AIR FLOW RATE FOR FIRE LOBBY & CORRIDOR PRESSURISATION- BASED ON 10 ACH ASPER QCDD

REQUIREMENT

SL NO

Floor Details

1
2
3
4
5
6
7
8
9
10
11
12

2nd Basement
1st Basement
Ground floor
Mezzanine floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
Lower roof

Area(Sq.m)
Lift lobby
Corridor
3
6.03
0
2.5
6.03
0
3
6.03
134
2.6
6.03
80.17
3
6.03
157
3
6.03
173.1
3
6.03
173.1
3
6.03
173.1
3
6.03
173.1
3
6.03
173.1
3
6.03
173.1
2.5
6.03
55.17
TOTAL AIR QTY REQUIRED (CFM)
CONSIDERING 10% SAFETY FACTOR

Height(m)

Hence, pls find below proposal


SL NO.
Description
Fan Ref.

Location

Type

Volume(CuM)
Lift lobby
Corridor
18.1
0
15.1
0
18.1
402.0
15.7
208.4
18.1
471.0
18.1
519.3
18.1
519.3
18.1
519.3
18.1
519.3
18.1
519.3
18.1
519.3
15.1
137.9

Airflow(CFM)

ESP (pa)

LIFT LOBBY
CFM
106
89
106
92
106
106
106
106
106
106
106
89
1227
1350

V/PH/HZ

Firelobby
pressurisation Fan

FLPF -01

Roof

Axial inline

1350

350

440/3/50

Corridor
pressurisation Fan

CPRF -01

Roof

Axial inline

14025

350

440/3/50

ACH ASPER QCDD

FIRE LOBBY
CFM
2365
1226
2771
3055
3055
3055
3055
3055
3055
811
25501
28051

Qty

Remarks
1 No.

Fire rated for 250


Deg C for 2 Hrs

2 Nos

Fire rated for 250


Deg C for 2 Hrs

AIR FLOW RATE FOR FIRE PUMP ROOM & GENERATOR ROOM PRESSURISATION- ASPER QCDD REQUIR

Area(Sq.m)
SL NO

Floor Details

Height(m)

1
2

Ground floor
2nd Basement

3.6
4.75

Fire pump
room
0
14.23

Generator
room
34
0

Fire pump room

Volume(CuM)
Fire pump
room
0.0
67.6

Generator
room
122.4
0.0

Fire condition( Based


on 10 ACH)
0
398

TOTAL AIR QTY REQUIRED (CFM)

398

CONSIDERING 10% SAFETY FACTOR


Hence, pls find below proposal

437

SL
Description
NO.

Fan Ref.

Location

Type

Airflow(CFM)

ESP (pa)

V/PH/HZ

Qty

Fire pump room


Exhaust fan

FREF -01

2nd
Basement

Axial inline

440

100

440/3/50

1 No.

Fire pump room


fresh air fan

FRFF -1

2nd
Basement

Axial inline

400

100

440/3/50

1 No.

Generator room
Exhaust fan

GEF -01

Ground floor
Room

Axial inline

800/475

150/85

440/3/50

1 No.

Generator room
fresh air fan

GFF-01

Ground floor
Room

Axial inline

720/430

150/85

440/3/50

1 No.

ASPER QCDD REQUIREMENT


Air Qty
(CFM) at
Normal
Generator Room
condition Air Qty (CFM)at
(based
Fire
on 6
condition( Based
ACH)
on 10 ACH)
432
720
0
0
432

720

475.2

792

Remarks
Fire rated for 250 Deg C for 2
Hrs
Fire rated for 250 Deg C for 2
Hrs
Fire rated for 250 Deg C for 2
Hrs.2SPEED FANS
Fire rated for 250 Deg C for 2
Hrs.2SPEED FANS

FIRE RATED FANS SCHEDULE EXCEPT CARPARK


Client :Consultant :Main Contractor:Airflow(CFM)

ESP (pa)

SL NO.

Description

Fan Ref.

Location

Type

high
speed/low
speed

high
speed/low
speed

V/PH/HZ

Qty

Remarks

Fire pump room Exhaust fan

FREF -01

2nd Basement

Axial inline

440

150/85

440/3/50

1 No.

Single speed fans-Fire


rated for 250 Deg C for
2 Hrs

Fire pump room fresh air fan

FRFF -1

2nd Basement

Axial inline

400

150/85

440/3/50

1 No.

Single speed fans-Fire


rated for 250 Deg C for
2 Hrs

Generator room Exhaust fan

GEF -01

Ground floor
Room

Axial inline

800/475

150/85

440/3/50

1 No.

Fire rated for 250 Deg


C for 2 Hrs.2SPEED
FANS

Generator room fresh air fan

GFF-01

Ground floor
Room

Axial inline

720/430

150/85

440/3/50

1 No.

Fire rated for 250 Deg


C for 2 Hrs.2SPEED
FANS

Firelobby pressurisation Fan

FLPF -01

Roof

Axial inline

1400

350

440/3/50

1 No.

Single speed fans-Fire


rated for 250 Deg C for
2 Hrs

Corridor pressurisation Fan

CPRF -01

Roof

Axial inline

14000

350

440/3/50

Single speed fans-Fire


2 Nos rated for 250 Deg C for
2 Hrs

Staircase pressurisation Fan

STPRF-01

Roof

Axial inline

16000

350

440/3/50

Single speed fans-Fire


2 Nos rated for 250 Deg C for
2 Hrs

FCC room fresh air fan

FCCFF -01

Ground Floor

Axial inline

500

100

440/3/50

1 No.

Fire rated for 250 Deg


C for 2 Hrs

Potrebbero piacerti anche