APPLN07/Settings - Gomathinagar
Rev-0
CTR HV: 500/1
CTR LV: 1250/1
Transformer Data :
Power: 60 MVA
HV voltage: 220 KV
LV1 Voltage: 33 KV
LV2 Voltage : 11kV
Transformer percentage imp: 12.5 %
Transformer vector group: YNyn0d11
Tap +15% & -5% at the rate of 1.25 %
Recommended settings:
Id> 0.2 Iref
Id>> 7 Iref ( should be 10% more than max. inrush current)
Id>>> 15 Iref
m1
0.2
m2
0.8
IRm2 1.5 Iref
Current in CT Secondary
= 1049.75/1250
AREVA T&D
AUTOMATION SUPPORT
19/1 GST Road, Pallavaram, Chennai -600043
Page 2
APPLN07/Settings - Gomathinagar
Rev-0
= 0.839A
Required Ratio compensation = 1 / 0.839 (will be calculated by the relay)
= 1.19
At +15 % tap condition current in HV bias circuit:
Primary current
= 1.054 -1
= 0.054
At +15% Tap Idiff2 = 1-0.868
= 0.132
APPLN07/Settings - Gomathinagar
Rev-0
Ibias1
= 1.054 + 1
2
=1.027
= 0.868 + 1
2
= 0.934
Ibias2
Idiff1
Iop1
= 0.2+(0.2 X1.027)
= 0.4054
= 0.054 = 13%
0.405
Since the differential current is not greater than 90% of the operating current at
-5% tap the relay will operate satisfactorily.
OPERATING CURRENT IOP
At +15% Tap
IOP2 = Is +(0.2 x Ibias2)
= 0.2 +(0.2 x 0.934)
= 0.387
Idiff2 = 0.132 = 34%
Iop2 0.387
Since the differential current is not greater than 90% of the operating current at
-15% tap the relay will operate satisfactorily.
Bias setting shall be kept at
m2
APPLN07/Settings - Gomathinagar
Rev-0
Data Provided by Customer :
Continuous over flux withstand capability : 110%
Withstand capability at 120%
: 1 minute
Withstand capability at 150%
: 1secs
Recommended settings are as below:
Alarms:
Alarms will be generated if V/f value is 1.12 the nominal value after a time delay of 10 secs.
Tripping chararateristic:
Overfluxing tripping IDMT characteristics can be made as per the transformer
withstand specifications .
/Parameters/Function parameters/Parameter subset 1/V/f
Address
| Group
| Description
| Active value
--------------+-------------+----------------------+---------------------------081.210
| V/f
| Enable
PS1 | Yes
081.211
| V/f
| V/f> (alarm) PS1 | 1.12 Vnom/fnom
081.212
| V/f
| V/f(t)>
PS1 | 1.15 Vnom/fnom
081.213
| V/f
| V/f>>
PS1 | Blocked
081.214
| V/f
| tV/f>
PS1 | 10 s
081.217
| V/f
| t at V/f=1.05 PS1 | 1000 s
081.218
| V/f
| t at V/f=1.10 PS1 | 1000 s
081.219
| V/f
| t at V/f=1.15 PS1 | 600 s
081.220
| V/f
| t at V/f=1.20 PS1 | 300 s
081.221
| V/f
| t at V/f=1.25 PS1 | 50 s
081.222
| V/f
| t at V/f=1.30 PS1 | 45 s
081.223
| V/f
| t at V/f=1.35 PS1 | 30 s
081.224
| V/f
| t at V/f=1.40 PS1 | 15 s
081.225
| V/f
| t at V/f=1.45 PS1 | 3 s
081.226
| V/f
| t at V/f=1.50 PS1 | 0.5 s
081.227
| V/f
| t at V/f=1.55 PS1 | 0.5 s
081.228
| V/f
| t at V/f=1.60 PS1 | 0.5 s
081.230
| V/f
| Reset time
PS1 | 0 s
081.229
| V/f
| tV/f>>
PS1 | Blocked
(Note :
1. Out put relays, LED s, Opto inputs front panel etc, need to be configured at site
during commissioning.
AREVA T&D
AUTOMATION SUPPORT
19/1 GST Road, Pallavaram, Chennai -600043
Page 5
APPLN07/Settings - Gomathinagar
Rev-0
2.220/33 KV, 60 MVA TRANSFORMER, REF PROTECTIONRelay type MiCOM P633
CTR : 500/1
R stab calculation
Fault current at 220 kV side neglecting source impedance
FLI/%imp = 157.46/ 0.125 = 1259 A
IF in secondary : 1259/ 500 = 2.51 A
RCT : 10 ohms (assumed)
Lead resistance RL 5 ohms ( provided by the customer)
Vs = If (Rct+2 Rl)
= 2.51 x (10 + (2 5))
= 50.2 Volts
Rstab = Vs
Is
= 502 ohm
Hence recommended stabilising resistor value is 502 ohms
AREVA T&D
AUTOMATION SUPPORT
19/1 GST Road, Pallavaram, Chennai -600043
Page 6