Sei sulla pagina 1di 153

PLANTA DE RESERVA FRA

DE GENERACIN DE ETEN S.A

PROYECTO
PROJECT

RESERVA FRA ETEN


CONTRATISTA
CONTRACTOR

TTULO
TITLE

CLCULOS ELCTRICOS
N DE DOCUMENTO PROYECTO
PROJECT DOCUMENT N

RFE-1-YE__-ECE-IDO-001

REV
FECHA
DATE

09-05-2014

EDITADO PARA
ISSUED FOR

PARA DISEO

JMM

PRV

JSA

REALIZADO
DONE BY

REVISADO
CHECKED BY

APROBADO
APPROVED BY

ESTE DOCUMENTO CONTIENE INFORMACIN PROPIETARIA Y NO PUEDE SER DUPLICADO, PROCESADO O CEDIDO A TERCEROS PARA UN USO DISTINTO AL DE
ESTE PROYECTO Y EL OBJETO PARA EL QUE HA SIDO PREVISTO SIN LA AUTORIZACIN ESCRITA DE COBRA.
THIS DOCUMENT CONTAINS PROPIETARY INFORMATION AND CAN NOT BE DUPLICATED, PROCESSED OR DISCLOSED TO THIRD PARTIES FOR ANY USE OTHER
THAN THIS PROJECT AND THE PURPOSE FOR WHICH IT IS INTENDED FOR WITHOUT THE WRITTEN CONSENT OF COBRA.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 2 de/of 23

CONTROL DE MODIFICACIONES/CHANGE LOG


Revisin

Fecha

Modificaciones

Revision

Date

Modifications

14/06/12

EDICIN INICIAL

28/03/2014

ACTUALIZACIN GENERAL

09/05/2014

ACTUALIZACIN DE ANLISIS

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 3 de/of 23

NDICE
1.

OBJETO ............................................................................................................................. 4

2.

REFERENCIAS ................................................................................................................... 5

3.

DATOS DE PARTIDA ......................................................................................................... 6


3.1.

CARACTERSTICAS DE LOS EQUIPOS .............................................................. 6

3.1.1.

RED DE 220 KV .................................................................................................... 6

3.1.2.

TRANSFORMADOR PRINCIPAL .......................................................................... 6

3.1.3.

TRANSFORMADOR AUXILIAR ............................................................................. 7

3.1.4.

GENERADORES ................................................................................................... 7

3.1.5.

TRANSFORMADORES M.T./M.T. ......................................................................... 8

3.1.6.

TRANSFORMADORES M.T./B.T........................................................................... 9

3.1.7.

MOTORES DE M.T................................................................................................ 9

3.1.8.

CARGAS DE B.T. ................................................................................................ 10

3.1.9.

GENERADOR DIESEL DE EMERGENCIA.......................................................... 11

3.1.10. LNEA DE TRANSMISIN ................................................................................... 11


3.1.11. CABLES DE MEDIA Y BAJA TENSIN............................................................... 11

4.

5.

6.

3.2.

CONSIDERACIONES .......................................................................................... 12

3.2.1.

GENERAL ........................................................................................................... 12

3.2.2.

CRITERIOS PARTICULARES PARA CADA ANLISIS ....................................... 13

ANALISIS DE LAS CONDICIONES DE FUNCIONAMIENTO........................................... 18


4.1.

ANLISIS DE FLUJO DE CARGAS ..................................................................... 18

4.2.

ANLISIS DE CORTOCIRCUITO ........................................................................ 18

4.3.

ANLISIS DE ARRANQUE DE MOTORES ......................................................... 18

CONCLUSIONES.............................................................................................................. 19
5.1.

ANLISIS DE FLUJO DE CARGAS ..................................................................... 19

5.2.

ANLISIS DE CORTOCIRCUITO ........................................................................ 20

5.3.

ANLISIS DE ARRANQUE DE MOTORES ......................................................... 20

ANEXOS ........................................................................................................................... 22

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

1.

Pg/Page 4 de/of 23

OBJETO

El objeto del presente documento es recoger el estudio de FLUJO DE CARGAS,


CORTOCIRCUITO y ARRANQUE DE MOTORES correspondiente al sistema elctrico de la
Planta de Reserva Fra de Eten (Per), a fin de establecer las caractersticas que debern tener
los equipos.

El estudio se ha realizado con el programa de diseo, anlisis y simulacin de sistemas


elctricos ETAP Powerstation, de Operation Technology, Inc., versin 12.0.0C.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

2.

Pg/Page 5 de/of 23

REFERENCIAS

[1] ISA-REP: PE-REQU-ANTE-2011-D230 Anteproyecto de Ingeniera Subestacin Reque


220 kV y obras conexas
[2] Email

RFE-CPI-GE-EML-0070. de 2012-12-13 con datos de la red 220 kV.

[3] Doc. 401A6263 GE LOAD SUMMARY


[4] Diagram

105T6742 ONE LINE DIAGRAM GAS TURBINE

[5] RFE-1-BAT-EHP-IDO-001 HOJA DE DATOS TRANSFORMADOR PRINCIPAL


[6] RFE-1-YE_-ECE-IDO-003 Clculo de Cables de Media Tensin
[7] RFE-1-YE_-ECE-IDO-004 Clculo de Cables de Baja Tensin
[8] RFE-1-YE_-ELC-IDO-001 Lista de Consumidores Electricos

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

3.

Pg/Page 6 de/of 23

DATOS DE PARTIDA

3.1. CARACTERSTICAS DE LOS EQUIPOS


En el anexo I se incluye el esquema simplificado empleado para la simulacin. En l se han
incluido los elementos descritos a continuacin.

3.1.1.

Red de 220 kV

Se considera la red de 220 kV definida por los siguientes valores:

Tensin nominal ............................................................................................................ 220 kV

Frecuencia nominal ......................................................................................................... 60 Hz

Intensidad de cortocircuito trifsica ................................................................................. 9,3 kA

Intensidad de cortocircuito monofsica ......................................................................... 10,5 kA

3.1.2.

Transformador principal

Los parmetros principales del transformador principal son los siguientes:

Potencia nominal ............................................................................................... 225 / 300 MVA

Refrigeracin ..................................................................................................... ONAN / ONAF

Relacin de transformacin .................................................................................... 220 / 18 kV

Regulacin: ............................................................................................. en carga, 10 x 1,5%

Tensin de cortocircuito ................................................................................... 10% (225 MVA)

Grupo de conexin .......................................................................................................... YNd1

Neutro a tierra .................................................................................................. Conexin slida

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

3.1.3.

Pg/Page 7 de/of 23

Transformador auxiliar

Los parmetros principales del transformador auxiliar son los siguientes:

Potencia nominal ............................................................................................... 8,5 / 11,5 MVA

Refrigeracin ..................................................................................................... ONAN / ONAF

Relacin de transformacin ..................................................................................... 18 / 6,9 kV

Regulacin: .............................................................................................. en vaco, 2 x 2,5%

Tensin de cortocircuito .................................................................................... 10% (8,5 MVA)

Grupo de conexin ......................................................................................................... Dyn11

Neutro a tierra ...................................................................... Mediante resist. De 796,74 (5A)

3.1.4.

Generadores

Los datos y curvas considerados para el generador de la turbina principal se han incluido en el
anexo II:

Generador Principal

Tensin nominal .............................................................................................................. 18 kV

Potencia aparente nominal ...................................................................................... 279,5 MVA

Potencia activa nominal ............................................................................................ 223,6 MW

Factor de potencia ........................................................................................................ 0,8 p.u.

Capacidad de potencia reactiva con cos =0,80 inductivo ....................................... 167 MVAr

Capacidad de potencia reactiva con cos =0,95 capacitivo ...................................... -86 MVAr

Reactancia subtransitoria saturada ............................................................................. 0,17 p.u.

Neutro a tierra ..........................................................................Mediante trafo-resist. (10Aprim)

Los datos del generador auxiliar se muestran a continuacin:

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 8 de/of 23

Generador Auxiliar

Tensin nominal ........................................................................................................... 6.600 V

Potencia aparente nominal .................................................................................... 10,549 MVA

Potencia activa nominal .............................................................................................. 8,44 MW

Factor de potencia ...................................................................................................... 0,80 p.u.

Capacidad de potencia reactiva con cos =0,80 inductivo .......................................6,33 MVAr

Capacidad de potencia reactiva con cos =0,95 capacitivo ................................... -3,29 MVAr

Reactancia subtransitoria saturada ............................................................................. 0,16 p.u.

Neutro a tierra Mediante resist. de 762 (5A)

3.1.5.

Transformadores M.T./M.T.

Se han empleado las siguientes caractersticas de los transformadores de los motores de MT:

Potencia nominal ......................................................................................................... 600 kVA

Refrigeracin ....................................................................................................................... AN

Relacin de transformacin ................................................................................ 6,6 / 0,505 kV

Regulacin de tensin ............................................................................................... En vaco

Regulacin en el primario .......................................................................................... 2x2,5%

Tensin de cortocircuito ...................................................................................................... 6 %

Grupo de conexin ............................................................................................................. Yd1

Neutro ............................................................................................................................ Aislado

Se han empleado las siguientes caractersticas del transformador del LCI:

Potencia nominal ..................................................................................... 5450-2725/2725 kVA

Configuracin........................................................................................................ 3 devanados

Refrigeracin ....................................................................................................................... AN

Relacin de transformacin .......................................................................... 6,6 / 2,08-2.08 kV

Tensin de cortocircuito ...................................................................................................... 6 %

Grupo de conexin ......................................................................................................... Dy1d1

Neutro ............................................................................................................................ Aislado

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

3.1.6.

Pg/Page 9 de/of 23

Transformadores M.T./B.T.

Se han empleado las siguientes caractersticas de los transformadores de servicio de MT/BT:

Potencia nominal ....................................................................................................... 3500 kVA

Refrigeracin ....................................................................................................................... AN

Relacin de transformacin ................................................................................ 6,6 / 0,505 kV

Regulacin de tensin ............................................................................................... En vaco

Regulacin en el primario .......................................................................................... 2x2,5%

Tensin de cortocircuito .................................................................................................... 12 %

Grupo de conexin ......................................................................................................... Dyn11

Neutro a tierra .................................................................................................. Conexin slida

Se han empleado las siguientes caractersticas del transformador de excitacin:

Potencia nominal ....................................................................................................... 1500 kVA

Refrigeracin .................................................................................................................. ONAN

Relacin de transformacin .................................................................................. 6,6 / 0,45 kV

Tensin de cortocircuito ...................................................................................................... 6 %

Grupo de conexin ............................................................................................................. Yd1

Neutro ............................................................................................................................ Aislado

3.1.7.

Motores de M.T.
Pn

Un

Cos

Rend.

Utilizac.

[kW]

[V]

[%]

[%]

[%]

375

4000

92

93,22

85

375

4000

92

93,22

85

224

4000

92

93

55

Motor
ATOMIZING AIR SYSTEM
COMPRESSOR DRIVE MOTOR 1
ATOMIZING AIR SYSTEM
COMPRESSOR DRIVE MOTOR 2
WATER INJECTION PUMP MOTOR

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 10 de/of 23

Pn

Un

Cos

Rend.

Utilizac.

[kW]

[V]

[%]

[%]

[%]

224

4000

92

93

55

Motor
88WN-1
WATER INJECTION PUMP MOTOR
88WN-2

Estos motores irn alimentados, cada uno, a travs de un transformador reductor de M.T./M.T.
(ver seccin 3.1.5).

3.1.8.

Cargas de B.T.

Las cargas empleadas para realizar los anlisis son los siguientes:

Cos Utilizac.

Tipo

Pn

Un

(% motor / % esttico)

[kW]

[V]

[%]

[%]

EXCITACIN

0 / 100

1500

480

100

100

LCI

0 / 100

3250

2080

100

CARGAS 1BJA76

60 / 40

230

480

85

75

1BJA80

25* / 75

340

480

85

85

MBN50AH010

0 / 100

450

480

100

90

CARGAS 1BNB52

10 / 90

74

380

90

80

CARGAS 1BMB20

75 / 25

200

480

85

83

CARGAS 1BJA11

85 / 15

570

480

80

85

CARGAS 1BJA12

85 / 15

481

480

80

85

CARGAS 1BMB52

50 / 50

190

480

80

67

CARGAS 1BJA51

50 / 50

520

480

80

70

Carga

* Indica el porcentaje de motores que no llevan variador de frecuencia.

Los motores empleados para realizar los anlisis son los siguientes:

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 11 de/of 23

Pn

Un

Cos

Rend.

Utilizac.

[kW]

[V]

[%]

[%]

[%]

PCI

200

480

85

90

80

COMPRESOR 1*

37

480

85

90

45

COMPRESOR 2*

37

480

85

90

45

AUX LUBE OIL PUMP MOTOR 1

75

480

85

95

90

AUX LUBE OIL PUMP MOTOR 2

75

480

85

95

90

Motor

* Estos motores arrancarn mediante un sistema estrella - tringulo, con el objeto de disminuir la
intensidad de arranque.

3.1.9.

Generador Diesel de Emergencia

Los datos principales del generador de emergencia son:

Tensin nominal .............................................................................................................. 480 V

Potencia aparente nominal ........................................................................................ 2500 kVA

Potencia activa nominal .............................................................................................. 2000 kW

Factor de potencia ...................................................................................................... 0,80 p.u.

Reactancia subtransitoria saturada ............................................................................. 0,19 p.u.

3.1.10. Lnea de Transmisin


Se considera la lnea de transmisin area desde la planta Reserva Fra Eten hasta S.E.
Reque, situada a 2.92 km mediante cable Narcissus (1272 MCM).

3.1.11. Cables de Media y Baja Tensin


Los cables de Media Tensin considerados son:

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Carga

Pg/Page 12 de/of 23

Configuracin Cable

Material

Aislamiento

Longitud [m]

3x(4x(1x240mm2))

Cu

XLPE (6/10 kV)

40

3x(1x150mm2)

Cu

XLPE (6/10 kV)

40

Trafo LCI

3x(3x(1x240mm2))

Cu

XLPE (6/10 kV)

40

Tablero MT Black Start

3x(3x(1x300mm2))

Cu

XLPE (6/10 kV)

120

Generador Auxiliar (BS)

3x(3x(1x300mm2))

Cu

XLPE (6/10 kV)

20

3x(1x300mm2)

Cu

XLPE (6/10 kV)

20

Trafo M.T./B.T. (1BFT51)

3x(2x(1x185mm2))

Cu

XLPE (6/10 kV)

40

Trafo M.T./B.T. (1BFT53)

3x(2x(1x185mm2))

Cu

XLPE (6/10 kV)

40

Trafo Atomizing Air 1

3x70mm2

Cu

XLPE (6/10 kV)

100

Motor Atomizing Air 1

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Atomizing Air 2

3x70mm2

Cu

XLPE (6/10 kV)

100

Motor Atomizing Air 2

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Water Injection 1

3x70mm2

Cu

XLPE (6/10 kV)

70

Motor Water Injection 1

3x70mm2

Cu

XLPE (6/10 kV)

50

Trafo Water Injection 2

3x70mm2

Cu

XLPE (6/10 kV)

70

Motor Water Injection 2

3x70mm2

Cu

XLPE (6/10 kV)

50

Acometida Tablero M.T.


Trafo Excitacin

Trafo Black Start

Adems, se han considerado los siguientes cables de Baja Tensin:


Carga

Configuracin Cable

Material

Aislamiento

Longitud [m]

Generador Diesel Emerg.

3x(6x(1x300mm2))

Cu

XLPE (0,6/1kV)

50

Cu

XLPE (0,6/1kV)

115

Sistema PCI

3x(2x(1x240mm2))+2x(
1x120mm2)

3.2. CONSIDERACIONES

3.2.1.

General

Como valores de los parmetros de los equipos elctricos no especificados en este documento

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 13 de/of 23

se han asumido los que aparecen por defecto en el programa de clculo.

No se ha incluido ningn cable ms de Baja Tensin ni embarrado de conexin, despreciando


as las prdidas que conllevaran estos elementos.

El regulador de tensin en vaco del transformador auxiliar se fija en la toma +2,5%, Los
reguladores de tensin en vaco de los transformadores de MT/BT, se han fijado en su toma
central (0%), salvo el transformador de los servicios auxiliares del Generador Auxiliar que se ha
fijado en la toma +2,5%.

Segn la norma IEC 60.076, se ha considerado una tolerancia de 10% para los
transformadores de Ucc<10%, y de 7,5% para los de Ucc>=10%.

Todos los consumidores se alimentarn desde un nico transformador de M.T./B.T.

Los clculos de flujo de carga se han realizado con el interruptor del embarrado de 480 V
acoplado, alimentando as desde un nico transformador de M.T./ B.T y con el generador disel
de emergencia parado.

Las cargas combinadas de 480 V se han empleado como equivalentes del conjunto de las
cargas en cada embarrado.

3.2.2.

Criterios particulares para cada anlisis

Flujo de cargas:

Se estudiarn los siguientes anlisis:

Caso de estudio
LF-1

Criterios de clculo

Tensin de red = 220 kV

Generador Principal; Generacin a

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Caso de estudio

Pg/Page 14 de/of 23

Criterios de clculo
cos =0,80 inductivo

LF-2

Generador Auxiliar; Generacin a cos


=0,80 inductivo

Regulador
de
tensin
de
Transformador Principal en Automtico
para conseguir la tensin nominal en el
sistema de 18 kV.

Todas
operando.

las

Cargas

Auxiliares

Tensin de red = 220 kV

Generador Principal y Auxiliar;


Generacin a cos =0,95 capacitivo

Regulador
de
tensin
de
Transformador Principal en Automtico
para conseguir la tensin nominal en el
sistema de 18 kV.

Todas
operando.

las

Cargas

Auxiliares

LF-3

(Mnima tensin en barras)

Generador
parados

Regulador
de
tensin
de
Transformador Principal en Automtico
para conseguir la tensin nominal en el
sistema de 18 kV.

Todas
operando.

LF-4

(Mxima tensin en barras)

Tensin de red = 220 kV

las

Principal

Cargas

Auxiliar;

Auxiliares

Tensin de red = 220 kV


Generador
parados

Principal

Auxiliar;

Regulador
de
tensin
de
Transformador Principal en Automtico
para conseguir la tensin nominal en el
sistema de 18 kV.

Todas las Cargas Auxiliares fuera de


servicio.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 15 de/of 23

Cortocircuito:

El mtodo utilizado para clculo de las corrientes de cortocircuito es el de la norma IEC 60909.

Para el clculo de las intensidades mximas de cortocircuito se han aplicado los siguientes
factores:

c=1,10 para M.T.

c=1,05 para B.T.

Segn la norma IEC 60909 se definen como:

I"k: la corriente de cortocircuito simtrica inicial

ip: el valor de cresta de la corriente de cortocircuito


ip = (1,02 + 0,98 * e-3*R/X) * 2 * I"k

id.c.: la componente de continua de la corriente de cortocircuito


id.c. = 2 * I"k * e-2**t*R/X

A: valor inicial de la componente de corriente continua id.c.


A = 2 * I"k

Ib: corriente de cortocircuito simtrica de corte (valor eficaz).

tmn: tiempo de retardo mnimo de un interruptor automtico (tiempo ms corto entre la


aparicin de la corriente de cortocircuito y la primera separacin de los contactos de un polo
del interruptor)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 16 de/of 23

Ib = tmin * I"k

Ik: corriente de cortocircuito de rgimen permanente (valor eficaz).

Para obtener la mxima intensidad de cortocircuito en cada embarrado se estudiarn los


siguientes casos:

Caso de estudio
SC-1

Criterios de clculo

Todas las cargas conectadas

Generador de Emergencia parado

Generador

Auxiliar

(Black

Start)

conectado
SC-2

Todas las cargas conectadas

Generador de Emergencia conectado

Generador Auxiliar (Black Start) parado

Nota: En ningn caso, y con el objetivo de no sobredimensionar los embarrados


auxiliares de la planta, se permitir que los Generadores de Emergencia y Auxiliar estn
trabajando en paralelo y sincronizados entre s.

Arranque de motores

Durante el arranque de los motores la cada de tensin no podr superar el 10% en barras ni el
20% en los terminales del motor arrancado.

El estudio de arranque realizado es esttico. En este modo de clculo, el programa utilizado,


obtiene las cadas de tensin en el momento del arranque (valor mximo) y tanto la cada de
tensin como la posterior recuperacin son instantneas. En cada caso, antes del arranque se
encuentran en funcionamiento todas las cargas a excepcin del motor seleccionado (que es la
ltima carga en entrar en servicio).

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 17 de/of 23

Se ha analizado el arranque de los siguientes motores (el arranque de los motores se realiza en
T=1 segundo en ambos estudios):

Casos de estudio
MS-1

Criterios de clculo

Arranque del motor de MT Atomizing


Air System Compressor Drive Motor 1
(88AK-1).

Generador
parados

Principal

Funcionamiento

del

Auxiliar;

regulador

en

carga del transformador principal en


automtico.

Regulador

de

tensin

del

transformador auxiliar en toma -2,5%.


MS-2

Arranque del motor PCI


Generador
parados

Principal

Funcionamiento

del

Auxiliar;

regulador

en

carga del transformador principal en


toma -4.5%.

Regulador

de

tensin

del

transformador auxiliar en toma -2,5%.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

4.

Pg/Page 18 de/of 23

ANALISIS DE LAS CONDICIONES DE FUNCIONAMIENTO

4.1. ANLISIS DE FLUJO DE CARGAS


En el anexo III se adjuntan los resultados de los siguientes anlisis de flujo de cargas:

LF-1

LF-2

LF-3

LF-4

4.2. ANLISIS DE CORTOCIRCUITO


En el anexo IV se adjuntan los resultados de los siguientes anlisis de cortocircuito:

SC-1

SC-2

4.3. ANLISIS DE ARRANQUE DE MOTORES


En el anexo V se adjuntan los resultados de los siguientes anlisis de arranque de motores:

MS-1

MS-2

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

5.

Pg/Page 19 de/of 23

CONCLUSIONES

5.1. ANLISIS DE FLUJO DE CARGAS


Las conclusiones extradas de los casos de estudio realizados son los siguientes:

La carga consumida en los sistemas auxiliares son siempre inferiores a la potencia nominal
de los transformadores que las alimentan, obteniendo as un sistema sin sobrecargas.

Para obtener una tensin en barras comprendida entre 90%110% Un, los reguladores de
tensin han de operar de las siguientes maneras:

Transformador Principal: Regulador de tensin en automtico para obtener el 100%


de tensin en el sistema de 18 kV.

Transformador Auxiliar: Regulador de tensin en la toma +2,5%.

Transformadores de servicio (1BFT51/53): Regulador de tensin en toma central.

Transformador de servicios auxiliares de Generador Auxiliar (1BFT76): Regulador de


tensin en toma +2,5%.

Teniendo una situacin de mxima tensin en barras (caso LF-4), se ha obtenido una tensin
del 112,96% en el embarrado auxiliar 1BNB52 (secundario del transformador 1BNT52). Al no
haber modelado el cableado de Baja Tensin que alimenta dicho panel, se da por sentado
que la tensin ser inferior a la obtenida en la simulacin. En la Puesta En Marcha se
recomienda realizar una medicin de tensin en esta situacin antes de cerrar el interruptor
de acometida de la barra 1BNB52 , para en caso de obtener un valor superior al 110%, subir
el regulador de tensin del transformador 1BNT52 a la toma +2,5%. Teniendo en cuenta el
margen existente en el caso de mnima tensin (LF-3), se puede asegurar que aun subiendo
la toma del transformador, la tensin en barras seguir estando dentro de los lmites. Este
comentario es extrapolable a las dems barras de 380-220V alimentados a travs de un
transformador de servicio.

Se han considerado las condiciones ms desfavorables de funcionamiento. Cualquier otra


situacin ser ms favorable para el flujo de las cargas en el sistema.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 20 de/of 23

5.2. ANLISIS DE CORTOCIRCUITO


Las conclusiones extradas de los casos de estudio realizados son los siguientes:

Las corrientes de cortocircuito trifsico mximas, en los diferentes niveles de tensin, para el
dimensionamiento de los equipos son las indicadas a continuacin:
Ib asym
Ik

(MT = 50 ms)

Ip

(kA)

(BT = 30 ms)

(kA)

Nivel de tensin
(kA)

220kV (S.E. GEN)

10,251

10,032

25,637

18kV (BUS GEN)

104,581

91,781

281,154

6,6kV (1BBA51)

16,829

14,709

42,505

48V (Cuadros Generales de BT)

62,417

56,471

144.677

480 V (CCMs)

57,077

52,343

124,789

En ningn momento, y con el objetivo de no sobredimensionar los embarrados auxiliares de


la planta, se permitir que los Generadores de Emergencia y Auxiliar estn trabajando en
paralelo y sincronizados entre s.

Cualquier otra situacin de funcionamiento ser ms favorable para el dimensionamiento de


los equipos de los distintos niveles de tensin.

5.3. ANLISIS DE ARRANQUE DE MOTORES


Las conclusiones extractadas de los casos de estudio realizados son los siguientes:

En las situaciones analizadas, la tensin en el momento del arranque de los motores se


mantiene por encima del 90% de la nominal en todas las barras.

En el momento de arranque de motores, no se permitir que los Generadores Principal y


Auxiliar estn trabajando en paralelo, a plena carga y con factor de potencia 0,95 capacitivo,

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 21 de/of 23

debido a la cada de tensin resultante en este modo de operacin. En caso de estar los dos
generadores en operacin, al menos, el Generador Auxiliar deber estar trabajando con
factor de potencia inductivo (generando reactiva) para no perjudicar el arranque de motores
principales.

Se considera que cualquier otra situacin ser ms favorable para el arranque de motores.

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

6.

Pg/Page 22 de/of 23

ANEXOS

Anexo I: Esquema Unifilar

Anexo II: Datos Generador Principal

Anexo III: Datos Transformador Principal

Anexo IV: Datos Generador Auxiliar

Anexo V: Datos Transformador Auxiliar

Anexo VI: Reportes del anlisis de flujo de cargas

Anexo VII : Reportes del anlisis de cortocircuito

Anexo VIII Reportes del anlisis de arranque de motores

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

ANEJO I

CLCULOS ELCTRICOS
Rev. C

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 3

ANEXO I:

ESQUEMA UNIFILAR

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

One-Line Diagram - OLV1 (Load Flow Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

AL

2,92 km
Narcissus

S.E. Etn
220 kV

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Dyn11
Isolated Phase CU
35 m

CU
1MKA10
225 MW

40 m
4-3/C 240

1BBA51
6,6 kV
Open
CU

120 m
3-3/C 300

CU

1BBA76
6,6 kV

40 m
1-3/C 150

CU

Open

40 m
3-3/C 240

CU
CU

20 m
1-3/C 300

CU

20 m
3-3/C 300

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

1BJA76
0,48 kV

Yd1

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z
Dyn11

CU

70 m
1-3/C 70

Excitacin 1MKC10
944 kVA

100 m
1-3/C 70
CU

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

50 m
1-3/C 70

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

40 m
2-3/C 185

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

88WN-1
224 kW

88WN-2
224 kW

88AK-1
375 kW

50 m
1-3/C 70

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

88AK-2
375 kW

1BMA52
0,48 kV

1BFA51
0,48 kV

Open

CARGAS 1BJA76
270 kVA

Open
CU

W-1BJA12

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

may 02, 2014

Project File: Eten

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

1BNB52
0,38 kV
Sistema PCI
200 kW

1XKA52
2000 kW

11:11:38

CU

100 m
1-3/C 70

1MKA76
8,44 MW

1BFA53
0,48 kV

page 1

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

Open
CU

70 m
1-3/C 70

Open

CARGAS 1BNB52
82,2 kVA

One-Line Diagram - OLV1 (Load Flow Analysis)

1BMA52

CU

1BFA51

1BFA53

50 m
4-3/C 240

CU

1BMB20
0,48 kV

50 m
6-3/C 240

CU

1BJA12
0,48 kV

1BJA11
0,48 kV

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,48 kV

20 m
4-3/C 240

1BJA51
0,48 kV

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

RESERVA FRA ETEN

page 2

11:11:38

may 02, 2014

Project File: Eten

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

Rev. C

CLCULOS ELCTRICOS
ANEXO II

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 13

ANEXO II:

DATOS GENERADOR PRINCIPAL

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

REV

ZONE

N/A

Page 1 of 12

SH

REV

DATE
(YYYY-MM-DD)
12/10/26

DESCRIPTION
Initial Release. ECO0078796

THIS DOCUMENT SHALL BE REVISED


IN ITS ENTIRETY. ALL SHEETS OF THIS
DOCUMENT ARE THE SAME REVISION
LEVEL AS INDICATED.

APPROVED
See PLM

THIS APPLIQUE IS FOR C SIZE DRAWINGS

THIS DRAWING TO BE REVISED IN MICROSOFT


WORD ONLY. THE SOURCE FILE IS STORED IN
A SECURE DATABASE

REVISION DESCRIPTION IS FULLY


STATED ON FIRST SHEET OF
DOCUMENT

3.000

1.200

THIS APPLIQUE IS FOR A AND B SIZE DRAWINGS

DWG Number 106T0023

ITEM

DESCRIPTION
DWG. NO.
LIST OF COMPLEMENTARY DOCUMENTS

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.


