Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Normal and heavyweight concrete density is assessed on target values with tolerances of 100kg/m3 on the average density
calculated on groups of results or 130kg/m3 on individual results. However, it is not intended that density on normal-weight
concrete be made a specification requirement. Density is determined in accordance with BS EN 12390-7.
Chloride Classes
BS EN 206-1 has introduced the concept of chloride class and this will have to be declared on all delivery tickets for designed concrete and may
have to declared for other concretes where required by the specifier.
Table 6:
Chloride classes
BS 8500 recommends that, where concrete is to be prestressed and where concrete contains reinforcement or other metal that is to be heat cured,
chloride class Cl 0,10 should be specified. Other concrete that contains reinforcement or other embedded metal should be specified as chloride
class Cl 0,40 except where SRPC (sulfate resisting Portland cement conforming to BS 4027) is used in this situation chloride class Cl 0,20 should
be specified.
Concrete Types
The traditional UK methods of specifying concrete have been retained in BS 8500 and one other concrete type added. In future one should refer
to "concrete type" instead of "mix type". Therefore it is incorrect to use the term " designed mix", the correct term is now "designed concrete".
Conformity
The European Standard has introduced the concept of Conformity evaluation, this requires the concrete producer to take
responsibility for declaring that the concrete conforms to the requirements of the standard based on regular testing and
statistical analysis of ongoing results. Where a purchaser tests concrete this is termed identity testing. Identity testing is based on a very limited
number of results obtained over a very short time period, whereas conformity evaluation is based on results obtained over an extended period of
time. Third party quality assurance bodies will check the records of readymixed concrete producers to verify they are implementing the conformity
procedures correctly.
On the 1st of December 2003 the UK Concrete Standard BS 5328 (published in four parts) will be withdrawn. This Standard is being replaced by
two Standards, a European Standard and a complementary British Standard, these are:
Some individuals may question which of the standards they should use, the answer is that both Standards need to be used to specify concrete.
BS EN 206-1 is applicable across the whole of the European Union and at present it has not been possible to agree all the parameters that need to
be included in a concrete specification. For example, the requirements for concrete to resist attack from aggressive agents (e.g. ice, snow etc)
in the Nordic countries are different to those required in the Mediterranean region because of local climatic conditions. The European Standard
(BS EN 206-1) has identified these parameters, which are called environmental actions, but has not given advice on how to specify concrete to resist
durability failures. This is given in Part 1 of the UK complementary Standard. It should also be noted that the majority of the testing standards
within the BS1881 series are also being withdrawn.
Workability -- Consistence
The term workability has been dropped from the new concrete standards and replaced by the term consistence.
Measurement of Consistence
There are four methods of assessing (measuring) consistence given in the European Standard (BS EN 206-1), these are:
Slump test
Vebe test
Generally, only the slump test and the flow table test will be called up in specifications in the UK (BS 8500 only lists these two tests). It should be
noted that the degree of compactability test is not the same as the compacting factor test, which has been used in the UK for many years.
(Concrete is sampled in accordance with BS EN 12350-1).
Specification of Consistence
The specification of consistence will in future be by consistence class. The classes for the slump test are:
Slump classes
Table 1:
Table 2:
Slump target tolerances
Where a customer requires a concrete with a slump, which is at a level other than the mid point of a slump class, they should order a Target slump,
a set of tolerances apply to the target value as shown in Table 2. It should be noted that slump measurements are reported to the nearest 10mm
instead of the current practice of reporting to the nearest 5mm.
Table 3:
Flow classes
Flow may also be specified by target values, the tolerance for all values is +30mm for conformity evaluation, for a single
composite sample it is -45, +60mm and for a single spot sample taken from the initial discharge -55, +70mm.
Flow is
reported to the nearest 10mm instead of the nearest 5mm as in BS 1881, the Flow Table test is undertaken in accordance with BS EN 12350-5.
Specifying Strength
Traditionally, in the UK concrete compressive strength has been specified by a compressive strength grade e.g. C30. This represents the strength
achieved by a cube when tested at twenty-eight days.
C40/50
A further change in terminology is that the term strength grade has been dropped and replaced by the term strength class. Traditionally, strength
classes have increased in most instances by increments of 5N/mm2 (i.e. 15, 20, 25, 30). The fact that cylinders are the primary design values has
led to some changes to this approach due to the conversion from cylinder to cube strength. Table 4 shows the range of strength classes that have
strength classes
Table 4:
Compressive
been adopted for normal weight and heavy-weight concrete and or light-weight concrete. It should be noted that the classes are different and that
light-weight concrete is indicated by the designatory letters "LC". The two strength classes marked with an asterisk (C28/35 and C32/40) are not
included in BS EN 206-1, but have been included in BS 8500 to take account of UK durability requirements.
Air Content
BS 5328 specified a target value with tolerances either side of the target. The new Standards have adopted a different approach and air
entrainment is now specified by a minimum value with a tolerance of +4%. The quantity of air entrainment is still related to the
maximum aggregate size:
40mm maximum aggregate size
20mm maximum aggregate size
10mm maximum aggregate size
This makes little difference to current practice, as normally a concrete producer would target the middle of the range (e.g. for a 20mm maximum
aggregate size target 5,5%). Air content is measured in accordance with BS EN 12350-6.
Table 5:
Density classes for
light-weight
concrete
An alternative approach is to supply to a target density, the tolerance is +100kg/m3 on the average density calculated on groups of results
or +130kg/m3 on individual results.