List Of Major Clarifications To The Technical Specifications


Sr. No.
1

1.2

1.5
3

Description

YIL Clarification

Instrumentation & Control


The Bidder shall be responsible for
providing materials & equipments
within the quoted price & without any
commercial implication.

Our Scope of Supply shall be as per our BOM


which is based on your present requirement as per
the enquiry specifications. Alterations to the
specifications have been highlighted in our offer.
We request you to kindly review the same.

Hardwired Facility in the form of


emergency trip pushbuttons

Since the quantity of hardwired switches,


pushbuttons, etc is not available. We have
assumed the same. Kindly refer to our BOM &
verify the quantities.

Design Objective

The following failures shall be taken


into account.
4

As applicable to DCS. Redundancy in DCS has


been considered at the Controller, Power Supply &
Datahighyway Communication levels. IO
Redundancy has been considered for all Closed
Loops.

Control & Monitoring Philosophy

4.1

For ease of operation the entire plant


has been divided into the following
subplants

Noted. However, no segregation considered in DCS


at any Level (controller & IO Cards Level). Serial
Loading of Controller & IO Cards considered.
Please refer to IO Summary for details.

4.7

The System shall be provided with


Management Information System
through Ethernet

MIS PC not considered in our scope presently.


Please clarify exact requirement, location, distances
etc.

System shall be provided with OPC


Connectivity

The Offered System is OPC Compliant. OPC


Connectivity is available through Engineering HIS.
No Ethernet switches, cables, application program
development considered in our scope.

4.8

5.2

Instrumentation Special
Requirements.
Hardware Backup control, if
necessary

Hardwired console with pushbuttons, lamps &


annunciator windows considered as per BOM. No
other hardware backup panel envisaged.

YOKOGAWA INDIA LIMITED


MUMBAI

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

Sr. No.

5.3

Description

YIL Clarification

All Signal Cables & Control Cables.

Only Interpanel Wiring between System &


Marshalling cabinets & Datahighway (Control
Network) cables considered in our scope. No Field
Cables, cable trays,JBs, cable glands or any other
erection material considered in our scope.

5.5

All Inputs shall be taken through


proximity switches

5.6
5.7

Contact Outputs
Cable Trays

Proximity Switches offered for 258 nos. of Digital


Inputs only as per IO Summary enclosed with the
RQF. All MCC Digital Inputs are assumed to be
potential free contacts without any relays.Kindly
confirm the same.
Interposing relays have been offered for all Digital
Outputs.
Not in our scope.

5.9

For Testing of DCS.

5.10

Safety Earthing

Tests & Inspection shall be as per Yokogawa


Standards. Detailed procedures shall be provided
for your review during CKOM.
Earth Pit Construction not considered in our scoep.
We shall provide scheme during CKOM.

Codes & Standards

Necessary Codes & Standards as applicable to


DCS shall apply.

Scope Of Work

7.1.1
7.1.2

Only Interpanel Wiring between System &


Marshalling cabinets & Datahighway (Control
Network) cables considered in our scope. No Field
Cables considered in our scope.Please refer to our
BOM for details.

Ordinary/ Special Cables


All Local instrument panels & JBs shall
be SS.
Not considered in our scope of supply.

7.1.3

All erection hardware, cable trays..

Not considered in our scope of supply. We shall


supervise the installation & Commissioning activity.
No Field Work/ Civil Work considered in our scope.

7.1.6

Sequence of Event Recording System


shall be integral part of DCS having 1
msec resolution.

We have offered standalone non redundant SOE


with 1msec time stamp resolution of Masibus/ Equiv
make.

5 nos. of Operating Stations.

The number of workstations have been offered as


per Annexure II of the RFQ. 4 nos. of Operator
Stations, 1 no of Engineering Cum Operator Station
& 3 nos. of remote operator stations. Please clarify
the distances/ locations of these remote operator
stations from the main control room for us to
estimate the datahighway cables.

