Sei sulla pagina 1di 74

MASTERPACT Universal Power

Circuit Breaker
Class 631

CONTENTS
Description
Page
Introduction ............................................................................................................... 1
Advantages ............................................................................................................... 3
Description ................................................................................................................ 6
Control Units ............................................................................................................. 7
Accessories ............................................................................................................. 23
Switch ..................................................................................................................... 36
Trip Curves ............................................................................................................. 37
Wiring Diagrams ..................................................................................................... 42
Circuit Breaker Dimensions .................................................................................... 46
Appendix ................................................................................................................. 62

Introduction
Standard Compliance
n UL489: MP08 to MP50 circuit breakers and their accessories are Listed under UL files E63335,

E103955 and E113555


n UL1066/ANSI: MC08 to MC50 circuit breakers are UL Listed according to UL1066 (ANSI C37-13)

under file E161835


n International Standards: the MASTERPACT circuit breaker has been designed to meet all the

major standards including:


IEC 947-2 and related standards such as VDE, BS, EN, etc.
o JEC, JIS
n UL 1008: MP12, MP20 and MP30 circuit breakers are suitable for use in transfer switch
equipment
n Marine Applications:
o Homologated by Bureau Veritas
o Approved by Det Norske Veritas and Germanische Lloyd's
o Listed by Lloyd's Register of Shipping
o American Bureau of Shipping application
o UL marine
o

High Short-time Current Rating: Up to 100 kA for 1 sec.


The exceptional short-time rating of 75,000 A in a 3000 A frame and 100,000 A in a 4000 A frame
and above allows the circuit breakers to be fully selective up to their interrupting ratings.

100% Rated
The circuit breakers are designed for continuous operation at 100% of their current rating.

Other Performances
The UL 489 and UL1066 (ANSI C37-13) standard performance tests assure that the circuit breaker
has sufficient characteristics to be used in normal conditions. However, the circuit breaker exceeds,
without additional costs, the UL standard 1,500 operations required in endurance. The heavy-duty
mechanism and the contact design provide a mechanical endurance of 10,000 operations (approx.)
without maintenance (see page 64).

Tropicalization
The standard moisture and fungus protection ensure normal operation under extreme ambient
conditions. MASTERPACT circuit breakers comply with T2 tropicalization (IEC Standard 68-2-30);
relative humidity 95% at 113F (45C) and 80% at 131F (55C) (hot, humid climate). Salt spray
resistance as per IEC 68-2-11.

Poles
The 4-pole version is an efficient solution to ground fault problems created by incorrectly grounded
standby generators and incorrect transfer switching systems. By isolating the neutral of multiple
sources coupled together, 4-pole circuit breakers prevent ground faults from returning to the source
via unintended paths. Where unintended paths exist, ground fault sensing can become inaccurate or
create nuisance tripping.
Ampere Rating (A)

3-Pole

4-Pole

800

MP-MC

MP-MC

1200

MP

MP

1600

MP-MC

MP-MC

2000

MP-MC

MP-MC

2500

MP

MP

3000

MP

MP

3200

MC

4000

MP-MC

MP (1)

5000

MP-MC

MP (1)

6300

MP (1)

(1) Not UL Listed.

1
11/98

1995 Square DAll Rights Reserved

Introduction
Ratings
Type

Ampere Rating (A)

MP/MC08

800

Sensor Ratings (A)


250400600800

MP12

1200

8001200

MP/MC16

1600

12001600

MP/MC20

2000

16002000

MP25

2500

20002500

MP30

3000

25003000

MC32

3200

25003200

MP/MC40

4000

250030004000

MP/MC50

5000

40005000

MP63

6300

50006300

Interrupting Ratings
UL489/NEMA AB1
Type

Rating (A)

480 Vac

600 Vac

Short-time

Standard Interrupting Rating


MP08 H1

800

65 kA

65 kA

50 kA

MP12 H1

1200

65 kA

65 kA

50 kA

MP16 H1

1600

65 kA

65 kA

50 kA

MP20 H1

2000

75 kA

75 kA

75 kA

MP25 H1

2500

75 kA

75 kA

75 kA

MP30 H1

3000

75 kA

75 kA

75 kA

MP40 H1

4000

100 kA

100 kA

100 kA

MP50 H1

5000

100 kA

100 kA

100 kA

MP63 H1

6300 (1)

100 kA

100 kA

100 kA

High Interrupting Rating


MP08 H2

800

100 kA

65 kA

50 kA

MP12 H2

1200

100 kA

65 kA

50 kA

MP16 H2

1600

100 kA

65 kA

50 kA

MP20 H2

2000

100 kA

75 kA

75 kA

MP25 H2

2500

100 kA

75 kA

75 kA

MP30 H2

3000

100 kA

75 kA

75 kA

MP40 H2

4000

125 kA

100 kA

100 kA

MP50 H2

5000

125 kA

100 kA

100 kA

MP63 H2

6300 (1)

150 kA

100 kA

100 kA

508 V

635 V

Short-time

(1) Not UL Listed.

UL1066/ANSI C3713/NEMA SG3


Type

Rating (A)

Special Interrupting Rating


MC08 N1

800

50 kA

50 kA

42 kA

MC16 N1

1600

50 kA

50 kA

50 kA

Standard Interrupting Rating


MC08 H1

800

65 kA

65 kA

50 kA

MC16 H1

1600

65 kA

65 kA

50 kA

MC20 H1

2000

65 kA

65 kA

65 kA

MC32 H1

3200

65 kA

65 kA

65 kA

MC40 H1

4000

100 kA

100 kA

100 kA

MC50 H1

5000

100 kA

100 kA

100 kA

2
1995 Square DAll Rights Reserved

11/98

Advantages
Drawout Circuit Breaker Design
n The drawout assembly mechanism allows the circuit breaker to be racked in four positions

(connected, test, disconnected and withdrawn).


n The closing and opening push buttons, the racking handle and racking mechanism are accessible

06313005

06313004

06313003

through the front door cutout. Therefore the circuit breaker can be disconnected without opening
the door and accessing live parts. Safety shutters can be provided as an option for protection from
live parts when the circuit breaker is removed.

Connected Position

Test Position

Disconnected Position

True Two-step Stored Energy Mechanism


The closing time is less than five cycles. The circuit breaker is operated via a stored-energy
mechanism which can be manually or motor charged. Closing and opening operations can be initiated
either from the local push buttons on the circuit breaker front face or by remote control.
OCO cycle is possible without recharging.

Designed for No Maintenance...


The circuit breaker has fewer parts (by a factor of at least five) than conventional circuit breakers
while performing the same functions. This leads to greatly enhanced reliability and reduction in
maintenance. Under normal operating conditions, according to standards and controlled by tests, the
circuit breaker does not require maintenance.

But Exceeds Standards with an Easy and Reduced Maintenance

06313006

06313007

It is easy to remove the arc chutes and visually inspect the contacts and wear indicator. The operation
counter (spring-charging motor option) can also indicate when inspections and possible maintenance
should be done. After operating conditions exceeding those given by standards, it is possible to
extend the circuit breaker life by:
n Replacement of arc chutes and spring charging motor by the user.
n Replacement of main contacts by an after sale service team.
Note: See pages 6263 for additional information.

Contact Good
(Circuit Breaker Closed)

Contact Worn
(Circuit Breaker Closed)

3
11/98

1995 Square DAll Rights Reserved

Advantages
Single Design up to 6300 A
All frame sizes have been designed with the same technology featuring identical depth and door
cutouts, and common control units and accessories.

40-50

32

08-30

06313008

63

IG

LI

G
off

LIG

reset V

push to reset

LG

masterpact
I

I3

I2

I1
90%

push OFF

I
push ON

STR 58 U

tr

Ir

.92
.95 60

.9

.88

Io=3000A
%Ir

.98 30

.85

.8

xIo

cat. no. 54775

for masterpact
with sensors

Im

3
2
1.5

Ir fault

.3

.2

frame size 2000A

12

off

O OPEN

240

th :

.2
.1
0
off

Ih

600
800

500

th

th .4

.4
.3

.3

1000 .2
320
250

i
+S

.95

.7

.98

.6

.2
.1
off

Ic2.8

.93

.85
.9

.86

.8

T+

.1
2
on I t

1200

Ic1 .9
.85

test

N LM-8792

22

400

Im fault
tm

fault

Doles. Issue

NEMA

interrupting rating
amps
max RMS sym
Amps
Volts
100K
240
100K
480
65K
600

.3

17

xIn
tr

Ih

E63335
List.
UND. LAB. O
CIRCUIT BREAKER

00000

480
15
at 1,5Ir

.1
2
on I t

10

xIo

6
4

Im :

120

tm.4

In = 6000A

Ir :

circuit breaker
3 pole
600V 50/60Hz

discharged

20%

90
105

M08 H2

operation
cubical
suitable for continious
in a minimum
inches
at 100% rating
by W21 by D14.1/4
space H17.5 not required
ventilation is

50%

1
xIr

.95
1

.5
xIr

690V 50/60Hz
IEC 957-2 rating
interrupting
75KA
Icu 380/440V
75KA
660V
75KA
Icu 380/440V
75KA
660V
short time rating
sec.
Icw=75KA 0.5

test

connected
test
disconnected

Field-installable Accessories
n As the installation develops and changes, the circuit breaker can develop and change with it.

06313009

Most accessories are field-installable, without losing the UL Listing mark, without any adjustment
and with only the aid of a screwdriver.
n The uniform design of the circuit breaker line allows these accessories to be common for the
whole line.

Front Connection of Secondary Circuits

06313010

All accessory terminals are located on a connecting block which is accessible from the front even
with the circuit breaker in the test or disconnected position. This is particularly useful for field
inspection and modification.

4
1995 Square DAll Rights Reserved

11/98

Advantages
Disconnecting through Door
The racking handle and racking mechanism are accessible through the front door cutout.
Disconnecting the circuit breaker will therefore be possible without opening the door and giving
access to live parts.

Isolation Function by Positive Indication of Contact Status


The mechanical indicator is truly representative of the status of all three main contacts.

Segregated Compartment
Once the front cover has been removed to provide access to the auxiliary compartment, the main
contacts remain fully isolated. Furthermore, interphase partitioning allows full insulation between
each pole even if the front cover has been removed.

Reinforced Insulation

06313011

Two insulation barriers separate the front of the circuit breaker from main circuits.

5
11/98

1995 Square DAll Rights Reserved

Description

Description

06313012

4
5

13
12
6

11

1. Arc chamber and terminal covers


2. Accessories and control unit front
connecting block
3. Position carriage switches
4. Opening coils
5. Arc chute
6. Spring charging motor
7. Front cover
8. Control unit
9. Racking crank
10. Pull-out handgrip
11. Retractable rails
12. Handling handgrip
13. Safety shutters

10
9

11

Front View
1.
2.
3.
4.

06313013

12

IG

LI

G
off

LIG

reset V

push to reset

LG

1
LIN GERIN

MER

masterpact

I3

I2

I1

push OFF

90%

MP20
H1
r
circuit breake
3 pole
z
600V 50/60H

push ON

STR 58 U

frame size 2000A


operation
cubical
suitable for continious
in a minimum
inches
at 100% rating
by W21 by D14.1/4
space H17.5 not required
ventilation is

50%

O
OPEN

20%
tr

Ir

Io=3000A

90
%Ir
105

.92
.95 60

.9

.88

.98 30

.85

.8

xIo

cat. no. 54775

for masterpact
with sensors

Ir :

t
Ir fault

.1
0
off

Ih

600
800

500

th

400

i
+S

1200

Ic1 .9

.4
.3

.3

z
690V 50/60H
IEC 957-2 rating
interrupting
75KA
Icu 380/440V
75KA
660V
75KA
Icu 380/440V
75KA
660V
rating
short time
sec.
Icw=75KA 0.5

.2
.1
.1
2
on I t off

.8

T+

Ic2.8

.93
.95

.7

.98

.6

.85
.9

.86
.85

test

th .4

1000 .2
320
250

7.
8.

off

th :
Im fault
tm

fault

6.

22

xIn
tr

Ih

N LM-8792

17

Im :

.2

.1
2
on I t

12

E63335
List.
UND. LAB. O
CIRCUIT BREAKER
Doles. Issue

interrupting rating
amps
max RMS sym
Amps
Volts
75K
240
75K
480
75K
600
75KA
short time rating

.3

.2

10

xIo

00000

15
at 1,5Ir

6 .3

3
2
1.5

240

480

tm.4

In = 6000A

Im

120

discharged

5.

1
xIr

.95
1

.5
xIr

test

connected
test

9.
10.
11.
12.

Charging handle
Manual opening push button
Manual closing push button
Stored energy mechanism status indicator
(charged or discharged)
Main contact position indicator (open or
closed)
Disconnected position locking (key
interlock)
Disconnected position padlocking
Drawout position indicator showing that the
circuit breaker is in the connected, test or
disconnected position
Racking crank storage
Door escutcheon
Fault indicator and reset button
Open position locking (key interlock)

disconnecte

10

6
1995 Square DAll Rights Reserved

11/98

Control Units
06313014

The circuit breaker can be equipped with a microprocessor-based, electronic control unit which
provides all the traditional protection of the universal power circuit breaker (long-time, short-time,
instantaneous and ground-fault) plus other built-in functions:
n RMS sensing (standard)
n Alarm switch (standard)
n Overcurrent trip switch (standard)
n Interchangeable rating plugs (on STR28DP, STR38SP and STR58UP)
n Thermal memory and I2t ramp (standard on STR 38-58 control unit)
n Defeatable instantaneous (standard on STR 38-58 control unit)
n Zone-selective interlocking for ground-fault and short-time (option)
n Current and load meter (option)
n Load-monitoring outputs (option)
n Fault indicators (option)
n Communication ability (option)
Control Units

STR 18M

STR 28D

STR 38S

STR 58U

Basic Features
Long-time (1)

Short-time

Setting

Adjustable

Adjustable

Adjustable

Delay

Fixed

Fixed

Adjustable

Pickup

Adjustable

Adjustable

Delay

Adjustable

Adjustable

Adjustable

Fixed (2)

Adjustable (2)

Standard

Standard

Standard

Instantaneous

Adjustable

Test Receptacle

Additional Features (Options)


Ground-fault Protection (3)
Built-in Ammeter

Fault Indicators

Segregated Alarm Switch

Zone-selective Interlocking

Load Monitoring

Communication Outputs

(1) Long-time pickup at 1.1 current setting.


(2) Defeatable on N1 and H1 types.
(3) Two types: residual sensing (T) or residual source ground return (W).

