CT-2000PLUS/PRO Series
AC MOTOR DRIVER
Instruction
- 2 -
Introduction
Thank you for choosing the CT-2000Plus/Pro inverter unit, this inverter unit is suitable for
operating squirrel cage induction motors. Please read this instruction manual carefully
before actual usage in order to ensure proper operation and suit your needs.
Table of Contents
1. Inspection upon receiving.............................................................................................4
2. Installation and Storage.................................................................................................4
A. Storage......................................................................................................................4
B. Installation place.....................................................................................................4
3. Application notes.............................................................................................................5
4. Block diagram and Wiring.............................................................................................5
A. Wiring of main and control circuit.......................................................................5
B. Signal circuit.............................................................................................................5
C. Connecting the power supply and the AC motor...........................................6
D. R.S.T. for Power source reactor.........................................................................7
E. Standard external connection diagram.............................................................8
F. Terminal specifications..........................................................................................9
5. Operation Test................................................................................................................10
6. Adjust and Function Specification.............................................................................12
A. Keypad operation..................................................................................................12
B. LCD Keypad Adjust Function Specification...................................................13
C. Display specification............................................................................................13
D. Keypad specification............................................................................................13
E. Function Code.......................................................................................................15
7. Description of alarm display indications...................................................................46
8. Troubleshooting..............................................................................................................48
9. Maintenance and Inspection.......................................................................................50
10. Standard Specification..................................................................................................51
A. CT2000PLUS/PRO 200Vseries........................................................................51
B. CT2000PLUS/PRO 400Vseries........................................................................51
C. Standard specification.........................................................................................51
D. Outline dimension.................................................................................................53
11. Function code Table......................................................................................................54
12. Modbus Address of Display Data...............................................................................65
13. Series Communication User Manual.........................................................................66
A. The physical link....................................................................................................66
B. Data structure in communication.......................................................................67
C. Function code in Modbus....................................................................................68
D. Error check generation........................................................................................69
E. Group & global broadcasting function.............................................................71
10cm
min.
10cm
min.
10cm
min.
10cm
min.
- 4 -
3. Application notes
A. Concerning the inverter unit
(1) Do not fit capacitors to the output side of the inverter in order to improve the
power ratio.
(2) In case of fitting MC between inverter and motor to control motor operation,
then the capacity of inverter must be 6 times the capacity of motor.
(3) Run a motor that is within the capacity of the inverter unit, light load current and
no-load current will cause the motor to develop ripple current.
(4) This unit is provided with a current limiting function. The starting torque is
assumed to be from 80% to 100%.
B. Concerning the AC motor
(1) When general-purpose motors are operated at low speeds, there is a reduced
cooling effect, please apply the special purpose motor.
(2) Operation at frequencies exceeding 60 Hz requires caution, as there is the
danger of the mechanical strength failure of the motor.
(3) When motors with brakes are being operated, the power for the brake and
inverter should be taken from the same power supply and the brake operation
must be in phase when the unit is started and stopped.
220
380
|
440
Model
NFB (A)
2
3
5
7.5
10
15
20
30
40
50
60
75
100
125
2
3
5
7.5
10
15
20
30
40
50
60
75
100
125
150
10A
15A
20A
30A
40A
60A
80A
120A
150A
200A
250A
300A
400A
500A
5A
7.5A
10A
15A
20A
30A
40A
60A
80A
100A
120A
150A
200A
250A
300A
- 6 -
NFB
A
DBU
PN
PR N
IM
COM
S1
Multi-step time 1
Multi-step time 2
FM
S2
S3
S4
3-wire operation
S5
S6
REV
RR
FWD
FR
Analog output
0~10V
Max 5mA
AM
CC
MA
MB
MC
M1
M2
M3
COM
P1
PC
Multi-function
Output terminals 1
AC 240V Max 1A
DC 28V Max 2A
Multi-function
Output terminals 2
Open collector
DC 48V
Max 50mA
10V
4~20mA
IN1 ( 4~20mA)
TA
IN2 (0~+10V)
TB
RA
IN3 (0~+10V)
RB
IG
2k
2k
CC
EG
Shield wirse
- 8 -
MODBUS
RS422/485
Main Circuit
Terminal
symbol
Terminal name
R.S.T
U.V.W
E
10V
CC
IN1
IN2
IN3
FM
AM
0~10V
nd
PPR
PN
Analog input/
output terminal
S1
S2
Multi-function
analog input
terminal
MODBUS
Communication
terminal
Open-collector
output common
Grounding
terminal
S4
S5
th
nd
RR
FR
COM
COM
Multi-function
analog output
contact
S3
S6
Operation
control trminal
Specification
MAM1
MBM2
MCM3
TA
TB
RA
RB
IG
P1
PC
EG
5mA output
nd
A
240VAC
28VDC
Max 1A
Max 10A
50mA
Operational Test
5. Operational Test
A. Check before test
Please check the following:
(1) Is wiring correct? Check especially the input and output terminals.
