Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
These can be
PRODUCTION relay functional testing which is carried out on every relay before it
leaves the factory.
The International Electrotechnical Vocabulary defines type tests as:
A test of one or more devices made to a certain design,
to show that the design meets certain specifications.
Before a product is developed the required performance is specified, as are the
required performance tests, and before any tests are carried out, test plans and test
procedures are written and agreed.
Products Laboratories carries out the EMC, Environmental, Electrical and Safety
Type Testing. The functional Type Testing is carried out by the R&D Department in
China (CTC) although Automation Products Laboratories will review both the
Functional Test Specifications and the Functional Test Results.
As a parallel process to this, the Automation Products Laboratories are also
responsible for gaining third party approval for the relays. The electricity suppliers
have their own formal approval processes for protection relays and the Automation
Products Laboratories take the responsibility of ensuring that the relays conform to
these requirements and that the approval process is carried out correctly. In the UK
the Energy Networks Association (ENA) is the main approval body which represents
a group of relay users involved in the generation, transmission, distribution and
supply of electricity. Its membership consists of mostly UK companies, although
there are associate members from Ireland, Japan, South Africa and Finland.
The market for protection relays is worldwide, and, it is most important that
internationally agreed standards are used as the basis for the tests carried out.
Hence most references in the publications are to IEC standards (International
Electrotechnical Commission).
5/4/2012
Typetest_notes_2012.doc
So, what type tests are carried out? Broadly speaking they can be split into five
groups.
1. Functional Tests
2. Electrical Tests
3. Environmental Tests
4. EMC Tests
5. Safety Tests
Functional tests are carried out to determine the accuracy and repeatability of each
of the discrete functions that the product can perform. They also determine the
effect of the interaction between each of the discrete functions within the relay, and
also the interaction between other items of equipment that the relay may be
interfaced with.
The electrical tests are designed to test that the relay is not damaged by transient
overvoltages that may be experienced on site. In addition the affect of variations on
the relays auxiliary supply voltage are also determined.
Environmental tests are designed to ensure that relays can operate as expected in
the environment they are installed in.
Typetest_notes_2012.doc
2. FUNCTIONAL TESTS
2.1 ACCURACY AND REPEATABILITY OF PROTECTION FUNCTIONS
Taken to the basic definition, functional tests consist of applying voltage, current or
frequency variations over the complete setting range for the function under test, and
measuring the performance in terms of accuracy and repeatability.
They are carried out under reference laboratory conditions, usually in a temperature
and humidity controlled environment.
5/4/2012
Typetest_notes_2012.doc
Range
Step Size
I>1
0.08 - 4.00In
0.01In
I>2
0.08 - 32In
0.01In
Directionality
Forward/Reverse/Non-directional
RCA
-95 to +95
Characteristic
DT/IDMT
0 - 100s
0.01s
Multiplier
0.025
(TMS)
IEEE IDMT Time Delay
0.5 15
0.1
0 - 100s
0.01s
IDMT/DT
0 - 100s
0.01s
5/4/2012
Typetest_notes_2012.doc
The functions described above are the basic building blocks of any overcurrent relay,
and, the following tests would be carried out to prove the functionality:
Test 1:- Three phase non-directional pick up and drop off accuracy over complete
current setting range for both stages
Test 2:- Three phase directional pick up and drop off accuracy over complete
RCA setting range in the forward direction, current angle sweep
Test 3:- Three phase directional pick up and drop off accuracy over complete
RCA setting range in the reverse direction, current angle sweep
Test 4:- Three phase directional pick up and drop off accuracy over complete
RCA setting range in the forward direction, voltage angle sweep
Test 5:- Three phase directional pick up and drop off accuracy over complete
RCA setting range in the reverse direction, voltage angle sweep
Test 6:- Three phase polarising voltage threshold test
Test 7:- Accuracy of DT timer over complete setting range
Test 8:- Accuracy of IDMT curves over claimed accuracy range
Test 9:- Accuracy of IDMT TMS/TD
Test 10:- Effect of changing fault current on IDMT operating times
Test 11:-Minimum Pick-Up of Starts and Trips for IDMT curves
Test 12:- Accuracy of reset timers
Test 13:- Effect of any blocking signals, opto inputs, VTS, Autoreclose
Test 14:- Voltage polarisation memory
5/4/2012
Typetest_notes_2012.doc
So, for even the most basic function, there are numerous tests that are carried out in
order to prove the correct implementation and operation of the function. This is a
very time consuming process, and for a large project, involves numerous engineers
and technicians for several months. In the case of the Px4x development, if only one
person were to carry out all the test duties, it would take a total of 4 years to write the
test specifications, and 30 years to carry out all of the tests. Then there would be the
small matter of writing the type test reports!