7
11/98

1995 Square DAll Rights Reserved

06313015

Control Units
STR 28D Control Unit for General Application
1

push to reset

1. Mechanical pop-out type fault indicator and reset button:


n Indicates that a fault trip has occurred
n Prevents closing of the circuit breaker after fault until reset
2. Ammeter (LCD digital display)
3. Ammeter selector used to read:
n Phase currents (1, 2, 3, N)
n Or the phase with the highest load current (max.)
4. Load indication (bar graph in % of current setting)
5. Sensor rating
6. Rating plug (on STR 28DP)
7. Long-time current setting
8. Instantaneous pickup
9. Local and remote pre-trip alarm:
n LED on at 90% of current setting
n LED flashing on overload (1)
n Remote indication by static contact
10. Available spaces for setting identification
11. Test receptacle

2
I1

I2

I3

90%

STR 28 D
50%

3
4
5

20%
Ir
90

.9

.92
.95

.88

%Ir
.98

.85

105

6
7

.8

xIo
Im

2
1.5

xIr
t

10

Ir :
Ir

9
10

Overcurrent ProtectionRMS Sensing

Im :

Long-time

Current Setting

i
+

Rating Plug

11

test

06313016

STR 28DP: 0.8 to 1 x Rating Plug (Pickup at 1.1 x Setting)


STR 28D: 0.4 to 1 x Current Sensor (Pickup at 1.1 x Setting)

Im

Long-time Setting

Instantaneous

Max. Delay

Fixed: 7.5 sec. at 6 x Current Setting

Current Sensor

Plug Rating

250 A

250200150125 A

400 A

400300250200 A

600 A

600500400300 A

800 A

800600500400 A

1200 A

12001000800600 A

1600 A

160012001000800 A

2000 A

2000160012001000 A

2500 A

2500200016001200 A

3000 A

3000250020001600 A

3200 A

32003000250020001600 A

4000 A

40003200300025002000 A

5000 A

50004000320030002500 A

6300 A

630060005000400032003000 A

Pickup

1.5 to 10 x Current Setting

Built-in Ammeter (Optional)


Option I

Instantaneous

Values Displayed

Phase 1, 2, 3, Max., Neutral Current

Accuracy

1.5 % (2)

Bar Graph Indication

Phase 1, 2, 310% Steps

Control Power

Not Required (3)

Fault or Alarm Indicators


Not Discriminated

Local

Pop-out Type Indicator and LED Pre-trip Alarm

Remote

Overcurrent Trip and Pre-trip Alarm Switches


(see pp. 1415)

(1) According to time-current curves: between 105% and 120% of current setting.
(2) Total accuracy including current sensors: 4.5%.
(3) Control power not required for loads greater than 20% of current sensor. Required for load less than 20%
of current sensors if maximum demand memory requested (see diagram on p. 43).

Note: Io: Rating plug


In: Sensor rating
Ir: Long-time pickup
tr: Long-time delay
Im: Short-time pickup

tm: Short-time delay


I: Instantaneous pickup
Ih: Ground-fault pickup
th: Ground-fault delay

8
1995 Square DAll Rights Reserved

11/98

Control Units
06313017

STR 38S Control Unit for Selective Application


1

push to reset

2
I1

I2

3
4

I3

90%

STR 38 S

50%

6
7
8
9

20%
Ir
90

.9

.92
.95

.88

%Ir
.98

.85

105

.8

xIo
Im

tm

.4

6 .3

2
1.5

8
10

xIr
t

.3

10

.2

.2

.1
.1
0
on I2t off

11
12
13

Ir :
Ir fault

Im :
max.
tr

off

xIn

th :
Ih

Ih

500

fault

Im fault
tm

th

600
800

400
320
I

250

th
.3

.4

.4

14

.3

1000 .2
.2
.1
.1
1200
on I2t off

15
16

i
overcurrent

test
ground

18

F
test

17

19

1. Mechanical pop-out type fault indicator and reset button:


n Indicates that a fault trip has occurred
n Prevents closure of the circuit breaker after fault until reset
2. Ammeter (LCD digital display)
3. Ammeter selector used to read:
n Phase currents (1, 2, 3, N, ground)
n Or the phase with the highest load current (max.)
4. Load indication (bar graph in % of current setting)
5. Sensor rating
6. Local and remote pre-trip alarm:
n LED on at 90% of current setting
n LED flashing on overload (1)
n Remote indication by static contact
7. Rating plug (on STR 38SP)
8. Long-time current setting
9. Short-time pickup
10. Short-time delay
11. Instantaneous ON/OFF selector
12. Available space for setting identification
13. Ground-fault (option T) pickup
14. Ground-fault (option T) time delay
15. Local (option F) fault indicators consisting of built-in light emitting
diodes; fault indicators differentiate the three causes of tripping:
overload, short circuit and ground fault, if any
16. Test receptacle
17. Fault indicator saving battery (option PIL)
18. Fault indicator reset or battery test button
19. Fault indicator reactivating button (option PIL) (2)
Overcurrent ProtectionRMS sensing
Long-time

Current Setting

STR 38SP: 0.8 to 1 x Rating Plug (Pickup at 1.1 x Setting)

Delay

Fixed: 7.5 sec. at 6 x Current Setting

06313018

STR 38S: 0.4 to 1 x Current Sensor (Pickup at 1.1 x Setting)

Thermal Memory as Standard


Rating Plug

4 to 6 Rating Plugs Available Per Sensor Rating: See STR 28D Control Unit, p. 8

Short-time

Pickup
Delay Bands

Long-time Setting

1.5 to 10 x Current Setting


00.10.20.30.4 with I2t OFF
0.10.20.3 with I2t ON

Instantaneous

Pickup

High-set Fixed Type (3)Defeatable on N1 and H1 Types

Ground-fault Protection (Option T or W) (4)

Ground-fault
Pickup
Ground-fault
Delay

Short-time
Pickup

Pickup

0.1 x Current Sensor to 1200 A (5)

Delay Band

0.10.20.30.4 with I 2t Ramp ON/OFF Switch

Fault Indicators (Option F)


Not Discriminated

Short-time Delay

Discriminated
Instantaneous

Local

Mechanical Pop-out Type Indicator and LED Pre-trip Alarm

Remote

Overcurrent Trip and Pre-trip Alarm Switches (see pp. 1415)

Local

With Option F (see p. 14)

Built-in Ammeter (Option I)


Values Display

Phase 1, 2, 3, Max., Neutral and Ground Current

Accuracy

1.5% (6)

Bar Graph Indication Phases 1, 2, 310% steps


Control Power

Not Required (7)

(1) According to time current curves: 105% to 120% of current setting.


(2) With PIL option, fault indicator lights (15) will light up only when this button is pushed in.
(3) See values on pp. 3840.
(4) Residual scheme (T). The maximum ground-fault pickup meets 1999 National Electrical Code paragraph
230-95 (a) (not exceeding 1200 A). Source Ground Return scheme (W) on request.
(5) 0.1 minimum pickup requires 24 Vdc external power.
(6) Total accuracy including current sensors: 4.5%.
(7) Control power not required for loads greater than 20% of current sensor. Required for loads less than
20% of current sensor if maximum demand memory requested (see diagram, p. 43).

9
11/98

1995 Square DAll Rights Reserved

06313019

Control Units
V

push to reset

reset V

I+T

L+I

off

L+I+T

1
2

L+T

3
I1

I2

I3

90%

STR 58 U

6
7
8
9
10
11

50%

20%
Ir
90

tr

.88

120
.92
.95 60

.85

.9

.98 30

240

%Ir
105

.8

Im

norm
min.

tr

tm

.4

6 .3

2
1.5

Ir :

12

.2

.1
.1
0
on I2t off

10

12

.3

.2

xIr
I

480
15
at 1.5Ir

xIo

13
14
15

14

19

Ir fault

Im :

22
Max.

2
tr

21

xIn
Ih 1200A Max th

th :

Ih
fault

Im fault
tm

th

i
overcurrent

test

22
23

F
test

.4

600
800

320
250

1000 .2
.2
.1
.1
1200
on I2t off

Ic1

.93
.95

.7

.8

.98

.6

xIr

16
17

.3

.3

Ic2

.9

.86
.85

ground

.4

500
400

.85
.9

.8

.95
.5

xIr

18
19
20

STR 58U Control Unit for Universal Application


1. Mechanical pop-out type fault indicator and reset button:
n Indicates that a fault trip has occurred
n Prevents closure of the circuit breaker after fault until reset
2. Switch selector for the type of fault to be remotely indicated and reset
flat push button (see option FV, p. 15)
3. Ammeter (LCD digital display)
4. Ammeter selector used to read:
n Phase currents (1, 2, 3, N, ground)
n Or the phase with the highest load current (max.)
5. Load indication (bar graph in % of current setting)
6. Sensor rating
7. Local and remote pre-trip alarm:
n LED on at 90% of current setting
n LED flashing on overload (according to time current curves: 105%
to 120% of current setting)
n Remote indication by static contact
8. Rating plug (on STR 58UP)
9. Long-time current setting
10. Long-time delay setting
11. Short-time pickup
12. Short-time delay
13. Thermal memory min./max. selector
14. Instantaneous pickup
15. Ground-fault (option T or W) pickup
16. Ground-fault (option T or W) time delay
17. Available space for setting identification
18. Load monitoring (option R) pickups (see p. 16)
19. Test receptacle
20. Fault indicator saving battery (option PIL)
21. Local (option F) fault indicators consist of built-in light emitting diodes
which differentiate the three causes of tripping: overload, short circuit
and ground fault, if any
22. Fault indicator reset or battery test button
23. Fault indicator reactivating button (with PIL option, fault-indicator
lights (21) will only light up when this button is pushed in)

10
1995 Square DAll Rights Reserved

11/98

06313020

Control Units
t

Overcurrent ProtectionRMS Sensing


Long-time

Current Setting

STR 58UP: 0.8 to 1 x Rating Plug (Pickup at 1.1 x Setting)


STR 58: 0.4 to 1 x Current Sensor (Pickup at 1.1 x Setting)

Delay Bands

Long-time Pickup

0.941.883.757.501530s at 6 x Current Setting

Thermal Memory as Standard with Min./Max. Selector


Rating Plug
Long-time Delay

Ground-fault
Pickup
Ground-fault
Delay

Short-time Pickup
Short-time Pickup

Instantaneous Pickup

Short-time

Current Sensor

Plug Rating

250 A

250200150125 A

400 A

400300250200 A

600 A

600500400300 A

800 A

800600500400 A

1200 A

12001000800600 A

1600 A

160012001000800 A

2000 A

2000160012001000 A

2500 A

2500200016001200 A

3000 A

3000250020001600 A

3200 A

32003000250020001600 A

4000 A

40003200300025002000 A

5000 A

50004000320030002500 A

6300 A

630060005000400032003000 A

Pickup

1.5 to 10 x Current Setting

Delay bands

00.10.20.30.4 with I2t OFF


0.10.20.3 with I2t ON

Zone-selective Interlocking with Option Z (see p. 13)


Instantaneous

Pickup

Adjustable from 2 to Max. Value (1); Defeatable on N1 and


H1 Types

Ground-fault Protection (Option T or W) (2)


Pickup Delay Band

0.1 x Current Sensor to 1200 A (3)


0.10.20.30.4 with I2t Ramp ON/OFF Switch
Zone-selective Interlocking with Option Z (see p. 13)

Fault Indicators (Option F)


Not Discriminated

Discriminated

Local

Mechanical Pop-out Type Indicator and LED Pre-trip Alarm

Remote

Overcurrent Trip and Pre-trip Alarm Switches (see pp. 1415)

Local

With Option F (see p. 14)

Remote

With Option FV (see p. 15)

Built-in Ammeter (Option I)


Values Display

Phase 1, 2, 3, Max., Neutral and Ground Current

Accuracy

1.5% (4)

Bar Graph Indication Phase 1, 2, 310% Steps


Control Power

Not Required (5)

Load Monitoring (Option R)


Inverse Time Alarm

Pickups

Ic1 = 0.8 to 1 x Current Setting


Ic2 = 0.5 to 1 x Current Setting

Time delay

See Curve, p. 41

Outputs for Communication through DIGIPACT System (Option C)


Transmitted Values

Entire Settings of the Trip Unit


Circuit Breaker Status: Open, Tripped, Closed
Alarms: Overload, Type of Fault, Internal Watchdog (6)
Ammeter Values: Phase, Neutral, Ground, Max. Currents

(1) See values on pp. 3840.


(2) Residual scheme (T). The maximum ground-fault pickup meets 1999 National Electrical Code paragraph
230-95 (a) (not exceeding 1200 A). Source Ground Return scheme (W) on request.
(3) 0.2 minimum pickup only with external power.
(4) Total accuracy including current sensors: 4.5%.
(5) Control power not required for loads greater than 20% of current sensors. Required for loads less than
20% of current sensor if maximum demand memory requested (see diagram, p. 43).
(6) Internal watchdog: Control unit internal temperature.

11
11/98

1995 Square DAll Rights Reserved

06313182

Control Units
Thermal Memory

push to reset

Purpose
The thermal memory function allows an optimization of cables or bus bar protection in case of low
amplitude repetitive faults. Such faults can be due to repetitive motor startings, fluctuating load or
subsequent closing after a fault.

I1 I2 I3
90%

STR 58 U

50%

Traditional electronic protection has no effect when facing such repetitive faults because the
duration of each overload above the pickup setting is too short to achieve effective tripping.
Nevertheless, each overload involves a temperature rise in the installation, the cumulative effect of
which could lead to overheating of the system.

20%

Ir
xIn

tr
xIo

Im

at 1.5Ir
tm

xIo
t

Principle

I
xIn
Ih

i Ic1

th

Ic2

DANGER

xIn

HAZARD OF ELECTRICAL SHOCK, BURN


OR EXPLOSION.

test
xIr

xIr

test

Use "min" position for emergency only when


closing on fault is absolutely necessary.
Failure to observe these precautions will
cause death, personal injury or electrical
shock.