(2) Is there a short-circuit or ground connection on external wiring?
(3) Make sure there is no loosening of screws.
(4) Check external sequence control circuit.
(5) Check voltage of power supply.
B. Operation Method
CT-2000 series inverter unit has both operator panel and external operation methods.
(1) Operator panel
PANEL INPUT
FN-800
SWITCH CONTROL
CT2000
series
FN-800
- 10 -
11
READY
7-segement
monitor
1.Displays frequency
Cd02=0
Displays current Cd02=1
Displays RPM NO2=2
Displays various readings
see Cd02
2. After indicates alarm,
ignore Cd02, directly
displays
failure status
Operation monitor
display
Monitor mode
display
Displays monitor status
Ten-key pad
Data input key
Cutes Corporation
READY
HZ
A
ALARM
Operation instruction
keys
Control from keyboard
External control operation, stop
mode by set Cd04=1
FWD
REV
STOP
PROG
PROG
SET
READ
SET
STOP key
1.
Stops inverter
1.Stops
inverteroperation
operation
2. Resets function
2.Resets
function
3. Resets alarm indication
Step keys
Shift key
1. To change frequency
2. Select function items
- 12 -
7-seqement Monitor
LCD Monitor
Hz
A LED
STOP
FWD
SET
REV
PROG
READ
STEP KEY
C. Display specification
LED
Display specification
RDY
HZ
FWD
REV
STOP
D. Keyboard specification
Bottom
Function
MOTOR RUN
FWD
Bottom specification
Push keypad to control forward of motor, and screen
display main display content (Cd02 setting).
MOTOR RUN
STOP
REV
STOP
RESET
13
READ
PROG
mode) or CE
READ
CANCEL
Item of display
changing
Parameter
selection
SET
shows Cd
Parameter
modification
(show as >)
SHIFT
Input a number
value.
Press , key at parameter input mode can change
parameter. Using with SET key to modify parameter.
Press > key to switch location of cursor. If press > key
again when cursor is at right end side, it will return to
left side. Parameter can be changed by using this key
with key.
Input a number
0
9
- 14 -
E. Function Code
If you see this symbol @ in each parameter descriptions which means that the LCD
display as an error, but the parameters are still this feature. (The next version of the
keyboards LCD will display the correct text.)
Cd00
There are 5 methods to change set frequency. Items A~C are methods of panel key
operation, items D-E are methods of external terminal input.
A. Use PROG key to input data (Cd01=0)
B. Use key to input data (Cd01=0)
C.
D.
E.
Note:
1. Set value should be in accordance with V/F slope (Cd05) and upper limit
frequency (Cd17).
Set by function key
A. Use PROG key to input data (Cd01=0)
PROG
READ
0.
0.
0
SET
C
READ
Note
0.
15
Cd01
The monitor is consisted of four 7-segment LEDs, displays frequency, current and
various data by digital number and character.
Cd02=0
Display the frequency, LED HZ active
Cd02=1
Display the current, LED I active
Cd02=2
Display Ultimate speed, Hz and I LED de-active.