All rights reserved. The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIGNATURES & DATES

DRAWN DATE (YYYY-MM-DD) - 12/10/26


CHECKED - See PLM

GENERATOR ELECTRICAL DATA

CHECKED DATE (YYYY-MM-DD) -12/10/26

UTE Reserva Fria Eten

ENGR - SEE PLM


ENGRG DATE (YYYY-MM-DD) - 12/10/26

APPLIED PRACTICES

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

GE ENERGY

DRAWN - L. Cruz

ADDITIONAL APPROVALS
SEE PLM SYSTEM FOR REGISTERED
INFORMATION
SIM TO:

FIRST MADE FOR: 761X201


SIZE

RDO CODE:

CAGE CODE

MLI/COST CODE: C902


DWG NO

106T0023
SHEET 1 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 2 of 12

SH

REV

ESTIMATED GENERATOR DATA

Customer:

ACS Cobra

Station/Project:

UTE Reserva Fria Eten

Generator Number:

761X201

Generator Type:

7FH2B LU

GENERATOR RATING
Data for Proposal No/Electrical Design:

726191G2

Jul 23 2012

ATB 2 281250 kVA 3600 RPM 18000 Volts 0.8 PF 45 psig (310 kPa) 42 C Gas 225000 kW 9021 Amps
410 Field Volts 79 Ft (24.1 m) Alt 0.44 SCR 60 Hz 3 Phase WYE Connection
Exciter Rating
Type Static
875 kW 410 Volts 2134 D.C.Amps Field Amps @ Generator rated Load 2011
Total temperatures are guaranteed not to exceed:

Insulation Class

Temperature Rise

Stator coils: 104 C by embedded detector

Armature

Field coils 120 C by Resistance

Field

Collector Gas Rise 20 C by RTD


COOLING WATER REQUIREMENTS @ GENERATOR RATING
Generator Output:

281250

kVA

Loss to Coolers:

2075

kW

Inlet Water Temperature:

36.4

Outlet Cold Gas Temperature

42

Coolant

100% Water

Maximum Fouling Factor:

0.0005

ft2 hr F/ Btu

(0.0881 m2 K/ kW)

Total Water Flow Required:

1820 GPM

(413.1 m3/hr)

(total for all coolers)

Coolant temperature Max

40.7

Head Loss Per Cooler:

12.92

Feet of Water

Maximum Operating Pressure:

125

psig

(38.6 kPa)

(862 kPa)

DIELECTRIC TESTS (Between coils and ground, 50/60 hertz AC for 1 min)
Stator 37000V
Rotor 3750V

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 2 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

REACTANCES (Per Unit):


Saturated Synchronous
Unsaturated Synchronous
Saturated Transient
Unsaturated Transient
Saturated Sub transient
Unsaturated Sub transient
Saturated Negative Sequence
Unsaturated Negative Sequence
Saturated Zero Sequence
Unsaturated Zero Sequence
Saturated Leakage Reactance
Unsaturated Leakage Reactance

Page 3 of 12

SH

REV

Direct Axis
Xdv
2.39
Xdi
2.39
X'dv
0.265
X'di
0.300
X"dv
0.170
X"di
0.220
X2v
0.170
X2i
0.220
X0v
0.115
X0i
0.115
Xlv
0.150
Xli
0.170

Quadrature Axis
Xqv
2.27
Xqi
2.27

FIELD TIME CONSTANTS (Seconds @ 125 C)


Open Circuit
T'd0
7.7
Three Phase Short Circuit Transient
T'd3
0.77
Line To Line Short Circuit Transient
T'd2
1.32
Line To Neutral Short Circuit Transient T'd1
1.6
Short Circuit Sub transient
T"d
0.026
Open Circuit Sub transient
T"d0
0.039

X'q
X"qv
X"qi

0.505
0.170
0.220

T'q0
T'q

0.62
0.14

T"q
T"q0

0.026
0.076

ARMATURE DC COMPONENT TIME CONSTANTS (Seconds@ 100 C)


Three Phase Short Circuit
Line To Line Short Circuit
Line To Neutral Short Circuit

Ta3
Ta2
Ta1

0.42
0.42
0.32

ARMATURE WINDING SEQUENCE RESISTANCES (Per Unit)


Positive
Negative
Zero

R1
R2
R0

0.0033
0.0155
0.0067

Reactance, Resistance and Time Constant data may be interpreted per IEEE 115, Part II.
The base reactance (UNIT) is calculated by the armature kV squared / MVA.
Base reactance = 1.152
Ohms
Rotor Short-Time Thermal Capacity, (I2)2t
10 s
Turbine-Generator Combined Train Inertia, WR2
389970 lb-ft2
(16433 kg-m2)
Turbine-Generator Combined Inertia Constant, H
4.151 kW-s/kVA
0.9651 F
0.001472 (100 C)
0.1804 (125 C)
2011 A
2460 A

Three Phase Armature Winding Capacitance


Armature Winding DC Resistance (Per Phase)
Field Winding DC Resistance
Field Current At Rated Kva, Armature Voltage, & PF
Field Current At Rated Kva, Armature Voltage, 0 PF Lagging*
(*For Systems Study Only - Not Allowable Operating Point)

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 3 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 4 of 12

SH

REV

MACHINE SATURATION DATA


S/1.0 = 0.0792

Machine saturation may be calculated from the data of curves A and B of

S/1.2 = 0.7214

ESTIMATED SATURATION AND SYNCHRONOUS IMPEDANCE CURVES.


S/1.0 is the field amp difference from B to A divided by the field amp of A at 1.0 pu voltage.

X/R RATIO
X/R = 134

X/R ratio equals XPP/DV * base reactance / armature DC resistance at 100 C

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 4 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 5 of 12

SH

REV

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 5 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 6 of 12

SH

REV

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 6 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 7 of 12

SH

REV

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 7 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 8 of 12

SH

REV

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 8 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 9 of 12

SH

REV

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 9 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 10 of 12

SH

REV

10

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 10 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 11 of 12

SH

REV

11

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 11 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 106T0023


SIZE

Rev -

Released 11/2/2012

DWG NO

106T0023

Page 12 of 12

SH

REV

12

COPYRIGHT 2012 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.
The information contained herein is GE Energy Generator Proprietary Technical Information that
belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or
corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such
information except as expressly authorized in writing by the General Electric Company, GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE

GE ENERGY

GENERAL ELECTRIC COMPANY


GENERATOR
Schenectady, NY, USA

CAGE CODE

DWG NO

106T0023

DRAWN - L. Cruz
DRAWN DATE (YYYY-MM-DD) - 12/10/26

RDO CODE:

SHEET 12 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR

Rev. C

CLCULOS ELCTRICOS
ANEXO III

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 7

ANEXO III:

DATOS TRANSFORMADOR PRINCIPAL

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

I-FOR INFORMATION

X AWC-APPROVED WITH COMMENTS

Approval not required

YOU MUST
START ON
NUMBER 1

Valid for construction. Return back the document


corrected within two weeks

A-APPROVED

R-REJECTED

Valid for construction

Not valid for construction. Return back the document


corrected within one week

RESPONSIBLE & DATE

HOJA DE DATOS XGR 29.01.2014


IMPORTANT NOTE: documentation approval does not relieve the manufacturer of its
responsibility for thePRINCIPAL
adequancy and suitability of the information, equipments and/or
TRANSFORMADOR
materials included in it for the function that is intended

YOU MUST FILL IN THE DOCUMENT WITH ALT INFORMATION


THE DOCUMENT'S TITLE IS: DATA SHEET
THE CODE'S TITLE IS: RFE-1-BAT-EHP-ALT-001

08/10/2013

AS COMPRADO (CON DATOS FABRICANTE)

PRV

PRV

01/10/2013

AS COMPRADO (punto 22)

PRV

PRV

JSA

07/03/2013

PUNTOS 141,142,143, 289, 322 a 330

PRV

JMM

JSA

12/11/2012

LINEA DE FUGA

PRV

JMM

JSA

31/10/2012

PARA PETICIN OFERTA

PRV

AAB

JSA

15/10/2012

COMENTARIOS COBRA

PRV

AAB

JSA

12/04/2012

ADECUACIN NORMATIVA

EAM

AAB

AOP

15/02/2012

ADECUACIN TURBINA GE

EAM

AAB

AOP

02/02/2012

EDICIN INICIAL

EAM

AAB

AOP

REV.

FECHA

DESCRIPCIN

PREPARADO

REVISADO

APROBADO

FIRMA

AOP

AOP

ESR

FECHA

09/12/2010

09/12/2010

09/12/2010

FIRMA

FECHA

EDICIN ORIGINAL

VLIDO PARA INFORMACIN


ESTADO

VLIDO PARA APROBACIN

EDITA

VLIDO PARA DISEO


VLIDO PARA OFERTA / COMPRA

VLIDO PARA CONSTRUCCIN

REVISADO
COBRA

AS BUILT

REVISADO

ALSTOM
COMPLETE
CLIENTE

RESERVA FRIA ETEN


DOCUMENTO No

HOJA
1

RFE-1-BAT-EHP-IDO-001

SIGUE
2

TTULO

HOJA DE DATOS
TRANSFORMADOR PRINCIPAL

JSA

ALSTOM

COMPLETE WITH ALSTOM


INFORMATION

CARACTERISTICAS
1
2 N DE UNIDADES
IDENTIFICACION DE EQUIPOS
3
4
5
6
7
8
9
10
11

MODELO
TIPO PROTECCIN
NORMA DE DISEO
FRECUENCIA
N DE FASES
N DE ARROLLAMIENTOS
CORRIENTE DE CORTOCIRCUITO:
EN PRIMARIO A.T.
INTENSIDAD MXIMA DE CORTOCIRCUITO EFICAZ
12
SIMTRICA
INTENSIDAD SIMTRICA DE CORTOCIRCUITO EFICAZ
SOPORTADA POR EL TRANSFORMADOR DURANTE 2
seg
13
INTENSIDAD DE CRESTA SOPORTADA POR EL
14
TRANSFORMADOR
EN SECUNDARIO B.T.
15
INTENSIDAD MXIMA DE CORTOCIRCUITO EFICAZ
16
SIMTRICA
INTENSIDAD SIMTRICA DE CORTOCIRCUITO EFICAZ
SOPORTADA POR EL TRANSFORMADOR DURANTE 2
seg
17
INTENSIDAD DE CRESTA SOPORTADA POR EL
18
TRANSFORMADOR
19 NIVEL CONTAMINACIN S/ IEC 60815
20 LINEA DE FUGA EN EXTERIOR
21

22

POTENCIAS ASIGNADAS EN SERV. CONTINUO, SIN


SOBREPASAR LOS CALENTAMIENTOS MXIMOS ADMISIBLES A
40C AMBIENTE

VALORES DE INCREMENTOS MXIMOS DE T (CALENTAMIENTO)


SOBRE LA T AMBIENTE SEGN IEC 60076-2 A LA POTENCIA
23 ASIGNADA:
EN EL COBRE (MEDIDO POR VARIACIN DE RESISTENCIA)
24
EN EL ACEITE (MEDIDO POR TERMMETRO EN LA CAPA
25
SUPERIOR DEL ACEITE)
SOBRETENSIN PERMITIDA SOBRE LA ASIGNADA, DURANTE 5
26 seg
TENSIONES ASIGNADAS EN VACO:
27
ARROLLAMIENTO DE A.T.
28
ARROLLAMIENTO DE B.T.
29
CORRIENTES
ASIGNADAS:
30
ARROLLAMIENTO DE A.T.:
31
NOMINAL INP
32
VACO IOP
33
CONEXIN ICP (INTENSIDAD MXIMA EN LA
34
CONEXIN INRUSH)
ARROLLAMIENTO DE B.T.:
35
NOMINAL INP
36
VACO IOP
37
CONEXIN ICP (INTENSIDAD MXIMA EN LA
38
CONEXIN INRUSH)
GRUPO
DE
CONEXIN (PRIMARIO/SECUNDARIO)
39
CAPACIDAD MXIMA DE SOBRECARGA A LA TEMP. AMB. 40C,
TENSIN NOM, CARGA INICIAL 100% Y SIN DISMINUCIN DE
40 VIDA APRECIABLE:
CONTINUA
41
DURANTE 4 HORAS
42
DURANTE 2 HORAS
43
DURANTE 1 HORA
44
45 CARACTERSTICAS DEL NCLEO :
TIPO DE CHAPA
46
SOBREXCITACIN SEGN CEI 60076-1, EN
47
ARROLLAMIENTO DE B.T.:
PLENA CARGA EN PERMANENCIA
48

SOLICITADO

UD

INTEMPERIE
IEC 60076
60
3
2
50

150

GENERAL

Uds.
Hz
Uds.
Uds.

DATOS DE FABRICANTE

1
Three phases, two windings with
on-load tap-changer
Outdoor
IEC 60076
60
3
2

kA

50

kA

IEC standard

VALOR ESTIMADO

kA

IEC standard

kA

150

kA

IEC standard

VALOR ESTIMADO

kA

IEC standard

mm/kV

IV (muy alto)
IV (muy alto)
31
31
CARACTERSTICAS DEL TRANSFORMADOR
MVA
225/300MVA ONAN/ONAF
225/300
ONAN/ONAF

Zona desrtica

IEC 60076-2

65
60
140

220 10x1,5%
18

YNd1

65

60

% Un

kV
kV

Over-excitation at 140% for 5


seconds
No-load winding voltage
(nominal voltage)
220 10x1,5 %
18

A
A
A

Rated current:787.2
No-load current: 0.35%pu
Inrush current: 4787A (0.008s)

A
A
A

Rated current: 9622.5A


No-load current: 0.35%pu
Inrush current: 58700A 0.008s)

YNd1

%PN

5% overload of transformer rated


power
15% overload of transformer rated
power
25% overload of transformer rated
power
30% overload of transformer rated
power

%PN
%PN
%PN

%VN/FN

1,05

49

VACO EN PERMANENCIA

%VN/FN

1,15

50

VACO DURANTE 2 min

%VN/FN

1,20

VACO DURANTE 2 seg


51
INDUCCIN MXIMA:
52
A TENSIN NOMINAL
53
AL 105% DE LA TENSIN NOMINAL
54
AL 110% DE LA TENSIN NOMINAL
55
AL 115% DE LA TENSIN NOMINAL
56
57 TENSIN DE CORTOCIRCUITO: (ONAN 225 MVA)
TENSIN DE CORTOCIRCUITO:
58
TOMA SUPERIOR
59

%VN/FN

1,50

TESLAS
TESLAS
TESLAS
TESLAS

1,72
1,80
1,90
2,00
Based on 225MVA
Impedance %
11.2% (Maximum tap)

RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13)

OBSERVACIONES

%UN

2/6

CARACTERISTICAS

60

TOMA CENTRAL

61

TOMA INFERIOR

SOLICITADO

UD
10

DATOS DE FABRICANTE

%UN

10% (Rated tap)

%UN

9.4% (Minimum tap)

TENSIN DE CORTOCIRCUITO HOMOPOLAR:

%UN

Base en 225MVA (cortocircuito


ZERO SEQ.IMPEDANCIA)
10.5%
(For reference only, test value will
be supplied)
9%
(For reference only, test value will
be supplied)
8.5%
(For reference only, test value will
be supplied)
Based on 225MVA
0,15%

%UN

0,16%

62
TOMA SUPERIOR

%UN

TOMA CENTRAL

%UN

TOMA INFERIOR

%UN

63

64

65
66 TENSIN RESISTIVA DE CORTOCIRCUITO:
TOMA SUPERIOR
67
68

TOMA CENTRAL

TOMA INFERIOR
69
70 TENSIN REACTIVA DE CORTOCIRCUITO:
TOMA SUPERIOR
71
72

TOMA CENTRAL

TOMA INFERIOR
73
74 IMPEDANCIA DE CORTOCIRCUITO (AT):
PRIMARIO TOMA SUPERIOR
75
PRIMARIO TOMA CENTRAL
76
PRIMARIO TOMA INFERIOR
77
SECUNDARIO
78
79 PRDIDAS:
EN VACO:
80

21,5

%UN

0,18%

%UN

Based on 225MVA
11,20%

%UN

10,00%

%UN

9,40%

Based on 225MVA
31,8
21,5
14,6
0.144
(based on rated voltage position)

81

90% UN

kW

No-load losses
170

82

100% UN

kW

180

83

105% UN

kW

220

84

110% UN

kW

282

85
86
87
88
89
90
91

115% UN
EN CARGA:
25% Sn
50% Sn
75% Sn
100 Sn
POR REFRIGERACIN
PRDIDAS TOTALES:

92
80 % Sn
93
100% Sn
94
RELACIN DE PRDIDAS DE DISPERSIN Y TOTALES
95
96 RENDIMIENTO COS = 0,85:
97
98
99

111
112
113
114
115
116
117
118
119
120

245
460
1050

COBRE

TENSIN MS ELEVADA PARA EL MATERIAL

ARROLLAMIENTO SECUNDARIO B.T.:

TENSIN MS ELEVADA PARA EL MATERIAL


TENSIN SOPORTADA A FRECUENCIA INDUSTRIAL
TENSIN SOPORTADA A IMPULSO TIPO RAYO (BIL)
MATERIAL DE PARTE ACTIVA
RIGIDEZ ELECTRODINMICA
DENSIDAD DE CORRIENTE

121
122 AISLADORES PASATAPAS:
123
ARROLLAMIENTO
FABRICANTE
124
TIPO CONEXIN

RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13)

583
810
1,1
eficiencia @ PF=0.85
0,9965

0,9973

0,9972

0,9968

kV
kV
kV
kV

245 (Sistema de tensin ms


elevada)
460
(A.C)
1050 (BIL)
1155

kV

212

kA

De cobre (material de winding)


Corriente de cortocircuito: HV 5.9
HV 3.0 (Normal.tap)

245
460
1050

kV

HV Neutral punto nivel de


aislamiento
123

kV
kV

230
550

24
50
125
COBRE

kV

24

kV
kV

50
125
De cobre (material de winding)
Corriente de cortocircuito: LV:41.6
~ 3.5

kA
A/mm

PRIMARIO A.T.:

125

kW
kW
kW
kW
kW

A/mm

NEUTRO AT:
TENSIN SOPORTADA A FRECUENCIA INDUSTRIAL
TENSIN SOPORTADA A IMPULSO TIPO RAYO (BIL)

300
On-load losses
40
158
355
630
8 (prdida auxiliar)
(Excluir prdida auxiliar)

kW
kW
p.u.

25% PN
50% PN
75% PN
100% PN

100
101 ARROLLAMIENTOS:
102
ARROLLAMIENTO PRIMARIO A.T.:
TENSIN MS ELEVADA PARA EL MATERIAL
103
TENSIN SOPORTADA A FRECUENCIA INDUSTRIAL
104
TENSIN SOPORTADA A IMPULSO TIPO RAYO (BIL)
105
TENSIN DE PRUEBA CON ONDA DE CHOQUE
CORTADA / TENSIN DE ENSAYO DE IMPULSO DE
106
MANIOBRA
TENSIN DE PRUEBA A TENSIN INDUCIDA (LARGA
107
DURACIN)
MATERIAL DE PARTE ACTIVA
108
RIGIDEZ ELECTRODINMICA
109
DENSIDAD DE CORRIENTE
110

kW

LNEA AREA CONDUCTOR


DESNUDO

OBSERVACIONES

Trench/CHINA
Oil-Air Bushings with air side
terminal

3/6

CARACTERISTICAS
CORRIENTE NOMINAL
TENSIN MS ELEVADA PARA EL MATERIAL

126
127

TENSIN DE PRUEBA A FRECUENCIA INDUSTRIAL


AMBIENTE SECO / 1 min
TENSIN DE PRUEBA A FRECUENCIA INDUSTRIAL
AMBIENTE LLUVIOSO /1 min

DATOS DE FABRICANTE

A
kV

1250
245

kV

460
460

kV
mm

1050
> =7595

kV
-

850
Oil-Air Bushings 245kV/1250A
245kV/1250A
YES
Brown

ZhiDa/CHINA
Oil-Air Bushings with air side
terminal

A
kV
kV

1250
123
230

kV

230

kV
mm
kV
-

BIL550
> =3813
BIL 550
Oil-Air Bushings 123kV/1250A
123KV/1250A
Brown

ZhiDa/CHINA
Insulated phase busbars

A
kV
kV

16000
24
50

kV

50

kV
mm
kV
V
dB(A)

125
744
BIL 125
Pure porcelain type bushing
Oil-Air bushing 24kv/16000A
NA
As per IEC
75dB(A) Nivel de presin

PRIMARIO

SECUNDARIO

914pF Capacitance of HV to earth


(For reference only, test value will
be supplied)
8372pF Capacitance of HV to earth
(For reference only, test value will
be supplied)
ONAN/ONAF

129
130

TENSIN DE PRUEBA A IMPULSO TIPO RAYO (BIL)


LNEA DE FUGA A TENSIN COMPUESTA
TENSIN DE ENSAYO A IMPULSO TIPO MANIOBRA
TIPO DE AISLAMIENTO
TIPO DE BORNA
TOMA CAPACITIVA
COLOR DE LA PORCELANA

1050
>=7565
850

NEUTRO AT:

FABRICANTE
TIPO CONEXIN

139
140
141

CORRIENTE NOMINAL
TENSIN MS ELEVADA PARA EL MATERIAL
TENSIN DE PRUEBA A FRECUENCIA INDUSTRIAL
AMBIENTE SECO / 1 min
TENSIN DE PRUEBA A FRECUENCIA INDUSTRIAL
AMBIENTE LLUVIOSO /1 min

142
143
144
145
146
147
148
149
150
151

1000
245
460

UD

kV

128

131
132
133
134
135
136
137
138

SOLICITADO

TENSIN DE PRUEBA A IMPULSO TIPO RAYO (BIL)


LNEA DE FUGA A TENSIN SIMPLE
TENSIN DE ENSAYO A IMPULSO TIPO MANIOBRA
TIPO DE AISLAMIENTO
TIPO DE BORNA
COLOR DE LA PORCELANA

CABLE DE COBRE
AISLADO
123
230

550
>=3.813

ARROLLAMIENTO SECUNDARIO B.T.:


FABRICANTE
TIPO CONEXIN

152
153
154

CORRIENTE NOMINAL
TENSIN MS ELEVADA PARA EL MATERIAL
TENSIN DE PRUEBA A FRECUENCIA INDUSTRIAL
AMBIENTE SECO / 1 min
TENSIN DE PRUEBA A FRECUENCIA INDUSTRIAL
AMBIENTE LLUVIOSO /1 min

155

156
TENSIN DE PRUEBA A IMPULSO TIPO RAYO (BIL)
157
LNEA DE FUGA A TENSIN COMPUESTA
158
TENSIN DE ENSAYO A IMPULSO TIPO MANIOBRA
159
TIPO DE AISLAMIENTO
160
TIPO DE BORNA
161
TOMA CAPACITIVA
162
163 NIVEL DE RADIOINTERFERENCIA
NIVEL DE RUIDO (PRESIN ACSTICA A 1 m, A POTENCIA
164 NOMINAL, CON TODA LA REFRIGERACIN FUNCIONANDO)
165 CAPACIDAD A TIERRA EN LA TOMA MEDIA:

BARRAS DE FASE
AISLADA
10.000
24
50

125

85

166

167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185

TIPO REFRIGERACIN
EQUIPO REFRIGERACIN FORZADA:

NMERO DE ETAPAS
NMERO DE RADIADORES
NMERO DE VENTILADORES POR ETAPA
POTENCIA DE CADA VENTILADOR
TENSIN DE LOS VENTILADORES / Hz
TIPO DEL ACEITE
CANTIDAD TOTAL DE ACEITE
VELOCIDAD MXIMA DEL ACEITE
GRADO DE PROTECCIN VENTILADORES

ONAN/ONAF

480 / 60
MINERAL

Uds.
Uds.
Uds.
kW
V/Hz
l
cm/seg
IP

CUBA:

kg/cm2
kg/cm2

OBSERVACIONES

Two cooling stage, ONAN/ONAF


30
15+1(On-line spare fans)
~0.5kW Per unit fan
480/60
mineral

IP 55
Principal tank
Yes
No
0.1Mpa (presin positiva)
133Pa (presin de vaco)

CUBA PRINCIPAL
CUBA SEGREGADA PARA EL REGULADOR
PRESIN MXIMA
PRESIN MNIMA

SI
NO

CMARA 1 CON BALN DE CAUCHO PARA


AISLAMIENTO DEL AMBIENTE
CMARA 2 DE LAS MISMAS
CARACTERSTICAS PARA EL REGULADOR

SI

S (conservador con la bolsa de


goma)

SI

S (para el cambiador)

DEPSITO DE EXPANSIN:

186
187
188 DIMENSIONES:
189
LARGO TOTAL
190
ALTO SIN PASATAPAS
191
ALTO CON PASATAPAS
192
ALTO CON DEPSITO DE EXPANSIN
193
ALTO CON AUTOVLVULAS EN A.T.

RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13)

CARACTERSTICAS FSICAS
mm
mm
mm
mm
mm

Consulte el outline
Consulte el outline
Consulte el outline
Consulte el outline
Consulte el outline

4/6

CARACTERISTICAS

SOLICITADO

194
ANCHO
195
LARGO DE TRANSPORTE
196
ALTO DE TRASNPORTE
197
ANCHO DE TRANSPORTE
198
ANCHO DE VIAS
199
TIPO DE CARRIL
200 PESOS:
201
TOTAL
202
DEL TRAFO SIN ACEITE
203
DEL ACEITE
204
DESENCUBADO
205
DEL COBRE
206
DE LA CHAPA MAGNTICA
207
DE LA PIEZA MS PESADA

UD

DATOS DE FABRICANTE

mm
mm
mm
mm
mm
kg/m

Consulte el outline
Consulte el outline
Consulte el outline
Consulte el outline

kg
kg
kg
kg
kg
kg
kg

276800
212200
64600
147000 (Un tanking peso)
23500
103000
178400

(NCLEO)
DE TRANSPORTE
CROQUIS ORIENTACIN ARMARIO CONTROL
Y OLTC

OBSERVACIONES

AT
OLTC
Y
CONTR
208
209
210 KKS
FABRICANTE
211
212 TIPO
213 MARGEN DE REGULACIN
214 TENSIN EN TOMAS:
SUPERIOR
215
216

BT

CAMBIADOR DE TOMAS
1BAT10GH002
EN CARGA
220 10x1,5%

INFERIOR

VALOR DEL PASO


217
NUMERO DE TOMAS
218
219 TENSIONES EN VACIO:
EN POSICIN SUPERIOR
220
EN POSICIN MEDIA
221
EN POSICIN INFERIOR
222
223 CORRIENTES ASIGNADAS EN SERVICIO CONTINUO:

115
85
1,5
21

EN POSICIN SUPERIOR
224
EN POSICIN MEDIA
225
EN POSICIN INFERIOR
226
227 TENSIN MS ELEVADA PARA EL MATERIAL
228 TENSIN DE ENSAYO A FRECUENCIA INDUSTRIAL
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249

TENSIN DE ENSAYO A IMPULSO TIPO RAYO


MANDO MOTORIZADO:
MOTOR
CONTROL
CALDEO
PROTECCIONES
NIVEL (MIN / MAX)
REL CONTROL FLUJO
REL SOBREPRESIN
ALIVIO SOBREPRESIN
TEMPERATURA

KKS
PROTECCIN
MATERIAL
INDICADORES LOCALES
LMPARAS INDICADORAS
PRUEBA LMPARAS
CONMUTADORES Y PULSADORES
ALIMENTACIN DE BARRAS DE POTENCIA
RESISTENCIA DE CALDEO
ALUMBRADO
Y TOMA DE CORRIENTE
250
251 CONTACTOS DE ALARMA LIBRES DE POTENCIAL
252 ALIMENTACIN PARA ALUMBRADO Y CALDEO
ALIMENTACIN PARA DISPOSITIVO DE IMAGEN TRMICA Y
253 CONTROL
254
255 TIPO
256 FABRICANTE
257 5% RESERVA

258
259 BORNAS A.T.:
260
CANTIDAD POR
261
CORRIENTE P
262
CORRIENTE S1

kV

El cambiador de tomas bajo carga


Huaming Shanghai, China o
equivalente
En carga
220 10x1,5 %

%UN

115

480 / 60
125 / DC
220 / 60

%UN

85

%UN
Uds.

