Installation calculation report

LVTN-original
Full

Page 2/142

Project information
Name :
Place :
Customer name:
Revision :

Project: LVTN-original

THIET KE CUNG CAP DIEN CHO CHUNG


CU 17 TANG
-

04/02/2015

Page 3/142

Content

Project description.................................................................................................................. 4
1.1

Project general settings................................................................................................................... 4

1.2

Settings for wiring device calculation............................................................................................ 4

1.3

List of loads...................................................................................................................................... 4

Installation general design.....................................................................................................6


2.1

List of devices.................................................................................................................................. 6

Calculation notes.................................................................................................................. 14
3.1

Source circuits............................................................................................................................... 14

3.2

Generator circuits.......................................................................................................................... 23

3.3

LV Source circuits.......................................................................................................................... 23

3.4

UPS circuits.................................................................................................................................... 24

3.5

Surge Arrester circuits................................................................................................................... 24

3.6

Capacitor bank circuits.................................................................................................................. 24

3.7

Feeder circuits................................................................................................................................ 24

3.8

LV Transformer circuits................................................................................................................. 25

3.9

Couplers circuits............................................................................................................................ 27

3.10

Generic load circuits................................................................................................................. 27

3.11

Lighting load circuits................................................................................................................ 27

3.12

Power socket load circuits....................................................................................................... 28

3.13

Motor starter combination........................................................................................................ 28

3.14

Busbar circuits.......................................................................................................................... 29

3.15

Busbar trunking system circuits............................................................................................. 29

3.16

Busbar trunking system circuits............................................................................................. 29

3.17

Lighting Busbar trunking system circuits..............................................................................29

Project: LVTN-original

04/02/2015

Page 4/142

1 Project description
1.1 Project general settings
Installation standard

IEC60364

Calculation standard
Circuit breaker standard
Frequency

TR50480
IEC 60947-2
50 Hz

1.2 Settings for wiring device calculation


Maximal CSA

630 mm

1.3 List of loads


Name
CS
TANGH
AM
TTM
PT
THONG
GIO
CSNT
CSCC
TANG
TRET
CSCC
TANG 2
CSCC
TANG 313
CSCC
TANG
14
CSCC
TANG15
CSCC
TANG16
CS
TANG
THUON
G
TDT2
TDT3
TDT4
TDT5
TDT6
TDT7
TDT8
TDT9
TDT10
TDT11
TDT12
TDT13
TDT14
TDT15

1.3.1 Generic loads


Sr (kVA)
Pr (kW) Ir (A)
7.02
5.9
10.1

Cos
0.84

Nbr
1

Polarity
3Ph+N

Non linear load THDi 3 (%)


No
0

38.7
31.3

33.3
25.1

55.8
45.2

0.86
0.8

1
1

3Ph+N
3Ph+N

No
No

0
0

1.22
9.2

1.16
8

1.76
13.3

0.95
0.87

1
1

3Ph+N
3Ph+N

No
No

0
0

1.15

0.989

1.66

0.86

3Ph+N

No

1.15

0.989

1.66

0.86

11

3Ph+N

No

1.42

1.25

2.05

0.88

3Ph+N

No

1.7

1.52

2.46

0.89

3Ph+N

No

0.66

0.594

2.86

0.9

1Ph+N

No

0.208

0.197

0.3

0.95

3Ph+N

No

41.7
41.7
41.7
41.7
41.7
41.7
41.7
41.7
41.7
41.7
41.7
41.7
20.9
20.9

35
35
35
35
35
35
35
35
35
35
35
35
17.7
17.7

60.2
60.2
60.2
60.2
60.2
60.2
60.2
60.2
60.2
60.2
60.2
60.2
30.1
30.1

0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.85
0.85

1
1
1
1
1
1
1
1
1
1
1
1
1
1

3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N

No
No
No
No
No
No
No
No
No
No
No
No
No
No

0
0
0
0
0
0
0
0
0
0
0
0
0
0

Project: LVTN-original

04/02/2015

Page 5/142

TDT16

6.93

Name
BNSH
BNT
BNCC

1.3.2 Motor loads


Sr (kVA)
Pr (kW) Ir (A)
27.7
23.8
40
7.97
6.61
11.5
27.7
23.8
40

Project: LVTN-original

5.82

10

0.84

3Ph+N

No

Cos
0.86
0.83
0.86

Nbr
1
1
1

Polarity
3Ph
3Ph
3Ph

Non linear load


No
No
No

THDi 3 (%)
0
0
0

04/02/2015

Page 6/142

2 Installation general design


2.1 List of devices
Name

2.1.1 MV/LV transformer


Nbr Range
Insulation

MBA

Name

Trihal

Dry-type

Sr (kVA)

ukrT (%) Connection U2 (V) SEA

500

2.1.2 LV backup generator


Nbr Sr (kVA)
xd (%)

G 100

250

20

TU PPC
TU MAY PHAT
TU BOM NUOC
TU BAO VE
TPP 234
TPP 567
TPP 890
TPP 11.13
TPP 14.16
WC 101

Name

2.1.4
Nbr

CB-TPPC

CB-TMP

CB-TBN

CB-BNSH

CB-BNT

Project: LVTN-original

Switchboard
name
TPPC
TU MAY PHAT
TU BOM NUOC
TU BAO VE
TPP 234
TPP 567
TPP 890
TPP 11.13
TPP 14.16
UC 102
Circuit breaker
Range Rating (A)
Designation
Masterpact 800
NT - NT08H1
Compact
160
NSX NSX160B
Compact
160
NG160 NG160E
Compact
100
NSX NSX100F
Acti9 P25M - 14
P25M

TN-S

xd (%)

x0 (%)

U (V)

SEA

30

400

TN-S

2.1.3 LV switchboards and busbar


Switchboard name
Range
TPPC
No preference
TU MAY PHAT
No preference
TU BOM NUOC
No preference
TPP 234
No preference
TU BAO VE
No preference
TPP 567
No preference
TPP 890
No preference
TPP 11.13
No preference
TPP 14.16
No preference
UC 102
No preference
Busbar name

420

Rating (A)
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Rb
(m)
10000

Rb
(m)
10000

IP
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined

Ks

Polarity

SEA

Equipotential bounding

1
1
1
1
1
1
1
1
1
1

3Ph+N
3Ph+N
3Ph
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N

TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S
TN-S

With
Without
Without
Without
Without
Without
Without
Without
Without
With

Poles

Trip unit/Curve

4P4d

Micrologic 5.0 E

4P4d

Micrologic 2.2

3P3d

TM-D

3P3d

MA

3P3d

M
04/02/2015

Page 7/142

CB-BNCC

CB-CS HAM 1
CB-TTM

CB-PT
1
THONG GIO
CB-CSNT
1
CB-TBV

CB-CSCC
TANG TRET
CB-CSCC
TANG2
CB-CSCC
TANG 3-13
CB-CSCC
TANG14
CB-CSCC
ATNG15
CB-CSCC
TANG16
CB-CS TANG
THUONG
CB-TPP

CB-TPP234

CB-TDT2

CB-TDT3

CB-TDT4

CB-TPP567

CB-TDT5

CB-TDT6

CB-TDT7

1
11
1
1
1
1
1

CB-TPP 890 1
CB-TDT8

CB-TDT9

CB-TDT10

CB-TPP
11.13

Project: LVTN-original

Compact
NSX NSX100F
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Compact
NG160 NG160E
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Compact
NSX NSX630F
Compact
NSX NSX250B
Acti9 iC60a iC60a
Acti9 iC60a iC60a
Acti9 iC60a iC60a
Compact
NSX NSX250B
Acti9 iC60a iC60a
Acti9 iC60a iC60a
Acti9 iC60a iC60a
Compact
NSX NSX250B
Acti9 iC60a iC60a
Acti9 iC60a iC60a
Acti9 iC60a iC60a
Compact
NSX NSX250B

100

3P3d

MA

13

4P4d

63

4P4d

50

4P4d

4P4d

160

4P4d

TM-D

16

4P4d

4P4d

4P4d

4P4d

4P4d

2P1d

0.5

4P4d

630

4P4d

Micrologic 2.3

250

4P4d

Micrologic 2.2

63

4P4d

63

4P4d

63

4P4d

250

4P4d

Micrologic 2.2

63

4P4d

63

4P4d

63

4P4d

250

4P4d

Micrologic 2.2

63

4P4d

63

4P4d

63

4P4d

250

4P4d

Micrologic 2.2

04/02/2015

Page 8/142

CB-TDT11

CB-TDT12

CB-TDT13

CBTPP14.16

CB-TDT14

CB-TDT15

CB-TDT16

CB-TU BU

CB-MPDP

Name
TPP

Acti9 iC60a iC60a


Acti9 iC60a iC60a
Acti9 iC60a iC60a
Compact
NSX NSX100B
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Acti9 iC60 iC60N
Compact
NSX NSX250B
Compact
NSX NSX400F

63

4P4d

63

4P4d

63

4P4d

100

4P4d

Micrologic 2.2

32

4P4d

32

4P4d

10

4P4d

250

3P3d

Micrologic 2.2

400

4P4d

Micrologic 5.3 A

2.1.5 Power distribution busbar trunking system


Incomer
Nb of Feeder
L (m)
Range
TPPC-TPP 5
10
KTC

2.1.6 Cable schedule


Name Nbr Incomer Feeder Type
TBV- 1
CB-CS CS
Multi-core
CS
TANG
TANG
TANG
THUON THUON
THUO
G
G
NG
TBV- 1
CB-TTM TTM
Multi-core
TTM
TBV- 1
CBCSCC Multi-core
CSCC
CSCC TANG16
TANG1
TANG16
6
TBV- 1
CBCSCC Multi-core
CSCC
CSCC TANG15
TANG1
ATNG15
5
TBV- 1
CBCSCC Multi-core
CSCC
CSCC TANG
TANG1
TANG14 14
4
TBV- 11 CBCSCC Multi-core
CSCC
CSCC TANG 3TANG
TANG 3- 13
3-13
13
TBV- 1
CBCSCC Multi-core
CSCC
CSCC TANG 2
TANG2
TANG2
TMP- 1
CB-TBV TU BAO Multi-core
TBV
VE
TBV- 1
CBCSNT
Multi-core
CSNT
CSNT
TBV- 1
CBCSCC Multi-core
Project: LVTN-original