Cd02=3
Display DC current of DC BUS, showing d in front of value
Cd02=4
Display rms value of U.V.W. AC outputLED HZ, I active
Cd02=5
Cd02=6
Cd02=7
Cd02=8
Cd02=9
Cd02=10
Cd02=11
Cd02=12
Cd02=13
Cd02=14
Cd02=15
- 16 -
Torque mode
50HZ
60HZ
50HZ 100HZ
6
F
60HZ 180HZ
60HZ
F
120HZ
8
F
50HZ 200HZ
60HZ
240HZ
10
F
87HZ 174HZ
7
F
50HZ 150HZ
5
V
11
F
Cd58
103HZ 206HZ
F
Cd57
Set motor overload protective current, in order to avoid motor failure because of
overload. Set value=100, please calculate the following formula:
Set Value = Motor rated current / Inverter rated current 100
Ex. Use inverter with 3.7KW(5HP) to drive motor with 2.2KW(3HP)
Inverter rated current = 17.4A
Motor rated current = 8A
Set Value = 8 / 17.4 100 = 46%
17
100%
50%
VB
15%
FS
0%
Acceleration/deceleration time
To control jogging, use external terminal 4-FR or 4-RR with COM shorted.
Set running direction
FR or RR
2
Running
mode:
Jogging
Forward(Reverse)
Note: Jogging operation is valid only when operation command selects the
external operation signal mode (e.g. Cd04=1) and Cd59=0 or 1.
Jogging operation procedures:
1. First put in 4, and then FR (or RR).
2. Put in 4 and FR (or RR) simultaneously.
Be sure always to put in 4 before FR (or RR).
Cd16
Start
Frequency
Time
Note: The most appropriate range for start frequency is 0.5Hz to 10Hz.
Cd17
19
Output
Frequency
Upper
Limiter
Lower
Limiter
Set Frequency Operation
Cd19
Cd22
Cd22
Time
- 20 -
Braking mode
DC braking voltage
DC braking time
Output Frequency
Start
Frequency
Braking
Frequency
Braking Voltage
Time
Braking
Rate
Time
Braking Time
Note:
1. DC braking time too long or too many times is possible to cause motor damage
because of overheating.
2. Set Cd23=0 when DC braking is not required.
21
Run direction
Output
Start by frequency detection
frequency
CE66
Output
voltage
CE69
Cd28=2
Current detect + MCK feedback speed searchStart searching motor speed by
frequency command or maximum output frequency, when output current is over 120%
rated current in searching and start by decreasing output frequency, after current is
lower than 120% rated current, then proceed regular operation.
- 22 -
Operation
command
Frequency command
Output
frequency
CE66
CE65
CE64
Output
current
Cd28=3
MCK disconnection start + inertial start: PCB control circuit is unable to operate when
disconnection or power voltage is too low. This function is able to automatic search
speed and restore setting frequency to operate normal when power reconnection.
Cd29
Time
Cd30=0 No function
Cd30=1 With function
Stop function: This function enables the inverter to be stopped by panel
key while the inverter is operated by external sequence.
Cd31
23
Clear the failure record content of code d1-00, 01, 02, and 03.
Cd36=0 No change
Cd36=1 All of the contents of data will be nOnE, display of LoAd after setting
Note: After this function is active, content value automatically returns to 0, thus
readable value is always 0.
Cd37 Frequency gain setting (Setting range 20-200)
Select ratio of frequency gain
Gain setting for external input signals are available using this function.
Output Frequency = Set Value Frequency Gain MAX. frequency
Ex. Under the mode of external voltage (0-10V) frequency setting,
frequency gain = 100%, set voltage to 2V,MAX. frequency (FH) is 120Hz:
Output Frequency = (2V/10V) 120Hz 100% = 24Hz
If change frequency gain to 150%, then
Output Frequency = (2V/10V) 120Hz 150% = 36H
200%
100%
200
20%
0V
100
20
4mA
Analog Setting Signal
10V
20mA
Note: If the maximum frequency ( FH ) exceeds more than 120Hz, gain setting of larger
than 100% is ignored and fixed at 100% and input data of Code 37 will not be
changed.