1,5

kV
kV
kV

21
Voltaje sin carga
253
220
187

A
A
A
kV
kV

685
787
926
123kV voltage class
AC230

kV

BIL550

V / Hz
V / Hz
V / Hz

480/60
125/DC
220/60

S
S
S
S
NO
NO
S
S
S
S
ARMARIO DE MANIOBRA Y CONTROL
Gabinete
de
control
del ventilador
1BAT10GH001
IP65
IP65

480 / 60
SI
SI
SI
220 / 60
125 / DC
MINERAL

V / Hz
-

ACERO
SI
SI
SI
480/60
SI
SI

SI

V / Hz
V / Hz

220/60
125/DC

ACEITE

Mineral (Nynas libra)


Nynas
SI

Uds.
A
A

/
/
/

SI
TRANSFORMADORES DE CORRIENTE EN BUSHING (A PARTE DEL DE LA IMAGEN TRMICA)

FASE

RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13)

NO REQUERIDO

5/6

N
263
264
265
266
267
268
269
270
271

CARACTERISTICAS

SOLICITADO

POTENCIA S1
PRECISIN S1
CORRIENTE S2
POTENCIA S2
PRECISIN S2
INTENSIDAD LIMITE TERMICA
INTENSIDAD LIMITE DINAMICA (PICO)
FABRICANTE
MODELO
FACTOR DE SEGURIDAD (PARA TRAFOS DE
MEDIDA)

272
273 BORNA DE NEUTRO AT:
274
CANTIDAD
275
CORRIENTE P
276
CORRIENTE S1
277
POTENCIA S1
278
PRECISIN S1
279
CORRIENTE S2
280
POTENCIA S2
281
PRECISIN S2
282
INTENSIDAD LIMITE
283
INTENSIDAD LIMITE
284
FABRICANTE
285
MODELO

TERMICA
DINAMICA (PICO)

311

CONEXIONES FLEXIBLES ENTRE LA CUBA Y


LA TAPA
VLVULA DE VACIADO
VLVULA DE TOMA DE MUESTRAS
DEPSITO DE EXPANSIN
DESECADOR DE SILICAGEL
TERMINALES PARA CONEXIN DE P.A.T.
PLACA DE CARACTERSTICAS INOX
VLVULA CONEXIN DE FILTRO

312
313
314
315 RELES DE PROTECCION:
316
INDICADOR DE NIVEL
317
TERMMETRO TEMPERATURA ACEITE
318
REL BUCHHOLZ
319
DETECCIN DE AUMENTO DE PRESION
320
IMAGEN TRMICA.
321
SISTEMA MONITORIZACIN DE GASES
PARARRAYOS
322
323
UNIDADES
324
FABRICANTE / MODELO
325
TECNOLOGA
326
TENSIN NOMINAL (Ur)
327
INTENSIDAD NOMINAL DE DESCARGA (Ir)
328
CLASE LINEA DE DESCARGA
329
AISLADORES
330
NIVEL CONTAMINACIN S/ IEC 60815

RFE-1-BAT-EHP-IDO-001-REVI GSU V00 (2013-12-13)

/
/
/
/
/
/
/
/
/
/

1
12.000
5
100
5P20
5
100
5P20

Uds.
A
A
VA
A
A
kA
kA
-

FACTOR DE SEGURIDAD (PARA TRAFOS DE

306
307
308
309
310

A
A
kA
kA
-

Uds.
A
A
VA
A
A
kA
kA
-

(PICO)

300
MEDIDA)
301
302 CUBA PRINCIPAL:
303
RUEDAS
304
CNCAMOS DE ELEVACIN
305
APOYOS PARA GATOS HIDRULICOS

DATOS DE FABRICANTE

1
2.000
5
100
5P20
5
100
5P20

FACTOR DE SEGURIDAD (PARA TRAFOS DE

286
MEDIDA)
287 BORNAS DE B.T.:
288
CANTIDAD POR FASE
289
CORRIENTE P
290
CORRIENTE S1
291
POTENCIA S1
292
PRECISIN S1
293
CORRIENTE S2
294
POTENCIA S2
295
PRECISIN S2
296
INTENSIDAD LIMITE TERMICA
297
INTENSIDAD LIMITE DINAMICA
298
FABRICANTE
299
MODELO

UD

OBSERVACIONES

Bushing tipo CT
1

2.000
5
100

5P20

5
100
5P20
Despues de orden
Despues de orden
China
Proteccion
1,3

12.000

5
100
5P20
5
100
5P20
Despues de orden
Despues de orden
China
Proteccion
1,3

ACCESORIOS
SI
SI
SI
SI

SI
SI
SI
SI

SI
SI
SI
SI
AL MENOS 2
SI
SI

SI
SI
SI
Consulte el outline

SI

SI

SI
SI
SI
SI
SI
S

SI
SI
SI
SI
SI
SI

Uds.

MO (Metal-Oxide)
198
10
3
CERAMICOS
IV (muy alto)

kV
kA
-

PENDIENTE.

Zona desrtica

6/6

Rev. C

CLCULOS ELCTRICOS
ANEXO IV

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 15

ANEXO IV:

DATOS GENERADOR AUXILIAR

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

PLANTA DE RESERVA FRA


DE GENERACIN DE ETEN S.A

PROYECTO

RESERVA FRA ETEN


CONTRATISTA

UTE RESERVA FRA ETEN

TTULO

Generator Technical Specification


N DE DOCUMENTO PROYECTO

RFE-1-MKA-EIP-WRT-001
Wrtsil doc id: DBAC857966 - | Original doc id:
REV

00

FECHA

04/02/2014

EDITADO PARA

Daniel Byskata

Tuomas Karri

Thomas Lnngrn

REALIZADO

REVISADO

APROBADO

Este documento contiene informacin privada y no puede ser duplicado, modificado o divulgado a terceros sin el consentimiento
escrito de COBRA. La nica copia controlada de este documento est en el Sistema Informtico de Gestin Documental de COBRA.

Wrtsil Finland Oy

Status: Approved

Internal

Document id: DBAC857966 - Page 2 (14)

Generator Technical Specification


Rev. 00

RFE-1-MKA-EIP-WRT-001

CONTROL DE MODIFICACIONES
Revisin
00

Fecha

Modificaciones

04/02/2014

For review

Este documento contiene informacin privada y no puede ser duplicado, modificado o divulgado a terceros sin el consentimiento
escrito de COBRA. La nica copia controlada de este documento est en el Sistema Informtico de Gestin Documental de COBRA.

Status: Approved

Internal

Document id: DBAC857966 - Page 3 (14)

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Copyright 2011 ABB

TECHNICAL SPECIFICATION
Project name:
Our reference number:
Customers reference number:
Customer:
Final customer:
Application:
Type designation:

Reserva Fria Eten


5430HG401
WRTSIL FINLAND OY
Diesel/Gas engine
AMG 1120LS10 DSE

NOTES

CONTENTS
SECTION:
1 PERFORMANCE DATA (Calculated values)

2 CONFIGURATION AND SCOPE OF SUPPLY

3 ACCESSORIES

4 P/Q DIAGRAM

11

5 NO LOAD AND SHORT-CIRCUIT CURVE

12

Revision
A

Change
Original

Helena Krivetz/PGD
Appr.
PGD
Resp. dept. PGD
Prep.

Date
19.12.2013

Updated by
HEKR

No. of sh.

19.12.2013 TECHNICAL SPECIFICATION

12
Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 4 (14)

PERFORMANCE DATA (Calculated values)

TYPE
Type designation:

AMG 1120LS10 DSE

RATINGS
Output:
Duty:
Voltage:
Current:
Power factor:
Frequency:
Speed:
Overspeed:

10549
S1
6600
923
0,80
60
720
864

kVA

Direction of rotation
(Facing drive end):
Weight:
Inertia:
Protection by enclosure:
Cooling method:
Mounting arrangement:

V
A
Hz
rpm
rpm

CCW
33400
kg
3190
kgm^2
IP23
IC0A1
IM1101

STANDARDS
Applicable standard:
Marine classification:
Hazardous area classification:
Temperature rise stator / rotor:
Insulation class:

IEC
None
None
B/B
F

ENVIRONMENTAL CONDITIONS (max. values)


Ambient temperature:
Coolant temperature:

50

C
C

Altitude:

1000

masl

ASSUMED DATA
Driving equipment:
Approx. mech. power:

Wrtsil 20V34SG/DF
8650
KW

EFFICIENCY in %
load:
Efficiency @ power factor
Efficiency @ power factor

0,80
1,00

110
97,64
98,26

100
97,59
98,21

75
97,32
97,99

50
96,60
97,39

25
94,10
95,34

REACTANCES in %
XD (U):
XQ (U):
X1 (U):

171,3
86,1
13,2

XD (S):
28,5
XQ (S):
18,2
XD (S):
16,0
X2 (S):
17,1
(S) = Saturated value, (U) = Unsaturated value

X0 (U):
XP (S):

9,4
23,5

TA:

0,182

TIME CONSTANTS (SEC.) AT 75 C


TD0:
TD0:

7,713
0,02938

TD:
TD:

1,410
0,01677

TQ0:
TQ:

0,1207
0,0280

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 5 (14)

RESISTANCES AT 20 C
Stator winding:
Excitation winding:

0,0093
5,7

W
W

Field winding:

1,0430

SHORT CIRCUIT
Short circuit ratio:
Sustained short circuit current:

0,67
1,7
> 2.5
5750
14650

Sudden short circuit current:

p.u. (rated excitation)


p.u. (voltage regulator)
A (symmetric RMS)
A (peak value)

VOLTAGE VARIATION
Maximum allowed amount of starting load:
Maximum voltage drop
15 %
15 %
15 %
20 %
20 %

Power factor
0.1
0.4
0.8
0.1
0.4

Voltage drop at sudden increase of rated load:


Voltage rise at sudden drop of rated load:

Load
5200
5650
8800
7300
7900
18
24

kVA
kVA
kVA
kVA
kVA
%
%

REACTIVE LOADING
Steady state reactive loading at rated excitation:
Steady state reactive loading at zero excitation:

8700
4650

KVAR (lagging)
KVAR (leading)

TORQUE
Rated load torque (Calculated of rated output in kVA):

139900

Nm

The peak values of sudden short circuit air gap torques:


2-phase short circuit:
790
%
3-phase short circuit:

560

BEARINGS
D-end:
Sleeve, self lubricated, locating
Oil viscosity:
ISO VG 46

N.D-end:

Sleeve, self lubricated, free

TERMINAL CONNECTIONS (Defined facing drive end)


Direction of main connection:
Direction of zero connection:

Right down
Left down

EXCITATION
No load:
Rated load:

Exciter field
3,8
A
8,1
A

27,9
59,3

V
V

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 6 (14)

OTHER
Stored energy constant (rotational energy divided by rated effect):
Earth capacitance (1-phase):

0,86
0,23

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

s
F

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 7 (14)

CONFIGURATION AND SCOPE OF SUPPLY

GENERAL
The generator is designed to operate together with a Gas engine.
CONSTRUCTION
The stator frame is a rigid welded steel structure construction. The stator core is built of thin
electric sheet steel laminations which are insulated on both sides with heat-resistant inorganic
resin. The radial cooling ducts in the stator core ensure uniform and effective cooling of the
stator.
The rotor consists of a shaft and poles fixed on the shaft, exciter and a fan(s). The shaft is
machined of steel forging. The poles are manufactured of 2 mm sheet steel and bolted from
the top to the shaft. The pole laminations are pressed together with steel bars which are
welded to the end plates. The exciter rotor and the fan are shrink fitted onto the shaft and
secured with a key.
All windings are completely vacuum pressure impregnated with high quality epoxy resin. The
windings are provided with very strong bracing which withstands all expected mechanical and
electrical shocks and vibrations as well as chemicals. For more information ask for brochure
"MICADUR-Compact Industry Insulation System".
The stator frame, core support and end-shields are made of fabricated steel and welded
together. The stator frame is closed with steel panels that guide the ventilation air and provide
the degree of protection required. The flange mounted bearings are bolted to the end-shields.
According to IM1101 the machine has 2 endshield bearings. The feet are raised. The shaft
end is cylindrical.
FOUNDATION
The machine can be mounted using shimming, machined blocks, chock fast or on grouted sole
plates or bed plate. Before using other mountings, contact us.
COOLING
The machine has a shaft mounted fan inside. The surrounding air is used for cooling. The
cooling air is drawn in through air filters (self charging electrostatic panels) and blown out to
the surrounding environment.
CONTROL SYSTEMS
A three phase transformer supplies the excitation power to the field winding of the shaft driven
three phase exciter under the control of the digital automatic voltage regulator (AVR) type ABB
UNITROL UN1020. A three phase voltage feedback is supplied by the voltage transformer. A
current feedback is provided by the current transformer. The transformers are installed in the
generator.
Thanks to a permanent magnet pole in the exciter no external power source is required for
initial excitation at start-up. The permanent magnet pole is already magnetized by the
generator manufacturer. Should the re-magnetization of the permanent magnet be necessary,
rated values for re-magnetization given on the main connection diagram of the generator are
Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 8 (14)

used. Thanks to Soft Start function it is possible to avoid over shooting at start-up.
Excitation power at short circuit is supplied by the CTs through rectifier. At nominal voltage the
contactor is shorting the output of CTs (and preventing over excitation from these CTs). At a
line short circuit AVR will notice the voltage drop and connect CTs to give full short circuit
excitation. ECL-10 current limiter limits sustained short circuit current approx. 250 - 300 % of
rated current.
The circuit breaker protects the field circuit and the AVR against thermal overload and short
circuit. The over voltage relay will trip the circuit breaker in excess of pre-set limit of over
voltage and thus interrupt the supply of the excitation power to the AVR.
Auxiliary supply can be 9 to 300 Vac (3-phase), 16 to 300 Vac (1-phase) or 18 to 300 Vdc.
UNITROL 1020 AVR can be operated using digital and analogue I/O signals, from local panel
or with CMT1000 PC software. CMT1000 is a commissioning and maintenance tool running
under Microsoft Windows. With CMT1000 the tuning of the AVR can be done easily, also by
using preset parameter files. The operation of a synchronous machine can be monitored and
controlled by an on-line power chart, four channel oscilloscope and by several measurements
and status indications with trending and memory functions. Measured data and parameters
can be saved to a file for future use and analysis.
UNITROL 1020 single channel AVR plate (dimensions: 334x570mm) includes:
- UNITROL UN1020 AVR
- Excitation breaker (ac) and MCB for Upwr supply
- Over voltage relay (stator over voltage protection)
- Boost circuit with ECL-10 current limiter
- Standard software functions as per UNITROL UN1020 brochure, including
- AVR/FCR/PF/VAR
- Limiters
- Modbus TCP
- Rotating diode monitoring
- Voltage matching prior to synchronizing
- VDC mode
- Synchronization
- Event logger
- Data logger
- Real time clock
- PSS (option)
- Interface for I/O signals:
Inputs
- Excitation On/Off
- Gen CB status
- Setpoint Increase
- Setpoint Decrease
- PF mode enable
- VDC (reactive load sharing by digital RS-485 bus)
- PWG status
- Remote SP enable (for analogue for PF setpoint)
- 4..20 mA analogue input for PF setpoint
- Line charging
- Secondary Net 1
- Secondary Net 2
Outputs
Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 9 (14)

- Synchronize
- FRT output
- Diode trip
- Close CB command output
- Over voltage
- Excitation On/Off Status
- Free programmable
- CMT 1000 Commissioning and maintenance tool
- PID setting calculation tool
TESTING
Testing is according to Wrtsil Generator testing instruction 4V64L0037, IEC and ABB
internal requirements. Test items are listed below. The test may be observed by the customer
without extra charges. The test procedures are described in Machine Description Document
8006327, available upon request. Other tests to be agreed separately.
ROUTINE TESTS
1.
2.
3.
4.
5.
6.
7.
8.
9.

10.
11.
12.

13.

Visual inspection *
Air gap measurement and bearing clearance *
Insulation resistance measurement *
Resistance measurement of windings and elements *
Direction of rotation
First running: checking of bearings *
No-load curve, U1= f(Im), n = nN
Short-circuit curve, I1= f(Im), n = nN
Tests with voltage regulator
- adjusting of basic settings
- initial voltage build-up and voltage regulation speed at no-load
- setting of under frequency limit and function testing
- measuring of sustained short-circuit current
- measuring of remanence voltage
Overspeed test, t = 2 min, n = 1.2 * nN
Vibration measurement at no-load, U1 = U1N, n = nN
High voltage test:
stator winding
rotor winding
field winding
space heaters
Pt-100 (stator)
Pt-100 (others)
Insulation resistance measurement
- polarization index 10/1 min for stator windings
Tests to be completed before witness tests
(Performing order of the tests may differ from the listed above.)

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 10 (14)

SURFACE TREATMENT
Colour:

RAL 5019

Grade:

C3, Special color

Surface treatment C3 according to the ISO 12944 standard, for standard industrial
environment.
DOCUMENTATION
User's Manual in electronic format. Documentation language is English.

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 11 (14)

ACCESSORIES

No pc/pcs

Item

PT100 for stator winding - PYR PT100LG10/3

PT100 for cold cooling air - PYR PT100RC0/4


L=50 mm

PT100 for warm cooling air - PYR PT100RC0/4


L=50 mm

PT100 for sleeve bearings (radial bearing surface) - PYR PT100A_7/4Z


Resistance temperature detector for sleeve bearings, insulated, quick connector

Varistor - SXV 40K550 C

Diode - LNM 260A/2000V


ABB Stock code: 9877911

Automatic Voltage Regulator system - UN 1020 WARTSILA 1CH SYSTEM (FULL)


Unitrol 1020 -Wrtsil system, Product code 3BHE036163R6106

1PT - Voltage transformer for exc.power & actual value meas. - KSG 3PU180/63/E
6600/110/110 V, 60 Hz
Secondary 1: 110 V 3200VA for excitation
Secondary 2: 110 V 300VA for actual value measurement

3CT - Current transformer for short circuit exc.power - KSG KOKM 1EF 1000
1000/7.5 A, class PX, 60 Hz

2CT - Current transformer for actual value measurement - KSG 1000T2


1000/1A, 5 VA, CL 0.5, 60 Hz

4CT - Current transformer for differential protection - KSG D 500/1000 1/1


KOFA 1000/1/1 A, 60 Hz
Core 1: 20VA, 5P10
Core 2: 20VA, 5P10

Top mounted direct air cooling unit incl. air filter

Inlet Air Filters - WJFA 500x1000x24


Pliotron CR, Galvanized Steel, 500*1000

Anticondensation heater - RER 1-800W/490V


Voltage 380-480 V, power 2x500-800 W

Auxiliary terminal box B3A - B3A Stand


Standard auxiliary terminal box for accessories. In stock.

Multidiameter cable entry seals (Rox System) for main cables - NLR...

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

Status: Approved

Internal

Document id: DBAC857966 - Page 12 (14)

Drive-end sleeve bearing - ZLL EFZLB28-250A


Side flange mounted sleeve bearing for AMG/Z 1120 in land application. D-end.
Normal end float +/- 2.5 mm or +/- 1/8 inch. Max. axial force 2 kN.
Machine seal on machine side IP44. Floating labyrinth seal on outer side IP44.

Non-drive-end sleeve bearing - ZLL EFZLQ28-250EP


Side flange mounted sleeve bearing
Insulation between bearing housing and shell

Welding inspection record for the frame

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

10

Status: Approved

Internal

Document id: DBAC857966 - Page 13 (14)

P/Q DIAGRAM

ABB Oy

Motors and Generators

Handled by: HEKR

19.12.2013

Type: AMG 1120LS10 DSE


Sn:
Un:
f:

10549
6600
60

kVA
V
Hz

cos:
n:

0.80
720

Tn:
In:

rpm

139910
922,8

Nm
A

P / Q -DIAGRAM
1. Stator current at rated load
2. Nominal working point
3. Active power limit
4. Rated rotor current

5. Minimum excitation limit


6. Stability limit
7. Theoretical stability limit
kW
22500

0,9

0,95

0,95

0,9

20000

0,8

0,8

17500

1,2

15000

1,0

12500

0,75
0,6

0,6

10000

0,5

3
7500

0,4

0,4

0,25

5000
0,1

2500

0
-15000

-10000

-5000

5000

10000

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

15000

Lang.

en

Rev. ind.

kVAr

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

11

Status: Approved

Internal

Document id: DBAC857966 - Page 14 (14)

NO LOAD AND SHORT-CIRCUIT CURVE

ABB Oy

Motors and Generators

Handled by: HEKR

19.12.2013

Type: AMG 1120LS10 DSE


Sn:
Un:
f:

10549
6600
60

kVA
V
Hz

cos:
n:

0.80
720

Tn:
In:

rpm

139910
922,8

Nm
A

Excitation current (A)


E/Un
1,4

I/In
2,8

1
1,2

2,4

3
1

0,8

1,6

0,6

1,2

1 Air-gap line

0,4

0,8

2 No load voltage
3 Short-circuit current

0,2

0,4

0
0

50

100

150

200

Document identification

ABB Oy / Motors and Generators

3AFP 54306401

250 A

Lang.

en

Rev. ind.

Sheet

TEMPLATE: TECHNICALSPECIFICATION.DOT; FILENAME: DG_SQLGLOVE_5430HG401_ASDOC__5430HG_401_A_TECHSPEC.DOC; PRINTDATE: 12/19/2013 6:08:00 PM;


SAVEDATE: 12/19/2013 5:46:00 PM

12

Rev. C

CLCULOS ELCTRICOS
ANEXO V

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 6

ANEXO V:

DATOS TRANSFORMADOR AUXILIAR

(DATOS DE LA OFERTA SIEMENS)

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

H1

CHARACTERISTICS

1
2
3
4
5
6
7
8
9
10
11

No. OF UNITS
EQUIPMENT IDENTIFICATION
MODEL
TYPE OF PROTECTION
DESIGN NORM
FREQUENCY
No. OF PHASES
No. OF WINDINGS
SHORT-CIRCUIT CURRENT
IN PRIMARY, HV
EFFICIENT, SYMMETRIC, MAXIMUM SHORT-CIRCUIT
12
CURRENT
EFFICIENT, SYMMETRIC SHORT-CIRCUIT CURRENT
RESISTED BY THE TRANSFORMER FOR 2 seconds
13
14
15
16

17
18
19

PEAK CURRENT RESISTED BY THE TRANSFORMER


IN SECONDARY, LV
EFFICIENT, SYMMETRIC, MAXIMUM SHORT-CIRCUIT
CURRENT
EFFICIENT, SYMMETRIC SHORT-CIRCUIT CURRENT
RESISTED BY THE TRANSFORMER FOR 2 seconds

NLI

REQUESTED

UNIT

GENERAL
1 Uds.
1BBT10
INTEMPERIE
IEC 60076
60
3
2
150

31,5

Hz
Uds.
Uds.

OBSERVATIONS

1
cKOUM
INTEMPERIE
IEC 60076
60
3
2
According to IEC

kA

kA

kA
kA

*
*
*

kA

ON IPBs

ESTIMATED VALUE

PEAK CURRENT RESISTED BY THE TRANSFORMER

kA
*
TRANSFORMER CHARACTERISTICS
POTENCIAS ASIGNADAS EN SERV. CONTINUO, SIN
8,5/11,5
8,5/11,5 MVA
SOBREPASAR LOS CALENTAMIENTOS MXIMOS ADMISIBLES A
ONAN/ONAF
ONAN/ONAF

20 LA TEMPERATURA DE DISEO (40C)


MAXIMUM TEMPERATURE INCREMENT VALUES (HEATING)
OVER AIR TEMPERATURE, AS SPECIFIED FOR ASSIGNED
21 POWER IN IEC 60076-2:
IN COPPER (MEASURED WITH RESISTANCE VARIATION)
22
IN OIL (MEASURED BY MEANS OF A THERMOMETER ON
23
THE UPPER OIL LAYER)
ALLOWED OVERVOLTAGE OVER SET OVERVOLTAGE, FOR 5
24 seconds
25 SET NO-LOAD VOLTAGE:
HV WINDING
26
LV WINDING
27
SET
CURRENTS:
28
HV WINDING:
29
RATED INP
30
IOP VACUUM
31
ICP CONNECTION (MAXIMUM INRUSH CONNECTION
32
CURRENT)
LV WINDING:
33
RATED INP
34
IOP VACUUM
35
ICP CONNECTION (MAXIMUM INRUSH CONNECTION
36
CURRENT)
37 CONNECTION GROUP (PRIMARY/SECONDARY)
MAXIMUM CAPACITY FOR AIR TEMPERATURE OVERLOAD:
40C; RATED VOLTAGE, 100% INITIAL LOAD AND NO
38 NOTICEABLE LIFE REDUCTION:
CONTINUOUS
39

65
60
140
18 2x2,5%
6,6

Dyn11

K
K
% Un

A
A
A

*
*

A
A
A

*
*

Dyn11

%PN
%PN

41

FOR 2 HOURS

%PN

FOR 1 HOUR

%PN

%VN/FN

ENDURANCE NO-LOAD

%VN/FN

48

NO-LOAD FOR 2 min

%VN/FN

49
50
51
52
53
54
55
56
57
58

NO-LOAD FOR 2 seconds

%VN/FN

STEP VALUE

61
NUMBER OF TAPS
62
NO-LOAD
VOLTAGES:
63
IN UPPER POSITION
64
IN INTERMEDIATE POSITION
65
IN LOWER POSITION
66
67 SET CURRENTS IN CONTINOUS OPERATION:
IN UPPER POSITION
IN INTERMEDIATE POSITION
IN LOWER POSITION

According to IEC
According to IEC
According to IEC
According to IEC
M4 o similar
According to IEC

47

MAXIMUM INDUCTION:
RATED VOLTAGE
105% OF RATED VOLTAGE
110% OF RATED VOLTAGE
115% OF RATED VOLTAGE
TAP CHANGER
TYPE
REGULATION MARGIN
TAP VOLTAGE:
UPPER
59
LOWER
60

According to IEC
18 2x2,5%
6,6

FOR 4 HOURS

42
43 CORE CHARACTERISTICS:
TYPE OF PLATE
44
OVERREPRESENTATION IN THE LP WINDING, AS
45
SPECIFIED IN CEI 60076-1:
FULL ENDURANCE LOAD
46

65
60

kV
kV

40

68
69
70

MANUFACTURER
DATA

TESLAS
TESLAS
TESLAS
TESLAS

EN VACO
18 2x2,5%
105
95
2,5
5

kV

1,7
1,78
1,87
2,15
EN VACIO
18 2x2,5%

%UN
Uds.

105
95
2,5
5

kV
kV
kV

18,9
18
17,1

A
A
A

259,65
272,64
286,98

%UN
%UN

REFER TO ONAN
REFER TO ONAN
REFER TO ONAN

Pgina 1 de 5

H1

CHARACTERISTICS

NLI

REQUESTED

UNIT

71 SHORTCIRCUIT VOLTAGE
72 SHORTCIRCUIT VOLTAGE
IN UPPER POSITION
73

75
76

IN LOWER POSITION

%UN

77

UNIPOLAR SHORT-CIRCUIT VOLTAGE


IN UPPER POSITION

%UN

78

IN INTERMEDIATE POSITION

%UN

10

IN LOWER POSITION
79
80 RESISTIVE SHORT-CIRCUIT VOLTAGE:
IN UPPER POSITION
81

%UN

%UN

IN LOWER POSITION

%UN

%UN

*
*
*

*
*
*
*

%UN

IN INTERMEDIATE POSITION

%UN

IN LOWER POSITION
87
88 SHORT-CIRCUIT IMPEDANCE (HV):
PRIMARIO TOMA SUPERIOR
89
PRIMARIO TOMA CENTRAL
90
PRIMARIO TOMA INFERIOR
91
SECUNDARIO
92
93 LOSSES:
IN NO-LOAD CONDITION:
94
90% UN

kW

96

100% UN

kW

97

105% UN

kW

98

110% UN

kW

99
100
101
102
103
104
105
106
107
108

115% UN
IN LOAD CONDITIONS:
25% Sn
50% Sn
75% Sn
100 Sn
CAUSED BY COOLING
TOTAL LOSSES:

80 % Sn
100% Sn
RELATION BETWEEN SCATTERING LOSSES AND TOTAL
109
LOSSES
110 PERFORMANCE COS = 0,85:
111
112
113

118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134

WITHSTOOD VOLTAGE AT INDUSTRIAL FREQUENCY


WITHSTOOD VOLTAGE AT LIGHTING TYPE IMPULSE
(BIL)
TEST VOLTAGE WITH CHOPPED SHOCK WAVE /
TEST VOLTAGE FOR SWITCHING IMPULSE
TEST VOLTAGE AT INDUCED VOLTAGE (LONG
DURATION)
ACTIVE PART MATERIAL
ELECTRODINAMIC RIGIDITY
CURRENT DENSITY

141
142

HIGHEST VOLTAGE FOR THE MATERIAL


WITHSTOOD VOLTAGE AT INDUSTRIAL FREQUENCY
WITHSTOOD VOLTAGE AT LIGHTING TYPE IMPULSE
(BIL)

2,9
15
29,6
50
1,2

REFER TO ONAN
REFER TO ONAN
REFER TO ONAN
REFER TO ONAN

kW
kW
p.u.