7.1.7

YOKOGAWA INDIA LIMITED


MUMBAI

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.
Sr. No.

Description

YIL Clarification

7.1.8

Printers.

7.1.12

Color shall be RAL 7032


All Cabinets & Consoles shall be Rittal
make.

The number of printers offered are as per Annexure


II of the RFQ. We have not received System
Architecture Drawing no. BG010-PI-15-3-001/ Rev
-NIL with the RFQ. Please provide the same.
RAL 7032 is obsolete & the latest available color is
RAL 7035.

7.1.13

Panels & Consoles shall be YIL Make.

SG Control, STG Control, Governor


Control, BOP, Electrical Interface

It is assumed that IOs for the same are included in


the IO Summary sheet provided by you.

Erection, Testing & Commissioning

We have considered Installation Supervision &


Commissioning Assistance in our scope. No Field
Work/ Civil Work considered in our scope. All
Activities are related to DCS Control room only &
applicable to DCS System shall be in our scope.

Data & Documents

Noted. As Applicable to DCS shall be offered.

10

Spares & Consumables

Offered as per our BOM. Please refer to our offer


for details.

11

Technical Specification

7.2 to 7.5

11.1.1
11.1.5

Closed Loops & Open Loops shall be implemented


Independent Multi Function processors in the same processors. Separate IO Cards
for Closed Loop & Open Loop Controls. considered for the same.
Functional Requirement of the Control
System.

All IOs connected shall have optical


isolation..Barriers for AIOs & switching
amplifiers for DIs.

Barriers have been considered for all Analog I/Os,


RTD Inputs, T/C Inputs & Proximity Digital Inputs. 420 mA Signals from RTD & T/C Barriers shall be
wired to 4-20mA Cards. Separate RTD & T/C Cards
not offered. Kindly refer to BOM for exact quantities.

20% Spare IO & 20% additional rack


space.

Installed spares have been considered as


calculated by you in Annexure I of the RFQ. 10%
Installed Rack Space has been considered in the IO
Racks as per Annexure II of the RFQ.

Communication protocol shall be in


compliance with standard protocol

Communication Protocol is deterministic,


mastreless token passing network with a speed of
10MBPS.

Performance Calculations

Shall be enginnered within the system. All


necessary Inputs o be made avilable from your end.

YOKOGAWA INDIA LIMITED


MUMBAI

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

Sr. No.

v
11.1.6
11.1.7
11.1.8

11.1.11
11.1.12

Description

YIL Clarification

DDE for communication with other


computers.
Temperature & Humidity
System Supplier to Prvide special
arrangement
Critical Signals exchange between
different cabinets to be hardwired.

The offered system is OPC Compliant.


5to 95% Non Condensing Type. For PC & Printers
as per manufacturer's standards.
G2 Coating considered.
We assume IOs are already included for the same.

Supply of UPS not in our Scope. DCS Distribution


shall be done by us. Also UPS Supply to be made
UPS
available for Remote Workstations , if any.
Different Sub Systems of DCS shall be Open Loops, Closed Loops & Sequence Controls
as follows
shall be implemented in the same controllers.
Scan Times
Scan times have been considered as follows:
Closed Loops @ 500ms
Open Loops @ 1000 ms
Digital IOs @ 200ms / 1000 ms (40% Interlocks:
60% Remaining IOs)
32 Bit RISC Processor with Unique Pair & Spare
Controller
Architcture offered.

Historical Storage Sub System

Historical Data shall be stored in Hard Disk of


Workstations. Separate History Module not
envisaged.

11.1.15.6

Data Communication System

Communication Protocol is deterministic,


masterless token passing network with a speed of
10MBPS.

11.1.15.7

Input/ Output System

11.1.15.5

The following type of IO Modules have been offered


Analog Input + Analog Output Module: 8 Input + 8
Outputs per module.
Analog Input Module: 16 Inputs/ Module
Digital Input Module: 32 Inputs / Module
Digital Output Module: 32 Outputs / Module
Serial Interface Module: 2 ports / module.
Pulse Input Modules not envisaged presently.
IO Card Specifications as per system standards.
Optionally 64 Channel Digital I/O Modules are also
proposed.

