Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Circuit Breaker
Class 631
CONTENTS
Description
Page
Introduction ............................................................................................................... 1
Advantages ............................................................................................................... 3
Description ................................................................................................................ 6
Control Units ............................................................................................................. 7
Accessories ............................................................................................................. 23
Switch ..................................................................................................................... 36
Trip Curves ............................................................................................................. 37
Wiring Diagrams ..................................................................................................... 42
Circuit Breaker Dimensions .................................................................................... 46
Appendix ................................................................................................................. 62
Introduction
Standard Compliance
n UL489: MP08 to MP50 circuit breakers and their accessories are Listed under UL files E63335,
100% Rated
The circuit breakers are designed for continuous operation at 100% of their current rating.
Other Performances
The UL 489 and UL1066 (ANSI C37-13) standard performance tests assure that the circuit breaker
has sufficient characteristics to be used in normal conditions. However, the circuit breaker exceeds,
without additional costs, the UL standard 1,500 operations required in endurance. The heavy-duty
mechanism and the contact design provide a mechanical endurance of 10,000 operations (approx.)
without maintenance (see page 64).
Tropicalization
The standard moisture and fungus protection ensure normal operation under extreme ambient
conditions. MASTERPACT circuit breakers comply with T2 tropicalization (IEC Standard 68-2-30);
relative humidity 95% at 113F (45C) and 80% at 131F (55C) (hot, humid climate). Salt spray
resistance as per IEC 68-2-11.
Poles
The 4-pole version is an efficient solution to ground fault problems created by incorrectly grounded
standby generators and incorrect transfer switching systems. By isolating the neutral of multiple
sources coupled together, 4-pole circuit breakers prevent ground faults from returning to the source
via unintended paths. Where unintended paths exist, ground fault sensing can become inaccurate or
create nuisance tripping.
Ampere Rating (A)
3-Pole
4-Pole
800
MP-MC
MP-MC
1200
MP
MP
1600
MP-MC
MP-MC
2000
MP-MC
MP-MC
2500
MP
MP
3000
MP
MP
3200
MC
4000
MP-MC
MP (1)
5000
MP-MC
MP (1)
6300
MP (1)
1
11/98
Introduction
Ratings
Type
MP/MC08
800
MP12
1200
8001200
MP/MC16
1600
12001600
MP/MC20
2000
16002000
MP25
2500
20002500
MP30
3000
25003000
MC32
3200
25003200
MP/MC40
4000
250030004000
MP/MC50
5000
40005000
MP63
6300
50006300
Interrupting Ratings
UL489/NEMA AB1
Type
Rating (A)
480 Vac
600 Vac
Short-time
800
65 kA
65 kA
50 kA
MP12 H1
1200
65 kA
65 kA
50 kA
MP16 H1
1600
65 kA
65 kA
50 kA
MP20 H1
2000
75 kA
75 kA
75 kA
MP25 H1
2500
75 kA
75 kA
75 kA
MP30 H1
3000
75 kA
75 kA
75 kA
MP40 H1
4000
100 kA
100 kA
100 kA
MP50 H1
5000
100 kA
100 kA
100 kA
MP63 H1
6300 (1)
100 kA
100 kA
100 kA
800
100 kA
65 kA
50 kA
MP12 H2
1200
100 kA
65 kA
50 kA
MP16 H2
1600
100 kA
65 kA
50 kA
MP20 H2
2000
100 kA
75 kA
75 kA
MP25 H2
2500
100 kA
75 kA
75 kA
MP30 H2
3000
100 kA
75 kA
75 kA
MP40 H2
4000
125 kA
100 kA
100 kA
MP50 H2
5000
125 kA
100 kA
100 kA
MP63 H2
6300 (1)
150 kA
100 kA
100 kA
508 V
635 V
Short-time
Rating (A)
800
50 kA
50 kA
42 kA
MC16 N1
1600
50 kA
50 kA
50 kA
800
65 kA
65 kA
50 kA
MC16 H1
1600
65 kA
65 kA
50 kA
MC20 H1
2000
65 kA
65 kA
65 kA
MC32 H1
3200
65 kA
65 kA
65 kA
MC40 H1
4000
100 kA
100 kA
100 kA
MC50 H1
5000
100 kA
100 kA
100 kA
2
1995 Square DAll Rights Reserved
11/98
Advantages
Drawout Circuit Breaker Design
n The drawout assembly mechanism allows the circuit breaker to be racked in four positions
06313005
06313004
06313003
through the front door cutout. Therefore the circuit breaker can be disconnected without opening
the door and accessing live parts. Safety shutters can be provided as an option for protection from
live parts when the circuit breaker is removed.
Connected Position
Test Position
Disconnected Position
06313006
06313007
It is easy to remove the arc chutes and visually inspect the contacts and wear indicator. The operation
counter (spring-charging motor option) can also indicate when inspections and possible maintenance
should be done. After operating conditions exceeding those given by standards, it is possible to
extend the circuit breaker life by:
n Replacement of arc chutes and spring charging motor by the user.
n Replacement of main contacts by an after sale service team.
Note: See pages 6263 for additional information.
Contact Good
(Circuit Breaker Closed)
Contact Worn
(Circuit Breaker Closed)
3
11/98
Advantages
Single Design up to 6300 A
All frame sizes have been designed with the same technology featuring identical depth and door
cutouts, and common control units and accessories.
40-50
32
08-30
06313008
63
IG
LI
G
off
LIG
reset V
push to reset
LG
masterpact
I
I3
I2
I1
90%
push OFF
I
push ON
STR 58 U
tr
Ir
.92
.95 60
.9
.88
Io=3000A
%Ir
.98 30
.85
.8
xIo
for masterpact
with sensors
Im
3
2
1.5
Ir fault
.3
.2
12
off
O OPEN
240
th :
.2
.1
0
off
Ih
600
800
500
th
th .4
.4
.3
.3
1000 .2
320
250
i
+S
.95
.7
.98
.6
.2
.1
off
Ic2.8
.93
.85
.9
.86
.8
T+
.1
2
on I t
1200
Ic1 .9
.85
test
N LM-8792
22
400
Im fault
tm
fault
Doles. Issue
NEMA
interrupting rating
amps
max RMS sym
Amps
Volts
100K
240
100K
480
65K
600
.3
17
xIn
tr
Ih
E63335
List.
UND. LAB. O
CIRCUIT BREAKER
00000
480
15
at 1,5Ir
.1
2
on I t
10
xIo
6
4
Im :
120
tm.4
In = 6000A
Ir :
circuit breaker
3 pole
600V 50/60Hz
discharged
20%
90
105
M08 H2
operation
cubical
suitable for continious
in a minimum
inches
at 100% rating
by W21 by D14.1/4
space H17.5 not required
ventilation is
50%
1
xIr
.95
1
.5
xIr
690V 50/60Hz
IEC 957-2 rating
interrupting
75KA
Icu 380/440V
75KA
660V
75KA
Icu 380/440V
75KA
660V
short time rating
sec.
Icw=75KA 0.5
test
connected
test
disconnected
Field-installable Accessories
n As the installation develops and changes, the circuit breaker can develop and change with it.
06313009
Most accessories are field-installable, without losing the UL Listing mark, without any adjustment
and with only the aid of a screwdriver.
n The uniform design of the circuit breaker line allows these accessories to be common for the
whole line.
06313010
All accessory terminals are located on a connecting block which is accessible from the front even
with the circuit breaker in the test or disconnected position. This is particularly useful for field
inspection and modification.
4
1995 Square DAll Rights Reserved
11/98
Advantages
Disconnecting through Door
The racking handle and racking mechanism are accessible through the front door cutout.
Disconnecting the circuit breaker will therefore be possible without opening the door and giving
access to live parts.
Segregated Compartment
Once the front cover has been removed to provide access to the auxiliary compartment, the main
contacts remain fully isolated. Furthermore, interphase partitioning allows full insulation between
each pole even if the front cover has been removed.
Reinforced Insulation
06313011
Two insulation barriers separate the front of the circuit breaker from main circuits.
5
11/98
Description
Description
06313012
4
5
13
12
6
11
10
9
11
Front View
1.
2.
3.
4.
06313013
12
IG
LI
G
off
LIG
reset V
push to reset
LG
1
LIN GERIN
MER
masterpact
I3
I2
I1
push OFF
90%
MP20
H1
r
circuit breake
3 pole
z
600V 50/60H
push ON
STR 58 U
50%
O
OPEN
20%
tr
Ir
Io=3000A
90
%Ir
105
.92
.95 60
.9
.88
.98 30
.85
.8
xIo
for masterpact
with sensors
Ir :
t
Ir fault
.1
0
off
Ih
600
800
500
th
400
i
+S
1200
Ic1 .9
.4
.3
.3
z
690V 50/60H
IEC 957-2 rating
interrupting
75KA
Icu 380/440V
75KA
660V
75KA
Icu 380/440V
75KA
660V
rating
short time
sec.
Icw=75KA 0.5
.2
.1
.1
2
on I t off
.8
T+
Ic2.8
.93
.95
.7
.98
.6
.85
.9
.86
.85
test
th .4
1000 .2
320
250
7.
8.
off
th :
Im fault
tm
fault
6.
22
xIn
tr
Ih
N LM-8792
17
Im :
.2
.1
2
on I t
12
E63335
List.
UND. LAB. O
CIRCUIT BREAKER
Doles. Issue
interrupting rating
amps
max RMS sym
Amps
Volts
75K
240
75K
480
75K
600
75KA
short time rating
.3
.2
10
xIo
00000
15
at 1,5Ir
6 .3
3
2
1.5
240
480
tm.4
In = 6000A
Im
120
discharged
5.
1
xIr
.95
1
.5
xIr
test
connected
test
9.
