Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
PROFIBUS
according to
IEC 61158/EN 50170
3/2
3/3
3/7
3/9
3/10
3/11
3/12
3/15
3/15
Introduction
Overview
Process or field communication
Data communication
Communications overview for SIMATIC
Communications overview for PG/PC
Configuration examples
Topologies
Technical specifications
Special notes
3/16
3/18
3/19
3/32
3/33
Network components
Network selection criteria
Overview
ECOFAST system
DESINA system
Connection examples
3/35
3/36
3/43
3/48
3/49
3/50
3/52
3/53
3/55
3/57
3/59
3/60
3/61
3/63
3/65
3/67
3/71
3/72
3/76
3/80
3/83
3/87
3/89
Wireless Link
ILM (Infrared Module)
3/92
3/99
3/117
3/124
3/130
3/138
3/171
3/178
3/182
3/183
3/186
3/195
3/197
3/199
Engineering tools
COM PROFIBUS
SIMATIC PDM
3/201
3/205
3/207
Technology components
ASICs
Development packages
Interface modules/interfaces
3/209
Sec. 7
Network transitions
Siemens IK PI 2002/2003
3/1
Electrical Networks
Network components
PROFIBUS FastConnect
Overview
Application
PROFIBUS FastConnect is
a system for fast and easy
assembly of PROFIBUS
copper cables.
Design
Functions
FastConnect PROFIBUS
bus connector
Note:
The PROFIBUS FastConnect bus
cables can also be connected to
conventional bus connectors.
Siemens IK PI 2002/2003
3/35
Electrical Networks
Network components
Bus cables for PROFIBUS
Overview
Application
Design
Due to double-shielding,
these cables are particularly
suitable for industrial environments subject to electromagnetic interference.
Cable types
3/36
Siemens IK PI 2002/2003
PROFIBUS FC
Trailing Cable:
Bus cable for special use in
cases of forced movement in
mobile cable handlers,
e.g. for continuously moving
machine parts (stranded
conductor).
PROFIBUS FC FRNC Cable:
Two-wire shielded, flame retardant and halogen-free
bus cable with copolymer
outer casing FRNC (Flame
Retardant Non Corrosive).
Bus cables without
FastConnect method
(design-related)
PROFIBUS Festoon Cable
Flexible bus cable (stranded
conductor) for special application in festoons.
For round cables, the
operation of a cable
cart is recommended.
PROFIBUS Flexible Cable
Bus cable for highly flexible
applications:
Special cable (stranded
conductor) for use on moving machine parts (5 million
torsional movements on 1 m
cable, 180 ).
Electrical Networks
Network components
Bus cables for PROFIBUS
Mounting
Siemens IK PI 2002/2003
3/37
Electrical Networks
Network components
Bus cables for PROFIBUS
Technical specifications
Cable type 1)
PROFIBUS
FC Standard Cable
PROFIBUS
FC Robust Cable
PROFIBUS
FC Food Cable
Applications
Universally applicable
Attenuation
at 16
at 4
at 9.6
MHz
MHz
kHz
< 42 dB/km
< 22 dB/km
< 2.5 dB/km
< 42 dB/km
< 22 dB/km
< 2.5 dB/km
< 42 dB/km
< 22 dB/km
< 2.5 dB/km
Impedance
at 9.6
at 38.4
at 3 to 20
kHz
kHz
MHz
270 27
185 18.5
150 15
270 27
185 18.5
150 15
270 27
185 18.5
150 15
Rated value
150
150
150
Loop resistance
110 /km
110 /km
110 /km
Shield resistance
9.5 /km
9.5 /km
9.5 /km
Effective capacitance
at 1 kHz
Operating voltage
(rms value)
100 V
100 V
100 V
Type of cable
(standard code)
02YSY (ST) CY
1 2 0.64/2.55-150 KF 40 FR VI
Sheath
Material
Diameter
Color
PVC
8.0 0.4 mm
purple
PUR
8.0 0.4 mm
purple
PE
8.0 0.4 mm
black
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
Bending radii
First & final bending
Repeated bending
75 mm
150 mm
75 mm
150 mm
75 mm
150 mm
100 N
100 N
100 N
Weight
76 kg/km
73 kg/km
67 kg/km
Halogen-free
No
No
No
Behavior in fire
flame-retardant
acc. to VDE 0472
T804
C test type
flame-retardant
acc. to VDE 0472
T804
B test type
Flammable
UL listing/300 V rating
Yes/CMX
Yes/CMX
No
Conditionally resistant
Good resistance
Conditionally resistant
UV resistance
No
Yes
Yes
Silicone-free
Yes
Yes
Yes
Yes
Yes
Yes
1) Electrical characteristics at 20 C, tested according to DIN 47 250 Part 4 or DIN VDE 0472.