Serial Device Interface Module

As per Annexure 1 of the RFQ, 7 Serial Links


envisaged. The Offered Serial Interface Card has 2
ports / card & for your requirement of 7 links we
have offered 4 Serial Interface cards. All Cards are
non redundant. Communication protocol considered
is MODBUS RTU. Serial Cable not considered in
our scope.

YOKOGAWA INDIA LIMITED


MUMBAI

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

Sr. No.

Description

YIL Clarification

11.1.15.8

Man- Machine Interface

MMI Quantity & Specifications shall be as per our


BOM. Also, Please refer our reply in point no. 7.1.7
above.

11.1.15.9/
11.5.15.10
19
d

Diagnostic Sub System / Display


Details
Pre Trip & Post Trip Relevant Data
SER

System Standard features considered.


Functionality & Tags need to be discussed.
Please refer our reply in point no. 7.1.6 above.

Control Console / Cabinets

Cabinets/Consoles & Wirings shall be as per YIL


Standards.

11.2
11.3 &
11.3.1

12

13

14

Instrumentation Cables/ Special Cables Not in our scope.


Maintenance & Calibration
Equipment

Not Applicable.

Testing & Inspection at works

Tests & Inspection shall be as per Yokogawa


Standards. Detailed procedures shall be provided
for your review during CKOM.

Testing at Site

Noted. All tests shall be with the Control Room


Limits only restricted to DCS. Hydrostatic Testing,
air testing, continuity , identificatioon test not
applicable.
Performance Guarantee Test within the control
room for DCS only has been considered for a
period of 3 days. Please refer our BOM for details.

Annexure I- IO Summary
Sr No. 7- Digital Outputs - SOVs,110V
AC
Sr No. 8- Digital Inputs - PMCC
Sr No.9- Digital Outputs - SOVs,110V
AC

The Total Count with spares is 195 & not 258 as


reflecting in your IO Summary.
The Total Count with spares is 491 & not 503 as
reflecting in your IO Summary.
The Total Count with spares is 771 & not 817 as
reflecting in your IO Summary.
Request you to please verify & reconfirm the
above quantities. Presently, we have sized the
system based on total IO Counts as calculated
by you.

Annexure II- Bill Of Material For


Reference

Please refer to BOM enclosed with our offer.


Please clarify the following points

YOKOGAWA INDIA LIMITED


MUMBAI

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

Sr. No.

1.2

Description

YIL Clarification

Operating Stataions - Remote

Please clarify distances of the same from the amin


control room. Presently ,we have assumed around
50 mtrs of datahighway cable per workstation from
the main control room.

2.5

Redundant Card for STG to be


considered.

2.8

Node Unit

Please clarify exact number of Serial Links.


Presently, we have offered 4 Non Redundant Cards
( 8 Links ) as against your requirement of 7 links in
Annexure 1.
As per this annexure, 10% Spare Space considered
in IO Racks.

2.15

Note: Temperature Inputs from


Thermocouple & some RTDs shall be
converted to Analog Inputs
Pulse Terminal Board

Presently, all T/C & RTD Inputs are considered


through barriers & wired as 4-20mA Signals to
AAV141 Cards. Separate RTD & T/C Modules not
considered.
Not envisaged presently.

3.4/3.5
3.6

Vendor To Quote for Elco terminals with


barrier & alternate YBNM/ YBNC
without barrier.
Pulse Inout Barrier/ Module
Trip Amplifiers

3.8 to 3.13 Lamps, Pushbuttons etc..


3.14
Signal Repeaters
3.23
128 channel SOE
4

Software Packages

Please clarify. Presently, barriers offered for all


Analog IOs.
Not envisaged presently.
Not envisaged presently.
Quantities not available & hence assumed presently
as per our BOM.
Please clarify quantity required.
Masibus / Equiv Make Offered.
Software considered as per our BOM. Web
Monitoring PC not in our scope.
Please refer BOM for exact quantities of other
items.