Rating (A)
1000

Insulation L (m)
PVC
80

L1/L2/L3
1x1.5
Copper

N
1x1.5
Copper

PE/PEN
1x4 Copper

XLPE

80

PVC

75

1x10
Copper
1x1.5
Copper

1x10
Copper
1x1.5
Copper

1x10
Copper
1x4 Copper

PVC

70

1x1.5
Copper

1x1.5
Copper

1x4 Copper

PVC

65

1x1.5
Copper

1x1.5
Copper

1x4 Copper

PVC

35

1x1.5
Copper

1x1.5
Copper

1x4 Copper

PVC

30

1x1.5
Copper

1x1.5
Copper

1x4 Copper

XLPE

30

XLPE

30
25

1x16
Copper
1x1.5
Copper
1x1.5

1x16
Copper
1x4 Copper

PVC

1x16
Copper
1x1.5
Copper
1x1.5

1x4 Copper
04/02/2015

Page 9/142

CSCC
TANG
TRET
TPPC- 1
TU BU
TPP- 1
TDT16
TPP- 1
TDT15
TPP- 1
TDT14
TPP- 1
TPP
14.16
TPP11. 1
13TDT13
TPP11. 1
13TDT12
TPP11. 1
13TDT11
TPP- 1
TPP
11.13
TPP8. 1
10TDT10
TPP8. 1
10TDT9
TPP8. 1
10TDT8
TPP- 1
TPP
890
TPP56 1
7TDT7
TPP56 1
7TDT6
TPP56 1
7TDT5
TPP- 1
TPP
567
TPP23 1
4TDT4
TPP23 1
4TDT3
TPP23 1
4TDT2
TPP- 1
TPP23
4

CSCC
TANG
TRET
CB-TU
BU
CBTDT16
CBTDT15
CBTDT14
CBTPP14.1
6
CBTDT13

TANG
TRET

Copper

Copper

TU BU

Single-core

XLPE

20

TDT16

Multi-core

PVC

20

TDT15

Multi-core

PVC

20

1x70
Copper
1x1.5
1x1.5
Copper
Copper
1x4 Copper 1x4 Copper

TDT14

Multi-core

PVC

20

1x4 Copper 1x4 Copper 1x4 Copper

TPP
14.16

Multi-core

XLPE

20

1x10
Copper

1x10
Copper

1x10
Copper

TDT13

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT12

TDT12

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT11

TDT11

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CB-TPP TPP
11.13
11.13

Multi-core

XLPE

20

1x50
Copper

1x50
Copper

1x25
Copper

CBTDT10

TDT10

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT9

TDT9

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT8

TDT8

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CB-TPP TPP 890 Multi-core


890

XLPE

20

1x50
Copper

1x50
Copper

1x25
Copper

CBTDT7

TDT7

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT6

TDT6

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT5

TDT5

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTPP 567 Multi-core


TPP567

XLPE

20

1x50
Copper

1x50
Copper

1x25
Copper

CBTDT4

TDT4

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT3

TDT3

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

CBTDT2

TDT2

Multi-core

PVC

20

1x16
Copper

1x16
Copper

1x16
Copper

XLPE

20

1x50
Copper

1x50
Copper

1x25
Copper

CBTPP 234 Multi-core


TPP234

Project: LVTN-original

1x35
Copper
1x4 Copper
1x4 Copper

04/02/2015

Page 10/142

TPPCTPP
TBVPT
THON
G GIO
TBVCS
HAM
TMPTBN
TPPCTMP
MBATPPC
TBNBNCC
TBNBNT
TBNBNSH
WD
100

CB-TPP TPP

1
1
1
1
1
1
1
1

Single-core

XLPE

20

CB-PT PT
Multi-core
THONG THONG
GIO
GIO

PVC

20

CB-CS
HAM

1x240
Copper
1x10
Copper

1x240
Copper
1x10
Copper

1x120
Copper
1x10
Copper

1x1.5
Copper

1x4 Copper

CS
TANGH
AM
CB-TBN TU BOM
NUOC
CB-TMP TU MAY
PHAT
MBA
CBTPPC
CBBNCC
BNCC
CB-BNT BNT

Multi-core

PVC

20

1x1.5
Copper

Multi-core

XLPE

20

Single-core

XLPE

20

Single-core

XLPE

20

Multi-core

XLPE

10

Multi-core

XLPE

10

CBBNSH
G 100

Multi-core

XLPE

10

QA 100 Multi-core

XLPE

1x16
Copper
1x35
Copper
1x400
Copper
1x10
Copper
1x1.5
Copper
1x10
Copper
1x150
Copper

BNSH

2.1.7 MV Cable
Name Nbr Designation CSA (mm) Icc (A)
MVWD 1
NA
1 x 185 Cu 25.7
0

Project: LVTN-original

In (A)
459

1x35
Copper
1x400
Copper

1x150
Copper

1x16
Copper
1x16
Copper
1x240
Copper
1x10
Copper
1x4 Copper
1x10
Copper
1x95
Copper

Un (kV)
24

04/02/2015

Page 11/142

3 Calculation notes
3.1 Source circuits
3.1.1 Circuit DIEN LUOI 15 KV
MV power supply
W0
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable
MVWD 0
Parameters
Length
20 m
Type of cable
Single core
Ib
19 A
Nb of conductor per phase
1
Cross section area
1 x 185 Cu mm
Core
Copper
Short circuit withstand
25.7 kA
Assigned voltage
15 kV
Insulation voltage
24 kV
MV/LV transformer
Range
Technology
Rated power
ukrT
Type of losses
PkrT
System earthing arrangement
MV Connection
LV Connection
No load secondary voltage Ur0
Ur LV
Rb (neutral grounding)
Ra (mass grounding)
Sizing information
Cable
Parameters
Length
Max length
Installation method

MBA
Trihal
Dry-type
500 kVA
6%
Normal
5.7 kW
TN-S
D
yn
420V
400V
NA
NA
UkrT and PkrT calculated by system
MBA-TPPC

20 m
NA
31
F
Single-core cables on horizontal
perforated tray
Type of cable
Single-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
722 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1

Project: LVTN-original

04/02/2015

Page 12/142

A-52-14
1
A-52-16
1
D-52-1
0.98
A-52-21
1
0.98

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x400 mm
Copper
851 A
1x400 mm
Copper
851 A
1x240 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 11.80
10.22

11.80

7.94

8.42

9.16 0.00

Operating mode Su co MBA


(kA) 11.80
10.22
11.80

7.94

8.42

9.16 0.00

Synthesis for all operating mode


(kA) 11.80
10.22
11.80

7.94

8.42

9.16 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
Ib
Distance from origin

CB-TPPC
722 A
NA

Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr

Sized by system
Masterpact NT
NT08H1
800 A
42 kA
NA
NA
NA
4P4d
Micrologic 5.0 E
800 A

Project: LVTN-original

736 (Setting: 0.92) A


24 s
04/02/2015

Page 13/142

Short delay settings


Isd current
Tsd
Instantaneous tripping
Ii current

5888 (Setting: 8) A
0.08 s
9600 (Setting: 12) A

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Operating mode Su co MBA


NA

Design current
IL1

Discrimination can't be determinated : no


upstream Lv Breaker

IL2

IL3

IN

Operating mode Normal


(A)
638.833
638.833

640.223

1.39

Operating mode Su co MBA


(A)
570.672
570.672

570.672

Synthesis for all operating mode


(A)
638.833
638.833
640.223
Voltage drop
Cumulated from upstream

1.39
Circuit

Operating mode Normal


0.615
U3L (%)
0.710
UL1L2 (%)
0.710
UL2L3 (%)
0.710
UL3L1 (%)
0.615
UL1N (%)
0.615
UL2N (%)
0.615
UL3N (%)

0.615
0.710
0.710
0.710
0.615
0.615
0.615

Operating mode Su co MBA


0.616
U3L (%)
0.711
UL1L2 (%)
0.711
UL2L3 (%)
0.711
UL3L1 (%)
0.616
UL1N (%)
0.616
UL2N (%)
0.616
UL3N (%)

0.616
0.711
0.711
0.711
0.616
0.616
0.616

Project: LVTN-original

04/02/2015

Page 14/142

3.2 Generator circuits


3.2.1 Circuit Source 100
LV generator
G 100
Rated power
250 kVA
Subtransient reactance xd
20 %
Transient reactance xd
30 %
Zero sequence reactance x0
6%
System earthing arrangement
TN-S
Ur
400 V
Rb (neutral grounding)
NA
Ra (mass grounding)
NA
Cable
WD 100
Parameters
Length
5m
Max length
NA
Installation method
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
361 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x150 mm
Copper
399 A
1x150 mm
Copper
399 A
1x95 mm
Copper

Short circuit current


Project: LVTN-original

04/02/2015

Page 15/142

Ik3max

Ik2max

Ik1max

Ik2min

Ik1min

Ief

1.80

0.99

1.55

1.55 0.00

Operating mode Su co MBA


(kA) 1.98
1.72
1.80

0.99

1.55

1.55 0.00

Synthesis for all operating mode


(kA) 1.98
1.72
1.80

0.99

1.55

1.55 0.00

Operating mode Normal


(kA) 1.98
1.72

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
Ib
Distance from origin

QA 100
361 A
NA

Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX400F
400 A
36 kA
NA
NA
NA
4P4d
Micrologic 5.3 A
400 A

Discrimination Results
UpStream

361 A
16 s
1083 A
0s
1800 A
Discrimination Limit

Operating mode Normal


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Operating mode Su co MBA


NA

Design current
IL1

Discrimination can't be determinated : no


upstream Lv Breaker

IL2

Operating mode Normal


(A)
0.000
0.000
Project: LVTN-original

IL3
0.000

IN
0
04/02/2015

Page 16/142

Operating mode Su co MBA


(A)
139.143
139.143

140.687

Synthesis for all operating mode


(A)
139.143
139.143
140.687
Voltage drop
Cumulated from upstream

1.54

1.54
Circuit

Operating mode Normal


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Operating mode Su co MBA


0.138
U3L (%)
0.159
UL1L2 (%)
0.159
UL2L3 (%)
0.159
UL3L1 (%)
0.138
UL1N (%)
0.138
UL2N (%)
0.138
UL3N (%)

0.138
0.159
0.159
0.159
0.138
0.138
0.138

Project: LVTN-original

04/02/2015

Page 17/142

3.3 Capacitor bank circuits


3.3.1 Circuit TU BU
Circuit breaker
CB-TU BU
Ib
178 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
NA
3P3d
Micrologic 2.2
250 A
242 A
16 s
2425 A
0.02 s
3000 A
Discrimination Limit