10.
11.
12.
Charging handle
Manual opening push button
Manual closing push button
Stored energy mechanism status indicator
(charged or discharged)
Main contact position indicator (open or
closed)
Disconnected position locking (key
interlock)
Disconnected position padlocking
Drawout position indicator showing that the
circuit breaker is in the connected, test or
disconnected position
Racking crank storage
Door escutcheon
Fault indicator and reset button
Open position locking (key interlock)
disconnecte
10
6
1995 Square DAll Rights Reserved
11/98
Control Units
06313014
The circuit breaker can be equipped with a microprocessor-based, electronic control unit which
provides all the traditional protection of the universal power circuit breaker (long-time, short-time,
instantaneous and ground-fault) plus other built-in functions:
n RMS sensing (standard)
n Alarm switch (standard)
n Overcurrent trip switch (standard)
n Interchangeable rating plugs (on STR28DP, STR38SP and STR58UP)
n Thermal memory and I2t ramp (standard on STR 38-58 control unit)
n Defeatable instantaneous (standard on STR 38-58 control unit)
n Zone-selective interlocking for ground-fault and short-time (option)
n Current and load meter (option)
n Load-monitoring outputs (option)
n Fault indicators (option)
n Communication ability (option)
Control Units
STR 18M
STR 28D
STR 38S
STR 58U
Basic Features
Long-time (1)
Short-time
Setting
Adjustable
Adjustable
Adjustable
Delay
Fixed
Fixed
Adjustable
Pickup
Adjustable
Adjustable
Delay
Adjustable
Adjustable
Adjustable
Fixed (2)
Adjustable (2)
Standard
Standard
Standard
Instantaneous
Adjustable
Test Receptacle
Fault Indicators
Zone-selective Interlocking
Load Monitoring
Communication Outputs
7
11/98
06313015
Control Units
STR 28D Control Unit for General Application
1
push to reset
2
I1
I2
I3
90%
STR 28 D
50%
3
4
5
20%
Ir
90
.9
.92
.95
.88
%Ir
.98
.85
105
6
7
.8
xIo
Im
2
1.5
xIr
t
10
Ir :
Ir
9
10
Im :
Long-time
Current Setting
i
+
Rating Plug
11
test
06313016
Im
Long-time Setting
Instantaneous
Max. Delay
Current Sensor
Plug Rating
250 A
250200150125 A
400 A
400300250200 A
600 A
600500400300 A
800 A
800600500400 A
1200 A
12001000800600 A
1600 A
160012001000800 A
2000 A
2000160012001000 A
2500 A
2500200016001200 A
3000 A
3000250020001600 A
3200 A
32003000250020001600 A
4000 A
40003200300025002000 A
5000 A
50004000320030002500 A
6300 A
630060005000400032003000 A
Pickup
Instantaneous
Values Displayed
Accuracy
1.5 % (2)
Control Power
Local
Remote
(1) According to time-current curves: between 105% and 120% of current setting.
(2) Total accuracy including current sensors: 4.5%.
(3) Control power not required for loads greater than 20% of current sensor. Required for load less than 20%
of current sensors if maximum demand memory requested (see diagram on p. 43).
8
1995 Square DAll Rights Reserved
11/98
Control Units
06313017
push to reset
2
I1
I2
3
4
I3
90%
STR 38 S
50%
6
7
8
9
20%
Ir
90
.9
.92
.95
.88
%Ir
.98
.85
105
.8
xIo
Im
tm
.4
6 .3
2
1.5
8
10
xIr
t
.3
10
.2
.2
.1
.1
0
on I2t off
11
12
13
Ir :
Ir fault
Im :
max.
tr
off
xIn
th :
Ih
Ih
500
fault
Im fault
tm
th
600
800
400
320
I
250
th
.3
.4
.4
14
.3
1000 .2
.2
.1
.1
1200
on I2t off
15
16
i
overcurrent
test
ground
18
F
test
17
19
Current Setting
Delay
06313018
4 to 6 Rating Plugs Available Per Sensor Rating: See STR 28D Control Unit, p. 8
Short-time
Pickup
Delay Bands
Long-time Setting
Instantaneous
Pickup
Ground-fault
Pickup
Ground-fault
Delay
Short-time
Pickup
Pickup
Delay Band
Short-time Delay
Discriminated
Instantaneous
Local
Remote
Local
Accuracy
1.5% (6)
9
11/98
06313019
Control Units
V
push to reset
reset V
I+T
L+I
off
L+I+T
1
2
L+T
3
I1
I2
I3
90%
STR 58 U
6
7
8
9
10
11
50%
20%
Ir
90
tr
.88
120
.92
.95 60
.85
.9
.98 30
240
%Ir
105
.8
Im
norm
min.
tr
tm
.4
6 .3
2
1.5
Ir :
12
.2
.1
.1
0
on I2t off
10
12
.3
.2
xIr
I
480
15
at 1.5Ir
xIo
13
14
15
14
19
Ir fault
Im :
22
Max.
2
tr
21
xIn
Ih 1200A Max th
th :
Ih
fault
Im fault
tm
th
i
overcurrent
test
22
23
F
test
.4
600
800
320
250
1000 .2
.2
.1
.1
1200
on I2t off
Ic1
.93
.95
.7
.8
.98
.6
xIr
16
17
.3
.3
Ic2
.9
.86
.85
ground
.4
500
400
.85
.9
.8
.95
.5
xIr
18
19
20
10
1995 Square DAll Rights Reserved
11/98
06313020
Control Units
t
Current Setting
Delay Bands
Long-time Pickup
Ground-fault
Pickup
Ground-fault
Delay
Short-time Pickup
Short-time Pickup
Instantaneous Pickup
Short-time
Current Sensor
Plug Rating
250 A
250200150125 A
400 A
400300250200 A
600 A
600500400300 A
800 A
800600500400 A
1200 A
12001000800600 A
1600 A
160012001000800 A
2000 A
2000160012001000 A
2500 A
2500200016001200 A
3000 A
3000250020001600 A
3200 A
32003000250020001600 A
4000 A
40003200300025002000 A
5000 A
50004000320030002500 A
6300 A
630060005000400032003000 A
Pickup
Delay bands
Pickup
Discriminated
Local
Remote
Local
Remote
Accuracy
1.5% (4)
Pickups
Time delay
See Curve, p. 41
11
11/98
06313182
Control Units
Thermal Memory
push to reset
Purpose
The thermal memory function allows an optimization of cables or bus bar protection in case of low
amplitude repetitive faults. Such faults can be due to repetitive motor startings, fluctuating load or
subsequent closing after a fault.
I1 I2 I3
90%
STR 58 U
50%
Traditional electronic protection has no effect when facing such repetitive faults because the
duration of each overload above the pickup setting is too short to achieve effective tripping.
Nevertheless, each overload involves a temperature rise in the installation, the cumulative effect of
which could lead to overheating of the system.
20%
Ir
xIn
tr
xIo
Im
at 1.5Ir
tm
xIo
t
Principle
I
xIn
Ih
i Ic1
th
Ic2
DANGER
xIn
test
xIr
xIr
test
06313184
06313183
The thermal memory function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay
and, therefore, the reaction of the control unit will be closer to the real heating of the power network
system. After tripping, the memory will also reduce the time delay when closing the circuit breaker
on fault.
I
Temperature
Pickup Setting
06313185
06313186
The STR 38S and STR 58U trip units incorporate the thermal memory as standard:
n Before tripping on long-time and ground-fault protection (if provided)
n After tripping on long-time protection only, adjustable min./max. position for the STR 58U trip unit
is standard
The control unit measures the internal temperature rise of the circuit breaker by thermal resistors. The
cooling time constant of the memory is not fixed, but depends on the over-temperature condition.
I2 t
I 2t
Trip Level
Trip Level
12
1995 Square DAll Rights Reserved
11/98
06313021
Control Units
Neutral Sensor
T1
T2
S1
S2
06313023
Neutral
Ground-fault
Neutral CTs
S1
T1
S2
T2
06313022
Z12
Z11
Z22 Out
Z21 In
Fault 1
Circuit breaker A will clear the fault
instantaneously, regardless of its time-delay
setting.
Z12
Z11 Out
Z22
Z21 In
Z12
Z11 Out
Z22
Z21 In
Z12
Z11
Z22
Z21
Out
In
Z12
Z11
Z22
Z21
Out
In
Z12
Z11 Out
Z22
Z21 In
Fault 2
Circuit breaker B will inform upstream circuit
breaker A that it is clearing the fault and will
prevent it from tripping instantaneously. Circuit
breaker A will trip at the end of its time delay
setting if the fault is not cleared during this time.
Note:
n Drawout circuit breaker terminals are
delivered with "in" terminals jumpered.
Remove the jumper when interlocking with a
downstream circuit breaker.
n The MASTERPACT circuit breaker may also
be interlocked with COMPACT NS and CK
type molded case circuit breakers with ZSI
option.
n Do not ground ZSI wiring.
Cable Size
#18#14 AWG/1.5mm2
Max. Length
90 ft./30 m
Wiring
Upstream: 2
Downstream: No Limit
13
11/98
push to reset
I1 I2 I3
90%
STR 58 U
50%
20%
Ir
tr
xIo
Im
at 1.5Ir
tm
xIo
t
i Ic1
06313025
xIn
Ih
th
xIn
Ic2
24 Vdc
1W
06313027
In addition to the mechanical fault indicator, this indicator differentiates the three causes of tripping:
overload, short circuit or ground fault, if any. Three light-emitting diodes indicate separately longtime, short-time/ instantaneous and ground-fault trip. A flat push button allows resetting of the
indicator after tripping. A separate power supply is required to maintain the indication after tripping
of the circuit breaker. Two different possibilities are offered:
n Connecting a reliable 24 Vdc control voltage on F1-F2. Auxiliary power module (AD) is used for
other voltages. When the control source is considered as unreliable, a battery pack (BAT) is to
be added to an AD power module.
n From a built-in battery module. When no external control source is available, a built-in battery
module may be ordered (option PIL). This module integrates battery testing and indicator
reactivating buttons.
