Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Volume 1 - Users
Guide
276192-111 Rev. G
Gemstart 5
Volume 1 Users Guide
Foreword
This Technical Handbook provides the User with the information necessary to Install,
Commission, Operate, Maintain and Test the equipment (as applicable). It is essential that
any Operator(s) reads and understands the content of this Technical Handbook and
follows the instructions contained within.
Every care has been taken to ensure the accuracy of the contents at the date of publication.
If the use of this equipment introduces new technology to your Operators, product training is
available from COMECA EBT to assist you in complying with relevant Health and Safety
Regulations.
Should you require further guidance or information regarding this equipment, or information
on our After Sales Services available, please contact our Customer Services Department at
the address below who will be pleased to assist:
COMECA Equipements Basse Tension
Route de Givry
ZI La Garenne
F71880 Chtenoy-le-Royal
France
Tel.:
+33 (0)3 85 98 22 00
Fax:
+33 (0)3 85 98 22 01
Web: www.gemstart.fr
Our policy is one of continuous product development.
equipment that may vary from that described.
The information contained within this Technical Handbook may not be reproduced or passed
on to third parties, either wholly or in part, without the express prior written consent of
COMECA EBT.
Gemstart5 declarations of conformity are available on the internet site or on demand.
-2-
Gemstart 5
Volume 1 Users Guide
+33 (0)3 85 98 22 00
Fax:
+33 (0)3 85 98 22 01
Web: www.gemstart.fr
-3-
Gemstart 5
Volume 1 Users Guide
Customer Services
COMECAs Customer Services Department can provide continuous Customer support
throughout the lifetime of your equipment. A comprehensive range of services is available,
including:
Equipment repair
Engineering services
Training
COMECAs specialised Customer Service Engineers are available to provide the services
listed above, either in our workshop, or alternatively, at your site.
To assist us in providing an efficient and timely service, before contacting COMECA EBT to
discuss existing equipment, please help us by having the following information available:
The original COMECA EBT works order number or the unit serial number and the unit type
and voltage rating.
When you have the information listed above, please contact us at the address below:
COMECA Equipements Basse Tension
Route de Givry
ZI La Garenne
F71880 Chtenoy-le-Royal
France
Tel.:
+33 (0)3 85 98 22 00
Fax:
+33 (0)3 85 98 22 01
Web: www.gemstart.fr
-4-
Gemstart 5
Volume 1 Users Guide
Table of Revisions
Issue
Description
Date
Original issue
May 2006
Added 2
nd
Reset Input
July 2006
September
2006
March 2007
April 2008
January 2010
-5-
September
2010
Gemstart 5
Volume 1 Users Guide
Information Gemstart5.3 end of life
G
-6-
October 2011
Gemstart 5
Volume 1 Users Guide
Meaning
Amperes
Alternating Current
Actual Load Current
Current Transformer
Direct Current
Full Load Current
Input / Output
Kilo Ampere
Kilo Volt
Light Emitting Diode
Liquid Crystal Display
Milli Ampere
Milli Metre
Milli Second
Mega Watt
Operations
Micro Amperes
Second
Volt
Voltage Transformer
ADVICE: information
intended to assist in
performing specified tasks
CAUTION: precautions to be
taken to avoid damaging the
equipment
YOUR ATTENTION IS
DRAWN: specific points
that should be noted
DANGER, ELECTRICITY:
precautions to be taken to avoid
injury to personnel
MECHANICAL DANGER:
precautions to be taken to
avoid injury to personnel
-7-
Gemstart 5
Volume 1 Users Guide
Readership:
The Guide is intended for operating and maintenance staff and general engineers who are
responsible for monitoring Gemstarts system but do not necessarily have responsibility for
commissioning or reconfiguring Gemstarts settings.
Related publications:
Volume 2:
Volume 2 is for use by expert engineers who will be setting up Gemstart systems.
Volume 3:
Volume 3 is for the user and expert engineers, it explains the main features of the GEMPRO
software, including how to take control of your Gemstart; it also explains the features of the
Configuration Editor, including how the database structure works, and how it is used to enter
Gemstarts settings.
-8-
Gemstart 5
Volume 1 Users Guide
Table of Contents
1
INTRODUCTION ............................................................................................................................................ 12
4.1
4.2
4.3
4.4
4.5
4.6
4.7
CT WIRING ................................................................................................................................................... 20
5.1
5.2
5.3
6
6.1
6.2
6.3
Local inputs............................................................................................................................................ 25
6.1.2
6.1.3
6.1.4
6.2.2
6.3.2
6.3.3
6.3.4
6.3.5
6.3.6
6.3.7
6.3.8
6.3.9
-9-
Gemstart 5
Volume 1 Users Guide
6.3.12 Pt100 RTD inputs ................................................................................................................................... 38
7
DISPLAY MODULES...................................................................................................................................... 46
7.1
7.2
7.3
9.1
9.2
9.3
10
10.1
10.2
10.3
10.4
- 10 -
Gemstart 5
Volume 1 Users Guide
10.4.5 Gemstart 3 Group Data ....................................................................................................................... 100
11
12
13
14
15
16
16.1
16.2
16.3
- 11 -
Gemstart 5
Volume 1 Users Guide
1 Introduction
Gemstart 5 is the next generation of the highly successful Gemstart family of intelligent
controller products brought to you by COMECA. It provides a completely new range of modular
units that enables the user to choose the level of complexity they require for their application.
This can range from a stand alone, single unit for status monitoring, to a fully extended control
and monitoring solution, integrated into a high level control system.
Its primary purpose it to control, protect and monitor important Medium and Low voltage
(MV/LV) loads used in process applications, such as motors, valves, and variable speed drive
units.
The Gemstart 5 can also be easily integrated into electrical distribution installations to monitor
and control various electrical supplies, including MV/LV feeders, circuit breakers and other
general purpose supplies.
It also has great flexibility in that you can incorporate Gemstart 5 units into a control scheme
with relative ease, as multiple devices may be connected on a single communications link with
options on three communications protocols: Modbus ; Profibus DPV1; and Gembus (proprietary
protocol);. All three come pre-loaded and are individually selectable.
- 12 -
Gemstart 5
Volume 1 Users Guide
2 Main Features
The main features provided by Gemstart 5 comprise:
Motor protection; for example protection against thermal overload, motor startup current and
earthing faults.
Application protection; for example protection against under current and instantaneous
overcurrent.
Maintenance prediction; for example the hours run and the number of start/stop operations.
User interface; which for example provides fault descriptions and warnings information.
Electrical feeder control and monitoring; allows you to gather information on your load
profile, highest current, power etc, and allows you to control the load (turn it on or off) from a
remote position.
- 13 -
Gemstart 5
Volume 1 Users Guide
- 14 -
Gemstart 5
Volume 1 Users Guide
4 Hardware Details
The hardware modules available on Gemstart 5 comprise the following:
Gemstart 5
Body unit
options :RS485 serial link
Version 5.1
Version 5.3 (end
of life)
Version 5.4
(optional extension
module)
(optional display
module)
4 x multi - voltage
inputs module
LED module
or
LCD module
or
4 x multi - voltage
inputs + 6 x
Thermistor inputs
module
RS232 PORT
Programming/
Configuration port
Primary
conduct
or
aperture
BODY UNIT
INPUT MODULE
- 15 -
Gemstart 5
Volume 1 Users Guide
5.3 BODY UNIT, AS 5.1 BUT WITH THE FOLLOWING ADDITIONS (end of life)
POWER PROTECTION
- 16 -
Gemstart 5
Volume 1 Users Guide
- 17 -
Gemstart 5
Volume 1 Users Guide
Contactor
with Aux.s
interface
wiring
MCCB &
Isolator
Main
conductors
Gemstart 5
Body Unit
inter-connecting
cable to front panel
- 18 -
Gemstart 5
Volume 1 Users Guide
NOTES:
The Earth Fault CT should not be earthed.
- 19 -
Gemstart 5
Volume 1 Users Guide
4.7 CT Wiring
When selecting which CT inputs to use there are some restrictions on which phases you can
use. The following tables show which built in CTs must be used.
The number of Motor Phases is configured in the GEMPRO Editor Supply form. The Number of
CTs used is configured in the GEMPRO Editor Phase CTs form.
Gemstart 5.3 (end of life)
Number of
Motor Phases
Phase to Neutral
Not Valid
Not Valid
Phase to Phase
Not Valid
Not Valid
3 Phase
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
Gemstart 5.4
Number of
Motor Phases
Phase to Neutral
Not Valid
Not Valid
Phase to Phase
Not Valid
3 Phase
Not Valid
Not Valid
Not Valid
- 20 -
Gemstart 5
Volume 1 Users Guide
Input Functions
Protection Functions
Output Functions.
Contactor type
DOL-E
MCCB Feeder
VSD Logic
VSD Cut Throat
General Purpose I/O
Star Delta 1 O/P
Star Delta 2 O/P
Star Delta 3 O/P
DOL-L
Forward/Reverse
Motor Operated Valve
Two Speed - Low Start Only
Two Speed
Two Speed - Dahlander
- 21 -
Gemstart 5
Volume 1 Users Guide
Input Function
Fault Types
Configuration Options
Contactor
input
Contactor
input
Contactor
input
Contactor
input
Hard Stop
N/O, N/C
Process Stop A
N/O, N/C
Process Stop B
N/O, N/C
Manual Start A
N/O, N/C
No Options
Manual Start B
N/O, N/C
No Options
Emergency Start A
N/O, N/C
No Options
Emergency Start B
N/O, N/C
No Options
N/O, N/C
No Options
Manual Select
N/O, N/C
INCH Select
N/O, N/C
Remote Select
N/O, N/C
Interlock
N/O, N/C
Overload Relay
N/O, N/C
User text 1
N/O, N/C
User text 2
N/O, N/C
Thermistor Relay
N/O, N/C
ELCB Relay
N/O, N/C
Isolator
N/O, N/C
Device Status
N/O, N/C
Reset input 1
N/O, N/C
None
Reset input 2
N/O, N/C
None
Test Position
N/O, N/C
Counter 1
N/O, N/C
None
Counter 2
N/O, N/C
None
Counter 3
N/O, N/C
None
- 22 -
Gemstart 5
Volume 1 Users Guide
Note that if an input is set as N/C the function will become active if the input loses its voltage.
Conversely, with the input set as N/O, when the input detects sufficient voltage the function will
become active. The standard input type option is shown in bold.
Key to abbreviations
Abbreviation
Meaning
N/A
Not Applicable
N/O
N/C
LT
Latched trip. The trip flag must be cleared by a reset trips command.
SCT
Self Clearing Trip. If the trip input signal clears the trip flag is cleared
automatically
LA
Latched Alarm. The alarm flag must be cleared by a reset trips or reset
alarms command
SCW
Self Clearing Warn. If the warn input signal clears the warn flag is
cleared automatically
None
- 23 -
Gemstart 5
Volume 1 Users Guide
ANSI/IEEE No.
