.S.A. 06.09

36

NET ACCESS MMU


TYPICAL FOR 3

PM-PLS

PowerManager Permissive/Load Shed Controller

Model 5509 PM-PLS

Controller Description

Specifications

The MPS product line is designed to support operation


even if a failure occurs to the System Controller or to the
RS485 data highway. Standard back-up mode allows
human intervention to manually bring the generators
on-line utilizing the capabilities built into the generator
controllers. Load is then sequenced manually by actuating
manual push buttons inside the System Controller. An
optional redundant load sequencing controller is available
for sites which desire fully automatic backup operation;
this redundant controller is Generac's Power ManagerPermissive/Load Shed Controller (PM-PLS).

Manufactured By.......................Generac Power Systems


Power Requirement..........................24VDC from PM-SC
PLC.........................................................Siemens S7-200
Display Unit........................................... Siemens TD 200
Relay Contacts............................... 4PDT, 5A @ 250VAC
Environmental

Temperature..................................................0 to 50C

Humidity............................ 0 to 95% non-condensing

Packaging and Mounting


Enclosure Type................................................. NEMA 12
Mounting.........................................................Wall Mount
Weight................................................................... 39 lbs.
Dimensions.........................................20H x 16W x 6D
Finish......................... ANSI 61 Gray, baked powder coat

The PM-PLS is capable of monitoring online generators


and provides automatic permissive and load shed
functions similar to the PM-SC.The PM-PLS is configured
by the dealers trained MPS technician with the same
parameters configured in the PM-SC. Additional site
wiring is required to support this level of redundancy.
For a complete description, refer to PM-SC Operators
Manual, 0F1076.

37

PM-PLS

Automatic Backup Operation


The Modular Power System normally is in an operational ready status with all key switches in the auto position and all generators communicating to the
system controller. If the systems communications are disrupted, an alarm is generated and the PM-PLS is activated. Once activated the PM-PLS takes over
the system controllers load sequencing functionality through a hardwire status contact from each generator. The redundant mode, operational sequence is as
follows:
When the utility fails, the transfer switch(es) will provide a 2-wire start to the system controller and a redundant start to each of the generators. The
generators will all start automatically.
Generators 1 and 2 will perform dead bus arbitration through a hardwired handshake line and then one of the generators will safely energize the dead bus.
All remaining units will then actively synchronize (functionality internal to each generator) to the energized bus.
The PM-PLS receives hardwired on-line status from each generator. It uses this information to manage system permissive and load shed functionality.
While system communications are lost, generator load-sharing is maintained through functionality internal to the generator controllers.
For more details on the operation of permissive and load shed signals, please refer to the Power Manger System Controller manual, part # 0F1076.
Gen #2 Connecting Signal
Remote
Annunciator
Panel

RS-485 Generator Communications Bus

SYSTEM
CONTROLLER

Load Sheds

Permissives

Enable Backup Control

Gen 2

Gen 1

Gen 3

Gen 4

Gen 5

Gen 6

Gen 7

Gen 8

Gen 9

Gen 10

2-wire Start
Gen Connected to Bus Under Backup Control

Permissives
ATS

PM-PLS
Load Sheds

Distributed by:

16.00"

3.00"
TYP

10.00"
TYP

6.00"

21.25" TYP
20.00"
TD 200

SIEMENS

F5

F6

F7

F1

F2

F3

F8
F4
SHIFT

ESC

ENTER

Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com
2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0183760SBY/Printed in U.S.A. 09/11/09

38

GEN2 AUX

GEN1 AUX

SPARE

PLS ENBL

39
39

NET ACCESS MMU:


TYPICAL FOR
3
PAGE 1 OF 1

SPARE

REVISION:
DATE: 10/25/05

SPARE

GEN10 AUX

GEN9 AUX

GEN8 AUX

GEN7 AUX

GEN6 AUX

GEN5 AUX

GEN4 AUX

GEN3 AUX

PLS CONTROLLER

DRAWING #: 0F9260

WIRING DIAGRAM

GROUP G

40

NET ACCESS MMU


TYPICAL FOR 3

PLS ENBL

SPARE

GEN1 AUX

GEN2 AUX

GEN3 AUX

GEN4 AUX

GEN5 AUX

GEN6 AUX

GEN7 AUX

GEN8 AUX

GEN9 AUX

GEN10 AUX

SPARE

SPARE

SIEMENS, INC.
UL LISTED
GEENRATOR MOUNTED
CIRCUIT BREAKERS
FOR
NET ACCESS MMU DATA CENTER
9 WING DRIVE
CEDAR KNOLLS, NJ

41

GENERAC POWER SYSTEMS


Circuit Breaker Part Number Reference Chart
For use when the generator set is configured with any of the following:
C, E or PMDCP control panel
Generator Ouput Voltage of 600V
A breaker rated below 40A or above 600A
A breaker with shunt trips and auxiliary contacts
Generator sets that do not meet any of these criteria are fitted with Generac Breakers, which are not displayed
in this document.

NET ACCESS MMU


TYPICAL FOR 3

Breaker Selection Guidelines


Volts - When a Standard Breaker is selected, use the breaker with the lowest volt rating that meets
or exceeds the generator output voltage. For example, a standard 15A breaker on a 120/208V
generator set will be a 0D5545, which has a 480V rating. A standard 50A breaker on a 120/208V
generator set will be 0D5539, which has a 240V rating.
Optional breakers are rated at 600V.
Accessories - Match the accessory's voltage with the genset electrical system voltage. The
electrical system voltage can be found on page 2 of each product's specification sheet.
Note: All MPS products are equipped with the shunt trip and aux contacts accessory for use in load
shedding. Since the shunt trip is not available for customer use, this accessory is not displayed as
a feature on the quote or order's bill of material.
8kW to 400kW generator sets
AMPS
15
15
15
15
15
15
20
20
20
20
20
20
25
25
25
25
25
25
30
30
30
30
30
30
35
35
35
35

VOLTS
480
480
480
600
600
600
480
480
480
600
600
600
480
480
480
600
600
600
480
480
480
600
600
600
480
480
480
600

GENERAC No.
0D5545
0D5545B
0D5545C
0D5558
0D5558B
0D5558C
0D5546
0D5546B
0D5546C
0D5559
0D5559B
0D5559C
0D5547
0D5547B
0D5547C
0D5560
0D5560B
0D5560C
0D5548
0D5548B
0D5548C
0D5561
0D5561B
0D5561C
0D5549
0D5549B
0D5549C
0D5562

ACCESSORIES
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories

0603560SSD - Released 12-05

SIEMENS PART No.