06313026
06313024
Control Units
AD (1)
test
xIr
xIr
AD (1)
test
BAT
+
F1
F2
F1
F2
F1
F2
Configuration with
Interruptible Control Voltage
06313028
Delivered as standard with control unit. The alarm indicator is a fixed, front face light-emitting diode
which operates as follows:
n Fixed when the current exceeds 90% of the current setting.
n Flashing on overload: according to time-current curves, 105% to 120% of current setting.
The pre-trip alarm switch is a static contact which closes when in the overload zone, up to the
tripping of the circuit breaker. This contact can be used for ultimate load shedding, alarm before
tripping, etc.
I1 I2 I3
90%
STR 58 U
50%
ALR
20%
Ir
tr
xIo
Im
at 1.5Ir
tm
Output Characteristics
Power Supply
Not Required
xIo
t
I
xIn
Ih
i Ic1
th
Ic2
xIn
test
xIr
xIr
test
14
1995 Square DAll Rights Reserved
11/98
Control Units
Overcurrent Trip Switch (SDE)
06313029
Delivered standard with control unit. In addition to the fault trip indicator/reset button, one SPDT
switch provides alarm/lockout information. This SPDT switch is operated only when the circuit
breaker is tripped by the control unit. When the circuit breaker is reset, the "a" switch (alarm) is
open and the "b" switch (lockout) is closed.
Output Characteristics
Power Supply
Not Required
Fault
82
84
SDE
81
V
06313030
This switch works exactly as the standard overcurrent trip switch (SDE) except that a commutator
on the front face is used to choose the type of fault which will operate the contact: overload, shortcircuit, ground-fault, or any combination of these types. This option can be used in addition to the
SDE switch for remote signalization of particular types of faults. A flat push button allows resetting of
the indicator after tripping.
I1 I2 I3
90%
STR 58 U
50%
Output Characteristics
5 A/240 Vac
Power Supply
Required
20%
tr
xIo
Im
at 1.5Ir
tm
Wired in parallel with the remote opening button which operates the shunt trip, the option FV
contact provides an electrical interlock which prevents the circuit breaker from being closed after the
pre-selected type of faults: for example the circuit breaker will be able to be remotely closed after
overload, but not after short circuit.
xIo
t
i Ic1
th
Ic2
xIn
test
xIr
xIr
06313031
xIn
Ih
06313032
Ir
Fault
Remote
Open
Fault
test
V2
C2
V2
MX
V
V
V1
V1
C1
15
11/98
06313033
Control Units
Load monitoring (R)
push to reset
Option R provides two independent static contacts which operate when the current exceeds
adjustable pickup limits:
n When the current exceeds the limit Ic1 (or Ic2), the contact C-R1 (or C-R2) closes following an
inverse time characteristic A.
n When the current drops below the limit Ic1 (or Ic2), the contact C-R1 (or C-R2) opens with
constant time delay (10 seconds) B.
These contacts can be used for load shedding, alarms, indications, etc.
I1 I2 I3
90%
STR 58 U
50%
20%
Ir
tr
xIo
Im
at 1.5Ir
tm
Voltage
Outputs
0.1 A triac
xIo
t
xIn
Ih
i Ic1
th
Ic2
06313034
xIn
Long-time
test
xIr
xIr
test
Test Kits
06313036
06313035
Every control unit is equipped with a test receptacle that can be used with a test kit. Tests
performed by test kits are only functional tests designed to electrically test the operating integrity of
the control unit, the flux transfer device and the mechanical operation of the circuit breaker. Tests
are not designed to calibrate the circuit breaker. Calibration can only be done at the factory.
16
1995 Square DAll Rights Reserved
11/98
Control Units
Communication
MASTERPACT circuit breakers can be easily connected to a supervising personal computer using
the DIGIPACT system. The following four functions can thus be provided:
n Indication:
o Status of the circuit breaker (on, off or tripped; connected or disconnected)
o Causes of tripping (overload, short circuit or ground fault)
n Monitoring:
o Operation of circuit breaker (open, closed or reset)
o Resetting a molded case circuit breaker (COMPACT NS and CK)
n Management:
o Control unit settings
o Pre-trip alarm
o Load monitoring status
o Control unit internal temperature alarm
o Number of operation cycles performed by the circuit breaker
n Metering:
o RMS value of the current in three phases
06313037
MODBUS /JBUS
IN
LIN GER
MERSV
pulsar
JBus
BBus
com
24V
OK
error
1 3
com
error
DIGIPACT DC150
Data Concentrator
POWERLOGIC
Circuit Monitor
POWERLOGIC
Power Meter
N1
N1
Internal Bus
push
to
trip
push
push
GERIN
MERLIN
9
multi
ATB1s
17
11/98
Control Units
06313038
Note: When associated with the SC150 interface, COMPACT NS circuit breakers are equipped with
standard auxiliary switches and motor operators. The SC150 indication and control interface is not
required with COMPACT NS circuit breakers equipped with communication-type auxiliary switches
or a communication-type motor operator.
Information or Function Managed by the SC150 Indication and Control Interface
Information Transmitted or
Function Carried Out
As Above
As Above
As Above
18
1995 Square DAll Rights Reserved
11/98
Control Units
SC150 Indication and Control Interface (continued)
Technical Data
Digital Inputs (24 V, Self-powered by the SC150 Interface)
O Auxiliary Switch
One Input
F Auxiliary Switch
One Input
One Input
One Input
CE Auxiliary Switch
One Input
CD Auxiliary Switch
One Input
One Input
Other Uses
Electrical Characteristics
Voltage (Supplied by SC150)
24 Vdc
120 mA dc
Resistance in On-state
< 30 m
Resistance in Off-state
> 10000 M
Control Outputs
Opening
Closing
Reset
Voltage
Interrupting Rating
AC
2500 VA
DC
Utilization Category
Electromagnetic Compatibility
Electrostatic Discharges
(IEC 1000-4-2)
Level 3
Radiated Susceptibility
(IEC 1000-4-3)
Level 3
Low-energy Conducted
Susceptibility (IEC 1000-4-4)
Level 4
High-energy Conducted
Susceptibility (IEC 1000-4-5)
Level 4
Class A
Dimensions
Weight
Front Face
IP30
Other Faces
IP30
Connections
IP20
Fc Test
Wiring Diagram
See p. 44
Dimensions
See pp. 61
19
11/98
Control Units
06313039
o
o
As Above
As Above
As Above
Accessories
Connection
Junction Block
06313042
06313116
06313040
RS232/RS485 Converter
06313041
Connector
20
1995 Square DAll Rights Reserved
11/98
Control Units
DC150 Data Concentrator (continued)
1
06313043
Description
1.
2.
3.
4.
MERLIN GERIN
Digipact
DC150
BBus
JBus
OK
com
com
error
24V
error
5.
9600
19200
456
23
78 9
CD E
N2
AB
N1
CD E
15
78 9
AB
456
23
16
N1
N2
8
9
14
10
13
12
11
6.
7.
8-9.
10.
11.
12.
13.
14-15.
16.
Technical Data
Electrical Characteristics
Voltage
Tolerance
+10%15%
Electromagnetic Compatibility
Electrostatic Discharges
Level 3
(IEC 1000-4-2)
Radiated Susceptibility
Level 3
(IEC 1000-4-3)
Low-energy Conducted
Level 4
Susceptibility (IEC 1000-4-4)
High-energy Conducted
Level 4
Susceptibility (IEC 1000-4-5)
Class A
Emissions (EN 50081-1)
Protocol
MODBUS/JBUS (Slave)
Speed
Data Format
Physical Link
Function 1 or 2
Read N Words
Function 3 or 4
Function 5
Function 6
Write N Bits
Function 15
Write N Words
Function 16
Weight
IP30
IP20 (Connections)
Wiring Diagrams
See p. 45
Dimensions
See p. 61
21
11/98
Control Units
Sizing of the DIGIPACT Internal Bus
Sizing of the DIGIPACT internal bus depends on two factors:
n The number of devices on the bus
n The length of the bus
Number of Devices
As on any communications network, the number of devices that may be connected on the
DIGIPACT internal bus is limited. The maximum number of devices is calculated in terms of
"communication points." Each type of device represents a number of points indicated in the table
below. The total number of points for the various devices connected to a single bus must not exceed
100. If the required devices represent more than 100 points, simply add a second DIGIPACT
internal bus with a second DC150 data concentrator. The same sizing rules apply to the second bus
as well.
Communicating Device
Number of Points
Communicating Auxiliary Switches OF, SD, SDE for COMPACT NS Circuit Breakers
Communicating Motor Operator and Auxiliary Switches for COMPACT NS Circuit Breakers
0
0
0
Length of Bus
The table below indicates the cross-sectional area of the cable that must be used depending on the
total length of the bus.
Cross-sectional Area
The total resistance of the two wires for the bus must be less than 12 ohms. If the bus is too long,
simply:
n Increase the cross-sectional area of the cable.
n Create two shorter buses for the installation (in this case, a second DC150 data concentrator
is required).