Protection Function
79
Fail/Recovery Voltages
Supply
50S
Startup Current
Motor Protection
48, 51LR
Motor Protection
49
Thermal Overload
Thermal Protection
Thermal Protection
Restart Inhibit
Thermal Protection
Temperature threshold
Thermal Protection
46
Single Phasing
Motor Protection
46
Imbalance
Motor Protection
66
Starts in Hour
Motor Protection
14
Speed sense
27, 59
Voltage protection
Supply
50N, 51N
46
Phase Reversal
Supply
37
Under Current
Application Protection
50
Instant ALC
Application Protection
51
Constant ALC
Application Protection
Under Power
Power Protection
Over Power
Power Protection
55
Power Protection
55
Power Protection
79
AutoRestart
Supply
74
Alarm Relay
86
Lockout
An explanation of the protection function and the settings parameters applicable to each of the
above can be found in volume 2 - Specification Reference.
NB: Current based protection is only applicable to Gemstart versions 5.3 & 5.4.
Voltage, Power and Auto-Restart protection is only applicable to Gemstart versions 5.3 & 5.4.
- 24 -
Gemstart 5
Volume 1 Users Guide
isolator opened/closed,
contactor opened/closed,
It is only permissible for wiring associated with these inputs to be carried out locally within a
motor starter chassis or a feeder cubicle.
The user must set the correct voltage rating for each of these inputs using the Configuration
Editor, under the Multi- voltage inputs item. The settings are either High Range (110/230v) or
Low Range (24/48v) The default is set to High Range. Please note that an input with low
volts applied will not become active if it has been set to sense the high voltage level.
In addition, a supply Ride Through Time setting of 0 to 200ms, in 10ms steps is also
configurable on these inputs. This is useful to prevent false input readings for momentary dips in
the input voltage. The default is set at 20ms. The switching on of the inputs is not delayed.
Warning! If input 8 is used for the Emergency Shut Down (ESD) option to control
output 4, the voltage applied to this input must be limited to 24V dc, otherwise the
output may be damaged.
Note : ESD version = end of life
A further four additional Multi voltage inputs, numbered 9 12, are available on both the
optional Input and the RTD/INPUT extension modules and these are connected to the body
units using the 8 way connection lead fitted with RJ45 plugs.
- 25 -
Gemstart 5
Volume 1 Users Guide
Input Number/Type
5* (multi-voltage input)
6* (multi-voltage input)
7*(multi-voltage input)
Not assigned
8*(multi-voltage input)
9**(multi-voltage input)
Not assigned
Not assigned
Not assigned
Not assigned
Output 4
Not assigned
Gemstart 5
Volume 1 Users Guide
Example:
Take the case of single contactor motors typical of direct on line starting; both Start A and Start
B functions can be used to start the motor. Start A could be for local control and Start B for
remote control. Assign Start A to input 6 and Start B to input 7.
It is also possible to set an output based on the level of an Input. This is available on a limited
number of inputs (Interlock, Local I/P 4, Multi-voltage I/P 7, and Extension module I/P 12). e.g.
For chassis test position, you could use the local input 4 to set output 3 to signal remotely that
the chassis is in test position.
Additionally, the status of output 4 can also be used to activate any input function.
A full description of all the input functions is detailed in Volume 2 Specification Reference
Manual.
There are also two low power rated output relays (outputs 3&4) that are typically used for
remote status indication or additional contactor control when using the interlock supply.
- 27 -
Gemstart 5
Volume 1 Users Guide
Gemstart 5 also has an option to replace output 4 with an Emergency Shut Down (ESD) relay.
This option allows a 24VDC input signal from an ESD system to operate an embedded relay
within the Gemstart unit. Note : this version is declared end of life
All output contacts will drop out if the power supply to Gemstart is lost either momentarily or
permanently. However, see also sections 6.3.4 & 6.3.5 for details on Voltage Monitoring and
Auto-Restart features.
The output contacts will also drop out if the Gemstart 5 system watchdog detects a hardware or
fatal error software failure.
All relay contacts should be protected from large transient voltages caused by
switching external inductive loads. Either RC networks for AC voltage or Freewheeling diodes for DC voltage should be used in parallel with the external
loads.
Description
Disabled
Active
Contactor Output A
This Function varies with contactor type but is generally the main
output drive
Contactor Output B
Contactor Output C
Contactor Output D
GP Output A
A GP Output bit supplied by the Host via the serial link. Used for
remote outputs
GP Output B
A GP Output bit supplied by the Host via the serial link. Used for
remote outputs
GP Output C
A GP Output bit supplied by the Host via the serial link. Used for
remote outputs
GP Output D
A GP Output bit supplied by the Host via the serial link. Used for
remote outputs
Motor Stopped
Running
Running A
Running B
In Startup
Available to Auto
Gemstart 5
Volume 1 Users Guide
Option
Description
Auto or Priority Mode, there are no trips present, there are volts on
the interlock input and the contactor is not in the test position.
No Trips Present
Warn Present
Alarm Present
Self
Clearing
Present
Available to Priority
A priority command can start the motor. I.e. there are no trips
present, the contactor is not in the test position, there are volts on
the interlock input and the Hard Stop input is not active.
Available to Manual
Interlock Input
If this input is active it will act directly upon any one of the outputs it
has been assigned to.
Inputs 4, 7 or 12
If any one of these inputs is active it will act directly upon any one
of the outputs it has been assigned to.
Gemstart 5
Volume 1 Users Guide
through the appropriate apertures in the Gemstart body unit.
The Gemstart body unit with the integral CTs has a current measuring error limit of 2%
across the nominal range of 0.5 30 amps, and within 5% across the range of 31 250
amps.
All external interposing phase CTs specified by COMECA comply with Class 5P10 Protection
category of IEC 60044-1, thereby providing exceptional total accuracy for all current
measurements.
Phase CT selection :
CT1 = INTEGRAL CT (NOT OPTIONAL)
CT2 = (100/1A)
CT2a = (100/1A)
(end of life)
Gemstart 5
Volume 1 Users Guide
limited to a maximum current of 250Amps for 30 seconds, and all Gemstart specified
interposing CTs are limited to10x their nominal primary current rating for 30 seconds. The
standard default starting current setting is 800%.
- 31 -
Gemstart 5
Volume 1 Users Guide
Gemstart Curves
Curve 31
Gemstart Curves
Curve 30
Curve 29
Curve 28
100000
Curve 27
Curve 26
Curve 25
Curve 24
10000
Curve 23
Curve 22
Curve 21
Curve 20
1000
Curve 19
Curve 18
Curve 17
Curve 16
100
Curve 15
Curve 14
Curve 13
Curve 12
10
Curve 11
Curve 10
Curve 9
Curve 8
Curve 7
Curve 6
Curve 5
0.1
Curve 4
10
11
Curve 3
Curve 2
Curve 1
- 32 -
Gemstart 5
Volume 1 Users Guide
EARTH
FAULT
CURRENT
DETECTION
- 34 -
Gemstart 5
Volume 1 Users Guide
Earth Fault setting below 10% of the FLC rating should not use this method.
The overall accuracy using this method of Earth Fault detection is +/- 5% in range 0.1
- 30A.
EF Limit must be between 10% and 100% of FLC. This accuracy does not include
any additional errors introduced by external CTs.
6.3.10
On Gemstart versions 5.3 & 5.4 the body unit incorporates a voltage transformer
which is used to directly measure the motor supply voltage up to a maximum of 240V
ac. Higher voltage monitoring is possible by using an external interposing, step down
transformer. The motor supply can be monitored to detect motor supply loss or dips
down to 10 ms. The Monitored Voltage level, which must be set to the correct value
under the Supply item in the Configuration Editor, is used for both the Auto-Restart
feature and the Under/Over Voltage protection. The under voltage level is set by the
value selected from the Supply Fail level in the Auto-Restart feature and the Over
voltage level is pre-set at 110% of the monitored voltage value. The severity of the
fault issued for voltage protection is also selectable from the configuration settings.
Gemstart versions 5.3 & 5.4 can be powered independently to the motor supply,
however if the control supply is derived from the same source as the motor voltage
then this can be linked across to the motor supply input terminals to monitor this
source.
- 35 -
Gemstart 5
Volume 1 Users Guide
6.3.11
Auto - Restart
When motor supply monitoring is included, as it is in Gemstart versions 5.3 & 5.4, the
Auto-Restart feature is available to carry out automatic re-starting of the motor upon
restoration of supply. The re-start is carried out either immediately or after a set time
delayed period.
The Auto-Restart feature has five settings to be entered using the Supply item under
the Configuration Editor:
1. Supply Fail and Recovery voltage levels entered as percentages of the
monitored voltage value.
2. Ride through will ride through a motor supply failure of up to 5s. This will enable
an immediate auto-restart of the motor should the motor supply return within this time
period.
3. Maximum Dip Time will sense if the monitored voltage has returned within this set
time period. Auto-restart is aborted if the supply does not return within the Maximum
Dip Time period.
4. Delay to Restart is the next timing phase, following a return of the supply within
the Maximum Dip Time, before an Auto-restart is initiated.
See also fig 2 below for further explanation of the Auto-Restart feature.
Note that the Auto-Restart feature can be disabled if the Maximum Dip Time is set to
OFF.
5. Inputs Supply Volatile allows Gemstart5 to know if Multi-Voltage inputs are wired
on the busbar or backup. In the first case, Gemstart5 knows that it has not to read
the opening of Normally Closed inputs during a voltage dip and go on autorestart.
Warning : a system with volatile Multi-Voltage inputs (that lose supply during a
supply dip) cannot be used with Supply Ride-Through set to No Limit.
- 36 -
Gemstart 5
Volume 1 Users Guide
- 37 -
Gemstart 5
Volume 1 Users Guide
6.3.12
- 38 -
Gemstart 5
Volume 1 Users Guide
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
RTD 1 +
RTD 1 RTD 1 + Sense
RTD 2 +
RTD 2 RTD 2 + Sense
RTD 3 +
RTD 3 RTD 3 + Sense
RTD 4 +
RTD 4 RTD 4 + Sense
RTD 5 +
RTD 5 RTD 5 + Sense
RTD 6 +
RTD 6 RTD 6 + Sense
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
RTD 1 +
RTD 1 RTD 1 + Sense
RTD 2 +
RTD 2 RTD 2 + Sense
RTD 3 +
RTD 3 RTD 3 + Sense
RTD 4 +
RTD 4 RTD 4 + Sense
RTD 5 +
RTD 5 RTD 5 + Sense
RTD 6 +
RTD 6 RTD 6 + Sense
6.3.12.1
2 wire connections
Installation
It is important to ensure a clean installation of the RTD sensors as the signal levels
involved are very low.
Each PT100 element should be screened with either a braid screen or foil screen.
Earthing of the screen should be applied both at the Pt100 element and at the
- 39 -
Gemstart 5
Volume 1 Users Guide
switchboard.
