Siemens Vacuum
Recloser 3AD
Medium-Voltage Equipment
Catalog HG 11.42 2008
Contents
Contents
Page
Description
General
Switch unit
13
14
Product Selection
15
16
17
Selection of controller
20
24
Technical Data
27
28
28
Voltage level 27 kV
29
Voltage level 38 kV
29
Annex
33
Inquiry form
34
Configuration instructions
35
Configuration aid
Foldout page
Siemens AG 2008
R-HG11-300.tif
Description
Contents
Contents
Page
Description
General
Switch unit:
Recloser principle
Design
Pole assemblies
Operating mechanism
Magnetic actuator
Mechanical lockout
Recloser cycle
R-HG11-301.tif
Controller:
User interface
Protection functions
10
Communications
11
Protocols
11
Metering functions
11
Data records
11
Software
12
Standards
12
Ambient conditions
13
13
13
14
Scope of delivery
14
Description
General
Switch unit
R-HG11-303.tif
R-HG11-302.tif
Description
Switch unit
Recloser principle
Reclosers are used in distribution systems of power supply
companies (utilities). Like circuit-breakers they are capable
of switching normal and fault currents. They are equipped
with sensors and a controller being the protection and
control device. In case of a line fault, they can break and
make several times, thus avoiding longer network interruptions due to temporary faults.
1
R-HG11-304.tif
Pole assemblies
Each vacuum interrupter is embedded in an epoxy-resin pole
made out of weather-proof cycloalyphatic resin. This enables
a small design as well as resistance against environmental
effects. The vacuum interrupter is vertically mounted inside
the pole, providing a long service life. Each recloser is equipped with an integrated current transformer. For special protection purposes, a resistive voltage sensor can also be
incorporated in the pole. The accuracy achieved in this way
is much higher than that of capacitive dividers.
R-HG11-305.tif
Operating mechanism
HG11-2728 eps
Description
Switch unit
Mechanical lockout
A mechanical lockout enables tripping independently on the
controller. If this handle is pulled, the recloser opens and is
simultaneously locked out electrically and mechanically. The
handle stays extended, thus indicating the interlocked state.
R-HG11-306.tif
The second and third interruption has a definite or inversetime delay. Thus, downstream fuses in the network have the
chance to operate and isolate the affected network section,
restoring normal operation in the remaining network. The
following dead time is usually 210 s (user settable).
The fourth (optional up to the fifth) interruption is fast
again and serves as a check. This for example utilizes the
physical effect that, when the short-circuit occurs, the lines
move due to the magnetic forces of the current, and foreign
objects are shaken off.
R-HG11-307.tif
If the fault still exists, the recloser turns to the lockout and
can only be closed from the operator panel or via SCADA.
Description
Controller
The controller
The Siemens Argus-M controller is based on the Argus-M
directional overcurrent protection relay. These relays provide
protection, control, monitoring, instrumentation and metering with integrated input and output logic, data logging
& fault reports.
R-HG11-308.tif
Argus-M controller
R-HG11-309.tif
Description
Controller
Protection functions
(in order of ANSI numbering)
37 Undercurrent
Each element has settings for pickup level and Definite Time
Lag (DTL) delays. Operates if current falls below setting for
duration of delay.
46BC Broken conductor/phase unbalance
Element has settings for pickup level and DTL delay. With the
circuit-breaker closed, if one or two of the line currents fall
below setting, this could be due to a broken conductor.
46NPS Negative phase-sequence overcurrent
Each element has user settings for pickup level and Inverse
Definite Minimum Time Lag (IDMTL) or DTL delay. It operates
if NPS current exceeds setting and delay. NPS current elements can be used to detect unbalances on the system or
remote earth faults when a delta-star transformer is in
circuit.
49 Thermal overload
The thermal algorithm calculates the thermal states from the
measured currents and can be applied to lines, cables and
transformers. Outputs are available for thermal overload and
thermal capacity.
50/51 Phase fault
50 INST (instantaneous)/DTL (Definite Time Lag) and
51 IDMTL (Inverse Definite Minimum Time Lag)/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and
time delays. The user can select IEC or ANSI time current
characteristics. The IDMT stage has a user programmable
reset characteristic, either DTL or shaped current/time reset
characteristic to improve grading with electromechanical
protection.
