Sei sulla pagina 1di 100

Energy Automation

Page 1

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

TPICOS PRINCIPAIS:
INSTALAO DO DIGSI
CONFIGURAO/PARAMETRIZAO
DESCRIO DOS CDIGOS: BF E MLFB
COMUNICAO PORTA B
DIFERENA ENTRE UM FIRMWARE E DRIVER
EXPORTAR/IMPORTAR UM IED
DIFERENA ENTRE UM VDADRESS, DEVICE E VARIANT
DIFERENA ENTRE UM UPLOADING E DOWNLOADING
VERIFICAO DOS EVENTOS/OSCILOGRAFIA E
MEDIES/TESTES
FORMA MATRICIAL DE ASSOCIAO DE VARIVEIS

Page 2

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Instalao

Instalao a partir do CD
Componentes do DIGSI 4
Equipamentos SIPROTEC 4 (device drivers)

Passos
Iniciar o Windows
Inserir CD para iniciar o processo de instalao
Digitar o nmero da licena
Selecionar componentes

Iniciar DIGSI 4 pelo menu Iniciar (Start menu)

Page 3

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Estrutura de Projetos no DIGSI 4 Manager

Componentes do Sistema podem ser classificados de acordo com as


necessidades do usurio:
.
Projetos (Project)
Sistemas (System)
Subestaes (Station)
Circuitos (Feeder)
Rels (Device)
Modens (Modems)
Adenda de Telefones (Phone Book)

Page 4

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI4 SIPROTEC 4 Conceito de Matriz

Page 5

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI4 Configurao da Matriz

Page 6

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI4 CONFIGURAO DA MATRIZ

Page 7

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Configurao das Informaes

Estrutura da Matriz
Insero de Informaes
Fonte (Source)
Destino (Destination)
Blocos de Informaes
- Informaes Gerais (Device, general)
- Funes de Proteo (Protection functions)
- Indicaes, Medies e Estatsticas (indications, measured values, statistics)
- Funes Especficas
- Funes do Usurio

Page 8

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Telas Grficas

Tela Normal (Default display)


- Smbolos no Operveis
- Indicao de estados, medies e textos

Tela de Controle (Control display)


- Operaes de Controle
- Indicao de estados, medies e textos

Page 9

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI4 SOFTWARE MANAGER

ABRIR DIGSI4 MANAGER

Page 10

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Definio de novos Projetos

Selecionar a caixa de dilogo correspondente (Menu: File


Digitar o nome do projeto
Definir o diretrio para gravao

New)

Page 11

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Pastas (Folders)

Estrutura

Pastas (Folders) podem conter os seguintes objetos


Sub-pastas
Rels SIPROTEC 4
Rels V3/V2 (verses anteriores do Digsi)
Verses de rels SIPROTEC 4
Conexes via Modem

Page 12

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Estrutura de Projetos

Page 13

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Descrio dos cdigos: BF e MLFB


BF: um endereo que indica o registro de fabricao do IED e
se encontra na parte traseira do rel, como analogia a
impresso digital do mesmo. Ele composto por 10 digtos,
sendo que os 2 primeiros indicam o ano de fabricao, os 2
seguintes o ms, os 2 seguintes o dia e os 4 ltimos o nmero
serial.
MLFB: o cdigo de compra do IED, ele indica a funcionalidade
do mesmo. Mudando-se o MLFB pode-se incrementar no IED,
por exemplo uma outra funo de proteo. A mudana atravs
de um arquivo auto-executvel, realizada pela SAG-Alemanha e
h um custo para este servio, porm h uma exceo para esta
regra quanto comunicao pela porta do sistema: Porta B. Para
tal o cdigo MLFB no precisa ser alterado e suficiente alterar
somente o protocolo de comunicao no parmetro:
Comunication Parameter, detalhado seguir:

Page 14

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Especificao do Equipamento

Propriedades
(MLFB = nmero de encomenda)

Page 15

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exemplo de Procedimentos :
Criar e estruturar um projeto - Parte I

Criar um novo projeto (Project 1).


Inserir pastas em nveis
hierrquicos e com nomes como
mostrado na figura ao lado.