embedded in the windings and the temperature rise when the current or voltage is
applied is measured. This gives an indication of the point where the insulation is
about to melt or deteriorate, although the wire itself may be able to withstand the
applied quantity.
components. For CTs this is the maximum current they will withstand for 1s, and for
VTs it is the maximum voltage they will withstand for 10s.
5/4/2012
Typetest_notes_2012.doc
Output contact ratings tests are performed to determine the ability of the relays
output contacts to perform repeated loaded operations. These are usually off the
shelf components, and the performance when breaking DC inductive and resistive
loads is rarely claimed by the manufacturer, so tests have to be performed to
determine this.
determined.
Some measurements are made directly by the relay, for example phase current and
voltage magnitude. However, others are derived by the relay, for example negative
sequence quantities, so tests have to be performed to determine the comparative
performance between direct and derived measurements.
5/4/2012
Typetest_notes_2012.doc
System X/R, where tests are performed with faults at various X/R values, ranging
from 1 up to 120. This results in fault waveforms with DC offset components, and
allows the effect on the relays operating times to be determined.
Point on Wave, where tests are performed with faults applied over the complete
point on wave range. Again this allows the affect on the relay operating times to
be determined.
Harmonics, where the effect of harmonics up to 17th, usually at 10% of the
fundamental are determined.
capacitive compensators, and arc furnaces will encounter distortion of the current
and voltage waveform due to the presence of various harmonics.
Frequency. Under normal operating conditions, the system frequency varies over
strictly specified limits.
required to operate over an extremely wide frequency range, and the accuracy
has to be determined over this range.
frequency rated to work with either 50Hz or 60Hz systems, so a comparison in the
protection performance at these two frequencies has to be determined. In fact, in
some cases, the functional tests are performed at 60Hz, because this is the most
onerous condition for the relay in terms of samples per cycle, i.e. the digital signal
processor (DSP) has to work 20% faster when the relay is configured for 60Hz,
than it does for comparable performance at 50Hz.
Auxiliary Voltage. In modern relays, the operating range of the auxiliary voltage is
very wide, and therefore tests are performed to ensure that the relay will perform
its functions with the same accuracy and speed over the complete operating
voltage range. Most relay power supplies are also dual rated to work with either
AC or DC voltage, and a comparison in functional performance is made between
these two parameters.
5/4/2012
Typetest_notes_2012.doc
(There is a separate
10
Typetest_notes_2012.doc
1.5 kV rms 50/60Hz for 1 minute applied across dedicated normally open contacts
of tripping output relays
1.0 kV rms 50/60Hz for 1 minute applied across normally open contacts of
watchdog relays or changeover pairs:
The pass criteria are that no breakdown or flashover shall occur, and the relay shall
still perform its main functions within the claimed tolerance after the test.
5 kV
Rise time : 1.2 us
Fall Time : 50 us to 50 %
Peak amplitude : 5 kV
50%
1.2 us
50 us
11
Typetest_notes_2012.doc
IEC 60255-27 Measuring Relays and Protection Equipment Part 27: Product
Safety Requirements.
4. ENVIRONMENTAL TESTS
As well as proving that the relay can carry out all the functions claimed to the
required accuracy over the claimed operating range, it also has to be ensured that
the relay is capable of performing these functions correctly in the environment it may
find itself in. This involves testing each new product to extremes of temperature,
humidity and vibration.
5/4/2012
12
Typetest_notes_2012.doc
-25C to +70C
Operating
-25C to +55C
For the storage and transit test, the relay is placed unenergised in a temperature
cabinet at -25C and held at this temperature for duration of 96 hours. After this time
has elapsed, the relay is removed from the cabinet and allowed to return to the
ambient temperature.
functions still operate within the claimed tolerances. The same process is repeated
for the +70C temperature.