22
1995 Square DAll Rights Reserved
11/98
Accessories
Location
Disconnected
Position
Switches
Terminal
Block
Connected
Position
Switches
Overcurrent
Trip Switch
06313046
Auxiliary
Switches
Opening Coil
Closing Coil
Heavy Usage
Auxiliary
Switches
Ready to
Close Switch
V
I+T
off
L+I+T
reset V
push to reset
L+I
L+T
I3
I2
I1
90%
STR 58 U
50%
20%
tr
Ir
.98 30
.85
%Ir
.8
105
Im
xIo
2
1.5
norm
min.
tr
I
8
Im :
tr
th :
Ih
th
19
22
320
250
i
overcurrent
Max.
xIn
.4
.4
.1
2
on I t
.1
off
.3
.3
.2
1000 .2
1200
A
Ic2
Ic1.9
.86
.8
th
800
.85
test
Spring
Charging
Motor
0
off
14
500
400
.2
.1
.2
.1
2
on I t
Ih 1200A Max
600
Im fault
tm
fault
480
.3
6 .3
8
10
xIr
12
Ir :
Ir fault
15
at 1.5Ir
tm.4
CTED
240
120
.92
.95 60
.9
.88
90
D
CONNECTE
TEST
DISCONNE
.93
.95
.7
.98
.6
xIr
R
.85
.9
.8
.95
.5
xIr
ground
F
test
Secondary Disconnects
Electrical accessories are UL Listed for field installation per UL file E113554. They are provided with
terminals and located on secondary disconnecting blocks above the circuit breaker:
n Fixed-mounted: By one or two connecting plugs (provided).
n Drawout-mounted: To terminal block A located in the front of the stationary assembly for easy
access. (This terminal block is then wired to another connection block B that operates
automatically to isolate the internal accessories when the circuit breaker is in the disconnected
position.)
06313010
06313044
23
11/98
Accessories
The MASTERPACT circuit breaker is equipped with a true two-step stored energy mechanism which
ensures fast opening and closing operations and complete open-close-open sequence without
recharging the mechanism. The MASTERPACT circuit breaker has manual actuators that include a
charging handle and push-to-open and push-to-close buttons. In addition, remote operation is
possible with the following field-installable accessories:
n Spring charging motor (MCH)
n Closing release (XF)
n Undervoltage trip device (MN) or shunt trip (MX) for opening
The manual operating mechanism can still be used in an emergency. The addition of the electrical
operating mechanism does not alter circuit breaker dimensions.
06313047
06313048
Consumption
60 Hz
120240
DC
2448125
AC
180 VA
DC
180 W
Inrush Current
Charging Time
3 to 4 sec.
Spring
Charged
262
B4
CH
B1
Spring-charged Switch
This type "b" switch is closed when the spring is charged. It comes standard with the spring
charging motor and is provided with a common terminal.
Max. Current (A)
60 Hz
240 V
10
DC
125 V
0.5
250 V
0.25
24
1995 Square DAll Rights Reserved
11/98
06313049
Accessories
Closing Coil (XF)
06313050
This device releases the circuit breaker closing mechanism when the spring is charged. The closing
coil is rated for continuous duty. The closing release is supplied on request and can be fitted even
on a manual operating mechanism.
Remote
Close
A4
XF
A1
Anti-pumping Function
When the closing coil (XF) is permanently energized, the circuit breaker remains in the open
position after it has been opened, either by manual or electrical operation. The circuit breaker can
only be closed if the closing coil is momentarily de-energized (see p. 32).
Note: This anti-pumping function can be disabled by series connecting a ready-to-close ("b" contact)
switch (PF) to the closing coil.
Circuit Breaker Closing Time
Less Than 80 ms
60 Hz
120240
DC
2448125
60 Hz
20 VA
DC
15 W
25
11/98
Accessories
Opening Coils
Three types of voltage releases can be used for remote opening of the circuit breakers:
n Shunt trip (MX)
n Instantaneous undervoltage trip device (MN)
n Time-delayed undervoltage trip device (MNR)
Possible Combinations
06313049
120240480
DC
2448125250
06313051
Operating Time
AC
20 VA
DC
15 W
40 ms
Remote
Open
C2
MX
C1
06313052
This release instantaneously opens the circuit breaker when supply voltage drops below a value
between 35% and 70% of rated voltage. If the release is not energized, the circuit breaker cannot
be closed (either manually or electrically). Any attempt to close it will have no effect on the main
contacts. Closing is possible when the release voltage reaches 85% of its rated value. The
instantaneous undervoltage trip device is field-installable.
Remote
Open
D4
MN
D1
26
1995 Square DAll Rights Reserved
11/98
Accessories
Time-delayed Undervoltage Trip Device (MNR) (1)
To prevent the circuit breaker from tripping in the event of transient voltage drops, this release has a
built-in adjustable time delay. If required, this time delay can be overridden by connecting an
external switch on an additional circuit (wired by the user). The undervoltage trip device is fieldinstallable.
MN
MNR (1)
DC
120
120
240
480
480
24
48
125
250
20 VA
20 VA
DC
15 W
15 W
0.09
0.50.91.53
06313053
06313054
Four SPDT switches with double break construction. They are directly operated by the main
contacts and ensure a large insulation distance in open position. They are therefore particularly
suitable for insulation of auxiliary circuits or reliable interlockings.
n "a" contacts are open when the circuit breaker is open and closed when the circuit breaker is
closed.
n "b" switches are closed when the circuit breaker is open and open when the circuit breaker is
closed.
See page 30 for operating diagrams. Auxiliary switches are field-installable.
Closed
Open
12
14
22
24
32
34
42
44
OF
11
21
31
41
27
11/98
06313055
Accessories
24 Additional Auxiliary Switches (OFSUP)
An external plate holds a set of 24 SPDT switches operated by means of a cable. They are
available only for drawout circuit breakers.
06313056
Open
Closed
212
222
234
244
211
221
231
241
06313057
This SPDT switch indicates that the circuit breaker is ready to close and that the following
conditions exist:
n The circuit breaker is open
n The stored energy mechanism is charged
n The control unit is reset
n The circuit breaker opening push button is neither locked nor padlocked
n The circuit breaker is in the fully-connected or test position
The switch is field-installable.
Ready-to-Close
252 254
PF
251
28
1995 Square DAll Rights Reserved
11/98
Accessories
Connected Position Switches (CE)
A block of four SPDT switches operate when a drawout circuit breaker is in the connected position.
The switch block is field-installable.
06313059
06313058
One SPDT switch is operated only when the circuit breaker is in the test position. The switch is fieldinstallable.
06313060
Disconnected
Connected
314
312
324
311
322
Test
334
321
332
344
342
321
321
352
354
351
362
364
372
374
361
371
DC
240
10
480
600
Auxiliary Switch
Ready-to-close
Standard 24 Additional Switch
15
15
10 (1)
125
250
12
Connected
Position Switch
Disconnected
Test
15
15
15
0.5
0.5
0.5
0.5
0.5
0.25
0.25
0.25
0.25
0.25
29
11/98
Accessories
Operating Diagrams
Auxiliary Switches
06313061
inch
mm
Fully
Closed
Fully
Open
Closed
Open
Closed
a
.1
Standard (O)
.1
Standard (F)
.1
24 Additional (OFSUP)
.1
b
a
.4
Open
Open
.2
Closed
.4
Closed
Open
.2
Open
Closed
.4
Closed
Open
Open
Closed
.2
Note: Contacts are shown with the circuit breaker in the open position. Scale applies only to
distance between main contacts.
06313062
Position Switches
Disconnected
Test
Connected
Main Disconnect
Position
Secondary Disconnect
Position
Connected
Connected
Connected Position
Switches (CE)
.1
Disconnected Position
Switches (CD)
.1
.1
b
a
.4
.2
.2
.4
Closed
Open
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Open
Closed
.4
.2
Open
Closed
Note: Position switches are shown with the circuit breaker in the connected position.
30
1995 Square DAll Rights Reserved
11/98
Accessories
Push Button Locking Device (VBP)
This device prevents local manual operation of the circuit breaker by covering the opening and/or
closing the push buttons. This locking device can be locked by a padlock or a sealing lead.
06313063
06313064
A key interlock that locks the circuit breaker in the open position by holding the push button in its
depressed position. The key interlock is provided.
06313065
31
11/98
Accessories
Mechanical Interlocks
n Disconnecting When Circuit Breaker Is Closed:
During any disconnecting attempt when the circuit breaker is closed, an interlocking device
ensures the tripping of the circuit breaker before the actual separation of the main disconnects.
The circuit breaker remains, however, operable in the other positions: test, disconnected and
withdrawn.
n Circuit Breaker Closing When Not Completely Connected:
The interlocking device mentioned above prevents closing of the circuit breaker if the connecting
operation is not completely achieved.
n Connecting Circuit Breaker When Door Opened:
VPEC and VPOC options prevent the compartment door from being opened when the circuit
breaker is in the connected position and from connecting the circuit breaker when the door is
open.
Electrical Interlocks
n Priority of Opening Orders (Standard):
06313066
Opening coils (undervoltage trip devices, shunt trip) and opening push button have priority over
the closing coils and closing push button.
n Mechanical Pop-out Type Indicator (Standard):
Under overcurrent or ground-fault conditions, the trip indicator located in the control unit will pop
out. It is not possible to close the circuit breaker until this trip indicator is reset. This standard
function can be disabled upon request.
n Anti-pumping Function (Standard):
In case the closing coil (XF) becomes permanently energized, the circuit breaker remains in the
open position A after it has been opened, either by manual or electrical operation. The circuit
breaker can be closed only if the closing coil is momentarily de-energized B.
Note: This anti-pumping function can be disabled by series connecting a "ready to close" (NC
contact) switch (PF) with the closing coil (XF).
Closing Coil
ON
ON
OFF B
OFF
OFF
OFF
Circuit
Breaker Status
ON
ON
Without
Anti-pumping
Function
OFF
OFF A
32
1995 Square DAll Rights Reserved
11/98
Accessories
06313067
06313068
N2
06313069
Two uses, independently powered supply by two transformers N1 and N2, standby through a circuit
breaker or a connection tie switch, preventing the connection in parallel of the two current
transformers.