Ideally the plant wiring should also be enclosed in earthed, armoured cable.
Connections within the switchboard should ensure that unshielded connections are
kept to a minimum and that all wiring is shielded even within the switchboard. It is
permissible to earth the shield locally within a chassis, separately to the RTD element
The wiring connecting to the PT100 sensor should be sized to ensure that the DC
resistance is kept below 30 ohms in each cable. This is to ensure that the RTD unit
can compensate for the additional cable resistance.
6.3.12.2
RTD Configuration
The RTD can measure a range of temperatures and each temperature input requires
a pre warn and fault level. It will be possible to group three RTDs together to allow a
common configuration setting for all three (i.e. bearings). The group settings will be
held in RTD 1 or RTD 4. When RTDs are grouped the highest RTD temperature will
be used to perform the protection.
The Fault must be configurable from 105C to 180C in steps of 5C (16 options)
The pre warn can be Off or provide a warning at a temperature of 5, 10 or 15C lower
than the fault level.
It will also be possible to disable each RTD (no error reporting).
- 40 -
Gemstart 5
Volume 1 Users Guide
The loss of link between the RTD module and the input module can be protected (no
protection, warn, alarm, trip, latched trip). Select module type in Fuses and
Contactor and the protection severity. Note : Select carefully the right module; if
RTD module is selected and IP is fitted, protection will be engaged.
- 41 -
Gemstart 5
Volume 1 Users Guide
6.3.12.3
The status is displayed on GEMPRO. Access is via the temperature sensors button.
For these three cases, protection will work:
If the RTD measures > 264 then the warning message RTD x Open
circuit is displayed.
If the RTD measures <88 then the warning message RTD x Short circuit
is displayed.
If the RTD measures >= 194 < 264 then the warning message RTD x
High Temp.(>250C) is displayed.
For these two cases, input channel will be ignored:
If the RTD is not connected when starting the application then the warning
message RTD x Not connected is displayed.
If the RTD measures >88 <= 100 then the warning message RTD X Low
Temp.(<0C) is displayed
Note : Disconnection during application running will lead to Open circuit.
If the groups are enabled then the relevant text will show the highest temperature in
the group.
The diagram overleaf shows the wiring fault conditions
Gemstart 5
Volume 1 Users Guide
Input +
100<R>250
ohms
Input -
Input +
sense
Working connection
Input +
Input +
Input -
Input -
Input +
sense
Input +
sense
Short circuit
Input +
Input -
Input -
Input +
sense
Input +
sense
Input +
Input -
Open circuit
Input +
sense
Input +
Input +
Input -
Input -
Input +
sense
Input +
sense
Unused inputs
Low temperature
- 43 -
Gemstart 5
Volume 1 Users Guide
6.3.12.4
Information previously explained is also available in a data word over the network. It
is the Word 5 of Group 11 (dedicated to RTD). This word is called RTD Status and is
decoded using the following table :
6.3.12.5
- 44 -
Gemstart 5
Volume 1 Users Guide
then the individual channel protection is disabled and a group fault code is generated
if the temperature for any of the RTDs in the group is over the configured level.
NB When group protection is enabled Open or Short Circuit faults are generated for
any of the RTDs in the group.
Between the 2 groups there are 6 fault codes that can be generated. The severity of
these faults is configurable.
Group 1 RTD Trip
Group 2 RTD Trip
Bearings RTD Trip
Stator RTD Trip
Low Speed RTD Trip
High Speed RTD Trip
These faults will be generated instead of an RTD fault if the RTDs are grouped.
On the network, RTD values are on one byte and correspond to:
0 = low temperature (<0C)
1-250 = temperature value in C
251 = high temperature (>250C)
252 = group value not available (e.g. all probes in this group are short-circuit)
253 = open circuit (e.g. a probe has been deplugged during functionning)
254 = probe short-circuit
255 = not connected (at gemstart startup, no probe has been detected)
- 45 -
Gemstart 5
Volume 1 Users Guide
7 Display Modules
There are two display modules, the LED module and the LCD module. These units
are mounted on the front panel of the chassis and fit a standard 68mm square, meter
size cut-out. They are wired to the body unit using an 8 core cable with RJ45
connectors. This cable supplies the power from the body unit to the display module
and transfers data between them.
LCD Module.
LED Module.
Common Features:
LED 1 = Green Healthy/Watchdog LED. This turns off if there is a hardware/software
fault and the contactor opens. It is advised to proceed to the remplacement of the
drawer in this case.
LEDs 2 to 5 = 4 x tri-coloured, Red/Green/Yellow LEDs.
LEDs 2 -5 are pre-assigned to the following status conditions:
LED 2 = Running - LED red = contactor closed, LED off = contactor open
LED 3 = Stopped - LED green = contactors open and no current flowing, LED off =
contactor closed or current flowing.
LED 4 = Tripped/Alarm
LED red = Tripped or LED red flashing = Latched trip.
LED yellow = Warn or LED yellow flashing = Alarm
- 46 -
Gemstart 5
Volume 1 Users Guide
LED OFF = no fault.
Note: A Latched Trip or an Alarm needs to be reset (see section 7.2 for ways to
reset), whereas a Trip or a Warn are self clearing. The resetting or self clearing of a
fault is only possible once the source of the fault has been cleared. However, an
Alarm caused by a protection trip will reset automatically once the source of the fault
has been cleared and a successful start has been achieved. If both a Trip and Alarm
are present simultaneously, the Trip will take precedence.
LED 5 = Serial Link - LED yellow = Link active but not in control or LED green = Link
active and in control or LED off = no link.
However, LEDs 2 to 5 can be freely assigned to any one of the different function
options which are available. In addition, all four LEDs are user configurable to any
one of the three colour states. The LEDs can be configured to be On or Off for
function on or function off indication.
e.g. LED Off/Green = Function Off/Function On and LED Green/Off = Function
Off/Function On.
The following table lists all the functions available and their auto (default) colour
configuration.
Function
Serial Mode
Function Status
Off = No link
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
Running A
OFF
ON
Running B
OFF
ON
Manual Mode
Stopped
Running (A or B)
- 47 -
Gemstart 5
Volume 1 Users Guide
Function
Avail to Manual
Avail to Host
Test
Current
Auto
ON
Fault
ON
Avail to Priority
Function Status
ON
Off = No fault
OFF
Yellow = Warn
ON
ON
Red = Trip
ON
ON
OFF
ON
Off = Stopped
OFF
ON
ON
ON
See Display item under the Configuration Editor for full settings options.
There is also the option to display current on a single LED as None (Off), Low
(Yellow), Normal (Green), and High (Red).
Easy knockout plugs are provided as standard for the option to fit 16mm diameter
push buttons. One can be fitted on the LCD module or up to three on the LED
module.
The display modules are designed to allow self-adhesive labels to be affixed to
identify customised LED and push button configurations.
The RS232 programming port allows Flash Memory updates of Gemstart 5
software and configuration changes, both using the PC Programming
Tool/Configuration Editor.
- 48 -
Gemstart 5
Volume 1 Users Guide
Running A
Status
90%,
90%,
LINE 1
2
3
4
5
L1-2= 415V
Voltage
123.4A,123.4A,123.4A AMPS
235Hr,
No Faults
L1^100%FLC
Highest Percentage
6
7
LINE 1
2
3
4
5
6
7
LINE 1
2
3
No Faults
4
5
- 49 -
6
7
Gemstart 5
Volume 1 Users Guide
- 50 -
Gemstart 5
Volume 1 Users Guide
SEVERITY
Config. Conflict ~.
Trip
Isolator Fault ~.
Config.
Undefined Fault ~.
Earth Fault ~.
Config.
Thermistor Relay ~.
Config.
Overload Relay ~.
Config.
Thermal Overload ~.
Config.
RESET
GROUP
FAULT MESSAGE
FAULT
CODE SENT
DOWN
SERIAL LINK
9
Manual Stop ~.
MEANING
input
to
Not Used
10
Trip
11
Not Used
Interlock ~.
12
Config.
Failed to Close A ~.
13
Trip &
Alarm
Failed to Close B ~.
14
Trip &
Alarm
Failed to Open A ~.
15
Trip &
Alarm
Failed to Open B ~.
16
Trip &
Alarm
- 51 -
Gemstart 5
FAULT
CODE SENT
DOWN
SERIAL LINK
RESET
GROUP
FAULT MESSAGE
SEVERITY
MEANING
PAMM Read/Write ~.
17
Config.
18
Warn
19
Trip &
Alarm
Fwd/Rev ~.
20
Warn
21
Warn
Under Current ~.
22
Config.
Start Current ~.
23
Config.
Start Time ~.
24
Config.
Continuous ALC ~.
25
Config.
Instant ALC ~.
26
Config.
Restart Inhibit ~.
27
Trip &
Alarm
28
ELCB Fault ~.
29
Not Used
Config.
- 52 -
Gemstart 5
AutoRestart ~.
FAULT
CODE SENT
DOWN
SERIAL LINK
RESET
GROUP
FAULT MESSAGE
SEVERITY
MEANING
30
Warn
Imbalance ~.
31
Config.
Single Phasing ~.
32
Config.
33
Config.
34
Config.
35
Trip
Device Fault ~.
36
Config.
37
Config.
38
Config.
Chassis Settings
Changed ~.
39
Warn
Failed to Close C ~.
40
Trip &
Alarm
Failed to Open C ~.
41
Trip &
Alarm
Unexpected Open A ~.
42
Trip &
Alarm
Unexpected Open B ~.
43
Trip &
Alarm
- 53 -
Gemstart 5
FAULT MESSAGE
FAULT
CODE SENT
DOWN
SERIAL LINK
SEVERITY
RESET
GROUP
MEANING
Unexpected Open C ~.
44
Trip &
Alarm
Unexpected Close A ~.
45
Trip &
Alarm
Unexpected Close B ~.
46
Trip &
Alarm
Unexpected Close C ~.
47
Trip &
Alarm
Changeover Timeout ~.
48
Trip &
Alarm
Phase Reversal ~.
49
Config.
Starts/Hr ~.
50
Config.
Unknown Contactor
Type ~.
51
Alarm
Over Voltage ~.
52
Config.
Under Voltage ~.
53
Config.
Test Mode ~.
54
Config.
55
Warn or
Trip
No GS RX ~.
56
Warn
GS RX Crossed ~.
57
Warn
Warn
58
- 54 -
Gemstart 5
Address in use ~.
59
Warn
TX RX Lines Crossed
~.
60
Warn
Speed Sense ~.
61
Config.
62
Warn
Warn
Gemstart
is
not
receiving
acknowledgements from the Host that
it has received a message from
Gemstart. (The sequence bit is not
changing.)
Alarm
FAULT MESSAGE
GS TX Fault ~.
Stop Delayed.
(Contactor Protection)
63
64
MEANING
65
Not Used
66
Not Used
67
Not Used
68
Not Used
69
Not Used
70
Alarm
71
PAMM Motor Data Lost
~.