Operating mode Normal


CB-TPPC
NT08H1
Micrologic 5.0 E
800 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPPC
NT08H1
Micrologic 5.0 E
800 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPPC-TU BU

Type of cable
Project: LVTN-original

20 m
61.1 m
31
F
Single-core cables on horizontal
perforated tray
Single-core
04/02/2015

Page 18/142

Nb of additional touching circuits


Insulation
Ambient temperature
Level of third harmonic THDI
Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

0
XLPE
30 C
0%
178 A
Iz
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
0.98
A-52-21
1
0.98

1x70 mm
Copper
273 A
1x35 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Ief2min

Operating mode Normal


(kA) 10.82
9.37

0.00

NA

NA

NA

NA

Operating mode Su co MBA


(kA) 10.82
9.37
0.00

NA

NA

NA

NA

Synthesis for all operating mode


(kA) 10.82
9.37
0.00

0.00

0.00

0.00 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
LV capacitor bank
Target P.F.
Downstream reactive power to
correct
Upstream reactive power to
correct
Range of the capacitor bank
Qr of the capacitor bank
Step
Accord
U
Frequency
Project: LVTN-original

TU BU
0.95
116 kvar
7.5 kvar
N/A
123 kvar
N/A
N/A
400 V
0 Hz
04/02/2015

Page 19/142

Pollution Gh/Sn
Type of correction
P.F. after correction
Design current
IL1

0%
None
0.000
IL2

IL3

IN

Operating mode Normal


(A)
178.142
178.142

178.142

Operating mode Su co MBA


(A)
178.142
178.142

178.142

Synthesis for all operating mode


(A)
178.142
178.142

178.142

Project: LVTN-original

04/02/2015

Page 20/142

Voltage drop
Cumulated from upstream

Circuit

Operating mode Normal


0.754
U3L (%)
0.870
UL1L2 (%)
0.870
UL2L3 (%)
0.870
UL3L1 (%)
0.615
UL1N (%)
0.615
UL2N (%)
0.615
UL3N (%)

0.139
0.160
0.160
0.160
0.000
0.000
0.000

Operating mode Su co MBA


0.755
U3L (%)
0.871
UL1L2 (%)
0.871
UL2L3 (%)
0.871
UL3L1 (%)
0.616
UL1N (%)
0.616
UL2N (%)
0.616
UL3N (%)

0.139
0.160
0.160
0.160
0.000
0.000
0.000

3.4 Feeder circuits


3.4.1 Circuit TPPC-TMP
Circuit breaker
CB-TMP
Ib
141 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX160B
160 A
25 kA
NA
NA
NA
4P4d
Micrologic 2.2
160 A
141 A
16 s
1410 A
0.02 s
2400 A
Discrimination Limit

Operating mode Normal


CB-TPPC
NT08H1
Micrologic 5.0 E
Project: LVTN-original

Full Discrimination

04/02/2015

Page 21/142

800 A / 4P4d
Operating mode Su co MBA
NA

Discrimination can't be determinated : no


upstream Lv Breaker

Cable
Parameters
Length
Max length
Installation method

TPPC-TMP

20 m
NA
31
F
Single-core cables on horizontal
perforated tray
Type of cable
Single-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
141 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
0.98
Standard table reference
A-52-21
User correction factor
1
Overall factor
0.98
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x35 mm
Copper
172 A
1x35 mm
Copper
172 A
1x16 mm
Copper

Short circuit current


Project: LVTN-original

04/02/2015

Page 22/142

Ik3max

Ik2max

Ik1max

Ik2min

Ik1min

Ief

9.99

6.06

4.97

3.96 0.00

Operating mode Su co MBA


(kA) NA
NA
NA

NA

NA

NA

Synthesis for all operating mode


(kA) 10.82
9.37
9.99

6.06

4.97

3.96 0.00

Operating mode Normal


(kA) 10.82
9.37

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
139.143
139.143

140.687

1.54

Operating mode Su co MBA


(A)
139.143
139.143

140.687

1.54

Synthesis for all operating mode


(A)
139.143
139.143
140.687
Voltage drop
Cumulated from upstream

1.54
Circuit

Operating mode Normal


1.374
U3L (%)
1.576
UL1L2 (%)
1.581
UL2L3 (%)
1.581
UL3L1 (%)
1.374
UL1N (%)
1.374
UL2N (%)
1.383
UL3N (%)

0.759
0.866
0.871
0.871
0.759
0.759
0.768

Operating mode Su co MBA


1.375
U3L (%)
1.577
UL1L2 (%)
1.583
UL2L3 (%)
1.583
UL3L1 (%)
1.375
UL1N (%)
1.375
UL2N (%)
1.384
UL3N (%)

0.759
0.866
0.871
0.871
0.759
0.759
0.768

Project: LVTN-original

04/02/2015

Page 23/142

3.4.2 Circuit TMP-TBN


Circuit breaker
CB-TBN
Ib
64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NG160
NG160E
160 A
16 kA
NA
NA
25 kA
3P3d
TM-D
80 A
80 A
NA
800 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TMP
NSX160B
Micrologic 2.2
160 A / 4P4d

2400 A

Operating mode Su co MBA


QA 103
NSX160B
Micrologic 2.2
160 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TMP-TBN

20 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 24/142

0%
64 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
100 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.69
7.53

0.00

3.44

0.00

1.96 0.00

Operating mode Su co MBA


(kA) 1.97
1.71
0.00

0.96

0.00

1.36 0.00

Synthesis for all operating mode


(kA) 8.69
7.53
0.00

0.96

0.00

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
64.050
64.050

64.050

Operating mode Su co MBA


(A)
64.050
64.050

64.050

Synthesis for all operating mode


(A)
64.050
64.050
64.050
Voltage drop
Cumulated from upstream
Project: LVTN-original

0
Circuit
04/02/2015

Page 25/142

Operating mode Normal


2.100
U3L (%)
2.415
UL1L2 (%)
2.420
UL2L3 (%)
2.420
UL3L1 (%)
1.374
UL1N (%)
1.374
UL2N (%)
1.383
UL3N (%)

0.726
0.839
0.839
0.839
0.000
0.000
0.000

Operating mode Su co MBA


2.101
U3L (%)
2.416
UL1L2 (%)
2.421
UL2L3 (%)
2.421
UL3L1 (%)
1.375
UL1N (%)
1.375
UL2N (%)
1.384
UL3N (%)

0.726
0.839
0.839
0.839
0.000
0.000
0.000

Project: LVTN-original

04/02/2015

Page 26/142

3.4.3 Circuit TMP-TBV


Circuit breaker
CB-TBV
Ib
92.3 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NG160
NG160E
160 A
16 kA
NA
NA
25 kA
4P4d
TM-D
100 A
100 A
NA
1000 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TMP
NSX160B
Micrologic 2.2
160 A / 4P4d

2400 A

Operating mode Su co MBA


QA 103
NSX160B
Micrologic 2.2
160 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TMP-TBV

30 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 27/142

0%
92 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
100 A
1x16 mm
Copper
100 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.69
7.53

6.48

2.76

1.73

1.56 0.00

Operating mode Su co MBA


(kA) 1.97
1.71
1.78

0.94

1.24

1.23 0.00

Synthesis for all operating mode


(kA) 8.69
7.53
6.48

0.94

1.24

1.23 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
90.553
90.553

92.269

1.72

Operating mode Su co MBA


(A)
90.553
90.553

92.269

1.72

Project: LVTN-original

04/02/2015

Page 28/142

Synthesis for all operating mode


(A)
90.553
90.553
92.269
Voltage drop
Cumulated from upstream

1.72
Circuit

Operating mode Normal


2.927
U3L (%)
3.334
UL1L2 (%)
3.357
UL2L3 (%)
3.357
UL3L1 (%)
2.927
UL1N (%)
2.927
UL2N (%)
2.966
UL3N (%)

1.553
1.758
1.776
1.776
1.553
1.553
1.583

Operating mode Su co MBA


2.928
U3L (%)
3.335
UL1L2 (%)
3.358
UL2L3 (%)
3.358
UL3L1 (%)
2.928
UL1N (%)
2.928
UL2N (%)
2.967
UL3N (%)

1.553
1.758
1.776
1.776
1.553
1.553
1.583

Project: LVTN-original

04/02/2015

Page 29/142

3.4.4 Circuit Feeder circuit 103


Circuit breaker
QA 103
Ib
141 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX160B
160 A
25 kA
NA
NA
NA
4P4d
Micrologic 2.2
160 A
141 A
16 s
1128 A
0.02 s
2400 A
Discrimination Limit

Operating mode Normal


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Operating mode Su co MBA


QA 100
NSX400F
Micrologic 5.3 A
400 A / 4P4d

969 A

Cable
Parameters
Length
Max length
Installation method

WD 103

5m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
141 A

Project: LVTN-original

04/02/2015

Page 30/142

Iz
Sized with Ir

Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x35 mm
Copper
158 A
1x35 mm
Copper
158 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Ief2min

Operating mode Normal


(kA) NA
NA

NA

NA

NA

NA

NA

Operating mode Su co MBA


(kA) 1.98
1.71
1.79

0.99

1.54

1.54 0.00

Synthesis for all operating mode


(kA) 1.98
1.71
1.79

0.99

1.54

1.54 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
139.143
139.143

140.687

1.54

Operating mode Su co MBA


(A)
139.143
139.143

140.687

1.54

140.687

1.54

Synthesis for all operating mode


(A)
139.143
139.143
Voltage drop
Project: LVTN-original

04/02/2015

Page 31/142

Cumulated from upstream

Circuit

Operating mode Normal


0.188
U3L (%)
0.215
UL1L2 (%)
0.216
UL2L3 (%)
0.216
UL3L1 (%)
0.188
UL1N (%)
0.188
UL2N (%)
0.190
UL3N (%)

0.188
0.215
0.216
0.216
0.188
0.188
0.190

Operating mode Su co MBA


0.326
U3L (%)
0.374
UL1L2 (%)
0.375
UL2L3 (%)
0.375
UL3L1 (%)
0.326
UL1N (%)
0.326
UL2N (%)
0.328
UL3N (%)

0.188
0.215
0.216
0.216
0.188
0.188
0.190

Project: LVTN-original

04/02/2015

Page 32/142

3.4.5 Circuit TPPC-TPP


Circuit breaker
CB-TPP
Ib
571 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX630F
630 A
36 kA
NA
NA
NA
4P4d
Micrologic 2.3
630 A
580 A
16 s
5796 A
0.02 s
6900 A
Discrimination Limit