42,5
59,5

REFER TO ONAN
REFER TO ONAN

99,3
99,39
99,31
99,18

REFER TO ONAN

%
%
%

24
50
125

kV
kV
kV

24
50
125

kV

kV

kA

COBRE
*
3,2

COBRE
A/mm

REFER TO ONAN
REFER TO ONAN
REFER TO ONAN

REFER TO ONAN

7,2
20
60

kV

7,2
20
60

kV

7,2
20
60

kV
kV

ARROLLAMIENTO SECUNDARIO B.T.:


HIGHEST VOLTAGE FOR THE MATERIAL
WITHSTOOD VOLTAGE AT INDUSTRIAL FREQUENCY
WITHSTOOD VOLTAGE AT LIGHTING TYPE IMPULSE
(BIL)
ACTIVE PART MATERIAL
ELECTRODINAMIC RIGIDITY
CURRENT DENSITY

RATED CURRENT
HIGHEST VOLTAGE FOR THE MATERIAL
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN DRY
ENVIRONMENT / 1 min
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN
RAINY ENVIRONMENT / 1 min

143
TEST VOLTAGE AT LIGHTING TYPE IMPULSE (BIL)
144
145 CONTAMINATION LEVEL S/IEC 60815
LINEA DE FUGA EN EXTERIOR
146
147

kW
kW
kW
kW
kW

LV NEUTRAL:

135
136 BUSHING INSULATORS
137
HV PRIMARY WINDING:
MANUFACTURER
138
TYPE OF CONNECTION
139
140

kW

7,2
9,5
11
13
15

25% PN
50% PN
75% PN
100% PN

114
115 WINDINGS
116
HV PRIMARY WINDING:
HIGHEST VOLTAGE FOR THE MATERIAL
117

*
*
*

%UN

IN INTERMEDIATE POSITION

REFER TO ONAN

*
*
*

%UN

83
84 REACTIVE SHORT-CIRCUIT VOLTAGE
IN UPPER POSITION
85

95

*
10
*

%UN

74

86

OBSERVATIONS

IN INTERMEDIATE POSITION

82

MANUFACTURER
DATA

TEST VOLTAGE AT SWITCHING IMPULSE

7,2
20
60

kV
kV

COBRE
kA
A/mm

BARRAS DE FASE
AISLADA
24
50

125
IV (muy alto)
31

A
kV

COBRE
*
3,2

CEDASPE o Similar
CUMPLE

kV

1000
24
50

kV

kV
mm/kV
kV

REFER TO ONAN

125
CUMPLE
31
N/A

Desert area
44 mm/kV According to IEEE C57.19

Pgina 2 de 5

H1

CHARACTERISTICS

REQUESTED

UNIT

TYPE OF INSULATION
TYPE OF BUSHING
CONDENSIVE TAP
PORCELAIN COLOR

148
149
150
151
152
153

NLI

MANUFACTURER
DATA

kV
-

OBSERVATIONS

52
SECO
N/A
CAF

LV NEUTRAL:
MANUFACTURER
TYPE OF CONNECTION

154
155

CABLE DE
COBRE AISLADO

RATED CURRENT
HIGHEST VOLTAGE FOR THE MATERIAL

CEDASPE o Similar
CUMPLE

7,2

A
kV

2000
7,2

20

kV

20

156
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN DRY
ENVIRONMENT / 1 min
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN
RAINY ENVIRONMENT / 1 min
TEST VOLTAGE AT LIGHTING TYPE IMPULSE (BIL)
LNEA DE FUGA A TENSIN SIMPLE
TENSIN DE ENSAYO A IMPULSO TIPO MANIOBRA
TIPO DE AISLAMIENTO
TIPO DE BORNA
COLOR DE LA PORCELANA

157
158
159
160
161
162
163
164
165
166

kV

60

kV
mm/KV
kV
kV
-

60
31
N/A
30
SECO
CAF

LV SECONDARY WINDING:
MANUFACTURER
TYPE OF CONNECTION

167
168

RATED CURRENT
HIGHEST VOLTAGE FOR THE MATERIAL

7,2

A
kV

CEDASPE o Similar
CUMPLE
2000
7,2

20

kV

20

CABLE DE

169
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN DRY
ENVIRONMENT / 1 min
TEST VOLTAGE AT INDUSTRIAL FREQUENCY IN
RAINY ENVIRONMENT / 1 min

170

171
TEST VOLTAGE AT LIGHTING TYPE IMPULSE (BIL)
172
LNEA DE FUGA A TENSIN COMPUESTA
173
TEST VOLTAGE AT SWITCHING IMPULSE
174
TYPE OF INSULATION
175
TYPE OF BUSHING
176
CONDENSIVE TAP
177
178 RADIOINTERFERENCE LEVEL
NOISE LEVEL (ACOUSTIC PRESSURE AT 1 m, RATED POWER
179 AND THE COOLING SYSTEM OPERATING FULLY)
180 GROUNDING CAPACITY OF MEDIUM TAP:
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228

kV

60

85

PRIMARY
SECONDARY
TYPE OF COOLING
FORCED COOLING EQUIPMENT

ONAN/ONAF

NUMBER OF STAGES
NUMBER OF RADIATORS
NUMBER OF FANS PER STAGE
POWER OF EACH FAN
FAN VOLTAGE / Hz
TYPE OF OIL
TOTAL AMOUNT OF OIL
MAXIMUM OIL SPEED
LEVEL OF FAN PROTECTION

480 V / 60 Hz

kV
mm/kV
kV
V
dB(A)

60
31
N/A
30
SECO
N/A
*
CUMPLE

F
F
-

*
*
ONAN/ONAF

Uds.
Uds.
Uds.
kW
V/Hz
l
cm/seg
IP

1
*
*
*
480 V / 60 Hz
Mineral
*

CAGE:

MAIN CAGE
MAXIMUM PRESSURE
MINIMUM PRESSURE

SI

EXPANSION TANK

kPa
kPa
-

SI
*
*
SI
SI

N/A

SI

CHAMBER 1 WITH RUBBER BALL FOR


ENVIRONMENTAL INSULATION
CHAMBER 2 WITH THE SAME FEATURES FOR
THE REGULATOR

PHYSICAL CHARACTERISTICS
DIMMENSIONS:

TOTAL LENGTH
HEIGHT WITH NO BUSHINGS
HEIGHT WITH BUSHINGS
HEIGHT WITH EXPANSION TANK
HEIGHT WITH AUTOMATIC VALVES IN HT
WIDTH
LENGTH FOR TRANSPORT
HEIGHT FOR TRANSPORT
WIDTH FOR TRANSPORT
WIDTH OF RAILWAY TRACKS
TYPE OF RAILWAY TRACKS

mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
kg/m

4100
2100
N/A

Without EXPANSION TANK


Bushing in side

3700
2500
3550
4100
2500
2000
*
*

WEIGHTS:

TOTAL
OF TRANSFORMER (NO OIL)
OF OIL
OUTSIDE THE CAGE
OF COPPER
OF MAGNETIC PLATE (CORE)
OF THE HEAVIEST PIECE TO TRANSPORT
PROTECTION
MATERIAL
LOCAL INDICATORS
INDICATING LAMPS
TEST LAMPS
SWITCHES AND BUTTONS

kg
kg
kg
kg
kg
kg
kg

19900
14700
5200
*
2450
5900
16700

CONTROL AND OPERATION CABINET


CUMPLE
IP65
COLD ROLLED
*
*
*
*
Pgina 3 de 5

H1

CHARACTERISTICS

REQUESTED

229 POWER BUS SUPPLY


230 FIRING RESISTANCE

UNIT

S 220 VAC
S 220 VAC
SI

231 LIGHTING AND ELECTRICAL SOCKETS


232 POTENTIAL-FREE ALARM CONTACTS
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252

NLI

LIGHTING AND AUXILIARY POWER SUPPLY


CONTROL AND THERMAL IMAGE POWER SUPPLY DEVICE

HV BUSHINGS:

AMOUNT PER PHASE


P CURRENT
S1 CURRENT
S1 POWER
S1 ACCURACY
S2 CURRENT
S2 POWER
S2 ACCURACY
THERMAL CURRENT LIMIT
DYNAMIC CURRENT LIMIT (PEAK)
MANUFACTURER
MODEL
SAFETY FACTOR (FOR INSTRUMENT
TRANSFORMERS)

MINERAL
NYNAS
SI
SI
BUSHING CURRENT TRANSFORMERS
PRIMEROS
1 Uds.
A
2000
A
5
VA
100
5P20
A
N/A
5
100 VA N/A
N/A
5P20
kA
*
kA
*
SIEMENS

306
307
308

1
2000
5
20
5P20

PENDING
1 TC PER PHASE FOR PROTECTION

SEGUNDOS
1
1000
5
100
5P20
5
25
CL 0,2

Uds.
A
A
VA
A
VA
kA
kA
-

1
1000

PENDING
1 TC PER PHASE FOR MEASURE

N/A
N/A
N/A
5
20
CL 0,2
*
*
SIEMENS

OPTIONAL

1
30
5
50
5P20

1
1500
5
50
5P20
5
50
CL 0,2

SAFETY FACTOR (FOR INSTRUMENT


TRANSFORMERS)
(NOTE: INCLUDE CURRENT TRANSFORMER FOR THERMAL IMAGE).

296
297 MAIN CAGE:
298
WHEELS ORIENTABLES 90
299
CNCAMOS DE ELEVACIN EN CUBA
300
APOYOS PARA GATOS HIDRULICOS

305

*
CUMPLE
CUMPLE
SI
*
*

SAFETY FACTOR (FOR INSTRUMENT

304

OBSERVATIONS

OIL
TYPE
MANUFACTURER
5% RESERVE TANK

267
TRANSFORMERS)
268 NEUTRAL TERMINAL
269
QUANTITY
270
P CURRENT
271
S1 CURRENT
272
S1 POWER
273
S1 ACCURACY
274
S2 CURRENT
275
S2 POWER
276
S2 ACCURACY
277
THERMAL CURRENT LIMIT
278
DYNAMIC CURRENT LIMIT
279
FABRICANTE
280
MANUFACTURER
281
MODEL
282 LV TERMINALS
283
AMOUNT PER PHASE
284
P CURRENT
285
S1 CURRENT
286
S1 POWER
287
S1 ACCURACY
288
S2 CURRENT
289
S2 POWER
290
S2 ACCURACY
291
THERMAL CURRENT LIMIT
292
DYNAMIC CURRENT LIMIT
293
FABRICANTE
294
MANUFACTURER

301
302
303

253
254 HV TERMINALS
255
AMOUNT PER PHASE
256
P CURRENT
257
S1 CURRENT
258
S1 POWER
259
S1 ACCURACY
260
S2 CURRENT
261
S2 POWER
262
S2 ACCURACY
263
THERMAL CURRENT LIMIT
264
DYNAMIC CURRENT LIMIT
265
MANUFACTURER
266
MODEL

295

MANUFACTURER
DATA

Uds.
A
A
VA
A
A
kA
kA
Uds.
A
A
VA
A
VA
kA
kA
-

1
300
5
20
5P20
N/A
N/A
N/A
*
*
SIEMENS
SIEMENS
2
1500
5
20

OPTIONAL
2 TC PER PHASE, ONE FOR MEASURE Y ONE
FOR PROTECTION

5P20
5
20
CL 0,2
*
*
SIEMENS
SIEMENS
INCLUDE TC FOR
THERMAL IMAGE

ACCESSORIES
Y TAPAS

CONEXIONES FLEXIBLES ENTRE LA CUBA Y


LA TAPA
VLVULA DE VACIADO
VLVULA DE TOMA DE MUESTRAS
DEPSITO DE EXPANSIN
DESECADOR DE SILICAGEL
TERMINALES PARA CONEXIN DE P.A.T.
PLACA DE CARACTERSTICAS INOX
VLVULA CONEXIN DE FILTRO
CAJA CUBREBORNAS PARA CONEXIN DE
CABLES/BARRAS, EQUIPADA CON
RESISTENCIA DE CALDEO Y TERMOSTATO

SI
SI
SI
SI

SI
SI
SI
SI

SI
SI
SI
SI
minimo 2
SI
SI
SI

SI
SI
SI
SI
CUMPLE
SI
SI
SI

OPPOSITE SIDES

BOTH SIDES (HV Y LV)

309
310 PROTECCIONES Y ALARMAS

Pgina 4 de 5

H1

311
312
313
314
315

CHARACTERISTICS

NLI

REQUESTED

REL BUCHHOLZ (ALARMA, 2xDISPARO)


INDICADOR DE NIVEL (ALARMA ALTA Y BAJA)
TERMMETRO TEMPERATURA ACEITE
(ALARMA, 2xDISPARO)
DETECCIN DE AUMENTO DE PRESION
(DISPARO)
IMAGEN TRMICA (ALARMA, 2xDISPARO)

UNIT

MANUFACTURER
DATA

SI
SI
SI

SI
SI
SI

SI

SI

SI

SI

OBSERVATIONS

* Dates according to final design and IEC Standard

Pgina 5 de 5

Rev. C

CLCULOS ELCTRICOS
ANEXO VI

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 17

ANEXO VI:

REPORTES DEL ANLISIS DE FLUJO DE CARGAS

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

One-Line Diagram - OLV1 (Load Flow Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

226624 kW
130683 kvar

AL

100%

ESTUDIO DE FLUJO DE CARGAS: CASO LF-1 (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL OPERANDO A PLENA CARGA Y FP=0,8 IND
-> GENERADOR AUXILIAR OPERANDO A PLENA CARGA Y FP=0,8 IND
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus
0,5 %Vd

S.E. Etn
220 kV

226860 kW
132202 kvar

100,

46%

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

99,9

227721 kW
170959 kvar

5%

223600 kW
167700 kvar

4117 kW
3259 kvar
Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Dyn11
Isolated Phase CU
35 m

CU
1MKA10
225 MW
1BBA51
6,6 kV

CU

120 m
3-3/C 300

CU

0,1 %Vd
8248 kW
6217 kvar
185 kW
119 kvar
CU

1BJA76
0,48 kV

CU

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

184 kW
114 kvar

108,

40 m
1-3/C 150

CU

CU
CU

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

0,0 %Vd

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

8440 kW
6330 kvar

Dyn11
1MKA76
8,44 MW

134 kW
59 kvar

40 m
3-3/C 240

20 m
3-3/C 300
0,0 %Vd

91%

2793 kW
1948 kvar

Open

2%

8440 kW
6324 kvar

20 m
1-3/C 300

0,0 %Vd

0
107,

106,

4138 kW
3632 kvar
0,0 %Vd

820 kW
428 kvar

1BBA76
6,6 kV

40 m
4-3/C 240

CARGAS 1BJA76
270 kVA

LCI 1BPA10_1
2725 kVA

0,0 %Vd

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

50 m
1-3/C 70

CU

50 m
1-3/C 70

409 kW
307 kvar

7%

310 kW
192 kvar

2749 kW
1575 kvar

100 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

0,0 %Vd

Dyn11

342 kW
145 kvar

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

0,0 %Vd
88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

1BMA52
0,48 kV

104,

1587 kW
1076 kvar

40 m
2-3/C 185

130 kW
97 kvar

69 kW
34 kvar

252 kW
142 kvar

67%

1136 kW
802 kvar

1BFA51
0,48 kV

Open
562 kW
397 kvar

400 kW
298 kvar

104,

174 kW
108 kvar

Open
CU

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

21%
108,

68 kW
33 kvar
1XKA52
2000 kW

10:05:48

CU

133 kW
57 kvar

88WN-1
224 kW
6
104,

CU

100 m
1-3/C 70

0,0 %Vd
88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

LCI 1BPA10_2
2725 kVA

W-1BJA12

page 1

CU

0,0 %Vd

1BFA53
0,48 kV
444 kW
0 kvar

70 m
1-3/C 70

0,0 %Vd

815 kW
395 kvar
Excitacin 1MKC10
944 kVA

CU

0,49 kW
-1 kvar

Open

CU

40 m
2-3/C 185

07%

184 kW
114 kvar

70 m
1-3/C 70

350 kW
157 kvar

Open

CARGAS 1BNB52
82,2 kVA

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240
173 kW
107 kvar
0,6 %Vd

Sistema PCI
200 kW

67%

One-Line Diagram - OLV1 (Load Flow Analysis)

1BMA52

CU

50 m
4-3/C 240

CU

50 m
6-3/C 240

0,2 %Vd

CU

0,2 %Vd

1BMB20
0,48 kV

4
104,

170 kW
105 kvar

1BFA51

1BFA53

0,3 %Vd

1BJA12
0,48 kV

9%

82 kW
36 kvar

4
104,

1BJA11
0,48 kV

5%

408 kW
306 kvar

CARGAS 1BJA11
695 kVA

1BMA52

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,1 %Vd 0,48 kV
130 kW
97 kvar

104,

56%

1BJA51
0,48 kV

20 m
4-3/C 240

0,1 %Vd
381 kW
286 kvar

19 kW
11 kvar

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

10:05:48

may 02, 2014

Project File: Eten

82 kW
36 kvar

1MBV10AP002-M1
75 kW

CARGAS 1BMB20
235 kVA

CU

3
104,

479 kW
359 kvar

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

104,

54%

7%

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-1


Eten

Informe de Flujo de Carga

Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV

% Mag.

6.600

106.915

6.600

0.480

0.480

107.022

104.673

104.673

Generacin

ng.
9.8

9.8

4.8

4.8

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.006

0.008

0.753

ID

-0.015

-0.012

0.192

1BBA76

MW

XFMR
Mvar

Amp

%PF

-8.241

-6.209

844.2

Bus17

0.134

0.059

12.0

91.5

Bus18

0.000

0.001

0.1

-34.4

Bus19

2.793

1.948

278.6

82.0

Bus20

0.820

0.428

75.7

88.7

79.9

Bus22

4.138

3.632

450.5

75.2

Bus15

0.350

0.157

31.4

91.3

1BBA51

8.248

6.217

844.2

79.9

Bus BS

-8.440

-6.324

862.0

80.0

Bus9

0.185

0.119

18.0

84.2

PCI_BUS

0.174

0.108

235.6

84.9

1BJA11

0.562

0.397

790.6

81.7

1BJA51

0.400

0.298

572.7

80.2

1BMA52

-1.136

-0.802

1598.4

81.7

1BJA12

0.409

0.307

587.3

80.0

-2.749

-1.575

3640.5

86.8

1BMA52

1.587

1.076

2203.0

82.8

Bus19

1BJA11

0.480

104.372

4.7

0.561

0.395

1BFA51

-0.561

-0.395

790.6

81.7

1BJA12

0.480

104.449

4.7

0.408

0.306

1BFA53

-0.408

-0.306

587.3

80.0

1BJA51

0.480

104.542

4.7

0.399

0.297

1BFA51

-0.399

-0.297

572.7

80.2

1BJA76

0.480

108.074

9.4

0.184

0.114

Bus9

-0.184

-0.114

240.5

85.0

1BMA52

0.480

104.673

4.8

1BMB20

0.252

0.142

332.2

87.1

1BMB52

0.130

0.097

186.3

80.0

1BNB52

0.069

0.034

88.8

89.5

1BFA51

1.136

0.802

1598.4

81.7

1BFA53

-1.587

-1.076

2203.0

82.8

1BMB20

0.480

104.486

4.7

0.252

0.141

1BMA52

-0.252

-0.141

332.2

87.2

1BMB52

0.480

104.556

4.8

0.130

0.097

1BMA52

-0.130

-0.097

186.3

80.0

1BNB52

0.380

108.211

4.2

0.068

0.033

1BMA52

-0.068

-0.033

106.6

90.0

Bus5

4.000

109.856

9.4

0.133

0.057

Bus10

-0.133

-0.057

19.0

91.9

Bus7

4.000

107.675

8.7

0.342

0.145

Bus13

-0.342

-0.145

49.8

92.1

Bus9

6.600

107.021

9.8

-0.001

0.002

Bus10

4.160

105.645

9.4

Bus13

4.000

107.713

8.7

%Tap

1BBA76

-0.185

-0.119

18.0

84.2

1BJA76

0.186

0.117

18.0

84.6

Bus5

0.133

0.057

19.0

91.9

Bus17

-0.133

-0.057

19.0

91.9

Bus7

0.342

0.145

49.8

92.1

2.500

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-1


Eten

Barra
ID

Bus15

Tensin
kV

% Mag.

6.600

106.886

Generacin

ng.

9.8

MW

Carga

Mvar

MW

Flujo de Carga
Mvar

ID

6.600

106.907

9.8

XFMR
Mvar

Amp

%PF

Bus15

-0.342

-0.145

49.8

92.1

1BBA51

-0.350

-0.157

31.4

91.3

0.350

0.157

31.4

91.3
91.5

Bus13
Bus17

MW

-0.134

-0.059

12.0

Bus10

1BBA51

0.134

0.059

11.9

91.6

Bus18

6.600

106.915

9.8

0.000

0.001

1BBA51

0.000

-0.001

0.1

-34.4

Bus19

6.600

106.891

9.8

0.000

0.001

1BBA51

-2.793

-1.947

278.6

82.0

1BFA53

2.793

1.946

278.6

82.0

Bus20

Bus22

6.600

6.900

106.900

102.250

9.8

9.8

-0.008

0.008

1BBA51

-0.820

-0.428

75.7

88.7

Bus EX

0.820

0.427

75.7

88.7

1BBA51

-4.138

-3.631

450.5

75.2

4.145

3.623

450.5

75.3
80.0

BUS GEN
Bus BS

6.600

107.040

9.8

8.440

6.330

-0.001

0.005

1BBA76

Bus EX

0.480

98.113

8.1

0.815

0.395

Bus20

18.000

99.953

7.0

223.600

167.700

-0.004

0.000

S.E. Etn

BUS GEN

Bus22
PCI_BUS

0.480

104.060

4.7

0.173

0.107

S.E. Etn

220.000

100.462

0.4

* S.E. Reque

220.000

100.000

0.0

-226.624

-130.684

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)
# Indica una barra con un error de convergencia superior a 0,1 MVA

1BFA51

8.441

6.325

862.0

-0.815

-0.395

1110.1

90.0

227.721

170.959

9137.7

80.0

-4.117

-3.259

168.5

78.4
85.0

-0.173

-0.107

235.6

S.E. Reque

226.860

132.202

685.9

86.4

BUS GEN

-226.860

-132.202

685.9

86.4

S.E. Etn

-226.624

-130.684

686.5

86.6

%Tap

2.500

9.000

One-Line Diagram - OLV1 (Load Flow Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

227322 kW
-108616 kvar

AL

100%

ESTUDIO DE FLUJO DE CARGAS: CASO LF-2 (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL OPERANDO A PLENA CARGA Y FP=0,95 CAP
-> GENERADOR AUXILIAR OPERANDO A PLENA CARGA Y FP=0,95 CAP
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus
0,2 %Vd

S.E. Etn
220 kV

227540 kW
-107236 kvar

99,7

6%

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

100,

228156 kW
-79546 kvar

34%

223600 kW
-73494 kvar

4556 kW
-6053 kvar
Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Dyn11
Isolated Phase CU
35 m

CU
1MKA10
225 MW
1BBA51
6,6 kV

CU

120 m
3-3/C 300

CU

0,0 %Vd
8270 kW
-2882 kvar
169 kW
106 kvar
CU

1BJA76
0,48 kV

CU

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

166 kW
103 kvar

95,6

40 m
1-3/C 150

CU

CU

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

0,0 %Vd

20 m
3-3/C 300
1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1
8440 kW
-2774 kvar

Dyn11
1MKA76
8,44 MW

134 kW
59 kvar

40 m
3-3/C 240
CU

0,0 %Vd

2%

2517 kW
1852 kvar

Open

8439 kW
-2775 kvar

20 m
1-3/C 300

0,0 %Vd

6
94,9

94,9

4615 kW
-5298 kvar
0,0 %Vd

647 kW
337 kvar

1BBA76
6,6 kV

40 m
4-3/C 240

LCI 1BPA10_1
2725 kVA

0,0 %Vd

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

50 m
1-3/C 70

CU

50 m
1-3/C 70

394 kW
295 kvar

254 kW
157 kvar

50 m
1-3/C 70

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

0,0 %Vd

Dyn11

342 kW
145 kvar

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

0,0 %Vd
88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW
91,6

1482 kW
1002 kvar

40 m
2-3/C 185

114 kW
85 kvar

54 kW
27 kvar

241 kW
135 kvar

1072 kW
754 kvar

1BFA51
0,48 kV

Open
544 kW
383 kvar

353 kW
263 kvar

91,6

175 kW
108 kvar

Open
50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

5%
94,6

54 kW
26 kvar
1XKA52
2000 kW

10:07:42

100 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

1BMA52
0,48 kV

CU

W-1BJA12

page 1

CU

133 kW
57 kvar

88WN-1
224 kW
2469 kW
1455 kvar

CU

100 m
1-3/C 70

0,0 %Vd
88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

LCI 1BPA10_2
2725 kVA
%
91,6

340 kW
0 kvar

CU

0,0 %Vd

1BFA53
0,48 kV

CARGAS 1BJA76
270 kVA

70 m
1-3/C 70

0,0 %Vd

642 kW
311 kvar
Excitacin 1MKC10
944 kVA

CU

0 kW
0 kvar

Open

CU

40 m
2-3/C 185

5%

166 kW
103 kvar

70 m
1-3/C 70

352 kW
160 kvar

Open

CARGAS 1BNB52
82,2 kVA

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240
173 kW
107 kvar
0,7 %Vd

Sistema PCI
200 kW

One-Line Diagram - OLV1 (Load Flow Analysis)

1BMA52

CU

50 m
4-3/C 240

CU

50 m
6-3/C 240

0,2 %Vd

CU

0,2 %Vd

1BMB20
0,48 kV
82 kW
36 kvar

5
91,3

1BJA11
0,48 kV

393 kW
294 kvar

CARGAS 1BJA11
695 kVA

1BMA52

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,1 %Vd 0,48 kV
114 kW
85 kvar

91,4

8%

1BJA51
0,48 kV

20 m
4-3/C 240

0,1 %Vd
334 kW
251 kvar

19 kW
11 kvar

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

10:07:42

may 02, 2014

Project File: Eten

82 kW
36 kvar

1MBV10AP002-M1
75 kW

CARGAS 1BMB20
235 kVA

CU

7
91,2

461 kW
346 kvar

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

0,3 %Vd

1BJA12
0,48 kV

%
91,4

159 kW
99 kvar

1BFA51

1BFA53

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

91,4

7%

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-2


Eten

Informe de Flujo de Carga

Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV
6.600

6.600

0.480

0.480

% Mag.
94.922

94.955

91.601

91.601

Generacin

ng.
10.5

10.6

4.7

4.7

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.594

ID
0

0.157

1BBA76

MW

XFMR
Mvar

Amp

%PF

-8.264

2.890

806.8

Bus17

0.134

0.059

13.5

91.5

Bus18

0.000

0.000

0.0

-50.1

Bus19

2.517

1.852

288.0

80.5

Bus20

0.647

0.337

67.2

88.7

Bus22

4.615

-5.298

647.5

-65.7

Bus15

0.352

0.160

35.7

91.0

1BBA51

8.270

-2.882

806.8

-94.4

Bus BS

-8.439

2.775

818.4

-95.0

-94.4

Bus9

0.169

0.106

18.4

84.5

PCI_BUS

0.175

0.108

269.8

84.9

1BJA11

0.544

0.383

874.3

81.8

1BJA51

0.353

0.263

578.0

80.3

1BMA52

-1.072

-0.754

1721.4

81.8

1BJA12

0.394

0.295

646.1

80.0

-2.469

-1.455

3763.4

86.2

1BMA52

1.482

1.002

2349.0

82.8

Bus19

1BJA11

0.480

91.268

4.6

0.543

0.382

1BFA51

-0.543

-0.382

874.3

81.8

1BJA12

0.480

91.354

4.6

0.393

0.294

1BFA53

-0.393

-0.294

646.1

80.0

1BJA51

0.480

91.468

4.7

0.353

0.262

1BFA51

-0.353

-0.262

578.0

80.3

1BJA76

0.480

95.647

10.1

0.166

0.103

Bus9

-0.166

-0.103

246.0

85.0

1BMA52

0.480

91.601

4.7

1BMB20

0.241

0.135

363.4

87.2

1BMB52

0.114

0.085

186.9

80.0

1BNB52

0.054

0.027

79.7

89.5

1BFA51

1.072

0.754

1721.4

81.8

1BFA53

-1.482

-1.002

2349.0

82.8

1BMB20

0.480

91.397

4.6

0.241

0.135

1BMA52

-0.241

-0.135

363.4

87.3

1BMB52

0.480

91.484

4.7

0.114

0.085

1BMA52

-0.114

-0.085

186.9

80.0

1BNB52

0.380

94.652

4.0

0.054

0.026

1BMA52

-0.054

-0.026

95.7

90.0

Bus5

4.000

97.209

9.9

0.133

0.057

Bus10

-0.133

-0.057

21.4

91.9

Bus7

4.000

94.714

9.0

0.342

0.145

Bus13

-0.342

-0.145

56.6

92.1

Bus9

6.600

94.954

10.6

1BBA76

-0.169

-0.106

18.4

84.5

1BJA76

0.169

0.106

18.4

84.6

Bus5

0.133

0.057

21.4

91.9

Bus17

-0.133

-0.057

21.4

91.9

Bus7

0.342

0.145

56.6

92.1

Bus10

4.160

93.486

9.9

Bus13

4.000

94.756

9.0

%Tap

2.500

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-2


Eten

Barra
ID

Bus15

Tensin
kV

6.600

% Mag.

94.889

Generacin

ng.

