CAUTION

NXL
0003-0012 5
0016-0031 5
0038-0061 5

VEDI MANUALE BASE CAPITOLO 1

D1

H1
Unit dimensions (mm)
NXL
H1 W1 D1
0003-0012 5 327 128 190
0016-0031 5 419 144 214
0038-0061 5 558 195 237

H2
B- B+ R- U/T1V/T2 W/T3
L1 L2 L3

W2

Mains

W1

4 CONTROL CONNECTIONS

1
2
3
4
5
6
7
8
9
10
11
18
19
A
B
30
21
22
23

1...10 kOhm

mA
9 10 11 18 19 A B 30

21 22 23

START-UP WIZARD

Brake
resistor

M
CONTROL I/O extension (optional)

CONTROL I/O standard


I/O extension boards

Fieldbus boards

Terminal
10 Vref
AI1+
AI1AI2+
AI224 Vout
GND
DIN1
DIN2
DIN3
GND
AO1+
AO1RS 485
RS 485
+24V
RO1
RO1
RO1

Signal
Default
Reference voltage
Analog input,
0-10V
Analog input common
Analog input,
0/4-20 mA
Analog input common
24 V auxiliary voltage
I/O ground
Digital input 1
Start forward
Digital input 2
Start reverse
Digital input 3
Preset speed 1
I/O ground
Analog output Output freq.
Analog output common
Serial bus (Modbus RTU)
Serial bus
External control voltage supply
Relay output 1
FAULT

OPT-AA

1
2
3
4
5
6
24
25
26

Terminal
+24V
GND
DIN1
DIN2
DIN3
DO1
RO1
RO1
RO1

Signal
Default
24 V auxiliary voltage
I/O ground
Digital input 1 Preset speed 2
Digital input 2 Fault reset
Digital input 3 Disable PID
Digital output Ready
Relay output 1
RUN

12
13
14
15
16
28
29
25
26

Terminal
+24 V
GND
DIN1
DIN2
DIN3
TI1+
TI1RO1
RO1

Signal
Default
24 V auxiliary voltage
I/O ground
Digital input 1 Preset speed 2
Digital input 2 Fault reset
Digital input 3 Disable PID
Thermistor input
Thermistor input

OR

OPT-AI

Relay output 1
RUN

=Push the button

START

rpmn

MODE

I n (A)

DONE

+
rpm

P2.1.6 Motor Un (V)*

P2.1.7 Motor fn(Hz)

3
s

3
s

I *1,5
H

400
V*

50
0=
0=
Hz Ramp Coasting

20 50
Hz Hz

20
s

20 I *1,1
L
s

400
V*

50
0=
0=
Hz Ramp Coasting

20 50
Hz Hz

5
s

5
s

IL*1,1

400
V*

50
0=
1=
Hz Ramp Ramp

0 50
Hz Hz

1
s

1 IH*1,8
s

400
V*

50
0=
0=
Hz Ramp Coasting

Fan

Pump

High
performance

P2.1.12 Stop funct.

P2.1.4 Dec time (s)

0 50
Hz Hz

P2.1.11Start funct.

P2.1.3 Acc time (s)

P2.1.5 Current limit(A)

P2.1..2 Max.Freq (Hz)

Standard

3 Accept

0=
Not
used
0=
Not
used
0=
Not
used
1=
automatic
torque
boost

ENTER
reset

5 Accept
4 Tune
n(rpm)

0=
Ai1
0-10V
0=
Ai1
0-10V
0=
Ai1
0-10V
0=
Ai1
0-10V

0=
Not
used
0=
Not
used
0=
Not
used
0=
Not
used

P3.1 Control place

mode. See
table below!

to activate (in
stop mode)

P2.1.21 Auto restart

2 Select the

1 Push 5 seconds

ENTER
reset

P2.1.14 I/0 ref

ENTER
reset

P2.1.13 U/f optimization

P2.1.1 Min. Freq (Hz)

Dimensions (mm)
A
B
C
D
20 20 100 50
20 20 120 60
30 20 160 80

3 POWER
CONNECTIONS

Mounting dimensions (mm)


H2 W2
313 100 7
406 100 7
541 148 9

1 2 3 4 5 6 7 8

VER EL CAPITULO. 1 DEL MANUAL

MOUNTING
NXL
0003-0012 5
0016-0031 5
0038-0061 5

A =Clearance around the unit


B =Distance from the unit to another unit
C =Free space above the unit
D =Free space underneath the unit

SEE USERS MANUAL CHAPTER 1


HIGH VOLTAGE!
VARAUSJNNITE! KATSO KYTTOHJE KOHTA 1
HG SPNNING! SE ANVNDARMANUALEN KAPITEL 1
HOCHSPANNUNG! SIEHE BETRIEBSANLEITUNG KAP. 1
HAUTE TENSION! VOIR MANUEL UTILISATEUR CHAP. 1

ALTA TENSIONE!
ALTA TENSIN!

COOLING

6 Tune 7 Accept
I(A)

I/O
I/O

I/O

I/O

*In drives of 208V...230V


this value is 230V

ENTER

reset

ENTER
reset

NOTE! Startup Wizard returns


all other parameters to factory
defaults!