Operating mode Normal


CB-TPPC
NT08H1
Micrologic 5.0 E
800 A / 4P4d

5291 A

Operating mode Su co MBA


CB-TPPC
NT08H1
Micrologic 5.0 E
800 A / 4P4d

5291 A

Cable
Parameters
Length
Max length
Installation method

TPPC-TPP

20 m
NA
31
F
Single-core cables on horizontal
perforated tray
Type of cable
Single-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 33/142

0%
571 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
0.98
A-52-21
1
0.98

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x240 mm
Copper
621 A
1x240 mm
Copper
621 A
1x120 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.82
9.37

9.99

7.28

7.19

7.53 0.00

Operating mode Su co MBA


(kA) 10.82
9.37
9.99

7.28

7.19

7.53 0.00

Synthesis for all operating mode


(kA) 10.82
9.37
9.99

7.28

7.19

7.53 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
570.672
570.672

570.672

Operating mode Su co MBA


(A)
570.672
570.672

570.672

Project: LVTN-original

04/02/2015

Page 34/142

Synthesis for all operating mode


(A)
570.672
570.672
570.672
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.266
U3L (%)
1.462
UL1L2 (%)
1.462
UL2L3 (%)
1.462
UL3L1 (%)
1.266
UL1N (%)
1.266
UL2N (%)
1.266
UL3N (%)

0.651
0.752
0.752
0.752
0.651
0.651
0.651

Operating mode Su co MBA


1.267
U3L (%)
1.463
UL1L2 (%)
1.463
UL2L3 (%)
1.463
UL3L1 (%)
1.267
UL1N (%)
1.267
UL2N (%)
1.267
UL3N (%)

0.651
0.752
0.752
0.752
0.651
0.651
0.651

Project: LVTN-original

04/02/2015

Page 35/142

3.4.6 Circuit TPP-TPP 234


Circuit breaker
CB-TPP234
Ib
163 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
36 kA
4P4d
Micrologic 2.2
250 A
163 A
16 s
1628 A
0.02 s
3000 A
Discrimination Limit

Operating mode Normal


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TPP234

20 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 36/142

0%
163 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x50 mm
Copper
192 A
1x50 mm
Copper
192 A
1x25 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.93
8.60

8.55

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
162.540
162.540

162.540

Operating mode Su co MBA


(A)
162.540
162.540

162.540

Project: LVTN-original

04/02/2015

Page 37/142

Synthesis for all operating mode


(A)
162.540
162.540
162.540
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.967
U3L (%)
2.271
UL1L2 (%)
2.271
UL2L3 (%)
2.271
UL3L1 (%)
2.058
UL1N (%)
2.058
UL2N (%)
2.058
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Operating mode Su co MBA


1.967
U3L (%)
2.272
UL1L2 (%)
2.272
UL2L3 (%)
2.272
UL3L1 (%)
2.059
UL1N (%)
2.059
UL2N (%)
2.059
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Project: LVTN-original

04/02/2015

Page 38/142

3.4.7 Circuit TPP-TPP 567


Circuit breaker
CB-TPP567
Ib
163 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
36 kA
4P4d
Micrologic 2.2
250 A
163 A
16 s
1628 A
0.02 s
3000 A
Discrimination Limit

Operating mode Normal


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TPP 567

20 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 39/142

0%
163 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x50 mm
Copper
192 A
1x50 mm
Copper
192 A
1x25 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.93
8.60

8.55

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
162.540
162.540

162.540

Operating mode Su co MBA


(A)
162.540
162.540

162.540

Project: LVTN-original

04/02/2015

Page 40/142

Synthesis for all operating mode


(A)
162.540
162.540
162.540
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.967
U3L (%)
2.271
UL1L2 (%)
2.271
UL2L3 (%)
2.271
UL3L1 (%)
2.058
UL1N (%)
2.058
UL2N (%)
2.058
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Operating mode Su co MBA


1.967
U3L (%)
2.272
UL1L2 (%)
2.272
UL2L3 (%)
2.272
UL3L1 (%)
2.059
UL1N (%)
2.059
UL2N (%)
2.059
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Project: LVTN-original

04/02/2015

Page 41/142

3.4.8 Circuit TPP-TPP11.13


Circuit breaker
CB-TPP 890
Ib
163 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
36 kA
4P4d
Micrologic 2.2
250 A
163 A
16 s
1628 A
0.02 s
3000 A
Discrimination Limit

Operating mode Normal


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TPP 890

20 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 42/142

0%
163 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x50 mm
Copper
192 A
1x50 mm
Copper
192 A
1x25 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.93
8.60

8.55

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
162.540
162.540

162.540

Operating mode Su co MBA


(A)
162.540
162.540

162.540

Project: LVTN-original

04/02/2015

Page 43/142

Synthesis for all operating mode


(A)
162.540
162.540
162.540
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.967
U3L (%)
2.271
UL1L2 (%)
2.271
UL2L3 (%)
2.271
UL3L1 (%)
2.058
UL1N (%)
2.058
UL2N (%)
2.058
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Operating mode Su co MBA


1.967
U3L (%)
2.272
UL1L2 (%)
2.272
UL2L3 (%)
2.272
UL3L1 (%)
2.059
UL1N (%)
2.059
UL2N (%)
2.059
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Project: LVTN-original

04/02/2015

Page 44/142

3.4.9 Circuit TPP-TPP 11.13


Circuit breaker
CB-TPP 11.13
Ib
163 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
36 kA
4P4d
Micrologic 2.2
250 A
163 A
16 s
1628 A
0.02 s
3000 A
Discrimination Limit

Operating mode Normal


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TPP 11.13

20 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 45/142

0%
163 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x50 mm
Copper
192 A
1x50 mm
Copper
192 A
1x25 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.93
8.60

8.55

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 9.93
8.60
8.55

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
162.540
162.540

162.540

Operating mode Su co MBA


(A)
162.540
162.540

162.540

Project: LVTN-original

04/02/2015

Page 46/142

Synthesis for all operating mode


(A)
162.540
162.540
162.540
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.967
U3L (%)
2.271
UL1L2 (%)
2.271
UL2L3 (%)
2.271
UL3L1 (%)
2.058
UL1N (%)
2.058
UL2N (%)
2.058
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Operating mode Su co MBA


1.967
U3L (%)
2.272
UL1L2 (%)
2.272
UL2L3 (%)
2.272
UL3L1 (%)
2.059
UL1N (%)
2.059
UL2N (%)
2.059
UL3N (%)

0.621
0.718
0.718
0.718
0.621
0.621
0.621

Project: LVTN-original

04/02/2015

Page 47/142

3.4.10 Circuit TPP-TPP14.16


Circuit breaker
CB-TPP14.16
Ib
63.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX100B
100 A
25 kA
NA
NA
36 kA
4P4d
Micrologic 2.2
100 A
64.4 A
16 s
644 A
0.02 s
1500 A
Discrimination Limit

Operating mode Normal


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP
NSX630F
Micrologic 2.3
630 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TPP 14.16

20 m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 48/142

0%
63 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x10 mm
Copper
75 A
1x10 mm
Copper
75 A
1x10 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.93
8.60

8.55

3.10

1.98

1.88 0.00

Operating mode Su co MBA


(kA) 9.93
8.60
8.55

3.10

1.98

1.88 0.00

Synthesis for all operating mode


(kA) 9.93
8.60
8.55

3.10

1.98

1.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
63.180
63.180

63.180

Operating mode Su co MBA


(A)
63.180
63.180

63.180

Project: LVTN-original

04/02/2015

Page 49/142

Synthesis for all operating mode


(A)
63.180
63.180
63.180
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.468
U3L (%)
2.850
UL1L2 (%)
2.850
UL2L3 (%)
2.850
UL3L1 (%)
2.560
UL1N (%)
2.560
UL2N (%)
2.560
UL3N (%)

1.123
1.297
1.297
1.297
1.123
1.123
1.123

Operating mode Su co MBA


2.469
U3L (%)
2.851
UL1L2 (%)
2.851
UL2L3 (%)
2.851
UL3L1 (%)
2.561
UL1N (%)
2.561
UL2N (%)
2.561
UL3N (%)

1.123
1.297
1.297
1.297
1.123
1.123
1.123

Project: LVTN-original

04/02/2015

Page 50/142

3.5 Generic load circuits


3.5.1 Circuit CS TANG HAM
Circuit breaker
CB-CS HAM
Ib
10.1 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
13 A
10 kA
NA
NA
NA
4P4d
C
13 A
13 A
NA
104 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

1000 A

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

1000 A

Cable
Parameters
Length
Max length
Installation method

TBV-CS HAM

Type of cable
Project: LVTN-original

20 m
55.6 m
31
E
Multi-core cables on horizontal
perforated tray
Multi-core
04/02/2015

Page 51/142

Nb of additional touching circuits


Insulation
Ambient temperature
Level of third harmonic THDI
Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

0
PVC
30 C
0%
10 A
Iz
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.53

0.31

0.40 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.48

0.31

0.41 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.48

0.31

0.40 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Project: LVTN-original

CS TANGHAM
400 V
7.02 kVA
5.9 kW
10.1 A
0.84
3Ph+N
04/02/2015

Page 52/142

Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

1
1
No
0
NA
IL3

IN

Operating mode Normal


(A)
10.130
10.130

10.130

Operating mode Su co MBA


(A)
10.130
10.130

10.130

Synthesis for all operating mode


(A)
10.130
10.130
10.130
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


4.022
U3L (%)
4.599
UL1L2 (%)
4.621
UL2L3 (%)
4.621
UL3L1 (%)
4.022
UL1N (%)
4.022
UL2N (%)
4.061
UL3N (%)

1.095
1.264
1.264
1.264
1.095
1.095
1.095

Operating mode Su co MBA


4.023
U3L (%)
4.600
UL1L2 (%)
4.622
UL2L3 (%)
4.622
UL3L1 (%)
4.023
UL1N (%)
4.023
UL2N (%)
4.062
UL3N (%)

1.095
1.264
1.264
1.264
1.095
1.095
1.095

Synthesis for all operating mode


4.023
U3L (%)
4.600
UL1L2 (%)
4.622
UL2L3 (%)
4.622
UL3L1 (%)
4.023
UL1N (%)
4.023
UL2N (%)
4.062
UL3N (%)

Project: LVTN-original

04/02/2015

Page 53/142

3.5.2 Circuit TU THANG MAY


Circuit breaker
CB-TTM
Ib
55.8 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
63 A
10 kA
NA
NA
NA
4P4d
C
63 A
63 A
NA
504 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