3/38
Siemens IK PI 2002/2003
Electrical Networks
Network components
Bus cables for PROFIBUS
Technical specifications
Cable type 1)
PROFIBUS
FC Underground Cable
PROFIBUS
FC Trailing Cable 2) 3)
PROFIBUS
Festoon Cable 3)
Applications
Attenuation
at 16
at 4
at 9.6
MHz
MHz
kHz
< 42 dB/km
< 22 dB/km
< 2.5 dB/km
< 49 dB/km
< 25 dB/km
< 3 dB/km
< 49 dB/km
< 25 dB/km
< 3 dB/km
Impedance
at 9.6
at 38.4
at 3 to 20
kHz
kHz
MHz
270 27
185 18.5
150 15
270 27
185 18.5
150 15
270 27
185 18.5
150 15
Rated value
150
150
150
Loop resistance
110 /km
133 /km
133 /km
Shield resistance
9.5 /km
14 /km
19 /km
Effective capacitance
at 1 kHz
approx. 28 nF/km
Operating voltage
(rms value)
100 V
100 V
100 V
Type of cable
(standard code)
Sheath
Material
Diameter
Color
PE/PVC
10.8 0.5 mm 4)
black
PUR
8.0 0.4 mm
petrol
PVC
8.0 0.3 mm
petrol
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
Bending radii
First & final bending
Repeated bending
80 mm
150 mm
40 mm
60 mm
30 mm
70 mm
100 N
100 N
80 N
Weight
117 kg/km
74 kg/km
56 kg/km
Halogen-free
No
No
No
Behavior in fire
flammable
flame-retardant
acc. to VDE 0472
T804
B test type
flame-retardant
acc. to VDE 0472
T804
B test type
UL listing/300 V rating
No
Yes/CMX
Yes/CMX
Conditionally resistant
Good resistance
Conditionally resistant
UV resistance
Yes
Yes
Yes
Silicone-free
Yes
Yes
Yes
Yes
Yes
No
1) Electrical characteristics at 20 C, tested according to DIN 47 250 Part 4 or DIN VDE 0472.
2) Trailing-type cables for the following requirements: min. 4 million bending cycles at the specified bending radius
and an acceleration of max. 4 m/s2
3) Restricted segment lengths (see the manual for PROFIBUS networks).
4) Outside diameter >8 mm; bus connectors can only be connected after removing the outer casing
Siemens IK PI 2002/2003
3/39
Electrical Networks
Network components
Bus cables for PROFIBUS
Technical specifications
Cable type 1)
PROFIBUS
FC FRNC Cable
PROFIBUS
Flexible Cable 2) 3)
SIENOPYR 6)
PROFIBUS Marine Cable
Applications
Marine engineering;
Attenuation
at 16
at 4
at 38.4
at 9.6
MHz
MHz
kHz
kHz
< 42 dB/km
< 22 dB/km
< 82 dB/km
< 28 dB/km
< 45 dB/km
< 22 dB/km
< 5 dB/km
< 3 dB/km
Impedance
at 9.6
at 38.4
at 3 to 20
kHz
kHz
MHz
270 27
185 18.5
150 15
270 27
185 18.5
150 15
250 25
185 18.5
150 15
Rated value
150
150
150
Loop resistance
110 /km
98 /km
110 /km
Shield resistance
9.5 /km
14 /km
Effective capacitance
at 1 kHz
approx. 29 nF/km
approx. 30 nF/km4)
Operating voltage
(rms value)
100 V
100 V
100 V
Type of cable
(standard code)
02Y SH (ST) CH
1 2 0.64/2.55-150 VI KF 25 FRNC
M-02Y (ST) CH X
1 2 0.35 100 V
Sheath
Material
Diameter
Color
FRNC
8.0 0.4 mm
light purple
PUR
8.0 0.4 mm
purple
Polymer 5)
10.3 0.5 mm
black
25 C to +60 C
25 C to +60 C
25 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +60 C
40 C to +80 C
40 C to +80 C
10 C to +50 C
Bending radii
First & final bending
Repeated bending
40 mm
75 mm
60 mm
120 mm
108 mm
216 mm
100 N
100 N
100 N
Weight
67 kg/km
65 kg/km
Halogen-free
Yes
No
Yes
Behavior in fire
flame-retardant
acc. to VDE 0472
T804
C test type
flame-retardant
acc. to VDE 0472
T804
B test type
flame-retardant
acc. to VDE 0472
T804
C test type
UL listing/300 V rating
Yes/CM
Yes/CMX
No
Conditionally resistant
Good resistance
UV resistance
Yes
Yes
Yes
Silicone-free
Yes
Yes
Yes
Yes
No
No
1)
2)
3)
4)
5)
6)
Electrical characteristics at 20 C, tested according to DIN 47 250 Part 4 or DIN VDE 0472.
Restricted segment lengths (see the manual for PROFIBUS networks).
Torsionally resistant cable for following requirements: min. 5 million torsional movements on 1 m cable 180
At 800 Hz
Outside diameter >8 mm; bus connectors can only be connected after removing the outer casing
Shipbuilding approvals
Lloyds Register of Shipping
Germanischer Lloyd
3/40
Siemens IK PI 2002/2003
Electrical Networks
Network components
Bus cables for PROFIBUS
Technical specifications
Cable type 1)
PROFIBUS
ECOFAST Hybrid Cable 2)
PROFIBUS
Cable for ET 200X
Applications
ET 200 X
Attenuation
at 16
at 4
at 9.6
MHz
MHz
kHz
< 49 dB/km
< 25 dB/km
< 3 dB/km
Impedance
at 9.6
at 38.4
at 3 to 20
kHz
kHz
MHz
270 27
185 18.5
150 15
135 165
Rated value
150
Loop resistance
168 /km
Shield resistance
15 /km
Effective capacitance
at 1 kHz
30 pF/m
30 pF/m
Operating voltage
(rms value)
100 V
35 V
Type of cable
(standard code)
Sheath
Material
Diameter
Color
PUR
approx. 11 mm
purple
PUR
approx. 9.5 mm
petrol
40 C to +60 C
40 C to +60 C
40 C to +60 C
30 C to +60 C
40 C to +60 C
40 C to +60 C
Repeated bending
38 mm
55 mm
70 mm
140 mm
300 N
300 N
Bending radii
First & final bending
Weight
Halogen-free
Yes
No
Behavior in fire
flame-retardant
acc. to VDE 0472
T804
B test type
flame-retardant
acc. to VDE 0472
T804
B test type
UL listing
No
Yes
Conditionally resistant
Conditionally resistant
UV resistance
No
No
Silicone-free
Yes
Yes
No
No
1) Electrical characteristics at 20 C, tested according to DIN 47 250 Part 4 or DIN VDE 0472.