RESET
GROUP
FAULT
CODE SENT
DOWN
SERIAL LINK
SEVERITY
72
Not Used
Alarm
73
Not Used
74
Not Used
75
Not Used
- 55 -
Gemstart 5
Host TX Range ~.
Unknown Function
Enabled ~.
Under Power ~.
Over Power ~.
CRC Failed ~.
76
Warn
LTrip
77
RESET
GROUP
FAULT MESSAGE
FAULT
CODE SENT
DOWN
SERIAL LINK
SEVERITY
MEANING
78
Not Used
79
LTrip
80
Warn
81
Not Used
82
Not Used
83
Alarm
84
Config.
85
Config.
86
Alarm
87
Warn
CT
rating
is
Gemstart 5
FAULT
CODE SENT
DOWN
SERIAL LINK
RESET
GROUP
FAULT MESSAGE
SEVERITY
MEANING
3 CTs
Gemstart5.3
configuration
on
Ride-Through = No Limit
incompatible with Volatile Supply
Inputs
88
Alarm
- 57 -
Gemstart 5
89
Warn
90
Config.
91
Config.
RTD 1 Over
Temperature
92
Config.
RTD 2 Over
Temperature
93
Config.
RTD 3 Over
Temperature
94
Config.
RTD 4 Over
Temperature
95
Config.
RTD 5 Over
Temperature
96
Config.
RTD 6 Over
Temperature
97
Config.
98
Config.
99
Config.
100
Config.
101
Config.
102
Config.
103
Config.
104
Config.
105
Config.
106
Config.
107
Config.
- 58 -
RESET
GROUP
FAULT MESSAGE
FAULT
CODE SENT
DOWN
SERIAL LINK
SEVERITY
MEANING
The
temperature
measurement
thermistor has reached its set point
The
temperature
measurement
thermistor has failed short circuit
Gemstart 5
108
Config.
109
Config.
Group 1 RTD
110
Config.
Group 2 RTD
111
Config.
Bearings RTD
112
Config.
Stator RTD
113
Config.
114
Config.
115
Config.
116
Config.
FAULT MESSAGE
RESET
GROUP
FAULT
CODE SENT
DOWN
SERIAL LINK
SEVERITY
MEANING
Description of Fault
The PAMM was not detected when Gemstart powered up. Note only
if External PAMM required.
The PAMM and internal PAMM backup are not present or working.
Check PAMM wiring.
Hardware Faults
Oscillator Fail
Internal (to the processor) memory fault. Replace the unit. Return for
repair.
External (to the processor) memory fault. Replace the unit. Return
for repair.
Software Faults:
- 59 -
Gemstart 5
Volume 1 Users Guide
Fatal Error Text
Description of Fault
Unexpected Reset
Unexpected RET
Register Corrupted
Stack Underflow
Stack Overflow
Software
0x##@####
Wdog,
Not In-Page
PAMM Faults:
Power Down & Replace This is the message displayed when replacing the PAMM using the
PAMM
GEMPRO command, REPLACE PAMM.
PAMM Wiring Fault
Gemstart has detected a problem with the PAMM data line. Check
the PAMM wiring.
- 60 -
Gemstart 5
Volume 1 Users Guide
8 Watchdog Functions
There is a green Healthy LED on all Gemstart body units which will flash at a slow
rate of approximately once a second, indicating that the unit is working correctly. If
there is a hardware or software failure this will cause a system Watchdog trip and this
LED will flash at a much faster rate of approximately four times a second.
On the display modules and on each extension module the green Healthy LED is
illuminated when the units are working correctly, but if there is a hardware or
software failure the system Watchdog trips and this LED is turned Off.
The system will also disable the serial link transmit, if connected, and disable the
output relays for a Watchdog trip.
In the unlikely event of the Watchdog being activated, firstly see if the LCD display, if
one is present, has reported an error message, such as Hardware or Software
Failure. If it is software it may be possible to reset the Gemstart by powering down
the unit and turning it back on again after 60 seconds. Any hardware or software fault
must be reported to COMECA for investigation.
- 61 -
Gemstart 5
Volume 1 Users Guide
9 Event Records
9.1 Motor History
A history of the last 16 trips that opened the contactor is maintained. Each entry has
the value of current, reason for trip, and the elapsed time since the trip occurred. The
records are overwritten on the first in first out principle (FIFO).
- 62 -
Gemstart 5
Volume 1 Users Guide
10 System Integration
A range of communications protocols are available for networking Gemstart 5s with
an intelligent control system, using either a 2 or 4 wire multi-drop RS485 serial link
:
Gembus (COMECAs proprietary protocol) (up to 100 devices/ 100 per link)
All the above protocols come pre-loaded into Gemstart 5 and may be selected under
item Communications using the Configuration Editor.
6,
7,
8,
Traffic Diagnostics
Sub Functions
0
10
Reset Counters 1 to 9
11
12
13
14
15
16
17
18
11,
15,
16,
- 63 -
Gemstart 5
Volume 1 Users Guide
10.1.1
Some aspects of the Modbus serial link cannot be changed. These are:
Start Bits
Data
Parity
None
Stop Bits
Modbus Type
RTU
3 characters
Additional Information
Link Timeout Time
2 seconds
1 seconds
8 registers
128 bits
64 registers
There are some aspects of the Modbus serial link that can be configured for each
Gemstart. These configuration parameters are:
Protocol (Communications/Protocol)
Select Modbus. Select 2 or 4 wire option. Note if the link address is set to 0 then
Modbus is not offered as this is an illegal address. Defaults to Profibus. The Profibus
options is discussed elsewhere.
Link Fail Action(Communications/Link Fail Action)
Gemstart can take action on a Serial Link failure. The link fail action is taken if the
serial link was controlling Gemstart when the link failed. The options are:
Trip:
Warn:
Off:
With Modbus the link has failed when Gemstart has not seen a valid message to any
address within the timeout time.
Configurable Host status bits(Communications/Status Bit Source)
Two bits are available in the status word, which may be separately configured to any
of the inputs of Gemstart 5. The available options for these bits are Disabled, Active,
INTERLOCK, INPUTS 1- 12, and OUTPUT 4.
Group 10 (Communications/Group 10 Word x)
A configurable data group has been provided. This allows the user to select items
from the 10 fixed groups which are grouped together in adjacent addresses as group
- 64 -
Gemstart 5
Volume 1 Users Guide
10.
Control Group (Communications/Control Group)
Define which Control Group this Gemstart is a member of. Options of Off and groups
1 to 7 are available. A Modbus Host can write (to register address 3) a Group Control
command to control several Gemstarts at the same time. This command contains a
standard 4 bit contactor control command and 7 Group Flags. If the Group Flag
corresponding to this Gemstarts group is set, then Gemstart will copy the 4 bit group
command to the command register (address 1). While the Group Flag is set the
Group Command is used regardless of what is written to address 1.
Link Number and Address (Communications/Address)
This value identifies a specific Gemstart on the Link. It can only be altered using
GEMPRO to change it from Not Set to the desired address. Once the address is set
only COMECA engineers can change the address. This protects the address from
accidental changes. Valid address values are 1 to 254.
Fixed Baud Rate(Communications/Baud Rate)
You can connect Gemstart to links running at 4800, 9600, 19k2, 38k4, 57k6, 115k2
and 128k baud. Gemstart can auto search for the baud rate of the link to which it is
connected or can be configured to always run at 115k2, 9600 or 19k2. Fixing the
baud rate means that time is not wasted searching for messages at the incorrect
rate.
Fixed Timeout (Communications/Fixed Timeout)
The serial link Fixed Timeout time has 4 options.
2.5s
5s
10s
20s
These options fix the timeout regardless of the baud rate. The timeout time is the
time between valid messages to any address seen on the link.
10.1.2
- 65 -
Gemstart 5
Volume 1 Users Guide
Contactor Command
Gemstart can be controlled via the contactor command using the codes listed in
Table 14:
Table 14 Serial link contactor command codes
Bits 3-0
Command
Mode
0000
0001
0010
0011
0100
0101
0110
0111
1000
1001
1010
1011
1100
1101
1110
1111
Stop
Close A
Close B
No Action
Reserved
Reserved
Reserved
Reserved
Stop
Close A
Close B
No Action
Reserved
Reserved
Reserved
Reserved
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Priority
Priority
Priority
Priority
Priority
Priority
Priority
Priority
Close A and Close B will mean different things to different contactor models (for
example Forward/Reverse, Low/High Speed, Close/Open Valve).
When Gemstart is operating as a General Purpose I/O device, bits 3 to 0 are the
requested states for outputs D, C, B, A respectively. There is no priority mode on a
General Purpose I/O device.
A close command is edge triggered. I.e. the command is only actioned when it first
appears. If a close command is present and the contactor is not closed then an Open
Required Fault is reported by Gemstart. This fault can be cleared by sending an open
command until the fault clears then send the close command again. Alternatively
close the contactor with the GEMPRO control program.
Resets and I/O Functions byte
Six bits of this field are relevant to you. These six bits include four GP Output bits and
two reset bits.
Table 15 - Reset and General Purpose Outputs Byte
Bit
Command
0
1
2
3
4
5
For non GP I/O contactor types any spare outputs can be configured (Fuses &
Contactors) to output the GP O/P bits received from the host.
- 66 -
Gemstart 5
Volume 1 Users Guide
The function of the Reset from Host Supervisor and Reset from Host Operator bits
depends on configuration (Communications). A range of individual resets can be
assigned to each of these bits, as given below:
Reset All
Thermal Overload
Application Protection
Interlocks
Alarms
All alarms
10.1.3
Bit Map
The following data bits can be read. Some of the bits can also be written to.
Address
read/Write
Read / Write
Close A
Read / Write
Close B
Read / Write
Reserved - leave at 0
Close C
Read / Write
Priority Select
Close D
Read / Write
GP Output A
Read / Write
GP Output B
- 67 -
Gemstart 5
Volume 1 Users Guide
Address
read/Write
Read / Write
GP Output C
Read / Write
GP Output D
Read / Write
10
Read / Write
11
Read
12
Read
13
Read
14
Read
15
Read
16
Read
17
Read
18
Read
19
Read
20
Read
Set if motor Stopped (Contactors open and current low - same as Stopped LED)
21
Read
22
Read
23
Read
24
Read
25
Read
Set if motor available to Host (i.e. no trips, and in auto or priority modes, and not in test
position)
26
Read
HW Interlock input
27
Read
Hardware Input 1
28
Read
Hardware Input 2
29
Read
Hardware Input 3
30
Read
Hardware Input 4
31
Read
Hardware Input 5
32
Read
Hardware Input 6
33
Read
Hardware Input 7
34
Read
Hardware Input 8
35
Read
Hardware Input 9
36
Read
Hardware Input 10
37
Read
Hardware Input 11
38
Read
Hardware Input 12
Word Map
The following words can be read from Gemstart. Some of the addresses can also be
written to. All values are unsigned 16 bit numbers unless indicated otherwise.
