PROGRAMMABLE

7-DAY RF THERMOSTAT

Installation and user instruction


This instructions to be retained by the user

Thank you for choosing Berettas radio


frequency (RF) Radiostat. This central
heating control device is easy to fit, and
with correct use, will deliver improved
comfort levels in your home whilst saving
you money.
This thermostat is designed to be used
only with heating controls system with a
maximum switching load of 2A at 30VDC
or 0,25A at 230VAC or with Beretta
boilers fitting a bus protocol connection
If installing for someone else, please
ensure that the instructions are handed to
the householder.

relevant national regulations and codes of


good practice. Always isolate the AC
Mains supply before installing this unit.
CE: This product is according R&TTE
Directive 1999/5/EC

Warning: Please read this manual prior


to installation or use.

From the main menu select the TYPE


parameter and those are the following
option:

Installation warning:
This programmer can be used either as a
central heating ON/OFF thermostat and
as boiler remote control (only with
selected Beretta boilers), therefore is
mandatory to determinate the correct
working mode (denominated TYPE)
before installation and setting.

Shock Hazard: This unit must be


installed by a competent person, in
accordance with local regulation, or other

Type
crt

rEc

crS

Description
Room thermostat working with
ON/OFF command to the boiler.
Connect the 2 right wires (highlighted
with T.A.) to room thermostat
connection on the boiler. Maximum
switching load of 2A at 30VDC or
0,25A at 230VAC.
Boiler remote control using a bus
protocol to communicate with the
boiler. Connect the 2 right wires
(highlighted with OT+.) to remote
control connection on the boiler.
To be used only when boiler is set in
a continuous pump running mode.
Room thermostat working with
ON/OFF command to the boiler.
Connect the 2 right wires (highlighted
with T.A.) to room thermostat
connection on the boiler. Maximum
switching load of 2A at 30VDC or
0,25A at 230VAC.

Your programmer is a room thermostat


(recognized by no house icon on display)
type crt
Your programmer is a boiler remote
control (recognized by house icon on
display) type rEc

Programming
button

Fast room
temperature
adjusting
buttons

Fast DHW
adjusting
buttons
(rEc only)

Heating
mode button

Adjusting
buttons
Display

Heating
mode button
Temperature
sensor

Battery flap

INSTALLATION AND OPERATING INSTRUCTIONS


Unlike the conventional thermostat, this
control separates the function in two
units. The receiver serves for wiring
connections and heat on/off control. The
transmitter serves as the user interface
and for temperature sensing/control. The
two units are linked by radio frequency
(RF).
The transmitter is a wall-mounted timerthermostat. The transmitter can be
located wherever a conventional room
thermostat would normally be sited. No
wiring is required, as the transmitter is
battery powered.
The receiver is connected to the boiler,
and can replace a conventional
mechanical or electronic time clock.
Important: these instructions should be
read in conjunction with the appliance
installation
instructions.
It
is

recommended that this device is installed


by a qualified electrician.
PACKING LIST
QTY
RF receiver with 6 wires fitted
1
RF transmitter
1
Anchors and screws
4
Double side adhesive
3
Instructions
1
Carton internal packaging
1
Batteries
2
NOTE: Eventual additional electronic boards
necessary to connect the controller to the
boiler main board are not included in this box
and need to be purchased separately.

PREPARATION: Isolate the appliance from


the electrical supply and remove the
appliance casing and PCB cover (refer to
boiler installation instructions for specific
details).
Connect the spade terminals of the
receiver to the boiler side. The 4 cables
have different color and different function.
6

Important: Secure the receiver wiring


harness to the internal boiler cable
anchors
Important: never connect the OT+
contact to 230V supply to avoid the
destruction of the bus circuit.
INSTALLATION OF RECEIVER
Secure the receiver in the proximity of the
boiler using 2 anchors (see picture below
for drill holes specifications) and screws
or the enclosed double side adhesive.