2) Trailing-type cables for the following requirements:
min. 2.5 million bending cycles at the specified bending radius and an acceleration of 2.5 m/s2
Siemens IK PI 2002/2003
3/41
Electrical Networks
Network components
Bus cables for PROFIBUS
Ordering data
Bus cables for PROFIBUS:
PROFIBUS FC Standard Cable
Standard type specially designed for
rapid installation, two-wire, shielded,
sold by the meter;
Consignment max. 1000 m max.,
min. odering quantity 20 m
Preferred lengths
20 m
50 m
100 m
200 m
500 m
Order No.
6XV1 830-0EH10
Order No.
PROFIBUS Festoon Cable
2-wire, shielded
sold by the meter:
max. consignment 1000 m,
minimum order 20 m
}
}
}
}
}
6XV1 830-0EN20
6XV1 830-0EN50
6XV1 830-0ET10
6XV1 830-0ET20
6XV1 830-0ET50
6XV1 830-0JH10
6XV1 830-0GH10
6XV1 830-3FH10
20 m
50 m
100 m
6XV1 830-3GH10
6XV1 830-0LH10
6XV1 830-0PH10
6XV1 830-7AH10
}
}
}
6XV1 830-7AN20
6XV1 830-7AN50
6XV1 830-7AT10
Preassembled lengths
and connectors
6XV1 830-3EH10
6GK1 905-6AA00
6GK1 905-6AB00
}
}
}
PROFIBUS FastConnect
RS 485 Bus Connector
Plug 180
with 180 cable outlet
using insulation displacement method
6ES7 972-0BA50-0XA0
6ES7 972-0BB50-0XA0
6GK1 500-0FC00
1) Order from:
DEHN & Shne
Hans-Dehn-Str. 1
92318 Neumarkt/Opf., Germany
Note:
Additional components for the SIMATIC NET cable range
can be ordered from your local contact.
For technical support, please contact:
J. Hertlein, A&D SE PS
Tel.: +49 91 17 50 44 65
Fax: +49 91 17 50 99 91
E-mail: juergen.hertlein@fthw.siemens.de
6ES7 194-1LY00-0AA0-Z
Z = length (specify in m)
6XV1 830-0MH10
}
}
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6ES7 194-1LY10-0AA0-Z
Z = length (specify in m)
919506
919510
906055
919508
919506
919570
919508
6GK1 975-1AA00-3AA0
3/42
Siemens IK PI 2002/2003
Electrical Networks
Network components
RS 485 bus connector for PROFIBUS
Used for connecting
PROFIBUS nodes to the
PROFIBUS cable
Overview
Easy assembly
Extremely short mounting
times with FastConnect
connectors due to insulation displacement method
Integrated terminating
resistors (not with
6ES7 972-0BA30-0XA0)
PG connection possible with
special bus connector without additional installation of
network nodes
Application
Design
Functions
Siemens IK PI 2002/2003
3/43
Electrical Networks
Network components
RS 485 bus connector for PROFIBUS
Technical specifications
Bus connector
6ES7 972-0BA12-0XA0
6ES7 972-0BB12-0XA0
6ES7 972-0BA41-0XA0
6ES7 972-0BB41-0XA0
6ES7 972-0BA30-0XA0 1)
Cable outlet
90 cable outlet
35 cable outlet
30 cable outlet
Baud rate
Terminating resistor
No terminating resistor,
cannot be used for the 1st and
last device in the bus segment
Interfaces
PROFIBUS stations
PROFIBUS bus cable
FastConnect insulation displacement
No
No
Yes
Supply voltage
(must be supplied by the terminal)
4.75 to 5.25 V DC
4.75 to 5.25 V DC
Current consumption
max. 5 mA
max. 5 mA
0 C to +60 C
25 C to +80 C
max. 75% at +25 C
0 C to +60 C
25 C to +80 C
max. 75% at +25 C
0 C to +60 C
25 C to +80 C
max. 75% at +25 C
Design
Dimensions (W H D) in mm
Weight
15.8 54 34
approx. 40 g
16 54 38
approx. 40 g
15 58 34
approx. 30 g
PG connection socket
No
Degree of protection
IP 20
IP 20
IP 20
Use in PLC
S7-200/-300/-400
C7-626 DP
S5-115U to -155U
2)
OLM/OBT
RS 485 repeater
I/O device
ET 200M
ET 200 B
ET 200L
ET 200 S
Programming device
PG 720/720C/PG 740/PG 760
Interface
IM 308-C.