YOKOGAWA INDIA LIMITED


MUMBAI

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

SYSTEM IO SUMMARY

SR.
NO.

TYPE OF SIGNAL

REDUNDANT CLOSED LOOPS

CL : 4-20MA ANALOG INPUT

CARD
MODEL

QTY
WITH
SPARE

QTY
OFFD

62

64

62

64

416

416

AAB841
2

CL : 4-20MA ANALOG OUTPUT

TOTAL
CARDS

NO OF
CHANNELS
PER CARD

8+8 (R)

26

16

NON REDUNDANT ANALOG


B

AAV141
INPUTS- TOTAL SPLIT AS

1
2
3

OL : 4-20MA ANALOG INPUT


RTD INPUTS
THERMOCOUPLE INPUTS

260
115
41

NON-REDUNDANT DIGITAL I/OS

DIGITAL INPUT

ADV151

1243

1248

39

32

DIGITAL OUTPUT

ADV551

1075

1088

34

32

RS485 LINKS( 2 PORTS PER CARD)

ALR121

2 PORTS

TOTAL IO COUNT

2858

2880

119

YOKOGAWA INDIA LIMITED


MUMBAI

16
16
16

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

BILL OF MATERIAL
CENTUM-CS3000 DISTRIBUTED CONTROL SYSTEM

SR.NO.

DESCRIPTION

1.0

OPERATOR/ENGINEERING SUB-SYSTEM

1.1

HUMAN INTERFACE STATION (OPERATOR/MONITORING)

QTY OFFD

PENTIUM IV, 2.8 GHz MAIN MEMORY : 512MB


HARD DISK : 80GB, 19" DUAL LCD ( DESKTOP)
WITH 52X CD RW DRIVE, 1.44 MB FDD, OPTICAL MOUSE
FULL STROKE - 101 KEY STANDARD PC KEYBOARD
MAKE : HP / COMPAQ / IBM
1.2

HUMAN INTERFACE STATION (OPERATOR/MONITORING- REMOTE


STATIONS)

PENTIUM IV, 2.8 GHz MAIN MEMORY : 512MB


HARD DISK : 80GB, 19" SINGLE LCD ( DESKTOP)
WITH 52X CD RW DRIVE, 1.44 MB FDD, OPTICAL MOUSE
FULL STROKE - 101 KEY STANDARD PC KEYBOARD
MAKE : HP / COMPAQ / IBM / WIPRO
1.3

HUMAN INTERFACE STATION (OPERATOR/MONITORING/ENGINEERING)

PENTIUM IV, 2.8 GHz MAIN MEMORY : 512MB


HARD DISK : 80GB, 19" SINGLE LCD ( DESKTOP)
WITH 52X CD RW DRIVE, 1.44 MB FDD, OPTICAL MOUSE
FULL STROKE - 101 KEY STANDARD PC KEYBOARD
MAKE : HP / COMPAQ / IBM / WIPRO
1.4

CONTROL BUS INTERFACE CARD


MODEL: VF-701

1.5

MO DRIVE

1.6
1.6.1
1.6.2
1.6.3
1.6.4

PRINTERS
B/W LASER PRINTER - A4 SIZE
COLOR DEKJET PRINTER- A3/A4 SIZE
B/W DOT-MATRIX PRINTER
PRINT SERVER
MAKE :HP/ WIPRO / EQV.

1
1
2
1

1.7
1.7.1
1.7.2
1.7.3

FURNITURE FOR WORKSTATIONS


OPEN DESK CONSOLES FOR PC
PRINTER TABLES
CHAIRS

2.0

8
4
8

CONTROLLER & DATA ACQUISITION SUB-SYSTEM


YOKOGAWA INDIA LIMITED.

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

SR.NO.