10.5

MW

Carga

Mvar

MW

Flujo de Carga
Mvar

ID

6.600

94.913

10.5

XFMR
Mvar

Amp

%PF

Bus15

-0.342

-0.145

56.6

92.1

1BBA51

-0.352

-0.160

35.7

91.0

0.352

0.160

35.7

91.0
91.5

Bus13
Bus17

MW

1BBA51

-0.134

-0.059

13.5

Bus10

0.134

0.059

13.5

91.5

Bus18

6.600

94.922

10.5

1BBA51

0.000

0.000

0.0

-50.1

Bus19

6.600

94.898

10.5

1BBA51

-2.516

-1.852

288.0

80.5

1BFA53

2.516

1.852

288.0

80.5

1BBA51

-0.647

-0.337

67.2

88.7

Bus EX

0.647

0.337

67.2

88.7

1BBA51

-4.614

5.299

647.5

-65.7

4.614

-5.299

647.5

-65.7
-95.0

Bus20

Bus22

6.600

6.900

94.909

90.797

10.5

10.5

BUS GEN
Bus BS

6.600

94.961

10.6

8.440

-2.774

Bus EX

0.480

87.108

8.8

0.642

0.311

18.000

100.344

6.4

223.600

-73.494

BUS GEN

1BBA76
Bus20
S.E. Etn
Bus22

PCI_BUS

0.480

90.899

4.6

0.173

0.107

S.E. Etn

220.000

99.762

0.4

* S.E. Reque

220.000

100.000

0.0

-227.322

108.616

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)
# Indica una barra con un error de convergencia superior a 0,1 MVA

1BFA51

8.440

-2.774

818.4

-0.642

-0.311

985.5

90.0

228.156

-79.546

7723.6

-94.4

-4.556

6.053

242.2

-60.1

-0.173

-0.107

269.8

85.0

S.E. Reque

227.540

-107.236

661.7

-90.5

BUS GEN

-227.540

107.236

661.7

-90.5

S.E. Etn

-227.322

108.616

661.2

-90.2

%Tap

2.500

-4.500

One-Line Diagram - OLV1 (Load Flow Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

3944 kW
2398 kvar

100%

ESTUDIO DE FLUJO DE CARGAS: CASO LF-3 - MNIMA TENSIN EN BARRAS (REV C)

3944 kW
2398 kvar
AL

CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL PARADO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus
0,0 %Vd

S.E. Etn
220 kV

99,9

9%

3944 kW
2879 kvar

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
99,8

BUS GEN
18 kV

5%

3943 kW
2867 kvar
Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

CU
1MKA10
225 MW
1BBA51
6,6 kV
172 kW
109 kvar
CU

120 m
3-3/C 300

CU

0,0 %Vd
7
97,6

40 m
1-3/C 150

CU

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

0,0 %Vd

1BJA76
0,48 kV

20 m
3-3/C 300

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

170 kW
105 kvar

98,4

CU
CU

0,0 %Vd
CU

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

Dyn11
1MKA76
8,44 MW

134 kW
59 kvar

40 m
3-3/C 240

Open
20 m
1-3/C 300

7%

2576 kW
1870 kvar

Open

172 kW
109 kvar
CU

97,6

3918 kW
2552 kvar
0,0 %Vd

685 kW
357 kvar

1BBA76
6,6 kV

40 m
4-3/C 240

CARGAS 1BJA76
270 kVA

LCI 1BPA10_1
2725 kVA

0,0 %Vd

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

50 m
1-3/C 70

CU

50 m
1-3/C 70

397 kW
298 kvar

266 kW
165 kvar

2529 kW
1481 kvar

100 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

0,0 %Vd

Dyn11

342 kW
145 kvar

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

0,0 %Vd
88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

1BMA52
0,48 kV

94,6

1504 kW
1018 kvar

40 m
2-3/C 185

117 kW
88 kvar

58 kW
29 kvar

244 kW
137 kvar

3%

1085 kW
766 kvar

1BFA51
0,48 kV

Open
548 kW
387 kvar

363 kW
271 kvar

94,6

174 kW
108 kvar

Open
CU

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

9%
97,7

57 kW
28 kvar
1XKA52
2000 kW

10:10:16

CU

133 kW
57 kvar

88WN-1
224 kW
3
94,6

CU

100 m
1-3/C 70

0,0 %Vd
88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

LCI 1BPA10_2
2725 kVA

W-1BJA12

page 1

CU

0,0 %Vd

1BFA53
0,48 kV
363 kW
0 kvar

70 m
1-3/C 70

0,0 %Vd

680 kW
330 kvar
Excitacin 1MKC10
944 kVA

CU

0,04 kW
0,21 kvar

Open

CU

40 m
2-3/C 185

5%

170 kW
105 kvar

70 m
1-3/C 70

352 kW
159 kvar

Open

CARGAS 1BNB52
82,2 kVA

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240
173 kW
107 kvar
0,7 %Vd

Sistema PCI
200 kW

3%

One-Line Diagram - OLV1 (Load Flow Analysis)

1BMA52

CU

50 m
4-3/C 240

CU

50 m
6-3/C 240

0,2 %Vd

CU

0,2 %Vd

1BMB20
0,48 kV

3
94,4

162 kW
100 kvar

1BFA51

1BFA53

0,3 %Vd

1BJA12
0,48 kV

82 kW
36 kvar

8
94,3

1BJA11
0,48 kV

396 kW
297 kvar

CARGAS 1BJA11
695 kVA

1BMA52

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,1 %Vd 0,48 kV
117 kW
88 kvar

94,5

1%

1BJA51
0,48 kV

20 m
4-3/C 240

0,1 %Vd
345 kW
258 kvar

19 kW
11 kvar

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

10:10:16

may 02, 2014

Project File: Eten

82 kW
36 kvar

1MBV10AP002-M1
75 kW

CARGAS 1BMB20
235 kVA

CU

%
94,3

465 kW
349 kvar

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

94,4

9%

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-3


Eten

Informe de Flujo de Carga

Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV
6.600

6.600

0.480

0.480

% Mag.
97.675

97.673

94.625

94.625

Generacin

ng.
-3.1

-3.1

-8.7

-8.7

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.000

0.629

ID

-0.002

0.165

MW

XFMR
Mvar

Amp

%PF

1BBA76

0.172

0.109

18.2

84.6

Bus17

0.134

0.059

13.1

91.5

Bus18

0.000

0.000

0.0

19.2

Bus19

2.576

1.870

285.1

80.9

Bus20

0.685

0.357

69.2

88.7

Bus22

-3.918

-2.552

418.8

83.8

Bus15

0.352

0.159

34.6

91.1

-0.172

-0.109

18.2

84.6

Bus9

0.172

0.109

18.3

84.5

PCI_BUS

0.174

0.108

261.0

84.9

1BJA11

0.548

0.387

852.4

81.7

1BJA51

0.363

0.271

575.6

80.2

1BMA52

-1.085

-0.766

1688.4

81.7

1BJA12

0.397

0.298

630.6

79.9

1BBA51

Bus19

-2.529

-1.481

3725.7

86.3

1BMA52

1.504

1.018

2308.2

82.8

1BJA11

0.480

94.301

-8.7

0.546

0.385

1BFA51

-0.546

-0.385

852.4

81.7

1BJA12

0.480

94.385

-8.7

0.396

0.297

1BFA53

-0.396

-0.297

630.6

80.0

1BJA51

0.480

94.494

-8.7

0.363

0.270

1BFA51

-0.363

-0.270

575.6

80.2

1BJA76

0.480

98.449

-3.5

0.170

0.105

Bus9

-0.170

-0.105

244.4

85.0

1BMA52

0.480

94.625

-8.7

1BMB20

0.244

0.137

355.3

87.2

1BMB52

0.117

0.088

186.4

80.1

1BNB52

0.058

0.029

81.8

89.5
81.7

1BFA51

1.085

0.766

1688.4

1BFA53

-1.504

-1.018

2308.2

82.8

1BMB20

0.480

94.426

-8.7

0.243

0.136

1BMA52

-0.243

-0.136

355.3

87.3

1BMB52

0.480

94.509

-8.7

0.117

0.088

1BMA52

-0.117

-0.088

186.4

80.0

1BNB52

0.380

97.790

-9.3

0.057

0.028

1BMA52

-0.057

-0.028

98.2

90.0

Bus5

4.000

100.117

-3.6

0.132

0.057

Bus10

-0.132

-0.057

20.8

91.9

Bus7

4.000

97.701

-4.5

0.342

0.145

Bus13

-0.342

-0.145

54.9

92.1

Bus9

6.600

97.671

-3.1

1BBA76

-0.172

-0.109

18.3

84.5

1BJA76

0.172

0.109

18.2

84.6

Bus10

4.160

96.281

-3.6

Bus5

0.132

0.057

20.8

91.9

Bus17

-0.132

-0.057

20.8

91.9

Bus13

4.000

97.743

-4.5

Bus7

0.342

0.145

54.9

92.1

Bus15

-0.342

-0.145

54.8

92.1

%Tap

2.500

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-3


Eten

Barra
ID
Bus15

Tensin
kV
6.600

% Mag.
97.643

Generacin

ng.
-3.1

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

1BBA51
Bus13

XFMR
Mvar

Amp

%PF

-0.352

-0.159

34.6

91.1

0.352

0.159

34.6

91.1

-0.134

-0.059

13.1

91.5

Bus17

6.600

97.667

-3.1

Bus10

0.134

0.059

13.1

91.5

Bus18

6.600

97.675

-3.1

1BBA51

0.000

0.000

0.0

19.2

Bus19

6.600

97.651

-3.1

1BBA51

-2.576

-1.870

285.1

80.9

1BFA53

2.575

1.870

285.1

80.9

1BBA51

-0.685

-0.357

69.2

88.7

Bus EX

0.685

0.357

69.1

88.7

1BBA51

3.919

2.553

418.8

83.8

BUS GEN

-3.919

-2.552

418.8

83.8

Bus20

-0.680

-0.330

1014.1

90.0

S.E. Etn

-3.944

-2.867

156.6

80.9

3.943

2.867

156.6

80.9

1BFA51

-0.173

-0.107

261.0

85.0

-3.944

-2.879

12.8

80.8

Bus20

6.600

97.661

-3.1

Bus22

6.900

93.442

-3.1

Bus EX
BUS GEN

0.480

89.634

-4.7

0.680

0.330

18.000

99.849

-0.1

0.001

0.000

1BBA51

MW

Bus22
PCI_BUS

0.480

93.946

-8.8

0.173

0.107

S.E. Etn

220.000

99.991

0.0

S.E. Reque
BUS GEN

3.944

2.879

12.8

80.8

* S.E. Reque

220.000

100.000

0.0

3.944

2.398

S.E. Etn

3.944

2.398

12.1

85.4

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)
# Indica una barra con un error de convergencia superior a 0,1 MVA

%Tap

2.500

One-Line Diagram - OLV1 (Load Flow Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

0,1 kW
481 kvar

AL

100%

ESTUDIO DE FLUJO DE CARGAS: CASO LF-4 - MXIMA TENSIN EN BARRAS (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL PARADO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS FUERA DE SERVICIO.

2,92 km
Narcissus
0,0 %Vd

S.E. Etn
220 kV

0,1 kW
0,45 kvar

100%

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

100%

0,1 kW
0,45 kvar

0,13 kW
0,44 kvar
Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

CU
1MKA10
225 MW
1BBA51
6,6 kV

CU

120 m
3-3/C 300

CU

0,0 %Vd
0 kW
0 kvar

Open

40 m
1-3/C 150

CU

0,0 %Vd

1BJA76
0,48 kV

CU
CU

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

0,0 %Vd
CU

20 m
3-3/C 300

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

Yd1

0 kW
0 kvar

40 m
3-3/C 240

Open
20 m
1-3/C 300

0 kW
0,36 kvar

102%

0 kW
-0,01 kvar
CU

102%

0,06 kW
0,51 kvar
0,0 %Vd

0,001 kW
0 kvar

1BBA76
6,6 kV

40 m
4-3/C 240

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z
Dyn11

CU

70 m
1-3/C 70

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

0,0 %Vd

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

50 m
1-3/C 70

CU

50 m
1-3/C 70

88WN-1
224 kW

LCI 1BPA10_2
2725 kVA

1BFA53
0,48 kV

3
107,

1%

0,03 kW
-0,18 kvar

CARGAS 1BJA76
270 kVA

0,18 kW
0,27 kvar

100 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

40 m
2-3/C 185

0,0 %Vd

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

0,0 %Vd
88AK-1
375 kW

88WN-2
224 kW

88AK-2
375 kW

1BMA52
0,48 kV

107,

0,21 kW
0,1 kvar

0 kW
0,05 kvar

31%

0,07 kW
-0,46 kvar

1BFA51
0,48 kV

Open
0,03 kW
-0,18 kvar

0,04 kW
-0,3 kvar

W-1BJA11

W-1BJA51

107,

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

1XKA52
2000 kW

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

0,001 kW
0 kvar 96%
112,

CARGAS 1BNB52
82,2 kVA

W-1BMB20

31%

0 kW
-0,01 kvar

Open
CU

W-1BJA12

10:11:32

CU

0,0 %Vd
LCI 1BPA10_1
2725 kVA

CU

100 m
1-3/C 70

0,0 %Vd
88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

0,0 %Vd

69%

Excitacin 1MKC10
944 kVA

page 1

CU

0 kW
-0,01 kvar

Open

CU

40 m
2-3/C 185

1MKA76
8,44 MW
104,

70 m
1-3/C 70

0,07 kW
0,13 kvar

Open

CU

115 m
2-3/C 240

0,0 %Vd
Sistema PCI
200 kW

One-Line Diagram - OLV1 (Load Flow Analysis)

1BMA52

CU

1BMB20
0,48 kV

1BFA51

1BFA53

50 m
4-3/C 240

CU

0,0 %Vd
0,01 kW
-0,05 kvar

50 m
6-3/C 240

CU

0,0 %Vd
3
107,

0,0 %Vd

1BJA12
0,48 kV

1%

3
107,

1BJA11
0,48 kV

1%

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,0 %Vd 0,48 kV
107,

31%

1BJA51
0,48 kV

20 m
4-3/C 240

0,0 %Vd

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

10:11:32

may 02, 2014

Project File: Eten

3
107,

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

107,

31%

1%

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-4


Eten

Informe de Flujo de Carga

Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV

% Mag.

6.600

101.997

6.600

0.480

0.480

101.997

107.310

107.310

Generacin

ng.
0.0

0.0

0.0

0.0

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

%PF

1BBA76

0.000

0.000

0.0

Bus17

0.000

0.000

0.0

0.0

Bus18

0.000

0.000

0.0

-1.8

Bus19

0.000

0.000

0.0

0.6

Bus20

0.000

0.000

0.0

38.9

Bus22

0.000

0.001

0.0

11.7

Bus15

0.000

0.000

0.0

47.6

%Tap

10.0

1BBA51

0.000

0.000

0.0

10.0

Bus9

0.000

0.000

0.0

-16.2

PCI_BUS

0.000

0.000

0.0

-17.9

1BJA11

0.000

0.000

0.2

-14.9

1BJA51

0.000

0.000

0.3

-14.9

1BMA52

0.000

0.000

0.5

-14.8

1BJA12

0.000

0.000

0.2

-14.9
55.4

Bus19

0.000

0.000

0.4

1BMA52

0.000

0.000

0.3

90.8

1BJA11

0.480

107.310

0.0

1BFA51

0.000

0.000

0.2

-14.9

1BJA12

0.480

107.310

0.0

1BFA53

0.000

0.000

0.2

-14.9

1BJA51

0.480

107.310

0.0

1BFA51

0.000

0.000

0.3

-14.9

1BJA76

0.480

104.692

0.0

Bus9

0.000

0.000

0.0

0.0

1BMA52

0.480

107.310

0.0

1BMB20

0.000

0.000

0.1

-17.9

1BMB52

0.000

0.000

0.1

3.7

1BNB52

0.000

0.000

0.0

-43.5

1BFA51

0.000

0.000

0.5

-14.8

1BFA53

0.000

0.000

0.3

90.8

1BMB20

0.480

107.310

0.0

1BMA52

0.000

0.000

0.1

-17.9

1BMB52

0.480

107.310

0.0

1BMA52

0.000

0.000

0.1

3.7

1BNB52

0.380

112.958

0.0

1BMA52

0.000

0.000

0.0

-43.5

Bus5

4.000

106.077

0.0

Bus10

0.000

0.000

0.0

18.7

Bus7

4.000

106.078

0.0

Bus13

0.000

0.001

0.1

6.8

Bus9

6.600

101.997

0.0

1BBA76

0.000

0.000

0.0

-16.2

1BJA76

0.000

0.000

0.0

0.0

Bus10

4.160

101.997

0.0

Bus5

0.000

0.000

0.0

18.7

Bus17

0.000

0.000

0.0

93.5

Bus13

4.000

106.078

0.0

Bus7

0.000

-0.001

0.1

6.8

Bus15

0.000

0.000

0.0

71.1

2.500

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: LF-4


Eten

Barra
ID
Bus15

Tensin
kV

% Mag.

6.600

101.997

Generacin

ng.
0.0

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

%PF

1BBA51

0.000

0.000

0.0

47.6

Bus13

0.000

0.000

0.0

71.1

1BBA51

0.000

0.000

0.0

0.0

Bus17

6.600

101.997

0.0

Bus10

0.000

0.000

0.0

93.5

Bus18

6.600

101.997

0.0

1BBA51

0.000

0.000

0.0

-1.8

Bus19

6.600

101.997

0.0

1BBA51

0.000

0.000

0.0

0.6

1BFA53

0.000

0.000

0.0

55.4

1BBA51

0.000

0.000

0.0

38.9

Bus EX

0.000

0.000

0.0

0.0

1BBA51

0.000

-0.001

0.0

11.7

BUS GEN

0.000

0.000

0.0

29.0

Bus20

0.000

0.000

0.0

0.0
21.6

Bus20

6.600

101.997

0.0

Bus22

6.900

97.562

0.0

Bus EX

0.480

95.622

0.0

18.000

100.001

0.0

BUS GEN

S.E. Etn

0.000

0.000

0.0

Bus22

0.000

0.000

0.0

29.0

PCI_BUS

0.480

107.310

0.0

1BFA51

0.000

0.000

0.0

-17.9

S.E. Etn

220.000

100.001

0.0

S.E. Reque

0.000

0.000

0.0

21.2

BUS GEN

0.000

0.000

0.0

21.6

* S.E. Reque

220.000

100.000

0.0

0.000

-0.481

S.E. Etn

0.000

-0.481

1.3

0.0

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)
# Indica una barra con un error de convergencia superior a 0,1 MVA

%Tap

2.500

Rev. C

CLCULOS ELCTRICOS
ANEXO VI

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 49

ANEXO VII:

REPORTES DEL ANLISIS DE CORTOCIRCUITO

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

One-Line Diagram - OLV1 (Short-Circuit Analysis)


Red elctrica Peruana
220 kV
3022 MVAsc

RESERVA FRA ETEN

S.E. Reque
220 kV

7,93
10,8

2,84
AL

ESTUDIO DE CORTOCIRCUITO: CASO SC-1 (REV C)

kA

CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL OPERANDO
-> GENERADOR AUXILIAR OPERANDO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus

S.E. Etn
220 kV

7,34

10,3

2,92

kA

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

104,

44,53

6 kA

58,48

1,63
Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Dyn11
Isolated Phase CU
35 m

18 kV
9021 A
1MKA10
225 MW
17 %Xd"

CU
1BBA51
6,6 kV

16,8

kA

40 m
4-3/C 240

8,07

7,35

1,05

,153

Open
CU
1BBA76
6,6 kV

120 m
3-3/C 300

CU

9,39
,092

CU

16,8

40 m
3-3/C 240

CU

CU
CU

7,32

20 m
1-3/C 300

70 m
1-3/C 70

70 m
1-3/C 70

CU

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

Dyn11

16,3

kA

Excitacin 1MKC10
944 kVA
1BFA53
0,48 kV

49,7

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

50 m
1-3/C 70

88WN-1
224 kW

kA

1BMA52
0,48 kV

31,86
4,08

,821

13,32

49,7

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

40 m
2-3/C 185

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW
49,7

Open
,944

,074

2,24

10,06

39,77

5,21

kA

1BFA51
0,48 kV

2,81

2,06

Open
CU

W-1BJA12

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

1BNB52
0,38 kV

,085

1XKA52
2000 kW

may 02, 2014

Project File: Eten

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

5,56
5,6
kA

0,48 kV
3007 A

10:00:39

100 m
1-3/C 70

kA

36,59

CARGAS 1BJA76
270 kVA

page 1

CU

100 m
1-3/C 70

CU
88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

20 m
3-3/C 300

Open

1MKA76
8,44 MW
16 %Xd"

15,12
1,23

CU

kA

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z
6,6 kV
922,9 A
1BJA76
0,48 kV

40 m
1-3/C 150

,233
Open

CARGAS 1BNB52
82,2 kVA

Sistema PCI
200 kW

One-Line Diagram - OLV1 (Short-Circuit Analysis)

1BMA52

CU

1BMB20
0,48 kV

50 m
4-3/C 240

CU

41,7

39,47
1,45

1BFA51

1BFA53

1BJA12
0,48 kV

kA

,82

50 m
6-3/C 240

40,48

CU

44,6

1BJA11
0,48 kV

kA

4,13

4,48

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

41,9

kA

1BFA51

20 m
2-3/C 150

40,98

CU

1BMB52
0,48 kV
,948

1BJA51
0,48 kV

20 m
4-3/C 240

43,5
2,67

46,3

,153

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

10:00:39

may 02, 2014

Project File: Eten

39,61

44,9

kA

,82

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

kA

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Informe de Cortocircuito
Falta trifsica en barra: 1BBA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

6.600
1.10
42.505
15.340

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BBA51

Total

0.00

1.477

-16.764

11.4

16.829

1BBA76

1BBA51

0.81

0.450

-7.339

16.3

7.353

Bus17

1BBA51

0.07

0.041

-0.147

3.6

0.153

Bus18

1BBA51

0.00

0.000

0.000

999.9

0.000

Bus19

1BBA51

0.07

0.303

-1.005

3.3

1.049

Bus20

1BBA51

0.00

0.000

0.000

999.9

0.000

Bus22

1BBA51

0.23

0.619

-8.048

13.0

8.072

Bus15

1BBA51

0.15

0.064

-0.224

3.5

0.233

Bus BS

1BBA76

0.94

0.413

-7.256

17.6

7.268

Bus9

1BBA76

0.81

0.037

-0.083

2.3

0.091

Bus10

Bus17

14.61

0.041

-0.147

3.6

0.153

1BFA53

Bus19

34.11

0.303

-1.005

3.3

1.049

Bus EX

Bus20

0.00

0.000

0.000

999.9

0.000

BUS GEN

Bus22

95.11

0.619

-8.048

13.0

8.072

Bus13

Bus15

23.23

0.064

-0.224

3.5

0.233

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

16.078

23.937

17.733

0.02

15.753

20.929

13.779

0.03

15.414

18.641

10.484

0.04

15.065

17.047

7.977

0.05

14.709

16.055

6.436

0.06

14.562

15.382

4.955

0.07

14.415

14.911

3.814

0.08

14.270

14.569

2.937

0.09

14.122

14.329

2.426

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

(Cont.)
Falta trifsica en barra: 1BBA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

6.600
1.10
42.505
15.340

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.10

13.973

14.099

0.15

13.740

13.751

1.883
0.530

0.20

13.509

13.510

0.149

0.25

13.280

13.280

0.042

0.30

13.111

13.111

0.012

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BBA76


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

6.600
1.10
42.389
15.327

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

1BBA76

Total

0.00

1.483

-16.725

1BBA51

1BBA76

1.03

1.057

Bus BS

1BBA76

0.13

0.389

Bus9

1BBA76

0.01

Bus17

1BBA51

Bus18

1BBA51

Bus19
Bus20

X/R
Cociente

kA
Magnitud

11.3

16.791

-9.331

8.8

9.391

-7.310

18.8

7.321

0.037

-0.084

2.3

0.092

1.10

0.041

-0.146

3.5

0.151

1.03

0.000

0.000

999.9

0.000

1BBA51

1.10

0.304

-0.994

3.3

1.040

1BBA51

1.03

0.000

0.000

999.9

0.000

Bus22

1BBA51

1.21

0.647

-7.969

12.3

7.996

Bus15

1BBA51

1.17

0.064

-0.222

3.4

0.231

1MKA76

Bus BS

100.00

0.389

-7.310

18.8

7.321

1BJA76

Bus9

7.25

0.037

-0.084

2.3

0.092

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

16.031

Ib asym
23.864

17.678

Idc

0.02

15.703

20.881

13.764

0.03

15.360

18.594

10.479

0.04

15.008

16.997

7.978

0.05

14.649

16.028

6.504

0.06

14.501

15.345

5.020

0.07

14.355

14.869

3.875

0.08

14.206

14.517

2.991

0.09

14.056

14.283

2.534

0.10

13.906

14.045

1.976

0.15

13.672

13.684

0.570

0.20

13.440

13.441

0.164

0.25

13.209

13.209

0.047

0.30

13.038

13.038

0.014

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BFA51


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
111.741
31.702

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BFA51

Total

0.00

10.201

-48.619

4.8

49.677

PCI_BUS

1BFA51

4.52

0.504

-1.997

4.0

2.060

1BJA11

1BFA51

1.66

1.970

-4.823

2.4

5.210

1BJA51

1BFA51

0.53

1.089

-2.586

2.4

2.806

1BMB20

1BMA52

1.07

0.802

-2.095

2.6

2.243

1BMB52

1BMA52

0.47

0.368

-0.870

2.4

0.944

1BNB52

1BMA52

1.45

0.029

-0.068

2.4

0.074

1BJA12

1BFA53

1.30

1.595

-3.755

2.4

4.080

Bus19

1BFA53

78.76

3.525

-31.668

9.0

31.863

1BJA80

1BFA53

100.00

0.318

-0.757

2.4

0.821

Sistema PCI

PCI_BUS

100.00

0.504

-1.997

4.0

2.060

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.770

3.2

0.807

CARGAS 1BJA11

1BJA11

100.00

1.728

-4.053

2.3

4.406

Compresor 1

1BJA51

100.00

0.057

-0.141

2.5

0.152

CARGAS 1BJA51

1BJA51

100.00

1.032

-2.445

2.4

2.654

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.775

3.2

0.812

CARGAS 1BMB20

1BMB20

100.00

0.560

-1.320

2.4

1.434

CARGAS 1BMB52

1BMB52

100.00

0.368

-0.870

2.4

0.944

CARGAS 1BNB52

1BNB52

105.26

0.035

-0.082

2.4

0.089

CARGAS 1BJA12

1BJA12

100.00

1.595

-3.755

2.4

4.080

1BBA51

Bus19

78.90

0.270

-2.423

9.0

2.438

1BMA52

1BFA51

0.00

6.637

-39.212

5.9

39.770

1BFA53

1BMA52

0.00

5.438

-36.179

6.7

36.586

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

47.777

61.138

38.147

0.02

46.760

52.772

24.463

0.03

45.612

47.842

14.435

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

(Cont.)
Falta trifsica en barra: 1BFA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
111.741
31.702

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.04

44.511

45.318

0.05

43.463

43.884

8.518
6.061

0.06

42.958

43.119

3.713

0.07

42.467

42.528

2.275

0.08

41.988

42.012

1.393

0.09

41.524

41.536

1.004

0.10

41.074

41.079

0.626

0.15

40.193

40.193

0.059

0.20

39.365

39.365

0.006

0.25

38.592

38.592

0.001

0.30

38.566

38.566

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BFA53


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
111.741
31.702

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

0.00

10.201

-48.619

4.8

kA
Magnitud

1BFA53

Total

1BJA12

1BFA53

1.30

1.595

-3.755

2.4

4.080

Bus19

1BFA53

78.76

3.525

-31.668

9.0

31.863

1BJA80

1BFA53

100.00

0.318

-0.757

2.4

0.821

1BMB20

1BMA52

1.07

0.802

-2.095

2.6

2.243

1BMB52

1BMA52

0.47

0.368

-0.870

2.4

0.944

1BNB52

1BMA52

1.45

0.029

-0.068

2.4

0.074

PCI_BUS

1BFA51

4.52

0.504

-1.997

4.0

2.060

1BJA11

1BFA51

1.66

1.970

-4.823

2.4

5.210

1BJA51

1BFA51

0.53

1.089

-2.586

2.4

2.806

CARGAS 1BJA12

1BJA12

100.00

1.595

-3.755

2.4

4.080

1BBA51

Bus19

78.90

0.270

-2.423

9.0

2.438

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.775

3.2

0.812

CARGAS 1BMB20

1BMB20

100.00

0.560

-1.320

2.4

1.434

CARGAS 1BMB52

1BMB52

100.00

0.368

-0.870

2.4

0.944

CARGAS 1BNB52

1BNB52

105.26

0.035

-0.082

2.4

0.089

Sistema PCI

PCI_BUS

100.00

0.504

-1.997

4.0

2.060

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.770

3.2

0.807

CARGAS 1BJA11

1BJA11

100.00

1.728

-4.053

2.3

4.406

Compresor 1

1BJA51

100.00

0.057

-0.141

2.5

0.152

CARGAS 1BJA51

1BJA51

100.00

1.032

-2.445

2.4

2.654

1BFA51

1BMA52

0.00

3.563

-9.407

2.6

10.059

1BMA52

1BFA53

0.00

4.762

-12.439

2.6

13.320

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

47.777

61.138

38.147

0.02

46.760

52.772

24.463

0.03

45.612

47.842

14.435

49.677

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

(Cont.)
Falta trifsica en barra: 1BFA53
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
111.741
31.702