CP 5431 FMS/DP
CP 342-5
CP 343-5
CP 443-5
IM 467
CP 5511/CP 5611/CP 5613/CP 5614
SIMATIC OP
3/44
Siemens IK PI 2002/2003
Electrical Networks
Network components
RS 485 bus connector for PROFIBUS
Technical specifications
Bus connector
6ES7 972-0BA50-0XA0
6ES7 972-0BB50-0XA0
6GK1 500-0FC00
6GK1 500-0EA02
Cable outlet
90 cable outlet
Baud rate
Terminating resistor
Interfaces
PROFIBUS stations
PROFIBUS bus cable
Yes
Yes
No
Supply voltage
(must be supplied by the terminal)
4.75 to 5.25 V DC
4.75 to 5.25 V DC
4.75 to 5.25 V DC
Current consumption
max. 5 mA
max. 5 mA
max. 5 mA
0 C to +60 C
25 C to +80 C
max. 75% at +25 C
0 C to +60 C
25 C to +80 C
max. 75% at +25 C
0 C to +60 C
25 C to +80 C
max. 75% at +25 C
Design
Dimensions (W H D) in mm
Weight
72.7 16 34
approx. 50 g
15 57 39
approx. 100 g
15 57 39
approx. 100 g
PG connection socket
No
No
Degree of protection
IP 20
IP 20
IP 20
Use in PLC
S7-200/-300/-400.
C7-626 DP
S5-115U to -155U
I/O device
ET 200M
ET 200 B
ET 200L
ET 200 S
Programming device
PG 720/720C/PG 740/PG 760
Interface
IM 308-C.
CP 5431 FMS/DP
CP 342-5
CP 343-5
CP 443-5
IM 467
CP 5511/CP 5611/CP 5613/CP 5614
SIMATIC OP
OLM/OBT
RS 485 repeater
Siemens IK PI 2002/2003
3/45
Electrical Networks
Network components
RS 485 bus connector for PROFIBUS
Ordering data
}
RS 485 bus connector
with axial cable outlet (180)
for industrial PC, SIMATIC HMI OP,
OLM; max. transmission rate 12 Mbit/s
RS 485 bus connector
with 90 cable outlet
with insulation displacement method,
max. transmission rate 12 Mbit/s
without PG interface
with PG interface
}
}
}
}
}
6GK1 500-0EA02
PROFIBUS FastConnect
}
RS 485 bus connector
plug 180
for the insulation displacement method
with 180 cable outlet for industrial PCs,
SIMATIC HMI OP, OLM;
max transfer rate 12 Mbit/s
6ES7 972-0BA12-0XA0
6ES7 972-0BB12-0XA0
6ES7 972-0BA41-0XA0
6ES7 972-0BB41-0XA0
6ES7 972-0BA30-0XA0
}
}
Siemens IK PI 2002/2003
}
}
}
6GK1 500-0FC00
6ES7 901-4BD00-0XA0
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
6ES7 972-0BA50-0XA0
6ES7 972-0BB50-0XA0
Note:
Additional components for the SIMATIC NET cable range can be ordered from
your local contact.
For technical support, please contact:
J. Hertlein, A&D SE PS
Tel.: +49 91 17 50 44 65
Fax: +49 91 17 50 99 91
E-mail: juergen.hertlein@fthw.siemens.de.
3/46
Order No.
Order No.
Electrical Networks
Network components
RS 485 bus connector for PROFIBUS
Dimension Drawings
Dimensions
in mm
15.8
35.6
34 _+ 0.2
7.9
25
35.4
64
54.5
11.6
G_IK10_deP0121s
10
6ES7 972-0BX11-0XA0
28.4
34 _+ 0.2
7.9
25
75.15 _+ 0.2
Thread
4-40 UNC
G_IK10_deP0122s
10+_ 0.1
6ES7 972-0BX50-0XA0
61.75
15,8
44.1
28.4
G_IK10_deP0123s
34.3
6GK1 500-0FC00
56
ON
35 39
G_IK10_deP0124s
OFF
15
10
6GK1 500-0EA02
Fig. 3/28 RS 485 bus connector
Siemens IK PI 2002/2003
3/47
Electrical Networks
Network components
830-1T PROFIBUS connecting cable
Preassembled cable for
fast, low-cost connection
of PROFIBUS nodes to
OLM or OBT
Overview
Flexible PROFIBUS
connecting cable
Design
Functions
Trouble-free connection of
end stations through preassembled connecting leads
Ordering data
Order No.
6XV1 830-1CH15
6XV1 830-1CH30
3/48
Siemens IK PI 2002/2003
Both cable ends are terminated by a resistor combination (cannot be switched off).
Electrical Networks
Network components
830-2 PROFIBUS connecting cable
Preassembled cable for
connecting PROFIBUS
nodes (e.g. HMI) to
automation devices
Overview
Flexible PROFIBUS
connecting cable up
to 12 Mbit/s.
Design
Functions
Ordering data
830-2 PROFIBUS connecting cable
Preassembled,
with two 9-pin connectors
3 m long
5 m long
10 m long
Trouble-free connection of
end stations through preassembled connecting leads
It is preassembled with
two 9-pin connectors
(6GK1 500-0EA02 and
6ES7 972-0BB11-0XA0).
Direct connection of a PG
through the PG interface
without interrupting the
connection between the
stations.
Order No.