Address
Data
Command
R/W
2
Description
Bit 0,1 command; bit 3 is priority. Bit 2 reserved - leave as 0.
Command 00 = stop, 01 = start A, 10 = start B, 11 = no action.
Group Control
Bits 0-3
R/W
3
R/W
Bits 4-7
Reserved
Bit 8
Group 1. Set to get Group 1 Gemstarts to obey the command in bits 0-3.
- 68 -
Gemstart 5
Volume 1 Users Guide
4
Status Bits
Bit 15
Reserved
Bit 0
Bit 1
Bit 2
Alarm Active
Bit 3
Warn Active
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Contactor A State
Bit 9
Contactor B State
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Display Data
The value being displayed on Gemstart. NB if 12.34 is being displayed 1234 will be in this
location.
Fault Code
The high byte is the severity the low byte is the fault code.
Address
Data
Description
10
Power (%Rating)
11
Power Factor
12
Link Timeouts
13
CRC Errors
Grp2:2. Number of CRC Errors detected at Gemstart since counter last reset
14
15
16
spare
17
Grp3.1. The number of complete hours that the contactor has been closed
18
Operations of A (Hundreds)
19
Operations of A (Units)
20
21
spare
22
Operations of B (Hundreds)
23
Operations of B (Units)
24
Operations of C (Hundreds)
- 69 -
Gemstart 5
Volume 1 Users Guide
Address
Data
Description
25
Operations of C (Units)
26
Motor
Supply
(%Nominal)
27
28
29
30
31
Hardware I/O
Voltage
32
Grp6:1. Highest phase current. Divide by Highest Current Divider (Group 6, Word
2) to get Amps
33
Grp6:2. Adjust Highest Current (Group 6, Word 1) to put the decimal point in the
correct place. (Values are 1, 10, 100, 1 000, 10 000)
34
Grp6:3. Real Power. Divide by Power Divider (Group 7, Word 5) to get kWatts
35
36
Grp6:4. Earth Fault Current. Divide by Earth Fault Divider (Group 6, Word 5) to get
Amps)
Amps
Grp6:5. Adjust Earth Fault Current (Group 6, Word 4) to put the decimal point in the
correct place. (Values are 1, 10, 100, 1 000, 10 000)
37
Grp7:1. Number of seconds for the last successful startup (Note: A successful start
is one with no trip or stop before the current drops below 100%FLC)
38
39
40
Imbalance (%)
41
Power Divider
Grp7:5. Adjust kW Power (Group 6, Word 3) to put the decimal point in the correct
place. (Values are 1, 10, 100, 1 000, 10 000)
42
Grp8:1. Estimation of heat energy used during last start as a percentage of the fault
level
43
44
45
Grp8:4. kWatt hours measured since Watt Hour meter was last reset (0-9999)
46
Grp8:5. MWatt hours measured since Watt Hour meter was last reset (0-9999)
47
48
49
50
51
Reactive Power
Grp9:5. Reactive Power. Divide by Power Divider (Group 7, Word 5) to get kVAR
52
Data Word
53
Data Word
54
Data Word
55
Data Word
56
Data Word
57
Status Bits
Same as Address 4
58
Fault Code
Same as Address 6
59
Data Word
Grp11:1. RTD 1 (MSB) & 2 (LSB) (see 6.3.12.4 for a description of values)
60
Data Word
61
Data Word
- 70 -
Gemstart 5
Volume 1 Users Guide
Address
Data
Description
62
Data Word
63
Data Word
Configuration Data
Address
Read/Write
Data
257-264
Read / Write
Configuration Page 0
265-272
Read / Write
Configuration Page 1
273-280
Read / Write
Configuration Page 2
281-288
Read / Write
Configuration Page 3
289-296
Read / Write
Configuration Page 4
297-304
Read / Write
Configuration Page 5
305-312
Read / Write
Configuration Page 6
313-320
Read / Write
Configuration Page 7
321-328
Read / Write
Configuration Page 8
329-336
Read / Write
Configuration Page 9
337-344
Read / Write
Configuration Page 10
345-352
Read / Write
Configuration Page 11
353-360
Read / Write
Configuration Page 12
361-368
Read / Write
Configuration Page 13
369-376
Read / Write
Configuration Page 14
377-384
Read Only
Configuration Page 15
Read/Write
Data
1025-32
Read Only
1033-40
Read Only
Trip History 2
1041-48
Read Only
Trip History 3
1049-56
Read Only
Trip History 4
1057-64
Read Only
Trip History 5
1065-72
Read Only
Trip History 6
1073-80
Read Only
Trip History 7
1081-88
Read Only
Trip History 8
1089-96
Read Only
Trip History 9
1097-04
Read Only
Trip History 10
1105-12
Read Only
Trip History 11
1113-20
Read Only
Trip History 12
1121-28
Read Only
Trip History 13
1129-36
Read Only
Trip History 14
1137-44
Read Only
Trip History 15
1145-52
Read Only
- 71 -
Gemstart 5
Volume 1 Users Guide
Event History Data
Address
Read/Write
Data
1153-60
Read Only
1161-68
Read Only
Event History 2
1169-76
Read Only
Event History 3
1177-84
Read Only
Event History 4
1185-92
Read Only
Event History 5
1193-00
Read Only
Event History 6
1201-08
Read Only
Event History 7
1209-16
Read Only
Event History 8
1217-24
Read Only
Event History 9
1225-32
Read Only
Event History 10
1233-40
Read Only
Event History 11
1241-48
Read Only
Event History 12
1249-56
Read Only
Event History 13
1257-64
Read Only
Event History 14
1265-72
Read Only
Event History 15
1273-80
Read Only
(Msb of
first
register)
1
- 72 -
Gemstart 5
Volume 1 Users Guide
position)
10. Manual
3
Event Type
0. No Event
1. Start A
2. Start B
3. Stop
4. Gemstart Power Up
5. Gemstart Power Down
6. Time Synchronised
7. Time Sync Lost
8. Start A Delayed
9. Start B Delayed
10. Stop Delayed
11. Motor Supply Fail
12. Motor Supply Recovery
4
msb
lsb
llsb
10
msb
of fractions of a second
11
lsb
of fractions of a second
Bit 0 is the Global Sync flag and is set if the PLC time is Globally synchronised.
12
Time Status
0 = Gemstart(no time update since power on)
1 = Synchronised (sync time received in last 100s)
2 = Estimated(no sync time received in last 100s)
3 = Invalid(time was not updated between power up and power down)
13
Spare set to 0
14
Spare set to 0
15
- 73 -
Gemstart 5
Volume 1 Users Guide
10.1.4
If no valid messages are received by Gemstart from the Host system within the
timeout period, a Link Fail Trip or Warn is flagged.
Once the link is established the timeout period of each baud rate on the link is 2.5s
except for 4800 which has a timeout of 5s.
The timeout time can be forced for any baud rate to be 5, 10 or 20s. See
configuration item Communications/Timeout
The auto detect method for Baud (and protocol) selection is as follows:
Gemstart will only try a new baud rate if it is receiving bytes but has not received a
valid message for 1.5s
The 1.5s time starts when the first byte has been received after a timeout. When an
active link times out the baud rate is not changed
The normal order of events is as follows:
1.
2.
After the timeout time associated with the baud rate, the link fail action
will occur (trip or warn). The baud rate will not change. No further
timeouts are possible until a byte has been received
3.
4.
5.
If data is being continuously transmitted by the Host the unit will spend 1.5s at each
baud rate until it receives a valid message.
To keep Gemstart operating in Auto or Priority mode, Gemstart must see a valid
message (to any address) every 2.5s. Given that there is enough activity on the link,
Gemstart will not go into Auto or Priority mode until the command register (address
1) or command bits (address 1, 2 or 4) have been written to.
10.1.5
Gemstart provides you with the following serial link statistics which can be viewed on
GEMPRO:
10.1.6
Baud rate
Command
Link
Timeouts
Gemstart indicates that a Serial Link Fault is present if there is no Modbus link
- 74 -
Gemstart 5
Volume 1 Users Guide
present. If a Modbus link is connected then the Link Fault indication will be cleared.
However Gemstart will not go into Auto or Priority mode until the command register
has been written to.
If the first command write after a link fail is a start command it will not be obeyed as
all commands are edge triggreed and in this case an edge was not seen.
It is therefore important that the Modbus Master continually monitors the status of
each Gemstart and if it sees that a Gemstart is not in Auto or Priotity then the
Modbus Master should write a No Action command to the command register.
10.1.7
Gemstart 5 time can be synchronised with a broadcast messaged from the master
PLC. The broadcast message should be to address 0x0801 (offset 0x0800) and be 4
registers long. The first byte of the message is taken as the time mark. The format of
the 4 registers of data is as follows:
( Inverted IEC 870-5-4 CP56Time2a):
Words
0
0
0
0
su
0
0
Year
0
00..99
Month
0
WeekDay
DayOfMonth
iv
Minutes
0..23 0..59
0
Hours
Millisecond Hi
215
Millisecond Lo
28 27
Notes:
To maintain synchronised time the broadcast message should be sent within 100s of
the previous broadcast. An update time of 30s would ensure time synchronisation is
not lost should a broadcast be corrupted.
This Time Synchronisation message is the same message used by MICOM relays.
Gemstart 5
Volume 1 Users Guide
Gemstart 5 will support all the profiles for Motor Management Starter. Motor Starter
will NOT be covered. Motor Starters are too similar but not compatible with Motor
Management starters and inclusion of both will cause confusion.
The Motor Management starter will be expanded to offer more data by using the
Gemstart profiles.
A reference document for PLC engineers (Profibus Cyclic & Acyclic Data.pdf) is
available on request. This document covers the Cyclic and Acyclic methods of
accessing data in Gemstart via the Profibus protocol.
10.2.1
Gemstart Term
Definition
Run Reverse
Running B
Off
Stopped
Run Forward
Running A
Overload
Warning
Overload
Warning
Restart Inhibit
Auto Mode
Auto Mode
Fault
Trip
Warning
Warning/Alarm
Local Control
Manual Control
Ramping
Startup
- 76 -
Gemstart 5
Volume 1 Users Guide
Motor Management Starter Monitor - Format 0
Transmitted as 4 bytes.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Warning
Fault
(Trip)
Lock Out
Time
O/load
Warning
Run
Forward
Off
(or Alarm)
Auto
Mode
Run
Reverse
Status Bit 2
Status Bit 1
Open
Required
Test
Position
Reserved
Reserved
Ramping
Local
Control
Ramping
Local
Control
(Stopped)
Reserved
Reserved
Gemstart Term
Definition
Run Reverse
Start B
Off
Stop
Stop the motor. Run forward and Run Reverse are ignored.