50G/51G/50N/51N Earth fault/sensitive earth fault
Earth-fault current is derived from the residual connection of
the 3 integrated line CTs. 50 INST/DTL and 51 IDMTL/DTL
elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and
time delays. The user can select IEC or ANSI time current
characteristics. The IDMT stage has a user programmable
reset characteristic, either DTL or shaped current/time reset
characteristic to improve grading with electromechanical
protection.
50BF Circuit-breaker fail
The circuit-breaker fail function is triggered from an internal
trip signal. Line currents are monitored following a trip signal
and an output is issued if any current is still detected after a
specified time interval. This can be used to re-trip the CB or
to back-trip an upstream CB. A second back-trip time delay is
available to enable another stage to be utilized if required.
10
Description
Controller
Metering functions
81 Under/overfrequency
Each element has settings for pickup level, drop-off level and
Definite Time Lag (DTL) delays. It operates if frequency exceeds setting for duration of delay. It is typically applied in
load shedding schemes.
79 Auto-reclose
Event records
Each element provides independent phase-fault and earthfault/sensitive earth-fault sequences of up to 5 trips, i.e.
4 reclose attempts before lockout. Auto-reclose sequence
can be user set to be initiated from internal protection
operation or via binary input from an external protection.
Each trip in the sequence can be user set to be either instantaneous (fast) or delayed. The user can set each reclose
(dead) time and the reclaim time.
Frequency
Waveform records
Circuit-breaker trip counters
It summation for contact wear
Direction
Primary line and phase voltages
Secondary voltages
Communications
Front USB port
Rear RS485 port
Optional functions
Rear fiber optic ports
IRIG-B ports
Data records
Sequence of event records
Up to 5000 events can be stored.
Fault records
RS232 ports
The last 10 fault records are displayed on the HMI, with time
and date of trip, measured quantities and type of fault.
Protocols
Disturbance recorder
IEC 60870-5-103
The waveform recorder stores analog data for all phases, the
states of protection functions, binary inputs, LEDs and binary
outputs with pre & post trigger data. A record can be triggered
from protection function, binary input or via data communications. The waveform recorder stores up to 10 s data.
Modbus RTU
DNP 3.0
11
Description
Controller, standards
Software
Reydisp Evolution
For communication with the relay via a PC (personal
computer) a user-friendly software package, Reydisp
Evolution, is available to allow transfer of relay settings,
waveform records, event records, fault data records,
instruments/meters and control functions. Reydisp Evolution
is compatible with IEC 60870-5-103.
R-HG11-310.tif
Programmable logic
12
Description
Ambient conditions, altitude correction factor and number of operating cycles
Ambient conditions
The recloser is designed for the normal operating conditions
defined in ANSI C37.60. This comprises an ambient temperature from 40 C to +55 C plus solar radiation.
55C
HG11-2515a_en eps
-40C
1.50
U0
Ka
Example
For a requested rated lightning impulse withstand voltage
of 75 kV at an altitude of 2500 m, an insulation level of
90 kV under standard reference atmosphere is required as
a minimum:
90 kV W 75 kV x 1.2
1.40
1.30
1.20
HG11-2517c_en eps
U W U0 x Ka
1.10
1.00
1000
1500
2000
2500
13
Description
Product range overview and scope of delivery
Rated
short-circuit
breaking current
Rated
lightning impulse
withstand voltage
kV
kA
kV
12
15.5
12.5
12.5
16
12.5
12.5
16
12.5
16
27
38
400 A
95
110
110
125
150
150
170
170
n
n
n
630 A
800 A
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Scope of delivery
Standard equipment
Switch unit
Operating mechanism
Operating mechanism
housing
Switching medium
Insulation
Power supply
Position indicator
Operations counter
Interlocking
Configuration
Sensors
Controller and
control cubicle
Cubicle
Socket outlet
Controller size
Number of inputs/
outputs for customer use
Temperature range
Control keys
Controller interfaces
14
Optional available
Remarks
Stainless steel
Stainless steel
Country-specific design
E12 (= 12" width)
Additional BI/BO and 12 LEDs
40 C
Customer-specific pushbuttons or
rotary CLOSE/OPEN switches
RS232, fiber optic, IRIG-B
Product Selection
Contents
Contents
Page
Product Selection
15
16
17
17
Voltage level 27 kV
18
Voltage level 38 kV
19
R-HG11-311.tif
Selection of controller:
20
20
Controller size
21
Auxiliary voltage
21
22
Communication protocols
22
Communication interfaces
22
Function packages
23
23
24
25
R-HG11-312.tif
Recloser configuration
Control cubicle
15
Product Selection
Ordering data and configuration example
Order codes
Individual equipment versions, marked with 9 or Z in the 8th
to 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.