PARAMETER SETTINGS

6 MENU STRUCTURE

SELECTED MODE

Expander board menu


System menu
Fault history menu

MOTOR NAME PLATE VALUES

Standard mode

P 2.1.8 Nominal motor speed

Fan mode

P 2.1.9 Nominal motor current

Pump mode

Active faults menu

High performance mode

Keypad control menu

BASIC PARAMETERS

ENTER
reset

Parameter menu

Navigation and
selection keys

Parameter

P 2.1.1

Min frequency

P 2.1.2

Max frequency

Signal name

Unit

P 2.1.5

V1.1
V1.2

Output frequency
Frequency reference
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC-link voltage
Unit temperature
Analogue input 1
Analogue input 2
Analogue output current
Analogue output current 1, expander board
Analogue output current 2, expander board
DIN1, DIN2, DIN3
DIE1, DIE2, DIE3
RO1
ROE1, ROE2, ROE3

Hz
Hz

P 2.1.6

Nominal voltage
of the motor

V1.7
V1.8
V1.9
V1.10
V1.11
V1.12
V1.13
V1.14
V1.15
V1.16
V1.17
V1.18
V1.19
V1.20
V1.21
V1.22
V1.23
V1.24
V1.25

rpm
A
%

mA
mA
mA

Parameters

ENTER
reset

Selections
(Hz)

P3.3 Keypad direction

0= Forward, 1= Reverse

P3.4 Stop button activation

0= Limited function, 1= Always enabled

P3.5 PID reference 1

(%)

P3.6 PID reference 2

(%)

(V)

P2.1.17 DIN2 function

(A)

Nominal current
of the motor

Check the rating plate


of the motor

P 2.1.10

Motor cos

Check the rating plate


of the motor

P 2.1.11

Start function

0=Ramp
1=Flying start

P 2.1.12

Stop function

0=Coasting
1=Ramp

P2.1.18 DIN3 function

P 2.1.13 U/f optimisation

0=Not used
1=Automatic torque boost

P 2.1.14

0=AI1
1=AI2
2=Keypad reference
3=Fieldbus reference
(FBSpeedReference)
4=Motor potentiometer
5=AI1/AI2 selection

I/O reference

P2.1.19 Preset speed 1


P2.1.20 Preset speed 2
P2.1.21 Autom. restart
P2.1.22 Parameter
conceal

1=0mA - 20mA
2=4mA - 20mA
3=0V - 10V
4=2V - 10V

0=Not used
1=Start Reverse
2=Reverse
3=Stop pulse
4=External fault, cc
5=External fault, oc
6=Run enable
7=Preset speed 2
8= Motor pot. UP (cc)
9= Disable PID (Direct freq. ref.)
10=Interlock 1
0=Not used
1=Reverse
2=External fault, cc
3=External fault, oc
4=Fault reset
5=Run enable
6=Preset speed 1
7=Preset speed 2
8=DC-braking command
9=Motor pot. UP (cc)
10=Motor pot. DOWN (cc)
11=Disable PID (PID ctrl selection)
12=PID Keypad ref. 2 selection
13=Interlock 2
14=Thermistor input (See Ch. 6.2.4)
15=Force control place to I/O
16=Force ctrl place to fieldbus
17=AI1/AI2 selection

(Hz)
(Hz)
0=Not used 1=Used
0=All parameters and
menus visible
1=P2.1 and menus
MI - H5 visible

FAULT CODES

10

1= I/O Terminals, 2=Keypad, 3=Fieldbus

R3.2 Keypad reference

Check the rating plate


of the motor

P 2.1.9

P2.1.15 AI2 signal range

%
%
%
%

Mode: 0= Not selected (default), 1= Standard,


2= Fan, 3= Pump, 4= High performance

P3.1 Selection of control place

(s)
Output current limit (A)
of the unit

Note

0=Not used
1=Output freq. (0-fmax)
2=Freq. reference (0-fmax)
3=Motor speed (0-Mot.nom. spd)
4=Output current (0-InMotor)
Analogue 5=Motor torque (0-TnMotor)
6=Motor voltage (0-UnMotor)
output function 7=DC-link volt (0-1000V)
8=PI controller ref. value
9=PI contr. act. value 1
10=PI contr. error value
11=PI controller output

size frequency converter.

%
V
V
C

DOE1
PID Reference
PID Actual value
PID Error value
PID Output
Autochange 1,2,3

P2.1.16

(s)

Parameter

(Hz)
P 2.1.7 Nominal frequency Check the rating plate
of the motor
of the motor
(rpm)
Nominal speed The default applies for a 4P 2.1.8
of the motor pole motor and a nominal

8 KEYPAD CONTROL MENU K3

NOTE: If fmax > than the


motor synchronous speed,
check suitability for motor
and drive system

P 2.1.4 Deceleration time


1

Code

V1.5
V1.6

Code

(Hz)

P 2.1.3 Acceleration time


1

Current
limit

V1.3
V1.4

Note
(Hz)

Monitoring menu

7 MONITORING MENU M1

Code

CODE

FAULT

CODE

1
2
3
8
9
11
13
14
15
16
17
22
24
25

Overcurrent
Overvoltage
Earth fault
System fault
Undervoltage
Output phase supervision
Frequency converter undertemperature
Frequency converter overtemperature
Motor stalled
Motor overtemperature
Motor underload
EEPROM checksum fault
Counter fault
Microprocessor watchdog fault

29
34
35
39
40
41
44
45
50
51
52
53
54
55

FAULT
Thermistor fault
Internal bus communication
Application fault
Device removed
Device unknown
IGBT temperature
Device change
Device added
Analogue input Iin < 4mA (sel. signal range 4to20 mA)
External fault
Keypad communication fault
Fieldbus fault
Slot fault
Actual value supervision

ud01074

www.vacon.com

vacon nxl
quick guide