Cd38
- 24 -
Frequency Output
Settable Range
Frequency Command
0V
10V
Selective speed
2
Terminal 5
Terminal 3
Terminal 4
: stands for external terminal to put in.
Cd44
Stop mode
Cd44=0
Cd44=1
Cd44=2
Deceleration stop
Free run stop
Free run stop, but restart after the deceleration time is reached,
deceleration time is set by Cd11.
25
CD45
TIME
FA-FC
OPEN
CLOSE
Cd46
Speed multiplier
TIME
The function shows revolution speed multiplied by a scaling factor on the Display.
Note:
1. HZ and A LED de-active.
2. RPM = Frequency Cd46
Cd47
Cd48
Specification
Remark
Time counter
Fault
Stop
Acceleration
Speed reached
Deceleration
Frequency reached
Current reached
CE70
OL fault action
10
No action
Accommodate Cd29
- 26 -
Software version
(Read only)
Voltage Output
(HZ)
Frequency Output
1. Vin Vrate
2. Vin Vrate
27
Time
Motor
speed
Without slip
differential
compensation
Motor
speed
With slip
differential
compensation
With slip
differential
compensation
Output
frequency
- 28 -
Normal
Status
Stall
preventive
mode
Frequency
Frequency
This function is to prevent when motor current exceeds stall current from stall.
There are 2 kinds of acceleration time slopes when motor acceleration current
exceeding stall current occurs:
Instantaneous load increase during steady operation and current exceeding over current
stall, revolution frequency will drop till current dropped to within stall current level.
Stall
preventive
mode
Stall
current
level
Time
During
acceleration
Time
Inverter current
Inverter current
Time
Stall
current
level
29
Cd59
CD59
S4
S6
S3
S5
JOG
MBS
3DF
2DF
JOG/
RST
3DF/
2DF/
Down speed %
UP speed %
Yards counter
2
5DF
MBS
3DF
2DF
5DF
RST
3DF
2DF
JOG
MBS
DOWN
UP
JOG
RST
DOWN
UP
5DF
MBS
DOWN
UP
5DF
RST
DOWN
UP
Terminal specification:
JOG: Jogging operation, accommodating with Cd15.
5DF: Multi-speed, accommodating with Cd40, 41, 42, 43 speed setting.
MBS: Free run stop, operates both panel key and external signal.
RST: Reset, operates both panel key and external signal
2DF: Second term operation, accommodating with Cd12 speed setting.
3DF: Third term operation, accommodating with Cd13 speed setting.
UP: Using external terminal control on frequency increasing. Max. frequency is
setting of Cd00
DOWN: Using external terminal control on frequency decreasing. Min. frequency is
setting of Cd16
Note: when use multi-steps function, and Cd59=1, functions of external terminal 3,4,5
are listed as below
Terminal 3: Down Speed %, means the speed will be decreased, according to
function CE37~CE45.
Terminal 4: Yards counter
Terminal 5: Up Speed %, means the speed will be decreased, according to
function CE37~CE45.
- 30 -
Output Voltage
15%
Cd7 VB
150
0
0%
FC
Cd60
Fb
Cd58
(HZ)
FH
Output Frequency
Cd57
PWM Frequency
Setting by Cd62 (1.5 4.0 Hz)
4 KHZ
6 KHZ
8 KHZ
10 KHZ
DC braking frequency
Set frequency
In stopping
Cd24
Start frequency
Cd 16
DC branking frequency
time in starting
Time
Instant initial fiend time
DC braking frequency
Cd 65
time in stopping
Cd23 ,Cd26
Cd23,Cd26
Output voltage
Output voltage of set
frequency
Output voltage of start
frequency
DC braking voltage
Time
Cd25
- 32 -
33
- 34 -
Speed
Amp
KW-H
Power
Temp.