Page 16

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Inserir Equipamentos

Abrir catlogo de equipamentos (View


Device catalog)
Selecionar equipamento
Arrastar e soltar o equipamento na estrutura do projeto

Page 17

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exemplo de Procedimentos :
Criar e estruturar um projeto - Parte II

Inserir os seguintes rels SIPROTEC


4:
Region North: Rel utilizado
neste curso
Substation 1: 7SJ610 V4.0
Feeder 1:

7SJ622 V4.1

Feeder 2:

7SJ622 V4.1
7SJ631 V4.1
Conexo por

Modem

Page 18

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Insero de Rels verses V2/V3

O programa DIGSI 4 Manager pode gerenciar equipamentos (rels) de verses


anteriores (V2, V3).
Antes de inclu-los na estrutura do projeto, estes devem criados utilizando-se o
programa DIGSI V3.
Comando:
Insert DIGSI Existing V2/V3 device

Page 19

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exemplo de Procedimentos :
Criar e estruturar um projeto - Parte III

Inserir um rel Siprotec verso 3


na pasta Feeder 6th Avenue.

Page 20

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Propriedades dos Rels SIPROTEC 4

Menu: Edit

Object properties

Page 21

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Propriedades dos Rels SIPROTEC V2/V3

Menu: Edit

Object properties

Page 22

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Gravar Projetos / Fechar Projetos

Gravar o projeto
Gravar como (Menu: File

Save as...)

- com ou sem reorganizao


(with / without rearrangement)
- definir novo nome do projeto
- definir diretrio de gravao

Gravar (Menu: File

Save)

Fechar o projeto (Menu: File

Close)

Page 23

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exemplo de Procedimentos :
Gravar (save) / Copiar (copy) / Apagar (delete)

Criar um novo projeto chamado Project 2.


Copiar a pasta Substation 2 do projeto anterior (Project 1) para
o novo projeto.
Inserir uma nova pasta com o nome 110kV na pasta Substation
2.
Copiar as pastas Feeder 1 and Feeder 2 do projeto anterior
(Project 1)
Mover o rel 7SJ631 V4.1 da pasta Feeder 2 para a pasta
Feeder 1
Apagar o rel 7SJ622 da pasta Feeder 2.
Inserir um novo rel tipo 7SJ610 V4.0.
Especificar o nmero de encomenda (MLFB).

Page 24

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Abrir Projetos

Menu: File
Open
Pr-ajuste automtico aps o incio do Programa
(global default setting)
ltimos projetos editados
Procurar

Page 25

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Arquivamento / Restaurao de Projetos

Arquivamento de Projetos (Menu: File

Archive)

Fazer selees iniciais


- Selecionar o programa de compactao
- Selecionar a pasta para arquivamento
Configurao do programa de compactao
- Arquivamento em disquete
- Verificao de consistncia (Consistency check)
- Sobrescrever objetos com nomes idnticos
- Criao automtica do caminho para arquivamento

Page 26

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Arquivamento / Restaurao de Projetos

Selees iniciais
Arquivamento
Restaurao

Page 27

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Arquivamento de Projetos

Arquivamento de projeto

Page 28

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Restaurao de Projetos

Restaurao de projetos (Menu: File

Retrieve)

Selecionar arquivo/fonte
Selecionar um destino

Page 29

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Apagamento / Reorganizao de Projetos

Apagamento de projetos (Menu: File

Delete)

Individual
Diversos

Reorganizao de projetos (Menu: File

Reorganize)

Page 30

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exemplo de Procedimentos :
Arquivar / Apagar / Restaurar

Arquivar o projeto Project 1 no diretrio C:\Floppy.


Apagar o projeto Project 1.
Fechar o projeto Project 2 e abri-lo novamente.
Restaurar o projeto Project 1 arquivado no diretrio
C:\Floppy.

Page 31

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Criao de Cpias

Um dado rel pode ser copiado:


Utilizar os comandos do Menu: Edit Copy e Edit Paste.
Ser criado um novo rel.
Nota: O novo rel ter tambm um novo endereo. Portanto
o original e a cpia sero diferentes.

Page 32

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Criao de Cpias Variantes

Para um dado rel pode ser criada uma variante:


Utilizar o comando do Menu: Edit Create variant.
Ser criada uma variante do rel .
Nota: A variante ter o mesmo endereo do rel original.
Portanto o original e a cpia no sero diferentes.

Page 33

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Comparao entre Cpias e Variantes

CPIAS
Um rel deve ser copiado quando existirem dois ou mais rels do
mesmo tipo e os parmetros necessitam ser copiados.
Neste caso o novo rel deve ser inicializado (para assumir o
novo endereo) antes da transferncia dos parmetros.
VARIANTES
Uma variante de um rel deve ser criada quando se requer dois
ou mais conjuntos de parmetros diferentes para um mesmo rel.
Neste caso o rel pode ser inicializado apenas uma vez, pois as
variantes tem o mesmo endereo.