Blue = main supply 230 Vac = neutral N


Brown = main supply 230 Vac = line L
Black & Black = OT+ boiler remote
control connection (bus protocol).
Red & Red = T.A. boiler ON/OFF room
thermostat connection
The choice between the two options
(defined as installation TYPE) depend
from the boiler capability and from the
installer decision. See picture for the
receiver internal connections.
Important: the link-wire (if fitted) must be
removed from room thermostat terminals
(both installation type)

The location should be chosen in order to


see the receiver leds and have access to
the receiver encoding button. For no

reason should the receiver box be


opened. The appliance can only be
mounted indoors and in areas free from
any water or moisture. Wiring must
conform to IEE regulations. RF Address
Code Setting: if there is another user
nearby, e.g. in the next dwelling, your
receiver may be operated in error by their
transmitter. You may select a different RF
address code to prevent this. (see
encoding section on the technical menu
list).
Note: do not fix the receiver to the boiler
casing.

there is not necessity to make any


encoding operation after installation (both
installation type) - follow the encoding
instruction if the communication is
missing or lost.
Before fixing the transmitter check that
the radio signal is active in the room that
you are fixing (if there is no
communication the receiver will flash
orange after 350 sec the communication
is lost). Because the transmitter uses
radio waves to communicate with the
receiver, you should also bear in mind
that metallic objects can weaken or
deflect radio signals: this includes steel
reinforced walls, filing cabinets, kitchen
appliances, mirrors. The range of the
Radiostat is 40 metres in open air, and 20
metres inside buildings, dependent on RF
obstructions as mentioned above.

INSTALLATION OF TRANSMITTER
Before installing the transmitter check the
encoding functionality while the receiver
and the transmitter are still very near. The
encoding between the transmitter and the
receiver is already factory set therefore

Position the Radiostat on a wall surface


away from obstructions and direct heat
sources or draughts, in a room that is
warmed by the heating system. The fixing
of the transmitter can be done either with
the anchors and screws or with the
double sided adhesive (both supplied).
See the diagram below as reference to
drill the wall.

and re-assembly to backplate. Pay


attention because it could be difficult to
open, follow the diagram for an easier
opening procedure.

WARNING! DO not touch the printed circuit


board of the transmitter as it contains
electrostatically sensitive components.
FUNCTIONS
The Beretta Programmable 7-day RF
Thermostat has the following functions:
Type Room thermostat (crt): for the
display appearance in this mode, please
refer to the relevant section of this
manual. The internal temperature sensor
detects the temperature and, comparing

In the case of using anchors, the


transmitter box must be open to fix the
screws to the anchors internally the box.
See the diagrams below for removal from
9

Programming timing: it is possible by


selecting the relative timing fascia to
select the desired time. The programming
is possible during 7 day 24-hours and the
minimum time fascia is 30 minutes. The
programming is possible in two separated
temperatures: COMFORT (T1
) and
ECONOMY (T2 ).

with the set point, switches ON or OFF


the heating request (according the
programmed timing). The temperature
sensor is located on the left side of the
item.
Temperatures: there are two level of
selectable temperature:
Comfort temperature T1
and economy
temperature T2
(T1 always > T2).
Both are selectable. Additionally there is
a third level of temperature indicated as
frost protection temperature
that is
active all the time (the frost protection
temperature is selectable only inside the
technical menu. T2 always > Frost
protection temperature)
Time: on the display it is possible to set
and read the time (24 hours display
mode)
Day: on the display it is possible to set
and read the day of the week

Status mode in crt: select the heating


mode button for fast switching between
the 4 status OFF AUTO PARTY HOLIDAY.
OFF mode, the heating request to
the boiler is off, on display there is not
equivalent icon, the heating layer and the
programming fascia is off. With this mode
only the frost protection function is active.
AUTO mode: the heating request is
according the programmed timing and
10

room temperature. In AUTO mode it is


possible to increase or decrease
temporary the room set temperature by
pressing the
and
buttons, only if
the current time is inside in a heating ON
fascia. The temporary new temperature
set (T1) is maintained only inside the
timing fascia. The next heating fascia will
be back to the original T1 set
temperature. It is possible to check the
set temperature by pressing once the
or the
buttons only if the current time
is inside in a heating ON fascia.