N1
N2
C
06313070
One use, power supplied by one group of transformers N1, N2 or N3 or of generators, preventing
any connection in parallel.
N1
N2
N3
33
11/98
Accessories
Safety Shutters (VO)
Comprising two independent parts, line and load side, the safety shutters automatically block
access to the main disconnects when the circuit breaker is in the disconnected, test or fully
withdrawn position.
06313072
06313071
A factory-mounted movable and lockable slide (padlock not supplied) is used to:
n Lock the line or load shutters in the closed position
n Hold the line or load shutters in the open position
A support is provided at the back of the stationary assembly to hold the slide when not in use.
Safety Shutters
Shutters Lock
06313074
06313073
The rejection feature ensures that only the properly designated circuit breaker is matched with the
selected cradle assembly. It is made of two parts (one for the frame and one for the stationary
assembly), and allows 20 different combinations.
2
4
6
1
3
Stationary
Assembly
C
E
Circuit Breaker
Frame
Possible Arrangements
Frame
Stationary
Assembly
Frame
Stationary
Assembly
ABC
456
BCD
156
ABD
356
BCE
146
ABE
346
BCF
145
ABF
345
BDE
136
ACD
256
BDF
135
ACE
246
BEF
134
ACF
245
CDE
126
ADE
236
CDF
125
ADF
235
CEF
124
AEF
234
DEF
123
34
1995 Square DAll Rights Reserved
11/98
Accessories
Interphase Barrier (EIP)
Mounted between terminals of the stationary assembly, the interphase barrier prevents arc
prolongation to the circuit breaker in the event of a line side fault and isolates the circuit breaker
connections in insulated bus bar installations.
06313076
06313075
Hinged-mounted and locked with a milled head, this cover is designed to be installed on the door
escutcheon. It provides a higher degree of protection and is suitable for drawout or fixed-mounted
circuit breakers.
Interphase Barrier
Transparent Cover
35
11/98
06313077
Switch
Ratings
Type
Ampere
Rating
(A)
Short-time Rating
(RMS Sym. Amperes)
600 Vac Max.
MP08 NA
800
50,000
800
50,000
MP12 NA
1200
50,000
1200
50,000
MP16 NA
1600
50,000
1600
50,000
MP20 NA
2000
50,000
2000
50,000
MP25 NA
2500
50,000
2500
50,000
MP30 NA
3000
50,000
3000
50,000
MP40 NA
4000
85,000
4000
85,000
MP50 NA
5000
85,000
5000
85,000
MP63 NA (1)
6300
85,000
6300
85,000
CAUTION
HAZARD OF EQUIPMENT DAMAGE.
This switch contains no overcurrent protection.
It is suitable for use at its ampere rating when
protected by a MASTERPACT circuit breaker
of the same ampere rating.
Failure to observe this precaution can
cause equipment damage.
Construction
The MASTERPACT switch is identical to the MP circuit breaker, except that the switch is not
equipped with current transformers or an actual control unit. However, it does have an STR08
dummy unit.
23
Wiring diagrams
42
46
36
1995 Square DAll Rights Reserved
11/98
Trip Curves
9000
8000
7000
6000
5000
5000
4000
4000
3000
3000
Current Setting:
STR 28D = 0.41 x Sensor Rating
STR 28DP = 0.81 x Plug Rating
2000
2000
1000
900
800
700
600
1000
900
800
700
600
500
500
400
400
300
300
200
200
100
90
80
70
60
100
90
80
70
60
50
50
40
40
30
30
20
20
10
9
8
7
6
10
9
8
7
6
Instantaneous Pickup
I = 1.510 x Ir
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
.4
.4
.3
.3
.2
.2
.1
.09
.08
.07
.06
.1
.09
.08
.07
.06
.05
.05
.04
.04
.03
.03
.02
.02
6000
7000
8000
9000
10000
40 50 60
5000
30
4000
20
3000
6 7 8 9 10
2000
600
700
800
900
1000
500
400
300
.5 .6 .7 .8 .9 1 1.2 1.5
200
.01
.01
70
80
90
100
Time in Seconds
6000
7000
8000
9000
10000
40 50 60
5000
30
4000
20
3000
6 7 8 9 10
2000
600
700
800
900
1000
500
400
300
.5 .6 .7 .8 .9 1 1.2 1.5
200
10000
9000
8000
7000
6000
70
80
90
100
06313078
37
11/98
Trip Curves
.5 .6 .7 .8 .9 1 1.2 1.5
6 7 8 9 10
20
30
40 50 60
5 6 7 8 9 10
20
30
40 50 60
70
80
90
100
10000
9000
8000
7000
6000
70
80
90
100
06313079
5000
5000
4000
4000
3000
3000
Current Setting:
STR 38S = 0.41 x Sensor Rating
STR 38SP = 0.81 x Plug Rating
2000
2000
Time in Seconds
1000
900
800
700
600
1000
900
800
700
600
500
500
400
400
300
300
200
200
100
90
80
70
60
100
90
80
70
60
50
50
40
40
30
30
20
20
10
9
8
7
6
10
9
8
7
6
Short-time Pickup
Im = 1.510 x (Ir)
I2 t ON
Inst (*)
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
.4
.4
.3
.3
0.3
0.3
.2
0.2
0.2
0.1
0.1
I2 t OFF
.1
.09
.08
.07
.06
.2
.1
.09
.08
.07
.06
.05
.05
.04
.04
.03
.03
.02
.02
6 7 8 9 10
20
30
40 50 60
x Ir
In (A)
I = In x
630
28
800/1000
28
5 6 7 8 9 10
20
30
40 50 60
70
80
90
100
.5 .6 .7 .8 .9 1 1.2 1.5
70
80
90
100
.01
.01
(*) Instantaneous
Rating
Fixed Threshold
0.4
x In
1200/1600
24
2000
20
2500
14
3000/3200
12
4000/5000/6300
10
38
1995 Square DAll Rights Reserved
11/98
Trip Curves
6 7 8 9 10
20
30
40 50 60
5 6 7 8 9 10
20
30
40 50 60
9000
8000
7000
6000
9000
8000
7000
6000
5000
5000
4000
4000
3000
3000
Current Setting:
STR 58U = 0.41 x Sensor Rating
STR 58UP = 0.81 x Plug Rating
2000
1000
900
800
700
600
1000
900
800
700
600
500
500
400
400
300
300
200
200
100
90
80
70
60
100
90
80
70
60
50
50
40
40
30
30
20
20
10
9
8
7
6
10
9
8
7
6
5
Short-time Pickup
Im = 1.510 x (Ir)
4
3
H1: 24812141922Off
H2: 24812141922Max.
1200/1600 A
H1: 24812141722Off
H2: 24812141722Max.
2000 A
I 2 t ON
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
.3
.2
H1: 2468101212Off
H2: 2468101212Max.
I 2 t OFF
.1
.09
.08
.07
.06
.05
3000/3200 A
H1: 2468101010Off
H2: 2468101010Max.
4000/5000/6300 A
H1: 2468888Off
H2: 2468888Max.
0.4
.4
0.3
0.3
.3
0.2
0.2
0.1
0.1
.4
H1: 24810121417Off
H2: 24810121417Max.
2500 A
.1
.09
.08
.07
.06
.05
.04
.03
.03
.02
.02
.01
.5 .6 .7 .8 .9 1 1.2 1.5
6 7 8 9 10
20
30
40 50 60
x Ir
(*) Instantaneous
Rating
In (A)
Maximum Threshold I = In x
.2
Instantaneous Pickup
I = 2 x In Max (*)
.04
70
80
90
100
800/1000 A
630
28
800/1000
28
5 6 7 8 9 10
20
30
40 50 60
.01
70
80
90
100
Time in Seconds
2000
Instantaneous Dial
Settings
70
80
90
100
.5 .6 .7 .8 .9 1 1.2 1.5
70
80
90
100
06313080
x In
1200/1600
24
2000
20
2500
14
3000/3200
12
4000/5000/6300
10
39
11/98
Trip Curves
6 7 8 9 10
20
30
40 50 60
600
700
800
900
1000
1000
900
800
700
600
Ground-fault Pickup
Ih = 0.1 x In 1200 A Max.
