Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Roger Bours
Fike Corp.
FIGURE 1.
Pressure-control
systems may not ensure the required level
of pressure safety, so
dedicated pressure-relief
systems are also needed
in many situations
No continuous operation
in this zone
Pressure
Normal
operating range
Pressure
control
system
Rupture disc
Relief valve
Complexity of device
Low
High
Investment cost
Low
High
After activation
Replace
Reset
Yes
Yes
Yes
No
Mounting-position restrictions
No
Vertical only
Installation cost
Low
High
Maintenance cost
Low
High
No
Yes
Affected by backpressure
Yes
Yes
No
Yes
Leak-tight
Yes
No
Large
Limited
Size range
Large
Limited
No
Yes
Yes
No
Reaction time
Low
High
Unrestricted opening
Yes
No
37
Feature Report
EN ISO 4126-3
Comments
Definition of an RD/PRV
combination
None
Certified combination
capacity factor (CCCF)
Protrusion of petals
into valve
No specific
requirement
Both codes use language prohibiting the RD to impair the performance of the PRV. The ISO document seems to take a firm stand on
the petal protrusion issue but points
to Clause 7 which allows a default
CCF (Fd) of 0.9
Documentation of the
combination
Nameplate marking
for the combination
provided by the user,
PRV, RD, or vessel
manufacturer
RD and RV in parallel
When using relief valves and rupture discs in parallel (Figure 4A),
the main objective is to allow the
relief valve to initially handle overpressure situations bleeding the
pressure until an acceptable, reduced pressure is achieved while
allowing the process to continue.
38
RD upstream of RV
Rupture-disc devices may also be
installed either upstream or downstream of a relief valve (Figure 4B).
Each geometry offers particular
benefits for the user. Using rupture
discs upstream of relief valves is a
common practice to achieve one or
more of the following, each of which
is explained further below:
Prevent plugging of the RV
Prevent corrosion on RV internals
Prevent leakage through the RV
Allow for in-situ testing of the RV
Prevent plugging or gumming
of the relief valve. Through the
FIGURE 4A and 4B. Rupture discs and relief valves can be used in parallel (left)
and in series (right)
39
Feature Report
disc device directly upstream of
the relief valve. Longer distances
between the rupture disc and relief valve by introducing pipe
sections or spacers may result
in the creation of reflective pressure waves when the rupture disc
opens. This phenomenon can result in undesired fragmentation or
re-closing of the rupture disc, and
should be avoided
Since, like the relief valve, the
rupture disc is a device that reacts to differential pressure between the upstream and downstream side, measures should
be taken to avoid any unnoticed
pressure increases in the closed
cavity between the rupture disc
and relief-valve inlet. Most industry standards and related regulations require that the pressure in
the cavity be monitored or vented
to the atmosphere. This is commonly achieved through the use
of a so-called tell-tale assembly,
consisting of pressure gage or indicator, try cock and free vent
RD downstream of RV
The following are primary reasons
for applying rupture discs downstream of pressure relief valves:
Prevent corrosion of relief valve
Prevent fouling or sticking of the
relief valve
Prevent variable superimposed
backpressure from affecting the
relief-valve operation
Detect opening or leakage of the
relief valve
Prevent fouling and plugging
of the relief valve. In situations
where relief systems are vented
into a common header, the risk exists that blowdown material may
enter the vent side of the installed
relief valves. Where such vented
media can result in either corrosion
or polymerization, the external side
of the relief-valve mechanism may
be affected, resulting in failure to
operate when required. By installing a rupture disc with suitable
properties at the downstream side
of the relief valve, vented media are
isolated from the relief valve, therefore avoiding the effects of corrosion
and polymerization, and increasing
the reliability of the safety system
and reducing the need for inspection and maintenance. To ensure
that the downstream rupture disc
will not impede the proper performance of the relief valve, the burst
pressure of the rupture disc should
be as low as possible, whereas the
provided minimum net flow area of
the rupture disc needs to be at least
as large as the relief area of the relief-valve outlet.
Prevent corrosion of the reliefvalve internals. To avoid corrosion and the resulting need for
inspection, maintenance and repair of the relief valve, the use of
a downstream rupture disc can be
considered. By installing a rupture
disc downstream of the relief valve,
the rupture disc will act as a chemical seal between the valve outlet
and the common header, which
could contain potentially corrosive
agents from process media released
through other emergency relief
valves. In this way, corrosion effects
of the process media on the valve
internals can be eliminated.
Benefits
While the use of rupture discs at the
downstream side of relief valves is
relatively uncommon, that arrangement can offer an array of benefits
to the plant owner. The acceptable
use of this setup has to comply with
the following sizing and set-pressure requirements:
The minimum net flow area of the
rupture-disc device installed at
the relief-valve outlet needs to be
equal to or larger than the reliefvalve-outlet relief area
The burst pressure of the rupture
41