midnight. After the counter down is ended


the programmer switch to AUTO mode.
PARTY mode automatically switch
the
programmer
ON
to
comfort
temperature (T1). This status is forced up
to midnight, after, the programmer goes
back to the programmed timing fascia.
Type Remote Control (rEc): for the
display appearance in this mode, please
refer to the relevant section of this
manual. The internal temperature sensor
detects the temperature and, comparing
with the set point, calculates the most
suitable boiler flow temperature according
the climatic curve (only if the external
sensor is fitted) and according the
velocity the set temperature is reached.
The
programmer
continuously
communicates with the boiler control
indicating the target flow temperature (the

HOLIDAY mode with choice how


many day off (by increasing or decreasing
using the button
and
). The
heating request to the boiler is to maintain
the economy temperature on the room
(T2). The number of days off is
considered on the day starting from
11

the 4 status OFF AUTO PARTY HOLIDAY.

values not just an ON/OFF) according to


the calculation made. With this type of
communication it is possible also to
adjust by remote the domestic hot water
(DHW)
temperature
in
case
of
instantaneous DHW production or DHW
storage tank controlled by a dedicated
sensor.
The functions of this type (rEc) are the
same as room thermostat type above
described. Additionally it is possible to
have a feedback from boiler status and
alarms. The display in rEc type give more
information
according
the
already
mentioned start up indications.
The 4 status mode have additional
functionality compared with the type room
thermostat.

OFF mode, the heating request to


the boiler is off, on display there is not
equivalent icon, the heating layer and the
programming fascia is off. With this mode
only the frost protection function is active.
The DHW function is active and it is
possible to increase or decrease the
target temperature by pressing the
and
buttons.
AUTO mode: the heating request is
according the programmed timing and
room temperature. In AUTO mode it is
possible to increase or decrease
temporary the room set temperature by
pressing the
and
buttons, only if
the current time is inside in a heating ON
fascia. The temporary new temperature

Status mode in rEc: select the heating


mode button for fast switching between

12

(T2). The number of days off is


considered on the day starting from
midnight. After the counter down is ended
the programmer switch to AUTO mode.

set (T1) is maintained only inside the


timing fascia. The next heating fascia will
be back to the original T1 set
temperature. It is possible to check the
target flow temperature communicated to
the boiler (according the various
calculations) by pressing once the
buttons only if the current time is inside in
a heating ON fascia.
In the case the outside sensor is fitted
(external temperature displayed) the
and
buttons increase or decrease of
equivalent degree indicated on display,
the room comfort level (from 5 to +5)

PARTY mode automatically switch


the
programmer
ON
to
comfort
temperature (T1). This status is forced up
to midnight, after, the programmer goes
back to the programmed timing fascia.
Other functions (common to crt and
rEc modes):
Battery low
Alarms and reset (only for rEc type)
Technical menu (only for experts)

HOLIDAY mode with choice how


many day off (by increasing or decreasing
using the button
and
). The
heating request to the boiler is to maintain
the economy temperature on the room
13

the scrolling give access to the following


settings:
Attention: the TYPE of the device (that is
part of the main menu selection) should
have already been set by the installer as
this set is according the installation made
(ON/OFF device T.A. or Remote Control
device OT+).

OPERATING INSTRUCTIONS
The programmer is factory set as room
thermostat type (crt). Most of the
parameters are already set, at the start
up it is necessary to set the time and the
day (please note no summer time is precharged inside therefore if during the year
there is time modification it must be
adjusted).
The following operation must done at
start up
END USER MENU (MAIN MENU)
Enter inside the end user menu pressing
the
button once. Use the
button
to escape at any time. Scroll inside the
end user menu pressing any of the
triangle buttons and press again the
button to enter inside the single setting,
14

icon

Description

Setting the time


Setting the day

Factory set
T1 = 21C
T2 = 16C
Unset
Unset

Setting the programming fascia

Unset

Setting the comfort (T1) and economy (T2) temperatures

Setting the domestic hot water temperature (only rEc type)


42C
Setting the TYPE
crt
Setting the technical menu (password required)
-Setting the Domestic hot water programming daily fascia
(only with boiler with tank and parameter 24 ON and only in
-24hr time)
memorized moving at the next setting.
Set the target room temperature
Use the
button to enter and exit.
(T1 and T2). Use the
and
to
Set the time. Use the
and
increase or decrease, use the
and
to increase or decrease, use the
to switch between T1 and T2. The
and
to switch between hours and
value
selected
is
automatically
tyPE
PL

15

Set the target domestic hot water.