ED43B015
ED43B015AESA
ED43B015AESB
ED63B015
ED63B015AESA
ED63B015AESB
ED43B020
ED43B020AESA
ED43B020AESB
ED63B020
ED63B020AESA
ED63B020AESB
ED43B025
ED43B025AFSA
ED43B025AESB
ED63B025
ED63B025AESA
ED63B025AESB
ED43B030
ED43B030AESA
ED43B030AESB
ED63B030
ED63B030AESA
ED63B030AESB
ED43B035
ED43B035AESA
ED43B035AESB
ED63B035
Page 1 of 4

42

AMPS
800
800
900
900
1000
1000
1200
1200
1400
1400
1600
1600

VOLTS
600
600
600
600
600
600
600
600
600
600
600
600

GENERAC No.
0D5583B
0D5583C
0D5584
0D5584C
0E1840
0A6219C
0E1841
0A6141C
0E1842
0A6143C
0E1843
0A6145C

AMPS
600
600
700
700
800
800
1000
1000
1400
1400
1800
2000
2500

VOLTS
600
600
600
600
600
600
600
600
600
600
600
600
600

GENERAC No.
0D6643
0D6992
0D6644
0D6993
0D6645
0D6994
0E1840
0A6220
0E1842
0A6144
0E1844
0E1845
0A6149

ACCESSORIES
12V Shunt Trip & Aux Contacts
24V Shunt Trip & Aux Contacts
No Accessories
24V Shunt Trip & Aux Contacts
No Accessories
24V Shunt Trip & Aux Contacts
No Accessories
24V Shunt Trip & Aux Contacts
No Accessories
24V Shunt Trip & Aux Contacts
No Accessories
24V Shunt Trip & Aux Contacts

SIEMENS PART No.


LMD63B800PAFSA
LMD63B800PAFSB
ND63B900P
ND63B900PAFSB
NXD63B100P
ND63B100PAFSB
NXD63B120P
ND63B120P AFSB
PXD63B140MP
PD63B140PAFSB
PXD63B160MP
PD63B160PAFSB

500kW and 600kW generator sets


RATING
80% rated
100% rated
80% rated
100% rated
80% rated
100% rated
80% rated
100% rated
80% rated
100% rated
80% rated
80% rated
100% rated

SIEMENS PART No.


MD63B600P
MXD63B600HP
MD63B700P
MXD63B700HP
MD63B800P
MXD63B800HP
NXD63B100P
NXD63B100HP
PXD63B140MP
PXD63B140HP
RXD63B180MP
RXD63B200MP
STD63F2500HLI25

0603560SSD - Released 12-05

Page 4 of 4

43

NET ACCESS
MMU
Revised

TYPICAL 4/06/2009
FOR 3

Molded Case Circuit Breakers


ND 1200A Frame Sentron Series

Selection

Type NXD6

Blue Label

Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)


2-Pole 600V AC
250V DC

Continuous
Current Rating
@ 40C

3-Pole 600V AC
500V DC

Catalog
Number

List
Price $

NXD62B900
NXD62B100
NXD62B120

0900
1000
1200

Catalog
Number

10498.00
10498.00
10498.00

List
Price $

NXD63B900
NXD63B100
NXD63B120

Type ND6

13167.00
13167.00
13167.00

Blue Label

Interchangeable Trip
Continuous
Current Rating
@ 40C

Complete Breaker
Unassembled with Lugs

Frame Only

Catalog
Number

Catalog
Number

List
Price $

Catalog
Number

List
Price $

9587.00
11675.00
11675.00
11675.00

ND62F120

5424.00

MD62T800
ND62T900
ND62T100
ND62T120

2987.00
5075.00
5075.00
5075.00

12259.00
14874.00
14874.00
14874.00

ND63F120

6806.00

MD63T800
ND63T900
ND63T100
ND63T120

3747.00
6362.00
6362.00
6362.00

List
Price $

Trip Unit Only

2-Pole 600V AC, 250V DC


0800
0900
1000
1200

ND62B800
ND62B900
ND62B100
ND62B120

3-Pole 600V AC, 500V DC


0800
0900
1000
1200

ND63B800
ND63B900
ND63B100
ND63B120

Interrupting Ratings

240

480

600

250

500

65
100
200

50
65
100

25
50
65

30 (2-P)
30 (2-P)

25 (3-P)
50 (3-P)
50 (3-P)

220/240
380/415
(lcu) (lcs) (lcu) (lcs)
65
33
40 20
100
50
65 33
200 100 100 50

500
(lcu)
30
42
65

(lcs)
15
21
33

Instantaneous Adjustment Trip Range


Nominal Instantaneous Values
+20%
Tolerance
High

Breaker Ampere
Rating

+20%
Tolerance
Low

800

4000

4570

5140

5710

6280

6850

7420

08000

900-1200

5000

5715

6430

7145

7860

8575

9290

10000

Lugs
Catalog
Cables Wire
Number
per Lug Range
TA2K500
2
#1-500 kcmil Cu/Al
TA3K500
3
#1-500 kcmil Cu/Al
TC2K500
2
#1-500 kcmil Cu
TC3K350
3
#1-350 kcmil Cu
Kits (2 Kits required per breaker)
2TA4P8500 4
250-500 kcmil Cu/Al
3TA4P8500
2TA4N8500
250-500 kcmil Cu/Al
3TA4N8500 4
2TA2N8750
3TA2N8750
2TA3N8750
3TA3N8750

500-750 kcmil Cu/Al

500-750 kcmil Cu/Al

List
Price $
71.00
98.00
120.00
151.00
584.00
843.00
588.00
853.00
365.00
513.00
579.00
832.00

Enclosures
Type
1
3R
12
Neutral

Built to order. Allow 23 weeks for delivery.