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.04

44.511

45.318

0.05

43.463

43.884

8.518
6.061

0.06

42.958

43.119

3.713

0.07

42.467

42.528

2.275

0.08

41.988

42.012

1.393

0.09

41.524

41.536

1.004

0.10

41.074

41.079

0.626

0.15

40.193

40.193

0.059

0.20

39.365

39.365

0.006

0.25

38.592

38.592

0.001

0.30

38.566

38.566

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BJA11


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
94.635
29.226

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA11

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen
0.00

kA
Activa

kA
Imaginario

11.720

-43.306

X/R
Cociente

kA
Magnitud

3.7

44.864

1BFA51

1BJA11

12.59

9.745

-38.395

3.9

39.613

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.784

3.2

0.820

CARGAS 1BJA11

1BJA11

100.00

1.734

-4.127

2.4

4.477

PCI_BUS

1BFA51

16.59

0.559

-1.744

3.1

1.831

1BJA51

1BFA51

13.05

1.111

-2.234

2.0

2.495

1BMB20

1BMA52

13.52

0.829

-1.814

2.2

1.994

1BMB52

1BMA52

13.00

0.375

-0.751

2.0

0.839

1BNB52

1BMA52

14.47

0.029

-0.059

2.0

0.066

1BJA12

1BFA53

13.71

1.625

-3.242

2.0

3.627

Bus19

1BFA53

80.63

4.894

-27.898

5.7

28.324

1BJA80

1BFA53

100.00

0.324

-0.654

2.0

0.730

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

43.408

Ib asym
51.107

26.975

Idc

0.02

42.475

44.542

13.412

0.03

41.505

41.961

6.166

0.04

40.572

40.671

2.835

0.05

39.681

39.712

1.559

0.06

39.251

39.258

0.743

0.07

38.831

38.833

0.354

0.08

38.422

38.423

0.169

0.09

38.025

38.025

0.094

0.10

37.638

37.638

0.046

0.15

36.877

36.877

0.001

0.20

36.159

36.159

0.000

0.25

35.487

35.487

0.000

0.30

35.464

35.464

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BJA12


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
93.861
29.226

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA12

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

11.744

-43.001

X/R
Cociente

kA
Magnitud

3.7

44.576

1BFA53

1BJA12

12.86

10.144

-39.193

3.9

40.484

CARGAS 1BJA12

1BJA12

100.00

1.600

-3.808

2.4

4.131

Bus19

1BFA53

80.68

4.906

-27.809

5.7

28.238

1BJA80

1BFA53

100.00

0.324

-0.651

2.0

0.728

1BMB20

1BMA52

13.80

0.828

-1.808

2.2

1.988

1BMB52

1BMA52

13.28

0.374

-0.748

2.0

0.837

1BNB52

1BMA52

14.76

0.029

-0.058

2.0

0.065

PCI_BUS

1BFA51

16.86

0.559

-1.738

3.1

1.825

1BJA11

1BFA51

14.30

2.015

-4.155

2.1

4.617

1BJA51

1BFA51

13.33

1.109

-2.226

2.0

2.487

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

43.201

50.764

26.657

0.02

42.282

44.307

13.243

0.03

41.343

41.786

6.070

0.04

40.439

40.534

2.782

0.05

39.576

39.605

1.534

0.06

39.159

39.166

0.729

0.07

38.752

38.753

0.347

0.08

38.355

38.356

0.165

0.09

37.969

37.969

0.092

0.10

37.594

37.594

0.045

0.15

36.855

36.855

0.001

0.20

36.157

36.157

0.000

0.25

35.503

35.503

0.000

0.30

35.481

35.481

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

10

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BJA51


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
99.706
30.178

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA51

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

11.263

-44.890

X/R
Cociente

kA
Magnitud

4.0

46.282

1BFA51

1BJA51

8.29

10.173

-42.289

4.2

43.495

Compresor 1

1BJA51

100.00

0.057

-0.142

2.5

0.153

CARGAS 1BJA51

1BJA51

100.00

1.033

-2.460

2.4

2.668

PCI_BUS

1BFA51

12.47

0.542

-1.831

3.4

1.909

1BJA11

1BFA51

9.80

2.006

-4.393

2.2

4.829

1BMB20

1BMA52

9.27

0.822

-1.910

2.3

2.079

1BMB52

1BMA52

8.72

0.373

-0.792

2.1

0.875

1BNB52

1BMA52

10.01

0.029

-0.062

2.1

0.068

1BJA12

1BFA53

9.47

1.619

-3.418

2.1

3.782

Bus19

1BFA53

79.99

4.458

-29.196

6.5

29.534

1BJA80

1BFA53

100.00

0.323

-0.689

2.1

0.761

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

44.772

Ib asym
54.082

30.337

Idc

0.02

43.809

46.850

16.604

0.03

42.823

43.632

8.363

0.04

41.874

42.085

4.212

0.05

40.967

41.047

2.563

0.06

40.529

40.552

1.341

0.07

40.102

40.108

0.701

0.08

39.685

39.687

0.367

0.09

39.279

39.280

0.226

0.10

38.885

38.885

0.121

0.15

38.109

38.109

0.005

0.20

37.377

37.377

0.000

0.25

36.691

36.691

0.000

0.30

36.669

36.669

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

11

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BJA76


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
27.361
15.044

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA76

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen
0.00

kA
Activa

kA
Imaginario

8.418

-13.999

X/R
Cociente

kA
Magnitud

1.7

16.335

Bus9

1BJA76

91.09

7.943

-12.867

1.6

15.121

CARGAS 1BJA76

1BJA76

100.00

0.476

-1.132

2.4

1.228

1BBA76

Bus9

91.16

0.593

-0.961

1.6

1.129

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

16.158

16.348

2.480

0.02

16.066

16.068

0.273

0.03

15.974

15.974

0.030

0.04

15.883

15.883

0.003

0.05

15.794

15.794

0.000

0.06

15.751

15.751

0.000

0.07

15.707

15.707

0.000

0.08

15.664

15.664

0.000

0.09

15.622

15.622

0.000

0.10

15.580

15.580

0.000

0.15

15.498

15.498

0.000

0.20

15.418

15.418

0.000

0.25

15.342

15.342

0.000

0.30

15.340

15.340

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

12

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BMA52


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
111.741
31.702

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BMA52

Total

0.00

10.201

-48.619

4.8

49.677

1BMB20

1BMA52

1.07

0.802

-2.095

2.6

2.243

1BMB52

1BMA52

0.47

0.368

-0.870

2.4

0.944

1BNB52

1BMA52

1.45

0.029

-0.068

2.4

0.074

1BJA12

1BFA53

1.30

1.595

-3.755

2.4

4.080

Bus19

1BFA53

78.76

3.525

-31.668

9.0

31.863

1BJA80

1BFA53

100.00

0.318

-0.757

2.4

0.821

PCI_BUS

1BFA51

4.52

0.504

-1.997

4.0

2.060

1BJA11

1BFA51

1.66

1.970

-4.823

2.4

5.210

1BJA51

1BFA51

0.53

1.089

-2.586

2.4

2.806

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.775

3.2

0.812

CARGAS 1BMB20

1BMB20

100.00

0.560

-1.320

2.4

1.434

CARGAS 1BMB52

1BMB52

100.00

0.368

-0.870

2.4

0.944

CARGAS 1BNB52

1BNB52

105.26

0.035

-0.082

2.4

0.089

CARGAS 1BJA12

1BJA12

100.00

1.595

-3.755

2.4

4.080

1BBA51

Bus19

78.90

0.270

-2.423

9.0

2.438

Sistema PCI

PCI_BUS

100.00

0.504

-1.997

4.0

2.060

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.770

3.2

0.807

CARGAS 1BJA11

1BJA11

100.00

1.728

-4.053

2.3

4.406

Compresor 1

1BJA51

100.00

0.057

-0.141

2.5

0.152

CARGAS 1BJA51

1BJA51

100.00

1.032

-2.445

2.4

2.654

1BFA51

1BMA52

0.00

3.563

-9.407

2.6

10.059

1BFA53

1BMA52

0.00

5.438

-36.179

6.7

36.586

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

47.777

61.138

38.147

0.02

46.760

52.772

24.463

0.03

45.612

47.842

14.435

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

13

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

(Cont.)
Falta trifsica en barra: 1BMA52
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
111.741
31.702

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.04

44.511

45.318

0.05

43.463

43.884

8.518
6.061

0.06

42.958

43.119

3.713

0.07

42.467

42.528

2.275

0.08

41.988

42.012

1.393

0.09

41.524

41.536

1.004

0.10

41.074

41.079

0.626

0.15

40.193

40.193

0.059

0.20

39.365

39.365

0.006

0.25

38.592

38.592

0.001

0.30

38.566

38.566

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

14

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BMB20


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
85.499
28.103

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BMB20

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

12.126

-39.926

X/R
Cociente

kA
Magnitud

3.3

41.727

1BMA52

1BMB20

18.81

11.324

-37.807

3.3

39.466

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.784

3.2

0.820

CARGAS 1BMB20

1BMB20

100.00

0.561

-1.336

2.4

1.449

1BMB52

1BMA52

19.20

0.371

-0.692

1.9

0.785

1BNB52

1BMA52

20.94

0.029

-0.054

1.9

0.061

1BJA12

1BFA53

19.87

1.607

-2.988

1.9

3.392

Bus19

1BFA53

81.61

5.330

-25.953

4.9

26.494

1BJA80

1BFA53

100.00

0.321

-0.602

1.9

0.683

PCI_BUS

1BFA51

22.56

0.569

-1.615

2.8

1.713

1BJA11

1BFA51

20.16

1.998

-3.844

1.9

4.332

1BJA51

1BFA51

19.24

1.099

-2.059

1.9

2.333

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

40.464

Ib asym
46.220

22.339

Idc

0.02

39.694

40.925

9.959

0.03

38.906

39.120

4.091

0.04

38.144

38.181

1.681

0.05

37.414

37.424

0.832

0.06

37.060

37.062

0.355

0.07

36.714

36.714

0.151

0.08

36.376

36.376

0.065

0.09

36.046

36.046

0.032

0.10

35.725

35.725

0.014

0.15

35.092

35.092

0.000

0.20

34.492

34.492

0.000

0.25

33.928

33.928

0.000

0.30

33.913

33.913

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

15

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BMB52


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
82.601
28.515

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BMB52

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

13.991

-39.528

X/R
Cociente

kA
Magnitud

2.8

41.931

1BMA52

1BMB52

20.21

13.624

-38.654

2.8

40.984

CARGAS 1BMB52

1BMB52

100.00

0.367

-0.874

2.4

0.948

1BMB20

1BMA52

21.05

0.907

-1.654

1.8

1.886

1BNB52

1BMA52

22.32

0.032

-0.053

1.7

0.062

1BJA12

1BFA53

21.21

1.756

-2.946

1.7

3.430

Bus19

1BFA53

81.57

6.540

-25.976

4.0

26.787

1BJA80

1BFA53

100.00

0.351

-0.594

1.7

0.690

PCI_BUS

1BFA51

23.89

0.647

-1.606

2.5

1.732

1BJA11

1BFA51

21.49

2.190

-3.793

1.7

4.380

1BJA51

1BFA51

20.62

1.202

-2.030

1.7

2.359

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

40.782

44.993

19.005

0.02

40.062

40.729

7.339

0.03

39.322

39.407

2.582

0.04

38.608

38.619

0.908

0.05

37.924

37.926

0.396

0.06

37.592

37.593

0.145

0.07

37.268

37.268

0.053

0.08

36.952

36.952

0.020

0.09

36.643

36.643

0.009

0.10

36.342

36.342

0.003

0.15

35.748

35.748

0.000

0.20

35.186

35.186

0.000

0.25

34.659

34.659

0.000

0.30

34.644

34.644

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

16

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: 1BNB52


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.380
1.05
9.416
5.310

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

1BNB52

Total

1BMA52
CARGAS 1BNB52

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

2.945

-4.814

1.6

5.644

1BNB52

86.27

2.912

-4.736

1.6

5.559

1BNB52

100.00

0.033

-0.079

2.4

0.085

1BMB20

1BMA52

86.37

0.137

-0.159

1.2

0.210

1BMB52

1BMA52

86.31

0.060

-0.065

1.1

0.088

1BJA12

1BFA53

86.39

0.259

-0.280

1.1

0.381

Bus19

1BFA53

88.88

1.310

-2.672

2.0

2.976

1BJA80

1BFA53

95.00

0.052

-0.056

1.1

0.077

PCI_BUS

1BFA51

86.69

0.107

-0.160

1.5

0.192

1BJA11

1BFA51

86.42

0.325

-0.362

1.1

0.487

1BJA51

1BFA51

86.32

0.177

-0.193

1.1

0.262

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

5.644

5.705

0.831

0.02

5.644

5.644

0.091

0.03

5.644

5.644

0.010

0.04

5.644

5.644

0.001

0.05

5.644

5.644

0.000

0.06

5.644

5.644

0.000

0.07

5.644

5.644

0.000

0.08

5.644

5.644

0.000

0.09

5.644

5.644

0.000

0.10

5.644

5.644

0.000

0.15

5.644

5.644

0.000

0.20

5.644

5.644

0.000

0.25

5.644

5.644

0.000

0.30

5.644

5.644

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

17

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: Bus EX


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
81.675
34.912

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Bus EX

Total

Bus20
1BBA51

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

5.513

-34.947

6.3

35.380

Bus EX

91.39

5.513

-34.947

6.3

35.380

Bus20

91.69

0.376

-2.383

6.3

2.412

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

35.380

Ib asym
44.987

27.787

Idc

0.02

35.380

38.646

15.550

0.03

35.380

36.426

8.669

0.04

35.380

35.708

4.833

0.05

35.380

35.484

2.725

0.06

35.380

35.412

1.523

0.07

35.380

35.390

0.851

0.08

35.380

35.383

0.475

0.09

35.380

35.381

0.270

0.10

35.380

35.380

0.151

0.15

35.380

35.380

0.008

0.20

35.380

35.380

0.000

0.25

35.380

35.380

0.000

0.30

35.380

35.380

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

18

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: BUS GEN


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

18.000
1.10
281.154
63.797

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

BUS GEN

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

3.765

-104.513

X/R
Cociente

kA
Magnitud

27.8

104.581
44.531

S.E. Etn

BUS GEN

50.48

3.186

-44.417

13.9

Bus22

BUS GEN

49.93

0.143

-1.621

11.4

1.628

1MKA10

BUS GEN

100.00

0.436

-58.475

134.0

58.476

S.E. Reque

S.E. Etn

54.18

0.261

-3.634

13.9

3.643

1BBA51

Bus22

52.31

0.382

-4.335

11.4

4.352

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

99.810

163.644

129.681

0.02

97.992

151.550

115.607

0.03

96.037

140.250

102.210

0.04

93.962

130.364

90.365

0.05

91.781

125.823

86.069

0.06

90.956

119.325

77.236

0.07

90.114

113.686

69.310

0.08

89.258

108.791

62.198

0.09

88.394

112.517

69.618

0.10

87.511

108.433

64.027

0.15

86.158

95.905

42.127

0.20

84.766

89.183

27.718

0.25

83.348

85.320

18.237

0.30

81.917

82.791

11.999

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

19

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: S.E. Etn


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

220.000
1.10
25.637
10.247

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin

Tensin y Corriente Inicial Simtrica (rms)

Barra Origen
ID

Barra Destino
ID

S.E. Etn

Total

S.E. Reque
BUS GEN
Red elctrica Peruana
Bus22
1MKA10

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

0.935

-10.209

S.E. Etn

7.47

0.892

S.E. Etn

40.52

0.043

S.E. Reque

100.00

0.892

BUS GEN

69.22

0.090

BUS GEN

100.00

0.437

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

10.169

14.558

10.418

0.02

10.142

12.884

7.946

0.03

10.110

11.696

5.882

0.04

10.073

10.974

4.355

0.05

10.032

10.852

4.139

0.06

10.019

10.524

3.221

0.07

10.006

10.315

2.507

0.08

9.992

10.181

1.951

0.09

9.978

10.382

2.870

0.10

9.963

10.247

2.397

0.15

9.936

9.984

0.975

0.20

9.907

9.914

0.396

0.25

9.874

9.875

0.161

0.30

9.839

9.840

0.066

X/R
Cociente

kA
Magnitud

10.9

10.251

-7.284

8.2

7.339

-2.925

67.9

2.925

-7.284

8.2

7.339

-0.964

10.7

0.968

-34.780

79.6

34.783

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

20

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-1


Eten

Falta trifsica en barra: S.E. Reque


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

220.000
1.10
26.744
10.755

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin

Tensin y Corriente Inicial Simtrica (rms)

Barra Origen
ID

Barra Destino
ID

S.E. Reque

Total

S.E. Etn
Red elctrica Peruana
BUS GEN

S.E. Etn

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

1.032

-10.710

10.4

10.759

S.E. Reque

2.89

0.048

-2.840

59.1

2.840

S.E. Reque

100.00

0.984

-7.869

8.0

7.931

42.24

0.048

-2.840

59.1

2.840

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

10.685

15.148

10.738

0.02

10.660

13.353

8.042

0.03

10.631

12.133

5.846

0.04

10.598

11.419

4.250

0.05

10.561

11.283

3.970

0.06

10.550

10.978

3.035

0.07

10.538

10.790

2.320

0.08

10.526

10.674

1.773

0.09

10.513

10.826

2.584

0.10

10.499

10.712

2.122

0.15

10.475

10.505

0.792

0.20

10.448

10.452

0.296

0.25

10.418

10.419

0.111

0.30

10.386

10.387

0.041

One-Line Diagram - OLV1 (Short-Circuit Analysis)


Red elctrica Peruana
220 kV
3022 MVAsc

RESERVA FRA ETEN

S.E. Reque
220 kV

7,93
10,7

2,81
AL

ESTUDIO DE CORTOCIRCUITO: CASO SC-2 (REV C)

kA

CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL OPERANDO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA OPERANDO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus

S.E. Etn
220 kV

7,34

10,2

2,9

kA

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
BUS GEN
18 kV

103,

44,53

6 kA

58,48

,619
Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Dyn11
Isolated Phase CU
35 m

18 kV
9021 A
1MKA10
225 MW
17 %Xd"

CU
1BBA51
6,6 kV

10,1

kA

40 m
4-3/C 240

8,07

,092

1,54

,153

,233

Open
CU
1BBA76
6,6 kV

120 m
3-3/C 300

CU

9,89

10,0

40 m
1-3/C 150

CU

Open

40 m
3-3/C 240

,092

20 m
1-3/C 300

CU

20 m
3-3/C 300

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z
6,6 kV
922,9 A
1BJA76
0,48 kV

70 m
1-3/C 70

CU

CU

100 m
1-3/C 70

100 m
1-3/C 70
CU

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

CU

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

Dyn11

50 m
1-3/C 70

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

40 m
2-3/C 185

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

CU

50 m
1-3/C 70

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

1MKA76
8,44 MW
16 %Xd"

14,46
1,23

70 m
1-3/C 70

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

Open
CU

CU
CU

kA

Open

15,7

kA

Excitacin 1MKC10
944 kVA
1BFA53
0,48 kV

62,4

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

88WN-1
224 kW

kA

1BMA52
0,48 kV

27,83
4,08

,821

29,88

62,4

32,56

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW
62,4

Open
kA

16,86

,944

,074

2,24

10,06

52,56

5,21

kA

1BFA51
0,48 kV

2,81

2,06

CARGAS 1BJA76
270 kVA
CU

W-1BJA12

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

40,62

0,48 kV

W-1BMB52

50 m
6-3/C 300

58,0

17,61

kA

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z
1BNB52
0,38 kV

page 1

10:02:18

may 02, 2014

Project File: Eten

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

5,67
,085

5,8
kA

0,48 kV
3007 A
1XKA52
2000 kW

W-1BMB20

CARGAS 1BNB52
82,2 kVA

Sistema PCI
200 kW

One-Line Diagram - OLV1 (Short-Circuit Analysis)

1BMA52

CU

1BMB20
0,48 kV

50 m
4-3/C 240

CU

50,2

47,97
1,45

1BFA51

1BFA53

1BJA12
0,48 kV

kA

,82

50 m
6-3/C 240

50,26

CU

54,4

1BJA11
0,48 kV

kA

4,13

4,48

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

50,7

kA

1BFA51

20 m
2-3/C 150

49,7

CU

1BMB52
0,48 kV
,948

1BJA51
0,48 kV

20 m
4-3/C 240

54,3
2,67

57,1

,153

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

10:02:18

may 02, 2014

Project File: Eten

49,45

54,7

kA

,82

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

kA

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Informe de Cortocircuito
Falta trifsica en barra: 1BBA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

6.600
1.10
24.995
9.060

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BBA51

Total

0.00

1.034

-10.019

9.7

10.072

1BBA76

1BBA51

0.01

0.037

-0.084

2.3

0.092

Bus17

1BBA51

0.07

0.041

-0.147

3.6

0.153

Bus18

1BBA51

0.00

0.000

0.000

999.9

0.000

Bus19

1BBA51

0.10

0.273

-1.515

5.5

1.539

Bus20

1BBA51

0.00

0.000

0.000

999.9

0.000

Bus22

1BBA51

0.23

0.619

-8.048

13.0

8.072

Bus15

1BBA51

0.15

0.064

-0.224

3.5

0.233

Bus9

1BBA76

0.02

0.037

-0.084

2.3

0.092

Bus10

Bus17

14.61

0.041

-0.147

3.6

0.153

1BFA53

Bus19

50.03

0.273

-1.515

5.5

1.539

Bus EX

Bus20

0.00

0.000

0.000

999.9

0.000

BUS GEN

Bus22

95.11

0.619

-8.048

13.0

8.072

Bus13

Bus15

23.23

0.064

-0.224

3.5

0.233

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

9.985

Ib asym
14.203

10.101

Idc

0.02

9.924

12.443

7.505

0.03

9.862

11.267

5.448

0.04

9.799

10.567

3.955

0.05

9.737

10.202

3.043

0.06

9.709

9.962

2.235

0.07

9.680

9.818

1.642

0.08

9.675

9.750

1.206

0.09

9.660

9.706

0.941

0.10

9.635

9.660

0.696

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BBA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

6.600
1.10
24.995
9.060

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.15

9.585

9.586

0.154

0.20

9.536

9.536

0.034

0.25

9.488

9.488

0.008

0.30

9.481

9.481

0.002

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BBA76


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

6.600
1.10
24.610
8.979

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BBA76

Total

0.00

1.069

-9.916

9.3

9.973

1BBA51

1BBA76

1.09

1.032

-9.832

9.5

9.886

Bus9

1BBA76

0.01

0.037

-0.084

2.3

0.092

Bus17

1BBA51

1.15

0.042

-0.146

3.5

0.151

Bus18

1BBA51

1.09

0.000

0.000

999.9

0.000

Bus19

1BBA51

1.19

0.277

-1.499

5.4

1.524

Bus20

1BBA51

1.09

0.000

0.000

999.9

0.000

Bus22

1BBA51

1.27

0.649

-7.966

12.3

7.992

Bus15

1BBA51

1.23

0.065

-0.222

3.4

0.231

1BJA76

Bus9

7.25

0.037

-0.084

2.3

0.092

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

9.889

Ib asym
13.945

9.832

Idc

0.02

9.829

12.174

7.183

0.03

9.768

11.031

5.126

0.04

9.707

10.373

3.659

0.05

9.646

10.036

2.769

0.06

9.618

9.824

1.999

0.07

9.590

9.698

1.444

0.08

9.595

9.652

1.042

0.09

9.570

9.604

0.801

0.10

9.546

9.564

0.582

0.15

9.497

9.498

0.118

0.20

9.449

9.449

0.024

0.25

9.402

9.402

0.005

0.30

9.395

9.395

0.001

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BFA51


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
144.677
44.263

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BFA51

Total

0.00

11.068

-61.428

5.6

62.417

PCI_BUS

1BFA51

4.52

0.504

-1.997

4.0

2.060

1BJA11

1BFA51

1.66

1.970

-4.823

2.4

5.210

1BJA51

1BFA51

0.53

1.089

-2.586

2.4

2.806

1BMB20

1BMA52

1.07

0.802

-2.095

2.6

2.243

1BMB52

1BMA52

0.47

0.368

-0.870

2.4

0.944

CGDE

1BMA52

4.93

1.327

-16.812

12.7

16.864

1BNB52

1BMA52

1.45

0.029

-0.068

2.4

0.074

1BJA12

1BFA53

1.30

1.595

-3.755

2.4

4.080

Bus19

1BFA53

68.80

3.065

-27.665

9.0

27.834

1BJA80

1BFA53

100.00

0.318

-0.757

2.4

0.821

Sistema PCI

PCI_BUS

100.00

0.504

-1.997

4.0

2.060

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.770

3.2

0.807

CARGAS 1BJA11

1BJA11

100.00

1.728

-4.053

2.3

4.406

Compresor 1

1BJA51

100.00

0.057

-0.141

2.5

0.152

CARGAS 1BJA51

1BJA51

100.00

1.032

-2.445

2.4

2.654

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.775

3.2

0.812

CARGAS 1BMB20

1BMB20

100.00

0.560

-1.320

2.4

1.434

CARGAS 1BMB52

1BMB52

100.00

0.368

-0.870

2.4

0.944

1XKA52

CGDE

100.00

1.327

-16.812

12.7

16.864

CARGAS 1BNB52

1BNB52

105.26

0.035

-0.082

2.4

0.089

CARGAS 1BJA12

1BJA12

100.00

1.595

-3.755

2.4

4.080

1BBA51

Bus19

68.92

0.235

-2.117

9.0

2.130

1BMA52

1BFA51

0.00

7.504

-52.022

6.9

52.560

1BFA53

1BMA52

0.00

4.978

-32.177

6.5

32.560

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

59.457

Ib asym
79.453

Idc
52.702

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BFA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
144.677
44.263

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.02

58.048

68.551

36.466

0.03

56.471

61.141

23.438

0.04

54.903

56.932

15.064

0.05

53.357

54.589

11.531

0.06

52.670

53.227

7.675

0.07

51.992

52.242

5.109

0.08

51.323

51.435

3.400

0.09

50.663

50.733

2.678

0.10

50.012

50.045

1.816

0.15

48.811

48.812

0.261

0.20

47.647

47.647

0.037

0.25

46.526

46.526

0.005

0.30

46.141

46.141

0.001

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BFA53


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
144.677
44.263

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

0.00

11.068

-61.428

5.6

kA
Magnitud

1BFA53

Total

62.417

1BJA12

1BFA53

1.30

1.595

-3.755

2.4

4.080

Bus19

1BFA53

68.80

3.065

-27.665

9.0

27.834

1BJA80

1BFA53

100.00

0.318

-0.757

2.4

0.821

1BMB20

1BMA52

1.07

0.802

-2.095

2.6

2.243

1BMB52

1BMA52

0.47

0.368

-0.870

2.4

0.944

CGDE

1BMA52

4.93

1.327

-16.812

12.7

16.864

1BNB52

1BMA52

1.45

0.029

-0.068

2.4

0.074

PCI_BUS

1BFA51

4.52

0.504

-1.997

4.0

2.060

1BJA11

1BFA51

1.66

1.970

-4.823

2.4

5.210

1BJA51

1BFA51

0.53

1.089

-2.586

2.4

2.806

CARGAS 1BJA12

1BJA12

100.00

1.595

-3.755

2.4

4.080

1BBA51

Bus19

68.92

0.235

-2.117

9.0

2.130

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.775

3.2

0.812

CARGAS 1BMB20

1BMB20

100.00

0.560

-1.320

2.4

1.434

CARGAS 1BMB52

1BMB52

100.00

0.368

-0.870

2.4

0.944

1XKA52

CGDE

100.00

1.327

-16.812

12.7

16.864

CARGAS 1BNB52

1BNB52

105.26

0.035

-0.082

2.4

0.089

Sistema PCI

PCI_BUS

100.00

0.504

-1.997

4.0

2.060

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.770

3.2

0.807

CARGAS 1BJA11

1BJA11

100.00

1.728

-4.053

2.3

4.406

Compresor 1

1BJA51

100.00

0.057

-0.141

2.5

0.152

CARGAS 1BJA51

1BJA51

100.00

1.032

-2.445

2.4

2.654

1BFA51

1BMA52

0.00

3.563

-9.407

2.6

10.059

1BMA52

1BFA53

0.00

6.089

-29.251

4.8

29.878

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

59.457

Ib asym
79.453

Idc
52.702

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BFA53
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
144.677
44.263

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.02

58.048

68.551

36.466

0.03

56.471

61.141

23.438

0.04

54.903

56.932

15.064

0.05

53.357

54.589

11.531

0.06

52.670

53.227

7.675

0.07

51.992

52.242

5.109

0.08

51.323

51.435

3.400

0.09

50.663

50.733

2.678

0.10

50.012

50.045

1.816

0.15

48.811

48.812

0.261

0.20

47.647

47.647

0.037

0.25

46.526

46.526

0.005

0.30

46.141

46.141

0.001

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BJA11


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
116.227
39.589

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA11

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

13.795

-52.929

X/R
Cociente

kA
Magnitud

3.8

54.697

1BFA51

1BJA11

15.71

11.820

-48.018

4.1

49.452

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.784

3.2

0.820

CARGAS 1BJA11

1BJA11

100.00

1.734

-4.127

2.4

4.477

PCI_BUS

1BFA51

19.59

0.575

-1.681

2.9

1.777

1BJA51

1BFA51

16.16

1.119

-2.146

1.9

2.421

1BMB20

1BMA52

16.62

0.838

-1.744

2.1

1.935

1BMB52

1BMA52

16.11

0.378

-0.722

1.9

0.815

CGDE

1BMA52

19.97

2.328

-14.359

6.2

14.546

1BNB52

1BMA52

17.71

0.030

-0.056

1.9

0.064

1BJA12

1BFA53

16.80

1.637

-3.115

1.9

3.519

Bus19

1BFA53

72.55

4.589

-23.566

5.1

24.009

1BJA80

1BFA53

100.00

0.327

-0.628

1.9

0.708

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

52.636

62.457

33.621

0.02

51.505

54.180

16.815

0.03

50.305

50.913

7.840

0.04

49.111

49.247

3.655

0.05

47.931

47.974

2.027

0.06

47.406

47.416

0.978

0.07

46.887

46.889

0.472

0.08

46.374

46.375

0.228

0.09

45.869

45.869

0.131

0.10

45.370

45.370

0.064

0.15

44.425

44.425

0.002

0.20

43.505

43.505

0.000

0.25

42.617

42.617

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BJA11
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
116.227
39.589

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.30

42.342

Ib asym
42.342

Idc
0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

10

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BJA12


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
115.299
39.589

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA12

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

13.824

-52.563

X/R
Cociente

kA
Magnitud

3.8

54.350

1BFA53

1BJA12

15.97

12.224

-48.754

4.0

50.264

CARGAS 1BJA12

1BJA12

100.00

1.600

-3.808

2.4

4.131

Bus19

1BFA53

72.62

4.596

-23.492

5.1

23.938

1BJA80

1BFA53

100.00

0.326

-0.626

1.9

0.706

1BMB20

1BMA52

16.87

0.837

-1.738

2.1

1.929

1BMB52

1BMA52

16.37

0.377

-0.719

1.9

0.812

CGDE

1BMA52

20.21

2.334

-14.314

6.1

14.503

1BNB52

1BMA52

17.98

0.029

-0.056

1.9

0.063

PCI_BUS

1BFA51

19.84

0.574

-1.676

2.9

1.771

1BJA11

1BFA51

17.36

2.032

-3.993

2.0

4.481

1BJA51

1BFA51

16.42

1.118

-2.139

1.9

2.413

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

52.389

Ib asym
62.049

33.249

Idc

0.02

51.275

53.904

16.626

0.03

50.113

50.706

7.733

0.04

48.955

49.087

3.596

0.05

47.809

47.851

2.000

0.06

47.301

47.311

0.964

0.07

46.798

46.800

0.465

0.08

46.300

46.301

0.224

0.09

45.809

45.810

0.129

0.10

45.325

45.325

0.064

0.15

44.407

44.407

0.002

0.20

43.513

43.513

0.000

0.25

42.648

42.648

0.000

0.30

42.375

42.375

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

11

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BJA51


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
124.789
41.360

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA51

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

13.004

-55.576

X/R
Cociente

kA
Magnitud

4.3

57.077

1BFA51

1BJA51

10.35

11.913

-52.975

4.4

54.298

Compresor 1

1BJA51

100.00

0.057

-0.142

2.5

0.153

CARGAS 1BJA51

1BJA51

100.00

1.033

-2.460

2.4

2.668

PCI_BUS

1BFA51

14.45

0.555

-1.790

3.2

1.874

1BJA11

1BFA51

11.83

2.023

-4.287

2.1

4.740

1BMB20

1BMA52

11.31

0.830

-1.864

2.2

2.041

1BMB52

1BMA52

10.77

0.376

-0.772

2.1

0.859

CGDE

1BMA52

14.84

2.019

-15.209

7.5

15.343

1BNB52

1BMA52

12.14

0.029

-0.060

2.1

0.067

1BJA12

1BFA53

11.50

1.631

-3.334

2.0

3.712

Bus19

1BFA53

71.24

4.124

-24.985

6.1

25.323

1BJA80

1BFA53

100.00

0.326

-0.672

2.1

0.747

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

54.829

67.438

39.264

0.02

53.614

58.019

22.176

0.03

52.343

53.618

11.624

0.04

51.075

51.437

6.092

0.05

49.820

49.967

3.828

0.06

49.263

49.307

2.080

0.07

48.711

48.724

1.131

0.08

48.166

48.170

0.614

0.09

47.627

47.629

0.399

0.10

47.096

47.097

0.221

0.15

46.097

46.097

0.012

0.20

45.124

45.124

0.001

0.25

44.183

44.183

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

12

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BJA51
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
124.789
41.360