AvqSp
AC V
Group 2
Frequency
Temp
Amp
COS
Vdc
Poewr
AC V
KW-H
Group 3
Speed
Step
Amp
Time
Vdc
Yards
AC V
AvqSp
- 35 -
Ext
Amp
MCK
Vdc
Temp.
AC V
KW-H
- 36 -
- 37 -
- 38 -
- 39 -
C E08
C E09
C E 13
C E 12
C E 11
C E 10
C E 09
C E 08
C E14
C E15
C E16
CE36
CE35
CE34
CE33
CE32
CE31
CE29
CE28
CE27
CE26
CE25
CE24
CE23
CE22
CE21
C E 07
C E 06
C E05
CE30
C E17
C E18
C E19
C E20
Gradually operation
Output frequency
C E 13
C E 12
C E 11
C E14
C E15
C E16
Up/Down Speed %
function
CE35
CE34
CE33
CE29
CE28
CE27
CE26
CE25
CE24
CE23
CE22
CE21
C E 06
C E05
C E09
CE32
C E 07
CE31
C E17
C E18
C E19
C E20
CE30
C E 08
CE36
C E 10
C E 09
CE08
CE09
Frequency
CE38
CE39
CE37
Output freq.
CE44
CE42
CE43
CE40
CE45
CE46
CE41
UP
DOWN
- 40 -
Frequency
last step
First step
t
Continuous
operation
frequency
last step
First step
Continuous
operation, perform
speed as the last
speed in the step,
till the RST or
CE48 set to1
frequency
Last step
First step
- 41 -
Time
Output frequency
Time
- 42 -
CE58 x CE57
.
Cd58
Base Frequency
Output frequency
Time
Output frequency
Time
- 43 -
Time
Time
Momentary power
Loss,compensation
time CE68
Speed search
Speed search
waiting time
when reset
- 44 -
CE69
Description
When motor operation exceeds motor rated current, it is overload operation, and it might
damage motor if under overload operation for long time.
CE73@ Current arrearage range (setting range 2-20)
CE74@ Current detect level (setting range 30-150)
Set the action range of current detect.
Current arrearage range: RELAY will jump when Cd47, 48, 49=7, current is lower than
rated current (CE73CE74) value
Current detect level: RELAY will start when Cd47, 48, 49=7,
current is over rated current CE74 value.
- 45 -
ErC
OCPA
OCPd
OCPn
OC
OCS
OU
LU
LU A
Processing
- 46 -
OL
OL A
bUOH
ES
Fb
PLU
Processing
- 47 -
Troubleshooting
8. Troubleshooting
Description of
trouble
The motor does
not run at all
OCPA is
indicated as soon
as the motor is
started.
(Overcurrent
protects
operation during
acceleration.)
Possible cause
Solution
1. Wiring error
Repair motor
Please contact us
2. Overload
Troubleshooting
Description of
trouble
Possible cause
Solution
Repair motor
Please contact us
OL is displayed 1. Overload
Reduce load or increase inverter
during inverter
capacity
operation
2. Is inverter over current limiter Apply Code 06 to re-set motor rated
appropriate
current
OH is displayed 1. Check if the cooling fan is
during inverter
still working
operation
2. Is ambient temperature too
hot
No any
1. Power failure
indication, the
output frequency 2. Is there loosen part on
displayed 0
external control terminal
- 49 -
Inspection item
- 50 -
2.2
3.7
5.5
7.5
11
15
22
30
37
45
55
75
93
2A2 3A7 5A5 7A5 011 015 022 030 037 045 055 075 093
11.1
18
23
33
48
61
86
4.4
7.1
3 200~230V 10%
50HZ 5%
3 200~230V 10%
60HZ 5%
68
84
111 131
or
3 200V220V230V
Cooling system
Forced air-cooling
Outline dimension Fig1 Fig1 Fig1 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2
Weight (Kg)
8
8
9
14 14 20 30 45 60 60 65 70 70