DESCRIPTION

2.1

CONTROLLER UNIT -REDUNDANT


MODEL NO : AFS30D

2.2

NODE INTERFACE UNIT


MODEL NO : ANB10D- LOCAL

QTY OFFD

17

3.0

I/O MODULES

3.1

ANALOG CONTROL I/O MODULE


MODEL : AAB841

3.2

ANALOG INPUT MODULE


MODEL : AAV141

26

3.3

CONTACT INPUT MODULE


MODEL : ADV151

39

3.4

CONTACT OUTPUT MODULE


MODEL : ADV551

34

3.5

SERIAL (RS485) COMMUNICATION MODULE


MAKE : ALR121

4.0
4.1
4.2
4.3
4.4

SIGNAL CONDITIONING SUB-SYSTEM AND TERMINAL BOARDS


YB-3 FOR AAB141
YB-4 FOR AAV141
TE32 FOR ADV151
RELAY BOARD FOR ADV551

8
26
39
34

5.1
5.2
5.3
5.4

SYSTEM CABLES INCLUDING DATAHIGHWAY WITHIN THE CONTROL ROOM


: PRE-FAB CABLE OF 5 MTR LENGTH EACH
KS CABLE FOR AAB841
KS CABLE FOR AAV141
KS CABLE FOR ADV151
KS CABLE FOR ADV551

16
26
39
34

6.0

BOUGHT OUT ITEMS

6.1

INTERCONNECTING CABLES WITHIN CONTROL ROOM: VNET

50 MTRS

6.2

INTERCONNECTING CABLES BETWEEN CONTROL ROOM & REMOTE


OPERATOR STATIONS- 50 MTRS Redundant Cable Considered Per
Workstation.

300 MTRS

6.3

24VDC DUAL REDUNDANT POWER SUPPLY FOR RELAYS

5.0

16
(8X2)

MAKE: COSEL/PHOENIX
6.4

BARRIERS
FOR ANALOG INPUTS
FOR ANALOG OUTPUTS
FOR RTD INPUTS

322
62
115
YOKOGAWA INDIA LIMITED.

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

SR.NO.

DESCRIPTION
FOR THERMOCOUPLE INPUTS
FOR DIGITAL INPUTS- PROXIMITY TYPE- DUAL CHANNEL
MAKE: MTL/P&F/EQUIV

6.5

STANDALONE NON-REDUNDANT SOE SYSTEM FOR 128 DI's WITH


DEDICATED 21"CRT MONITOR AND 1 NO. DOT MATRIX PRINTER.

QTY OFFD
41
129

MAKE : MASIBUS-HATHWAY 7000SERIES / TECHMARK/EQUIV


6.6
6.6.1
6.6.2
6.6.3
6.6.4
6.6.5
6.6.6
6.6.7
6.6.8

AUXILIARY CONSOLE WITH THE FOLLOWING MOUNTED


MAKE: YIL
48 POINT ALARM ANNUNCIATOR WINDOW
PUSHBUTTONS
ILLUMINATED PUSHBUTTONS
3 POSITION KEY SWITCHES
MUSHROOM PUSH BUTTONS
2 POSITION KEY SWITCHES
INDICATING LAMPS
HOOTER

1
1
10
10
10
10
10
10
1

6.7

VOLTMETER, AMMETER, HOOTER

1 EACH

7.0

CABINETS

7.1

SYSTEM / MARSHALLING / RELAY/BARRIER/ PDB CABINETS


DIM : 600/1200MMW X 800MMD X 2105MM H

8.0

SOFTWARE

8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10
8.11
8.12
8.13
8.14

SYSTEM SOFTWARE : OPERATING & MONITORING


BUILDER SOFTWARE : ENGINEERING
REPORT SOFTWARE
OPC SOFTWARE
MODBUS COMMUNICATION PACKAGE
TEST FUNCTION SOFTWARE
LINE PRINTER PACKAGE
GRAPHIC BUILDER
ELECTRONIC INSTRUCTION MANUAL
SEQUENCE TABLE. CONTROL DRAWING VIEWER
LOGIC CHART VIEWER
SELF DOCUMENTATION
LONG TERM TREND PACKAGE
WEB MONITORING PACKAGE
PC, PHONE LINE, MODEM, WEB SITE REGISTRATION ETC NOT IN OUR
SCOPE FOR WEB MONITORING PACKAGE.