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.30

43.874

Ib asym
43.874

Idc
0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

13

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BJA76


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
26.532
14.320

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BJA76

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen
0.00

kA
Activa

kA
Imaginario

7.826

-13.581

X/R
Cociente

kA
Magnitud

1.7

15.674

Bus9

1BJA76

87.09

7.351

-12.449

1.7

14.457

CARGAS 1BJA76

1BJA76

100.00

0.476

-1.132

2.4

1.228

1BBA76

Bus9

87.15

0.549

-0.929

1.7

1.079

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

15.498

15.716

2.609

0.02

15.406

15.410

0.315

0.03

15.315

15.315

0.038

0.04

15.225

15.225

0.004

0.05

15.136

15.136

0.001

0.06

15.093

15.093

0.000

0.07

15.050

15.050

0.000

0.08

15.007

15.007

0.000

0.09

14.965

14.965

0.000

0.10

14.923

14.923

0.000

0.15

14.842

14.842

0.000

0.20

14.762

14.762

0.000

0.25

14.686

14.686

0.000

0.30

14.685

14.685

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

14

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BMA52


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
144.677
44.263

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

1BMA52

Total

0.00

11.068

-61.428

5.6

62.417

1BMB20

1BMA52

1.07

0.802

-2.095

2.6

2.243

1BMB52

1BMA52

0.47

0.368

-0.870

2.4

0.944

CGDE

1BMA52

4.93

1.327

-16.812

12.7

16.864

1BNB52

1BMA52

1.45

0.029

-0.068

2.4

0.074

1BJA12

1BFA53

1.30

1.595

-3.755

2.4

4.080

Bus19

1BFA53

68.80

3.065

-27.665

9.0

27.834

1BJA80

1BFA53

100.00

0.318

-0.757

2.4

0.821

PCI_BUS

1BFA51

4.52

0.504

-1.997

4.0

2.060

1BJA11

1BFA51

1.66

1.970

-4.823

2.4

5.210

1BJA51

1BFA51

0.53

1.089

-2.586

2.4

2.806

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.775

3.2

0.812

CARGAS 1BMB20

1BMB20

100.00

0.560

-1.320

2.4

1.434

CARGAS 1BMB52

1BMB52

100.00

0.368

-0.870

2.4

0.944

1XKA52

CGDE

100.00

1.327

-16.812

12.7

16.864

CARGAS 1BNB52

1BNB52

105.26

0.035

-0.082

2.4

0.089

CARGAS 1BJA12

1BJA12

100.00

1.595

-3.755

2.4

4.080

1BBA51

Bus19

68.92

0.235

-2.117

9.0

2.130

Sistema PCI

PCI_BUS

100.00

0.504

-1.997

4.0

2.060

1MBV10AP002-M1

1BJA11

104.35

0.242

-0.770

3.2

0.807

CARGAS 1BJA11

1BJA11

100.00

1.728

-4.053

2.3

4.406

Compresor 1

1BJA51

100.00

0.057

-0.141

2.5

0.152

CARGAS 1BJA51

1BJA51

100.00

1.032

-2.445

2.4

2.654

1BFA51

1BMA52

0.00

3.563

-9.407

2.6

10.059

1BFA53

1BMA52

0.00

4.978

-32.177

6.5

32.560

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

59.457

Ib asym
79.453

Idc
52.702

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

15

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BMA52
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
144.677
44.263

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.02

58.048

68.551

36.466

0.03

56.471

61.141

23.438

0.04

54.903

56.932

15.064

0.05

53.357

54.589

11.531

0.06

52.670

53.227

7.675

0.07

51.992

52.242

5.109

0.08

51.323

51.435

3.400

0.09

50.663

50.733

2.678

0.10

50.012

50.045

1.816

0.15

48.811

48.812

0.261

0.20

47.647

47.647

0.037

0.25

46.526

46.526

0.005

0.30

46.141

46.141

0.001

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

16

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BMB20


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
103.029
37.545

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BMB20

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

14.447

-48.108

X/R
Cociente

kA
Magnitud

3.3

50.230

1BMA52

1BMB20

22.86

13.644

-45.989

3.4

47.970

1MBV10AP001-M01

1BMB20

104.35

0.242

-0.784

3.2

0.820

CARGAS 1BMB20

1BMB20

100.00

0.561

-1.336

2.4

1.449

1BMB52

1BMA52

23.23

0.372

-0.654

1.8

0.752

CGDE

1BMA52

26.79

2.615

-13.178

5.0

13.435

1BNB52

1BMA52

25.15

0.029

-0.051

1.8

0.059

1BJA12

1BFA53

23.87

1.612

-2.822

1.8

3.250

Bus19

1BFA53

74.38

5.000

-21.603

4.3

22.174

1BJA80

1BFA53

100.00

0.322

-0.569

1.8

0.654

PCI_BUS

1BFA51

26.45

0.585

-1.533

2.6

1.641

1BJA11

1BFA51

24.15

2.008

-3.633

1.8

4.151

1BJA51

1BFA51

23.28

1.102

-1.945

1.8

2.236

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

48.529

55.451

26.828

0.02

47.642

49.068

11.746

0.03

46.710

46.954

4.776

0.04

45.777

45.818

1.942

0.05

44.849

44.859

0.948

0.06

44.439

44.440

0.400

0.07

44.031

44.031

0.169

0.08

43.628

43.628

0.071

0.09

43.228

43.228

0.036

0.10

42.834

42.834

0.016

0.15

42.081

42.081

0.000

0.20

41.343

41.343

0.000

0.25

40.626

40.626

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

17

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

(Cont.)
Falta trifsica en barra: 1BMB20
Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
103.029
37.545

(Definido por el Usuario)


kA Mtodo C
kA rms

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.30

40.405

Ib asym
40.405

Idc
0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

18

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BMB52


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
99.126
38.255

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
1BMB52

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

17.173

-47.650

X/R
Cociente

kA
Magnitud

2.8

50.651

1BMA52

1BMB52

24.51

16.806

-46.776

2.8

49.704

CARGAS 1BMB52

1BMB52

100.00

0.367

-0.874

2.4

0.948

1BMB20

1BMA52

25.30

0.926

-1.559

1.7

1.813

CGDE

1BMA52

28.41

3.356

-13.211

3.9

13.630

1BNB52

1BMA52

26.79

0.032

-0.050

1.6

0.060

1BJA12

1BFA53

25.46

1.784

-2.773

1.6

3.297

Bus19

1BFA53

74.31

6.226

-21.618

3.5

22.497

1BJA80

1BFA53

100.00

0.357

-0.559

1.6

0.663

PCI_BUS

1BFA51

28.02

0.675

-1.522

2.3

1.665

1BJA11

1BFA51

25.73

2.229

-3.573

1.6

4.211

1BJA51

1BFA51

24.90

1.221

-1.911

1.6

2.268

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

49.063

Ib asym
53.820

22.123

Idc

0.02

48.226

48.905

8.124

0.03

47.344

47.422

2.736

0.04

46.458

46.467

0.921

0.05

45.576

45.578

0.385

0.06

45.188

45.189

0.135

0.07

44.803

44.803

0.048

0.08

44.422

44.422

0.017

0.09

44.044

44.044

0.007

0.10

43.671

43.671

0.003

0.15

42.960

42.960

0.000

0.20

42.262

42.262

0.000

0.25

41.584

41.584

0.000

0.30

41.360

41.360

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

19

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: 1BNB52


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.380
1.05
9.572
5.523

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

1BNB52

Total

1BMA52
CARGAS 1BNB52

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

3.027

-4.895

1.6

5.755

1BNB52

88.00

2.994

-4.816

1.6

5.671

1BNB52

100.00

0.033

-0.079

2.4

0.085

1BMB20

1BMA52

88.08

0.115

-0.125

1.1

0.170

1BMB52

1BMA52

88.04

0.050

-0.051

1.0

0.072

CGDE

1BMA52

88.37

0.564

-1.147

2.0

1.278

1BJA12

1BFA53

88.10

0.217

-0.220

1.0

0.309

Bus19

1BFA53

88.46

0.990

-1.863

1.9

2.110

1BJA80

1BFA53

95.00

0.044

-0.044

1.0

0.062

PCI_BUS

1BFA51

88.34

0.091

-0.127

1.4

0.156

1BJA11

1BFA51

88.13

0.274

-0.285

1.0

0.395

1BJA51

1BFA51

88.04

0.149

-0.152

1.0

0.213

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

5.755

Ib asym
5.813

0.821

Idc

0.02

5.755

5.756

0.086

0.03

5.755

5.755

0.009

0.04

5.755

5.755

0.001

0.05

5.755

5.755

0.000

0.06

5.755

5.755

0.000

0.07

5.755

5.755

0.000

0.08

5.755

5.755

0.000

0.09

5.755

5.755

0.000

0.10

5.755

5.755

0.000

0.15

5.755

5.755

0.000

0.20

5.755

5.755

0.000

0.25

5.755

5.755

0.000

0.30

5.755

5.755

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

20

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: Bus EX


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
74.926
31.580

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Bus EX

Total

Bus20
1BBA51

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

4.951

-31.945

6.5

32.327

Bus EX

83.50

4.951

-31.945

6.5

32.327

Bus20

83.78

0.338

-2.178

6.5

2.204

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

32.327

Ib asym
41.347

25.779

Idc

0.02

32.327

35.518

14.715

0.03

32.327

33.387

8.349

0.04

32.327

32.672

4.737

0.05

32.327

32.442

2.730

0.06

32.327

32.364

1.554

0.07

32.327

32.339

0.885

0.08

32.327

32.330

0.503

0.09

32.327

32.328

0.292

0.10

32.327

32.327

0.166

0.15

32.327

32.327

0.010

0.20

32.327

32.327

0.001

0.25

32.327

32.327

0.000

0.30

32.327

32.327

0.000

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

21

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: BUS GEN


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

18.000
1.10
278.448
63.353

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

BUS GEN

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

3.735

-103.501

27.7

103.568
44.531

S.E. Etn

BUS GEN

50.48

3.186

-44.417

13.9

Bus22

BUS GEN

19.00

0.112

-0.609

5.4

0.619

1MKA10

BUS GEN

100.00

0.436

-58.475

134.0

58.476

S.E. Reque

S.E. Etn

54.18

0.261

-3.634

13.9

3.643

1BBA51

Bus22

19.90

0.300

-1.628

5.4

1.656

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

98.818

162.088

128.482

0.02

97.002

150.200

114.676

0.03

95.050

139.035

101.470

0.04

92.980

129.254

89.785

0.05

90.808

124.841

85.670

0.06

89.982

118.402

76.956

0.07

89.142

112.806

69.129

0.08

88.288

107.939

62.098

0.09

87.420

111.714

69.553

0.10

86.539

107.651

64.029

0.15

85.188

95.127

42.335

0.20

83.799

88.351

27.991

0.25

82.386

84.439

18.507

0.30

80.967

81.886

12.236

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

22

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: CGDE


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

0.480
1.05
132.146
43.154

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin
Barra Origen
ID
CGDE

Tensin y Corriente Inicial Simtrica (rms)


Barra Destino
ID

Total

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

11.402

-56.823

X/R
Cociente
5.0

kA
Magnitud
57.956

1BMA52

CGDE

11.88

10.477

-39.241

3.7

40.616

1XKA52

CGDE

100.00

0.925

-17.582

19.0

17.606

1BMB20

1BMA52

12.83

0.798

-1.828

2.3

1.995

1BMB52

1BMA52

12.29

0.362

-0.758

2.1

0.840

1BNB52

1BMA52

13.77

0.028

-0.059

2.1

0.066

1BJA12

1BFA53

13.03

1.571

-3.271

2.1

3.629

Bus19

1BFA53

71.76

3.854

-24.454

6.3

24.755

1BJA80

1BFA53

100.00

0.313

-0.659

2.1

0.730

PCI_BUS

1BFA51

15.89

0.530

-1.754

3.3

1.832

1BJA11

1BFA51

13.35

1.947

-4.205

2.2

4.634

1BJA51

1BFA51

12.35

1.073

-2.253

2.1

2.496

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

0.01

55.457

Ib asym
72.782

47.136

Idc

0.02

54.181

63.911

33.898

0.03

52.841

57.161

21.800

0.04

51.491

53.365

14.019

0.05

50.143

51.805

13.017

0.06

49.554

50.366

9.009

0.07

48.969

49.364

6.236

0.08

48.388

48.580

4.316

0.09

47.811

48.052

4.803

0.10

47.240

47.369

3.505

0.15

46.199

46.205

0.725

0.20

45.180

45.181

0.150

0.25

44.189

44.189

0.031

0.30

43.774

43.774

0.006

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

23

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: S.E. Etn


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

220.000
1.10
25.559
10.214

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin

Tensin y Corriente Inicial Simtrica (rms)

Barra Origen
ID

Barra Destino
ID

S.E. Etn

Total

S.E. Reque
BUS GEN
Red elctrica Peruana
Bus22
1MKA10

%V
Barra Origen

kA
Activa

kA
Imaginario

0.00

0.934

-10.179

S.E. Etn

7.47

0.892

S.E. Etn

40.11

0.042

S.E. Reque

100.00

BUS GEN

50.45

BUS GEN

100.00

kA
Magnitud

10.9

10.222

-7.284

8.2

7.339

-2.895

69.1

2.895

0.892

-7.284

8.2

7.339

0.069

-0.364

5.3

0.371

0.443

-35.019

79.1

35.022

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
Ib asym

X/R
Cociente

TD (S)

Ib sym

Idc

0.01

10.138

14.512

10.384

0.02

10.110

12.843

7.920

0.03

10.077

11.658

5.862

0.04

10.039

10.937

4.339

0.05

9.997

10.816

4.129

0.06

9.984

10.489

3.214

0.07

9.970

10.279

2.502

0.08

9.956

10.145

1.947

0.09

9.941

10.348

2.873

0.10

9.926

10.212

2.401

0.15

9.898

9.947

0.979

0.20

9.868

9.876

0.399

0.25

9.835

9.836

0.163

0.30

9.800

9.800

0.066

ETAP

Proyecto:

12.0.0C

Ubicacin:

Pgina:

24

Fecha:

02-05-2014

Contrato:

SN:

IDOMINGC-3

Ingeniero:

Revisin:

Base

Config.:

Normal

Archivo:

Caso de Estudio: SC-2


Eten

Falta trifsica en barra: S.E. Reque


Nominal kV
Tensin Factor c
Valor Pico
Estado Estable

=
=
=
=

220.000
1.10
26.672
10.724

(Definido por el Usuario)


kA Mtodo C
kA rms

Contribucin

Tensin y Corriente Inicial Simtrica (rms)

Barra Origen
ID

Barra Destino
ID

S.E. Reque

Total

S.E. Etn
Red elctrica Peruana
BUS GEN

S.E. Etn

%V
Barra Origen

kA
Activa

kA
Imaginario

X/R
Cociente

kA
Magnitud

0.00

1.031

-10.682

10.4

10.731

S.E. Reque

2.86

0.047

-2.812

60.1

2.813

S.E. Reque

100.00

0.984

-7.869

8.0

7.931

41.82

0.047

-2.812

60.1

2.813

Corriente de Falta e Interrupcin en CC (kA)


Basada en la Corriente Total de Falta en Bar
TD (S)

Ib sym

Ib asym

Idc

0.01

10.655

15.105

10.707

0.02

10.630

13.315

8.019

0.03

10.600

12.097

5.829

0.04

10.566

11.384

4.237

0.05

10.528

11.249

3.963

0.06

10.516

10.944

3.030

0.07

10.504

10.756

2.316

0.08

10.491

10.640

1.771

0.09

10.478

10.793

2.589

0.10

10.464

10.678

2.127

0.15

10.439

10.470

0.796

0.20

10.411

10.416

0.298

0.25

10.381

10.382

0.112

0.30

10.349

10.349

0.042

Rev. C

CLCULOS ELCTRICOS
ANEXO VIII

RFE-1-YE__-ECE-IDO-001

Pg/Page 1 de/of 21

ANEXO VIII:

REPORTES DEL ANLISIS DE ARRANQUE DE MOTORES

Este documento contiene informacin propiedad de Cobra y est sujeto a las restricciones detalladas en la pgina de portada.
La nica copia controlada de este documento es la incluida en la intranet de Cobra.
This document contains proprietary information of Cobra and is subject to the restrictions set forth on the title page.
The only controlled copy of the document is located on the Cobra intranet.

One-Line Diagram - OLV1 (Motor Acceleration Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

3600 kW
2196 kvar

AL

100%

ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-1 - MOTOR DE MT (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL PARADO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus

S.E. Etn
220 kV

99,9

9%

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
99,8

BUS GEN
18 kV

6%

Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

Bus22

CU
1MKA10
225 MW

40 m
4-3/C 240

1BBA51
6,6 kV

97,9

7%

Open
CU

120 m
3-3/C 300

CU

1BBA76
6,6 kV

7
97,9

40 m
1-3/C 150

CU

Open

40 m
3-3/C 240

CU
CU

Bus23
Bus20
20 m
1-3/C 300

Bus9

CU

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

20 m
3-3/C 300

Dyn11

Bus25

Bus EX
1BJA76
0,48 kV

98,7

100 m
1-3/C 70

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

Bus12
50 m
1-3/C 70

CU

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

40 m
2-3/C 185

Bus18

Bus11

Bus13

Bus6

Bus5

Bus14

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU
Bus8

Bus7

50 m
1-3/C 70

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

6%

Excitacin 1MKC10
944 kVA

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

88WN-1
224 kW
5
94,9

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

1BMA52
0,48 kV

94,9

CARGAS 1BJA76
270 kVA

5%

1BFA51
0,48 kV

Open

94,9

Open
CU

W-1BJA12

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

1XKA52
2000 kW

09:56:51

CU

100 m
1-3/C 70

1MKA76
8,44 MW

1BFA53
0,48 kV

page 1

CU

Bus15

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

Bus10

Bus24

70 m
1-3/C 70

Bus16

Bus17

Bus19

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

Bus BS

CU

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

Open
CU

70 m
1-3/C 70

Open

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

98,1

CARGAS 1BNB52
82,2 kVA

2%

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

PCI_BUS

Sistema PCI
200 kW

5%

One-Line Diagram - OLV1 (Motor Acceleration Analysis)

1BMA52

CU

1BFA51

1BFA53

50 m
4-3/C 240

CU

1BMB20
0,48 kV

5
94,7

50 m
6-3/C 240

CU

1BJA12
0,48 kV

1
94,7

1BJA11
0,48 kV

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,48 kV
94,8

3%

20 m
4-3/C 240

1BJA51
0,48 kV

94,8

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

09:56:51

may 02, 2014

Project File: Eten

3
94,6

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

2%

One-Line Diagram - OLV1 (Motor Acceleration Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

4103 kW
4433 kvar

AL

99,9

2%

ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-1 - MOTOR DE MT (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL PARADO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN AUTO.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus

S.E. Etn
220 kV

99,9

1%

1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
99,6

BUS GEN
18 kV

7%

Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

Bus22

CU
1MKA10
225 MW

40 m
4-3/C 240

1BBA51
6,6 kV

94,7

3%

Open
CU

120 m
3-3/C 300

CU

1BBA76
6,6 kV

3
94,7

40 m
1-3/C 150

CU

Open

40 m
3-3/C 240

CU
CU

Bus23
Bus20
20 m
1-3/C 300

Bus9

CU

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

20 m
3-3/C 300

Dyn11

Bus25

Bus EX
1BJA76
0,48 kV

95,4

100 m
1-3/C 70

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

Bus12
50 m
1-3/C 70

CU

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

40 m
2-3/C 185

Bus18

Bus11

Bus13

Bus6

Bus5

Bus14

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU
Bus8

Bus7

50 m
1-3/C 70

Dyn11

298 kW
1550 kvar

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

1%

Excitacin 1MKC10
944 kVA

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

88WN-1
224 kW
9
91,3

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

1BMA52
0,48 kV

91,3

CARGAS 1BJA76
270 kVA

9%

1BFA51
0,48 kV

Open

91,3

Open
CU

W-1BJA12

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

1XKA52
2000 kW

09:57:10

CU

100 m
1-3/C 70

1MKA76
8,44 MW

1BFA53
0,48 kV

page 1

CU

Bus15

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

Bus10

Bus24

70 m
1-3/C 70

Bus16

Bus17

Bus19

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

Bus BS

CU

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

Open
CU

70 m
1-3/C 70

Open

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

94,4

CARGAS 1BNB52
82,2 kVA

3%

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

PCI_BUS

Sistema PCI
200 kW

9%

One-Line Diagram - OLV1 (Motor Acceleration Analysis)

1BMA52

CU

1BFA51

1BFA53

50 m
4-3/C 240

CU

1BMB20
0,48 kV

8
91,1

50 m
6-3/C 240

CU

1BJA12
0,48 kV

4
91,1

1BJA11
0,48 kV

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,48 kV
91,2

7%

20 m
4-3/C 240

1BJA51
0,48 kV

91,2

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

09:57:10

may 02, 2014

Project File: Eten

5
91,0

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

5%

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-1

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 0.000Barra


ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV
6.600

6.600

0.480

0.480

% Mag.
97.972

97.970

94.948

94.948

Generacin

ng.
-2.8

-2.8

-8.4

-8.4

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.633

ID
0

0.166

MW

XFMR
Mvar

Amp

% PF

1BBA76

0.173

0.109

18.2

84.6

Bus17

0.134

0.059

13.1

91.5

Bus18

0.000

0.000

0.0

0.0

Bus19

2.584

1.873

284.9

81.0

Bus20

0.689

0.359

69.4

88.7

Bus22

-3.579

-2.400

384.8

83.1

Bus15

0.000

0.000

0.0

0.0
84.6

1BBA51

-0.173

-0.109

18.2

Bus9

0.173

0.109

18.2

84.6

PCI_BUS

0.174

0.108

260.1

84.9

1BJA11

0.549

0.387

850.3

81.7

1BJA51

0.365

0.271

575.6

80.2

1BMA52

-1.088

-0.766

1685.4

81.8

1BJA12

0.397

0.298

629.2

80.0

-2.537

-1.484

3723.9

86.3

1BMA52

1.507

1.020

2305.8

82.8

Bus19

1BJA11

0.480

94.625

-8.4

0.547

0.385

1BFA51

-0.547

-0.385

850.3

81.8

1BJA12

0.480

94.709

-8.4

0.396

0.297

1BFA53

-0.396

-0.297

629.2

80.0

1BJA51

0.480

94.817

-8.4

0.364

0.271

1BFA51

-0.364

-0.271

575.6

80.3

1BJA76

0.480

98.755

-3.3

0.170

0.106

Bus9

-0.170

-0.106

244.2

85.0

1BMA52

0.480

94.948

-8.4

1BMB20

0.244

0.137

354.4

87.2

1BMB52

0.118

0.088

186.4

80.0

1BNB52

0.058

0.029

82.0

89.5

1BFA51

1.088

0.766

1685.4

81.8

1BFA53

-1.507

-1.020

2305.8

82.8

1BMB20

0.480

94.750

-8.4

0.244

0.136

1BMA52

-0.244

-0.136

354.4

87.2

1BMB52

0.480

94.832

-8.4

0.118

0.088

1BMA52

-0.118

-0.088

186.4

80.0

1BNB52

0.380

98.125

-9.0

0.057

0.028

1BMA52

-0.057

-0.028

98.4

90.0

Bus5

4.000

100.430

-3.3

0.133

0.057

Bus10

-0.133

-0.057

20.7

91.9

Bus7

4.000

101.891

-2.8

Bus13

0.000

0.000

0.0

0.0

Bus9

6.600

97.969

-2.8

1BBA76

-0.173

-0.109

18.2

84.6

1BJA76

0.173

0.109

18.2

84.6

Bus5

0.133

0.057

20.7

91.9

Bus17

-0.133

-0.057

20.7

91.9

Bus7

0.000

0.000

0.0

0.0

Bus15

0.000

0.000

0.0

0.0

1BBA51

0.000

0.000

0.0

0.0

Bus13

0.000

0.000

0.0

0.0

Bus10

Bus13

Bus15

Bus17

Bus18

4.160

4.000

6.600

6.600

6.600

96.583

101.891

97.972

97.964

97.972

-3.3

-2.8

-2.8

-2.8

-2.8

1BBA51

-0.134

-0.059

13.1

91.5

Bus10

0.134

0.059

13.1

91.5

1BBA51

0.000

0.000

0.0

0.0

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-1

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 0.000Barra


ID
Bus19

Tensin
kV
6.600

% Mag.
97.948

Generacin

ng.
-2.8

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

% PF

1BBA51

-2.583

-1.872

284.9

81.0

1BFA53

2.583

1.872

284.9

81.0

-0.689

-0.359

69.4

88.7

Bus20

6.600

97.959

-2.8

1BBA51
Bus EX

0.689

0.359

69.4

88.7

Bus22

6.900

93.726

-2.8

1BBA51

3.580

2.400

384.8

83.1

BUS GEN

-3.580

-2.400

384.8

83.1

Bus EX

0.480

89.907

-4.5

0.684

0.332

Bus20

-0.684

-0.332

1017.2

90.0

18.000

99.860

-0.1

S.E. Etn

-3.600

-2.666

143.9

80.4

3.600

2.666

143.9

80.4

1BFA51

-0.173

-0.107

260.1

85.0

S.E. Reque

-3.600

-2.676

11.8

80.3

BUS GEN

3.600

2.676

11.8

80.3

BUS GEN

Bus22
PCI_BUS

0.480

94.272

-8.5

0.173

0.107

S.E. Etn

220.000

99.992

0.0

* S.E. Reque

220.000

100.000

0.0

S.E. Etn
Red elctrica Peruana

* Red elctrica Peruana

220.000

100.087

0.1

3.601

2.202

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)

S.E. Reque

3.600

2.196

11.1

85.4

-3.600

-2.196

11.1

85.4

3.601

2.202

11.1

85.3

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-1

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 1,000+


Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV
6.600

6.600

0.480

0.480

% Mag.
94.728

94.726

91.387

91.387

Generacin

ng.
-3.2

-3.2

-9.0

-9.0

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.592

ID
0

0.157

MW

XFMR
Mvar

Amp

% PF

1BBA76

0.168

0.106

18.4

84.5

Bus17

0.134

0.059

13.5

91.5

Bus18

0.000

0.000

0.0

0.0

Bus19

2.512

1.851

288.2

80.5

Bus20

0.644

0.336

67.1

88.7

Bus22

-4.060

-4.349

549.4

68.2

Bus15

0.602

1.997

192.6

28.8
84.5

1BBA51

-0.168

-0.106

18.4

Bus9

0.168

0.106

18.4

84.5

PCI_BUS

0.175

0.108

270.4

84.9

1BJA11

0.544

0.383

875.9

81.8

1BJA51

0.353

0.262

578.2

80.3

1BMA52

-1.071

-0.754

1723.9

81.8

1BJA12

0.393

0.295

647.2

80.0

-2.465

-1.453

3766.2

86.1

1BMA52

1.480

1.001

2351.9

82.8

Bus19

1BJA11

0.480

91.054

-9.1

0.542

0.382

1BFA51

-0.542

-0.382

875.9

81.8

1BJA12

0.480

91.140

-9.0

0.392

0.294

1BFA53

-0.392

-0.294

647.2

80.0

1BJA51

0.480

91.255

-9.0

0.352

0.262

1BFA51

-0.352

-0.262

578.2

80.3

1BJA76

0.480

95.411

-3.7

0.166

0.103

Bus9

-0.166

-0.103

246.1

85.0

1BMA52

0.480

91.387

-9.0

1BMB20

0.241

0.135

364.0

87.2

1BMB52

0.114

0.085

186.9

80.0

1BNB52

0.054

0.027

79.6

89.5

1BFA51

1.071

0.754

1723.9

81.8

1BFA53

-1.480

-1.001

2351.9

82.8

1BMB20

0.480

91.183

-9.1

0.241

0.135

1BMA52

-0.241

-0.135

364.0

87.3

1BMB52

0.480

91.270

-9.0

0.113

0.085

1BMA52

-0.113

-0.085

186.9

80.0

1BNB52

0.380

94.430

-9.6

0.053

0.026

1BMA52

-0.053

-0.026

95.5

90.0

Bus5

4.000

97.004

-3.7

0.133

0.057

Bus10

-0.133

-0.057

21.5

91.9

Bus7

4.000

74.565

2.7

0.298

1.550

Bus13

-0.298

-1.550

305.6

18.9

Bus9

6.600

94.725

-3.2

1BBA76

-0.168

-0.106

18.4

84.5

1BJA76

0.168

0.106

18.4

84.5

Bus5

0.133

0.057

21.5

91.9

Bus17

-0.133

-0.057

21.5

91.9

Bus10

Bus13

Bus15

4.160

4.000

6.600

93.289

74.684

94.622

-3.7

2.6

-3.1

Bus7

0.302

1.552

305.6

19.1

Bus15

-0.302

-1.552

305.6

19.1

1BBA51

-0.598

-1.996

192.6

28.7

0.598

1.996

192.6

28.7

Bus13
Bus17

Bus18

6.600

6.600

94.719

94.728

-3.2

-3.2

1BBA51

-0.134

-0.059

13.5

91.5

Bus10

0.134

0.059

13.5

91.5

1BBA51

0.000

0.000

0.0

0.0

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-1

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 1,000+


Barra
ID
Bus19

Tensin
kV
6.600

% Mag.
94.704

Generacin

ng.
-3.2

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

% PF

1BBA51

-2.512

-1.850

288.2

80.5

1BFA53

2.512

1.850

288.2

80.5

-0.644

-0.335

67.1

88.7

Bus20

6.600

94.715

-3.2

1BBA51
Bus EX

0.644

0.335

67.1

88.7

Bus22

6.900

90.629

-3.2

1BBA51

4.061

4.350

549.4

68.2

BUS GEN

-4.061

-4.350

549.4

68.2

Bus EX

0.480

86.930

-4.8

0.640

0.310

Bus20

-0.640

-0.310

983.5

90.0

18.000

99.670

-0.1

S.E. Etn

-4.103

-4.892

205.5

64.3

4.103

4.892

205.5

64.3

1BFA51

-0.173

-0.107

270.4

85.0

S.E. Reque

-4.103

-4.912

16.8

64.1

BUS GEN

4.103

4.912

16.8

64.1

BUS GEN

Bus22
PCI_BUS

0.480

90.684

-9.1

0.173

0.107

S.E. Etn

220.000

99.909

0.0

* S.E. Reque

220.000

99.924

0.0

S.E. Etn
Red elctrica Peruana

* Red elctrica Peruana

220.000

100.087

0.1

4.105

4.445

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)