a: alphabetical
Position:
Order No.:
1st position
n: numerical
10 11 12
13 14 15 16
3 A D n
Order codes
n n n
Primary part
Superior group
Switching devices
2nd position
Main group
Circuit-breaker
3rd position
Subgroup
Outdoor vacuum recloser
Basic equipment
Design and ratings
of the vacuum recloser
Secondary part
Controller, sensors, cables and
other necessary data
Order codes
Group of 3 after the Order No.
Format: a n a
Special versions ( )
Initiated with -Z
Group of 3 after the Order No.
Format: a n n
Configuration example
In order to simplify the selection of the correct order number
for the requested recloser type, you will find a configuration
example on each page of the chapter Equipment Selection.
For the selection of the auxiliary voltages, the fixing options,
the controller, etc. always the last example of the primary
part was taken over and continued, so that at the end of the
equipment selection (page 24) a completely configured
recloser results as an example.
16
3 A D 6
n n n n n
n n n n
Product Selection
Selection of primary ratings
12 kV
Position:
Order No.:
50/60 Hz
3 A D
n n n n
n n n n n
10 11 12
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
D
D
D
D
D
D
D
D
1
3
4
6
1
3
4
6
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
1
3
4
6
1
3
4
6
1
3
4
6
1
3
4
6
1
3
4
6
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
1
1
1
1
2
2
2
2
3
3
3
3
2
2
2
2
3
3
3
3
3 A D 6
13 14 15 16
n n n n
Order codes
n n n
kV
kV
kV
kA
12
75
42
12.5
630
800
See page 24
See page 23
See page 23
See page 22
See page 22
See page 22
See page 21
See page 21
See page 20
Ir
See page 20
Isc
Three-phase for
loop automation
Rated short-circuit
breaking current
Ud
3 x single-phase/
single-triple
Rated short-duration
power-frequency
withstand voltage
Up
Three-phase
Ur
Single-phase
Rated voltage
Type
15.5 kV
50/60 Hz
Ur
Up
Ud
Isc
Ir
kV
kV
kV
kA
15.5
110
50
12.5
400
630
800
16
630
800
Configuration example
Siemens vacuum recloser 3AD
Rated voltage Ur = 15.5 kV
Rated lightning impulse withstand voltage Up = 110 kV
Rated short-duration power-frequency withstand voltage Ud = 50 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 630 A
Type: Three-phase recloser for loop automation
Example for Order No.:
Order codes:
3 A D
n n n n n
n n n n
Siemens HG 11.42 2008
17
Product Selection
Selection of primary ratings
27 kV
Position:
Order No.:
50/60 Hz
n n n n
n n n n n
kV
kV
kA
125
60
12.5
400
630
800
60
12.5
400
630
800
16
630
800
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1 3 2 1
3 3 2 1
4 3 2 1
6 3 2 1
1 3 2 2
3 3 2 2
4 3 2 2
6 3 2 2
1 3 2 3
3 3 2 3
4 3 2 3
6 3 2 3
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
Configuration example
Siemens vacuum recloser 3AD
Rated voltage Ur = 27 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 60 kV
Rated short-circuit breaking current Isc = 12.5 kA
Rated normal current Ir = 400 A
Type: Three-phase
Example for Order No.:
Order codes:
Siemens HG 11.42 2008
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
10 11 12
13 14 15 16
n n n n
Order codes
n n n
3 A D
3 A D 3
n n n n n
n n n n
See page 24
See page 23
See page 23
See page 22
See page 22
See page 22
See page 21
See page 21
See page 20
See page 20
kV
27
Three-phase for
loop automation
Rated short-circuit
breaking current
Ir
3 x single-phase/
single-triple
Rated short-duration
power-frequency
withstand voltage
Isc
Three-phase
Ud
Single-phase
Rated voltage
Up
18
Type
Ur
150
3 A D