}
}
}
6XV1 830-2AH30
6XV1 830-2AH50
6XV1 830-2AN10
Siemens IK PI 2002/2003
3/49
Electrical Networks
Network components
Bus terminals for PROFIBUS
Overview
Unambiguous localization
of bus termination faults with
the 12M bus terminal
Application
Design
Functions
3/50
Siemens IK PI 2002/2003
Electrical Networks
Network components
Functions
(continued)
Bus terminal
G_IK10_deP0020s
PROFIBUS
Fig. 3/29 System connection with PROFIBUS terminals, e.g. for SIMATIC S7
Ordering data
Baud rate
1000 m
400 m
200 m
100 m
BT 12M
System
3
3
3
SIMATIC S7-200
CPU 215
PC modules
CP 5511
CP 5611
CP 5613
CP 5614
System
SIMATIC S7-300
CP 342-5
CP 343-5
CPU 313
CPU 314
CPU 315
CPU 316
CPU 315-2 DP
3
3
3
3
3
3
3
SIMATIC S7-400
CP 443-5 Basic
CP 443-5 Extended
IM 467
CPU 413-2 DP
CPU 414-2 DP
3
3
3
3
3
SIMATIC DP
ET 200M, IM 153
ET 200U, IM 318-C
ET 200 B
ET 200L
ET 200 X
ET 200 S
SIMATIC 505
SIMATIC 505 FIM
SIMATIC 505
PROFIBUS DP RBC
}
}
SIMATIC S5
IM 308 C
CP 5431 FMS/DP
S5-95U/DP
Order No.
BT 12M
3
3
3
3
3
3
3
3
}
}
}
6GK1 500-0AB00
6GK1 500-0DA00
6GK1 500-0AA10
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
Miscellaneous
3
RS 485 repeater
DP/AS-Interface Link 20 3
3
DP/RS 232 Link
1) Additional language versions and manuals
can be found for the various products at:
http://www.siemens.de/automation/csi/net
Siemens IK PI 2002/2003
3/51
Electrical Networks
Network components
Active RS 485 bus terminating element
for PROFIBUS
Overview
Application
Design
Functions
Technical specifications
Ordering data
Baud rate
Interfaces
Connection for bus segment
Connection for power supply
Supply voltage
Rated voltage
24 V DC (20.4 V to 28.8 V)
Current consumption
Approx. 30 mA
0 C to +60 C
40 C to +70 C
95% at +25 C
max.
Design
Dimensions (W H D) in mm
Weight
approx.
60 70 43
95 g
Degree of protection
IP 20
3/52
Siemens IK PI 2002/2003
Order No.
6ES7 972-0DA00-0AA0
Electrical Networks
Network components
RS 485 repeater for PROFIBUS
Automatic transfer
rate search
Overview
Application
Design
Functions
24 V DC voltage display
Terminal block for power
supply (24 V DC external)
Baud rate
PG/OP interface
1000 m
1000 m
1000 m
1000 m
1000 m
400 m
200 m
100 m
100 m
100 m
Startup assistance
Switch for disconnecting
segments
Display of bus activity
Isolation of a segment
with incorrectly inserted
terminating resistor
Siemens IK PI 2002/2003
3/53
Electrical Networks
Network components
RS 485 repeater for PROFIBUS
Technical specifications
Ordering data
Baud rate
Interfaces
Connection for bus segment
Connection for power supply
2 terminal blocks
terminal block
Supply voltage
Rated voltage
24 V DC (20.4 V to 28.8 V)
max.
100 mA
130 mA
200 mA
0 C to +60 C
40 C to +70 C
95% at +25 C
Design
Dimensions (W H D) in mm
Weight
approx.
45 128 67
350 g
Degree of protection
IP 20
3/54
Siemens IK PI 2002/2003
RS 485 repeater
for PROFIBUS
Transmission rate
up to max. 12 Mbit/s
24 V DC housing to IP 20
Order No.
6ES7 972-0AA01-0XA0
Electrical Networks
Network components
Diagnostic repeater for PROFIBUS DP
RS 485 repeater with
online line diagnostics
for PROFIBUS DP
Overview
DP standard PROFIBUS
slave
Automatic determination
of fault types and locations
Application
Design
Siemens IK PI 2002/2003
3/55
Electrical Networks
Network components
Diagnostic repeater for PROFIBUS DP
Distance of fault location in
meters from station X or Y
and from the repeater
Fault type
The following faults
can be diagnosed:
Break in the data
cables A or B
Data cable short-circuit
against the shield
Missing bus terminating
resistor
Sporadic faults are also
recognized.
The error messages are displayed graphically in STEP 7
and COM PROFIBUS. They
are fully integrated into the
SIMATIC system diagnostics
(e.g.overview diagnostics,
"report system error" function).
Principle of operation
Repeater functionality
The diagnostic repeater is
integrated in the bus system
as a normal RS 485 repeater
but has a separate PROFIBUS
DP address:
Increased number of stations (max. 127) and expansion in the bus system
Regenerating the signals
in amplitude and time
Optical isolation of
connected segments
Configuration is executed through STEP 7,
COM PROFIBUS, or a
GSD file.
Ordering data
Technical specifications
Transmission speed
Interfaces
Connection for bus segment
Connection for power supply
FastConnect
insulation displacement
Terminal block
Supply voltage
Rated voltage
24 V DC (20.4 to 28.8 V)
0 C to +60 C
40 C to +70 C
95% at +25 C
max.