B. CT2000PLUS/PRO 400Vseries
Motor rating (KW) 2.2 3.7 5.5 7.5 11 15
Model
CT2000PLUS- 2A2 3A7 5A5 7A5 011 015
CT2000PRORated current (A) 6.2 9
13 17.3 24 31
Rated capacity
4.9 7.1 10.4 13.8 19.1 24.7
(KVA)
Power supply
3 380~460V 10%
50HZ
3 380~460V 10%
Output voltage
22
30
37
45
55
75
93 112
65
71
or
60HZ 5%
3 380V400V440V460V
Cooling system
Forced air-cooling
Outline dimension Fig1 Fig1 Fig1 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2
Weight (Kg)
8
9
9
14 14 18 35 38 40 46 50 65 70 70
- 51 -
Standard Specification
C.Standard specification
Control method
Sine P.W.M control
Frequency
Digital setting: 0.1% Analog setting: 0.5% (35)
accuracy
Frequency
Digital setting: 0.5100Hz0.01Hz
100Hz240Hz0.1Hz
resolution
Analog setting: (setting value/1000)Hz
Frequency range 0.5240HZInitial frequency 0.530Hz
V/F ratio
Torque boost
Acceleration /
0.16000 seclinear, two-step setting
Deceleration time
Motor Braking
100% DB. Under 20% DB. Connect extra braking resister to reach
3.7KW Including
100% DB.
braking resister.
DC Braking
DC Injection BrakingSetting mode, torque, time, active frequency
Standard feature
Altitude 1,000m or lower, keep from corrosive gasses, liquid and dust
-1050 (Non-condensing and not frozen)
Below 0.6G
Relative between 45 to 90% (No condensing)
- 52 -
Standard Specification
D. Outline dimension (unit: mm)
Fig1
Fig2
220V Series
KW
7.5/11
430
414
401
244
190
215
H
7
15/22
3045
492
477
466
283
200
254
699
679
668
408
270
314
10
10
5593
912
892
872
530
350
313
10
10
KW
7.5/15
430
414
401
244
190
215
H
7
22/30
3755
492
477
466
283
200
254
699
679
668
408
270
314
10
10
75112
912
892
872
530
350
313
10
10
400V Series
- 53 -
11.
Code
No.
Detail of Data
0-400Hz
10
128
129
0: Frequency (HZ)
1: Current (A)
2: Ultimate speed
3: DC Voltage(d)
4: Output AC Voltage(V)
5: External I/O status(E)
6: Temperature of PIM module(b)
7: operation frequency feedback
8: average speed of multi-step
function.
9: current step of multi-step function
10: current time of multi-step
function (min)
11: Yards counter
12: power factor
13: instant power (Kw)
14: KWh
15: MWh
130
131
Cd04 Operation
command mode
0: Operation panel
1: External signal
132
- 54 -
Function
Detail of Data
1-7 fixed Modes
11: Set by CD57, CD58
133
100
134
0-15.0 (0-15.0%)
135
Cd08 1 acceleration
time
0-6000 (S/50HZ)
136
0-6000 (S/50HZ)
137
0-6000 (S/50HZ)
10
138
0-6000 (S/50HZ)
10
139
0-400HZ
20
140
0-400HZ
30
141
0-400HZ
40
142
143
0.5HZ-60HZ
144
10-400HZ
60
145
0-100HZ
146
Cd19 Jogging
0-600(S/50HZ)
acceleration /
deceleration time
147
148
149
0-6HZ
150
0: de-active
1: Active when stop
2: Active when start
3: Active both stop and start
151
- 55 -
Code
No.
Function
Detail of Data
Cd24 DC braking
frequency
0-20HZ
152
Cd25 DC braking
voltage
0-100
50
153
1-60 Sec.
0: Reverse
1: Prohibited reverse
0: Invalid
1: MCK feedback
2: Detected current +MCK feedback
3: MCK disconnection start + coast
start
154
155
0~3
156
157
158
159
164
Cd28
Speed search
selecting
Cd29 Time
1-60000 (Sec.)