NXD6

circuit breakers are UL listed for reverse


connection applications.
2-pole units available in 3-pole width only.
When wired as shown on page 6-3, this circuit breaker is
UL listed and rated for use on 500VDC ungrounded UPS
systems only.
Use 2 3TA4P8500 kits for 3-pole, or 2 2TA4P8500
kits for 2-pole. Use for 100% rated breakers.

Discount Schedule MCCB

Catalog
Number
MND61
MND63
MND612
W63623

List
Price $
897.00
2202.00
2883.00
606.00

Use

2 3TA4N8500 for 3-pole or 2 2TA4N8500 for


2-pole. Rated for 75C cable.
Note: A, page 6-81.
80% rated breakers with the CE mark will also be
marked in the 100% rated version.
HACR rated.
Note: ND frame qualified to UL489 supplement B NAVAL.
See page 6-84 for additional information.
See

Modifications page 6-84


Enclosures Section 5
Accessories pages 6-58 and 6-86 to 6-91

Siemens Power Distribution & Control, SPEEDFAX 2007-2008 Product Catalog

44

6-55

MOLDED CASE
CIRCUIT BREAKERS

ND6, NXD6
HND6, HNXD6
CND6

IEC 947-2
Volts AC (50/60HZ)

Complete Breaker Unassembled


with Lugs
Prices of ND6 and HND6 breakers
include frame, trip, and both line and
load lugs (3TA4N8500). These catalog
numbers are the frame, trip and lugs
separately packaged. For applications
requiring different lugs, order
individual items as needed.
Complete Breaker Assembled
without Lugs
Prices of NXD6, HNXD6, and
CND6 include frame with
non-interchangeable trip units
installed only. Order required
terminal connectors separately.
For line and load lugs (3TA4N8500)
installed, add suffix L to catalog
number (add 2 times list price of
lug kit).
100% Rated (3-Pole only)
Types NXD6, HNXD6 and CND6
breakers are available with 100%
ratings. To order, add suffix H to
catalog number, and add 10% to
list price. 100% rated ND breakers
require 90C Cu cable sized at 75C
ampacity and lug kit 3TA4P8500
or 3TA3N8750.
50C Applications see page 6-84.
400Hz Applications see page 6-84.

Breaker
Type

RMS Symmetrical Amperes (KA)


UL 489 A IR
Volts AC
Volts DC

Ordering Information

Molded Case Circuit Breakers


ND 1200A Frame Sentron Series

Selection/Dimensions

Type HNXD6 

Black Label

Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)


2-Pole

3-Pole

Continuous
Current Rating
@ 40C

600V AC/250V DC

600V AC/500V DC

0900
1000
1200

For 2-pole application use outside


poles of 3-pole circuit breaker

Catalog
Number

List
Price $

HNXD63B900
HNXD63B100
HNXD63B120

14794.00
14794.00
14794.00

Type HND6 

Black Label

Interchangeable Trip
Continuous
Current Rating
@ 40C

Complete Breaker
Unassembled with Lugs

Frame Only

Catalog
Number

Catalog
Number

List
Price $

Trip Unit Only


List
Price $

Catalog
Number

List
Price $

2-Pole 600V AC, 250V DC 


0800
0900
1000
1200

For 2-pole application use outside poles of 3-pole circuit breaker

3-Pole 600V AC, 500V DC 


0800
0900
1000
1200

HND63B800
HND63B900
HND63B100
HND63B120

13883.00
16498.00
16498.00
16498.00

HND63F120

8430.00

MD63T800
ND63T900
ND63T100
ND63T120

MOLDED CASE
CIRCUIT BREAKERS

Type CND6 

3747.00
6362.00
6362.00
6362.00

Red Label

Fuseless Current Limiting


Non-Interchangeable Trip (Assembled Circuit Breaker)
Continuous
Current Rating
@ 40C
0900
1000
1200

2-Pole

Catalog
Number
For 2-pole application,
use outside poles of
3-pole circuit breaker

Lugs

3-Pole

CND63B900
CND63B100
CND63B120

List
Price $
20489.00
20489.00
20489.00

Shipping Weights

When lugs shield NDTS is used.


Note: NDTS lug shields are required when oversized lugs
TA4P8500 or TA4N8500 are used. The kits include
the NDTS shield.

Dimensions (in inches)

Number of
Number per
Shipping
Poles
Carton
Weight (lbs.)
ND6, HND6, NXD6, HNXD6, CND6
Assembled Breaker (less terminals)
2
1
53
3
1
61.5
ND6, HND6 Frame Only
2
1
42.25
3
1
46
ND6, HND6 Trip Unit Only
2
1
04.5
3
1
06.5

Breaker
Type

D1

ND6, NXD6, HND6,


HNXD6, CND6,
SND6, SHND6, and
SCND6

16

8.25

with NDTS
lug shield

24

8.25

For inches / millimeters conversion, see Application Data section.


Built to order. Allow 23 weeks for delivery.
 HNXD6

and CND6 circuit breakers are UL Listed for


reverse connection applications.
 2-pole units available in 3-pole width only.

6-56

 When

wired as shown on page 6-3, this circuit breaker is


UL listed and rated for use on 500V DC ungrounded
UPS systems only.
 HACR rated.