The criteria for acceptance are that after the temperature testing the relay should
carry out its main functions correctly, and that the results should be within the
claimed tolerance.
For the operating temperature test, the relay is placed energised in the temperature
cabinet, and subjected to the following temperatures:
-25C, 0C, +20C, +40C, +55C.
At each of these temperatures the relay is allowed to stabilise until it is at the same
temperature as the test level. It is then powered down and up again, and subjected
to tests to determine that the functions still operate within the claimed tolerances.
5/4/2012
13
Typetest_notes_2012.doc
The criteria for acceptance in this case is that the relay must power up correctly,
(particularly important at low temperatures), it must perform all its main functions
within the claimed tolerance, and the LCD should be legible, (again, this is important
at the low temperatures).
5/4/2012
14
Typetest_notes_2012.doc
In this case, the criteria for acceptance is that for the 56 day duration no unwanted
operations shall occur including transient operation of indicating devices. After the
test the relays insulation resistance should not have significantly reduced, and it
should perform all of its main protection and communications functions within the
claimed tolerance. The relay should also suffer no significant corrosion or growth,
and photographs are usually taken of each PCB and the case as a record of this.
5/4/2012
15
Typetest_notes_2012.doc
For these tests the relay is placed in a humidity cabinet, and energised with normal
in-service quantities for the complete duration of the tests. In practical terms this
usually means energising the relay with currents and voltages such that it is 10%
from the threshold for operation. Throughout the duration of the test the relay is
monitored to ensure that no unwanted operations occur.
Once the relay is removed from the humidity cabinet, its insulation resistance is
measured to ensure that it has not deteriorated to below the claimed level. The relay
is then functionally tested again, and finally dismantled to check for signs of
component corrosion and growth.
5/4/2012
16
Typetest_notes_2012.doc
The criteria for acceptance is that no unwanted operations shall occur including
transient operation of indicating devices.
resistance should not have significantly reduced, and it should perform all of its main
protection and communications functions within the claimed tolerance. The relay
should also suffer no significant corrosion or growth, and photographs are usually
taken of each PCB and the case as a record of this.
5/4/2012
17
Typetest_notes_2012.doc
5/4/2012
18
Typetest_notes_2012.doc
5/4/2012
19
Typetest_notes_2012.doc
5/4/2012
20
Typetest_notes_2012.doc
- - - - - nominal pulse.
limits of tolerance.
D
T1
minimum time during which the pulse shall be monitored for shocks and
minimum time during which the pulse shall be monitored for shocks and
5/4/2012
21
Typetest_notes_2012.doc
5/4/2012
22
Typetest_notes_2012.doc
(mm).
(gn).
of
sweep cycles
in each axis
x (horizontal)
y (vertical)
X (horizontal)
y (vertical)
7.5
3.5
2.0
1.0
The criteria for acceptance is that the equipment shall not maloperate, and shall still
perform its main functions within the claimed tolerance after the test.
The substation
23
Typetest_notes_2012.doc
exploded. Fire spread below decks, and by the time it was extinguished, 134 men
were either dead or missing. Total damages were put at $72 million.
Early Antilock Braking Systems (ABS) on both aircraft and automobiles were
susceptible to EMI.
5/4/2012
24
Typetest_notes_2012.doc
So, it is evident that EMC can cause real and serious problems, and does need to be
taken into account when designing electronic equipment. To achieve this, in addition
to designing for statutory compliance to the EMC and Low Voltage Directives, the
following range of tests are carried out during our products development process.
5.1 DC INTERRUPT
This is a test to determine the maximum length of time that the relay can withstand
an interruption in the auxiliary supply without de-energising e.g. switching off, and
that time when it is exceeded and it does transiently switch off, that no maloperation
occurs.
It simulates the effect of a loose fuse in the battery circuit, or a short circuit in the
common DC supply, interrupted by a fuse. Another source of DC interruption is if
there is a power system fault and the battery is supplying both the relay and the
circuit breaker trip coils. When the battery energises the coils to initiate the circuit
breaker trip, the voltage may fall below the required level for operation of the relay
and hence a DC interrupt occurs.