1000 A

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

1000 A

Cable
Parameters
Length
Max length
Installation method

TBV-TTM

80 m
124 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 54/142

0%
56 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x10 mm
Copper
75 A
1x10 mm
Copper
75 A
1x10 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.74

0.44

0.42 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.61

0.44

0.43 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.61

0.44

0.42 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TTM
400 V
38.7 kVA
33.3 kW
55.8 A
0.86
3Ph+N
1
1
04/02/2015

Page 55/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
55.822
55.822

55.822

Operating mode Su co MBA


(A)
55.822
55.822

55.822

Synthesis for all operating mode


(A)
55.822
55.822
55.822
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


6.946
U3L (%)
7.975
UL1L2 (%)
7.998
UL2L3 (%)
7.998
UL3L1 (%)
6.946
UL1N (%)
6.946
UL2N (%)
6.985
UL3N (%)

4.019
4.641
4.641
4.641
4.019
4.019
4.019

Operating mode Su co MBA


6.947
U3L (%)
7.976
UL1L2 (%)
7.999
UL2L3 (%)
7.999
UL3L1 (%)
6.947
UL1N (%)
6.947
UL2N (%)
6.986
UL3N (%)

4.019
4.641
4.641
4.641
4.019
4.019
4.019

Synthesis for all operating mode


6.947
U3L (%)
7.976
UL1L2 (%)
7.999
UL2L3 (%)
7.999
UL3L1 (%)
6.947
UL1N (%)
6.947
UL2N (%)
6.986
UL3N (%)

Project: LVTN-original

04/02/2015

Page 56/142

3.5.3 Circuit PHU TAI THONG GIO


Circuit breaker
CB-PT THONG GIO
Ib
45.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
50 A
10 kA
NA
NA
NA
4P4d
C
50 A
50 A
NA
400 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-PT THONG GIO

20 m
174 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 57/142

0%
45 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x10 mm
Copper
60 A
1x10 mm
Copper
60 A
1x10 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

1.70

1.02

0.96 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.87

0.92

0.91 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.87

0.92

0.91 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

PT THONG GIO
400 V
31.3 kVA
25.1 kW
45.2 A
0.8
3Ph+N
1
1
04/02/2015

Page 58/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
45.200
45.200

45.200

Operating mode Su co MBA


(A)
45.200
45.200

45.200

Synthesis for all operating mode


(A)
45.200
45.200
45.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.642
U3L (%)
4.159
UL1L2 (%)
4.182
UL2L3 (%)
4.182
UL3L1 (%)
3.641
UL1N (%)
3.641
UL2N (%)
3.680
UL3N (%)

0.714
0.825
0.825
0.825
0.714
0.714
0.714

Operating mode Su co MBA


3.642
U3L (%)
4.160
UL1L2 (%)
4.183
UL2L3 (%)
4.183
UL3L1 (%)
3.642
UL1N (%)
3.642
UL2N (%)
3.681
UL3N (%)

0.714
0.825
0.825
0.825
0.714
0.714
0.714

Synthesis for all operating mode


3.642
U3L (%)
4.160
UL1L2 (%)
4.183
UL2L3 (%)
4.183
UL3L1 (%)
3.642
UL1N (%)
3.642
UL2N (%)
3.681
UL3N (%)

Project: LVTN-original

04/02/2015

Page 59/142

3.5.4 Circuit CS NGOAI THAT


Circuit breaker
CB-CSNT
Ib
1.76 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
2A
50 kA
NA
NA
15 kA
4P4d
C
2A
2A
NA
16 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSNT

30 m
360 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 60/142

0%
2A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
23 A
1x1.5 mm
Copper
23 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.35

0.20

0.28 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.34

0.21

0.29 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.34

0.20

0.28 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSNT
400 V
1.22 kVA
1.16 kW
1.76 A
0.95
3Ph+N
1
1
04/02/2015

Page 61/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
1.760
1.760

1.760

Operating mode Su co MBA


(A)
1.760
1.760

1.760

Synthesis for all operating mode


(A)
1.760
1.760
1.760
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.271
U3L (%)
3.731
UL1L2 (%)
3.754
UL2L3 (%)
3.754
UL3L1 (%)
3.270
UL1N (%)
3.270
UL2N (%)
3.310
UL3N (%)

0.344
0.397
0.397
0.397
0.344
0.344
0.344

Operating mode Su co MBA


3.272
U3L (%)
3.732
UL1L2 (%)
3.755
UL2L3 (%)
3.755
UL3L1 (%)
3.271
UL1N (%)
3.271
UL2N (%)
3.311
UL3N (%)

0.344
0.397
0.397
0.397
0.344
0.344
0.344

Synthesis for all operating mode


3.272
U3L (%)
3.732
UL1L2 (%)
3.755
UL2L3 (%)
3.755
UL3L1 (%)
3.271
UL1N (%)
3.271
UL2N (%)
3.311
UL3N (%)

Project: LVTN-original

04/02/2015

Page 62/142

3.5.5 Circuit CS CC TANG TRET


Circuit breaker
CB-CSCC TANG TRET
Ib
13.3 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
16 A
10 kA
NA
NA
NA
4P4d
C
16 A
16 A
NA
128 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSCC TANG TRET

25 m
44.3 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 63/142

0%
13 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.44

0.25

0.34 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.41

0.26

0.35 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.41

0.25

0.34 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSCC TANG TRET


400 V
9.2 kVA
8 kW
13.3 A
0.87
3Ph+N
1
1
04/02/2015

Page 64/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
13.280
13.280

13.280

Operating mode Su co MBA


(A)
13.280
13.280

13.280

Synthesis for all operating mode


(A)
13.280
13.280
13.280
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


4.785
U3L (%)
5.479
UL1L2 (%)
5.502
UL2L3 (%)
5.502
UL3L1 (%)
4.784
UL1N (%)
4.784
UL2N (%)
4.824
UL3N (%)

1.858
2.145
2.145
2.145
1.858
1.858
1.858

Operating mode Su co MBA


4.786
U3L (%)
5.480
UL1L2 (%)
5.503
UL2L3 (%)
5.503
UL3L1 (%)
4.785
UL1N (%)
4.785
UL2N (%)
4.825
UL3N (%)

1.858
2.145
2.145
2.145
1.858
1.858
1.858

Synthesis for all operating mode


4.786
U3L (%)
5.480
UL1L2 (%)
5.503
UL2L3 (%)
5.503
UL3L1 (%)
4.785
UL1N (%)
4.785
UL2N (%)
4.825
UL3N (%)

Project: LVTN-original

04/02/2015

Page 65/142

3.5.6 Circuit CS CC TANG 2


Circuit breaker
CB-CSCC TANG2
Ib
1.66 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
2A
50 kA
NA
NA
15 kA
4P4d
C
2A
2A
NA
16 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSCC TANG2

30 m
384 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 66/142

0%
2A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.37

0.22

0.29 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.36

0.22

0.30 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.36

0.22

0.29 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSCC TANG 2
400 V
1.15 kVA
0.989 kW
1.66 A
0.86
3Ph+N
1
1
04/02/2015

Page 67/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
1.660
1.660

1.660

Operating mode Su co MBA


(A)
1.660
1.660

1.660

Synthesis for all operating mode


(A)
1.660
1.660
1.660
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.203
U3L (%)
3.652
UL1L2 (%)
3.675
UL2L3 (%)
3.675
UL3L1 (%)
3.202
UL1N (%)
3.202
UL2N (%)
3.241
UL3N (%)

0.275
0.318
0.318
0.318
0.275
0.275
0.275

Operating mode Su co MBA


3.204
U3L (%)
3.653
UL1L2 (%)
3.676
UL2L3 (%)
3.676
UL3L1 (%)
3.203
UL1N (%)
3.203
UL2N (%)
3.242
UL3N (%)

0.275
0.318
0.318
0.318
0.275
0.275
0.275

Synthesis for all operating mode


3.204
U3L (%)
3.653
UL1L2 (%)
3.676
UL2L3 (%)
3.676
UL3L1 (%)
3.203
UL1N (%)
3.203
UL2N (%)
3.242
UL3N (%)

Project: LVTN-original

04/02/2015

Page 68/142

3.5.7 Circuit CS CC TANG 3-13


Circuit breaker
CB-CSCC TANG 3-13
Ib
1.66 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
2A
50 kA
NA
NA
15 kA
4P4d
C
2A
2A
NA
16 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSCC TANG 3-13

35 m
384 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 69/142

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

0%
2A
Iz
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.33

0.19

0.26 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.32

0.19

0.27 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.32

0.19

0.26 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSCC TANG 3-13


400 V
1.15 kVA
0.989 kW
1.66 A
0.86
3Ph+N
11
1
04/02/2015

Page 70/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
1.660
1.660

1.660

Operating mode Su co MBA


(A)
1.660
1.660

1.660

Synthesis for all operating mode


(A)
1.660
1.660
1.660
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.249
U3L (%)
3.705
UL1L2 (%)
3.728
UL2L3 (%)
3.728
UL3L1 (%)
3.248
UL1N (%)
3.248
UL2N (%)
3.287
UL3N (%)

0.321
0.371
0.371
0.371
0.321
0.321
0.321

Operating mode Su co MBA


3.250
U3L (%)
3.706
UL1L2 (%)
3.729
UL2L3 (%)
3.729
UL3L1 (%)
3.249
UL1N (%)
3.249
UL2N (%)
3.288
UL3N (%)

0.321
0.371
0.371
0.371
0.321
0.321
0.321

Synthesis for all operating mode


3.250
U3L (%)
3.706
UL1L2 (%)
3.729
UL2L3 (%)
3.729
UL3L1 (%)
3.249
UL1N (%)
3.249
UL2N (%)
3.288
UL3N (%)

Project: LVTN-original

04/02/2015

Page 71/142

3.5.8 Circuit CS CC TANG 14


Circuit breaker
CB-CSCC TANG14
Ib
2.05 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
15 kA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSCC TANG14