Page 34

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Variantes de Rels - Importar e Exportar

Original: ajustes previstos no projeto


Departamento de Projeto/Engenharia

Exportar

Importar

Verso de comissionamento
do Departamento de Comissionamento

Verso de operao

do Departamento de Operao

Page 35

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exportar e Importar um IED


Quando h muitos IEDs em um projeto como o listado abaixo (71 IEDs) o
arquivo do projeto fica muito grande o que dificulta a transferncia e portanto
quando h a necessidade de se trabalhar com alguns IEDs isoladamente h
a possibilidade de se exportar e importar somente estes IEDs.

Para tanto durante o processo de Exportar um IED h duas


possibilidades para se salvar o arquivo: Variant ou Device, vistos
abaixo:

Page 36

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Exportar Dados do Rel

Abrir a caixa de dialogo (Menu: File Export device)


Definir o destino
Iniciar o processo de exportao (OK)

Page 37

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Importar Dados do Rel

Importar dados do rel como uma variante


Abrir a caixa de dialogo (Menu: File ImportDevice)
Selecionar o arquivo
Iniciar o processo de importao (OK)

Page 38

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Importar Dados do Rel

Importar dados do rel como um novo equipamento


Abrir a caixa de dialogo (Menu: File ImportDevice)
Selecionar o arquivo
Iniciar o processo de importao (OK)

Page 39

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Variantes de Rels

Uma variante de um rel criada da seguinte forma


Gerar uma variante de um rel SIPROTEC 4
Importar os dados do rel
Obter os ajustes por conexo ao rel (opo Plug & Play)

Page 40

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre um: VD Address, Variant e Device

Para o Digsi, VD Address um endereo utilizado para referenciar o


IED. Se o arquivo for Variant significa que o VD Address permanecer
o mesmo, se for Device ele mudar.

Page 41

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre um: VD Address, Variant e Device


Por exemplo vamos exportar o arquivo: AT01-52A.

Observar que a extenso do arquivo ser: *.dex

Page 42

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre um: VD Address, Variant e Device

Importando o arquivo

Observar que h duas possibilidades: Variant ou Device. Escolhendo


Variant caso haja um sistema com o SICAM no ser possvel realizar a
comunicao via sistema.

Page 43

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Exemplo de Procedimentos :
Trabalho com Variantes

Criar uma nova variante do rel na pasta Region North


denominada Meu_rele1. Alterar algum parmetro.
Exportar a variante para o arquivo Meu_rele1.dex no
diretrio C:\Floppy).
Importar o arquivo exportado como uma variante
denominada Meu_rele2.
Alterar a parametrizao do rel original.
Importar o arquivo exportado como um novo rel e substituir
o original.

Page 44

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Parametrizao e Configurao


Sem Conexo ao Rel (Offline)

Trabalho com SIPROTEC 4


no modo Offline

Page 45

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Ajustes do Rel

Abrir rel
Abrir rvore de Seleo
Selecionar Ajustes (Settings)

Page 46

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Configurao do Rel

Selecionar Configurao do Rel (Device Configuration)

Page 47

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Grupos de ajustes

Edio
Mostrar Grupo de Ajustes Ativado
Selecionar Grupo de Ajustes
Copiar
Reajuste (Reset)
Exportar Ajustes de Proteo

Page 48

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Definio do Grupo de Ajustes

Definir Grupo de Ajustes

Page 49

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Seleo do Grupo de Ajustes

Seleo com DIGSI 4


Entrada binria
Sistema de Superviso
via Protocolo

Page 50

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Edio dos Ajustes do Rel

Definio de Ajustes do Rel

Page 51

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Edio dos Dados do Sistema

Definio de dados de alto nvel

Page 52

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Definio de Interfaces

Definio dos parmetros para interface com micro-computador

Page 53

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Sincronizao do Relgio Interno

Definio dos parmetros para sincronizao do relgio interno

Page 54

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Senhas de Proteo

Definio de Senhas (Password)