Design
Dimensions (W H D) in mm
Weight
approx.
80 125 67.5
300 g
Degree of protection
IP 20
3/56
Diagnostics functionality
Initiated by STEP 7 or
COM PROFIBUS, the diagnostic repeater determines
the topology of the bus
system and stores it in the
internal diagnostics memory.
In the event of a fault, the
repeater automatically relays
a standard diagnostics message to the bus master containing details on the following:
Affected segment
Fault location (e.g.between
station X and Y)
Siemens IK PI 2002/2003
Order No.
} 6ES7 972-0AB00-0XA0
Diagnostic repeater RS 485
for connection of up to 2 segments to
PROFIBUS DP; with online diagnostics
function for the monitoring of bus cables
Diagnostic
repeater RS 485 manual
German
English
French
}
}
}
6ES7 972-0AB00-8AA0
6ES7 972-0AB00-8BA0
6ES7 972-0AB00-8CA0
Electrical Networks
Network components
DP/DP coupler for PROFIBUS DP
Used to connect two
PROFIBUS DP networks
Overview
Application
Design
Functions
Parameterization
Configuration is performed
through the GSD (device
data) file using the configuration tool of the connected
PROFIBUS DP master.
Siemens IK PI 2002/2003
3/57
Electrical Networks
Network components
DP/DP coupler for PROFIBUS DP
Ordering data
Technical specifications
PROFIBUS transfer rate
max.
Interfaces
PROFIBUS DP
Supply voltage
24 V DC
Current input
12 Mbit/s
typical
Mounting
0 C to +55 C
20 C to +80 C
95% at +25 C
max.
DP/DP coupler
for connecting two PROFIBUS DP
networks; including documentation
and GSD file on 3 diskette
H D) in mm
Weight
approx.
Degree of protection
3/58
Siemens IK PI 2002/2003
6ES7 158-0AD00-0XA0
40 110 70
500 g
IP 20
Note:
The manual is available free of charge in the Internet.
Design
Dimensions (W
Order No.
http://www.ad.siemens.de/simatic-dp
Electrical Networks
Network components
DP/RS 232C link for PROFIBUS DP
Converter between an
RS 232C (V.24) interface
and PROFIBUS DP
Overview
Application
Design
Functions
Parameterization
Configuration is performed
through the GSD file with the
configuration tool of the connected device.
Ordering data
Technical specifications
Order No.
6ES7 158-0AA01-0XA0
Interfaces
PROFIBUS DP
RS 232C
Note:
The manual is available free of charge in the Internet.
Supply voltage
24 V DC
Current consumption
300 mA
0 C to +55 C
40 C to +70 C
95% at +25 C
Max. 12 Mbit/s
max.
max.
Design
Dimensions (W H D) in mm
Weight
approx.
70 95 80
300 g
Degree of protection
IP 20
http://www.ad.siemens.de/simatic-dp
Siemens IK PI 2002/2003
3/59
Electrical Networks
Network components
Power rail booster
Device for the cost-effective
transmission of PROFIBUS
DP through slip conductors
and sliprings, degree of protection IP 20
Overview
Simple design
because connection to the
slip conductors is made
without a terminating resistor
Large diagnostics display
for power supply, bus activity and group errors
Isolated changeover contact
for external group error display
Application
Design
Principle of operation
Ordering data
Power rail booster
Signal booster for transmission
of PROFIBUS DP through slip
conductors, max. 500 kbit/s
3/60
Siemens IK PI 2002/2003
6ES7 972-4AA00-0XA0
Monorail conveyors
Vehicle control for monorail
conveyors can be achieved
cost-effectively with a concept
based on SIMATIC standard
components. High availability,
short response times and
simple expandability can be
achieved through the use of
distributed PLCs, e.g.
SIMATIC ET 200S IM151/CPU.
These can also be programmed by the user through
the slip conductor using
SIMATIC STEP 7.
Electrical Networks
Network components
BT 200 hardware test device for PROFIBUS DP
Used to check bus cables,
RS 485 interfaces and the
accessibility of slaves
Overview
Application
Functions
Specific addressing
of individual slaves
Checking the RS 485 interface of slaves/masters:
RS 485 driver
Power supply for line
termination
RTS signal
Siemens IK PI 2002/2003
3/61
Electrical Networks
Network components
BT 200 hardware test device for PROFIBUS DP
Technical specifications
9.6 kbit/s to 12 Mbit/s
Interface: PROFIBUS DP
Supply voltage
Languages
Ordering data
Baud rate
max.
+5 C to +45 C
20 C to +60 C
95%
Design
Dimensions (W H D) in mm
Weight
approx.
210 100 55
350 g
Degree of protection
IP 20
3/62
Siemens IK PI 2002/2003
Order No.
6ES7 181-0AA01-0AA0
6ES7 193-8LA00-0AA0
6ES7 193-8LB00-0AA0
6ES7 193-8MA00-0AA0
Test connector
Spare part
6EP8 106-0AC20
6EP8 106-0HA01
Point-to-point cable
for station test
Spare part
6EP8 106-0HC01
Electrical Networks
Network components
SpliTConnect for field bus systems
according to IEC 61158-2, e.g. PROFIBUS PA
Used for configuring field
bus segments according
to IEC 61158-2 (e.g.