Use the
and
to increase or

minutes. Use the


button to enter and
exit.
Set the day of the week. Use
the
and
to increase or decrease.
Use the

decrease the value. Use the


button
to enter and exit.
tyPE Set the device installation type.

button to enter and exit.

Use the
and
to switch between
the values (see the table at page 2 for
details).
PL Enter inside the technical menu.

Set the programming heating


fascia. Use the
to select the day
(only ahead, not back). Use the
to
switch ON or OFF the layer T2 or T2+T1,
once selected maintain the copy to the

Password required. Use the


and
to increase or decrease the password
code. (see specific paragraph for better
details)

following 30 minutes pressing the


button. Move ahead or back the point
using the
and
buttons. Heating
fascia are pre-set with day 1-5 from 68,30 and from 16 to 22 on T1and days 67 from 8-11 and from 16 to 23 on T1.
The setting is made on 30 minutes

Set the daily programming


fascia for domestic hot water
production (only for boilers installed with
tank and sensor). Parameter active only if
the parameter 24 inside the technical

16

be shown in the main display, together

menu is set ON. Set the programming


fascia in the same way used for heating
fascia. The setting is possible daily, not
weekly. The heating of the DHW tank will
be done according the selected
programmed fascia.

with the

spanner icon. In most of the

cases it is sufficient to press the


button to reset the system, but exceptions
apply according to the following list:

Battery low
When the controller feels that the battery

ALARMS RELATED TO THE CONTROLLER


The following are alarms related to the
controller only:
A80 = room sensor broken. Replace the
controller
A81 = EEPROM alarms. Following this
alarm after the reset, the set of factory
parameters are recharged in the
controller memory
A82 = no radio communication with the
receiver (rEc or crt mode)
A83 = (only for rEc mode) the cable
between the receiver and the boiler is
broken or not connected properly. There

are about to be exhausted, the


battery icon will lit up. In this case the
batteries needs to be changed in due
time. If the battery completely run out of
energy,
or
during
the
battery
replacement, the settings will be kept in
the controller memory, except for the time
and the day
ALARMS
Should anything occur during the
functioning of the controller, a display will
17

is no communication between receiver


and boiler. Or receiver connected on the
room thermostat (T.A.) boiler connection.
A99 = too many resets. There have been
more than 5 resets in 15 minutes.
Following this alarm, it is necessary to
reset the boiler directly on its dashboard
and is not possible to do it from the
controller.

CLIMATIC CURVES
Below the climatic curves of the
programmer. Curves from 0,2 to 0,8 are
used when the boiler is set for low
temperature (i.e. floor heating).
Curves from 1 to 3 are used when the
boiler is used for high temperature (i.e.
radiator heating),
Selection of the climatic curve can be
made inside the technical menu only.
The climatic curve function is active only
if an external sensor if fitted to the boiler.
If there is not external sensor fitted, the
programmer make an automatically
regulation using the room sensor.

ALARMS RELATED TO THE BOILER (ONLY REC


TYPE):

The alarms are displayed as per the


display of the boiler: refer to the boiler
instruction manual for the meaning of the
symbols. REMARK: the alarms type A2X
can be reset only from the boiler fascia.
ALARMS RESET
The reset of the alarms is done pressing
the button on the RF receiver

18

Boiler flow temperature

External temperature

The
icon means that there is a heat
request from the room to the boiler. The
boiler will switch ON.

DISPLAY IN crt (ON/OFF) MODE:


When the device is in its standard mode
of functioning, the appearance of the
display will be the following:

The
central heating symbol and bar
is a proportional indication of the set-point
of the desired temperature in the room.
Each bar represents to 2C. They will
disappear when the central heating is
turned OFF.

The
icon means that the device is set
as a wireless device, and that the
communication is effective
19

The
temperature
display
indicates
the
actual
temperature
measured inside the room

The
day icon and the night icon
indicate whether the current set point for
the current time is night or day.

The
time display indicates the
actual time
The
day icon indicates the
actual day of the week

The
party icon is lit up when the
party mode is selected. In this mode the
central heating fascia bar will be
completely lit up at T1 together with the
day icon. After midnight, the display will
turn back to the pre-set working fascia.

