Centurion System Electrical Maintenance Manual

A.3.3 Alarm Signals


Table A-11 shows the alarm signals will be shown on the seven segment display of the SDCS-CON-2 Control
Board as codes A. . . On the LCD of the Common Display Panel CDP-312 the alarm signals will be shown as numbers (without the leading digit 1) with text.
Seven Segment
Display Code
A101

CDP-312
Text

Definition / Action

01 Start Inh

Alarm: Start Inhibition. Check:

Status Signal
(Fault Word)

Reaction

9.04

bit 0

Self resetting after


enable.

9.04

bit 1

Self resetting after


enable.

9.04

bit 5

9.04

bit 6

9.04

bit 3

9.04

bit 10

Parameter settings (P 13.11) and


(P 15.14).
A102

02 Emer Stop

Alarm: EMERGENCY STOP. Check:

Signal binary input DI5.


Logic of a.m. signal parameter
(P13.12), if necessary, invert the
signal.
A103

03 Mot1 Temp

Alarm: Overtemperature MOTOR 1.


Check:

Parameter setting (P 28.10) correct.


A104

04 Mot1 Load

Alarm: Overload MOTOR 1 (Thermal


Model 1). Check:

Overload of motor.
Parameter setting (P 28.03) correct.
A105

05 Conv Temp

Alarm: Overtemperature Power Section.


This signal will already appear approximately 10C (50F) below the shutdown temperature applying for Fault
Signal F4, see max. temperature (P
04.17).
Check:

See Fault Code F4.


A118

18 Main Uvlt

Alarm: Mains Undervoltage (AC). Setting of undervoltage monitoring with


Parameter (P 40.01) and/or (P 40.02).
Check:

See Fault Code F29.


Table A-11: SDCS-CON-2 Alarm Signals

Copyright 2007 P&H Mining Equipment, Inc.


Appendix A, Fault Information.fm

-A.19-

Peak Services
Appendix A, Version 04 - 12/07

"Uncontrolled Copy"

Centurion System Electrical Maintenance Manual

Seven Segment
Display Code
A120

CDP-312
Text
20 Curr dev

Definition / Action
Alarm: Armature Current Deviation. If
the current reference ARM_CUR_REF (P
3.12) deviates from the current feedback for more than 5s by more than
20%, referenced to the rated current,
this signal will be shown. Check:

Status Signal
(Fault Word)
9.04

bit 13

9.04

bit 8

9.04

bit 9

9.04

bit 12

9.04

bit 15

Reaction

Ratio between mains supply voltage and EMF.


A123

23 Mot2 Temp

Alarm: Overtemperature MOTOR 2.


Check:

Parameter setting (P 28.13) correct. See Fault Code F6.


A124

24 Mot2 Load

Alarm: Overload MOTOR 2 (Thermal


Model 2). Check:

Overload of motor.
Parameter setting (P 28.07) correct.
A126

26 Conv Fan

Alarm: No (Thyristor Power) Converter


FAN Acknowledge. Check:

See Fault Code F50.


A127

27 Ext fan

Alarm: No Acknowledge from External


FAN (of Motor). Check:

Contactor circuit/supply for fan


of motor.

Status of binary inputs/outputs


(DI2/DO1) on SDCS-CON-2
board.

Parameter setting (P15.07).


Table A-11: SDCS-CON-2 Alarm Signals

Peak Services
Appendix A, Version 04 - 12/07

-A.20-

Copyright 2007 P&H Mining Equipment, Inc.


Appendix A, Fault Information.fm

"Uncontrolled Copy"

Centurion System Electrical Maintenance Manual

Seven Segment
Display Code
A129

CDP-312
Text
29 Type Code

Definition / Action
Alarm: Type Code (Hardware Code of
Thyristor Power Converter) Changed.
Unit type code stored in memory differs
from the hardware coding. Check:

Status Signal
(Fault Word)
9.05

bit 1

9.05

bit 2

9.05

bit 3

Reaction

New control board SDCS-CON-2


installed?

Control Board SDCS-CON-2 and


SDCS-PIN-xx board interchanged.
Action:

Save values in non-volatile memory using parameter DRIVEMODE (P 15.02) = 22


Special Note: A129 alarm may be seen
when power is taken away from the
supervisory module (AC 80).
A132

32 Aux Uvolt

Auxiliary Voltage Alarm. The auxiliary


voltage (230V) is too low while the
drive is not in operation.
For more details see Fault Code F1.

A133

33 Overvolt

Overvoltage Protection Active. Converter blocked (via DI2 in field exciter


mode).
Table A-11: SDCS-CON-2 Alarm Signals