Page 55

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Senhas de Proteo

Senhas (Password)
Definio
Alterao

Page 56

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Senhas de Proteo

Senhas (Password)
Ativao
Desativao

Page 57

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Senhas de Proteo

Reset de todas a Senhas

Page 58

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Parametrizao

Configurao das informaes


Configurao de funes CFC
Configurao dos telas

Page 59

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Configurao das Informaes

Page 60

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Configurao das Informaes

Estrutura da Matriz
Insero de Informaes
Fonte (Source)
Destino (Destination)
Blocos de Informaes
- Informaes Gerais (Device, general)
- Funes de Proteo (Protection functions)
- Indicaes, Medies e Estatsticas (indications, measured values, statistics)
- Funes Especficas
- Funes do Usurio

Page 61

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Configurao das Informaes

Trabalho com a Matriz de Configurao


Configurao
Insero de Informaes
Mudana da Apresentao

- expandir e comprimir grupos e colunas


Filtro

- por informao
- por tipo de configurao

Page 62

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Propriedades dos Objetos

Indicao Simples
(Single Point Indication SP)

Page 63

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Telas Grficas

Tela Normal (Default display)


- Smbolos no Operveis
- Indicao de estados, medies e textos

Tela de Controle (Control display)


- Operaes de Controle
- Indicao de estados, medies e textos

Page 64

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

DIGSI 4 - Telas Grficas

Page 65

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Editor de Display Mmico no DIGSI 4

Display mmicos podem


ser criados utilizando-se
uma biblioteca de
smbolos.
Flexibilidade para retratar
as configuraes
primrias da instalao.

Page 66

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Comunicao pela
porta de Sistema B

Page 67

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Comunicao pela porta de sistema


Vamos alterar o protocolo de comunicao IEC-103 tico da porta B
para o protocolo DNP3.0 tico.
Observar que o MLFB permanece o mesmo: Porta B ou System Port

Page 68

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Comunicao pela porta de sistema


Para realizar a mudana deve-se escolher o protocolo em
Communication modules, conforme abaixo:

Escolha do
protocolo de
comunicao

Page 69

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre um
Driver e um Firmware

Page 70

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre um Driver e um Firmware


Em uma comunicao serial frontal vamos associar o Driver instalado no
computador e o firmware instalado no IED. Vamos supor que a Siemens
SAG lanou um firmware(disponvel no site: www.siprotec.com) para o
rel 7SJ62 e vamos alterar a verso 4.6 para 4.7. Como analogia vamos
supor que este novo firmware 4.7 possui uma nova funcionalidade e
portanto esta nova funcionalidade dever ser acessada pelo Digsi.
Assim como regra deveremos ter: Verso Firmware>=Verso Driver
sendo que a condio ideal : VFirmware = VDriver.
Verso do Driver
instalado no
computador(Digsi)

Idioma, para norma


ANSI escolher: English
(US)

Page 71

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre
Uploading/Downloading

Page 72

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre Uploading e downloading

Para se evitar alguma operao errada, recomenda-se utilizar sempre o


ltimo back-up quando isto no ocorrer deve-se utilizar a ferramenta:
Compare Parameter disponvel em Edit para verificar eventuais
modificaes.

Page 73

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre Uploading e downloading


partir da Verso do software Digsi V>=4.70 possvel alterar o
endereo de VD Address, como pode ser observado na folha 6.
Alm da comunicao em rede com o SICAM que afetada quando se
altera o VD Address no possvel realizar a comunicao frontal pois
o endereo que est no IED diferente do que est no arquivo do rel
no Digsi, portanto importando-se o arquivo como Variant e estando a
verso do software V<4.70 no possvel realizar a comunicao
frontal com o IED.
Como uma alternativa para este caso pode-se realizar a comunicao
entre o software e o IED via Plug&Play.

Page 74

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Diferena entre Uploading e downloading


Segue abaixo o modo de comunicao:

O arquivo ter a
extenso: Variant, ou
seja ter o mesmo VD
Address.

Page 75

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Verificao dos
Eventos/Oscilografia/Medies/Testes

Page 76

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Verificao dos Eventos/Oscilografia e medies/testes


A maneira matricial de como o software Digsi trabalha:
Texto Curto e
Longo

Entradas

Leds
Sadas

Page 77

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Verificao das Entradas e Sadas


Exemplo de configurao de entrada e sada:
Por exemplo: A entrada digital 01 ser sensibilizada para a funo >Manual
Close e a sada 01 ter a funo: Relay Trip associada.

Entrada Digital 01

Sada Digital 01

Para os Leds segue a mesma lgica.