Siemens Power Distribution & Control, SPEEDFAX 2007-2008 Product Catalog

45

Discount Schedule MCCB

NET ACCESS MMU: TYPICAL FOR 3


Siemens Circuit Breaker Lug Types and Minimum and
Maximum Wire Sizes
Amp
Rating

Breaker
Type

Standard Lugs
Min/Max Wire Size

Siemens Lug Part


Number

15-100

BQ 240 V

#14 - 1/0

Part of C.B

125

BQ 240 V

#2 - 2/0

Part of C.B

30-60

ED (600 V)

#10 - 1/0

Part of C.B

70-100

ED

#10 - 1/0 Cu or Al

LN1E100

125

ED

#3 - 3/0

TA1E6125

150

FD

#6 - 350 MCM

TA1FD350A

175

FD

#6 - 350 MCM

TA1FD350A

200

FD

#6 - 350 MCM

TA1FD350A

225

FD

#6 - 350 MCM

TA1FD350A

250

FD

#6 - 350 MCM

TA1FD350A

300

JD

2 - 3/0 - 500 MCM

TA2J6500

350

JD

2 - 3/0 - 500 MCM

TA2J6500

400

LD

2 - 3/0 - 500 MCM

TA2J6500

500

LD

2 - 3/0 - 500 MCM

TA2J6500

600

LD

2 - 3/0 - 500 MCM

TA2J6500

700

LMD

3 - 1/0 - 500 MCM

TA3K500

800

LMD

3 - 1/0 - 500 MCM

TA3K500

900

ND

4 - 250 - 500 MCM

3TA4N8500

1000

ND

4 - 250 - 500 MCM

3TA4N8500

1200

ND

4 - 250 - 500 MCM

3TA4N8500

1400

PD

5 - 300 - 600 MCM

TA5P600

1600

PD

5 - 300 - 600 MCM

TA5P600

1800

RD

5 - 300-600 MCM

TC5R600

2000

RD

5 - 300-600 MCM

TC5R600

2500

STD

6-250-600 MCM

TA6R600STD

3200

STD

6-250-600 MCM

TA6R600STD
5/12/2006

Document 0603600SSD 5/06

46

NET ACCESS MMU:


TYPICAL FOR 3

POWER SYSTEMS

COOLANT HEATERS

1) ALL DIMENSIONS ARE REFERENCE


2) BY-PASS IS LOCATED INTERNAL
3) HEATER MUST BE MOUNTED HORIZONTALLY

47

BL 09/08

0A9779$

SHEET 2 OF 2

NET ACCESS MMU:


TYPICAL FOR 3

48

Battery Index
800-346-3760 National Hotline
Warranty by Exide Corp.
Lead Calcium Type
Dry Batteries Available**

NET ACCESS MMU:


TYPICAL FOR 3

Gas Gensets Available Batteries

Generac Part #

Engine

System
Voltage

Battery
Quantity

77483 (75AH)

G2.4 QTA

12

G4.2

12

G5.4 QTA

12

G6.8 QTA

58208 (75AH)

58665 (90AH)

61119 (110AH)

12

G6.8

12

G13.3

24

61104 (225AH)

X or L

58665 (90AH)

61119 (110AH)

61104 (225AH)

X = Battery available installed.


L = Battery available only as shipped dry and loose for location outside the generator skid.

Diesel Gensets Available Batteries


Generac Part #

Engine

System
Voltage

Battery
Quantity

D2.4

12

D3.0

12

D3.9

24

D4.5

12

D6.8

24

D7.5

24

D9.0

24

D12.0

24

D13.5

24

D16.0 Mits

24

D16.0 Volvo

24

X or L

D18.0

24

X or L

D22.0

24

X or L

77483 (75AH)

58208 (75AH)

X = Battery available installed.


L = Battery available only as shipped dry and loose for location outside the generator skid.

Battery Specifications
Dimensions (inches)

Part
Number

Group
Number

Amp
Hours*

CCA
@ 0 F

77483
58208
58665
61119
61104

26
24F
27F
31
8D

75
75
90
110
225

525
525
700
925
1155

6.75
6.75
6.75
6.75
11.12

8.19
10.63
12.50
13.00
20.75

7.75
8.88
9.00
9.40
9.88

8D
B

26
27F
31

All batteries are 12 volt, 6 cell construction.


For 24 volt systems, batteries are paired in series.
* Battery ampere-hours (AH) are estimated for reference only. Use cold cranking amps (CCA) as the
actual performance criteria.
** Add an "A" suffix to the Generac part number for dry batteries, which are shipped without electrolyte.

49

0161970SBY
Printed in USA 8.99,
rev. 07.09

NET ACCESS MMU: TYPICAL FOR 3


Batter
y War
mers
Battery
armers

War
ms and Insulates Batter
y
arms
Battery
Ther
mostatically Controlled
Thermostatically
30F On Temper
ature
emperature
40F Off Temper
ature
emperature
120V Operation
2 Siz
es A
vailab
le
Sizes
Av
ailable
80W - One Battery
160W - Two Batter
y
Battery

Blank
et type Batter
y War
mers are designed ffor
or installations where
Blanket
Battery
armers
reliable starts are a must.
Batter
y War
mers in conjuction with a coolant jac
ket heater will insure
Battery
armers
jack
that the engine will reach maximum cranking speed.
Batter
y War
mers are ffactor
actor
y installed and wired to a 4 junction bo
x,
Battery
armers
actory
box,
the junction box houses the ambient temperature sensor and provides a con
venient location ffor
or hard wir
ing to a utility source
conv
wiring
source..
6

Batter
y War
mer
Battery
armer

Batter
y War
mer
Battery
armer
Dimensions
6
72
Thermostat
Black

36

Green
White

UP

UP

Customer
Connections

Electrical Schematic
0161980SBY / Printed in USA 8.99, 12.99

50

NET ACCESS MMU:


TYPICAL FOR 3

10 Amp
Dual Rate Battery Chargers
n

12 and 24 volt systems available.

Fully automatic high performance.

Controlled 10 amp charging current.

n
n
n

Simple, concise monitoring with


panel-mounted DC ammeter and DC
voltmeter.
Switch-mode power supply maintains
proper charge voltage.
Compact and lightweight design.

n
High Performance
12 and 24 Volt Systems

Automatic Response to
Battery Voltage Levels

Safe, Accurate Charging

The Generac 12 and 24 volt battery


charging systems are designed to
provide the ultimate in automatic
battery voltage maintenance.