0: No change
1: Initial factory setting
2:Reset CE05~CE36=0
20-200%
100
165
90-110%
100
166
Cd39 Frequency
command bias
0-250
125
167
0-400HZ
45
168
0-400HZ
50
169
0-400HZ
55
170
0-400HZ
60
171
- 56 -
Function
Detail of Data
0: Decelerate stop
1: Free run stop
2: Free run stop after
deceleration time is reached
172
0.5
173
0-500
174
0-10
175
0-10
176
177
Read only
178
10-450
179
5-60%
30
180
0.0-10.0%
181
182
0~60%
20
183
30-200%
180
184
10-240HZ (FH)
240
185
10-240HZ (Fb)
FH Fb
240
186
- 57 -
Function
Detail of Data
Set
0
1
187
20
188
Cd61 PWM
0: 2k 1: 4k 2: 6k 3: 8k 4: 10k
Frequency
Cd62 PWM Frequency2 15~40
Cd64 Dynamic braking 0~1
mode
Cd65 Instant initial field Instant initial field time when start
time
motor.
4-64
Cd66 Analog input filter
time
DC Bus fine tune
Adjust the standard score of DC Bus
Cd67
189
30
1
190
192
00~
20.00
32
193
2
3
4
5
6
7
DI4
JOG
JOG/
yards
5DF
5DF
JOG
JOG
5DF
5DF
DI6
MBS
RST
MBS
RST
MBS
RST
MBS
RST
DI3
DI5
3DF
2DF
3DF/
2DF/
Down% Up%
3DF
2DF
3DF
2DF
DOWN UP
DOWN UP
DOWN UP
DOWN UP
15.0
194
195
0~10
10
196
120~140%
130
198
130~150%
140
199
1: clear
- 58 -
Cd81 RS485
communication
address setting
Cd82 Series
communication
baud rate setting
Series
communication
Cd83
response time
setting
Cd84 Series
Communication
broadcasting
function setting
Cd85 LCD Display
Setting
Cd87 Display Group of
LCD monitor
Detail of Data
0: Disable
1: Enable
0: De-active
1: Active with RTU mode, only for
monitoring.(8,n,1)
2: Active with RTU mode, change
general parameter.(8,n,1)
3: Active with RTU mode, change of
general parameter. Operational
command by remote control.(8,n,1)
1240
0:2400 bps
1:4800 bps
2:9600 bps
208
209
210
211
015
- 59 -
Code
No.
Function
Detail of Data
nOnE
nOnE
nOnE
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
Function
2nd step time
setting
3rd step time
setting
4th step time
setting
5th step time
setting
6th step time
setting
7th step time
setting
8th step time
setting
9th step time
setting
10th step time
setting
11th step time
setting
12th step time
setting
13th step time
setting
14th step time
setting
15th step time
setting
16th step time
setting
1st frequency
increase setting
2nd frequency
increase setting
3rd frequency
increase setting
Setting Times of
1st frequency
increase
Setting Times of
2nd frequency
increase
1st frequency
decrease setting
2nd frequency
decrease setting
Detail of Data
0100Min
250
0100Min
251
0100Min
252
0100Min
253
0100Min
254
0100Min
255
0100Min
256
0100Min
257
0100Min
258
0100Min
259
0100Min
260
0100Min
261
0100Min
262
0100Min
263
0100Min
264
0~10.0%
265
0~10.0%
266
0~10.0%
267
0~200 min
268
0~200 min
269
0~10.0%
270
0~10.0%
271
- 61 -
272
273
274
275
277
100
0~1
284
30~
200
285
Stall prevention
CE58 limit during
acceleration
30~
100
286
Stall prevention
CE59 limit during
deceleration
0: Invalid
1: Valid
0~1
287
- 62 -
Speed search
current
Detail of Data
0: Invalid
1: Decelerate by deceleration time 2
(Cd11)
0~1
289
30~
200
290
155~
500
291
0~
200
292
Speed search
When Cd28=2 is valid
deceleration time
Speed search
CE66
When Cd28=2 is valid
waiting time
0: Invalid
1: Valid, restart when power
recovered in time of (Cd80), detect
low voltage of master power when
Momentary power
CE67
oss direction
exceeded.