Produt Selection
Selection of primary ratings
38 kV
Position:
Order No.:
50/60 Hz
3 A D
n n n n
n n n n n
10 11 12
13 14 15 16
n n n n
Order codes
n n n
kV
kV
kV
kA
38
170
70
12.5
630
800
16
630
800
Configuration example
Siemens vacuum recloser 3AD
Rated voltage Ur = 38 kV
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-duration power-frequency withstand voltage Ud = 70 kV
Rated short-circuit breaking current Isc = 16 kA
Rated normal current Ir = 800 A
Type: Single-phase
Example for Order No.:
Order codes:
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
See page 24
See page 23
See page 23
See page 22
See page 22
See page 22
See page 21
See page 21
See page 20
Ir
See page 20
Isc
Three-phase for
loop automation
Rated short-circuit
breaking current
Ud
3 x single-phase/
single-triple
Rated short-duration
power-frequency
withstand voltage
Up
Three-phase
Ur
Single-phase
Rated voltage
Type
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
On request
3 A D
on request
3 A D
n n n n n
n n n n
Siemens HG 11.42 2008
19
Product Selection
Selection of controller
Options
Recloser for pole mounting 1) incl. cubicle, controller and control cable
Recloser for substation application incl. cubicle and controller
Switch unit only (w/o cubicle, controller and control cable) 2)
10 11 12
n n n n n
1
2
3
13 14 15 16
n n n n
9th position
Current and voltage measuring
Current transformers
1 integrated CT
per pole
Voltage sensors
1 integrated sensor
per pole
(including sensor cables)
n
n
n 1)
n
n 1)
3 x external VTs
(to be defined as
accessories)
A
B
C
n 1)
Configuration example
Siemens vacuum recloser 3AD
3 A D
(Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)
Type: Three-phase
3
Recloser for pole mounting incl. control cubicle and control cable
Current and voltage measuring: current transformers, 1 integrated CT per pole
Example for Order No.:
Order codes:
20
3 A D 3
1
A
1 A
n n n
n n n n
Order codes
n n n
See page 24
See page 23
See page 23
n n n n
See page 22
See page 22
See page 22
3 A D
See page 21
Position:
Order No.:
See page 21
8th position
Recloser configuration
Product Selection
Selection of controller
16
13
23
33
43
n
n
n
n
n
n
n
n
n
n
n
n
n
14
n
n
n
n
10 11 12
n n n n n
n
n
22
See page 22
13 14 15 16
n n n n
Order codes
n n n
30
A
B
C
D
E
n
n
See page 24
See page 23
n n n n
See page 23
See page 22
See page 22
3 A D
12
Function keys
E10 E12
Position:
Order No.:
Number of
tri-color LEDs
Controller size
10th position
Controller size
11th position
Auxiliary voltage
DC voltage
AC voltage
Configuration example
Siemens vacuum recloser 3AD
(Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)
Type: Three-phase
Controller size: E12, 12 function keys,
16 tri-color LEDs, 33 binary inputs, 30 binary outputs
Auxiliary voltage 110/120 V AC
Example for Order No.:
Order codes:
0
On request
On request
3
4
5
6
9
9
9
9
T
T
T
T
3
3
3
3
A
B
C
D
3 A D
3
1 A
D
5
3 A D 3
1 A D 5
n n n n
Siemens HG 11.42 2008
21
Product Selection
Selection of controller
n n n n
10 11 12
n n n n n
13 14 15 16
n n n n
Options
(also comprises sensor cables for external voltage sensors if selected)
0
1
9
Options
0
1
2
n
n
n
n
n
n
1 x RS232 (rear)
2 x optical
n
n
1 x IRIG-B
n
n
2 x RS485 (rear)
1 x RS485 (rear)
1 x USB (front)
14th position
Communication interfaces
n
n
n
n
n
A
B
C
D
E
Y
Configuration example
Siemens vacuum recloser 3AD
(Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)
Type: Three-phase