S.E. Reque

4.103

4.433

15.9

67.9

-4.103

-4.433

15.9

67.9

4.105

4.445

15.9

67.8

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-1

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 2,000+


Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV
6.600

6.600

0.480

0.480

% Mag.
97.601

97.599

94.542

94.542

Generacin

ng.
-3.1

-3.1

-8.8

-8.8

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.628

ID
0

0.165

MW

XFMR
Mvar

Amp

% PF

1BBA76

0.172

0.109

18.2

84.6

Bus17

0.134

0.059

13.1

91.5

Bus18

0.000

0.000

0.0

0.0

Bus19

2.575

1.870

285.3

80.9

Bus20

0.684

0.356

69.1

88.7

Bus22

-3.981

-2.585

425.4

83.9

Bus15

0.416

0.191

41.0

90.9
84.6

1BBA51

-0.172

-0.109

18.2

Bus9

0.172

0.109

18.2

84.6

PCI_BUS

0.174

0.108

261.3

84.9

1BJA11

0.548

0.386

853.1

81.7

1BJA51

0.363

0.270

575.8

80.2

1BMA52

-1.086

-0.765

1689.6

81.8

1BJA12

0.397

0.298

631.2

80.0

-2.529

-1.481

3728.4

86.3

1BMA52

1.504

1.018

2310.8

82.8

Bus19

1BJA11

0.480

94.218

-8.8

0.546

0.385

1BFA51

-0.546

-0.385

853.1

81.8

1BJA12

0.480

94.301

-8.8

0.396

0.297

1BFA53

-0.396

-0.297

631.2

80.0

1BJA51

0.480

94.410

-8.8

0.363

0.270

1BFA51

-0.363

-0.270

575.8

80.3

1BJA76

0.480

98.373

-3.6

0.170

0.105

Bus9

-0.170

-0.105

244.4

85.0

1BMA52

0.480

94.542

-8.8

1BMB20

0.244

0.137

355.4

87.2

1BMB52

0.117

0.088

186.5

80.0

1BNB52

0.058

0.029

81.8

89.5

1BFA51

1.086

0.765

1689.6

81.8

1BFA53

-1.504

-1.018

2310.8

82.8

1BMB20

0.480

94.343

-8.8

0.243

0.136

1BMA52

-0.243

-0.136

355.4

87.2

1BMB52

0.480

94.426

-8.8

0.117

0.088

1BMA52

-0.117

-0.088

186.5

80.0

1BNB52

0.380

97.703

-9.4

0.057

0.028

1BMA52

-0.057

-0.028

98.1

90.0

Bus5

4.000

100.039

-3.7

0.133

0.057

Bus10

-0.133

-0.057

20.8

91.9

Bus7

4.000

96.895

-4.8

0.402

0.170

Bus13

-0.402

-0.170

65.1

92.1

Bus9

6.600

97.598

-3.1

1BBA76

-0.172

-0.109

18.2

84.6

1BJA76

0.172

0.109

18.2

84.6

Bus5

0.133

0.057

20.8

91.9

Bus17

-0.133

-0.057

20.8

91.9
92.1

Bus10

Bus13

Bus15

4.160

4.000

6.600

96.206

96.944

97.564

-3.7

-4.8

-3.1

Bus7

0.402

0.170

65.1

Bus15

-0.402

-0.170

65.1

92.1

1BBA51

-0.416

-0.190

41.0

90.9

0.416

0.190

41.0

90.9

Bus13
Bus17

Bus18

6.600

6.600

97.593

97.601

-3.1

-3.1

1BBA51

-0.134

-0.059

13.1

91.5

Bus10

0.134

0.059

13.1

91.5

1BBA51

0.000

0.000

0.0

0.0

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-1

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 2,000+


Barra
ID
Bus19

Tensin
kV
6.600

% Mag.
97.577

Generacin

ng.
-3.1

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

% PF

1BBA51

-2.575

-1.870

285.3

80.9

1BFA53

2.575

1.870

285.3

80.9

-0.684

-0.356

69.1

88.7

Bus20

6.600

97.588

-3.1

1BBA51
Bus EX

0.684

0.356

69.1

88.7

Bus22

6.900

93.372

-3.1

1BBA51

3.982

2.585

425.4

83.9

BUS GEN

-3.982

-2.585

425.4

83.9

Bus EX

0.480

89.566

-4.8

0.679

0.329

Bus20

-0.679

-0.329

1013.4

90.0

18.000

99.837

-0.1

S.E. Etn

-4.007

-2.911

159.1

80.9

4.007

2.911

159.1

80.9

1BFA51

-0.173

-0.107

261.3

85.0

S.E. Reque

-4.007

-2.922

13.0

80.8

BUS GEN

4.007

2.922

13.0

80.8

BUS GEN

Bus22
PCI_BUS

0.480

93.863

-8.8

0.173

0.107

S.E. Etn

220.000

99.981

0.0

* S.E. Reque

220.000

99.990

0.0

S.E. Etn
Red elctrica Peruana

* Red elctrica Peruana

220.000

100.087

0.1

4.008

2.450

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)

S.E. Reque

4.007

2.442

12.3

85.4

-4.007

-2.442

12.3

85.4

4.008

2.450

12.3

85.3

% Tap

2.500

One-Line Diagram - OLV1 (Motor Acceleration Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

3972 kW
2297 kvar

AL

100%

ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-2 - MOTOR DE BT (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL PARADO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN TOMA -4,5%.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus

S.E. Etn
220 kV

99,9

9%

-4,5% TapP
1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
104,

BUS GEN
18 kV

57%

Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

Bus22

CU
1MKA10
225 MW

40 m
4-3/C 240

1BBA51
6,6 kV

102,

8%

Open
CU

120 m
3-3/C 300

CU

1BBA76
6,6 kV

8
102,

40 m
1-3/C 150

CU

Open

40 m
3-3/C 240

CU
CU

Bus23
Bus20
20 m
1-3/C 300

Bus9

CU

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

20 m
3-3/C 300

Dyn11

Bus25

Bus EX
1BJA76
0,48 kV

103,

100 m
1-3/C 70

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

Bus12
50 m
1-3/C 70

CU

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

40 m
2-3/C 185

Bus18

Bus11

Bus13

Bus6

Bus5

Bus14

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU
Bus8

Bus7

50 m
1-3/C 70

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

73%

Excitacin 1MKC10
944 kVA

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

88WN-1
224 kW
8
100,

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

1BMA52
0,48 kV

100,

CARGAS 1BJA76
270 kVA

8%

1BFA51
0,48 kV

Open

100,

Open
CU

W-1BJA12

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

1XKA52
2000 kW

09:53:38

CU

100 m
1-3/C 70

1MKA76
8,44 MW

1BFA53
0,48 kV

page 1

CU

Bus15

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

Bus10

Bus24

70 m
1-3/C 70

Bus16

Bus17

Bus19

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

Bus BS

CU

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

Open
CU

70 m
1-3/C 70

Open

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

104,

CARGAS 1BNB52
82,2 kVA

2%

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

PCI_BUS

Sistema PCI
200 kW

8%

One-Line Diagram - OLV1 (Motor Acceleration Analysis)

1BMA52

CU

1BFA51

1BFA53

50 m
4-3/C 240

CU

1BMB20
0,48 kV

6
100,

50 m
6-3/C 240

CU

1BJA12
0,48 kV

1%

5
100,

1BJA11
0,48 kV

7%

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,48 kV
100,

69%

20 m
4-3/C 240

1BJA51
0,48 kV

100,

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

09:53:38

may 02, 2014

Project File: Eten

5
100,

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

67%

One-Line Diagram - OLV1 (Motor Acceleration Analysis)


Red elctrica Peruana
3022 MVAsc

S.E. Reque
220 kV

RESERVA FRA ETEN

4150 kW
4058 kvar

AL

99,9

4%

ESTUDIO DE ARRANQUE DE MOTORES: CASO MS-2 - MOTOR DE BT (REV C)


CONDICIONES:
-> TENSIN DE RED: 220 kV
-> GENERADOR PRINCIPAL PARADO
-> GENERADOR AUXILIAR PARADO
-> GENERADOR EMERGENCIA PARADO
-> TRANSFORMADOR PRINCIPAL CON REGULADOR DE TENSIN EN TOMA -4,5%.
-> TRANSFORMADOR AUXILIAR CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> TRANSFORMADOR DE SERVICIO DE BACL START CON REGULADOR DE TENSIN EN TOMA +2,5%.
-> RESTO DE TRANSFORMADORES DE SERVICIO MT/BT CON REGULADOR DE TENSIN EN TOMA CENTRAL.
-> TODAS LAS CARGAS DE BT SUMINISTRADAS DESDE UN NICO TRAFO MT/BT.

2,92 km
Narcissus

S.E. Etn
220 kV

99,9

3%

-4,5% TapP
1BAT10
300 MVA
220/18 kV
YNd1
13,33 %Z
104,

BUS GEN
18 kV

42%

Isolated Phase CU
8 m

Isolated Phase CU
35 m

2,5% TapP
1BBT51
11,5 MVA
18/6,9 kV
13,5 %Z

Open
Dyn11
Isolated Phase CU
35 m

Bus22

CU
1MKA10
225 MW

40 m
4-3/C 240

1BBA51
6,6 kV

100,

36%

Open
CU

120 m
3-3/C 300

CU

1BBA76
6,6 kV

3
100,

40 m
1-3/C 150

CU

6%

Open

40 m
3-3/C 240

CU
CU

Bus23
Bus20
20 m
1-3/C 300

Bus9

CU

2,5% TapP
1BFT76
500 kVA
6,6/0,505 kV
Dyn11
4 %Z

20 m
3-3/C 300

Dyn11

Bus25

Bus EX
1BJA76
0,48 kV

101,

100 m
1-3/C 70

CU

1BFT53
3500 kVA
6,6/0,505 kV
12 %Z

Bus12
50 m
1-3/C 70

CU

88AK-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU

88AK-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

40 m
2-3/C 185

Bus18

Bus11

Bus13

Bus6

Bus5

Bus14

88WN-2_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

50 m
1-3/C 70

CU
Bus8

Bus7

50 m
1-3/C 70

Dyn11

1BFT51
3500 kVA
6,6/0,505 kV
12 %Z

22%

Excitacin 1MKC10
944 kVA

LCI 1BPA10_1
2725 kVA

LCI 1BPA10_2
2725 kVA

88WN-1
224 kW
7
91,8

88WN-2
224 kW

88AK-1
375 kW

88AK-2
375 kW

1BMA52
0,48 kV

91,8

CARGAS 1BJA76
270 kVA

7%

1BFA51
0,48 kV

Open

91,8

Open
CU

W-1BJA12

50 m
6-3/C 300

W-1BMB52

1BNT52
150 kVA
0,48/0,4 kV
Dyn1
4 %Z

CGDE
MBN50 AH010
450 kVA

1BJA80
400 kVA

0,48 kV

1XKA52
2000 kW

09:54:33

CU

100 m
1-3/C 70

1MKA76
8,44 MW

1BFA53
0,48 kV

page 1

CU

Bus15

88WN-1_XFR
600 kVA
6,6/4,16 kV
Yd1
6 %Z

Bus10

Bus24

70 m
1-3/C 70

Bus16

Bus17

Bus19

1MKC20
1500 kVA
6,6/0,45 kV
6 %Z

Yd1

Bus BS

CU

CU

40 m
2-3/C 185

1BPT10
5450/2725/2725 kVA
6,6/2,08/2,08 kV
6/6/6 %Z

Open
CU

70 m
1-3/C 70

Open

may 02, 2014

Project File: Eten

1BNB52
0,38 kV

3%
94,9

CARGAS 1BNB52
82,2 kVA

W-1BMB20

W-1BJA11

W-1BJA51
CU

115 m
2-3/C 240

PCI_BUS
295 kW
1281 kvar
Sistema PCI
200 kW

7%

One-Line Diagram - OLV1 (Motor Acceleration Analysis)

1BMA52

CU

1BFA51

1BFA53

50 m
4-3/C 240

CU

1BMB20
0,48 kV

7
91,6

50 m
6-3/C 240

CU

1BJA12
0,48 kV

2
91,6

1BJA11
0,48 kV

CARGAS 1BJA11
695 kVA

CARGAS 1BMB20
235 kVA

1BMA52

CU

1BFA51

20 m
2-3/C 150

CU

1BMB52
0,48 kV
91,7

5%

20 m
4-3/C 240

1BJA51
0,48 kV

91,7

Open

CARGAS 1BMB52
231 kVA
Compresor 2
37 kW

page 2

09:54:33

may 02, 2014

Project File: Eten

4
91,5

1MBV10AP002-M1
75 kW

CARGAS 1BJA12
592 kVA

1MBV10AP001-M01
75 kW

50 m
6-3/C 240

CARGAS 1BJA51
650 kVA
Compresor 1
37 kW

4%

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-2

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 0.000Barra


ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV

% Mag.

6.600

102.798

6.600

0.480

0.480

102.796

100.804

100.804

Generacin

ng.
-2.8

-2.8

-7.8

-7.8

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.704

ID
0

0.181

MW

XFMR
Mvar

Amp

% PF

1BBA76

0.180

0.113

18.1

84.6

Bus17

0.134

0.059

12.4

91.5

Bus18

0.000

0.000

0.0

0.0

Bus19

2.527

1.758

262.0

82.1

Bus20

0.758

0.395

72.8

88.7

Bus22

-3.950

-2.483

397.0

84.7

Bus15

0.351

0.158

32.7

91.2

1BBA51

-0.180

-0.113

18.1

84.6

Bus9

0.180

0.113

18.1

84.6

PCI_BUS

0.000

0.000

0.0

0.0

1BJA11

0.557

0.393

812.8

81.7

1BJA51

0.385

0.287

573.2

80.2

1BMA52

-0.942

-0.679

1385.9

81.1

1BJA12

0.404

0.303

602.8

80.0

-2.488

-1.429

3424.1

86.7

1BMA52

1.380

0.945

1995.8

82.5

Bus19

1BJA11

0.480

100.495

-7.8

0.555

0.391

1BFA51

-0.555

-0.391

812.8

81.7

1BJA12

0.480

100.575

-7.8

0.403

0.302

1BFA53

-0.403

-0.302

602.8

80.0

1BJA51

0.480

100.673

-7.8

0.385

0.286

1BFA51

-0.385

-0.286

573.2

80.2

1BJA76

0.480

103.725

-3.3

0.177

0.110

Bus9

-0.177

-0.110

242.0

85.0

1BMA52

0.480

100.804

-7.8

1BMB20

0.249

0.140

340.4

87.2

1BMB52

0.125

0.094

186.2

80.0

1BNB52

0.065

0.032

86.1

89.5

1BFA51

0.942

0.679

1385.9

81.1

1BFA53

-1.380

-0.945

1995.8

82.5

1BMB20

0.480

100.614

-7.8

0.248

0.139

1BMA52

-0.248

-0.139

340.4

87.2

1BMB52

0.480

100.688

-7.7

0.125

0.094

1BMA52

-0.125

-0.094

186.2

80.0

1BNB52

0.380

104.199

-8.4

0.064

0.031

1BMA52

-0.064

-0.031

103.3

90.0

Bus5

4.000

105.520

-3.3

0.133

0.057

Bus10

-0.133

-0.057

19.7

91.9

Bus7

4.000

103.241

-4.1

0.342

0.145

Bus13

-0.342

-0.145

51.9

92.1

Bus9

6.600

102.795

-2.8

1BBA76

-0.180

-0.113

18.1

84.6

1BJA76

0.180

0.113

18.1

84.6

Bus5

0.133

0.057

19.7

91.9

Bus17

-0.133

-0.057

19.7

91.9

Bus10

Bus13

Bus15

4.160

4.000

6.600

101.476

103.280

102.768

-3.3

-4.1

-2.8

Bus7

0.342

0.145

51.9

92.1

Bus15

-0.342

-0.145

51.9

92.1

1BBA51

-0.351

-0.158

32.7

91.2

0.351

0.158

32.7

91.2

Bus13
Bus17

Bus18

6.600

6.600

102.790

102.798

-2.8

-2.8

1BBA51

-0.134

-0.059

12.4

91.5

Bus10

0.134

0.059

12.4

91.5

1BBA51

0.000

0.000

0.0

0.0

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-2

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 0.000Barra


ID
Bus19

Tensin
kV

% Mag.

6.600

102.776

Generacin

ng.
-2.8

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

% PF

1BBA51

-2.527

-1.758

262.0

82.1

1BFA53

2.527

1.758

262.0

82.1

-0.758

-0.395

72.8

88.7

Bus20

6.600

102.784

-2.8

1BBA51
Bus EX

0.758

0.395

72.8

88.7

Bus22

6.900

98.342

-2.8

1BBA51

3.950

2.483

397.0

84.7

BUS GEN

-3.950

-2.483

397.0

84.7

Bus EX

0.480

94.336

-4.5

0.753

0.365

Bus20

-0.753

-0.365

1067.3

90.0

18.000

104.572

-0.1

S.E. Etn

BUS GEN

-3.972

-2.767

148.5

82.1

Bus22

3.972

2.767

148.5

82.1

0.000

0.000

0.0

0.0

PCI_BUS

0.480

100.804

-7.8

1BFA51

S.E. Etn

220.000

99.991

0.0

S.E. Reque

-3.972

-2.777

12.7

82.0

BUS GEN

3.972

2.777

12.7

82.0

* S.E. Reque

220.000

100.000

0.0

S.E. Etn
Red elctrica Peruana

* Red elctrica Peruana

220.000

100.092

0.1

3.973

2.304

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)

S.E. Reque

3.972

2.297

12.0

86.6

-3.972

-2.297

12.0

86.6

3.973

2.304

12.0

86.5

% Tap

2.500

-4.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-2

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 1,000+


Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV

% Mag.

6.600

100.360

6.600

0.480

0.480

100.358

91.870

91.870

Generacin

ng.
-2.9

-2.9

-8.5

-8.5

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.597

ID
0

0.158

MW

XFMR
Mvar

Amp

% PF

1BBA76

0.176

0.111

18.1

84.6

Bus17

0.134

0.059

12.7

91.5

Bus18

0.000

0.000

0.0

0.0

Bus19

2.730

3.359

377.3

63.1

Bus20

0.723

0.377

71.0

88.7

Bus22

-4.113

-4.064

504.0

71.1

Bus15

0.351

0.158

33.6

91.2

1BBA51

-0.176

-0.111

18.1

84.6

Bus9

0.176

0.111

18.1

84.6

PCI_BUS

0.348

1.328

1798.0

25.4

1BJA11

0.545

0.384

872.3

81.8

1BJA51

0.354

0.263

577.7

80.3

1BMA52

-1.247

-1.975

3058.6

53.4

1BJA12

0.394

0.296

644.7

80.0

-2.648

-2.677

4930.5

70.3

1BMA52

1.658

2.224

3631.1

59.8

Bus19

1BJA11

0.480

91.539

-8.5

0.543

0.382

1BFA51

-0.543

-0.382

872.3

81.8

1BJA12

0.480

91.624

-8.5

0.393

0.295

1BFA53

-0.393

-0.295

644.7

80.0

1BJA51

0.480

91.738

-8.5

0.354

0.263

1BFA51

-0.354

-0.263

577.7

80.3

1BJA76

0.480

101.215

-3.4

0.174

0.108

Bus9

-0.174

-0.108

243.0

85.0

1BMA52

0.480

91.870

-8.5

1BMB20

0.242

0.135

362.6

87.2

1BMB52

0.114

0.086

186.8

80.0

1BNB52

0.055

0.027

79.9

89.5

1BFA51

1.247

1.975

3058.6

53.4

1BFA53

-1.658

-2.224

3631.1

59.8

1BMB20

0.480

91.667

-8.5

0.241

0.135

1BMA52

-0.241

-0.135

362.6

87.3

1BMB52

0.480

91.753

-8.5

0.114

0.086

1BMA52

-0.114

-0.086

186.8

80.0

1BNB52

0.380

94.931

-9.1

0.054

0.026

1BMA52

-0.054

-0.026

95.9

90.0

Bus5

4.000

102.950

-3.4

0.133

0.057

Bus10

-0.133

-0.057

20.2

91.9

Bus7

4.000

100.608

-4.2

0.342

0.145

Bus13

-0.342

-0.145

53.3

92.1

Bus9

6.600

100.357

-2.9

1BBA76

-0.176

-0.111

18.1

84.6

1BJA76

0.176

0.111

18.1

84.6

Bus5

0.133

0.057

20.2

91.9

Bus17

-0.133

-0.057

20.2

91.9

Bus10

Bus13

Bus15

4.160

4.000

6.600

99.005

100.648

100.330

-3.4

-4.2

-2.9

Bus7

0.342

0.145

53.3

92.1

Bus15

-0.342

-0.145

53.3

92.1

1BBA51

-0.351

-0.158

33.6

91.2

0.351

0.158

33.6

91.2

Bus13
Bus17

Bus18

6.600

6.600

100.352

100.360

-2.9

-2.9

1BBA51

-0.134

-0.059

12.7

91.5

Bus10

0.134

0.059

12.7

91.5

1BBA51

0.000

0.000

0.0

0.0

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-2

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 1,000+


Barra
ID
Bus19

Tensin
kV

% Mag.

6.600

100.329

Generacin

ng.
-2.9

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

% PF

1BBA51

-2.728

-3.358

377.3

63.1

1BFA53

2.728

3.358

377.3

63.1

-0.723

-0.377

71.0

88.7

Bus20

6.600

100.347

-2.9

1BBA51
Bus EX

0.723

0.377

71.0

88.7

Bus22

6.900

96.015

-2.9

1BBA51

4.114

4.065

504.0

71.1

BUS GEN

-4.114

-4.065

504.0

71.1

Bus EX

0.480

92.099

-4.6

0.718

0.348

Bus20

-0.718

-0.348

1042.0

90.0

18.000

104.425

-0.1

S.E. Etn

-4.149

-4.521

188.5

67.6

4.149

4.521

188.5

67.6

1BFA51

-0.295

-1.281

1798.0

22.4

S.E. Reque

-4.150

-4.538

16.1

67.5

BUS GEN

4.150

4.538

16.1

67.5

BUS GEN

Bus22
PCI_BUS

0.480

87.967

-6.8

0.295

1.281

S.E. Etn

220.000

99.927

0.0

* S.E. Reque

220.000

99.941

0.0

S.E. Etn
Red elctrica Peruana

* Red elctrica Peruana

220.000

100.092

0.1

4.151

4.070

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)

S.E. Reque

4.150

4.058

15.2

71.5

-4.150

-4.058

15.2

71.5

4.151

4.070

15.2

71.4

% Tap

2.500

-4.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-2

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 2,000+


Barra
ID
1BBA51

1BBA76

1BFA51

1BFA53

Tensin
kV

% Mag.

6.600

102.474

6.600

0.480

0.480

102.472

99.687

99.687

Generacin

ng.
-3.0

-3.0

-8.4

-8.4

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

0.690

ID
0

0.178

MW

XFMR
Mvar

Amp

% PF

1BBA76

0.179

0.113

18.1

84.6

Bus17

0.134

0.059

12.5

91.5

Bus18

0.000

0.000

0.0

0.0

Bus19

2.735

1.952

286.8

81.4

Bus20

0.754

0.393

72.5

88.7

Bus22

-4.152

-2.674

421.6

84.1

Bus15

0.351

0.158

32.8

91.2

1BBA51

-0.179

-0.113

18.1

84.6

Bus9

0.179

0.113

18.1

84.6

PCI_BUS

0.224

0.139

318.1

84.9

1BJA11

0.555

0.391

819.6

81.7

1BJA51

0.381

0.284

573.5

80.2

1BMA52

-1.160

-0.814

1710.4

81.9

1BJA12

0.403

0.302

607.6

80.0

-2.688

-1.558

3748.5

86.5

1BMA52

1.595

1.078

2322.4

82.9

Bus19

1BJA11

0.480

99.375

-8.4

0.553

0.390

1BFA51

-0.553

-0.390

819.6

81.7

1BJA12

0.480

99.455

-8.4

0.402

0.301

1BFA53

-0.402

-0.301

607.6

80.0

1BJA51

0.480

99.555

-8.4

0.381

0.283

1BFA51

-0.381

-0.283

573.5

80.2

1BJA76

0.480

103.392

-3.4

0.177

0.110

Bus9

-0.177

-0.110

242.1

85.0

1BMA52

0.480

99.687

-8.4

1BMB20

0.248

0.139

342.9

87.2

1BMB52

0.123

0.093

186.2

80.0

1BNB52

0.063

0.031

85.3

89.5

1BFA51

1.160

0.814

1710.4

81.9

1BFA53

-1.595

-1.078

2322.4

82.9

1BMB20

0.480

99.494

-8.4

0.247

0.139

1BMA52

-0.247

-0.139

342.9

87.2

1BMB52

0.480

99.570

-8.4

0.123

0.092

1BMA52

-0.123

-0.092

186.2

80.0

1BNB52

0.380

103.040

-9.0

0.062

0.030

1BMA52

-0.062

-0.030

102.4

90.0

Bus5

4.000

105.179

-3.4

0.133

0.057

Bus10

-0.133

-0.057

19.8

91.9

Bus7

4.000

102.891

-4.2

0.342

0.145

Bus13

-0.342

-0.145

52.1

92.1

Bus9

6.600

102.471

-3.0

1BBA76

-0.179

-0.113

18.1

84.6

1BJA76

0.179

0.113

18.1

84.6

Bus5

0.133

0.057

19.8

91.9

Bus17

-0.133

-0.057

19.8

91.9

Bus10

Bus13

Bus15

4.160

4.000

6.600

101.148

102.930

102.445

-3.4

-4.2

-3.0

Bus7

0.342

0.145

52.1

92.1

Bus15

-0.342

-0.145

52.1

92.1

1BBA51

-0.351

-0.158

32.8

91.2

0.351

0.158

32.8

91.2

Bus13
Bus17

Bus18

6.600

6.600

102.466

102.474

-3.0

-3.0

1BBA51

-0.134

-0.059

12.5

91.5

Bus10

0.134

0.059

12.5

91.5

1BBA51

0.000

0.000

0.0

0.0

% Tap

2.500

ETAP

Proyecto:

Pgina:

12.0.0C

Ubicacin:
Contrato:
Ingeniero:
Archivo:

Caso de Estudio: MS-2

Eten

Fecha:

02-05-2014

SN:

IDOMINGC-3

Revisin:

Base

Config.:

Normal

Informe de Flujo de Carga @ T = 2,000+


Barra
ID
Bus19

Tensin
kV

% Mag.

6.600

102.450

Generacin

ng.
-3.0

MW

Carga

Mvar
0

MW
0

Flujo de Carga
Mvar

ID
0

MW

XFMR
Mvar

Amp

% PF

1BBA51

-2.734

-1.952

286.8

81.4

1BFA53

2.734

1.952

286.8

81.4

-0.754

-0.393

72.5

88.7

Bus20

6.600

102.460

-3.0

1BBA51
Bus EX

0.754

0.393

72.5

88.7

Bus22

6.900

98.033

-3.0

1BBA51

4.152

2.675

421.6

84.1

BUS GEN

-4.152

-2.675

421.6

84.1

Bus EX

0.480

94.038

-4.6

0.749

0.363

Bus20

-0.749

-0.363

1064.0

90.0

18.000

104.552

-0.1

S.E. Etn

-4.177

-2.994

157.7

81.3

4.177

2.994

157.7

81.3

1BFA51

-0.222

-0.138

318.1

85.0

S.E. Reque

-4.177

-3.006

13.5

81.2

BUS GEN

4.177

3.006

13.5

81.2

BUS GEN

Bus22
PCI_BUS

0.480

98.859

-8.5

0.222

0.138

S.E. Etn

220.000

99.982

0.0

* S.E. Reque

220.000

99.992

0.0

S.E. Etn
Red elctrica Peruana

* Red elctrica Peruana

220.000

100.092

0.1

4.178

2.534

* Indica una barra con tensin regulada (con mquinas de tensin controlada o mquinas de referencia conectadas)

S.E. Reque

4.177

2.526

12.8

85.6

-4.177

-2.526

12.8

85.6

4.178