Our automatic equalizer system uses


a control circuit to limit charging
current to 10 amps. maximum
battery charge is 2.30 volts per cell,
or 13.8 volts for a 12 volt battery and
27.6 volts for a 24 volt battery.

When the battery reaches maximum


charge, this high-performance charger
switches to its equalize mode.
Charging current is allowed to taper
off. At 2 amps, the charger shifts to
float mode. Just enough current is
supplied to maintain the battery at or
above 13 (or 26) volts.

The key is a switch-mode power


supply system with automatic float
and equalizer control. Precise
monitoring of the battey's voltage
automatically activates the correct
charging mode. The charge rate is
limited and controlled to efficiently
and safely maintain ideal battery
levels under varying conditions.

When battery voltage drops beyond a


pre-set level below its maximum
charge, charging current increases to
5 amps, then to the 10 amp bulk
charge rate if needed to reach
optimum levels.

51

Battery voltage must be above 11


(22) volts before charging begins, and
maximum open circuit voltage is 17.5
(35) volts. Charger and battery are
protected agains reverse connection.

Specifications

Part No.
Nominal Battery Voltage
Bulk Charge Voltage
Equalize/Float Voltage
Ampere TaperMax. to Min.
Nominal Output Voltage Regulation
Input Voltage
Net Weight (lbs.)
Depth x Width x Height (inches)
Ambient Temperature

79535

79525

12
11 to 13.8
13 to 13.8
10 to 0
+2%
120 VAC
7.5
5.5 x 10 x 7.5
-40oF to 140oF

24
22 to 27.6
26 to 27.6
10 to 0
+2%
120 VAC
7.5
5.5 x 10 x 7.5
-40oF to 140oF

GENERAC POWER SYSTEMS, INC. P.O. BOX 8 WAUKESHA, WI 53187


262/544-4811 FAX 262/544-4851
All specifications subject to change without notice.

Bulletin 074800000S / Printed in USA 6.97 rev: 11.02

52

53

NET ACCESS MMU


TYPICAL FOR 3

NET ACCESS MMU:


TYPICAL FOR 3

125A Load Center

DESCRIPTION

The 125A Load Center is a unit-mounted distribution panel that is standard equipment on all Generac generator sets
that utilize PM-GC or PM-PC control systems. This main lug load center includes all of the circuit breakers required
for the coolant heater, battery charger, and other factory-installed optional AC loads within the generator set, and
serves as a convenient connection point for the customers utility feed for these AC loads. All breakers are labeled and
factory-wired to the AC loads.

SPECIFICATIONS
Siemens part number E0816ML1125SCU
125A Main Lugs EQ Load Center
100,000A IR
Single phase, copper bus
UL listed
Uses Siemens QP type circuit breakers
Maximum of 8 single pole breakers
Maximum of 4 two pole 240V breakers
Enclosure type: NEMA 1
Mounted on genset frame near control panel/display unit*
Dimensions (inches): 14.75H x 12.375W x 3.875D
*Please refer to applicable generator set installation drawing for load center location details.

Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com
2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0183630SSD/Printed in U.S.A. 06.09

54

NET ACCESS MMU: TYPICAL FOR 3

21 Light Remote Annunciator

Model
Model
Model
Model

0054650
0054660
0054640
0056370

Remote Annunciator Panel without Relays


Remote Relay Panel without LEDs and Keypad ( Relays Only)
Remote Annunciator Panel with 8 Relays
Flush Mount Enclosure w/o Annunciator

Description:
The remote Annunciator Panel provides remote monitoring
and annunciation of up to 18 generator parameters using
LEDs located on the annunciator keypad. It also provides
two system level warnings which are System Ready and
Communications OK.
The Relay panel has up to 8 selectable functions on form
A relays, and multiple relay panels can be connected for
all 18 generator parameters.

The specific faults can be selected using either the DIP


switches located on the annunciator circuit board or through
a computer via the RS232 connection on the circuit board.
All relays are energized on power up and open during a
fault condition.
Communication is via a RS485 serial data link and power is
supplied by the generator battery (+12VDC or +24 VDC).
The remote Annunciator Panel complies with NFPA 99
and NFPA 110.

Environmental Specifications:
Operating Temperature.............................................................................................................................-25 C to 60 C
Humidity..................................................................................................................................0 to 95% Non Condensing
Power Supply....................................................................................................... Generator Battery, +12 or +24 Volts DC
Power Usage............................................................................................................................................... 6 watts typical
Communication Line............................................................................ RS485 fully isolated twisted pair cable with shield
Maximum Cable Length.......................................................................................................................................4000 feet
Relay Output............................... One NO contact (Engergized when annunciator is powered and no faults are present)
Relay Contact Rating................................................................................................................................ 30 VDC, 1 amp
Enclosure Rating.................................................................................................................................................. NEMA 1

55

Specifications

21 Light Remote Annunciator

Function
Color
Alarm
Latched
Pre-low Oil Pressure
Yellow
Yes
Yes
Pre- High Water Temp
Yellow
Yes
Yes
Pre Low Water Temp
Yellow
Yes
Yes
Pre- Low Fuel
Yellow
Yes
Yes
Battery Chrg AC Fail
Yellow
Yes
No
Low Battery Voltage
Yellow
Yes
No
High Battery Voltage
Yellow
No
No
Not in Auto
Red
Yes
No
RPM Sensor Loss
Red
Yes
Yes
Overcrank
Red
Yes
Yes
Over speed
Red
Yes
Yes
Low Oil Pressure
Red
Yes
Yes
Hi Water Temp
Red
Yes
Yes
Lo Water Level
Red
Yes
Yes
Emergency Stop
Red
Yes
No
Gen Running
Yellow
No
No
Gen Power (ATS)
Yellow
No
No
Line Power (ATS)
Green
No
No
Systems Ready
Green
Yes
No
Communications OK
Green
Yes
No
Spare
Green
No
No
Spare Keypad Switch - Can be used to implement a remote start function. (Model 005464 only)
9.06

Surface Mount Annunciator

1.64

The 21 Light Annunciator can mount to


a flat surface with connections through
the 0.812 Dia knockout on the back
surface or through 0.812 knockouts on
sides as shown.