06313184

06313183

The thermal memory function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay
and, therefore, the reaction of the control unit will be closer to the real heating of the power network
system. After tripping, the memory will also reduce the time delay when closing the circuit breaker
on fault.
I

Temperature

Pickup Setting

STR Trip Units

06313185

06313186

The STR 38S and STR 58U trip units incorporate the thermal memory as standard:
n Before tripping on long-time and ground-fault protection (if provided)
n After tripping on long-time protection only, adjustable min./max. position for the STR 58U trip unit
is standard
The control unit measures the internal temperature rise of the circuit breaker by thermal resistors. The
cooling time constant of the memory is not fixed, but depends on the over-temperature condition.
I2 t

I 2t

Trip Level

Trip Level

STR Trip Unit with


Thermal Memory

STR Trip Unit without


Thermal Memory

12
1995 Square DAll Rights Reserved

11/98

06313021

Control Units
Neutral Sensor

Main Circuit Breaker

T1

T2

S1

S2

06313023

Ground-fault protection may be applied on


34W or 33W circuits. On 34W circuits an
external neutral sensor must be used. This
neutral current sensor must have the same
ampere rating as the circuit breaker sensor.

Neutral

Ground-fault
Neutral CTs

S1

T1

S2

T2

Zone-selective Interlocking (ZSI)


Option Z on the STR58U control unit provides
selective interlocking on short time or ground
fault. A pilot wire links several trip units in the
distribution network, as shown in the opposite
figure. In the event of a fault, the trip unit will
respond to the preset delay only if receiving a
signal from the downstream unit. If not receiving
a signal, the tripping will be instantaneous.
Therefore, the fault is cleared instantaneously
by the nearest circuit breaker: the thermal
stresses (I2t) in the network are minimized,
without any effect on the correct time-delay
coordination in the installation.

Note: #18 to #14 AWG cables, max. length 90 ft./30m.

06313022

Z12
Z11
Z22 Out
Z21 In

Fault 1
Circuit breaker A will clear the fault
instantaneously, regardless of its time-delay
setting.

Z12
Z11 Out
Z22
Z21 In

Z12
Z11 Out
Z22
Z21 In

Z12
Z11
Z22
Z21

Out
In

Z12
Z11
Z22
Z21

Out
In

Z12
Z11 Out
Z22
Z21 In

Fault 2
Circuit breaker B will inform upstream circuit
breaker A that it is clearing the fault and will
prevent it from tripping instantaneously. Circuit
breaker A will trip at the end of its time delay
setting if the fault is not cleared during this time.

Note:
n Drawout circuit breaker terminals are
delivered with "in" terminals jumpered.
Remove the jumper when interlocking with a
downstream circuit breaker.
n The MASTERPACT circuit breaker may also
be interlocked with COMPACT NS and CK
type molded case circuit breakers with ZSI
option.
n Do not ground ZSI wiring.
Cable Size

#18#14 AWG/1.5mm2

Max. Length

90 ft./30 m

Wiring

Twisted in Pairs One Turn per 4 in./10 cm

No. of Circuit Breakers

Upstream: 2
Downstream: No Limit

13
11/98

1995 Square DAll Rights Reserved

Fault Indicator (F)

push to reset

I1 I2 I3
90%

STR 58 U

50%

20%

Ir

tr
xIo

Im

at 1.5Ir
tm

xIo
t

i Ic1

06313025

xIn
Ih

th
xIn
Ic2

24 Vdc
1W

06313027

In addition to the mechanical fault indicator, this indicator differentiates the three causes of tripping:
overload, short circuit or ground fault, if any. Three light-emitting diodes indicate separately longtime, short-time/ instantaneous and ground-fault trip. A flat push button allows resetting of the
indicator after tripping. A separate power supply is required to maintain the indication after tripping
of the circuit breaker. Two different possibilities are offered:
n Connecting a reliable 24 Vdc control voltage on F1-F2. Auxiliary power module (AD) is used for
other voltages. When the control source is considered as unreliable, a battery pack (BAT) is to
be added to an AD power module.
n From a built-in battery module. When no external control source is available, a built-in battery
module may be ordered (option PIL). This module integrates battery testing and indicator
reactivating buttons.
06313026

06313024

Control Units

AD (1)

test
xIr

xIr

AD (1)

test

BAT
+

F1

F2

F1

F2

F1

F2

(1) AC: 120 V, 60 Hz


DC: 2448125 Vdc

Configuration with Reliable


Control Voltage

Configuration with
Interruptible Control Voltage

06313028

Alarm Indicator Pre-trip Alarm Switch (ALR)


push to reset

Delivered as standard with control unit. The alarm indicator is a fixed, front face light-emitting diode
which operates as follows:
n Fixed when the current exceeds 90% of the current setting.
n Flashing on overload: according to time-current curves, 105% to 120% of current setting.
The pre-trip alarm switch is a static contact which closes when in the overload zone, up to the
tripping of the circuit breaker. This contact can be used for ultimate load shedding, alarm before
tripping, etc.

I1 I2 I3
90%

STR 58 U

50%

ALR

20%

Ir

tr
xIo

Im

at 1.5Ir
tm

Output Characteristics

0.1 A/240 Vac (Optical Triac)

Power Supply

Not Required

xIo
t

I
xIn
Ih

i Ic1

th

Ic2

xIn

test
xIr

xIr

test

14
1995 Square DAll Rights Reserved

11/98

Control Units
Overcurrent Trip Switch (SDE)

06313029

Delivered standard with control unit. In addition to the fault trip indicator/reset button, one SPDT
switch provides alarm/lockout information. This SPDT switch is operated only when the circuit
breaker is tripped by the control unit. When the circuit breaker is reset, the "a" switch (alarm) is
open and the "b" switch (lockout) is closed.
Output Characteristics

SPDT 10 A/240 Vac

Power Supply

Not Required

Fault
82

84

SDE

81

V
06313030

Segregated Trip Switch (FV)


push to reset

This switch works exactly as the standard overcurrent trip switch (SDE) except that a commutator
on the front face is used to choose the type of fault which will operate the contact: overload, shortcircuit, ground-fault, or any combination of these types. This option can be used in addition to the
SDE switch for remote signalization of particular types of faults. A flat push button allows resetting of
the indicator after tripping.

I1 I2 I3
90%

STR 58 U

50%

Output Characteristics

5 A/240 Vac

Power Supply

Required

20%

tr
xIo

Im

at 1.5Ir
tm

Wired in parallel with the remote opening button which operates the shunt trip, the option FV
contact provides an electrical interlock which prevents the circuit breaker from being closed after the
pre-selected type of faults: for example the circuit breaker will be able to be remotely closed after
overload, but not after short circuit.

xIo
t

i Ic1

th

Ic2

xIn

test
xIr

xIr

06313031

xIn
Ih

06313032

Ir

Fault

Remote
Open

Fault

test

V2

C2

V2

MX

V
V

V1

V1

C1

15
11/98

1995 Square DAll Rights Reserved

06313033

Control Units
Load monitoring (R)

push to reset

Option R provides two independent static contacts which operate when the current exceeds
adjustable pickup limits:
n When the current exceeds the limit Ic1 (or Ic2), the contact C-R1 (or C-R2) closes following an
inverse time characteristic A.
n When the current drops below the limit Ic1 (or Ic2), the contact C-R1 (or C-R2) opens with
constant time delay (10 seconds) B.
These contacts can be used for load shedding, alarms, indications, etc.

I1 I2 I3
90%

STR 58 U

50%

20%

Ir

tr
xIo

Im

at 1.5Ir
tm

Voltage

240 Vac max.

Outputs

0.1 A triac

xIo
t

xIn
Ih

i Ic1

th

Ic2

06313034

xIn

Long-time

test
xIr

xIr

test

Test Kits

06313036

06313035

Every control unit is equipped with a test receptacle that can be used with a test kit. Tests
performed by test kits are only functional tests designed to electrically test the operating integrity of
the control unit, the flux transfer device and the mechanical operation of the circuit breaker. Tests
are not designed to calibrate the circuit breaker. Calibration can only be done at the factory.

Mini Test Kit

Calibration Test Kit

16
1995 Square DAll Rights Reserved

11/98

Control Units
Communication
MASTERPACT circuit breakers can be easily connected to a supervising personal computer using
the DIGIPACT system. The following four functions can thus be provided:
n Indication:
o Status of the circuit breaker (on, off or tripped; connected or disconnected)
o Causes of tripping (overload, short circuit or ground fault)
n Monitoring:
o Operation of circuit breaker (open, closed or reset)
o Resetting a molded case circuit breaker (COMPACT NS and CK)
n Management:
o Control unit settings
o Pre-trip alarm
o Load monitoring status
o Control unit internal temperature alarm
o Number of operation cycles performed by the circuit breaker
n Metering:
o RMS value of the current in three phases

06313037

Communication with Supervision,


Personal Computer

MODBUS /JBUS

IN
LIN GER
MERSV
pulsar

JBus
BBus
com
24V

OK
error

1 3

com
error

DIGIPACT DC150
Data Concentrator

POWERLOGIC
Circuit Monitor

POWERLOGIC
Power Meter

N1
N1

Internal Bus

SC150 Indication and


Control Interface

SC150 Indication and


Control Interface

push
to
trip

push
push

COMPACT NS Circuit Breaker


with Communications-type
Auxiliary Switches, Motor
Operator and Carriage Switches

GERIN
MERLIN
9
multi
ATB1s

MASTERPACT Circuit Breaker


with STR 58U Trip Unit and
Communications Option

MASTERPACT Circuit Breaker


with STR 58U Trip Unit and
Communications Option

ATB MULTI 9 Interface


for C60 with Motor Operator

17
11/98

1995 Square DAll Rights Reserved

Control Units

06313038

SC150 Indication and Control Interface


Function
The SC150 indication and control interface is used to:
n Transmit to the DC150 data concentrator:
o Status information (on, off, tripped, tripped due to electrical fault, tripped due to ground fault)
for COMPACT CK and MASTERPACT circuit breakers or any other power circuit actuator
o The connected or disconnected status of withdrawable COMPACT CK and MASTERPACT circuit
breakers
o The status of any external contact
n Receive commands transmitted by a personal computer or programmable logic controller (PLC)
via the DC150 data concentrator (on, off and reset of the COMPACT CK and MASTERPACT
circuit breakers or any other power circuit actuator)
n Receive the information transmitted by the communications option on electronic control units
(STR43, STR53, STR55 and STR58) installed in COMPACT NS, COMPACT CK and
MASTERPACT circuit breakers:
o Trip-unit settings
o The RMS value of the current in the three phases and the neutral
o Current overloads
o The causes of tripping (overloads, short circuits or ground fault)
n Count the number of cycles carried out by the device
The SC150 interface is connected to:
n The DC150 data connector
n The auxiliary switches (OF, SD, SDE, SDV, CE, CD) on the circuit breaker with which the interface
is associated
n The motor operator for execution of the on, off and reset commands
n The communications outputs of the STR43, STR53, STR55 and STR58 control units installed in
COMPACT NS, COMPACT CK and MASTERPACT circuit breakers
A non-assigned digital input is available for other use. The SC150 interface is associated with a
single circuit breaker.
Important: The SC150 interface is used with COMPACT NS circuit breakers to:
n Remote to the user the information supplied by the communications option on STR43 and STR53
control units
n Actuate non-communicating motor operators
n Count the number of cycles carried out by the circuit breaker

Note: When associated with the SC150 interface, COMPACT NS circuit breakers are equipped with
standard auxiliary switches and motor operators. The SC150 indication and control interface is not
required with COMPACT NS circuit breakers equipped with communication-type auxiliary switches
or a communication-type motor operator.
Information or Function Managed by the SC150 Indication and Control Interface
Information Transmitted or
Function Carried Out

Devices Associated with the SC150 Interface

Display Device Status:


n On, Off
n Tripped
n Tripped Due to Electrical Fault
n Tripped Due to Ground Fault
n Connected or Disconnected Position

Circuit Breaker or Other Power-circuit Actuator


+ Standard OF Auxiliary Switches
+ Standard SD Auxiliary Switches (COMPACT Circuit Breakers)
+ Standard SDE Auxiliary Switches
+ SDV Auxiliary Switches (COMPACT NS) or Output Contact of a Ground-fault Relay
+ Standard CE and CD Auxiliary Switches

Remotely Control a Device (On, Off or Reset)

COMPACT or MASTERPACT Circuit Breaker Equipped with Standard Motor Operator

Count the Number of Operating Cycles

As Above

Display the Cause of Tripping and the


Trip Unit Settings (Settings and Time Delays)

COMPACT or MASTERPACT Circuit Breaker Equipped with STR43, STR53, STR55


or STR58 Electronic Trip Unit with Communications Option (COM)

Trip an Alarm for Long-time Fault

As Above

Display the Value of the Current for Each Phase

As Above

Display Internal Temperature of Switchboard

PT100 Probe 4 to 212F (20 to 100C)

18
1995 Square DAll Rights Reserved

11/98

Control Units
SC150 Indication and Control Interface (continued)
Technical Data
Digital Inputs (24 V, Self-powered by the SC150 Interface)
O Auxiliary Switch

One Input

F Auxiliary Switch

One Input

SD Auxiliary Switch (Tripping)

One Input

SDE Auxiliary Switch (Tripping Due to Electrical Fault)

One Input

CE Auxiliary Switch

One Input

CD Auxiliary Switch

One Input

SDV Auxiliary Switch (Tripping Due to Ground Fault)

One Input

Other Uses

One Unassigned Input

Electrical Characteristics
Voltage (Supplied by SC150)

24 Vdc

Current (Supplied by SC150)

120 mA dc

Resistance in On-state

< 30 m

Resistance in Off-state

> 10000 M

Control Outputs
Opening

One N.O. and N.C. Control Terminal

Closing

One N.O. Control Terminal

Reset

One N.O. Control Terminal


Note: The opening, closing and reset control signals delivered by
the SC150 interface are of the impulse type. The pulse
duration is one second for the closing signal and two
seconds for the opening and reset signals.