500
400
500
400
300
300
200
200
100
90
80
70
60
100
90
80
70
60
50
50
40
40
30
30
20
20
10
9
8
7
6
10
9
8
7
6
I 2t ON
Time in Seconds
.5 .6 .7 .8 .9 1 1.2 1.5
500
.4
400
.3
300
.2
200
.1 .12 .15
70
80
90
100
1000
900
800
700
600
.05
.06
.07
.08
.09
06313081
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
.4
0.4
.4
.3
0.3
.3
.2
0.2
.2
I2t OFF
.1
.09
.08
.07
.06
.1
.09
.08
.07
.06
0.1
.005
.005
.004
.004
.003
.003
.002
.002
.001
.001
.1 .12 .15
.2
.3
.4
.5 .6 .7 .8 .9 1 1.2 1.5
6 7 8 9 10
20
30
40 50 60
600
700
800
900
1000
.01
.009
.008
.007
.006
500
.01
.009
.008
.007
.006
400
.02
300
.03
.02
200
.04
.03
70
80
90
100
.05
.04
.05
.06
.07
.08
.09
.05
40
1995 Square DAll Rights Reserved
11/98
Trip Curves
10000
9000
8000
7000
6000
6 7 8 9 10
20
30
40 50 60
10000
9000
8000
7000
6000
5000
5000
4000
4000
3000
3000
Current Setting
Ir = 0.81 x Plug Rating
2000
2000
1000
900
800
700
600
Ic1 = 0.8 1 x Ir
1000
900
800
700
600
500
Ic2 = 0.5 1 x Ir
500
400
400
300
300
200
200
100
90
80
70
60
100
90
80
70
60
tr1 = tr / 2
50
50
40
40
30
30
tr2 = tr / 4
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
.4
.4
.3
.3
.2
.2
.1
.09
.08
.07
.06
.1
.09
.08
.07
.06
.05
.05
.04
.04
.03
.03
.02
.02
.1 .12 .15
.2
.3
.4
.5 .6 .7 .8 .9 1 1.2 1.5
6 7 8 9 10
20
30
40 50 60
.01
600
700
800
900
1000
.01
500
400
10
9
8
7
6
300
10
9
8
7
6
200
20
70
80
90
100
20
.05
.06
.07
.08
.09
Time in Seconds
600
700
800
900
1000
.5 .6 .7 .8 .9 1 1.2 1.5
500
.4
400
.3
300
.2
200
.1 .12 .15
70
80
90
100
.05
.06
.07
.08
.09
06313082
41
11/98
Wiring Diagrams
06313083
Connected
Auxiliary Switches
Disconnected
Test
Standard
Remote Operation
Heavy
Duty
Undervoltage
Trip Device or
Closed
Disconnected
Motor
Operator
Spring
Charged
Open
Remote
Close
314 312 324 322 334 332 344 342 352 354 362 364 372 374
321
Ready
to Close
Remote
Open
Test
Connected
311
Shunt
Trip
331
341
351
361
12 14
22 24
32 34
42 44
D4
C2
A4
252 254
262 B4
371
MN
Standard
MX
XF
OF
11
21
31
PF
41
D1
C1
A1
CH
251
Note: Circuit breaker shown in connected, charged and open position with undervoltage releases energized.
42
1995 Square D All Rights Reserved
11/98
B1
Wiring Diagrams
06313084
Ground-fault
Protection
Ammeter
Zoneselective
Interlocking
Load
Monitoring
Data
Transmission
Ic2
Fault
Alarm
Selected
Fault
Overload
Alarm
Ic1
Upstream
Circuit
Breaker
82 84 (1)
LR2
S2
S1
T2
T1
Z11
LT
1
I Option
LT
Alarm
SDE
81
F1
_
(5)
F2
Z12
Gnd
R1 R2
Z Option
F or FV Option
e+
Out
T or W Option
(4)
LR1
ST
Communication (3)
Network
(6)
C Option
R Option
In
Z21
Z22
+
(2)
24 Vdc
Downstream
Circuit
Breaker
43
11/98
Wiring Diagrams
SC150 Indication and Control Interface
Motor
Operator
Power Supply
06313085
To Power
Supply "L"
400
630
C1 NO NC ON C2 reset
Control Outputs
C3 CD CE SDV SD
Inputs
PT100
Temperature
Probe
External
Contact
24-250V CC
100-440V CA
DIGIPACT
Internal Bus
COM
+ NC 0 24V e+ e T+ T
SC150 Indication and Control Interface
Inputs
C4 ON IN OFFSDE
To "IN"
SC150
Input
Terminals
1 4
To "C4"
SC150
Input
Terminals
N
To SC150
Terminals
"T+" and "T"
To "C3"
on SC150
Input Terminals
To "C4"
on SC150
Input Terminals
To "CD"
on SC150
Input
Terminals
To "SDE"
on SC150
Input Terminals
To "OFF"
on SC150
Input Terminals
To "ON"
on SC150
Input Terminals
To "CE"
on SC150
Input
Terminals
2 1 4
2 1 4
2 1 4
CE
CD
Control Unit
STR28 / 38 / 58
To "ON"
SC150 Control
Output Terminals
to "NO"
SC150 Control
Output Terminals
To Power Supply "L"
A4 C2 B4
Remote
Control
2 1
SDE
Control Unit
STR58U
Control Unit
XF MX M
C1
To Auxiliary
Source
e+ e
SDE
A1
2 1 4
To "SDE"
on SC150
Input Terminals
2 1 4
OF
To "C4"
on SC150
Input Terminals
B1
To Power Supply "N"
Internal Bus
Marking
Color
24 V
Red
0V
Black
Internal Bus
White
Internal Bus +
Blue
44
1995 Square DAll Rights Reserved
11/98
Wiring Diagrams
DC150 Data Concentrator
06313086
DC150
9600
3456
2
2
110240 Vac
115125 Vdc
Protection
78 9A
B CD
N2
3456
78 9A
N1
B CD
Internal
Bus
NC
Internal Bus
Internal Bus +
MODBUS/JBUS
Speed
19200
24 V
0V
DC150 Address
on MODBUS/JBUS
Network
RS485
MODBUS/JBUS
C
Connectors
06313088
The DC150 concentrator is connected using a SUBD9 male connector with a metal hood (e.g., ITT
canon, DE9P K83 + hood or DE115-500-5-RD). The DC150 concentrator is equipped with a SUBD9
female connector. For a multidrop configuration, the tap-offs can be made either via a branching off
of RS485 connector Catalog No. 50788 or standard connection boxes, taking care to respect the
necessary precautions when connecting the shieldings. The adaptation of an RS232 output on a
personal computer to accept the RS485 standard connector should be done with the RS485/RS232
converter Catalog No. 50786.
1
06313087
0V
5V
0V
Rp
Rp
Rc
3
RD+ (A')
RD (B')
TD+ (A)
L+ (A / A')
L (B / B')
TD (B)
Recommended
Protection
Type
Catalog No.
3-Phase
MG24466 or 24214
Fuse-link 10 A
aM
15660
Marking (1)
Connection
Cable
Voltages
Internal Bus
MODBUS/JBUS
Internal bus
Marking
Color
24 V
Red
0V
Black
Internal Bus
White
Internal Bus +
Blue
45
11/98
06313089
06313090
Door Cutout
6
153
10.63
270
0.75
Basis:
19
MP08 to MP30
2.6 MC08 to MC32
66
1.85
47 1.77
2.17
45
55
12.8
325
2.82
72
MP40 to MP63
MC40/MC50
5.83
0.73 149
19
2.72
69
Mounting
Holes
0.19 Dia.
5
7.1
180
7.1
180
0.69/ 18
06313093
06313092
Door Cutout
6
153
10.63
270
2.82
2.82
72
72
2.72
69
1.06
27
Mounting
1.48 Holes
38
12.8
325
0.57 5.83
15 149
0.19 Dia.
5
7.1
180
7.1
180
0.69
18
Rear Cutout
0.15
4
0.79
20
0.15
4
06313097
06313095
06313096
Door Interlock
14.2
360
0.80
20
0.12
3
14.5/368 MP30
29.4/748 MP50/MC50
38.4/978 MP63
1.69
43
0.12
3
Circuit
Breaker
Base
Mounting
Holes
17.5
445
2.36
60
Dimensions: inch
mm
46
1995 Square DAll Rights Reserved
11/98
0.7
18
0.7
18
3.15
80
1.75
45
MP25/MP30/MP40, MC32/MC40
06313099
06313098
0.56 Dia.
14
0.39/10
MP08 to MP16
MC08 to MC16
1.73
44
0.79/20
MP20/MC20
1.75
45
0.79
20
3.94
100
6.30
160
2.36
60
1.75
45
0.7
18
1.8
46
0.78
20
4.72
120
0.7
18
3.15
80
1.75
45
06313101
06313100
0.7
18
0.56 Dia.
14
2.9
74
0.79/20
MP25/MP30/MC32
3.31
84
1.18/30
MP40/MC40
1.75
45
0.79
20
3.94
100
6.30
160
2.36
60
1.75
45
0.7
18
1.8
46
0.78
20
4.72
120
4.5
114
0.58
15
7.47
190
1.17
30
2.11
54
0.54
14
9.12 / 9.41
235 / 240
6.27
160
1.57
40
0.47 Dia.
12
4.7
120
06313104
0.58
15
06313103
06313102
MP50 to MP63
0.58
15
2.35
60
=
3.13
80
2.35
60
8.62
220
0.68
17.5
0.78
20
3.5
89.5
2.19
56
1.17
30
= =
7.84
200
0.98
25
7.84
200
Dimensions: inch
mm
47
11/98
4.53
115
4.53
3.35
115
85
3.15
0.98 80 0.98
25
25 0.47 Dia.
12
06313106
06313105
3-Pole
4.53
115
0.5 Dia.
12,7
4.53
115
3.35
85
0.63
16
06313108
06313107
14.88
378
17.24
438
(4) Mounting
Holes
0.44 Dia. / 11
1
25,4
4.41
112
5.59
142
3.15
80
2.08
53
0.43
11
15.75
400
0.43
11
16.61
422
2.83
72
1.18 / 30 Min.
2.36 / 60 Max.
5.91
150
2.68
68
9.17
233
11.14
283
15.78
401
0.39
10
0.19 1.69
3 43
0.49
12,5
0.71
18
0.98
25
4.53
115
4.53
4.53
115 3.15115
80
3.35
85
0.47 Dia.
12
0.63
16
4.53
115
4.53
115
4.53
115
3.35
85
0.5 Dia.
12,7
06313110
06313109
4-Pole
19.4
493
3.15
80
21.8
553
06313112
06313111
0.69
17,5
(4) Mounting
Holes
0.44 Dia. / 11
20.2
515
0.43
11
2.83
72
1.18 / 30 Min.
2.36 / 60 Max.