PROFIBUS PA) with field
device connecting points
Overview
Terminals connectable
through FC Process Cable
or SpliTConnect M12 outlet/
M12 jack
Application
Design
SpliTConnect
coupler
SpliTConnect
M12 outlet
SpliTConnect
terminator
Functions
SpliTConnect
M12 jack
Siemens IK PI 2002/2003
3/63
Electrical Networks
Network components
SpliTConnect for field bus systems
to IEC 61158-2, e.g. PROFIBUS PA
Procedure
Ordering data
Technical specifications
Baud rate
31.25 kbit/s
Type of connection
Cable gland
M22
Housing material
PBT
(polybuteneterephthalate)
40 C to +50 C
40 C to +85 C
Yes
Design
Dimensions (W H D) in mm
Weight
approx.
84 54 49
170 g
Degree of protection
IP 67
UL listing
Yes
Order No.
SpliTConnect tap
} 6GK1 905-0AA00
for assembling PROFIBUS PA segments
and connecting PA field devices, insulation displacement method, IP 67
Delivery unit: 1 packet = 10 pcs.
SpliTConnect M12 outlet
Element for direct connection of
PROFIBUS PA field devices to the
SpliTConnect tap through
M12 connection
Delivery unit: 1 packet = 5 pcs.
SpliTConnect coupler
Coupling element for connecting
SpliTConnect taps in series to
configure star points
Delivery unit: 1 packet = 10 pcs.
6GK1 905-0AB10
6GK1 905-0AC00
}
SpliTConnect terminator
(Ex version)
for terminating PROFIBUS PA segments,
can be used in hazardous areas
Delivery unit: 1 packet = 5 pcs.
}
SpliTConnect terminator
(non-Ex version)
for terminating PROFIBUS PA segments,
for use in hazardous areas not possible
Delivery unit: 1 packet = 5 pcs.
SpliTConnect M12 Jack
Connector element
for direct connection of
PROFIBUS PA field devices to the
PROFIBUS PA segment through
M12 connection
Delivery unit: 1 packet = 5 pcs.
3/64
Siemens IK PI 2002/2003
6GK1 905-0AD00
6GK1 905-0AE00
6GK1 905-0AF00
Electrical Networks
Network components
Bus cables for field bus systems
to IEC 61158-2, e.g. PROFIBUS PA
Overview
Application
Design
Cable types
FC Process Cable:
Special bus cable according
to IEC 61158-2 for use in
hazardous areas (Ex version) and in non-hazardous
areas (non-Ex version).
Mounting
FastConnect
The FastConnect stripping
tool can be used to strip the
FC process cable for
PROFIBUS PA to the correct
length for casing and shield.
Cable installation
Keep the bus cable sealed
with a shrink-on cap at each
end during storage, transportation and installation.
Do not exceed bending radii
and tensile stress!
Siemens IK PI 2002/2003
3/65
Electrical Networks
Network components
Bus cables for field bus systems
to IEC 61158-2, e.g. PROFIBUS PA
Technical specifications
Cable type 1)
Ordering data
FC process cable 2)
Attenuation
at 38.4 kHz
3 dB/km
Inductance
0.7 mH/km
Impedance
at 38.4 kHz
100 20
Rated value
100
Loop resistance
44 /km
Effective capacitance
at 1 kHz
Approx. 90 nF/km
Operating voltage
(rms value)
100 V
Type of cable
(standard code)
02Y SY(ST) CY
1 2 1.0/2.55-100 BL OE FR
Sheath
Material
Diameter
Color
PVC
8.0 0.4 mm
blue or black
40 C to +60 C
40 C to +60 C
20 C to +60 C
Bending radii
First & final bending
Repeated bending
60 mm
120 mm
100 N
Weight
101 kg/km
Halogen-free
No
Behavior in fire
UL listing/300 V rating
Yes/CMX
Conditionally resistant
UV resistance
Yes
Silicone-free
Yes
Order No.
6XV1 830-5EH10
6XV1 830-5FH10
6GK1 905-6AA00
6GK1 905-6AB00
}
}
}
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
3/66
Siemens IK PI 2002/2003
Electrical Networks
Network components
DP/PA coupler and DP/PA link for PROFIBUS PA
Implements the transition
between PROFIBUS DP and
PROFIBUS PA
Overview
Modular expansion
Ex version available
Non-Ex version available
Design
DP/PA coupler
Housing in degree of protection IP 20
Two versions of the DP/PA
coupler:
Non-Ex version with up to
400 mA output current for
the PA cable;
Ex version with up to 90 mA
output current.
The PA cable of the Ex
version can be used in
hazardous areas. The DP/PA
coupler itself must be installed outside any hazardous areas.
DP/PA link
The DP/PA link is formed by
the IM 157 interface module
and one or more DP/PA
couplers (Ex and non-Ex
versions).
All components of the DP/PA
link are interconnected
through S7 backplane bus
connectors.
Ex and non-Ex versions of
the DP/PA link are also
possible by combining the
IM 157 with Ex and non-Ex
versions of the DP/PA coupler.
This modular system can
be expanded to up to 5 PA
lines.
The total depth is a max.
130 mm, the height 125 mm.
The width of the IM 157 is
80 mm. The total width of the
DP/PA link depends on the
number of DP/PA couplers
used.
Connection to PROFIBUS
DP only at the IM 157
through 9-pin Sub-D
connector.