Voltage

100440 Vac/24250 Vdc

Interrupting Rating

AC

2500 VA

DC

300 W Continuous/500 W for Two Seconds

Utilization Category

AC15/DC13 as Defined by IEC 947-5

Operating Temperature Range

13 to 158F (25 to 70C)

Storage Temperature Range

67 to 185F (55C to 85C)

Damp Heat Not in Operation (IEC 68-2-30)

6 cycles 77F (25C)/131F (55C)/RH 95%

Damp Heat in Operation (IEC 68-2-56)

2 days 86F (30C)/RH 93%

Salt Mist (IEC 68-2-52)

Kb Test, Severity Level 2

Electromagnetic Compatibility

Electrostatic Discharges
(IEC 1000-4-2)

Level 3

Radiated Susceptibility
(IEC 1000-4-3)

Level 3

Low-energy Conducted
Susceptibility (IEC 1000-4-4)

Level 4

High-energy Conducted
Susceptibility (IEC 1000-4-5)

Level 4

Conducted and Radiated


Emissions (EN 50081-1)

Class A

Dimensions

2 x 4 x 6.5 in. (50 x 105 x 165 mm)

Weight

2.5 lb. (1 kg)

Degree of Protection (as Per IEC 529)

Vibrations (Lloyds 1996)

Front Face

IP30

Other Faces

IP30

Connections

IP20

Fc Test

513.2 Hz: .04 in. (1 mm)


13.2100 Hz: .03 oz. (0.7 g)

Wiring Diagram
See p. 44

Dimensions
See pp. 61

19
11/98

1995 Square DAll Rights Reserved

Control Units
06313039

DC150 Data Concentrator


Function
The DC150 data concentrator is used to:
n Centralize all the information supplied by the various communicating devices:
o Auxiliary switches and motor operator
o SC150 indication and control interface
n Make information available to a personal computer or programmable logic controller (PLC) via the
MODBUS/JBUS protocol
n Log status changes and tripping of the communicating circuit breakers in order to provide the
user with a list of time-stamped events
n Supply the 24 V and 15 V power required by the communicating devices and the internal bus
n Carry out addressing for the communicating devices
Each DC150 data concentrator can be connected to a maximum of 48 instrumented outgoing or
incoming circuits.
Information or Function Managed by the DC150 Data Concentrator
Information Transmitted or
Function Carried Out

Devices Required to Display the Information or


Carry Out the Function

Display Device Status:

Circuit Breaker or Other Power-circuit Actuator

On, Off, Tripped, Tripped Due to Electrical Fault,


Connected, Disconnected

o
o

Tripped Due to Ground Fault

COMPACT NS Circuit Breaker + Communicating Auxiliary Switches


COMPACT/MASTERPACT Circuit Breaker + SC150 Indication and Control
Interface
COMPACT NS Circuit Breaker + Communicating Auxiliary Switches
MULTI 9 Control Device + ATB Interface
COMPACT NS Circuit Breaker + Vigi or Ground-fault Relay + SC150
Indication and Control Interface

Remotely Operate a Circuit Breaker


(On, Off or Reset)

Inhibit Reset Following Tripping Due


to Electrical Fault

As Above

Select Operating Mode of Motor


Operators (Local or Remote)

As Above + CLS150 Indication and Local Control Module

Measure Currents (Phases and Neutral)

COMPACT/MASTERPACT Circuit Breaker Equipped with Electronic Control Unit


Comprising Communications Option + SC150 Indication and Control Interface

Count Number of Operating Cycles

SC150 Indication and Control Interface

Display Causes of Tripping

COMPACT/MASTERPACT Circuit Breaker Equipped with Electronic Control Unit


Comprising Communications Option + SC150 Indication and Control Interface

Display Trip Alarm for Long-time Fault

As Above

Display Trip Unit Settings


(Thresholds and Time Delay)

As Above

COMPACT NS Circuit Breaker + Communicating Motor Operator


COMPACT/MASTERPACT Circuit Breaker + SC150 Indication and Control
Interface
n MULTI 9 Control Device + ATB Interface
n

Accessories
Connection

Junction Block for Internal Bus

Cat. No. 50778

RS485/RS232 Conversion Unit

Cat. No. 50786

Junction Block

06313042

06313116

06313040

RS232/RS485 Converter

Cat. No. 50779 65 ft. (20 m)


or 50780 330 ft. (100 m)

An RS232/RS485 converter is required for connection to a personal computer


equipped with an RS232 output to the MODBUS/RS485 bus.

06313041

Connection to Personal Computer

Cable for Internal Bus

Connector

Internal Bus Cable

20
1995 Square DAll Rights Reserved

11/98

Control Units
DC150 Data Concentrator (continued)
1

06313043

Description

1.
2.
3.
4.

MERLIN GERIN
Digipact

DC150

BBus

JBus

OK

com

com

error

24V

error

5.

9600
19200

456
23

78 9

CD E

N2

AB

N1

CD E

15

78 9

AB

456
23

16

N1
N2

8
9

14
10

13

12

11

6.
7.
8-9.
10.
11.
12.
13.
14-15.
16.

LED indicating that address is correct


LED indicating that address is incorrect
LED indicating presence of 24 V power
LED indicating communication on
internal bus
LED indicating MODBUS/JBUS
communication
LED indicating MODBUS/JBUS error
MODBUS/JBUS speed setting
Coding wheels for JBUS address
JBUS connector
Power supply connector
Internal bus connector
Confirmation button
Keys for DIGIPACT module addresses
Address display

Technical Data
Electrical Characteristics
Voltage

110240 Vac/115125 Vdc

Tolerance

+10%15%

Operating Temperature Range

13 to 158F (25 to 70C)

Storage Temperature Range

67 to 158F (55 to + 70C)

Electromagnetic Compatibility

Electrostatic Discharges

Level 3
(IEC 1000-4-2)

Radiated Susceptibility

Level 3
(IEC 1000-4-3)

Low-energy Conducted

Level 4
Susceptibility (IEC 1000-4-4)

High-energy Conducted

Level 4
Susceptibility (IEC 1000-4-5)

Conducted and Radiated

Class A
Emissions (EN 50081-1)

Protocol

MODBUS/JBUS (Slave)

Speed

9600 or 19200 Baud

Data Format

Eight Bits, No Parity, One Stop

Physical Link

RS485 (2-Wire or 4-Wire)

Implemented MODBUS/JBUS Protocol Functions

Read N Consecutive Bits

Function 1 or 2

Read N Words

Function 3 or 4

Write One Bit

Function 5

Write One Word

Function 6

Write N Bits

Function 15

Write N Words

Function 16

Weight

4 lb. (1.5 kg)

Degree of Protection (as Per IEC 529)

IP30
IP20 (Connections)

Wiring Diagrams
See p. 45

Dimensions
See p. 61

21
11/98

1995 Square DAll Rights Reserved

Control Units
Sizing of the DIGIPACT Internal Bus
Sizing of the DIGIPACT internal bus depends on two factors:
n The number of devices on the bus
n The length of the bus

Number of Devices
As on any communications network, the number of devices that may be connected on the
DIGIPACT internal bus is limited. The maximum number of devices is calculated in terms of
"communication points." Each type of device represents a number of points indicated in the table
below. The total number of points for the various devices connected to a single bus must not exceed
100. If the required devices represent more than 100 points, simply add a second DIGIPACT
internal bus with a second DC150 data concentrator. The same sizing rules apply to the second bus
as well.
Communicating Device

Number of Points

DC150 Data Concentrator

Communicating Auxiliary Switches OF, SD, SDE for COMPACT NS Circuit Breakers

Communicating Motor Operator and Auxiliary Switches for COMPACT NS Circuit Breakers

Communicating Auxiliary Switches CE and CD for COMPACT NS Circuit Breakers

SC150 Indication and Control Interface

CLS150 Indication and Local Control Module Associated with:


n Communicating Auxiliary Switches
n Communicating Motor Operator and Auxiliary Switches
n SC150 Indication and Control Interface

0
0
0

PM150 Power Meter

ATB MULTI 9 Interface

Length of Bus
The table below indicates the cross-sectional area of the cable that must be used depending on the
total length of the bus.
Cross-sectional Area

Maximum Length of Bus

0.03 in.2 (0.75 mm2)

660 ft. (200 m)

0.06 in.2 (1.5 mm2)

1310 ft. (400 m)

0.1 in.2 (2.5 mm2)

2300 ft. (700 m)

The total resistance of the two wires for the bus must be less than 12 ohms. If the bus is too long,
simply:
n Increase the cross-sectional area of the cable.
n Create two shorter buses for the installation (in this case, a second DC150 data concentrator
is required).

22
1995 Square DAll Rights Reserved

11/98

Accessories
Location
Disconnected
Position
Switches

Terminal
Block

Connected
Position
Switches

Overcurrent
Trip Switch

06313046

Auxiliary
Switches

Opening Coil
Closing Coil

Heavy Usage
Auxiliary
Switches
Ready to
Close Switch
V

I+T

off

L+I+T

reset V

push to reset

L+I

L+T

I3

I2

I1
90%

STR 58 U
50%

20%
tr

Ir

.98 30

.85

%Ir

.8

105
Im

xIo

2
1.5

norm
min.

tr

I
8

Im :

tr

th :

Ih

th

19
22

320
250

i
overcurrent

Max.

xIn
.4

.4

.1
2
on I t

.1
off

.3

.3

.2

1000 .2
1200

A
Ic2

Ic1.9
.86

.8

th

800

.85

test

Spring
Charging
Motor

0
off

14

500
400

.2
.1

.2
.1
2
on I t

Ih 1200A Max
600

Im fault
tm

fault

480

.3

6 .3
8
10

xIr

12

Ir :
Ir fault

15
at 1.5Ir

tm.4

CTED

240

120
.92
.95 60

.9

.88

90

D
CONNECTE
TEST
DISCONNE

.93
.95

.7

.98

.6

xIr

R
.85
.9

.8

.95
.5

xIr

ground

F
test

Secondary Disconnects
Electrical accessories are UL Listed for field installation per UL file E113554. They are provided with
terminals and located on secondary disconnecting blocks above the circuit breaker:
n Fixed-mounted: By one or two connecting plugs (provided).
n Drawout-mounted: To terminal block A located in the front of the stationary assembly for easy
access. (This terminal block is then wired to another connection block B that operates
automatically to isolate the internal accessories when the circuit breaker is in the disconnected
position.)

06313010

06313044

Fixed-mounted Circuit Breaker

Drawout-mounted Circuit Breaker

Additional Connections (BS):


Single connection only is allowed in the terminal block. Multiple connections have to be made by
adding extra terminals in the block located on the stationary assembly. The BS option consists of
five additional terminals.
Connection:
Accessory terminals are maintenance-free and may be connected by standard #18 to #14 AWG
copper wires. Cable strip length: 3/8 in. (10 mm).

23
11/98

1995 Square DAll Rights Reserved

Accessories
The MASTERPACT circuit breaker is equipped with a true two-step stored energy mechanism which
ensures fast opening and closing operations and complete open-close-open sequence without
recharging the mechanism. The MASTERPACT circuit breaker has manual actuators that include a
charging handle and push-to-open and push-to-close buttons. In addition, remote operation is
possible with the following field-installable accessories:
n Spring charging motor (MCH)
n Closing release (XF)
n Undervoltage trip device (MN) or shunt trip (MX) for opening
The manual operating mechanism can still be used in an emergency. The addition of the electrical
operating mechanism does not alter circuit breaker dimensions.
06313047

Spring-charging Motor (MCH)


The spring-charging motor automatically charges the stored energy mechanism (when the circuit
breaker closes) making OCO cycles possible without recharging. Opening and closing operations
are instantaneous.
Control Voltage (V)

06313048

Consumption

60 Hz

120240

DC

2448125

AC

180 VA

DC

180 W

Inrush Current

2 to 3 x In for 0.1 sec.

Charging Time

3 to 4 sec.

Spring
Charged
262

B4

CH

B1

Operation Counter (CDM)


With spring-charging motor option only. The operation counter is read from the front and gives the
total number of circuit breaker operating cycles.

Spring-charged Switch
This type "b" switch is closed when the spring is charged. It comes standard with the spring
charging motor and is provided with a common terminal.
Max. Current (A)
60 Hz

240 V

10

DC

125 V

0.5

250 V

0.25

24
1995 Square DAll Rights Reserved

11/98

06313049

Accessories
Closing Coil (XF)

06313050

This device releases the circuit breaker closing mechanism when the spring is charged. The closing
coil is rated for continuous duty. The closing release is supplied on request and can be fitted even
on a manual operating mechanism.

Remote
Close
A4

XF

A1

Anti-pumping Function
When the closing coil (XF) is permanently energized, the circuit breaker remains in the open
position after it has been opened, either by manual or electrical operation. The circuit breaker can
only be closed if the closing coil is momentarily de-energized (see p. 32).
Note: This anti-pumping function can be disabled by series connecting a ready-to-close ("b" contact)
switch (PF) to the closing coil.
Circuit Breaker Closing Time

Less Than 80 ms

Operating Voltage Range

0.85 to 1.1 x Rated Voltage

Control Voltage (V)

60 Hz

Consumption (Inrush and Sealed)

120240

DC

2448125

60 Hz

20 VA

DC

15 W

25
11/98

1995 Square DAll Rights Reserved

Accessories
Opening Coils
Three types of voltage releases can be used for remote opening of the circuit breakers:
n Shunt trip (MX)
n Instantaneous undervoltage trip device (MN)
n Time-delayed undervoltage trip device (MNR)
Possible Combinations

06313049

Each MASTERPACT circuit breaker can be equipped with:


n One shunt trip (MX) + one undervoltage trip device (MN or MNR)
n Or two shunt trips (MX)

Shunt Trip (MX)


This release is rated for continuous duty and operates with control voltages between 85% and 110%
of its rating. However, when series connected with an "a" auxiliary switch, the shunt trip can be
operated with 55% or more of its rated voltage and can be used for ground-fault protection when
combined with a Class 1 ground-fault sensing element. The shunt trip is field-installable.
Control Voltage (V)
60 Hz

120240480

DC

2448125250

Consumption (Inrush and Sealed)

06313051

Operating Time

AC

20 VA

DC

15 W

40 ms

Remote
Open
C2

MX

C1

Instantaneous Undervoltage Trip Device (MN)

06313052

This release instantaneously opens the circuit breaker when supply voltage drops below a value
between 35% and 70% of rated voltage. If the release is not energized, the circuit breaker cannot
be closed (either manually or electrically). Any attempt to close it will have no effect on the main
contacts. Closing is possible when the release voltage reaches 85% of its rated value. The
instantaneous undervoltage trip device is field-installable.
Remote
Open
D4

MN

D1

26
1995 Square DAll Rights Reserved

11/98

Accessories
Time-delayed Undervoltage Trip Device (MNR) (1)
To prevent the circuit breaker from tripping in the event of transient voltage drops, this release has a
built-in adjustable time delay. If required, this time delay can be overridden by connecting an
external switch on an additional circuit (wired by the user). The undervoltage trip device is fieldinstallable.
MN

MNR (1)

Control Voltage (V)


60 Hz

DC

120

120

240

480

480

24

48

125

250

Consumption (Inrush and Sealed)


AC

20 VA

20 VA

DC

15 W

15 W

0.09

0.50.91.53

Operating Time (s)

(1) Not UL Listed.