5.91
150
2.68
68
9.17
233
11.14
283
15.78
401
0.39
10
1
25,4
4.41
112
5.59
142
3.15
80
2.08
53
0.43
11
0.71
18
0.19 1.69
3 43
0.49
12,5
Dimensions: inch
mm
48
1995 Square DAll Rights Reserved
11/98
4.53
115
4.53
115
1.87
48
3.15
80
0.98
25
06313114
06313113
3-Pole
4.53
115
0.5 Dia.
12,7
4.53
115
1.87
48
0.63
16
0.47 Dia.
12
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
14.21
361
06313115
06313120
0.69
18
0.98
25
1
25
0.39
10
5.98
152
3.15
80
3.23
82
4.41
112
3.62
92
(4) Mounting
Holes
0.44 Dia./11
12.8
325
17.14
435
2.17
55
3.98
101
4.21
107
2.17
55
6.89
175
3.35
85
11.81
300
17.32
440 Min.
1.65
42
0.49
13
13.78
350
0.49
13
4.53
115
0.98
25
4.53
4.53
115 3.15115
80
1.87
47,5
0.47 Dia.
12
06313118
06313117
4-Pole
4.53
115
0.63
16
4.53
115
4.53
115
1.87
47,5
0.5 Dia.
12,7
06313119
06313120
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
14.21
361
Cell (Insulation Not Required)
21.89
556
0.98
25
0.39
10
(4) Mounting
Holes
0.44 Dia. / 11
4.41
112
3.62
92
2.75
70
16.73
425
21.65
550
2.17
55
3.98
101
4.21
107
6.89
175
3.35
85
11.81
300
13.78
350
0.49
13
0.69
18
1
25
17.32
440 Min.
5.98
152
3.15
80
3.23
82
1.65
42
0.49
13
Dimensions: inch
mm
49
11/98
06313121
3-Pole
4.53
115
0.79
20
0.56 Dia.
14
4.53
115
3.35
85
3.15
80
06313123
06313122
14.88
378
4.53
115
(4) Mounting
Holes
0.44 Dia. / 11
0.43
11
15.75
400
5.98
152
3.15
80
0.43
11
16.61
422
15.78
401
1.75
44,5
2.83
72
1.18 / 30 Min.
2.36 / 60 Max.
5.91
150
2.68
68
0.71
18
14.98
380,5
0.12
3
1.75
44,5
1.69
43
06313124
4-Pole
0.79
20
4.53
115
4.53
115
4.53
115
3.35
85
0.56 Dia.
14,3
19.4
493
3.15
80
06313123
06313125
4.53
115
(4) Mounting
Holes
0.44 Dia. / 11
0.43
11
20.2
515
0.43
11
15.78
401
1.75
44,5
5.98
152
3.15
80
2.83
72
1.18 / 30 Min.
2.36 / 60 Max.
5.91
150
2.68
68
14.98
380,5
0.71
18
0.12
3
1.75
44,5
1.69
43
Dimensions: inch
mm
50
1995 Square DAll Rights Reserved
11/98
06313127
3-Pole
0.56 Dia.
14
4.53
115
0.79
20
4.53
115
1.87
48
06313129
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
14.21
361
06313128
4.53
115
1.75
45
17.32
440 Min.
(4) Mounting
Holes
0.44 Dia./11
2.17
55
12.8
325
17.14
435
2.17
55
5.98
152
3.15
80
3.23
82
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.65
42
0.7
18
1.75
45
4-Pole
4.53
115
4.53
115
06313130
0.79
20
4.53
115
1.87
47,5
0.56 Dia.
14,3
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
06313129
06313131
14.21
361
21.89
556
4.53
115
1.75
45
17.32
440 Min.
(4) Mounting
Holes
0.44 Dia. / 11
2.75
70
16.73
425
21.65
550
2.17
55
5.98
152
3.15
80
3.23
82
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.75
45
1.65
42
0.7
18
Dimensions: inch
mm
51
11/98
06313133
3-Pole
0.56 Dia.
14
5.85
149
0.25
6
5.85
149
2.01
51
0.25
6
14.88
378
17.24
438
3.15
80
06313138
06313134
1.57
40 Min.
1.75
44,5
15.78
401
(4) Mounting
Holes
0.44 Dia. / 11
15.75
400
0.43
11
16.61
422
10.24
260
2.28
58
0.43
11
2.83
72
5.91 2.68
68
150
13.95
354,5
4.72
120
1.75
44,5
2.24
57
1.13 0.24
29
6
06313136
4-Pole
5.85
149
4.55
115
0.25
6,35
0.56 Dia.
14,3
5.85
149
2.01
51
0.25
6,35
06313137
19.4
493
06313138
21.8
553
3.15
80
1.57
40 Min.
1.75
44,5
15.78
401
(4) Mounting
Holes
0.44 Dia. / 11
0.43
11
20.2
515
0.43
11
2.28
58
2.83
72
5.91 2.68
68
150
13.95
354,5
10.24
260
4.72
120
1.75
44,5
2.24
57
1.13 0.24
29
6
Dimensions: inch
mm
52
1995 Square DAll Rights Reserved
11/98
3-Pole
06313139
0.56 Dia.
14
5.75
146
0.25
6
0.65
17
5.75
146
0.25
6
Withdrawn Position
06313144
9.56 1.77
243 45
Disconnected Position
14.21
361
06313140
1.75
44
17.32
440 Min.
10.24
260
(4) Mounting
Holes
0.44 Dia./11
12.8
325
17.14
435
2.17
55
4.72
120
2.17
55
3.98
101
4.21
107
6.89
175
3.35
85
1.75
17.64
448
45
1.30
0.71
1.14 33 18
29
4-Pole
06313142
5.35
136
4.92
125
5.75
146
0.65
17
0.25
6,35
0.25
6,35
0.25
6,35
0.65
16,5
0.56 Dia.
14,3
06313143
06313144
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
14.21
361
21.89
556
1.75
44
17.32
440 Min.
(4) Mounting
Holes
0.44 Dia./ 11
10.24
260
4.72
120
2.75
70
16.73
425
21.65
550
2.17
55
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.75
45
1.30
0.71
1.14 33 18
29
Dimensions: inch
mm
53
11/98
0.25
0.53 Dia. 6
14
6.10
155
6.10
155
2.55
65
0.25
6
06313147
06313145
3-Pole
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
14.21
361
Cell (Insulation Not Required)
06313146
2.28
58
1.75
44
17.32
440 Min.
10.24
260
(4) Mounting
Holes
0.44 Dia./11
2.75
70
21.65
550
16.73
425
2.17
55
4.72
120
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.75
45
1.30
0.71
1.14 33 18
29
Dimensions: inch
mm
54
1995 Square DAll Rights Reserved
11/98
9.76
248
9.76
248
0.25 0.5
6 13
06313149
06313148
3-Pole
5.59
142
0.25
6,35
1.14
29
1.14
29
9.76
248
0.78
20
9.76
248
5.59
142
1.14
29
06313150
MP50
0.25
6,35
1.14
29
9.76
248
9.76
248
0.5
13
5.59
142
1.14
29
0.25
6,35
06313152
1.57
40 Min.
06313151
29.88
759
32.24
819
1.75
44,5
2.28
58
(4) Mounting
Holes
0.44 Dia. / 11
0.43
11
31.57
802
30.71
780
0.43
11
15.78
401
10.24
260
4.72
120
1.18 / 30 Min.
2.36 / 60 Max.
2.83
72
5.91
2.68
150
68
14.35
364,5
1.75
44,5
2.24
57
1.13 0.24
29
6
55
11/98
0.25
6
MP40MC50
9.94
253
9.94
253
1.26
32
0.56 Dia.
14
3.94
100 0.25
6
9.94
253
9.94
253
0.25
6
06313154
06313153
3-Pole
3.94
100
1.26
32
0.25
6
0.56 Dia.
14
06313155
MP50MC50
3.94
100
9.94
253
1.26
32
9.94
253
0.25
6
0.56 Dia.
14
0.25
6
Withdrawn Position
Disconnected Position
9.56
243
1.77
45 14.21
361
0.56 Dia.
14
1.75
45
2.28
58
06313157
06313156
19.1
485 Min.
10.24
260
4.72
120
(6) Mounting
Holes
0.44 Dia./11
2.36
60
13.78
350
13.78
350
32.08
815
2.17
55
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.75
45
1.06
27
3.08
78
1.14
29
56
1995 Square DAll Rights Reserved
11/98
MP40
9.94
252,5
0.25
6,35
9.94
252,5
1.26
32
3.94
100
0.25
6,35
06313159
06313158
9.94
252,5
0.56 Dia.
14,3
9.94
252,5
0.25
6,35
9.94
252,5
9.94
252,5
3.94
100
0.25
6,35
1.26
32
0.56 Dia.
14,3
06313160
MP50
9.94
252,5
0.25
6,35
9.94
252,5
9.94
252,5
1.26
32
3.94
100
0.25
6,35
0.56 Dia.
14,3
Withdrawn Position
Disconnected Position
1.77
45 14.21
361
06313162
06313161
9.56
243
41.38
1051
0.56 Dia.
14
2.28
58
19.1
485 Min.
10.24
260
4.72
120
(6) Mounting
Holes
0.44 Dia. / 11
1.57
40
18.70
475
41.14
1045
18.70
475
2.36
60
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.75
45
1.06
27
3.08
78
1.14
29
Dimensions: inch
mm
57
11/98
06313163
3-Pole
0.25
6
13.78
350
13.78
350
4.62
118
2.00
51
0.25
6 0.56 Dia.
14
Withdrawn Position
9.56 1.77
243 45
Disconnected Position
14.21
361
06313164
06313165
1.75
45
19.1
485 Min.
10.24
260
(6) Mounting
Holes
0.44 Dia./11
1.57
40
18.70
475
18.70
475
2.16
55
41.14
1045
4.72
120 3.08
78
3.98
101
4.21
107
6.89
175
3.35
85
17.64
448
1.75
45
1.06
27
1.14
29
Dimensions: inch
mm
58
1995 Square DAll Rights Reserved
11/98
06313174
Drawout Mounting
1.96
50
1.57
40
2.03
52
4.9
125
1.17
30
1.96
50
0.19
5
0.54
14
4.9
125
35.29
900
Max.