The
central heating fascia bar is a
permanent display of the functioning
fascia set for the central heating set point
setting. If a bar is completely blank, the
set-point is the anti-frost level (central
heating OFF). If only the lower part of a
bar is black, the set point is the economy
(T2). If the whole bar is black, the set
point is the comfort (T1). They will
disappear when the central heating is
turned OFF.

The
holiday icon is lit up when the
holiday mode is selected. In this mode
the central heating fascia bar will be lit up
at T2 together with the night icon. After
the holiday counter is over, the display
will turn back to the pre-set working
fascia.

20

When the
icon appears, the controller
is working as to keep the anti-frost
temperature.

The
icon means that the device is set
as a wireless device, and that the
communication is effective

DISPLAY IN rEc (remote control)


MODE:
When the device is in its standard mode
of functioning, the appearance of the
display will be the following:

The
icon means that there is a heat
request from the room to the boiler. The
boiler is ON with flame present.
The
central heating symbol and bar
is a proportional indication of the set-point
of the desired temperature in the room.
Each bar represents to 2C.They will
disappear when the central heating is
turned OFF. In case of external sensor
fitted, the bar is moved up and down
according the room comfort level chosen.

21

fascia set for the central heating set point


setting. If a bar is completely blank, the
set-point is the anti-frost level (central
heating OFF). If only the lower part of a
bar is black, the set point is the economy
(T2). If the whole bar is black, the set
point is the comfort (T1). They will
disappear when the central heating is
turned OFF.

The
temperature
display
indicates
the
actual
temperature
measured inside the room
The
house icon around the
temperature display, indicates that the
controller is set as a Remote Control
(rEc) and appears only in this mode of
functioning.

The
day icon and the night icon
indicate whether the current set point for
the current time is night or day.

The
display on the right side of the
house indicates the external temperature
reading, and it appears only when the
outdoor sensor is correctly connected.

The
domestic hot water symbol and
bar is a proportional indication of the setpoint of the desired temperature when the
boiler works in domestic hot water mode.
Each bar represents 1C.

The
central heating fascia bar is a
permanent display of the functioning

22

controller to the installation. Following


instructions are dedicated to expert
personnel as they have a deep impact on
the working mode of your boiler and your
system.
To enter inside the PL menu it is
requested a password. From the end user

The
party icon is lit up when the
party mode is selected. In this mode the
central heating fascia bar will be
completely lit up at T1 together with the
day icon. After midnight, the display will
turn back to the pre-set working
fascia.The
holiday icon is lit up when
the holiday mode is selected. In this
mode the central heating fascia bar will
be lit up at T2 together with the night icon.
After the holiday counter is over, the
display will turn back to the pre-set
working fascia.
When the
icon appears, the controller
is working as to keep the anti-frost
temperature.
TECHNICAL MENU
The device has the possibility to set a
series of parameters to better adapt the

menu, select the PL pressing the


button. Increase
or decrease
the
values up to reach the value 53 (that is
the technical menu password). Once
reached the value 53, press the
button to enter. You are now inside the
technical menu (only for expertise). Use
the
and
to scroll the parameters
list, below the sequence and the
explanation of each parameter. Note: the
visibility of the parameters depends of the
type selected.

23

Par.
Ref.

Descr.

Factory
set value

Type

Operation
Display shows the wireless channel and the address. Use
the

button to start the encoding procedure. On the

01

Encoding
procedure

codified

Type
rEc
and crt

08

Max set
point
heating

85C
(30C
85C)

Type
rEc
only

Use the
button to decrease and the
button to
increase the temperature value. The value is automatically
memorized when moving to the next parameter. This
parameter put a high limit on the maximum temperature
value communicated to the boiler.

09

Min set
point
heating

30C
(30C
85C)

Type
rEc
only

Use the
button to decrease and the
button to
increase the temperature value. The value is automatically
memorized when moving to the next parameter. This
parameter put a low limit on the minimum temperature
value communicated to the boiler.

receiver press for 5 second the


button up to the
orange light is flashing, the transmitter start to codify all the
values and the display shows P00..-P90. After reaching
the P90 value the encoding procedure is done and the
light on the receiver stops to flash.