06313053

Heavy Usage Auxiliary Switches (OF)

06313054

Four SPDT switches with double break construction. They are directly operated by the main
contacts and ensure a large insulation distance in open position. They are therefore particularly
suitable for insulation of auxiliary circuits or reliable interlockings.
n "a" contacts are open when the circuit breaker is open and closed when the circuit breaker is
closed.
n "b" switches are closed when the circuit breaker is open and open when the circuit breaker is
closed.
See page 30 for operating diagrams. Auxiliary switches are field-installable.
Closed
Open
12

14

22

24

32

34

42

44

OF

11

21

31

41

27
11/98

1995 Square DAll Rights Reserved

06313055

Accessories
24 Additional Auxiliary Switches (OFSUP)
An external plate holds a set of 24 SPDT switches operated by means of a cable. They are
available only for drawout circuit breakers.

Standard Auxiliary Switches (O and F)

06313056

2a + 2b switches available as standard:


n "a" contacts are open when the circuit breaker is open and closed when the circuit breaker is
closed.
n "b" switches are closed when the circuit breaker is open and open when the circuit breaker is
closed.
See page 30 for operating diagrams.

Open

Closed
212

222

234

244

211

221

231

241

Ready-to-close Switch (PF)

06313057

This SPDT switch indicates that the circuit breaker is ready to close and that the following
conditions exist:
n The circuit breaker is open
n The stored energy mechanism is charged
n The control unit is reset
n The circuit breaker opening push button is neither locked nor padlocked
n The circuit breaker is in the fully-connected or test position
The switch is field-installable.

Ready-to-Close
252 254

PF

251

28
1995 Square DAll Rights Reserved

11/98

Accessories
Connected Position Switches (CE)
A block of four SPDT switches operate when a drawout circuit breaker is in the connected position.
The switch block is field-installable.

Disconnected Position Switches (CD)


A block of two SPDT switches operate when a drawout circuit breaker is in the disconnected
position. The switch block is field-installable. See page 30 for operating diagrams.

Test Position Switch (CT)

06313059

06313058

One SPDT switch is operated only when the circuit breaker is in the test position. The switch is fieldinstallable.

Connected Position Switches (CE)

06313060

Disconnected Position Switches (CD)

Disconnected
Connected

314

312

324

311

322

Test

334

321

332

344

342

321

321

352

354

351

362

364

372

374

361

371

Connection by 1/4 in. Male Quick Connect Terminal

Current Ratings (A)


Voltage (V)
Heavy Usage
60 Hz

DC

240

10

480
600

Auxiliary Switch
Ready-to-close
Standard 24 Additional Switch
15

15

10 (1)

125

250

12

Connected

Position Switch
Disconnected

Test

15

15

15

0.5

0.5

0.5

0.5

0.5

0.25

0.25

0.25

0.25

0.25

See page 65 for IEC voltage ratings.


(1) 8 A for MC08.

29
11/98

1995 Square DAll Rights Reserved

Accessories
Operating Diagrams
Auxiliary Switches
06313061

inch

mm
Fully
Closed

Fully
Open
Closed

Main Contact Position

13/8 in. (35 mm)


Between Contacts

Open
Closed
a

Heavy Usage (OF)

.1

Standard (O)

.1

Standard (F)

.1

24 Additional (OFSUP)

.1

b
a

.4

3/8 in. (9.5 mm)


Between Contacts
in Open Position

Open
Open

.2

Closed

.4

Closed

Open

.2

Open

Closed

.4

Closed

Open

Open

Closed

.2

Note: Contacts are shown with the circuit breaker in the open position. Scale applies only to
distance between main contacts.
06313062

Position Switches

Disconnected

Test

Connected

Main Disconnect
Position

Isolation Distance (1 in. [25.4 mm] or More)

Secondary Disconnect
Position

Isolation Distance (1/2 in. [13 mm] or More)

Connected

Connected

Connected Position
Switches (CE)

.1

Disconnected Position
Switches (CD)

.1

Test Position Switches


(CT)

.1

b
a

.4
.2

.2
.4

Closed
Open

Open

Closed

Closed

Open

Open

Closed

Open

Closed

Open

Closed

.4
.2

Open
Closed

Note: Position switches are shown with the circuit breaker in the connected position.

30
1995 Square DAll Rights Reserved

11/98

Accessories
Push Button Locking Device (VBP)
This device prevents local manual operation of the circuit breaker by covering the opening and/or
closing the push buttons. This locking device can be locked by a padlock or a sealing lead.

Open Position Lock (VSKA)

06313063

06313064

A key interlock that locks the circuit breaker in the open position by holding the push button in its
depressed position. The key interlock is provided.

06313065

Push Button Locking Device (VBP)

Open Position Lock (VSKA)

Door Interlock (VPEC)


This lock prevents the compartment door from being opened when the circuit breaker is in the
connected position. If the circuit breaker is put into the "connected" position with the door open, the
door can be closed without disconnecting the circuit breaker.
Note: For greater protection, this interlock can be used with racking interlock (VPOC) below.

Racking Interlock (VPOC)


This lock prevents racking in the circuit breaker when the door is open. (Insertion of the circuit
breaker racking crank is not possible when the compartment door is open.)

Disconnected Position Locking


The circuit breaker can be locked in the disconnected position by means of one to three padlocks
(padlocks not provided) or one key interlock (factory-mounted option VSKC). The key interlock is on
the stationary assembly and accessible with the cubicle door locked.
Note:
n Key interlock is of the captive key type, free when locked.
n By special order, locking may be possible on disconnected, test and connected positions
(VSKEC).

Spring Charge Interlock (VEAA)


This selection is for a device that prevents the circuit breaker or switch from being fully withdrawn
from its cradle when the closing spring is charged. It is standard for ANSI (UL1066) circuit breakers
and an option on others. The VEAA interlock is not compatible with undervoltage releases (MN,
MNR or MNRI).

31
11/98

1995 Square DAll Rights Reserved

Accessories
Mechanical Interlocks
n Disconnecting When Circuit Breaker Is Closed:

During any disconnecting attempt when the circuit breaker is closed, an interlocking device
ensures the tripping of the circuit breaker before the actual separation of the main disconnects.
The circuit breaker remains, however, operable in the other positions: test, disconnected and
withdrawn.
n Circuit Breaker Closing When Not Completely Connected:
The interlocking device mentioned above prevents closing of the circuit breaker if the connecting
operation is not completely achieved.
n Connecting Circuit Breaker When Door Opened:
VPEC and VPOC options prevent the compartment door from being opened when the circuit
breaker is in the connected position and from connecting the circuit breaker when the door is
open.

Electrical Interlocks
n Priority of Opening Orders (Standard):

06313066

Opening coils (undervoltage trip devices, shunt trip) and opening push button have priority over
the closing coils and closing push button.
n Mechanical Pop-out Type Indicator (Standard):
Under overcurrent or ground-fault conditions, the trip indicator located in the control unit will pop
out. It is not possible to close the circuit breaker until this trip indicator is reset. This standard
function can be disabled upon request.
n Anti-pumping Function (Standard):
In case the closing coil (XF) becomes permanently energized, the circuit breaker remains in the
open position A after it has been opened, either by manual or electrical operation. The circuit
breaker can be closed only if the closing coil is momentarily de-energized B.
Note: This anti-pumping function can be disabled by series connecting a "ready to close" (NC
contact) switch (PF) with the closing coil (XF).
Closing Coil
ON

ON

OFF B

OFF

Shunt Trip (same anti-pumping function with undervoltage trip device)


ON

OFF

OFF

Circuit
Breaker Status
ON

ON
Without
Anti-pumping
Function

OFF

OFF A

32
1995 Square DAll Rights Reserved

11/98

Accessories

06313067

Interlocking Rods and Cables


Two or three MASTERPACT circuit breakers can be mechanically interlocked by means of rods or
cables. This accessory is mountable on the right side of the circuit breaker. This adaptation can be
made on site without modifying the circuit breaker.
Mechanical Interlock Between Two or Three Stacked Circuit Breakers
This interlocking is obtained by the joining of:
n One adaptation block
n One or two adjustable and nonadjustable rods
Maximum distance between the two fixing surfaces of the devices: 35 in. (0.89 m)
Mechanical Interlocks Between Two Side-by-Side Circuit Breakers
This interlocking is obtained by the joining of:
n One adaptation block
n One set of adjustable cables with a maximum length of 78 in. (2 m)

Possible Mounting Arrangements Among Three Stacked Circuit Breakers

06313068

One use, power supplied by:


n Two transformers N1 and N2 which are connected in parallel
n Or one standby source G
N1

N2

06313069

Two uses, independently powered supply by two transformers N1 and N2, standby through a circuit
breaker or a connection tie switch, preventing the connection in parallel of the two current
transformers.
N1

N2
C

06313070

One use, power supplied by one group of transformers N1, N2 or N3 or of generators, preventing
any connection in parallel.
N1

N2

N3

33
11/98

1995 Square DAll Rights Reserved

Accessories
Safety Shutters (VO)
Comprising two independent parts, line and load side, the safety shutters automatically block
access to the main disconnects when the circuit breaker is in the disconnected, test or fully
withdrawn position.

Shutters Lock (VVC)

06313072

06313071

A factory-mounted movable and lockable slide (padlock not supplied) is used to:
n Lock the line or load shutters in the closed position
n Hold the line or load shutters in the open position
A support is provided at the back of the stationary assembly to hold the slide when not in use.

Safety Shutters

Shutters Lock

Rejection Feature (VDC)

06313074

06313073

The rejection feature ensures that only the properly designated circuit breaker is matched with the
selected cradle assembly. It is made of two parts (one for the frame and one for the stationary
assembly), and allows 20 different combinations.

2
4
6

1
3

Stationary
Assembly

C
E

Circuit Breaker
Frame

Possible Arrangements
Frame

Stationary
Assembly

Frame

Stationary
Assembly

ABC

456

BCD

156

ABD

356

BCE

146

ABE

346

BCF

145

ABF

345

BDE

136

ACD

256

BDF

135

ACE

246

BEF

134

ACF

245

CDE

126

ADE

236

CDF

125

ADF

235

CEF

124

AEF

234

DEF

123

34
1995 Square DAll Rights Reserved

11/98

Accessories
Interphase Barrier (EIP)
Mounted between terminals of the stationary assembly, the interphase barrier prevents arc
prolongation to the circuit breaker in the event of a line side fault and isolates the circuit breaker
connections in insulated bus bar installations.

Transparent Cover (CB)

06313076

06313075

Hinged-mounted and locked with a milled head, this cover is designed to be installed on the door
escutcheon. It provides a higher degree of protection and is suitable for drawout or fixed-mounted
circuit breakers.

Interphase Barrier

Transparent Cover

35
11/98

1995 Square DAll Rights Reserved

06313077

Switch
Ratings
Type

Ampere
Rating
(A)

Short-time Rating
(RMS Sym. Amperes)
600 Vac Max.

Short-circuit Withstand When


Protected by a MASTERPACT
Circuit Breaker (A)
Max. Frame (A)
600 Vac Max.

MP08 NA

800

50,000

800

50,000

MP12 NA

1200

50,000

1200

50,000

MP16 NA

1600

50,000

1600

50,000

MP20 NA

2000

50,000

2000

50,000

MP25 NA

2500

50,000

2500

50,000

MP30 NA

3000

50,000

3000

50,000

MP40 NA

4000

85,000

4000

85,000

MP50 NA

5000

85,000

5000

85,000

MP63 NA (1)

6300

85,000

6300

85,000

(1) Not UL Listed.

CAUTION
HAZARD OF EQUIPMENT DAMAGE.
This switch contains no overcurrent protection.
It is suitable for use at its ampere rating when
protected by a MASTERPACT circuit breaker
of the same ampere rating.
Failure to observe this precaution can
cause equipment damage.

Construction
The MASTERPACT switch is identical to the MP circuit breaker, except that the switch is not
equipped with current transformers or an actual control unit. However, it does have an STR08
dummy unit.

Accessories, Dimensions and Connections


Switch accessories, dimensions and connections are identical to those of the corresponding circuit
breaker, except that the overcurrent trip switch is not available with the switch version.
Page
Accessories

23

Wiring diagrams

42

Circuit Breaker Dimensions

46

36
1995 Square DAll Rights Reserved

11/98

Trip Curves

9000
8000
7000
6000

5000

5000

4000

4000
3000

3000

Current Setting:
STR 28D = 0.41 x Sensor Rating
STR 28DP = 0.81 x Plug Rating

2000

2000

1000
900
800
700
600

1000
900
800
700
600

500

500

400

400

300

300

200

200

100
90
80
70
60

100
90
80
70
60

50

50

40

40

30

30

20

20

10
9
8
7
6

10
9
8
7
6

Instantaneous Pickup
I = 1.510 x Ir

1
.9
.8
.7
.6

1
.9
.8
.7
.6

.5

.5

.4

.4

.3

.3

.2

.2

.1
.09
.08
.07
.06

.1
.09
.08
.07
.06

.05

.05

.04

.04

.03

.03

.02

.02

Multiple of Current Setting (Ir)

6000
7000
8000
9000
10000

40 50 60

5000

30

4000

20

3000

6 7 8 9 10

2000

600
700
800
900
1000

500

400

300

.5 .6 .7 .8 .9 1 1.2 1.5

200

.01

.01

70
80
90
100

Time in Seconds

6000
7000
8000
9000
10000

40 50 60

5000

30

4000

20

3000

6 7 8 9 10

2000

600
700
800
900
1000

500

400

300

.5 .6 .7 .8 .9 1 1.2 1.5

200

10000
9000
8000
7000
6000

70
80
90
100

06313078

Overcurrent Protection STR 28D Control Unit

37
11/98

1995 Square DAll Rights Reserved

Trip Curves

.5 .6 .7 .8 .9 1 1.2 1.5

6 7 8 9 10

20

30

40 50 60

5 6 7 8 9 10

20

30

40 50 60

70
80
90
100

10000
9000
8000
7000
6000

70
80
90
100

06313079

Overcurrent Protection STR 38S Control Unit


9000
8000
7000
6000

5000

5000

4000

4000
3000

3000

Current Setting:
STR 38S = 0.41 x Sensor Rating
STR 38SP = 0.81 x Plug Rating

2000

2000

Time in Seconds

1000
900
800
700
600

1000
900
800
700
600

500

500

400

400

300

300

200

200

100
90
80
70
60

100
90
80
70
60

50

50

40

40

30

30

20

20

10
9
8
7
6

10
9
8
7
6

Short-time Pickup
Im = 1.510 x (Ir)

I2 t ON

Inst (*)
1
.9
.8
.7
.6

1
.9
.8
.7
.6

.5

.5
.4

.4
.3

.3

0.3

0.3

.2

0.2

0.2

0.1

0.1

I2 t OFF

.1
.09
.08
.07
.06

.2

.1
.09
.08
.07
.06

.05

.05

.04

.04

.03

.03

.02

.02

6 7 8 9 10

20

30

40 50 60

x Ir

In (A)
I = In x

630
28

800/1000
28

5 6 7 8 9 10

20

30

40 50 60

70
80
90
100

.5 .6 .7 .8 .9 1 1.2 1.5

70
80
90
100

.01

.01

(*) Instantaneous
Rating
Fixed Threshold

0.4

x In

1200/1600
24

2000
20

2500
14

3000/3200
12

4000/5000/6300
10

38
1995 Square DAll Rights Reserved

11/98

Trip Curves

6 7 8 9 10

20

30

40 50 60

5 6 7 8 9 10

20

30

40 50 60

9000
8000
7000
6000

9000
8000
7000
6000

5000

5000

4000

4000
3000

3000

Current Setting:
STR 58U = 0.41 x Sensor Rating
STR 58UP = 0.81 x Plug Rating

2000

1000
900
800
700
600

1000
900
800
700
600

500

500

400

400

300

300

200

200

100
90
80
70
60

100
90
80
70
60

50

50

40

40

30

30

20

20

10
9
8
7
6

10
9
8
7
6
5

Short-time Pickup
Im = 1.510 x (Ir)

4
3

H1: 24812141922Off
H2: 24812141922Max.