Length of control and sensor cable 6 m
Communication protocol IEC 60870-5-103 and Modbus RTU
Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B
Example for Order No.:
Order codes:
22
3 A D
3
1 A D 5
1
1
C
3 A D 3
1 A D 5
n n n
M 1
13th position
Communication protocols
Order codes
See page 24
3 A D
See page 23
Position:
Order No.:
See page 23
12th position
Control and sensor cables
n n
Product Selection
Selection of controller
15th position
Function packages
Position:
3 A D
n n n n
10 11 12
n n n n n
13 14 15 16
n n n n
Order codes
n n n
See page 24
Order No.:
Options
A
C
D
E
F
G
Y
16th position
Languages and power socket
Language of operating
instructions and nameplate
English
American English
Spanish
Portuguese
Other languages on request
UK
USA
Mexico
Brazil
Configuration example
Siemens vacuum recloser 3AD
(Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A)
Type: Three-phase
Controller with standard protection and monitoring functions
Language of operating instructions and nameplate: English
Standard of power socket: UK
Example for Order No.:
Order codes:
1
2
3
4
9
3 A D
3
1 A D 5
C
A
1
3 A D 3
1 A D 5
C A
23
Product Selection
Selection of additional equipment
Position:
Order No.:
3 A D
n n n n
10 11 12
n n n n n
13 14 15 16
n n n n
Order codes
n n n
Z
Z
Z
Z
Z
A
F
T
T
T
3
0
0
0
0
8
2
1
2
3
Z
Z
F
T
0
0
2
1
Options
Configuration example
Siemens vacuum recloser 3AD
3 A D
Rated voltage Ur = 27 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 60 kV
Rated short-circuit breaking current Isc = 12.5 kA
Rated normal current Ir = 400 A
Type: Three-phase
3
Recloser for pole mounting incl. control cubicle and control cable
Current and voltage measuring: current transformers, 1 CT integrated per pole
Controller size: E12, 12 function keys,
16 tri-color LEDs, 33 binary inputs, 30 binary outputs
Auxiliary voltage 110/120 V AC
Length of control and sensor cable 6 m
Communication protocol IEC 60870-5-103 and Modbus RTU
Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B
Controller with standard protection and monitoring functions
Language of operating instructions and nameplate: English
Standard of power socket: UK
Seaworthy packing inside Germany
Stainless steel for tank, control cubicle
Example for Order No.:
Order codes:
24
1
A
D
5
1
C
A
1
3 A D 3
0
1 A D 5
C A
Product Selection
Accessories and spare parts
HG11-2732_en eps
25
R-HG11-313.tif
26
Technical Data
Contents
Contents
Page
Technical Data
27
28
Voltage level 27 kV
29
Voltage level 38 kV
29
R-HG11-314.tif
Voltage level 12 kV
R-HG11-315.tif
27
Technical Data
Rated short-duration
power-frequency withstand voltage
Clearance,
phase-to-phase
Minimum clearance,
phase-to-earth
Weight
Ir
tk
Isc
Ima
Up
Ud
kA
kA
kV
kV
mV
mm
mm
mm
kg
12 kV
Rated normal current
50/60 Hz
Order No.
3AD123
3AD 122
15.5 kV
50/60 Hz
3AD222
3AD223
3AD232
3AD233
3AD 221
28
630
12.5
31.5
75
42
24
810
312
287
142
10
800
12.5
31.5
75
42
24
810
312
287
142
10
Ir
tk
Isc
Ima
Up
Ud
kA
kA
kV
kV
mV
mm
mm
mm
kg
400
12.5
31.5
110
50
24
810
312
287
142
10
630
12.5
31.5
110
50
24
810
312
287
142
10
800
12.5
31.5
110
50
24
810
312
287
142
10
630
16
40
110
50
24
810
312
287
142
10
800
16
40
110
50
24
810
312
287
142
10
Technical Data
Rated short-duration
power-frequency withstand voltage
Clearance,
phase-to-phase
Minimum clearance,
phase-to-earth
Weight
Ir
tk
Isc
Ima
Up
Ud
kA
kA
kV
kV
mV
mm
mm
mm
kg
27 kV
Rated normal current
50/60 Hz
Order No.
3AD322
3AD323
3AD ...