Run Forward
Start A
Self Test
Emergency
Start
Emergency
Start A
Auto Mode
Priority Mode
Trip Reset
Supervisor
Reset
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Trip Reset
Auto
Mode
Emergency
Self Test
Run
Forward
Off
Run
Reverse
Operator
Reset
Reset
kWh
(Supervisor)
GP Output
B
GP Output
A
Start A
- 77 -
(Not used)
Reserved
Reserved
(Stop)
Reserved
Reserved
Gemstart 5
Volume 1 Users Guide
Byte
0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Trip Reset
Auto
Mode
Emergency
Self Test
Run
Forward
Off
Run
Reverse
Operator
Reset
Reset
kWh
(Supervisor)
GP Output
B
GP Output
A
start
(Not used)
Reserved
(Stop)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Analogue Output
Reserved
10.2.2
Reserved
Reserved
Reserved
Reserved
Monitoring Format
Command Format
10.2.3
Gemstart 5 Profile
Bytes
Description
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Warning
Fault
Lock Out
(Trip)
O/load
Warning
Run
Forward
Off
(or Alarm)
Auto
Mode
Run
Reverse
Status Bit 2
Status Bit 1
Open
Required
Test
Position
Reserved
Reserved
Ramping
Local
Control
Ramping
Local
Control
(Restart
Inhibit)
- 78 -
(Stopped)
Reserved
Reserved
Gemstart 5
Volume 1 Users Guide
5
Fault Code
7
8
9
10
11
12
Amps. 0-65,535 A
14
Power. 0-65,535 kW
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
This table gives the details of the greatest possible profile. See after to have different
profiles. Please note that Group13 is used for the Engineering Working Station
Gemview5. For more information about EWS please contact us.
Output Data Command
Transmitted as 1, 2, 3, 4, 5 or 6 bytes.
The definition of the first 4 bytes is the same as the Motor Management Starter.
Byte
0
1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Trip Reset
Auto Mode
Emergency
Self Test
Run
Forward
Off
Run
Reverse
GP Output
(Supervisor)
(Priority)
GP Output
Operator
- 79 -
start
Reset
(Not Used)
Reserved
Reserved
(Stop)
Reserved
Reserved
Gemstart 5
Volume 1 Users Guide
B
Reset
kWh
Analogue Output
Reserved
10.2.4
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
The following table shows the sizes of the transferred data blocks in the case of each
of the supported profiles.
Command type
Command
size
Monitoring
size
Manager Starter 1
2 bytes
4 bytes
MS (Manager Starter)
Manager Starter 2
4 bytes
4 bytes
MS
1 byte
1 byte
MS (1 byte only)
1 byte
2 bytes
MS (2 bytes)
1 byte
3 bytes
MS (3 bytes)
1 byte
4 bytes
MS
1 byte
6 bytes
MS + default
1 byte
6 bytes + 1
word
MS + default + current
1 byte
6 bytes + 2
words
2 bytes
1 byte
MS (1 byte only)
2 bytes
2 bytes
MS (2 bytes)
2 bytes
3 bytes
MS (3 bytes)
2 bytes
4 bytes
MS
2 bytes
6 bytes
MS + default
2 byte
6 bytes + 1
word
MS + default + current
2 bytes
6 bytes + 2
words
3 bytes
1 byte
MS (1 byte only)
3 bytes
2 bytes
MS (2 bytes)
3 bytes
3 bytes
MS (3 bytes)
3 bytes
4 bytes
MS
3 bytes
6 bytes
MS + default
3 byte
6 bytes + 1
word
MS + default + current
- 80 -
st
st
st
Gemstart 5
Volume 1 Users Guide
Command type
Command
size
Monitoring
size
3 bytes
6 bytes + 2
words
4 bytes
1 byte
MS (1 byte only)
4 bytes
2 bytes
MS (2 bytes)
4 bytes
3 bytes
MS (3 bytes)
4 bytes
4 bytes
MS
4 bytes
6 bytes
MS + default
4 byte
6 bytes + 1
word
MS + default + current
4 bytes
6 bytes + 2
words
4 bytes
14 bytes +
8 words
4 bytes
12 bytes +
2 words
4 bytes
12 bytes +
8 words
5 bytes
6 bytes + 8
words
5 bytes
6 bytes +
14 words
5 bytes
12 bytes +
14 words
6 bytes
6 bytes +
14 words
6 bytes
6 bytes +
14 words +
6 words
6 bytes
12 bytes +
14 words +
6 words
10.2.5
st
Group Data
It is possible for the Profibus Master to issue one or two requests for specific groups
of data from a specific Gemstart. Gemstart offers 10 different data groups. All values
are Unsigned 16 bit numbers unless indicated otherwise.
Group 1 - Current and Power Percentage
Field
Description
- 81 -
Gemstart 5
Volume 1 Users Guide
Field
Description
Earth
Fault
(%EFC)
Power (%Rating)
Power Factor
Description
Link Timeouts
CRC Errors
Input Counter
(Thousands)
Spare
Description
Operations
(Hundreds)
Operations
(Units)
of
of
Spare
Description
of
Operations of B (Units)
Operations
(Hundreds)
of
Operations of C (Units)
- 82 -
Gemstart 5
Volume 1 Users Guide
Field
Motor Supply
(%Nominal)
Description
Voltage The motor supply voltage as a percentage of
nominal supply voltage
Description
Input Counter
(Thousands)
Hardware I/O
Description
Earth
Fault
(Scaled Amps)
Group 7 - Startup
Field
Description
- 83 -
Gemstart 5
Volume 1 Users Guide
Field
Peak Startup
(%FLC)
Description
Current Maximum current achieved during last successful
startup as a percentage of FLC. (Note: A
successful start is one with no trip or stop before
the current drops below 100%FLC)
Auto Restart Timer (1s Time in seconds before the motor is restarted
units)
Imbalance (%)
Power Divider
Description
Thermal Content used by Estimation of heat energy used during last start
start (%)
as a percentage of the fault level
Thermal Content (%)
Time to Trip / Available The number of seconds before Gemstart will trip
(s)
or become available
kW hour meter (kWh)
Description
Other Protection
Counter
Reactive Power
- 84 -
Gemstart 5
Volume 1 Users Guide
Group 10 - Configurable
Field
Description
Data
Word
Data
Word
Data
Word
Data
Word
Data
Word
Field
Description
RTD measurement
RTD measurement
RTD measurement
RTD measurement
RTD Status
Group 11 - RTD
Description
Current Phase 1
Current Phase 2
Current Phase 3
Spare
Spare
NOTE: The data items, Highest Phase Current (Amps), Earth Fault Current
(Amps) and Real Power (kW), are scaled to keep a reasonable amount of
detail in the readings. The scaling values are defined by the configuration
and do not change dynamically.
The following table may help you understand how the data is related.
CT Current (adjusted GS Display
for Turns)
0.010A-0.099A
0.1234 A
10000
1234 = 0.1234A
0.10A-0.99A
1.234 A
1000
1234 = 1.234A
- 85 -
Gemstart 5
Volume 1 Users Guide
1.0A-9.9A
12.34 A
100
1234 = 12.34A
10A-99A
123.4 A
10
1234 = 123.4A
100A-990A
1234 A
1234 = 1234A
1.0k - 9.9k
12.34 kA
12340 = 12340A
10k
23.4 kA
23400 = 23400A
- 86 -
Gemstart 5
Volume 1 Users Guide
Rated Power
GS Display
Power
Divider Power
Group7: Word 5
Group 6: Word 3
0.10kW-0.99kW
1.234 kW
1000
1234 = 1.234 kW
1.0kW-9.9kW
12.34 kW
100
1234 = 12.34 kW
10kW -99kW
123.4 kW
10
1234 = 123.4 kW
100kW -990kW
1234 kW
1234 = 1234 kW
1.0MW - 9.9MW
12.34 MW
12340 = 12340 kW
10MW
23.4 MW
23400 = 23400 kW
10.3.1
There are some aspects of the Gembus serial link that can be configured for each
Gemstart. These configuration parameters are:
Protocol
Select Gembus. (Note if the link address is > 99 then Gembus will not be
offered).The Modbus and Profibus options are discussed elsewhere.
Link Fail Action (Communications/Link Fail Action)
Gemstart can take action on a Serial Link failure. The link fail action is taken if the
serial link was controlling Gemstart when the link failed. The options are:
Trip:
Warn:
Off:
- 87 -
Gemstart 5
Volume 1 Users Guide
A configurable data group has been provided. This allows the user to select items
from the 10 fixed groups to be sent as one group 10 message. See the section, Data
Groups, where the available options are covered.
Control Group (Communications/Control Group)
Define which Control Group this Gemstart is a member of. Options of Off and groups
1 to 7 are available. The Gembus Host can send a Group Control command to
control several Gemstarts at the same time. This command contains a standard 4 bit
contactor control command and 7 Group Flags. If the Group Flag corresponding to
this Gemstarts group is set, then Gemstart will use the 4 bit group command as the
serial link command and ignore the normal serial link command. When the relevant
Group Flag is cleared Gemstart will revert to using the normal serial link command.
The Command display under the LINK status key will show (Grp) when a Group
Command is being used.
Link Number and Address (Communications/Advanced Settings/Address)
This value identifies a specific Gemstart on the Link. It can only be altered using the
GEMPRO control program to change it from Not Set to the desired address. Once
the address is set only COMECA engineers can change the address. This protects
the address from accidental changes. Links can be numbered 0 to 15. Each link can
support one hundred units. Valid address values are 0 to 99.
Fixed Baud Rate(Communications/Advanced Settings/Baud Rate)
You can connect Gemstart to links running at 600, 1200, 2400, 4800, 9600, 19200 &
115 200 baud. Gemstart can auto search for the baud rate of the link to which it is
connected or can be configured to always run at one of the three fastest rates. Fixing
the baud rate means that time is not wasted searching for messages at the incorrect
rate.
Fixed Timeout (Communications/Advanced Settings/Fixed Timeout)
The serial link Fixed Timeout time defaults to Auto. The Auto option has a different
timeout time for each baud rate as follows:
115200
2.5s
19200 & 9600,
2.5s
4800
5s
2400
10s
1200 & 600
20s
The Fixed Timeout configuration also allows fixed timeouts of 5s, 10s and 20s. These
options fix the timeout regardless of the baud rate. The timeout time is the time
between valid messages to any address seen on the link. It is NOT related to the link
scan time.
10.3.2
- 88 -
Gemstart 5
Volume 1 Users Guide
Contactor Command
Gemstart can be controlled via the contactor command using the codes listed in
Table 6.
Table 6 Gembus contactor command codes
Bits 3-0
Command
Mode
0000
Stop
Auto
0001
Close A
Auto
0010
Close B
Auto
0011
No Action
Auto
0100
Priority Open
Priority
0101
Auto
0110
Auto
Reserved for Gemstart 3 functionality
0111
Auto
1000
Stop
Priority
1001
Close A
Priority
1010
Close B
Priority
1011
No Action
Priority
1100
Priority Open
Priority
1101
1110
Priority
1111
Priority
Close A and Close B will mean different things to different contactor models (for
example Forward/Reverse, Low/High Speed, Close/Open Value).