1200/1600 A
H1: 24812141722Off
H2: 24812141722Max.

2000 A

I 2 t ON
1
.9
.8
.7
.6

1
.9
.8
.7
.6

.5

.5

.3

.2

H1: 2468101212Off
H2: 2468101212Max.

I 2 t OFF

.1
.09
.08
.07
.06
.05

3000/3200 A
H1: 2468101010Off
H2: 2468101010Max.

4000/5000/6300 A
H1: 2468888Off
H2: 2468888Max.

0.4

.4

0.3

0.3

.3

0.2

0.2

0.1

0.1

.4

H1: 24810121417Off
H2: 24810121417Max.

2500 A

.1
.09
.08
.07
.06
.05
.04

.03

.03

.02

.02

.01

.5 .6 .7 .8 .9 1 1.2 1.5

6 7 8 9 10

20

30

40 50 60

x Ir

(*) Instantaneous
Rating
In (A)
Maximum Threshold I = In x

.2

Instantaneous Pickup
I = 2 x In Max (*)

.04

70
80
90
100

800/1000 A

630
28

800/1000
28

5 6 7 8 9 10

20

30

40 50 60

.01

70
80
90
100

Time in Seconds

2000

Instantaneous Dial
Settings

70
80
90
100

.5 .6 .7 .8 .9 1 1.2 1.5

70
80
90
100

06313080

Overcurrent Protection STR 58U Control Unit

x In

1200/1600
24

2000
20

2500
14

3000/3200
12

4000/5000/6300
10
39

11/98

1995 Square DAll Rights Reserved

Trip Curves

6 7 8 9 10

20

30

40 50 60

600
700
800
900
1000

1000
900
800
700
600

Ground-fault Pickup
Ih = 0.1 x In 1200 A Max.

500
400

500
400

300

300

200

200

100
90
80
70
60

100
90
80
70
60

50

50

40

40

30

30

20

20

10
9
8
7
6

10
9
8
7
6

I 2t ON

Time in Seconds

.5 .6 .7 .8 .9 1 1.2 1.5

500

.4

400

.3

300

.2

200

.1 .12 .15

70
80
90
100

1000
900
800
700
600

.05
.06
.07
.08
.09

06313081

Ground-fault Protection STR 38SSTR 58U Control Units

1
.9
.8
.7
.6

1
.9
.8
.7
.6

.5

.5

.4

0.4

.4

.3

0.3

.3

.2

0.2

.2

I2t OFF

.1
.09
.08
.07
.06

.1
.09
.08
.07
.06

0.1

.005

.005

.004

.004

.003

.003

.002

.002

.001

.001

.1 .12 .15

.2

.3

.4

.5 .6 .7 .8 .9 1 1.2 1.5

6 7 8 9 10

20

30

40 50 60

600
700
800
900
1000

.01
.009
.008
.007
.006

500

.01
.009
.008
.007
.006

400

.02

300

.03

.02

200

.04

.03

70
80
90
100

.05

.04

.05
.06
.07
.08
.09

.05

Multiple of Current Sensor (In)

40
1995 Square DAll Rights Reserved

11/98

Trip Curves

10000
9000
8000
7000
6000

6 7 8 9 10

20

30

40 50 60

10000
9000
8000
7000
6000

5000

5000

4000

4000

3000

3000

Current Setting
Ir = 0.81 x Plug Rating

2000

2000

1000
900
800
700
600

Ic1 = 0.8 1 x Ir

1000
900
800
700
600

500

Ic2 = 0.5 1 x Ir

500

400

400

300

300

200

200

100
90
80
70
60

100
90
80
70
60

tr1 = tr / 2

50

50

40

40

30

30

tr2 = tr / 4

1
.9
.8
.7
.6

1
.9
.8
.7
.6

.5

.5

.4

.4

.3

.3

.2

.2

.1
.09
.08
.07
.06

.1
.09
.08
.07
.06

.05

.05

.04

.04

.03

.03

.02

.02

.1 .12 .15

.2

.3

.4

.5 .6 .7 .8 .9 1 1.2 1.5

6 7 8 9 10

20

30

40 50 60

.01

600
700
800
900
1000

.01

500

400

10
9
8
7
6

300

10
9
8
7
6

200

20

70
80
90
100

20

.05
.06
.07
.08
.09

Time in Seconds

600
700
800
900
1000

.5 .6 .7 .8 .9 1 1.2 1.5

500

.4

400

.3

300

.2

200

.1 .12 .15

70
80
90
100

.05
.06
.07
.08
.09

06313082

Load Monitoring STR 58U Control Unit

Multiple of Current Setting (Ir)

41
11/98

1995 Square DAll Rights Reserved

Wiring Diagrams

06313083

Diagram No. 689 889

Drawout Position Switches

Connected

Auxiliary Switches

Disconnected

Test

Standard

Remote Operation

Heavy
Duty

Undervoltage
Trip Device or

Closed
Disconnected

Motor
Operator

Spring
Charged

Open

Remote
Close

314 312 324 322 334 332 344 342 352 354 362 364 372 374

212 222 234 244

321

Ready
to Close

Remote
Open

Test

Connected

311

Shunt
Trip

331

341

351

361

12 14

22 24

32 34

42 44

D4

C2

A4

252 254

262 B4

371

MN
Standard

211 221 231 241

MX

XF

OF

11

21

31

PF

41

D1

C1

A1

CH

251

Note: Circuit breaker shown in connected, charged and open position with undervoltage releases energized.
42
1995 Square D All Rights Reserved

11/98

B1

Wiring Diagrams

06313084

Diagram No. 689 889


Remote Fault
and Overload
Indication

Ground-fault
Protection

Ammeter

Local Fault Indications


and Remote Selected
Fault Indication

Zoneselective
Interlocking

Load
Monitoring

Data
Transmission

Ic2
Fault
Alarm

Selected
Fault

Overload
Alarm

Ic1
Upstream
Circuit
Breaker

82 84 (1)

LR2

S2

S1

T2

T1

Z11

LT

1
I Option

LT
Alarm

SDE

81

F1
_

(5)

F2

Z12

Gnd

R1 R2

Z Option
F or FV Option

e+

Out

T or W Option

(4)

LR1

ST

Communication (3)
Network

(6)

C Option
R Option

In

Z21

Z22

+
(2)

24 Vdc

(1) 84 terminal not available with Z or C option.


(2) Zone-selective interlocking with downstream circuit breaker: remove
the jumper.
(3) Communication output through DIGIPACT module.
(4) Use 24 Vdc supply for loads less than 20% of current sensor
rating, or one-phase load less than 40% of sensor rating.

Downstream
Circuit
Breaker

(5) Use 24 Vdc supply for lower setting.


(6) Use 24 Vdc supply for F option if not supplied with PIL (battery)
option; use 24 Vdc supply (mandatory) for FV option.

43
11/98

1995 Square DAll Rights Reserved

Wiring Diagrams
SC150 Indication and Control Interface
Motor
Operator
Power Supply

06313085

To Power
Supply "L"
400

630

C1 NO NC ON C2 reset
Control Outputs

C3 CD CE SDV SD
Inputs

PT100
Temperature
Probe

External
Contact

24-250V CC
100-440V CA

DIGIPACT
Internal Bus
COM
+ NC 0 24V e+ e T+ T
SC150 Indication and Control Interface

Inputs
C4 ON IN OFFSDE

To "IN"
SC150
Input
Terminals

1 4

To "C4"
SC150
Input
Terminals

N
To SC150
Terminals
"T+" and "T"

To "C3"
on SC150
Input Terminals

To "C4"
on SC150
Input Terminals

To "CD"
on SC150
Input
Terminals

To "SDE"
on SC150
Input Terminals

To "OFF"
on SC150
Input Terminals
To "ON"
on SC150
Input Terminals

To "CE"
on SC150
Input
Terminals
2 1 4

2 1 4

2 1 4

CE
CD
Control Unit
STR28 / 38 / 58

To "ON"
SC150 Control
Output Terminals
to "NO"
SC150 Control
Output Terminals
To Power Supply "L"

A4 C2 B4
Remote
Control

2 1

SDE

Control Unit
STR58U
Control Unit

To "e +" and "e "


on SC150
"COM" Terminals

XF MX M

C1

To Auxiliary
Source

e+ e

SDE

A1

2 1 4

To "SDE"
on SC150
Input Terminals

2 1 4

OF

To "C4"
on SC150
Input Terminals

B1
To Power Supply "N"

MASTERPACT Circuit Breaker

Internal Bus
Marking

Color

24 V

Red

0V

Black

Internal Bus

White

Internal Bus +

Blue

44
1995 Square DAll Rights Reserved

11/98

Wiring Diagrams
DC150 Data Concentrator
06313086

DC150
9600

3456

2
2

110240 Vac
115125 Vdc

Protection

78 9A
B CD

N2

3456

78 9A

N1

B CD

Internal
Bus

NC
Internal Bus
Internal Bus +

MODBUS/JBUS
Speed

19200

24 V
0V

DC150 Address
on MODBUS/JBUS
Network

RS485
MODBUS/JBUS
C

Connectors

06313088

The DC150 concentrator is connected using a SUBD9 male connector with a metal hood (e.g., ITT
canon, DE9P K83 + hood or DE115-500-5-RD). The DC150 concentrator is equipped with a SUBD9
female connector. For a multidrop configuration, the tap-offs can be made either via a branching off
of RS485 connector Catalog No. 50788 or standard connection boxes, taking care to respect the
necessary precautions when connecting the shieldings. The adaptation of an RS232 output on a
personal computer to accept the RS485 standard connector should be done with the RS485/RS232
converter Catalog No. 50786.

1
06313087

0V
5V

0V

Rp
Rp

Rc

3
RD+ (A')

RD (B')

TD+ (A)

L+ (A / A')
L (B / B')

TD (B)

Recommended Protection and Cable Sizes

DC150 Concentrator with


Polarization and 2-wire
Adaptation

Recommended
Protection

Type

Catalog No.

C60N Supplementary Circuit Protector


Curve C10 A

3-Phase

MG24466 or 24214

Fuse-link 10 A

aM

15660

Marking (1)

Connection

Cable

Voltages

0.06 to 0.1 in.2 (0.75 to 2.5 mm2)

Internal Bus

0.03 to 0.1 in.2 (0.75 to 2.5 mm2) (Twisted)

MODBUS/JBUS

0.03 to 0.1 in.2 (0.75 to 2.5 mm2) (Shielded)

Internal bus

Marking

Color

24 V

Red

0V

Black

Internal Bus

White

Internal Bus +

Blue

(1) See first drawing above.

45
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


Door Escutcheon (Drawout Mounting)
Drilling of the Door
06313091

06313089

06313090

Door Cutout

6
153

10.63
270
0.75
Basis:
19
MP08 to MP30
2.6 MC08 to MC32
66
1.85
47 1.77
2.17
45
55

12.8
325

2.82
72

MP40 to MP63
MC40/MC50

5.83
0.73 149
19
2.72
69
Mounting
Holes

0.19 Dia.
5

7.1
180

7.1
180

0.69/ 18

Door Escutcheon (Fixed Mounting)


Drilling of the Door
06313094

06313093

06313092

Door Cutout

6
153

10.63
270

2.82
2.82
72
72

2.72
69

1.06
27
Mounting
1.48 Holes
38

12.8
325

0.57 5.83
15 149

0.19 Dia.
5

7.1
180

7.1
180

0.69
18

Note: Refer to shop drawings for verification.

Rear Cutout
0.15
4

0.79
20

0.15
4

06313097

06313095

06313096

Door Interlock

14.2
360
0.80
20

0.12
3

14.5/368 MP30
29.4/748 MP50/MC50
38.4/978 MP63

1.69
43

0.12
3

Circuit
Breaker
Base

Mounting
Holes
17.5
445

2.36
60

Note: The door interlock can be mounted on


either the right side or the left side of the circuit
breaker.

Dimensions: inch
mm

46
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


External Neutral Sensor

0.7
18

0.7
18

3.15
80
1.75
45

MP25/MP30/MP40, MC32/MC40
06313099

06313098

MP08 to MP20, MC08 to MC20

0.56 Dia.
14

0.39/10
MP08 to MP16
MC08 to MC16

1.73
44

0.79/20
MP20/MC20

1.75
45

0.79
20

3.94
100

6.30
160

2.36
60

1.75
45

0.7
18

1.8
46

0.78
20
4.72
120

0.7
18

3.15
80
1.75
45

06313101

06313100

0.7
18

0.56 Dia.
14

2.9
74

0.79/20
MP25/MP30/MC32

3.31
84

1.18/30
MP40/MC40

1.75
45

0.79
20

3.94
100

6.30
160

2.36
60

1.75
45
0.7
18

1.8
46

0.78
20
4.72
120

4.5
114

0.58
15

7.47
190

1.17
30

2.11
54

0.54
14

9.12 / 9.41
235 / 240

6.27
160
1.57
40

0.47 Dia.
12

4.7
120

06313104

0.58
15

06313103

06313102

MP50 to MP63

0.58
15

2.35
60

=
3.13
80

2.35
60

8.62
220

0.68
17.5
0.78
20

3.5
89.5

2.19
56

1.17
30

= =
7.84
200

0.98
25

7.84
200

Dimensions: inch
mm

47
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


MP08MP12MP16 Fixed Mounting

4.53
115

4.53
3.35
115
85
3.15
0.98 80 0.98
25
25 0.47 Dia.
12

06313106

06313105

3-Pole
4.53
115

0.5 Dia.
12,7

4.53
115

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
21 in. (530 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #688 378 for
verification. Vertical
terminals are optional
for MP08MP12 circuit
breakers.