3AD
3AD
3AD
3AD
3AD 321
38 kV
50/60 Hz
3AD
3AD
3AD
3AD
400
12.5
31.5
125
60
24
810
312
287
142
25
630
12.5
31.5
125
60
24
810
312
287
142
25
800
12.5
31.5
125
60
24
810
312
287
142
25
400
12.5
31.5
150
60
On request
25
630
12.5
31.5
150
60
On request
25
800
12.5
31.5
150
60
On request
25
630
16
40
150
60
On request
25
800
16
40
150
60
On request
25
3
Ir
tk
Isc
Ima
Up
Ud
kA
kA
kV
kV
mV
mm
mm
mm
kg
630
12.5
31.5
170
70
On request
40
800
12.5
31.5
170
70
On request
40
630
16
40
170
70
On request
40
800
16
40
170
70
On request
40
29
Technical Data
Dimension drawings
Dimension drawings
HG11-2729 eps
638
600
600
350
365
HG11-2730_en eps
615
10
962
250
597
460
520.5
Mabild 2
Mabild 1
30
Technical Data
Dimension drawings
Dimension drawings
901
600
1341
962
407
357
1334
Mabild 2
HG11-2731 eps
425
1173
425
31
R-HG11-181.tif
32
Annex
Contents
Contents
Page
Annex
33
Inquiry form
34
Configuration instructions
35
Foldout page
R-HG11-180.eps
Configuration aid
33
Annex
Inquiry form
Please copy, fill in and return to your
Siemens partner
Inquiry concerning
o Siemens vacuum
Technical data
Rated voltage
recloser 3AD
Please
o Submit an offer
o Call us
o Visit us
Your address
Rated short-duration
power-frequency
withstand voltage
Rated short-circuit
breaking current
Rated normal current
Other values
o 12 kV
o 27 kV
o 15.5 kV
o 38 kV
o 75 kV
o 150 kV
o 110 kV
o 170 kV
o 42 kV
o 60 kV
o 50 kV
o 70 kV
o _ _ _ kV
o 12.5 kA
o 16 kA
o _ _ _ kA
o 400 A
o 630 A
o _ _ _ kV
o 125 kV
o _ _ _ kV
o 800 A
o ___A
Secondary equipment
For possible combinations see pages 20 to 23
Company
Recloser configuration
o Recloser for
o
Dept.
Name
pole mounting
Without control
cubicle
o Integrated current
o Made of
o
o Integrated voltage
transformers
Street
Controller equipment
Postal code/city
Phone
Fax
4 binary inputs
34 binary inputs
9 binary outputs
___
transformers
14 binary inputs
24 binary inputs
17 binary outputs
25 binary outputs
_ _ _ V AC, _ _ _ Hz
o Without
o 6m
o ___m
o USB
o Optical
o RS485
o IRIG-B
o RS232
o Synchronizing and
o Fault locating
Siemens AG
_ _ _ V DC
synchro-check
Loop automation
o Single-triple
Dept.
o External voltage
sensors
Communication interfaces
34
substation
Auxiliary voltage
o
o
o
o
o Application in
stainless steel
Others
_ _ _ Please fill in
12 kV to 38 kV
75 kV to 170 kV
42 kV to 70 kV
12.5 kA and 16 kA
400 A to 800 A
3 A D
13 14 15 16
3 A D
3 A D
Possible options:
Recloser configuration
(position 8)
Sensors
(position 9)
Controller
(position 10)
Auxiliary voltage
(position 11)
Cable length of control and sensor cable
(position 12)
Communication protocol
(position 13)
Communication interfaces
(position 14)
Functions of the controller
(position 15)
Language of operating instructions and nameplate
(position 16)
Recloser incl. control cubicle and cables, recloser without control cubicle
and cables, recloser for transformer substation, retrofit recloser
Integrated current transformers, integrated voltage transformers,
external voltage transformers
Housing size, number of function keys and three-color LEDs,
number of available binary inputs and outputs
Voltages from 48 V DC to 240 V AC
3 A D
3 A D
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24)
3 A D
Should you still need more options than the possible special equipment like country-specific mains sockets,
weather resistance down to 40 C, stainless-steel design, etc. please contact your responsible sales partner.
3 A D
35
3 A D
See page 24
See page 23
n n n n
See page 23
Ur:
Up:
Ud:
Isc:
Ir:
See page 22
9 10 11 12
See page 22
Possible options:
See page 22
n n n n n
See page 17
See page 21
See page 21
See page 20
See page 20
n n n n n n n
See page 19
Please follow the steps for configuration and enter the order number in the configuration aid.
Alternatively you can also use your prompted online configurator under www.siemens.com/energy
to
You prefer to configure your Siemens vacuum recloser 3AD on your own?
Siemens AG
Energy Sector
Medium Voltage Division
Nonnendammallee 104
13623 Berlin
Germany
www.siemens.com/energy
General editing:
Siemens AG, Dept. PTD CC M
Erlangen
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
The required features should therefore be specified in each individual case at the time of closing the contract.