8
1
1
1
1
1
1
1
1
1
1
1
1
1

9.0

APPLICATION SOFTWARE DEVELOPMENT & ENGINEERING CHARGES.

LOT

10.0

SUPERVISION OF INSTALLATION ACTIVITY & COMMISSIONING ASSITANCE

LOT

10.1

(MAX. 30 DAYS CONSIDERED)


SITE ACCEPTANCE TEST (SAT)
(MAX. 3 DAYS CONSIDERED)
YOKOGAWA INDIA LIMITED.

10

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

SR.NO.
10.2
NOTE:

DESCRIPTION

QTY OFFD

PERFORMANCE GUARANTEE TEST(PGT)


(MAX. 3 DAYS CONSIDERED)
TO-FRO TRAVEL, LODGING, BOARDING & LOCAL CONVEYENCE OF OUR
ENGINEER WILL BE TO YOUR ACCOUNT.

11.0

TRAINING
AT BANGLORE - 4 PERSONS FOR 1 WEEK
NOTE: 1] DURATION : 1 WEEK = 5 WORKING DAYS
2] LANGUAGE OF TRAINING : ENGLISH.
3] TEXT FOR THE TRAINING : SHALL BE SUPPLIED BY US.

LOT

4] CHARGES ARE EXCLUSIVE OF TO & FRO TRAVEL, LODGING, BOARDING


& LOCAL CONVEYANCE FOR THE TRAINEESDURING THEIR STAY IN
BANGALORE. THIS WILL BE TO YOUR ACCOUNT.
12.0

FACTORY ACCEPTANCE TEST

LOT

13.0

DOCUMENTATION (4 SETS + 2 CD)

LOT

14.0

PACKING & FORWARDING

LOT

15.0

TRANSPORTATION TILL SITE

LOT

YOKOGAWA INDIA LIMITED.

PROPOSAL NO. : YIL/ CS3/FW00608973PO/BPM/R0/29-08-06


PROJECT 43 MW COAL BASED THERMAL POWER PLANT
CLIENT : M/S FINOLEX INDUSTRIES LIMITED, RATNAGIRI.

12

SPARES & OPTIONAL BILL OF MATERIALS


SR.NO.

DESCRIPTION

QTY.

RECOMMENDED SPARES FOR 2 YEARS & CONSUMABLES

SPARES
ANALOG CONTROL I/O MODULE
MODEL : AAB841

ANALOG INPUT MODULE


MODEL : AAV141

CONTACT INPUT MODULE


MODEL : ADV151

CONTACT OUTPUT MODULE


MODEL : ADV551

CONSUMABLES
1
2
3
4
5

PRINTER PAPERS : DOT MATRIX ( 1000 SHTS / BOX )


PRINTER PAPERS :INKJET ( 1000 SHTS / BOX )DOT MATRIX PRINTER RIBBON
INKJET PRINTER REFILL
LASERJET PRINTER REFILL

COMMISSIONING SPARES

4 BOX
2 BOX
1
1
1

YIL WILL BRING THE SAME SPARES DURING DCS COMMISSIONING & SHALL TAKE BACK
AFTER THE DCS COMMISSIONING IS OVER.
NOTE:
NO PRICE IMPLICATION TO CLIENT.
NOTE:

OPTIONAL: 32 FUNCTION MEMBRANE KEYBOARDS


MAKE:YOKOGAWA

OPTIONAL: 64 CHANNEL DIGITAL IO CARDS IN LIEU OF


32 CHANNEL DIGITAL IO CARDS

YOKOGAWA INDIA LIMITED


MUMBAI

8
SHALL BE
INDICATED IN
PRICED OFFER.