65 m
254 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 72/142

0%
2A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.19

0.11

0.15 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.18

0.11

0.15 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.18

0.11

0.15 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSCC TANG 14
400 V
1.42 kVA
1.25 kW
2.05 A
0.88
3Ph+N
1
1
04/02/2015

Page 73/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
2.050
2.050

2.050

Operating mode Su co MBA


(A)
2.050
2.050

2.050

Synthesis for all operating mode


(A)
2.050
2.050
2.050
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.681
U3L (%)
4.205
UL1L2 (%)
4.228
UL2L3 (%)
4.228
UL3L1 (%)
3.681
UL1N (%)
3.681
UL2N (%)
3.720
UL3N (%)

0.754
0.871
0.871
0.871
0.754
0.754
0.754

Operating mode Su co MBA


3.682
U3L (%)
4.206
UL1L2 (%)
4.229
UL2L3 (%)
4.229
UL3L1 (%)
3.682
UL1N (%)
3.682
UL2N (%)
3.721
UL3N (%)

0.754
0.871
0.871
0.871
0.754
0.754
0.754

Synthesis for all operating mode


3.682
U3L (%)
4.206
UL1L2 (%)
4.229
UL2L3 (%)
4.229
UL3L1 (%)
3.682
UL1N (%)
3.682
UL2N (%)
3.721
UL3N (%)

Project: LVTN-original

04/02/2015

Page 74/142

3.5.9 Circuit CSCC TANG 15


Circuit breaker
CB-CSCC ATNG15
Ib
2.46 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
15 kA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSCC TANG15

70 m
254 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 75/142

0%
2A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.17

0.10

0.14 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.17

0.10

0.14 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.17

0.10

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSCC TANG15
400 V
1.7 kVA
1.52 kW
2.46 A
0.89
3Ph+N
1
1
04/02/2015

Page 76/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
2.460
2.460

2.460

Operating mode Su co MBA


(A)
2.460
2.460

2.460

Synthesis for all operating mode


(A)
2.460
2.460
2.460
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.913
U3L (%)
4.472
UL1L2 (%)
4.495
UL2L3 (%)
4.495
UL3L1 (%)
3.912
UL1N (%)
3.912
UL2N (%)
3.951
UL3N (%)

0.985
1.138
1.138
1.138
0.985
0.985
0.985

Operating mode Su co MBA


3.914
U3L (%)
4.473
UL1L2 (%)
4.496
UL2L3 (%)
4.496
UL3L1 (%)
3.913
UL1N (%)
3.913
UL2N (%)
3.952
UL3N (%)

0.985
1.138
1.138
1.138
0.985
0.985
0.985

Synthesis for all operating mode


3.914
U3L (%)
4.473
UL1L2 (%)
4.496
UL2L3 (%)
4.496
UL3L1 (%)
3.913
UL1N (%)
3.913
UL2N (%)
3.952
UL3N (%)

Project: LVTN-original

04/02/2015

Page 77/142

3.5.10 Circuit CSCC TANG 16


Circuit breaker
CB-CSCC TANG16
Ib
2.86 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
25 kA
2P1d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CSCC TANG16

75 m
144 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 78/142

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

0%
3A
Iz
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x1.5 mm
Copper
22 A
1x1.5 mm
Copper
22 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.16

0.09

0.13 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.16

0.09

0.13 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.16

0.09

0.13 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CSCC TANG16
400 V
0.66 kVA
0.594 kW
2.86 A
0.9
1Ph+N
L3-N
1
1
04/02/2015

Page 79/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
0.000
0.000

2.860

2.86

Operating mode Su co MBA


(A)
0.000
0.000

2.860

2.86

Synthesis for all operating mode


(A)
0.000
0.000
2.860
Voltage drop
Cumulated from upstream

2.86
Circuit

Operating mode Normal


4.168
U3L (%)
3.334
UL1L2 (%)
3.357
UL2L3 (%)
3.357
UL3L1 (%)
2.927
UL1N (%)
2.927
UL2N (%)
5.448
UL3N (%)

1.241
0.000
0.000
0.000
0.000
0.000
2.482

Operating mode Su co MBA


4.169
U3L (%)
3.335
UL1L2 (%)
3.358
UL2L3 (%)
3.358
UL3L1 (%)
2.928
UL1N (%)
2.928
UL2N (%)
5.449
UL3N (%)

1.241
0.000
0.000
0.000
0.000
0.000
2.482

Synthesis for all operating mode


4.169
U3L (%)
3.335
UL1L2 (%)
3.358
UL2L3 (%)
3.358
UL3L1 (%)
2.928
UL1N (%)
2.928
UL2N (%)
5.449
UL3N (%)

Project: LVTN-original

04/02/2015

Page 80/142

3.5.11 Circuit CHIEU SANG TANG THUONG


Circuit breaker
CB-CS TANG THUONG
Ib
0.3 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
0.5 A
50 kA
NA
NA
15 kA
4P4d
C
0.5 A
0.5 A
NA
4A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TBV
NG160E
TM-D
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TBV-CS TANG THUONG

80 m
1542 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 81/142

0%
0A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

0.15

0.09

0.12 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.15

0.09

0.13 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.15

0.09

0.12 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

CS TANG THUONG
400 V
0.208 kVA
0.197 kW
0.3 A
0.95
3Ph+N
1
1
04/02/2015

Page 82/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
0.300
0.300

0.300

Operating mode Su co MBA


(A)
0.300
0.300

0.300

Synthesis for all operating mode


(A)
0.300
0.300
0.300
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.074
U3L (%)
3.503
UL1L2 (%)
3.526
UL2L3 (%)
3.526
UL3L1 (%)
3.073
UL1N (%)
3.073
UL2N (%)
3.112
UL3N (%)

0.146
0.169
0.169
0.169
0.146
0.146
0.146

Operating mode Su co MBA


3.075
U3L (%)
3.504
UL1L2 (%)
3.527
UL2L3 (%)
3.527
UL3L1 (%)
3.074
UL1N (%)
3.074
UL2N (%)
3.113
UL3N (%)

0.146
0.169
0.169
0.169
0.146
0.146
0.146

Synthesis for all operating mode


3.075
U3L (%)
3.504
UL1L2 (%)
3.527
UL2L3 (%)
3.527
UL3L1 (%)
3.074
UL1N (%)
3.074
UL2N (%)
3.113
UL3N (%)

Project: LVTN-original

04/02/2015

Page 83/142

3.5.12 Circuit TU DIEN TANG 2


Circuit breaker
CB-TDT2
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP234
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP234
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP234-TDT2

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 84/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT2
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 85/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 86/142

3.5.13 Circuit TU DIEN TANG 3


Circuit breaker
CB-TDT3
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP234
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP234
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP234-TDT3

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 87/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT3
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 88/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 89/142

3.5.14 Circuit TU DIEN TANG 4


Circuit breaker
CB-TDT4
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP234
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP234
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP234-TDT4

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 90/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT4
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 91/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 92/142

3.5.15 Circuit TU DIEN TANG 5


Circuit breaker
CB-TDT5
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP567
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP567
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP567-TDT5

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 93/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT5
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 94/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 95/142

3.5.16 Circuit TU DIEN TANG 6


Circuit breaker
CB-TDT6
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP567
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP567
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP567-TDT6

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 96/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT6
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 97/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 98/142

3.5.17 Circuit TU DIEN TANG 7


Circuit breaker
CB-TDT7
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP567
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP567
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP567-TDT7

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 99/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT7
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 100/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 101/142

3.5.18 Circuit TU DIEN TANG 8


Circuit breaker
CB-TDT8
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP 890
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP 890
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP8.10-TDT8

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 102/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT8
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 103/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 104/142

3.5.19 Circuit TU DIEN TANG 9


Circuit breaker
CB-TDT9
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP 890
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP 890
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP8.10-TDT9

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 105/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT9
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 106/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 107/142

3.5.20 Circuit TU DIEN TANG 10


Circuit breaker
CB-TDT10
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP 890
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP 890
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP8.10-TDT10

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 108/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT10
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 109/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 110/142

3.5.21 Circuit TU DIEN TANG 11


Circuit breaker
CB-TDT11
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP 11.13
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP 11.13
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP11.13-TDT11

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 111/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT11
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 112/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 113/142

3.5.22 Circuit TU DIEN TANG 12


Circuit breaker
CB-TDT12
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP 11.13
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP 11.13
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP11.13-TDT12

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 114/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT12
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 115/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 116/142

3.5.23 Circuit TU DIEN TANG 13


Circuit breaker
CB-TDT13
Ib
60.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60a
iC60a
63 A
6 kA
NA
NA
10 kA
4P4d
C
63 A
63 A
NA
536 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP 11.13
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP 11.13
NSX250B
Micrologic 2.2
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP11.13-TDT13

20 m
244 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 117/142

0%
60 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
80 A
1x16 mm
Copper
80 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

3.57

2.36

2.05 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

3.57

2.36

2.05 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT13
400 V
41.7 kVA
35 kW
60.2 A
0.84
3Ph+N
1
1
04/02/2015

Page 118/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
60.200
60.200

60.200

Operating mode Su co MBA


(A)
60.200
60.200

60.200

Synthesis for all operating mode


(A)
60.200
60.200
60.200
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.597
U3L (%)
2.999
UL1L2 (%)
2.999
UL2L3 (%)
2.999
UL3L1 (%)
2.689
UL1N (%)
2.689
UL2N (%)
2.689
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Operating mode Su co MBA


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

0.631
0.728
0.728
0.728
0.631
0.631
0.631

Synthesis for all operating mode


2.598
U3L (%)
3.000
UL1L2 (%)
3.000
UL2L3 (%)
3.000
UL3L1 (%)
2.690
UL1N (%)
2.690
UL2N (%)
2.690
UL3N (%)

Project: LVTN-original

04/02/2015

Page 119/142

3.5.24 Circuit TU DIEN 14


Circuit breaker
CB-TDT14
Ib
30.1 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
32 A
10 kA
NA
NA
NA
4P4d
C
32 A
32 A
NA
256 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP14.16
NSX100B
Micrologic 2.2
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP14.16
NSX100B
Micrologic 2.2
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TDT14

20 m
54.2 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 120/142

0%
30 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x4 mm
Copper
34 A
1x4 mm
Copper
34 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.99
4.32

