Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Battery Review
The Available Capacity of a battery is relative to a batterys Total
Capacity. The Total Capacity is frequently abbreviated to C and is a
measure of how much energy the battery can store.
Typically, the amp-hour capacity of a battery is measured at a rate of
discharge that will leave it empty in 20 hours (a.k.a. the C/20 rate).
If you attempt to discharge a battery faster than the C/20 rate, you
will have less available capacity and vice-versa.
===================================================================
The average discharge rate is determined from the total operating time over the
period of autonomy, taking the allowable depth of discharge into account. Using
the daily operating time calculated in the load analysis, the average discharge
rate is calculated using the following formula(s):
First, note that: rd x DODa = top x ta
rd = average discharge rate (the time in hours to completely discharge the
battery)
DODa = allowable depth of discharge (percentage).
For example, suppose rd = 60 hr and DODa = 80% then : rd x DODa = 48 hr
top = average operating time of loads (in hr/day)
ta = autonomy (in days)
For example, suppose top = 16 hr and ta = 3 days then : top x ta = 48 hr
Now transpose the equation above so that:
rd = ( top x ta ) / DODa
So, if the daily operating time (top) for system loads is 16 hr/day over an
autonomy (ta) of 3 days, and the allowable depth of discharge is 80%, what is
the average discharge rate?
rd = ( top x ta ) / DODa
rd = ( 16 x 3 ) / 0.80 = 60 hr
The battery bank will discharge at a rate that would completely discharge the
batteries in 60 hr. Therefore, the battery-bank average discharge rate is C/60.
In other words, with the measure loads, a C/60 battery at 80% DOD will give you
3 days of autonomy at an average of 16 hours per day.
Battery Selection
Individual batteries or cells are selected with enough capacity to avoid or
minimize parallel battery connections. Due to wiring resistance and small
differences among individual cells, paralleled strings of batteries may not charge
and discharge uniformly. A single series-connected string of batteries is
preferable but capacity requirements and the ' size of batteries available may
require more than one string. Generally, the number of parallel battery
connections should be limited to no more than 3 to 4 strings. Also, the size and
weight of the batteries must be considered with regard to transportation and
installation.
The nominal voltage and rated capacity of the selected battery is used to
determine the configuration of the battery bank. This information is found on
battery nameplates or in manufacturer's literature.
The nominal DC-system voltage divided by the nominal battery voltage
determines the number of batteries in a series string (eg 24v / 6v = 4). This
number should calculate evenly.
The required battery-bank rated capacity (Ah) divided by the individual-battery
rated capacity (Ah) determines the number of strings to be connected in
parallel. This number will likely not be a whole number, but should be rounded
up to the nearest whole number.
When the battery is chosen and the battery-bank design is configured, the final
rated capacity of the battery bank is equal to the rated capacity of an individual
battery multiplied by the number of parallel strings.
For example, a battery bank must supply 600 Ah and will operate at 24 V
nominal. A nominal 12 V battery is chosen with a rated capacity of 250 Ah. To
produce a nominal voltage of 24 V. two 12 V batteries will be connected in
series for each string. The number of strings in parallel is calculated to be 2.4
(600 Ah 250 Ah = 2.4). Rounded up to a whole number of 3 strings, the rated
capacity of the battery bank will then be 750 Ah (250 Ah/string x 3 strings = 750
Ah).
This is acceptable, but very conservative, and would result in an unnecessary
increase in cost. Choosing a different battery with a rated capacity closer to 200
Ah would be better if the bank were to have 3 strings. A battery with a rated
capacity of 300 Ah or slightly higher would be even better, as it would allow a
battery bank with only 2 strings. Battery choices may require changes and
recalculations to optimize the design of the battery bank.
Array Sizing
The array for a stand-alone system must be sized to meet the load requirements
during the critical design month (worst case of high loads and low insolation).
For stand-alone systems, the array must be sized to produce enough electrical
energy to meet the load requirements during the critical design month while
accounting for normal system losses. This ensures that the battery will always
be properly charged and that system availability is high throughout the year.
Required Array Output
First, the required array current is calculated from the load requirement and
insolation of the critical design month, and the nominal DC system voltage.
However, because battery efficiency is less than 100%, more current must be
supplied to charge a battery than is withdrawn on discharge. A battery-system
charging efficiency factor increases the required array output to a slightly higher
value. A value between 0.85 and 0.95 is appropriate for most batteries. The
required array current is calculated using the following formula:
For example, consider a nominal 24 V system in a location with 4.9 peak sun
hours that must supply 1580 Wh per day. The battery-system charging efficiency
is estimated at 0.90. What is the required array current?
Iarray = Irated x Cs
Irated = rated array maximum-power current (in A)
Iarray = required array maximum-power array current (in A)
Cs = soiling derating factor
Suppose the current required from an array Iarray = 14.9 A (as above) with light
soiling conditions, how much current would the array have to be rated for?
Since Iarray = Irated x Cs Then
Irated = Iarray / Cs
For example, consider an array for a nominal 24 V DC system that must output
18 A. The soiling conditions are expected to be light and the maximum module
temperature is estimated at 50C. What are the minimum rated maximumpower current and voltage parameters? (recall max power point on IV curves)
Since Iarray = Irated x Cs Then Irated = Iarray / Cs
The rated array maximum power is calculated by multiplying the rated module
maximum power by the total number of modules.
The critical design ratio is the ratio of electrical energy demand to average
insolation during a period.
The critical design month is the month with the highest critical design ratio.
System availability is the percentage of time over an average year that a
stand-alone PV system meets the system load requirements.
Autonomy is the amount of time a fully charged battery system can supply
power to system loads without further charging.
The load fraction is the portion of load operating power that comes from the
battery bank over the course of a day.
Soiling is the accumulation of dust and dirt on an array surface that shades the
array and reduces electrical output.