5.8

0.86

0.812 Dia.

4.53

0.812 Dia.
Both sides

11.42
2.32

10.24

Flush Mount Annunciator

1.93

7.09

Four mounting holes for


21 Light Annunciator
4-mm -0.7 Female Thread

8.27

1.57
Thru

6.49

R0.59
Both Sides

1.42

1.21
9.64
Outside

Cut
Rough Opening
6.75 " x 9.88 "

This Flush Mount Box is recessed


into the wall opening and the surface mount annunciator mounts to
the (4) 4 mm screw holes on the
back surface. After wire connections are made the front annunciator cover is attached.

0.87

Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com
2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0604160SSD/Printed in U.S.A. 04.08, rev: 07.09

56

57

58

59

60

61

62

63

64

65

66

67

68

POWER SYSTEMS

EMERGENCY

BL - 10/07

061129E

PART NUMBER

NET ACCESS MMU


TYPICAL FOR 3

69

POWER SYSTEMS

BL - 10/07

0F5764

PART NUMBER

NET ACCESS MMU


TYPICAL FOR 3

WIRING DIAGRAM/PROGRAMMING, G PANEL REMOTE E-STOP

NET ACCESS MMU TYPICAL FOR 3


PLEASE NOTE:
QTY. 6 PIECES WILL SHIP LOOSE,
FOR JOB SITE INSTALLATION, BY
OTHERS.

70
70

71

POWER SYSTEMS, INC.

GenLink - DCP
Operating Manual
Version
1.0
for NET ACCESS
MMU
Typical for 3
Version 1

SAVE THESE INSTRUCTIONS The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators and potential operators of this equipment.

This manual should remain with the unit.


72

Table of Contents
GenLink-DCP Operating Manual

GENERAL INFORMATION ................................1


Introduction ..........................................................1
Features ................................................................1
Installing GenLink
Prerequisites........................................................1
GenLink ..............................................................1
Online Help............................................................1
Add Notes for Online Help ..................................1

OPERATION ........................................................2
GenLink Menus ....................................................2
GenLinks Power Manager Screens ........................3
Power Manager Configuration Screens ..................4

NOTES ..................................................................5

Generac Power Systems, Inc.

73

General Information
GenLink-DCP Operating Manual

SAVE THESE INSTRUCTIONS The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators and potential operators of this equipment.

Next, install the Microsoft Data Access Components


version 2.8 by double-clicking on this file:

INTRODUCTION
Genlink-DCP

has been developed alongside


Generac's latest control technology to give a more upto-date and feature-rich user experience. Generac
has incorporated such things as parameter file storage, variable trending, demo modes and a host of
other features. Genlink-DCP uses the industry standard Modbus protocol to communicate with
Generac's latest controllers and allows for local or
remote (via modem) communications. The package is
easy to install and user friendly with it's own online
context sensitive help system. It is recommended
using Genlink along with the user manual for the particular product purchased.

Prerequisites/MDAC_TYP.EXE
Follow the instructions. Rebooting shouldn't be necessary.

GENLINK
Install Genlink by double-clicking on the "Setup.exe"
file in the Genlink_Setup subdirectory.

ONLINE HELP
Genlink is being constantly improved with new features added on a regular basis. In order to keep the
documentation up to date, the main source of this
documentation is provided by the online help system.
This provides for context sensitive help on every
Genlink screen. This manual should only be viewed
as an introductory guide, the main source of documentation being from the online help system.

FEATURES

Context sensitive online help system


Uses industry standard Modbus protocol
Allows for local or remote (modem) connection
Runs in "Demo" mode offline
Allow product parameter uploading/storage in
files/copying and downloading
Allows product parameter editing offline
Generates multiple reports
Allows upgrades to the controller software
upgrades in the field via modem
Can perform variable trending and graphing of
multiple variables in real time
Multiple diagnostic functions
Upload and download file to controllers inbuilt
PLC (PLC programming tool is separate)
Allows setup of controllers maintenance parameters

To access online help, either click on the "Help" button or use the "F1" key. This will bring up a help document which is displayed via explorer.

ADD NOTES FOR ONLINE HELP


Personal help notes can be created with just a few
simple keystrokes. Each help screen has it's own
individual help document which is stored in the
"\help" directory. Each help page has a link to an
associated "notes" document where notes can be
added. There is one "notes" file per help document
(i.e. one per page).
The easiest way to edit the notes files is to run
Genlink and bring up the help page that needs editing. Click on the "notes" link to bring up the notes file
for that page. Right click on the help text and select
"view source" to bring up the document in notepad.
An alternative is to edit the file in notepad (or an
HTML editor) without going through Genlink, but by
using explorer to find the files. These are stored
under the "\help" directory, under the directory where
Genlink was installed.

INSTALLING GENLINK
PREREQUISITES
Before Genlink .NET can be installed, two other components will need to be in place. The two requisite
files MUST BE LOADED FIRST before Genlink is
installed.
First, install the .NET Framework version 1.1. This is
available via Windows Update, or double-click on this
file:

Note that these files are in HTML format. By using the


HTML format, headings, colored text, etc. can be
used to enhance online notes.

Prerequisites/dotnetfx.exe
Follow the instructions presented, then be sure to
shutdown and restart the machine before going on to
the next steps.

Generac Power Systems, Inc.

74

Operation
GenLink-DCP Operating Manual

In the sample shown below, text can be simply added


or edited as normal in the area shown in bold.

GENLINK MENU'S
Genlink uses pull down menu's to access it's features
(Figure 1).

<html>
<head>
<!-- $Id: E_Panel_Display.html,v 1.1 2003/10/10 20:17:22 Exp $ -->
<title>Genlink: E Panel Display</title>
</head>
Background Color
<body bgcolor="white">
<h1>Genlink: E Panel Display</h1>

The tables at the top of page 3 show where the features can be found:

The Header

This is the main area of text that will be displayed when help is
requested.
</body>
</html>

Main Text

For additional features that HTML offers, consult a


guide to the HTML format.