2.86

1.13

0.66

0.65 0.00

Operating mode Su co MBA


(kA) 4.99
4.32
2.86

1.13

0.66

0.65 0.00

Synthesis for all operating mode


(kA) 4.99
4.32
2.86

1.13

0.66

0.65 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT14
400 V
20.9 kVA
17.7 kW
30.1 A
0.85
3Ph+N
1
1
04/02/2015

Page 121/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
30.100
30.100

30.100

Operating mode Su co MBA


(A)
30.100
30.100

30.100

Synthesis for all operating mode


(A)
30.100
30.100
30.100
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.710
U3L (%)
4.284
UL1L2 (%)
4.284
UL2L3 (%)
4.284
UL3L1 (%)
3.801
UL1N (%)
3.801
UL2N (%)
3.801
UL3N (%)

1.241
1.433
1.433
1.433
1.241
1.241
1.241

Operating mode Su co MBA


3.711
U3L (%)
4.285
UL1L2 (%)
4.285
UL2L3 (%)
4.285
UL3L1 (%)
3.802
UL1N (%)
3.802
UL2N (%)
3.802
UL3N (%)

1.241
1.433
1.433
1.433
1.241
1.241
1.241

Synthesis for all operating mode


3.711
U3L (%)
4.285
UL1L2 (%)
4.285
UL2L3 (%)
4.285
UL3L1 (%)
3.802
UL1N (%)
3.802
UL2N (%)
3.802
UL3N (%)

Project: LVTN-original

04/02/2015

Page 122/142

3.5.25 Circuit TU DIEN TANG 15


Circuit breaker
CB-TDT15
Ib
30.1 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
32 A
10 kA
NA
NA
NA
4P4d
C
32 A
32 A
NA
256 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP14.16
NSX100B
Micrologic 2.2
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP14.16
NSX100B
Micrologic 2.2
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TDT15

20 m
54.2 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 123/142

0%
30 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x4 mm
Copper
34 A
1x4 mm
Copper
34 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.99
4.32

2.86

1.13

0.66

0.65 0.00

Operating mode Su co MBA


(kA) 4.99
4.32
2.86

1.13

0.66

0.65 0.00

Synthesis for all operating mode


(kA) 4.99
4.32
2.86

1.13

0.66

0.65 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT15
400 V
20.9 kVA
17.7 kW
30.1 A
0.85
3Ph+N
1
1
04/02/2015

Page 124/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
30.100
30.100

30.100

Operating mode Su co MBA


(A)
30.100
30.100

30.100

Synthesis for all operating mode


(A)
30.100
30.100
30.100
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.710
U3L (%)
4.284
UL1L2 (%)
4.284
UL2L3 (%)
4.284
UL3L1 (%)
3.801
UL1N (%)
3.801
UL2N (%)
3.801
UL3N (%)

1.241
1.433
1.433
1.433
1.241
1.241
1.241

Operating mode Su co MBA


3.711
U3L (%)
4.285
UL1L2 (%)
4.285
UL2L3 (%)
4.285
UL3L1 (%)
3.802
UL1N (%)
3.802
UL2N (%)
3.802
UL3N (%)

1.241
1.433
1.433
1.433
1.241
1.241
1.241

Synthesis for all operating mode


3.711
U3L (%)
4.285
UL1L2 (%)
4.285
UL2L3 (%)
4.285
UL3L1 (%)
3.802
UL1N (%)
3.802
UL2N (%)
3.802
UL3N (%)

Project: LVTN-original

04/02/2015

Page 125/142

3.5.26 Circuit TU DIEN TANG 16


Circuit breaker
CB-TDT16
Ib
10 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
10 A
10 kA
NA
NA
NA
4P4d
C
10 A
10 A
NA
80 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TPP14.16
NSX100B
Micrologic 2.2
100 A / 4P4d

Full Discrimination

Operating mode Su co MBA


CB-TPP14.16
NSX100B
Micrologic 2.2
100 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

TPP-TDT16

20 m
73.6 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C

Project: LVTN-original

04/02/2015

Page 126/142

0%
10 A
Iz
Sized with Ir

Level of third harmonic THDI


Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.99
4.32

2.86

0.54

0.31

0.42 0.00

Operating mode Su co MBA


(kA) 4.99
4.32
2.86

0.54

0.31

0.42 0.00

Synthesis for all operating mode


(kA) 4.99
4.32
2.86

0.54

0.31

0.42 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Project: LVTN-original

TDT16
400 V
6.93 kVA
5.82 kW
10 A
0.84
3Ph+N
1
1
04/02/2015

Page 127/142

Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

No
0
NA
IL3

IN

Operating mode Normal


(A)
10.000
10.000

10.000

Operating mode Su co MBA


(A)
10.000
10.000

10.000

Synthesis for all operating mode


(A)
10.000
10.000
10.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


3.549
U3L (%)
4.098
UL1L2 (%)
4.098
UL2L3 (%)
4.098
UL3L1 (%)
3.641
UL1N (%)
3.641
UL2N (%)
3.641
UL3N (%)

1.081
1.248
1.248
1.248
1.081
1.081
1.081

Operating mode Su co MBA


3.550
U3L (%)
4.099
UL1L2 (%)
4.099
UL2L3 (%)
4.099
UL3L1 (%)
3.642
UL1N (%)
3.642
UL2N (%)
3.642
UL3N (%)

1.081
1.248
1.248
1.248
1.081
1.081
1.081

Synthesis for all operating mode


3.550
U3L (%)
4.099
UL1L2 (%)
4.099
UL2L3 (%)
4.099
UL3L1 (%)
3.642
UL1N (%)
3.642
UL2N (%)
3.642
UL3N (%)

Project: LVTN-original

04/02/2015

Page 128/142

3.6 Motor starter combination


3.6.1 Circuit BOM NUOC SINH HOAT
Circuit breaker
CB-BNSH
Ib
NA
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX100F
100 A
36 kA
NA
NA
NA
3P3d
MA
50 A
50 A
NA
600 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBN
NG160E
TM-D
80 A / 3P3d

476 A

Operating mode Su co MBA


CB-TBN
NG160E
TM-D
80 A / 3P3d

476 A

Thermal relay
Designation
Ir

LTMR100
LTMR100
40

Cable
Parameters
Length
Max length
Installation method

TBN-BNSH

Project: LVTN-original

10 m
40.9 m
70
D
04/02/2015

Page 129/142

Multi-core cable in conduit or in cable


ducting in the ground
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ground temperature
25 C
Level of third harmonic THDI
0%
Ib
40 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
0.96
Standard table reference
A-52-15
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-19
User correction factor
1
Overall factor
0.96
Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x10 mm
Copper
58.6 A
1x10 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 5.43
4.70

0.00

2.46

0.00

1.39 0.00

Operating mode Su co MBA


(kA) 1.91
1.65
0.00

0.93

0.00

1.16 0.00

Synthesis for all operating mode


(kA) 5.43
4.70
0.00

0.93

0.00

1.16 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Sr for sizing
Project: LVTN-original

BNSH
Direct
400 V
22 kW
7.2
<=19
40 A
27.7 kVA
04/02/2015

Page 130/142

Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

23.8 kW
0.86
3Ph
1
1
No
0%
NA
IL3

IN

Operating mode Normal


(A)
40.000
40.000

40.000

Operating mode Su co MBA


(A)
40.000
40.000

40.000

Synthesis for all operating mode


(A)
40.000
40.000
40.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.460
U3L (%)
2.831
UL1L2 (%)
2.836
UL2L3 (%)
2.836
UL3L1 (%)
1.374
UL1N (%)
1.374
UL2N (%)
1.383
UL3N (%)

0.360
0.416
0.416
0.416
0.000
0.000
0.000

Operating mode Su co MBA


2.461
U3L (%)
2.832
UL1L2 (%)
2.837
UL2L3 (%)
2.837
UL3L1 (%)
1.375
UL1N (%)
1.375
UL2N (%)
1.384
UL3N (%)

0.360
0.416
0.416
0.416
0.000
0.000
0.000

Startup Voltage drop


UStartUp

3.750

3.6.2 Circuit BOM NUOC THAI


Circuit breaker
CB-BNT
Ib
NA
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Project: LVTN-original

Sized by system
Acti9 P25M
P25M
14 A
15 kA
NA
NA
NA
3P3d
M
14 A
04/02/2015

Page 131/142

Long delay settings


Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

12 A
NA
170 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBN
NG160E
TM-D
80 A / 3P3d

800 A

Operating mode Su co MBA


CB-TBN
NG160E
TM-D
80 A / 3P3d

800 A

Cable
Parameters
Length
Max length
Installation method

TBN-BNT

10 m
44.8 m
70
D
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ground temperature
25 C
Level of third harmonic THDI
0%
Ib
12 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
0.96
Standard table reference
A-52-15
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-19
User correction factor
1
Overall factor
0.96

Project: LVTN-original

04/02/2015

Page 132/142

Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
21.1 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 5.43
4.70

0.00

0.91

0.00

0.67 0.00

Operating mode Su co MBA


(kA) 1.91
1.65
0.00

0.69

0.00

0.68 0.00

Synthesis for all operating mode


(kA) 5.43
4.70
0.00

0.69

0.00

0.67 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Sr for sizing
Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

BNT
Direct
400 V
5.5 kW
7.2
<=19
11.5 A
7.97 kVA
6.61 kW
0.83
3Ph
1
1
No
0%
NA
IL3

IN

Operating mode Normal


(A)
11.500
11.500

11.500

Operating mode Su co MBA


(A)
11.500
11.500

11.500

Synthesis for all operating mode


(A)
11.500
11.500
11.500
Voltage drop
Cumulated from upstream
Operating mode Normal
2.755
U3L (%)
Project: LVTN-original

0
Circuit
0.655
04/02/2015

Page 133/142

UL1L2 (%)
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.172
3.177
3.177
1.374
1.374
1.383

0.756
0.756
0.756
0.000
0.000
0.000

Operating mode Su co MBA


2.756
U3L (%)
3.173
UL1L2 (%)
3.178
UL2L3 (%)
3.178
UL3L1 (%)
1.375
UL1N (%)
1.375
UL2N (%)
1.384
UL3N (%)

0.655
0.756
0.756
0.756
0.000
0.000
0.000

Startup Voltage drop


UStartUp

3.320

3.6.3 Circuit BOM NUOC CHUA CHAY


Circuit breaker
CB-BNCC
Ib
NA
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX100F
100 A
36 kA
NA
NA
NA
3P3d
MA
50 A
50 A
NA
600 A
NA
NA
Discrimination Limit