24

Par.
Ref.

Descr.

10

Climatic
curve
selection

11

Influence
of
temperatur
e sensor

Factory
set value
1.2
(see
climatic
curves)

Type

Operation

Type
rEc
only

Use the
button to decrease and the
button to
increase the climatic curve value (see below the climatic
curves). The value is automatically memorized when
moving to the next parameter.

10
(020)

Type
rEc
only

Use the
button to decrease and the
button to
increase the influence of room sensor on the calculation of
the boiler flow temperature. 10 is the standard, higher
values is good for pour insulation houses. The value is
automatically memorized when moving to the next
parameter.

13

Calibration
of the
room
sensor

Actual

Type
rEc
and crt

Use the
button to decrease and the
button to
increase the reference room temperature. Use this
parameter in case of not proper installation of the device.
The value is automatically memorized when moving to the
next parameter.

14

Programm
er reset

Type
rEc
and crt

Use the

button to move to value 1 and reset the device

to a factory set values. Press the


reset.

25

button to confirm the

Par.
Ref.

Descr.

Factory
set value

Type

Operation

Actual

Type
rEc
and crt

This parameter just shows the software reference number


on the device

Type
rEc
and crt

Use either the


button and the
button to switch to F
or C. all the temperatures values will change. In case of
F values there is not equivalent letter F displaye d The
value is automatically memorized when moving to the next
parameter.

16

Software
release

17

Choice
C or F

18

Hysteresis
OFF

0.1C
(0.02.0)

Type
rEc
and crt

Use the
button to decrease and the
button to
increase the hysteresis OFF of the device. The value is
automatically memorized when moving to the next
parameter

19

Hysteresis
ON

0.5C
(0.02.0)

Type
rEc
and crt

Use the
button to decrease and the
button to
increase the hysteresis ON of the device. The value is
automatically memorized when moving to the next
parameter

20

Frost
protection
temp.

5C
(3C
10C)

Type
rEc
and crt

Use the
button to decrease and the
button to
increase the frost protection temperature limit. The value is
automatically memorized when moving to the next par.

26

Par.
Ref.

Descr.

Factory
set value

21

Alarms
history

Actual

22

Boiler TSP
reading

Actual

23

AntiLegionella
function

OFF

24

Clock on
DHW

OFF

Type
Type
rEc
only
Type
rEc
only
Type
rEc
only
Type
rEc
only

Operation
Use the
and the
button to scroll last 9 alarms code
memorized on the device.
Unused
Use the
and the
button to switch ON or OFF the
legionella function (function active only with boiler
connected to a tank with sensor control).
Use the
and the
button to switch ON or OFF the
programming time on the DHW production via a tank with
sensor. (function active only with boiler connected to a
tank with sensor control). If selected ON, on the end user
menu will appear a dedicated programming fascia to be
set (programmable daily fascia only)

27

TRANSMITTER
Linked with receiver via RF: frequency
868 MHz
Power rating: 2 x 1,5AA - Alkaline
batteries

TECHNICAL SPECIFICATIONS
LIMIT OF SETTING OF THE TEMPERATURES:
Anti-frost temperature: 3C 10C
T2: anti-frost temperature 35C
T1: T2 35C
DHW (if applicable): 37C 60C
Room temperature: 5C 30C
READING LIMITS
Outdoor sensor: -10C 40C
Room sensor: -10C 40C
RECEIVER
Linked with transmitter via RF:
frequency 868 MHz
Power rating: 230 VAC 10%, 50 Hz
T.A. Switching capacity (crt only):
Min 1mA,
Max 2A at 30 VDC
Max 0,25A at 230 VAC
OT+ contact: for bus protocol only.
Never supply with 230V this contact.

Install transmitter and receiver in an


environment with normal pollution level.
Radio range 40 m in free space, (the
range can be altered depending on the
installation conditions and on the
electromagnetic environment).
Beretta -Via Risorgimento 23/A
23900 Lecco (Italy)
www.berettaclima.com
Beretta reserve the right to change
specification without prior notice - Consumers
statutory rights are not affected.
A Riello Group Company
Manual Issue 08/2012 rev.01