When Gemstart is operating as a GP I/O device, bits 3 to 0 are the requested states
for outputs D, C, B, A respectively. There is no priority mode on a GP I/O device.
A close command is edge triggered. I.e. the command is only actioned when it first
appears. If a close command is present and the contactor is not closed then an
Open Required Fault is reported by Gemstart. This fault can be cleared by sending
an open command until the fault clears then send the close command again.
Alternatively close the contactor with the GEMPRO control program.
Resets and I/O functions byte
Six bits of this field are relevant to you. These six bits include four GP Output bits and
two reset bits.
Table 7 - Reset and General Purpose Outputs Byte
Bit
Command
- 89 -
Gemstart 5
Volume 1 Users Guide
Bit
Command
Operator Reset
Supervisor Reset
Any spare outputs can be configured (Fuses And Contactors) to output the GP O/P
bits received from the host.
The function of the Reset from Host Supervisor and Reset from Host Operator bits
depends on configuration (see Communications/Host Resets). A range of individual
resets can be assigned to each of these bits, as given below:
Reset All
Thermal overload
Application Protection
Interlocks
Alarms
All alarms
Earth
10.3.3
Status Message
A Gembus Host allows you to define the length of the Status message Gemstart
sends on every scan. The more data sent in the status message by each Gemstart
the longer the scan time. Although on some systems the increase may only be
marginal. The options are:
Message Types
Contents
Status
Word
Fault Code
- 90 -
Display
Value
Gemstart 5
Volume 1 Users Guide
Message Types
Contents
Group 10 Status
Status Word
The following status word is provided in every response to the Host.
Table 8 - Gembus Status Word
Bit
Set if Any Trip active (latching or self clearing) (Same as Trip LED)
Set
if
(Same as Alarm LED)
Any
Alarm
is
active
Set
if
(Same as Warn LED)
Any
Warn
is
active
Contactor A State
Contactor B State
10
11
Configurable
defaults to Disabled
12
13
Configurable
defaults to Disabled
14
15
Set if motor available to Host (i.e. no trips, and in auto or priority modes,
and not in test position)
Host
Host
Status
Bit
1,
Status
Bit
2,
Display Value
This is the value which is displayed on the Gemstart LCD. The value does not
include the decimal point. So if Gemstart is displaying 12.34A then value 1234 is
passed on the link.
Fault Code
The Fault Code is represented by two bytes. The least significant byte holds a code
- 91 -
Gemstart 5
Volume 1 Users Guide
defining what the fault is. The most significant byte holds a code for the severity of
the fault (0=warn, 1=alarm, 2=trip, 3=latching trip).
Group 10 Data
The group data items. As configured in Communications section of the Configuration
Editor, Group 10 Word sources.
10.3.4
Group Data
It is possible for the Host to issue a request for a specific group of data from a
specific Gemstart. Gemstart offers 11 different data groups. Each group data
message includes the Long Status Message described above.
If the Group 10 Status message is active, a request for a specific group message will
cause the correct group message to be sent, for 1 scan, in place of the group 10
status message.
Gemstart provides you with data groups 1 to 11. All values are Unsigned 16 bit
numbers unless indicated otherwise.
See section 10.2.5 in the Profibus section for a definition of the Group Data contents.
10.3.5
If no valid messages are received by Gemstart from the Host system within the
timeout period, a Link Fail Trip or Warn is flagged.
Once the link is established the timeout period of each baud rate on the link is:
Baud Rate:
19200
9600
4800
2400
1200
600
Seconds:
2.5
2.5
10
20
20
The baud rate can be forced for any baud rate to be 5, 10 or 20s. See configuration
item Communications/s/Advanced Settings/Fixed Timeout
The auto detect method for Baud (and protocol) selection is as follows:
Gemstart will only try a new baud rate if it is receiving bytes but has not received a
valid message for 1.5s
The 1.5s time starts when the first byte has been received after a timeout. When an
active link times out the baud rate is not changed .
The normal order of events is as follows:
1.
2.
After the timeout time associated with the baud rate, the link fail action will
occur (trip or warn). The baud rate will not change. No further timeouts are possible
until a byte has been received
3.
4.
5.
If a valid message is not received, a timeout is recorded and the baud rate is
changed. The mechanism then goes back to step 3
If data is being continuously transmitted by the Host the unit will spend 1.5s at each
baud rate until it receives a valid message.
- 92 -
Gemstart 5
Volume 1 Users Guide
10.3.6
Gemstart provides you with the following serial link statistics which can be viewed on
the GEMPRO control program:
10.3.7
Link Status
Baud rate
Address
Range
Scan Time
Link Timeouts
CRC Errors
PCM Version
Broadcasts
Command
Gemstart 1
Gembus 1 Host
Gemstart 1 is Cannot
use
fully functional
Gemstart 2 on this
Host due to the
extended
Set
Configuration
message
Gembus 2 Host
GEM80 IOP mode 8
or
FAST I/O 8331-4002
Gemstart 2
Gemstart 3
Gemstart 4/5
Cannot
use
Gemstart 3 on
this Host due to
the
extended
Set
Configuration
message
Cannot
use
Gemstart on this
Host due to the
extended
Set
Configuration
message
- 93 -
Gemstart 5
Volume 1 Users Guide
Host
Gembus
Hosts
ICIS Version 2.x
GE Fanuc PLC
PCM
Gembus
driver
X-Link
Gemstart 1
Gemstart 2
Gemstart 3
Gemstart 4/5
Gembus Host
As above
As above
Gemstart Hosts
deal
with
Group 10 Status Group 10 Status
Gemstart
3s
message is not message is not
correctly. Only
supported
supported
later releases of
Gemstart
3
support
short
status message
Gemstart is fully
functional
Group 10 Status
message
supported from
version F1.
Group 10 Status
message is not
supported
Gemstart cannot be used with a Gemstart 3 Host set to Host Read Only.
If operating on a Gemstart 3 Host, the messages returned by Gemstart to the Host
are identical to those returned from Gemstart 3, refer to Table 11and Table 12.
10.3.8
The cable used for the four-wire serial link should consist of two twisted pairs with an
overall screen, have a maximum capacitance of 180nF/km, and a maximum
resistance of 40 ohms/km. When routing the cables and wiring outside the cubicles
you should ensure that there is a minimum distance of 600mm (2 feet) exists
between the serial link cabling and any electrically dirty wiring. The recommended
cable type is: Belden 9729.
When connecting Gemstart to a Westermo unit the connections go as follows:
Westermo Tx+ connects to Gemstart RxWestermo Tx- connects to Gemstart Rx+
Westermo Rx+ connects to Gemstart TxWestermo Rx- connects to Gemstart Tx+
10.3.9
You must correctly terminate the serial link for communications to be successful. You
achieve correct termination by fitting a 220 ohm, 0.25W resistor across each pair of
Tx and Rx wires on Gemstart located at each end of the serial link.
- 94 -
Gemstart 5
Volume 1 Users Guide
10.4.1
There are some aspects of the Gembus 3 serial link that can be configured for each
Gemstart. These configuration parameters are:
Protocol
Select Gembus . The Modbus options is discussed elsewhere.
Link Fail Action(Communications/Link Fail Action)
Gemstart can take action on a Serial Link failure. The link fail action is taken if the
serial link was controlling Gemstart when the link failed. The options are:
Trip:
Warn:
Off:
2.5s
5s
- 95 -
Gemstart 5
Volume 1 Users Guide
2400
1200 & 600
10s
20s
The Fixed Timeout configuration also allows fixed timeouts of 5s, 10s and 20s. These
options fix the timeout regardless of the baud rate. The timeout time is the time
between valid messages to any address seen on the link. It is NOT related to the link
scan time.
10.4.2
Gembus 3 Commands
Gemstart can be controlled via the contactor command using the codes listed in
Table 10:
Table 10 Gembus 3 contactor command codes
Bits 3-0
Command
Mode
0000
Stop
Auto
0001
Close A
Auto
0010
Close B
Auto
0011
No Action
Auto
0100
Stop
Priority
0101
Auto
0110
Auto
0111
Auto
1000
Stop
Priority
1001
Close A
Priority
1010
Close B
Priority
1011
No Action
Priority
1100
Stop
Priority
1101
Priority
1110
Priority
1111
Priority
Close A and Close B will mean different things to different contactor models (for
example Forward/Reverse, Low/High Speed, Close/Open Value).
When Gemstart is operating as a GP I/O device, bits 3 to 0 are the requested states
for outputs D, C, B, A respectively. There is no priority mode on a GP I/O device.
A close command is edge triggered. I.e. the command is only actioned when it first
appears. If a close command is present and the contactor is not closed then an
Open Required Fault is reported by Gemstart. This fault can be cleared by sending
an open command until the fault clears then send the close command again.
Alternatively close the contactor with the GEMPRO control program.
- 96 -
Gemstart 5
Volume 1 Users Guide
10.4.3
Status Message
Some Gembus 3 Host allows you to define the length of the Status message
Gemstart sends on every scan. The more data sent in the status message by each
Gemstart the longer the scan time. Although on some systems the increase may only
be marginal. The options are:
Message Types
Contents
Status
Standard
Message
Status
Status Gemstart
Word
Gemstart
Value
Load
10.4.4
Bits
Description
0-5
10
11
12
13
14
15
The following tables indicate the fault codes generated by Gemstart 5 when
communicating with a Gemstart 2 or Gemstart 3 Host. The tables show the fault
codes that are generated for each of the 3 severity levels. (Gemstart allows the
severity of most faults to be configured.) The first figure is the code generated when
a fault is defined as a LTrip (Latched Trip) or a self clearing Trip. The second code is
for an Alarm and the third for a Warn. e.g. A Thermal Overload Trip will generate a
fault code of 8. A Thermal Overload Warn will generate a code of 51.
- 97 -
Gemstart 5
Volume 1 Users Guide
FAULT CODE
GEMSTART FAULT
COMMENT
No faults present
01
02, 02, 02
Configuration Conflict
03, 03, 03
Isolator Fault
04, 04, 04
Undefined Fault
05, 05, 63
Earth Fault
06, 06, 06
07, 07, 63
08, 08, 51
09, 09, 36
10, 10, 37
11, 11, 11
Manual Stop
Pressed
12, 12, 12
Interlock fault
13, 13, 13
14, 14, 14
15, 15, 15
16, 16, 16
17
Generated by Host.