3.35
85

0.63
16

Necessary Space for Removing the Arc Chutes


3.15
80

06313108

06313107

14.88
378

17.24
438

Cell (Insulation Not Required)


1.57
40 Min.
0.69
17,5

(4) Mounting
Holes
0.44 Dia. / 11

1
25,4

4.41
112

5.59
142
3.15
80

2.08
53
0.43
11

15.75
400

0.43
11

16.61
422

2.83
72
1.18 / 30 Min.
2.36 / 60 Max.

5.91
150

2.68
68

9.17
233

11.14
283

15.78
401

0.39
10

0.19 1.69
3 43
0.49
12,5

0.71
18

0.98
25

4.53
115

4.53
4.53
115 3.15115
80

3.35
85
0.47 Dia.
12

0.63
16

4.53
115

4.53
115

4.53
115

3.35
85
0.5 Dia.
12,7

06313110

06313109

4-Pole

19.4
493

3.15
80

21.8
553

Cell (Insulation Not Required)


1.57
40 Min.

06313112

06313111

Necessary Space for Removing the Arc Chutes

0.69
17,5

(4) Mounting
Holes
0.44 Dia. / 11

20.2
515

0.43
11

2.83
72
1.18 / 30 Min.
2.36 / 60 Max.

5.91
150

2.68
68

9.17
233

11.14
283

15.78
401

0.39
10

1
25,4

4.41
112

5.59
142
3.15
80

2.08
53
0.43
11

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
25.5 in. (645 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #691 378 for
verification. Vertical
terminals are optional
for MP08MP12 circuit
breakers.

0.71
18

0.19 1.69
3 43
0.49
12,5

Dimensions: inch
mm

48
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


MP08MP12MP16MC08MC16 Drawout Mounting

4.53
115

4.53
115

1.87
48

3.15
80

0.98
25

06313114

06313113

3-Pole
4.53
115

0.5 Dia.
12,7

4.53
115

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
21 in. (530 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #688 378 for
verification. Vertical
terminals are optional
for MP08MP12MC08
circuit breakers.

1.87
48

0.63
16

0.47 Dia.
12

Withdrawn Position
9.56 1.77
243 45

Disconnected Position
14.21
361

06313115

06313120

Cell (Insulation Not Required)

0.69
18

0.98
25

1
25

0.39
10

5.98
152
3.15
80
3.23
82

4.41
112
3.62
92

(4) Mounting
Holes
0.44 Dia./11
12.8
325
17.14
435

2.17
55

3.98
101
4.21
107

2.17
55

6.89
175

3.35
85
11.81
300

17.32
440 Min.

1.65
42

0.49
13

13.78
350

0.49
13

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
25.5 in. (645 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #691 381 for
verification. Vertical
terminals are optional
for MP08MP12MC08
circuit breakers.

4.53
115

0.98
25

4.53
4.53
115 3.15115
80

1.87
47,5
0.47 Dia.
12

06313118

06313117

4-Pole
4.53
115

0.63
16

4.53
115

4.53
115

1.87
47,5
0.5 Dia.
12,7

06313119

06313120

Withdrawn Position
9.56 1.77
243 45

Disconnected Position
14.21
361
Cell (Insulation Not Required)

21.89
556

0.98
25
0.39
10

(4) Mounting
Holes
0.44 Dia. / 11

4.41
112
3.62
92

2.75
70

16.73
425

21.65
550

2.17
55

3.98
101
4.21
107

6.89
175

3.35
85
11.81
300

13.78
350

0.49
13

0.69
18
1
25

17.32
440 Min.

5.98
152
3.15
80
3.23
82
1.65
42
0.49
13

Dimensions: inch
mm

49
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


MP20 Fixed Mounting
Note: Suitable for
continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
21 in. (530 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #688 379 for
verification.

06313121

3-Pole
4.53
115
0.79
20

0.56 Dia.
14

4.53
115

3.35
85

Necessary Space for Removing the Arc Chutes


17.24
438

3.15
80

06313123

06313122

14.88
378

Cell (Insulation Not Required)


1.57
40 Min.

4.53
115
(4) Mounting
Holes
0.44 Dia. / 11

0.43
11

15.75
400

5.98
152
3.15
80

0.43
11

16.61
422

15.78
401

1.75
44,5

2.83
72
1.18 / 30 Min.
2.36 / 60 Max.

5.91
150

2.68
68

0.71
18

14.98
380,5

0.12
3
1.75
44,5

1.69
43

06313124

4-Pole
0.79
20

4.53
115

4.53
115

4.53
115

3.35
85

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
25.5 in. (645 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #691 379 for
verification.

0.56 Dia.
14,3

19.4
493

3.15
80

06313123

06313125

Necessary Space for Removing the Arc Chutes


21.8
553

Cell (Insulation Not Required)


1.57
40 Min.

4.53
115
(4) Mounting
Holes
0.44 Dia. / 11

0.43
11

20.2
515

0.43
11

15.78
401

1.75
44,5

5.98
152
3.15
80

2.83
72
1.18 / 30 Min.
2.36 / 60 Max.

5.91
150

2.68
68
14.98
380,5

0.71
18

0.12
3
1.75
44,5

1.69
43

Dimensions: inch
mm

50
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


MP20MC20 Drawout Mounting

06313127

3-Pole
0.56 Dia.
14

4.53
115
0.79
20

4.53
115

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
21 in. (530 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #688 379 for
verification.

1.87
48

06313129

Withdrawn Position
9.56 1.77
243 45

Disconnected Position
14.21
361

06313128

Cell (Insulation Not Required)

4.53
115

1.75
45
17.32
440 Min.

(4) Mounting
Holes
0.44 Dia./11
2.17
55

12.8
325
17.14
435

2.17
55

5.98
152
3.15
80
3.23
82
3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.65
42
0.7
18

1.75
45

4-Pole
4.53
115

4.53
115

06313130

0.79
20

4.53
115

1.87
47,5
0.56 Dia.
14,3

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
17.5 in. (440 mm) h. by
25.5 in. (645 mm) w. by
14.25 in. (360 mm) d.
Ventilation is not
required. Refer to shop
drawing #691 382 for
verification.

Withdrawn Position
9.56 1.77
243 45

Disconnected Position

Cell (Insulation Not Required)

06313129

06313131

14.21
361

21.89
556

4.53
115

1.75
45
17.32
440 Min.

(4) Mounting
Holes
0.44 Dia. / 11

2.75
70

16.73
425

21.65
550

2.17
55

5.98
152
3.15
80
3.23
82
3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.75
45

1.65
42
0.7
18

Dimensions: inch
mm

51
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


MP25MP30 Fixed Mounting

06313133

3-Pole
0.56 Dia.
14

5.85
149
0.25
6

5.85
149

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
26 in. (660 mm) h. by
21 in. (530 mm) w. by
14.25 in. (360 mm) d.
with a ventilation of 30
sq. in. (200 cm2) at top
and bottom. Refer to
shop drawing #688 380
for verification.

2.01
51
0.25
6

14.88
378

17.24
438

3.15
80

06313138

06313134

Necessary Space for Removing the Arc Chutes


Cell (Insulation Not Required)

1.57
40 Min.
1.75
44,5
15.78
401

(4) Mounting
Holes
0.44 Dia. / 11

15.75
400

0.43
11

16.61
422

10.24
260

2.28
58

0.43
11

2.83
72

5.91 2.68
68
150
13.95
354,5

4.72
120
1.75
44,5

2.24
57

1.13 0.24
29
6

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
26 in. (660 mm) h. by
25.5 in. (645 mm) w. by
14.25 in. (360 mm) d.
with a ventilation of 30
sq. in. (200 cm2) at top
and bottom. Refer to
shop drawing #691 380
for verification.

06313136

4-Pole
5.85
149

4.55
115

0.25
6,35
0.56 Dia.
14,3

5.85
149

2.01
51

0.25
6,35

06313137

19.4
493

06313138

Necessary Space for Removing the Arc Chutes

21.8
553

3.15
80

Cell (Insulation Not Required)

1.57
40 Min.
1.75
44,5
15.78
401

(4) Mounting
Holes
0.44 Dia. / 11

0.43
11

20.2
515

0.43
11

2.28
58

2.83
72

5.91 2.68
68
150
13.95
354,5

10.24
260

4.72
120
1.75
44,5

2.24
57

1.13 0.24
29
6

Dimensions: inch
mm

52
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


MP25MP30 Drawout Mounting
Note: Suitable for
continuous operation at
100% rating in a
minimum cubicle space
26 in. (660 mm) h. by
21 in. (530 mm) w. by
14.25 in. (360 mm) d.
with a ventilation of 30
sq. in. (200 cm2) at top
and bottom. Refer to
shop drawing #688 380
for verification.

3-Pole
06313139

0.56 Dia.
14

5.75
146
0.25
6

0.65
17

5.75
146

0.25
6

Withdrawn Position

06313144

9.56 1.77
243 45

Disconnected Position
14.21
361

06313140

Cell (Insulation Not Required)


2.28
58

1.75
44

17.32
440 Min.
10.24
260
(4) Mounting
Holes
0.44 Dia./11
12.8
325
17.14
435

2.17
55

4.72
120

2.17
55

3.98
101
4.21
107

6.89
175

3.35
85

1.75

17.64
448

45

1.30
0.71
1.14 33 18
29

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
26 in. (660 mm) h. by
25.5 in. (645 mm) w. by
14.25 in. (360 mm) d.
with a ventilation of 30
sq. in. (200 cm2) at top
and bottom. Refer to
shop drawing #691 380
for verification.

4-Pole

06313142

5.35
136

4.92
125

5.75
146

0.65
17
0.25
6,35

0.25
6,35

0.25
6,35

0.65
16,5

0.56 Dia.
14,3

06313143

06313144

Withdrawn Position
9.56 1.77
243 45

Disconnected Position
14.21
361

21.89
556

Cell (Insulation Not Required)


2.28
58

1.75
44

17.32
440 Min.

(4) Mounting
Holes
0.44 Dia./ 11

10.24
260
4.72
120

2.75
70

16.73
425

21.65
550

2.17
55

3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.75

45

1.30
0.71
1.14 33 18
29

Dimensions: inch
mm

53
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


MC32 Drawout Mounting

0.25
0.53 Dia. 6
14

6.10
155

6.10
155

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
22 in. (560 mm) h. by
25.25 in. (640 mm) w.
by 14.25 in. (360 mm)
d. with a ventilation of
30 sq. in. (200 cm2) at
bottom. Refer to shop
drawing #689 074 for
verification.

2.55
65
0.25
6

06313147

06313145

3-Pole

Withdrawn Position
9.56 1.77
243 45

Disconnected Position
14.21
361
Cell (Insulation Not Required)

06313146

2.28
58

1.75
44

17.32
440 Min.
10.24
260

(4) Mounting
Holes
0.44 Dia./11
2.75
70

21.65
550

16.73
425

2.17
55

4.72
120
3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.75

45

1.30
0.71
1.14 33 18
29

Dimensions: inch
mm

54
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


MP40MP50 Fixed Mounting
MP40
1.14
29
0.56 Dia.
14

9.76
248

9.76
248

0.25 0.5
6 13

06313149

06313148

3-Pole
5.59
142

0.25
6,35

1.14
29

1.14
29

9.76
248

0.78
20

9.76
248

5.59
142
1.14
29

06313150

MP50

0.25
6,35

1.14
29

9.76
248

9.76
248
0.5
13

5.59
142

1.14
29

0.25
6,35

Necessary Space for Removing the Arc Chutes

06313152

1.57
40 Min.

06313151

29.88
759

Cell (Insulation Not Required)

32.24
819

1.75
44,5

2.28
58

(4) Mounting
Holes
0.44 Dia. / 11
0.43
11

31.57
802

30.71
780

0.43
11

15.78
401
10.24
260
4.72
120

1.18 / 30 Min.
2.36 / 60 Max.

2.83
72

5.91
2.68
150
68
14.35
364,5

1.75
44,5

2.24
57

1.13 0.24
29
6

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
26 in. (660 mm) h. by
34 in. (870 mm) w. by
14.25 in. (360 mm) d.
with a ventilation of 30
sq. in. (200 cm2) both at
top and bottom. Refer to
shop drawing #688 381
for verification.
Dimensions: inch
mm

55
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


MP40MP50MC50MC50 Drawout Mounting

0.25
6

MP40MC50
9.94
253

9.94
253

1.26
32

0.56 Dia.
14

3.94
100 0.25
6

9.94
253

9.94
253

0.25
6

06313154

06313153

3-Pole

3.94
100

1.26
32

0.25
6

0.56 Dia.
14

06313155

MP50MC50
3.94
100

9.94
253
1.26
32

9.94
253

0.25
6
0.56 Dia.
14

0.25
6

Withdrawn Position
Disconnected Position
9.56
243

1.77
45 14.21
361

0.56 Dia.
14

1.75
45

2.28
58

06313157

06313156

Cell (Insulation Not Required)

19.1
485 Min.
10.24
260
4.72
120

(6) Mounting
Holes
0.44 Dia./11
2.36
60

13.78
350

13.78
350
32.08
815

2.17
55

3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.75
45

1.06
27

3.08
78

1.14
29

Note: Suitable for


continuous operation at
100% rating in a
minimum cubicle space
26 in. (660 mm) h. by
34 in. (870 mm) w. by
14.25 in. (360 mm) d.
with a ventilation of 30
sq. in. (200 cm2) both at
top and bottom. Refer to
shop drawing #688 381
for verification.
Dimensions: inch
mm

56
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


MP40MP50 Drawout Mounting
4-Pole (Not UL Listed)

MP40
9.94
252,5

0.25
6,35

9.94
252,5
1.26
32

3.94
100
0.25
6,35

06313159

06313158

9.94
252,5

0.56 Dia.
14,3

9.94
252,5

0.25
6,35

9.94
252,5

9.94
252,5

3.94
100

0.25
6,35

1.26
32

0.56 Dia.
14,3

06313160

MP50
9.94
252,5

0.25
6,35

9.94
252,5

9.94
252,5
1.26
32

3.94
100

0.25
6,35

0.56 Dia.
14,3

Withdrawn Position
Disconnected Position
1.77
45 14.21
361

06313162

06313161

9.56
243
41.38
1051

0.56 Dia.
14

Cell (Insulation Not Required)


1.75
45

2.28
58

19.1
485 Min.
10.24
260
4.72
120

(6) Mounting
Holes
0.44 Dia. / 11

1.57
40

18.70
475

41.14
1045

18.70
475

2.36
60

3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.75
45

1.06
27

3.08
78

1.14
29

Note: Refer to shop


drawing #691 384 for
verification.