The relevant test standard is:
IEC 60255-11 Measuring Relays and Protection Equipment Part 11: Voltage
Dips, Short Interruptions, Variations and Ripple on Auxiliary Power Supply Port.
The relevant test level is:
20ms interruption without de-energising
10, 20, 30, 50, 100, 200, 300, 500, 1000 & 5000ms interruptions without
maloperating.
The relay is powered from a battery supply, and both short circuit and open circuit
interruptions are carried out. Each interruption is applied 10 times, and for auxiliary
power supplies with a large operating range, the tests are performed at minimum,
maximum, and other voltages across this range, to ensure compliance over the
complete range.
5/4/2012
25
Typetest_notes_2012.doc
The pass criteria for this test is that for interruptions of 20ms and less, the relay shall
not maloperate or de-energise, i.e. it shall not respond to the d.c. interrupt. For
interruptions greater than 20ms, the relay shall not maloperate, and power up
correctly.
60.00
50.00
Voltage
40.00
30.00
20.00
10.00
1393
1306
1219
1132
1045
958
871
784
697
610
523
436
349
262
175
88
0.00
Time (ms)
5/4/2012
26
Typetest_notes_2012.doc
For auxiliary power supplies with a large operating range, the tests are performed at
minimum, maximum, and other voltages across this range, to ensure compliance for
the complete range. The interference is applied using a full wave rectifier network,
connected in parallel with the battery supply.
The pass criteria is that during application of the ripple, the relay shall not
maloperate, and shall still perform its main functions within the claimed tolerance.
27
Typetest_notes_2012.doc
Voltage Variations: Levels of 100, 40 and 0% of the 80% of lower voltage range
(LVR) and 110% of higher voltage range (HVR) for 1s duration. Time to reach
new level: 2s.
5/4/2012
28
Typetest_notes_2012.doc
f =
1
2 LC
Where:
F is the oscillating frequency
L is the inductance in the circuit
C is the capacitance in the circuit
5/4/2012
29
Typetest_notes_2012.doc
5/4/2012
30
Typetest_notes_2012.doc
t
V
Repetition Period.
31
Typetest_notes_2012.doc
32
Typetest_notes_2012.doc
3. Main protection and communications functions are tested to determine the effect
of the interference.
The pass criteria is that during application of the power frequency interference, the
relay shall not maloperate, and shall still perform its main functions within the
claimed tolerance.
contact discharge. Air discharges are used on surfaces that are normally insulators,
and contact discharges are used on surfaces that are normally conducting. Typical
application points are shown in the diagrams below.
5/4/2012
33
Typetest_notes_2012.doc
Figure 8 Application points for the ESD tests. Front cover on.
Figure 9 Application points for the ESD tests. Front cover removed.
The shaded labels indicate those points which are not normally conducting and
which will therefore be subjected to the air discharge. The unshaded areas are
those that are normally conducting and will be subjected to the contact discharge.
5/4/2012
34
Typetest_notes_2012.doc
100
90
Current, % of Peak
80
70
60
50
40
30
20
10
0
0
10
20
30
40
50
60
70
80
90
Time, ns
35
Typetest_notes_2012.doc
3. Main protection and communications functions are tested to determine the effect
of the discharge.
The pass criteria is that during application of the electrostatic discharge, the relay
shall not maloperate, and shall still perform its main functions within the claimed
tolerance.
36
Typetest_notes_2012.doc
Conducted emissions are measured from the equipments power supply ports and
communications ports.
Radiated emissions measurements are to ensure that the interference radiated from
the equipment is not at a level which could cause interference to other equipment.
When performing these two tests, the relay is in a quiescent condition, that is not
tripped, with currents and voltages applied at 90% of the setting values. This is
because for the majority of its life, the relay will be in the quiescent state and the
emission of electromagnetic interference when the relay is tripped is considered to
be of no significance.