Figure 1 GenLink Menu

Pull Down Menu

Menu Bar

Generac Power Systems, Inc.

75

Operation
GenLink-DCP Operating Manual

Connection

Configuration

Tools

Diagnostics

Alarm/Event log

Connect
Disconnect
Demo
Exit

Analog inputs
Digital inputs
Output Functions
Communications
Engine settings
Regulator settings
Governor settings
Generator settings

Get slave ID
Test COM port
Test dial out

Analog input
Digital input
Output functions
Digital outputs

Alarm log
Event log
Alarm log parameters
Event log parameters

Files

PLC

Trending

File transfer

PLC

Trending setup

Index

Local trending

Search

Remote trending

About

File edit (offline)

Maintenance

Help

GENLINK'S POWER MANAGER SCREENS


The Power Manager screens that are shown by
Genlink incorporate mimic screens and other methods to access extra features that are particular to this
product (Figures 2 and 3).

Figure 2 Power Manager Screen


Output relay status

Utility monitoring option

Generator total power measurements

Click here to alter the time/date

16:04:32 12/02/03

Click to configure
Power Manager
Click here to access
this generator

Click here to access


this generator

Mimic of main
transfer switch

Mimic of generators
transfer switch

Lights RED when LIVE

Generac Power Systems, Inc.

76

Operation
GenLink-DCP Operating Manual

POWER MANAGER CONFIGURATION


SCREENS

Figure 3 Power Manager


Screen
This generators power and power factor

See Figure 4.
For detail of individual features and commands, refer
to the online help system or the product manual.

Rotates to
indicate
generator is
running

Turns RED when


switched to AUTO

Turns RED when an


alarm is present

Shows the status of this generators transfer


switch (mimic will open and close)

Figure 4 Power Manager Configuration Screens


Click on these tabs to select the configuation types (pages)

To add a new generator, fill


in the details here then click
ADD TO LIST

To edit generator details, first click on


the one that needs to be edited. Then
use the boxes on the right to edit them.
Then click UPDATE to apply them.

Generac Power Systems, Inc.

77

NET ACCESS MMU: TYPICAL FOR 3


GENERAC POWER SYSTEMS STANDARD TWO-YEAR LIMITED WARRANTY
FOR MODULAR STATIONARY EMERGENCY POWER SYSTEMS (MPS)
NOTE: ALL UNITS MUST HAVE A START-UP INSPECTION PERFORMED BY AN AUTHORIZED GENERAC DEALER.
For a period of two (2) years or two thousand (2,000) hours of operation from the date of start-up, which ever occurs first, Generac Power Systems,
Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/
Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty
schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/Certified
Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "MPS" Stationary
Emergency applications, as Generac Power Systems, Inc. has defined MPS Stationary Emergency, provided said generator has been initially installed
and/or inspected on-site by an Authorized/Certified Generac Power Systems Dealer, or branch thereof. Scheduled maintenance, as outlined by the
generator owner's manual, must be performed by an Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This will verify service
has been performed on the unit throughout the warranty period. This warranty is limited to and available only on Liquid-cooled units.

WARRANTY SCHEDULE
YEAR ONE One hundred percent (100%) coverage on mileage, labor, and parts listed.
ALL COMPONENTS ENGINE, ALTERNATOR AND TRANSFER SWITCH
YEAR TWO One hundred percent (100%) coverage on parts listed.
ALL COMPONENTS ENGINE, ALTERNATOR AND TRANSFER SWITCH PARTS ONLY

Gearbox Equipped Units - Limited Gearbox Coverage


YEARS ONE THROUGH FIVE Parts and labor coverage on gearbox and components.
YEARS SIX THROUGH TEN Parts only coverage on gearbox and components.

Guidelines:
Warranty only applies to permanently wired and mounted units.
Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or
branch thereof.
A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the generator set. If a Non-Generac Power
Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the generator set, no warranty coverage shall apply.
All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, Procedures and Flat Rate
Manual.
Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable except with change of
ownership of original structure.
Unit enclosure is only covered during the first year of the warranty provision.
Use of Non-Generac replacement part(s) will void the warranty in its entirety.
Engine coolant heaters (block-heaters), heater controls and circulating pumps are only covered during the first year of the warranty provision.

THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:


1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.

Any unit built/manufactured prior to July 1, 2004.


Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).
Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.
Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems has defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and.
Failures caused by any act of God and other force majeure events beyond the manufactures control.
Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.
Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s).
Damage related to rodent and/or insect infestation.
Failure due to misapplication, misrepresentation, or bi-fuel conversion.
Telephone, facsimile, cellular phone, satellite, Internet, or any other communication expenses.
Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.).
Overtime, holiday, or emergency labor.
Modes of transportation deemed abnormal (refer to Generac Power Systems Warranty, Policies, Procedures and Flat Rate Manual).
Steel enclosures that are rusting due to improper installation, location in a harsh or saltwater environment or scratched where integrity of paint
applied is compromised.
Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem.
Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).

THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Any implied warranties which
are allowed by law, shall be limited in duration to the terms of the express warranty provided herein. Some states do not allow limitations on how long
an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT
SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A
DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/
owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner
specific legal rights. Purchaser/owner also may have other rights that vary from state to state.