Dimensions: inch
mm

57
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


MP63 Drawout Mounting (Not UL Listed)

06313163

3-Pole

0.25
6

13.78
350

13.78
350

Note: Refer to shop


drawing #688 382 for
verification.

4.62
118
2.00
51

0.25
6 0.56 Dia.
14

Withdrawn Position
9.56 1.77
243 45

Disconnected Position
14.21
361

06313164

06313165

Cell (Insulation Not Required)


2.28
58

1.75
45

19.1
485 Min.
10.24
260

(6) Mounting
Holes
0.44 Dia./11

1.57
40

18.70
475

18.70
475

2.16
55

41.14
1045

4.72
120 3.08
78
3.98
101
4.21
107

6.89
175

3.35
85
17.64
448

1.75

45

1.06
27
1.14
29

Dimensions: inch
mm

58
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


Mechanical Interlocks for Drawout or Fixed Circuit Breakers
Connecting Links for Two Stack-mounted Circuit Breakers
Fixed Mounting
06313175

06313174

Drawout Mounting

1.96
50

1.57
40

2.03
52

4.9
125

1.17
30

1.96
50

0.19
5

0.54
14

4.9
125

35.29
900
Max.

1.17
30

35.29
900
Max.

35.29
900
Max.

6.86
175
4.11
105

6
153
(*)

6.39
163
2.54
65

6.5
166

1.76
45

Circuit Breaker Basis


for Rating:
MP40 (3-Pole) to MP63,
MC40 (3-Pole)

3.21
82

1.17
30

(*)

(*)

Circuit Breaker Basis


7.05
180
1.17 / 2.35
30 Min./ 60 Max.

1.72
44
(*)

Circuit Breaker Basis


for Rating:
MP08 to MP30 (4-Pole),
MC08 to MC32

Dimensions: inch
mm

59
11/98

1995 Square DAll Rights Reserved

Circuit Breaker Dimensions


Connecting Links for Three Stack-mounted Circuit Breakers
Fixed Mounting

06313176

06313177

Drawout Mounting

1.96
50

1.57
40

2.03
52

7.05
180

2.35
60

0.19
5

7.05
180

0.54
14

2.35
60

0.54
14

2.35
60

35.29
900
Max.

35.29
900
Max.

1.96
50
50

1.57
40

2.03
52

7.05
180

2.35
60

0.19
5

7.05
180
35.29
900
Max.

35.29
900
Max.
1.96
50
1.96
50
2.54
65

(*)

1.76
45

6.5
166

6.86
175
4.11
105

35.29
900
Max.

1.17
30

Circuit Breaker Basis for Ratings:


MP40 (3-Pole) to MP63, MC40 (3-Pole)

2.35
60

(*)
Circuit
Breaker
7.05
Basis
180
1.17 / 2.35
30 Min. / 60 Max.

2.43
62
(*)

Circuit Breaker Basis for Ratings:


MP08 to MP30 (4-Pole), MC08 to MC32

Mechanical Interlocks for Drawout or Fixed Circuit Breakers


Cables for Two Side-by-Side Circuit Breakers

06313178

6.56 ft.
2 m Max.

7.87
200 Min.
r= 4.72
r= 120 Min.

Mounted on Rails

r= 4.72
r= 120 Min.

Mounted on Backplate

Dimensions: inch
mm

(Except as otherwise
indicated)
60
1995 Square DAll Rights Reserved

11/98

Circuit Breaker Dimensions


DC150 Data Concentrator
06313179

4 .20
4 5

BBus

JBus

OK

com

com

error

24V

error

CD
0

EF

1
456
23

EF

789

CD

N2

AB

N1

5.47
139

4.92
125

AB

456
23

9600
19200
789

N1
N2

3.94
100

7.60
193

3.94
100

1.97
50

06313180

SC150 Indication and Control Interface

1.97
50
4.13
105

6.50
165
2 .20
2 5

2.80
71

4.92
125

6.89
175

Dimensions: inch
mm

61
11/98

1995 Square DAll Rights Reserved

Appendix

Routine Maintenance Guidelines

DANGER
HAZARD OF ELECTRICAL SHOCK, BURN
OR EXPLOSION.
Turn OFF all power supplying the equipment
before installing or removing circuit breaker.
Failure to observe these precautions will
cause death, personal injury or electrical
shock.

CAUTION
HAZARD OF EQUIPMENT DAMAGE.
Since circuit breakers contain factory-sealed
and calibrated elements. Do not break seal. In
case of malfunction, repairs must be made at
a Square D factory or by an authorized
company representative.
Failure to observe this precaution can
cause equipment damage.

Recommended Inspection Intervals


MASTERPACT circuit breakers are designed to be maintenance free (see page 64). However, all
equipment with moving parts requires periodic inspection to ensure optimum performance and
reliability. It is recommended that the circuit breakers be routinely inspected six months after
installation, followed by an annual inspection. Intervals can vary depending on particular use and
experience.
Inspection of Circuit Breaker Terminals
n Inspect terminals; if there is discoloration due to overheating, the joint should be disassembled

and the surface cleaned before reinstallation. It is essential that electrical connections are made
carefully in order to prevent overheating.
n Check for terminal tightness.
Inspection of Main Contacts
The arc chutes are easily removed to allow access to the main contacts and to the wear indicator.
The wear indicator consists of a groove located within the contacts support (see page 3). When the
circuit breaker is closed, this groove is entirely covered up by the moving contacts. Over time, the
wear of the contacts will make the groove appear. When the groove is fully visible, replace the
breaker or have an authorized service center change the contacts.
Inspection of Clusters
Totally maintenance free, they have to be replaced only after overheating due to a defective
connection or after a major fault. Inspection is advised when checking the terminal connections.
Cleaning
Remove any dust and dirt that may have accumulated on the circuit breaker surface and terminals.
Mechanical Checks
For long periods circuit breakers may not be required to operate on overload or short-circuit
conditions. Therefore it is essential to operate the circuit breaker periodically to avoid mechanical
gumming.

62
1995 Square DAll Rights Reserved

11/98

Appendix

Insulation Resistance Tests


When circuit breakers are subjected to severe operating conditions, an insulation resistance test
may be performed as indicated in NEMA standard publication No. AB4-1991. An insulation
resistance test is used to determine the quality of the insulation between phases and phase-toground. The resistance test is made at a dc voltage higher than the rated voltage to determine the
actual resistance of the insulation. The most common method employs a "megger" type instrument.
A 1000-volt instrument will provide a more reliable test because it is capable of detecting tracking on
insulated surfaces. Investigate resistance values below 1 megohm. The insulation test shall be
made:
n Between line and load terminals of individual poles with the circuit breaker contacts open
n Between adjacent poles and from poles to the metallic supporting structure with the circuit
breaker contacts closed
This test may be made with the circuit breaker in place after the line and load conductors have been
removed, or with the circuit breaker bolted to a metallic base which simulates the in-service
mounting.
Electrical Tests
These tests require equipment for pole resistance measurement and for overcurrent and
instantaneous tripping in accordance with NEMA Standard publication No. AB4. They are not within
the scope of normal field operation.

63
11/98

1995 Square DAll Rights Reserved

Appendix
Endurances
AEndurance Without Maintenance
MASTERPACT
MP or MC
Mechanical
Electrical

08

12

16

20

25

30 - 32

40

50

63

12,500

10,000

10,000

10,000

10,000

10,000

5,000

5,000

5,000

480 Vac

10,000

10,000

10,000

9,000

8,000

4,000

3,000

3,000

2,000

600 Vac

10,000

10,000

10,000

7,000

6,000

2,600

2,500

2,500

1,500

20,000

15,000

15,000

15,000

10,000

10,000

10,000

BEndurance With Service Maintenance


Electrical (480 Vac) or Mechanical
20,000

20,000

CEndurance Required by Standards


Frame size
UL489

800
Mechanical 3,500
Electrical

ANSI

500

1200

1600

2000

2500

3000

4000

5000

6300

2,000

2,000

2,000

2,000

1,500

1,500

1,500

1,500

500

500

500

500

400

400

400

400

Mechanical 12,500

NS

4,000

4,000

NS

1,500

1,500

NS

NS

Electrical

NS

800

800

NS

400

400

NS

NS

2,800

Important Notice:
All endurances given are based on normal operating conditions and conventional tests:
n Closing and opening operations at rated current
n Power factor: 0.750.80
As actual conditions differ, use these values only as inspection guidelines and periodically check
contact wear.
Under normal operating conditions of use, as determined by UL 489 or ANSI Standards (see table
C) and controlled by tests, MASTERPACT circuit breakers do not require maintenance. However,
these circuit breakers exceed, without maintenance and additional costs, the endurances required
by standards. See tables A and C. Service maintenance by a field service representative will extend
the endurance according to table B. This service can be performed on site and consists in changing
contacts, arc chutes and some other parts.
Example:
MP16 at 480 V requires no maintenance before 10,000 cycles (mechanical or electrical). Endurance
may be increased after servicing at 10,000 operations.

64
1995 Square DAll Rights Reserved

11/98

Appendix
IEC 947-2 Interrupting Ratings
In addition to UL 489 and ANSI C37-13, MASTERPACT circuit breakers comply with the IEC 947-2
Standard as per the table below. For further information, contact a sales representative.
Type
3-Pole

Ampere
Rating (A)

Interrupting Ratings
UL489
RMS Symmetrical Amps
480 Vac
600 Vac

IEC 947-2
Short-time

440 Vac
Icu

Ics

690 Vac
Icu

Ics

Standard Interrupting Rating


MP08 H1

800

65 kA

65 kA

50 kA

65 kA

65 kA

65 kA

65 kA

MP12 H1

1200

65 kA

65 kA

50 kA

65 kA

65 kA

65 kA

65 kA

MP16 H1

1600

65 kA

65 kA

50 kA

65 kA

65 kA

65 kA

65 kA

MP20 H1

2000

75 kA

75 kA

75 kA

75 kA

75 kA

75 kA

75 kA

MP25 H1

2500

75 kA

75 kA

75 kA

75 kA

75 kA

75 kA

75 kA

MP30 H1

3000

75 kA

75 kA

75 kA

75 kA

75 kA

75 kA

75 kA

MP40 H1

4000

100 kA

100 kA

100 kA

100 kA

100 kA

85 kA

85 kA

MP50 H1

5000

100 kA

100 kA

100 kA

100 kA

100 kA

85 kA

85 kA

MP63 H1

6300 (1)

100 kA

100 kA

100 kA

100 kA

100 kA

85 kA

85 kA

High Interrupting Rating


MP08 H2

800

100 kA

65 kA

50 kA

100 kA

100 kA

85 kA

85 kA

MP12 H2

1200

100 kA

65 kA

50 kA

100 kA

100 kA

85 kA

85 kA

MP16 H2

1600

100 kA

65 kA

50 kA

100 kA

100 kA

85 kA

85 k A

MP20 H2

2000

100 kA

75 kA

75 kA

100 kA

100 kA

85 kA

85 kA

MP25 H2

2500

100 kA

75 kA

75 kA

100 kA

100 kA

85 kA

85 kA

MP30 H2

3000

100 kA

75 kA

75 kA

100 kA

100 kA

85 kA

85 kA

MP40 H2

4000

125 kA

100 kA

100 kA

150 kA

125 kA

85 kA

85 kA

MP50 H2

5000

125 kA

100 kA

100 kA

150 kA

125 kA

85 kA

85 kA

MP63 H2

6300 (1)

150 kA

100 kA

100 kA

150 kA

125 kA

85 kA

85 kA

(1) Not UL Listed.

65
11/98

1995 Square DAll Rights Reserved

Appendix
IEC 947-2 Ratings
Auxiliary and Position Switches
Voltage (V)

Auxiliary Switch
OF

50/60 Hz

DC

110

OFSUP

Overcurrent
Trip Switch
SDE

Ready to
Close Switch
PF

Position
Switches
CE/CD/CT

15

240

10

10

10

10

10

10

380

10

480

10

600

48

6
3
3

125

0.5

0.5

0.3

0.3

0.5

250

0.25

0.25

0.15

0.15

0.25

500

0.5

OF: Heavy Duty

O: Standard

OFSUP: 24 Additional

CE: Connected

CD: Disconnected

CT: Test

Spring Charging Motor


Rated Voltage (V)
UL 489 Listed
60 Hz

IEC 947-2
120

50/60 Hz

240
DC

24

100-127
200-240

DC

24-30

48

48-60

125

100-125

Closing Coil
Rated Voltage (V)
UL 489 Listed
60 Hz

IEC 947-2
120

50/60 Hz

240
DC

24

110-127
220-250

DC

24

48

48

125

125

250

250

Shunt Trip
Rated Voltage (V)
UL 489 Listed
60 Hz

IEC 947-2
120

50/60 Hz

240

220-250

480
DC

24

110-127

440-480
DC

24

48

48

125

125

250

250

Undervoltage Trip
Rated Voltage (V)
UL 489 Listed
60 Hz

IEC 947-2
120

50/60 Hz

240

220-250

480
DC

24

110-127

440-480
DC

24

48

48

125

125

250

250

66
1995 Square DAll Rights Reserved

11/98

Notes

67
11/98

1995 Square DAll Rights Reserved

Notes

68
1995 Square DAll Rights Reserved

11/98

Notes

69
11/98

1995 Square DAll Rights Reserved

Notes

70
1995 Square DAll Rights Reserved

11/98

Notes

71
11/98

1995 Square DAll Rights Reserved

Notes

72
1995 Square DAll Rights Reserved

11/98

Square D Company
PO Box 3069, 3700 Sixth St SW
Cedar Rapids, IA 52406-3069 USA
Field Services: 1-800-634-2003
www.squared.com

are registered trademarks of Square D Company.


POWERLOGIC, Square D and
MASTERPACT, COMPACT and MULTI 9 are registered trademarks of Schneider Electric.
DIGIPACT is a registered trademark of Merlin Gerin. MODBUS is a registered trademark of
Schneider Automation. All other trademarks are the intellectual property of their respective
companies.
0631CT9501R11/98November 98Printed in USA 1998 Square DAll Rights Reserved

Potrebbero piacerti anche