The relevant test standards are:
IEC 60255-25 - Electrical Relays Part 25: Electromagnetic Emission Tests for
Measuring Relays and Protection Equipment
30 to 230MHz
40 2
230 to 1000MHz
47
Notes:
1. The limits can be changed for different measurement distances
2. The lower limit shall apply at the transition frequency
5/4/2012
37
Typetest_notes_2012.doc
(V/m)
1 to 3
56 1
76
3 to 6
60
80
Notes:
1. The lower limit shall apply at the transition frequency
The highest frequency that the radiated emissions is measured up to is determined
by the highest frequency generated or used within the EUT as follows:
If the highest frequency of the internal sources of the EUT is less than
108MHz, the measurement shall only be made up to 1GHz
Table 3. Test level requirements for conducted emissions on power supply inputs
Frequency Range (MHz)
Limits dB (V)
Quasi-peak
Average
0.15 to 0.5
79 1
66 1
0.5 to 30
73
60
Notes:
1.
5/4/2012
38
Typetest_notes_2012.doc
Voltage limits 1
Current limits 1
(MHz)
dB (V)
dB (A)
Quasi-
Average
Quasi-peak
Average
peak
0.15 to 0.5
97 to 87 2
84 to 74 2
53 to 43 2
40 to 30 2
0.5 to 30
87
74
43
30
Notes:
1. The current and voltage disturbance limits are derived for use with an
impedance stabilization network (ISN) which represents a common mode
(asymmetric mode) impedance of 150 to the communications port under
test (conversion factor is 20 log10 150/1 = 44dB). The choice of whether the
current limits or voltage limits are used for measurement depends on the
availability of test equipment at the time of testing.
2. The limits decrease linearly with the logarithm of the frequency in the range
of 0.15MHz to 0.5MHz
5/4/2012
39
Typetest_notes_2012.doc
Note that at the radiated immunity lower frequency limit of 80MHz, a conductor
length of approximately 1.0m is required. At this frequency radiated immunity tests
can be performed in confidence that the relay will conduct this interference, through
a combination of the attached cabling and the PCB tracks.
Although the test standards state that all 6 faces of the equipment should be
subjected to the interference, in practice this is not carried out. Applying interference
to sides and top and bottom of the relay would have little affect as the circuitry inside
is effectively screened by the earthed metal case. However, the front and rear of the
relay are not completely enclosed by metal and are therefore not at all well screened,
and can be regarded as an EMC hole. Electromagnetic interference when directed
at the front and back of the relay can enter freely onto the PCBs inside.
When performing these two tests, the relay is in a quiescent condition, that is not
tripped, with currents and voltages applied at 90% of the setting values. This is
because for the majority of its life, the relay will be in the quiescent state and the
coincidence of an electromagnetic disturbance and a fault is considered to be
unlikely.
However, spot functional checks are performed at selected frequencies, where the
relay is tested to exercise all of its main protection and control functions, to ensure
that it will operate as expected, should it be required to do so.
The frequencies for the spot checks are in general selected to coincide with the radio
frequency broadcast bands and in particular, the frequencies of substation
attendants mobile communications.
vicinity of a relay, the substation attendant should be able to operate his walkie-talkie
without fear of causing the relay to maloperate.
In addition, two further frequency sweeps are performed between 800MHz - 960MHz
and 1.4GHz - 2.0GHz at 30V/m to replicate the digital radio telephone and base
station frequencies used throughout the world.
The relevant test standards for the radiated immunity test are:
IEC 60255-22-3 - Measuring Relays and Protection Equipment Part 22-3:
Electrical Disturbance Tests Radiated Electromagnetic Field Immunity.
5/4/2012
40
Typetest_notes_2012.doc
5/4/2012
41
Typetest_notes_2012.doc
Induction Coil
Induction Coil
EUT
Ground Plane
5/4/2012
42
Typetest_notes_2012.doc
The pass criteria is that during the application of the steady state condition, the relay
shall not maloperate, and shall still perform its main functions within the claimed
tolerance.
During the application of the short duration test, the main protection
function shall be exercised and verified that the operating characteristics of the relay
are unaffected.
Level 5: 1000A/m
The pass criteria is that during the application of the magnetic field, the relay shall
not maloperate, and shall still perform its main functions within the claimed tolerance.