Page 78

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Forma Matricial de Associao de Variveis

A forma Matricial de como os rels Siemens trabalham torna-se uma vantagem


em relao aos outros fabricantes uma vez que h uma melhor visualizao
das variveis envolvidas. O desafio para um melhor entendimento est em
compreender o banco de dados das variveis. Um outra vantagem que o
software Digsi comunica com todos os rels Siprotec, logo a forma de
parametrizao/programao a mesma para todos os rels.
Veremos a seguir como realizado o roteamento para as funes: Event
Log, Trip Log, Oscilografia e qual a capacidade do rel para com os
mesmos.

Page 79

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Forma Matricial de Associao de Variveis

Event Log

Trip Log

Event Log:
Funo
Sensitiva Terra

Page 80

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Forma Matricial de Associao de Variveis


Quanto capacidade de processamento do rel temos que:
Event Log: O rel registra os ltimos 200 Eventos
Trip Log: O rel registra as ltimas 8 faltas com um total de 600 mensagens
Sensitive Earth Fault: O rel possui uma tratativa especial para faltas terra
sensitiva tendo a mesma forma de registro que o Trip Log.
Oscilografia: O rel registra as ltimas 8 oscilografias sendo possvel configurar
at 40 dados digitais.
Spontaneous Annunciation (Medio em Tempo Real dos Eventos com
resoluo mnima de 1mseg e registro das ltimas 1000 linhas.
General Interrogation (Fotografia do estado atual das variveis)
Alm dos modos de registro o rel possui uma poderosa ferramenta de teste,
acessada somente no modo On-Line. Esta ferramenta possibilita testar as
entradas, sadas e leds e tambm algumas funes do algoritmo, como: Pickup, Trip, Bloqueio, etc...

Page 81

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Variveis utilizadas no Controle do Digsi


A terminologia adotada para as variveis :
Controle Simples (Single Control)
Controle Duplo (Double Control)
Indicao Simples (Single Point Indication)
Indicao Dupla (Double Point Indication)
1 Plo (Single Pole)
2 Plos (Double Pole)
Realimentao (Feedback)

Page 82

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Simples / Controle Duplo - 1 Plo / 2


Plos
Controle Simples
Controle Duplo
Lmpada
Ligar - Desligar
Bobina de Operao nica
Abrir - Fechar
(Contator)

1 Plo
BO1

Plo
Contato de
Rel

1 Plo

(sada binria)

2 Plos

BO1

52
52TC

BO2
52CC

BO3

Page 83

Maio-09

Eng Rafael Fernandes

(+)

(-)

Siemens EA 2009
Power Transmission and Distribution

Indicao Simples / Indicao Dupla Realimentao


Entradas / Realimentao
Contatos Auxiliares de Disjuntores, Seccionadores
Indicao Simples / Indicao Dupla
Bloqueio de Proteo, ...

Indicao Dupla

52

52b

Indicao Simples

52a
OU
52b

Realimentao para o Rel

Page 84

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Simples (Single Binary Output)


1 Plo

Configurao dos
Contatos na Matriz
BO1
1
Equipamento x

Sinal

Equipamento

Binary Output (Sadas


Binrias)
2

Page 85

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Duplo
1Plo

Configurao dos
Contatos na Matriz
BO2

BO1
Equipa 52TC
mento

Equipa
mento

x x
Abrir
Fechar

52CC

Binary Output (Sadas Binrias)


1 2

52TC = Bobina de Abertura


52CC = Bobina de Fechamento

Contatos de Abrir e Fechar


devem ser seqenciais

Page 86

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Duplo
1 Plo para Abertura -2 Plos para Fechamento
Configurao dos
Contatos na Matriz
Binary Output (Sadas
Binrias)

BO2

BO1

1
52TC

52CC

Equip.
BO3

52TC = Bobina de Abertura


52CC = Bobina de Fechamento

x x x
Abrir
Fechar 1
Fechar 2

Equip.