Not
Generated
Gemstart 5
by
Invalid
Contactor
Feedback
A Not
Generated
Gemstart 5
by
18
Invalid
Contactor
Feedback
B Not
Generated
Gemstart 5
by
19, 19, 19
Current
Flow
Detected
While Contactor Open
20, 20, 20
21, 21, 21
22, 41, 52
23, 23, 63
24, 42, 53
25, 43, 54
26, 44, 55
27, 27, 27
Restart Inhibit
28, 28, 28
Supply Fail
29, 29, 29
ELCB Fault
- 98 -
or
STOP
Gemstart 5
Volume 1 Users Guide
FAULT CODE
GEMSTART FAULT
COMMENT
31, 38, 48
Imbalance Fault
32
Yellow
trip
33
34, 45, 63
35, 35, 35
09, 09, 36
10, 10, 37
31, 38, 48
Imbalance Fault
39
Yellow
alarm
40
Blue
alarm
22, 41, 52
24, 42, 53
25, 43, 54
26, 44, 55
34, 45, 63
46
Not
Generated
Gemstart 5
by
47
Not
Generated
Gemstart 5
by
31, 38, 48
Imbalance Fault
49
Yellow
warn
Imbalance Not
Generated
Gemstart 5
by
50
by
08, 08, 51
22, 41, 52
24, 42, 53
25, 43, 54
26, 44, 55
- 99 -
Phase
Phase
Phase
Phase
Imbalance Not
Generated
Gemstart 5
by
Not
Generated
Gemstart 5
by
Imbalance Not
Generated
Gemstart 5
by
Imbalance Not
Generated
Gemstart 5
by
or
or
Gemstart 5
Volume 1 Users Guide
FAULT CODE
GEMSTART FAULT
COMMENT
57, 57, 57
58, 58, 58
59
Not Defined
Not
Generated
Gemstart 5
by
60
Not Defined
Not
Generated
Gemstart 5
by
61, 62, 63
Non
Fault
Specific
Description
0-10
11
12
13
14-15
Encoded as:
10.4.5
Gemstart 3 Links
If group data is requested from a Gemstart on a Gemstart 3 Host link, Gemstart will
emulate Gemstart 3 and return the groups shown below.
All values are unsigned 16 bit numbers unless indicated otherwise.
Gemstart 3 Group 1
Field
Current
%FLC)
Description
(%ALC, The percentage current of the highest phase. The
percentage is a ratio of FLC during startup and ALC
at all other times.
- 100 -
Gemstart 5
Volume 1 Users Guide
Field
Description
Power (%Rating)
Gemstart 3 Group 2
Field
Description
Power (%Rating)
Time to Trip / Available The number of seconds before Gemstart will trip
(s)
or become available
Earth Fault
(%EFC)
Power Factor
Gemstart 3 Group 3
Field
Description
Power (%Rating)
Operations
(Hundreds)
of
Operations
(Hundreds)
of
Motor Supply
(%Nominal)
Gemstart 3 Group 4
Field
Description
Power (%Rating)
- 101 -
Gemstart 5
Volume 1 Users Guide
Field
Description
Peak Startup
(%FLC)
Current Maximum
current
achieved
during
last
successful startup as a percentage of FLC.
(Note: A successful start is one with no trip or
stop before the current drops below 100%FLC)
Link Timeouts
CRC Errors
Bits
Field
Description
015
Gemstart
Word
015
See above
015
015
Operations
(Hundreds)
of
015
Operations
(Hundreds)
of
0-7
815
015
0-7
Earth Fault
(%EFC)
815
- 102 -
Gemstart 5
Volume 1 Users Guide
Word
Bits
Field
Description
0-7
Power Factor
815
015
Link Timeouts
10
015
CRC Errors
Bad CRC
Bus
Messages
Events
Broadcasts
Messages
Me
Exceptions
Pressing RESET then LINK while displaying Bus Messages, Event Counter,
Broadcasts, or Slave Messages will reset all 4 statistics.
Pressing RESET then LINK while displaying CRC Errors, Bus Exceptions, or
Timeouts will reset all 3 statistics.
- 103 -
by
Gemstart 5
Volume 1 Users Guide
GS51_DC
Gemstart 5.1 - 24 48 V DC
GS53_AC*
GS53_DC*
Gemstart 5.3 - 24 48 V DC
GS54_AC
GS54_DC
Gemstart 5.4 - 24 48 V DC
GS51/ESD_AC*
GS51/ESD_DC*
GS53/ESD_AC*
GS53/ESD_DC*
GS54/ESD_AC*
GS54/ESD_DC*
* end of life
Optional display modules:
GS5_LED
GS5_LCD
GS5_GEMPRO
CABLE
GS5_RTD
GS5_PAMM
(3 CTS IN 3CT
(2 CTS IN 3CT
Earth Fault CT
GS5_CBCT
- 104 -
Gemstart 5
Volume 1 Users Guide
View its online system measurements such as currents, volts, & power.
Check the status of overload timers, input/output contacts, and last start
information.
Enter and modify all the Gemstarts configuration settings to suit your particular
contactor type and application requirement.
- 105 -
Gemstart 5
Volume 1 Users Guide
- 106 -
Gemstart 5
Volume 1 Users Guide
Wiring : Gemstart5 have different connectors, which caracteristics are:
PHOENIX 1757048 1757158 Body connector: wire section 0,2 to 2,5
mm2 , minimal torque for each screw 0,5 Nm.
PHOENIX 1840324 Body connector : wire section 0,14 to 1,5 mm2 ,
minimal torque for each screw 0,22 Nm.
PHOENIX 1840335 IP Module connector : wire section 0,14 to 1,5 mm2 ,
minimal torque for each screw 0,22 Nm.
PHOENIX 1757080 RTD Module connector : wire section 0,2 to 2,5 mm2 ,
minimal torque for each screw 0,5 Nm.
Please refer to PHOENIX CONTACT technical documentation for connectors
characteristics.
- 107 -
Gemstart 5
Volume 1 Users Guide
- 108 -
Gemstart 5
Volume 1 Users Guide
- 109 -
Gemstart 5
Volume 1 Users Guide
Function
Earth
Control supply -
Control supply +
Motor supply
Pin 1
Motor supply +
(GS5.3 and 5.4 only)
Field I/P 5 -
Field I/P 5 +
Field I/P 6 -
Field I/P 6 +
10
Field I/P 7 -
11
Field I/P 7 +
12
Output 1
13
Output 2
14
Interlock -
15
Interlock +
16
Output 3
17
Output 3
18
Output 4
19
Output 4
20
Input 8/ESD -
21
Input 8/ESD +
L3
L1
Warning! If input 8 is used for the Emergency Shut Down (ESD) option (end of life)
to control output 4, the voltage applied to this input must be limited to 24V dc,
otherwise the output may be damaged.
- 110 -
Gemstart 5
Volume 1 Users Guide
Body Unit - Low Power Connector
Function
Pin No.
22
23
Not connected
24
PTC (GS5.4)
25
PTC + (GS5.4)
26
27
28
29
Chassis I/P 1
30
Chassis I/P 2
31
Chassis I/P 3
32
Chassis I/P 4
33
Pin 22
Chassis
Common
I/P
34
TX/RX - [Profibus A]
35
TX/RX + [Profibus B]
36
RX - (4 wire)
37
RX + (4 wire)
38
Notes:
L3
- 111 -
Gemstart 5
Volume 1 Users Guide
Input unit pin out
Pin No
Function
Earth
Field I/P 9 -
Field I/P 9 +
Field I/P 10 -
Field I/P 10 +
Field I/P 11 -
Field I/P 11 +
Field I/P 12 +
Pin No
Function
10
RTD 1 +
11
RTD 1 -
12
RTD 1 + Sense
13
RTD 2 +
14
RTD 2 -
15
RTD 2 + Sense
16
RTD 3 +
17
RTD 3 -
18
RTD 3 + Sense
19
RTD 4 +
20
RTD 4 -
21
RTD 4 + Sense
22
RTD 5 +
23
RTD 5 -
24
RTD 5 + Sense
25
RTD 6 +
26
RTD 6 -
27
RTD 6 + Sense
Pin 1
Pin 10
- 112 -
Gemstart 5
Volume 1 Users Guide
16 Technical Specifications
16.1 Gemstart 5 Body units
High Voltage units
Power Supply
options
: 110V/240V AC &
Supply Range
: 110V AC -35%
110V DC
24V DC -25%
to 48V DC+25%
110V DC - 15%
to 110V DC +25%
Frequency
: 45-63 Hz & DC
DC
Inrush current
: 8A max.
Supply Interruption
Ride-through
Inputs
Local inputs
nos. 1 to 4
Input voltage
Threshold voltage
Current consumption
24V DC
12V DC
4 mA DC
48V DC
12V DC
8 mA DC
130V DC
65V DC
2.5 mA DC
110 AC
55V AC
4 mA AC
230V AC
55V AC
8 mA AC
- 113 -
Gemstart 5
Volume 1 Users Guide
Outputs
: Rated Current 6A
Rated Voltage 250V AC
Max breaking voltage 440V AC
Max breaking capacity 1500VA
Make current ( max. 4s at duty cycle 10%) = 15A
Phase Current
Measurement method : Integral CTs for 0.5 -30 amps nominal, then in conjunction with
interposing CTs from 30 1000 amps nominal
Accuracy
0.02 A
Accuracy
Range
CBCT rating
Motor Voltage
- 114 -
Gemstart 5
Volume 1 Users Guide
Consumption
0.5VA
Power
Measurement method : V x A
Accuracy
: +/- 5%
Rate
Distance
: 1000m max.
Cable type
Profibus DP V1
Format
: RS485 (2 wire)
Rate
: 1.5Mbits/second
Distance
: 1000m max.
Cable type
: Profibus standard
Connections
High power
connections
wire size
Low power
connections
wire size
Weight
: 500g
IP Rating
: IP20
- 115 -
Gemstart 5
Volume 1 Users Guide
Mechanical
Weight
: 150g
Dimensions
IP Rating
LCD module
Input unit
multi-voltage inputs
no. 9 to12
Power Supply
Connections
High power
connections
wire size
Mechanical
Weight
: 160g
Dimensions
IP Rating
: IP20
- 116 -
Gemstart 5
Volume 1 Users Guide
RTD / Input unit
Inputs
multi-voltage inputs
no. 9 to12
Power Supply
RTD
Measurement method
Accuracy
Connections
Digital input
connections
wire size
RTD connections
Wire size
Mechanical
Weight
: 200g
Dimensions
IP Rating
: IP20
- 117 -
Gemstart 5
Volume 1 Users Guide
16.3 Environmental
16.3.1
EMC
16.3.1.1
Emissions
EN 55011
Conducted Emission
Class A
EN 55011
Radiated emission
Class A
16.3.1.2
Susceptibility
EN61000-4-2
Level 3
EN61000-4-3
Level 3
EN61000-4-4
Level 4
EN61000-4-5
Level 3
EN61000-4-6
Level 3
EN61000-4-8
Level 4
EN61000-4-11
ENV50204
16.3.1.3
IEC 61000-4-16
16.3.2
Vibration
1.0g
Climatic
-5C to + 60C
Operating
-40C to + 85C
Storage
IEC 68-2-3
16.3.4
Level 4
Mechanical
16.3.3
Level 3
5 to 95 % RH
UL94 V0
IEC 60695-2-10 and IEC 60695-2-11
- 118 -
650C