43
Typetest_notes_2012.doc
The pass criteria is that during the application of the magnetic field, the relay shall
not maloperate, and shall still perform its main functions within the claimed tolerance.
5.13 SAFETY
All relays sold within Europe are required to comply with the European Low Voltage
directive (LVD) 2006/95/EC. This requirement has been mandatory since January
1997 in order to CE mark a product.
complied with the appropriate Health and Safety at Work and Consumer Protection
legislation.
Note that this legislation covers the Product Safety i.e. whether the
product is inherently safe and does not pose any hazard to the user of the product.
The ability to detect and protect against external events which might cause a hazard
is dealt with under any applicable functional safety requirements.
The essential requirement of the legislation is to show due diligence that the product
is safe and will not cause electric shock or fire hazard under normal conditions and in
the presence of a single fault.
product and are not just confined to the electrical connections. The product must be
well constructed according to good engineering practice i.e. it must not fall apart
exposing live parts or presenting mechanical hazards. Walls must not be so flimsy
that pressing against these reduces the insulation distances below the minimum
requirement. The product must be adequately insulated and be suitably earthed with
clearly labelled manufacturer mark/logo, product ratings and any safety warnings. In
addition the product publication must contain adequate instructions and warnings
affecting safety.
Compliance with the Low Voltage Directive is demonstrated via self assessment with
the information being stored in a Technical File.
5/4/2012
44
Typetest_notes_2012.doc
6. ADDITIONAL TESTING
In addition to the Type Testing that is carried out on our products the Automation
Products Laboratories has introduced additional testing. This testing is carried out
after the Type Testing has been completed and prior to the products being available
for sale to our customers. This testing is carried out by a team of Technicians who
are effectively acting as our first customers. The testing focuses on the functional
operation of the product in that tests are carried out to ensure that the product
performs according to the claims made in the publications, the commissioning
instructions are also followed to ensure that they are correct and the product
performs as detailed in these instructions.
Another aspect of this additional testing is what we term Break-It Testing. This
again is carried out by our team of Technicians who carry out unusual tests on the
products to ensure that they do not have any unforeseen problems, an example of
such a test is:
5/4/2012
45
Typetest_notes_2012.doc
IEC 61850 standard? The set of rules that the DUT protocol implementation
must adhere to. The standard is broken down into many parts of which the
following IEC documents for Communication networks and systems in
substations are used as reference during Conformance Testing:
5/4/2012
46
Typetest_notes_2012.doc
IEC 61850
Title
Part 1
Part 2
Glossary
Part 3
General Requirements
Part 4
Part 5
Part 6
Part 7-1
Part 7-2
Part 7-3
Part 7-4
Part 8-1
Part 10
Conformance Testing
5/4/2012
47
Typetest_notes_2012.doc
SIMULATOR / PC
ANALYZER
Time Master
Test (DUT)
EQUIPMENT SIMULATOR
5/4/2012
48
Typetest_notes_2012.doc
UniCA SCL Checker KEMA Tool for the checking of the SCL File and Data
Model to ensure that there are no conflicts when compared to what is defined
in the standard.
7.5 TESTING
We are currently running Conformance Tests to the latest edition of the UCA Test
Procedures, Conformance Test Procedures for Server Devices with IEC 61850-8-1
interface Revision 2.3.
UCA Test Procedures requires the testing of:
Documents
o
5/4/2012
49
Typetest_notes_2012.doc
Data Set
Substitution
Setting Group
File Transfer
7.6 TESTING
When all tests have been performed and conducted according to the structured UCA
Test Procedures using the tools provided, an IEC 61850 Conformance Test
Certificate is issued.
5/4/2012
50
Typetest_notes_2012.doc
The tests and certificate can only be conducted and issued respectively by a UCA
accredited laboratory. Alstom Grid UK Stafford Laboratory is UCA accredited. A list
of other UCA accredited Test Laboratories from the UK and abroad is listed on the
UCA website, www.ucaiug.org.
References
[1] IEC 61850 Communication networks and systems in substations
[2] Conformance Test Procedures for Server Devices with IEC 61850-8-1 interface
Revision 2.3
[3] www.ucaiug.org
5/4/2012
51
Typetest_notes_2012.doc