Operating mode Normal


CB-TBN
NG160E
TM-D
80 A / 3P3d

476 A

Operating mode Su co MBA


CB-TBN
NG160E
TM-D
80 A / 3P3d
Project: LVTN-original

476 A

04/02/2015

Page 134/142

Thermal relay
Designation
Ir

LTMR100
LTMR100
40

Cable
Parameters
Length
Max length
Installation method

TBN-BNCC

10 m
40.9 m
70
D
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ground temperature
25 C
Level of third harmonic THDI
0%
Ib
40 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
0.96
Standard table reference
A-52-15
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-19
User correction factor
1
Overall factor
0.96
Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x10 mm
Copper
58.6 A
1x10 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 5.43
4.70

0.00

2.46

0.00

1.39 0.00

Operating mode Su co MBA


(kA) 1.91
1.65
0.00

0.93

0.00

1.16 0.00

Project: LVTN-original

Ief2min

04/02/2015

Page 135/142

Synthesis for all operating mode


(kA) 5.43
4.70
0.00

0.93

0.00

1.16 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Sr for sizing
Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

BNCC
Direct
400 V
22 kW
7.2
<=19
40 A
27.7 kVA
23.8 kW
0.86
3Ph
1
1
No
0%
NA
IL3

IN

Operating mode Normal


(A)
40.000
40.000

40.000

Operating mode Su co MBA


(A)
40.000
40.000

40.000

Synthesis for all operating mode


(A)
40.000
40.000
40.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


2.460
U3L (%)
2.831
UL1L2 (%)
2.836
UL2L3 (%)
2.836
UL3L1 (%)
1.374
UL1N (%)
1.374
UL2N (%)
1.383
UL3N (%)

0.360
0.416
0.416
0.416
0.000
0.000
0.000

Operating mode Su co MBA


2.461
U3L (%)
2.832
UL1L2 (%)
2.837
UL2L3 (%)
2.837
UL3L1 (%)
1.375
UL1N (%)
1.375
UL2N (%)
1.384
UL3N (%)

0.360
0.416
0.416
0.416
0.000
0.000
0.000

Startup Voltage drop


UStartUp
Project: LVTN-original

3.750
04/02/2015

Page 136/142

3.7 Busbar circuits


3.7.1 Circuit TU PPC
Busbar
TU PPC
Parameters
Switchboard Name
TPPC
Switchboard Range
No preference
Rating (A)
0
IP
Undefined
Feeder
Circuit name
Protection name

Protection type

TPPC-TMP
TPPC-TPP
TU BU

NSX160B
NSX630F
NSX250B

CB-TMP
CB-TPP
CB-TU BU

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.82
9.37

9.99

7.96

8.47

9.19 0.00

Operating mode Su co MBA


(kA) 10.82
9.37
9.99

7.96

8.47

9.19 0.00

Synthesis for all operating mode


(kA) 10.82
9.37
9.99

7.96

8.47

9.19 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.2
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit TU MAY PHAT


TU MAY PHAT

TMP-TBN
TMP-TBV

TU MAY PHAT
No preference
0
Undefined
Protection name

Protection type

CB-TBN
CB-TBV

NG160E
NG160E

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.69
7.53

6.48

6.06

4.97

3.96 0.00

Operating mode Su co MBA


(kA) 1.97
1.71
1.78

0.99

1.54

1.54 0.00

Project: LVTN-original

Ief2min

04/02/2015

Page 137/142

Synthesis for all operating mode


(kA) 8.69
7.53
6.48

0.99

1.54

1.54 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.3
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit TU BOM NUOC


TU BOM NUOC
TU BOM NUOC
No preference
0
Undefined

BOM NUOC SINH


HOAT
BOM NUOC THAI
BOM NUOC CHUA
CHAY

Protection name

Protection type

CB-BNSH

NSX100F

CB-BNT
CB-BNCC

P25M
NSX100F

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 5.43
4.70

0.00

3.44

0.00

1.96 0.00

Operating mode Su co MBA


(kA) 1.91
1.65
0.00

0.96

0.00

1.36 0.00

Synthesis for all operating mode


(kA) 5.43
4.70
0.00

0.96

0.00

1.36 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.4
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit TU BAO VE
TU BAO VE

TU THANG MAY
CS NGOAI THAT
PHU TAI THONG GIO
CS TANG HAM
CS CC TANG TRET
CS CC TANG 2
CS CC TANG 3-13
CS CC TANG 14
CSCC TANG 15
CSCC TANG 16
Project: LVTN-original

TU BAO VE
No preference
0
Undefined
Protection name

Protection type

CB-TTM
CB-CSNT
CB-PT THONG GIO
CB-CS HAM
CB-CSCC TANG TRET
CB-CSCC TANG2
CB-CSCC TANG 3-13
CB-CSCC TANG14
CB-CSCC ATNG15
CB-CSCC TANG16

iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
04/02/2015

Page 138/142

CHIEU SANG TANG


THUONG

CB-CS TANG THUONG

iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.45
3.85

2.49

2.76

1.73

1.56 0.00

Operating mode Su co MBA


(kA) 1.86
1.61
1.53

0.94

1.24

1.23 0.00

Synthesis for all operating mode


(kA) 4.45
3.85
2.49

0.94

1.24

1.23 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.5
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit TPP 234


TPP 234
TPP 234
No preference
0
Undefined

TU DIEN TANG 2
TU DIEN TANG 3
TU DIEN TANG 4

Protection name

Protection type

CB-TDT2
CB-TDT3
CB-TDT4

iC60a
iC60a
iC60a

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.6
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Project: LVTN-original

Circuit TPP 567


TPP 567
TPP 567
No preference
0
Undefined
04/02/2015

Page 139/142

Feeder
Circuit name

Protection name

Protection type

TU DIEN TANG 5
TU DIEN TANG 6
TU DIEN TANG 7

CB-TDT5
CB-TDT6
CB-TDT7

iC60a
iC60a
iC60a

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.7
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit TPP 890


TPP 890
TPP 890
No preference
0
Undefined

TU DIEN TANG 8
TU DIEN TANG 9
TU DIEN TANG 10

Protection name

Protection type

CB-TDT8
CB-TDT9
CB-TDT10

iC60a
iC60a
iC60a

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.8
Busbar
Parameters
Project: LVTN-original

Circuit TPP 11.13


TPP 11.13
04/02/2015

Page 140/142

Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

TPP 11.13
No preference
0
Undefined
Protection name

Protection type

TU DIEN TANG 11
TU DIEN TANG 12
TU DIEN TANG 13

CB-TDT11
CB-TDT12
CB-TDT13

iC60a
iC60a
iC60a

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 8.53
7.38

6.43

5.95

4.93

3.88 0.00

Operating mode Su co MBA


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Synthesis for all operating mode


(kA) 8.53
7.38
6.43

5.95

4.93

3.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.7.9
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit TPP 14.16


TPP 14.16

TU DIEN 14
TU DIEN TANG 15
TU DIEN TANG 16

TPP 14.16
No preference
0
Undefined
Protection name

Protection type

CB-TDT14
CB-TDT15
CB-TDT16

iC60N
iC60N
iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 4.99
4.32

2.86

3.10

1.98

1.88 0.00

Operating mode Su co MBA


(kA) 4.99
4.32
2.86

3.10

1.98

1.88 0.00

Synthesis for all operating mode


(kA) 4.99
4.32
2.86

3.10

1.98

1.88 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Project: LVTN-original

04/02/2015

Page 141/142

3.7.10 Circuit WC 101


Busbar
WC 101
Parameters
Switchboard Name
UC 102
Switchboard Range
No preference
Rating (A)
0
IP
Undefined
Feeder
Circuit name
Protection name

Protection type

Feeder circuit 103

NSX160B

QA 103

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Ief2min

Operating mode Normal


(kA) 1.98
1.71

1.79

NA

NA

NA

NA

Operating mode Su co MBA


(kA) 1.98
1.71
1.79

0.99

1.55

1.55 0.00

Synthesis for all operating mode


(kA) 1.98
1.71
1.79

0.99

1.55

1.55 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.8 Busbar trunking system circuits


3.8.1 Circuit Distribution 57
Vertical distribution (riser)
TPP
Busway
Parameters
Length
10 m
Installation method
Standard
Ambiant temperature
35 C
Ib
571 A
System earthing arrangement
TN-S
Correction factor
Temperature factor
1
Installation factor
1
Protection factor
1
Chosen BTS
Designation
KTC1000
Rating
1000 A
Type of PE
Standard PE
IP
55
IK
08
Core
Copper
Icw
50 kA
Ip
110 kA
Reinforced short circuit
NA
withstand
Feed unit position
End
Feeders
Distribution type
Uniform
Project: LVTN-original

04/02/2015

Page 142/142

Circuit
TPP-TPP 234
TPP-TPP 567
TPP-TPP11.13
TPP-TPP 11.13
TPP-TPP14.16

Protection
CB-TPP234
CB-TPP567
CB-TPP
890
CB-TPP
11.13
CBTPP14.16

Tap off unit


Withdrawable
Withdrawable
Withdrawable

Protection type
NSX250B
NSX250B
NSX250B

Withdrawable

NSX250B

Withdrawable

NSX100B

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 9.93
8.60

8.55

7.18

6.97

6.23 0.00

Operating mode Su co MBA


(kA) 9.93
8.60
8.55

7.18

6.97

6.23 0.00

Synthesis for all operating mode


(kA) 9.93
8.60
8.55

7.18

6.97

6.23 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Voltage drop
Cumulated from upstream

Circuit

Operating mode Normal


1.345
U3L (%)
1.553
UL1L2 (%)
1.553
UL2L3 (%)
1.553
UL3L1 (%)
1.437
UL1N (%)
1.437
UL2N (%)
1.437
UL3N (%)

0.079
0.091
0.091
0.091
0.171
0.171
0.171

Operating mode Su co MBA


1.346
U3L (%)
1.554
UL1L2 (%)
1.554
UL2L3 (%)
1.554
UL3L1 (%)
1.438
UL1N (%)
1.438
UL2N (%)
1.438
UL3N (%)

0.079
0.091
0.091
0.091
0.171
0.171
0.171

Project: LVTN-original

04/02/2015