1.17
30
35.29
900
Max.
35.29
900
Max.
6.86
175
4.11
105
6
153
(*)
6.39
163
2.54
65
6.5
166
1.76
45
3.21
82
1.17
30
(*)
(*)
1.72
44
(*)
Dimensions: inch
mm
59
11/98
06313176
06313177
Drawout Mounting
1.96
50
1.57
40
2.03
52
7.05
180
2.35
60
0.19
5
7.05
180
0.54
14
2.35
60
0.54
14
2.35
60
35.29
900
Max.
35.29
900
Max.
1.96
50
50
1.57
40
2.03
52
7.05
180
2.35
60
0.19
5
7.05
180
35.29
900
Max.
35.29
900
Max.
1.96
50
1.96
50
2.54
65
(*)
1.76
45
6.5
166
6.86
175
4.11
105
35.29
900
Max.
1.17
30
2.35
60
(*)
Circuit
Breaker
7.05
Basis
180
1.17 / 2.35
30 Min. / 60 Max.
2.43
62
(*)
06313178
6.56 ft.
2 m Max.
7.87
200 Min.
r= 4.72
r= 120 Min.
Mounted on Rails
r= 4.72
r= 120 Min.
Mounted on Backplate
Dimensions: inch
mm
(Except as otherwise
indicated)
60
1995 Square DAll Rights Reserved
11/98
4 .20
4 5
BBus
JBus
OK
com
com
error
24V
error
CD
0
EF
1
456
23
EF
789
CD
N2
AB
N1
5.47
139
4.92
125
AB
456
23
9600
19200
789
N1
N2
3.94
100
7.60
193
3.94
100
1.97
50
06313180
1.97
50
4.13
105
6.50
165
2 .20
2 5
2.80
71
4.92
125
6.89
175
Dimensions: inch
mm
61
11/98
Appendix
DANGER
HAZARD OF ELECTRICAL SHOCK, BURN
OR EXPLOSION.
Turn OFF all power supplying the equipment
before installing or removing circuit breaker.
Failure to observe these precautions will
cause death, personal injury or electrical
shock.
CAUTION
HAZARD OF EQUIPMENT DAMAGE.
Since circuit breakers contain factory-sealed
and calibrated elements. Do not break seal. In
case of malfunction, repairs must be made at
a Square D factory or by an authorized
company representative.
Failure to observe this precaution can
cause equipment damage.
and the surface cleaned before reinstallation. It is essential that electrical connections are made
carefully in order to prevent overheating.
n Check for terminal tightness.
Inspection of Main Contacts
The arc chutes are easily removed to allow access to the main contacts and to the wear indicator.
The wear indicator consists of a groove located within the contacts support (see page 3). When the
circuit breaker is closed, this groove is entirely covered up by the moving contacts. Over time, the
wear of the contacts will make the groove appear. When the groove is fully visible, replace the
breaker or have an authorized service center change the contacts.
Inspection of Clusters
Totally maintenance free, they have to be replaced only after overheating due to a defective
connection or after a major fault. Inspection is advised when checking the terminal connections.
Cleaning
Remove any dust and dirt that may have accumulated on the circuit breaker surface and terminals.
Mechanical Checks
For long periods circuit breakers may not be required to operate on overload or short-circuit
conditions. Therefore it is essential to operate the circuit breaker periodically to avoid mechanical
gumming.
62
1995 Square DAll Rights Reserved
11/98
Appendix
63
11/98
Appendix
Endurances
AEndurance Without Maintenance
MASTERPACT
MP or MC
Mechanical
Electrical
08
12
16
20
25
30 - 32
40
50
63
12,500
10,000
10,000
10,000
10,000
10,000
5,000
5,000
5,000
480 Vac
10,000
10,000
10,000
9,000
8,000
4,000
3,000
3,000
2,000
600 Vac
10,000
10,000
10,000
7,000
6,000
2,600
2,500
2,500
1,500
20,000
15,000
15,000
15,000
10,000
10,000
10,000
20,000
800
Mechanical 3,500
Electrical
ANSI
500
1200
1600
2000
2500
3000
4000
5000
6300
2,000
2,000
2,000
2,000
1,500
1,500
1,500
1,500
500
500
500
500
400
400
400
400
Mechanical 12,500
NS
4,000
4,000
NS
1,500
1,500
NS
NS
Electrical
NS
800
800
NS
400
400
NS
NS
2,800
Important Notice:
All endurances given are based on normal operating conditions and conventional tests:
n Closing and opening operations at rated current
n Power factor: 0.750.80
As actual conditions differ, use these values only as inspection guidelines and periodically check
contact wear.
Under normal operating conditions of use, as determined by UL 489 or ANSI Standards (see table
C) and controlled by tests, MASTERPACT circuit breakers do not require maintenance. However,
these circuit breakers exceed, without maintenance and additional costs, the endurances required
by standards. See tables A and C. Service maintenance by a field service representative will extend
the endurance according to table B. This service can be performed on site and consists in changing
contacts, arc chutes and some other parts.
Example:
MP16 at 480 V requires no maintenance before 10,000 cycles (mechanical or electrical). Endurance
may be increased after servicing at 10,000 operations.
64
1995 Square DAll Rights Reserved
11/98
Appendix
IEC 947-2 Interrupting Ratings
In addition to UL 489 and ANSI C37-13, MASTERPACT circuit breakers comply with the IEC 947-2
Standard as per the table below. For further information, contact a sales representative.
Type
3-Pole
Ampere
Rating (A)
Interrupting Ratings
UL489
RMS Symmetrical Amps
480 Vac
600 Vac
IEC 947-2
Short-time
440 Vac
Icu
Ics
690 Vac
Icu
Ics
800
65 kA
65 kA
50 kA
65 kA
65 kA
65 kA
65 kA
MP12 H1
1200
65 kA
65 kA
50 kA
65 kA
65 kA
65 kA
65 kA
MP16 H1
1600
65 kA
65 kA
50 kA
65 kA
65 kA
65 kA
65 kA
MP20 H1
2000
75 kA
75 kA
75 kA
75 kA
75 kA
75 kA
75 kA
MP25 H1
2500
75 kA
75 kA
75 kA
75 kA
75 kA
75 kA
75 kA
MP30 H1
3000
75 kA
75 kA
75 kA
75 kA
75 kA
75 kA
75 kA
MP40 H1
4000
100 kA
100 kA
100 kA
100 kA
100 kA
85 kA
85 kA
MP50 H1
5000
100 kA
100 kA
100 kA
100 kA
100 kA
85 kA
85 kA
MP63 H1
6300 (1)
100 kA
100 kA
100 kA
100 kA
100 kA
85 kA
85 kA
800
100 kA
65 kA
50 kA
100 kA
100 kA
85 kA
85 kA
MP12 H2
1200
100 kA
65 kA
50 kA
100 kA
100 kA
85 kA
85 kA
MP16 H2
1600
100 kA
65 kA
50 kA
100 kA
100 kA
85 kA
85 k A
MP20 H2
2000
100 kA
75 kA
75 kA
100 kA
100 kA
85 kA
85 kA
MP25 H2
2500
100 kA
75 kA
75 kA
100 kA
100 kA
85 kA
85 kA
MP30 H2
3000
100 kA
75 kA
75 kA
100 kA
100 kA
85 kA
85 kA
MP40 H2
4000
125 kA
100 kA
100 kA
150 kA
125 kA
85 kA
85 kA
MP50 H2
5000
125 kA
100 kA
100 kA
150 kA
125 kA
85 kA
85 kA
MP63 H2
6300 (1)
150 kA
100 kA
100 kA
150 kA
125 kA
85 kA
85 kA
65
11/98
Appendix
IEC 947-2 Ratings
Auxiliary and Position Switches
Voltage (V)
Auxiliary Switch
OF
50/60 Hz
DC
110
OFSUP
Overcurrent
Trip Switch
SDE
Ready to
Close Switch
PF
Position
Switches
CE/CD/CT
15
240
10
10
10
10
10
10
380
10
480
10
600
48
6
3
3
125
0.5
0.5
0.3
0.3
0.5
250
0.25
0.25
0.15
0.15
0.25
500
0.5
O: Standard
OFSUP: 24 Additional
CE: Connected
CD: Disconnected
CT: Test
IEC 947-2
120
50/60 Hz
240
DC
24
100-127
200-240
DC
24-30
48
48-60
125
100-125
Closing Coil
Rated Voltage (V)
UL 489 Listed
60 Hz
IEC 947-2
120
50/60 Hz
240
DC
24
110-127
220-250
DC
24
48
48
125
125
250
250
Shunt Trip
Rated Voltage (V)
UL 489 Listed
60 Hz
IEC 947-2
120
50/60 Hz
240
220-250
480
DC
24
110-127
440-480
DC
24
48
48
125
125
250
250
Undervoltage Trip
Rated Voltage (V)
UL 489 Listed
60 Hz
IEC 947-2
120
50/60 Hz
240
220-250
480
DC
24
110-127
440-480
DC
24
48
48
125
125
250
250
66
1995 Square DAll Rights Reserved
11/98
Notes
67
11/98
Notes
68
1995 Square DAll Rights Reserved
11/98
Notes
69
11/98
Notes
70
1995 Square DAll Rights Reserved
11/98
Notes
71
11/98
Notes
72
1995 Square DAll Rights Reserved
11/98
Square D Company
PO Box 3069, 3700 Sixth St SW
Cedar Rapids, IA 52406-3069 USA
Field Services: 1-800-634-2003
www.squared.com