2 3

Contatos de Abrir, Fechar 1 e Fechar 2


devem ser seqenciais

Page 87

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Duplo 1 Plo


Abrir/Fechar/Comum

Configurao dos
Contatos na Matriz
BO2

52TC

Binary Output (Sadas Binrias)


1 2 3
Equip. x

52CC

BO3

x x

Abrir
Fechar
Comum

BO1

52TC = Bobina de Abertura

Contatos de Abrir, Fechar e Comum

52CC = Bobina de Fechamento

devem ser seqenciais

Page 88

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Duplo Mltiplo


1 Plo Abrir 1Plo Fechar 1Plo Comum

52TC

BO7

BO2

52CC

52TC

Configurao dos
Contatos na Matriz

BO8

52CC

Binary Output (Sadas Binrias)


1 2 3
7 8 9
DJ 1
DJ 2

x x x
x

x x

Abrir
Fechar
Comum

BO1

Disjuntor ...n

BO3

Abrir
Fechar

Disjuntor 1

Contatos de Abrir e Fechar


52TC = Bobina de Abertura
52CC = Bobina de Fechamento

devem ser seqenciais


Comum livremente configurvel

Page 89

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle Duplo
2 Plos Abrir 2 Plos Fechar
Configurao dos
Contatos na Matriz
Binary Output (Sadas
Binrias)

BO2

BO1

1 2 3
52TC

Equip.

52CC

BO3

BO4

x x x x
Abrir
Fechar
Abrir
Fechar

Equip.

52TC = Bobina de Abertura

Contatos de Abrir e Fechar

52CC = Bobina de Fechamento

devem ser seqenciais

Page 90

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Controle de Motores (somente para


7SJ63/6MD3) Contatores de Potncia

BO4.1
J4

BO5.2

J3

(+)

BO5.1
BO4.2
J2 (-)
J1 (+)
J2 (-)
J3

BO4
BO5

Os pares de contatos de potncia


so intertravados entre si.
Configurao dos
Contatos na Matriz

Motor

Binary Output (Sadas


Binrias)
4 5

x x
M

J4

A Frente
Reverso

J1

BO6

K18

Ativao

BO7

K17

Nenhuma Motor Parado


Par de Contatos 4
Frente
Par de Contatos 5 Reverso

Page 91

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Indicaes Simples

Bloqueio da Proteo
Rel de Gs

F10
F11

BI1

F12
F13
F15

BI3

F16
F14
F17
F18

Rel de Nvel

BI2
BI4

Configurao dos
Contatos na Matriz

BI5
BI6

Binary Intput (Entradas


Binrias)

BI7

2 3
Bloqueio da Proteo
Rel de Gs

4 5

6 7

x
x

Rel de Nvel

Page 92

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Indicao Dupla (1)

52b
52a

F10
F11

BI1

F12
F13
F15

BI3

BI2

Configurao dos
Contatos na Matriz

BI4
BI5

F16
F14
F17
F18

BI6

Binary Intput (Entradas


Binrias)
2 3 4 5 6 7

BI7

52b/a

x x

52b = Contato Normalmente Fechado


52a = Contato Normalmente Aberto

Page 93

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Indicao Dupla (2)

(+)

52b

BI4

52a

BI5

(-)

Os contatos normalmente fechados devem ser


ligados sempre antes dos contatos normalmente
abertos, isto :
Contato normal. fechado (52b) = BO n
Contato normal. aberto (52a) = BO n+1
Configurao interna dos bits
Disjuntor Aberto ==> 1
0
Disjuntor Fechado==> 0
1

Disjuntor

52

Page 94

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Tratamento de Posies Intermedirias: 2 Opes

DP 0=not valid (invlido)


Posio Intermediria processada como 3 (bits 1 1)

52b
52a
52b
52a

Posio Intermediria processada como 3 (bits 1 1)


DP_I intermediate (intermediria)
Posio Intermediria processada como 0 (bits 0 0)

52b
52a

Posio Intermediria processada como 3 (bits 1 1)

52b
52a

Page 95

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Posio Intermediria no Catlogo de Informaes:


Information Catalog

DP
0= Not valid
(invlido)
DP_I
0= intermediate
(intermediria)

Page 96

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Vantagens da Indicao Dupla e comando por 2 plos

52b

52CC
52a

Indicao Dupla Detecta


Falha no Disjuntor
Interrupo na fiao
Curto-circuitos na fiao
Falha nas entradas binrias

Comando por 2 Plos Evita


Comando indevido por
Curto-circuitos na fiao
Falha nas sadas binrias

Operao Segura

Page 97

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Intertravamentos Internos

Intertravamentos - CFC

52 Breaker

0
1

52 Open

Page 98

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Possibilidade de Intertravamento

Subestao1
Subestao2

ATUAO DAS
PROTEES

TELAS DE COMANDO

COMANDO CENTRAL (DIGSI 4, SCADA)

Page 99

Maio-09

Eng Rafael Fernandes

Siemens EA 2009
Power Transmission and Distribution

Fim!