2: Movement of CPU is valid, restart
when power recovered (Cd80 will
not be considered)
Momentary power
Restart valid time limit when set
CE68 loss compensation
Cd79=1
time
From 0V to recover is time of
Voltage recovery
CE69
maximum output voltage when set
time
restart
Inverter
Set Cd84 as 100% for level of
overheating
CE70
detecting overheating forecast for
forecast detection
inverter
level
Active when
0: Deceleration stop
inverter
1: Coast stop
CE71
overheating
2: Emergency stop
forecast detection 3: Continuous operation
Set 50 as unit for detecting level
of inverter overheating
Software protection is invalid when
Temperature
CE72
set 130
protection level
(OH is only hardare protection)
CE65
- 63 -
0.1~
10.0
0.0~
20.0
293
294
0~2
295
0~2.0
296
0.1~
20.0
297
50~
100
298
0~3
299
50~
130
300
Code
Function
No.
Detail of Data
- 64 -
301
30~
150
302
Notes
Range
Unit
MODBUS
Address
0.01HZ
328
Operation frequency
024000
Current feedback
09999
0.1A
329
Operation command
024000
0.01HZ
330
DC voltage
09999
0.1V
331
09999
0.1
332
Output voltage
Vac=Output voltage / 2
0255
External terminal
mode
1121130
Module Temperature
333
0.1
335
336
337
Power factor
Instant power
KW-H
0~100
0~65535
0~9999
MW-H
Current time of
multi-step function
Yards counters low 0~7 bit: Current step of
8bits & Current step
multi-step function
of multi-step function 8~15 bit : Yards counters low
8bits
Yards counters high
16bits
- 65 -
334
0~65535
0~999
0.01
0.01KW
0.01KW
H
0.1MWH
1min
341
342
016
1step
343
0255
0.01 yard
338
339
340
344
INVERTER
..
A+ A- B+ B-
A+ A- B+ B-
1/2W 150
R
R+
RT+
T-
Master
R
1/2W 150
R
R
1/2W 150
Fig 13-1
RS485
INVERTER
INVERTER
..
A+ A- B+ B-
A+ A- B+ B-
1/2W 150
R
Data+
Data-
Master
1/2W 150
Fig13-2
- 66 -
ASCII code
30H
31H
32H
33H
34H
35H
36H
37H
Char
ASCII code
38H
39H
41H
42H
43H
44H
45H
46H
Char
CR
LF
ASCII code
3AH
0DH
0AH
- 67 -
Example (hex)
F0
03
06
03
E8
00
07
00
00
- 68 -
ASCII code
: (colon)
F0
03
06
03
E8
00
07
00
00
LRC (2 chars)
CR LF
23
Example (hex)
F0
06
00
80
17
70
Example (hex)
F0
06
00
80
17
70
ASCII code
: (colon)
F0
06
00
80
17
70
LRC (2 chars)
CR LF
17
ASCII code
: (colon)
F0
06
00
80
17
70
LRC (2 chars)
CR LF
17
- 69 -
/* X16 = X15 + X2 + X1 */
/* CRC16 initial */
/* LOOP COUNTER */
/* DATA BUFFER */
FOR (i=1;i=LENGTH;i++)
{
/* BYTE LOOP */
DATA == BUFFER[i];
CRC16 == CRC16 XOR DATA
FOR (j=1;j=8;J++)
{
/* BIT LOOP */
};
};
RETURN(CRC16);
};
- 70 -
Group
Individual
Address
Group address
Global address
Group1
116
241
Group 2
1732
242
Group 3
3348
243
Group 4
49...64
244
Group 5
65...80
245
Group 6
8196
246
Group 7
97112
247
Group 8
113...128
248
Group 9
129...144
249
Group 10
145...160
250
Group 11
161...176
251
Group 12
177...192
252
Group 13
193...208
253
Group 14
209...224
254
Group 15
225...240
255