Generac Power Systems, Inc. P.O. Box 8 Waukesha, WI 53187


Ph: (262) 544-4811 Fax: (262) 544-4851
1-888-GENERAC (1-888-436-3722)
Bulletin 0166310SBY Rev. B / Printed in U.S.A. 12.08

78

WARSHAUER

19

54

GeneratorDivision

800ShrewsburyAvenue,TintonFalls,NJ07724Phone732.741.6400Fax732.741.3866

JOBNAME:______________________________ADDRESS______________________________
STANDBYGENERATORSETINSTALLATIONCHECKLIST
PLEASECHECKTHEEMERGENCYPOWERSYSTEMWITHTHEFOLLOWINGLISTTOINSURE
PROPERANDCOMPLETEINSTALLATION.CHECKLISTMUSTBECOMPLETEDANDRETURNED
TOTHEADDRESSABOVE,ATTENTIONOFJOHNWERDEN,ATLEASTTWOWEEKSPRIORTO
SCHEDULEDSTARTUPDATE.
PLEASENOTE:IF,FORANYREASON,THESTARTUPCANNOTBECOMPLETEDDUETO
CIRCUMSTANCESBEYONDOURCONTROL,ORNOTINCLUDEDONTHISCHECKLISTBYTHE
ELECTRICALCONTRACTORORPERSON(S)RESPONSIBLEFORITSCOMPLETION,THE
CUSTOMERWILLBECHARGEDATOURSTANDARDRATESFORLABOR,TRAVELANDMILEAGE.

3TO5FOOTCLEARANCEAROUNDTHEGENERATORISREQUIRED.
TURNMAINGENERATORCONTROLSWITCH,ONTHECONTROLPANEL,OFF.
(___)1.CONTROLWIRING: AllDCVoltagewiresshouldberunbetweenjunctionbox,
transferswitches,annunciator,etc.,thecontroller,andterminated.Contractortosizewires
toallowforvoltagedrops.

WARNING: DO NOT RUN ANY DC CONTROL WIRES IN THE SAME CONDUIT AS THE AC
POWER WIRES. DOING SO WILL CAUSE DAMAGE AND FAILURE TO THE CONTROL LOGIC IN
GENERATORANDTRANSFERSWITCH.
(___)2.ACCONDUCTORS:InsureACConductorsarerunandterminatedbetweengenerator
andtransferswitches.

79

NOTE:NEUTRALANDEQUIPMENTEARTHGROUNDWILLBERUNPERCODES.
(___)3.EMERGENCYPANEL:Properlysizedfuseddisconnectorbreakershouldbeinstalled
beforestartupifgeneratorfeedsanemergencypanelbeforegoingtothetransferswitches.
(___)4.DIESELFUELLINES:(WHEREAPPLICABLE)
A. Fuellinesfromdaytanktomaintankandengineshouldbecomplete.
B. Supplylinefrommaintanktopumpondaytankshouldbeconnectedtothepick
uptubeonmaintank.
C. Runreturnlinefromenginetodaytank.
D. Runreturnlinefromdaytanktomaintank.
E. Daytankandmaintankshouldbevented.
F. Blackpipeorcoppershouldbeusedforfuellines.

NOTE:NEVERUSEGALVANIZEDPIPE
(___)5.MAINFUELTANK:Besurefueltankisfilledwithfuel.
(___)6.DAYTANK:
A. A.C.Motorshouldbewiredtotheemergencypanel.
B. Daytankshouldbeinstalledonsamelevelastheengine.
(___)7.NATURAL/LPGAS:
A. Insurethatpropergaspressureisavailable.NOTE:RefertoOwnersManualfor
HomeStandbyGenerators.
B. Ifusingvapor,thepressureshouldbe(11)to(14)incheswatercolumnfromthe
primaryregulatortotheinletofsecondaryregulatorortheengine.
C. Pipingfromthemainandthegaspipingtotheunitneedstobeproperlysizedto
supplythecorrectvolumeandpressuretotheengineatfullratedload.
D. GASFUELFLEXLINEMUSTBEINSTALLEDATTHEGENERATOR.

NOTE:CHECKSUBMITTALDRAWINGSFORREQUIREMENTS.
(___)9.ISOLATORS:GENERACgeneratorsetsareequippedwithstandardfactoryinstalled
rubberisolatorsbetweenengine/generatorbaseassemblyandframe.Ifspringisolatorsare
required,theyshouldbeinstalledbetweenthegeneratorandthetankorpad.

80

(___)10.ENGINEHEATERS:Thewiringtotheblockheatershouldbeinstalledand
terminated.DONOTPOWERUP.
(___)11.RADIATORDUCT:iftheinstallationisindoors,allductwork,betweentheradiator
andthelouvers,needstobecompleted.
(___)12.LOUVERS:Intakeanddischargelouversneedtobecompletelyinstalled.Allcontrol
wiringbetweentheenginerunrelayandthelouversshouldberunandterminated.
(___)13.BATTERIES:Batteriesareprovidedwiththegeneratorbutnotinstalled.

NOTE:DONOTCONNECTBATTERIES.THISWILLBEDONEBYWARSHAUER
SERVICEATTIMEOFSTARTUP.

(___)14.BATTERYCHARGER:ACpowerconnectionsshouldbemadefromtheemergency
panel.

NOTE:DONTENERGIZETHECIRCUIT
(___)15.Makesuregeneratorissecuredtothepad.
(___)16.Allapplicableelectricalinspectionsmustbecompletedpriortostartup.
(___)17.CLEANING:Inordertopreventinjurytopersonnelanddamagetoequipment,
debrisshouldbecleanedfromunderneaththegeneratorandfromthesurroundingarea.
(___)18.Warshauerrequeststhattheelectricalcontractordoingtheinstallationbepresent
attimeofstartup.
(___)19.ADDRESS&DIRECTIONS:PleaseprovidedirectionstothejobsitefromTintonFalls,
NJ.
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

81

IMPORTANT
BEFOREASTARTUPCANBESCHEDULED,GENERATORMUSTBEPAIDINFULL.

CONTACTINFORMATION

ELECTRICIAN:Company,Contact,Phone_________________________________
___________________________________________________________________
JOBSITE:Superintendent,Phone_______________________________________
__________________________________________________________________
COMPLETIONVERIFIEDBY:________________________DATE:_______________
SCHEDULEDSTARTUPDATE:__________________________________________

PLEASENOTIFYWARSHAUERSERVICEIFTHEREISANYTHINGTHATWESHOULD
KNOWABOUTTHEJOBSITEORINSTALLATIONTHATISNTCOVEREDABOVEOR
IFANYPROBLEMARISESTHATMAYDELAYTHESTARTUP.