The PROFIBUS DP interfaces of the DP/PA couplers
used in the DP/PA link have
no function.
Redundancy mode possible
on the S7-400 M.
Siemens IK PI 2002/2003
3/67
Electrical Networks
Network components
DP/PA coupler and DP/PA link for PROFIBUS PA
Possible applications
3
Functions
DP/PA coupler
Conversion of the data format from asynchronous
(11 bit/ character) to synchronous (8 bit/character)
and conversion of the transmission rate
Powering of field devices
Limiting of the supply
current through barriers
In the Ex version, the supply
current is limited to 90 mA,
with the non-Ex version to
400 mA .
The number of connectable
slaves or field devices is limited by the power consumption of the field devices.
3/68
Siemens IK PI 2002/2003
http://www.ad.siemens.de/simatic-cs
Redundancy
The S7-400 M supports
redundancy mode. Two
IM 157 are plugged in for this
purpose. The hot-swappable
function is made possible by
the backplane bus modules
BM 157 and BM DP/PA and
the sectional rail for active bus
modules.
Electrical Networks
Network components
DP/PA coupler and DP/PA link for PROFIBUS PA
System-wide integration
due to direct connection
of the PA field devices to
PROFIBUS DP
Technical specifications
DP/PA coupler
Interfaces
Connection for PROFIBUS PA
Intrinsically safe version (Ex)
IM 157
Function
2-pin screw-type terminal
integrated terminating resistor
output current in the range of
90 mA
4-pin screw-type terminal
switchable terminating resistor
output current <400 mA
9-pin Sub-D plug, contact
assignment as described
in IEC 61158/EN 50170
Connection through S7 backplane
bus connector (only necessary for
PA-Link ); non-isolated
Backplane bus
Displays
Supply voltage
24 V DC (green)
24 V DC
Current consumption
Ex version
Non-Ex versionmax.
Design
Dimensions (W H D) in mm
Interfaces
Connection for PROFIBUS DP
Backplane bus
SF (red)
BF DP (red)
BF PA (red)
24 V DC (red)
Displays
Supply voltage
max.
700 mA
1A
Mains buffering
Perm. ambient conditions
Operating temperature
Ex version
Non-Ex version
max.
max.
0 C to +60 C
25 C to +60 C,
horizontal mounting position
(vertical mounting position not
permissible)
80 125 130
Current consumption
24 V DC
max.
250 mA
Mains buffering
20 ms
Mechanical design
0 C to +60 C
Design
Dimensions (W H D) in mm
40 125 130
Configuration
Siemens IK PI 2002/2003
3/69
Electrical Networks
Network components
DP/PA coupler and DP/PA link for PROFIBUS PA
Ordering data
DP/PA coupler
for conversion of the transmission
method from RS 485 to IEC 1158-2
Intrinsically safe version (Ex)
Non-intrinsically safe version
(non-Ex)
IM 157
Interface module for DP/PA link
Manual
for DP/PA coupler/link
German
English
Order No.
}
}
6ES7 157-0AD81-0XA0
6ES7 157-0AC80-0XA0
6ES7 157-0AA81-0XA0
}
}
6ES7 157-0AA00-8AA0
6ES7 157-0AA00-8BA0
3/70
Order No.
Siemens IK PI 2002/2003
6ES7 195-7HE80-0XA0
6ES7 195-7HF80-0XA0
}
}
}
}
6ES7 195-1GA00-0XA0
6ES7 195-1GF30-0XA0
6ES7 195-1GG30-0XA0
6ES7 195-1GC00-0XA0
Optical Networks
Network components
Fiber-optic cable for PROFIBUS
Overview
Electrical isolation
No impairment through
external interference fields
Low weight
No grounding problems
Simple installation
62.5
Coating
Fiber sheath
250 m
125
Fiber core
Application
Material
Abbreviation
Symbol
Operating temperature range (C)
Halogen-free
Polyethylene Polyvinylchloride
PE
PVC
Polyurethane
PUR
High polymer
(flame retardent non
corrosive)
FRNC
Olefin/EVA
FRNC
PUR
2Y
11Y
11Y
40 to +70
20 to +70
50 to +80
25 to +90
40 to +80
No
No
Yes
Yes
Yes
Behavior in fire
Flammable
Oxygen index
LOI (%)
17
2132
30
36
26
Good
Poor
Poor
Good
Moderate
Moderate to
Good
Good
Moderate
Moderate to
Good
Good
Moderate
Moderate to
Good
Good
Moderate
Poor
Good
Good
Moderate
Good
Good
Abrasion
resistance
Good
Moderate
Very good
Good
Good
Mechanical
resistance
Good
Moderate
Good
Good
Good
Chemical
resistance
Moderate to
good
Poor
Moderate
Moderate
Moderate
Siemens IK PI 2002/2003
3/71
Optical Networks/OLM
Network components
Glass FOC (duplex cable) for PROFIBUS
Overview
Outer sheath
Kevlar strands
Support elements
Wire sheath
Glass fiber
Application
3/72
Siemens IK PI 2002/2003
G_IK10_deP0024s
INDOOR fiber-optic
indoor cable
Halogen-free, tread-resistant
and flame-retardant FOC for
use in buildings (e.g. in factory halls and building automation). Available in fixed
lengths, preassembled with
4 BFOC connectors.
Flexible fiber-optic
trailing cable
Fiber-optic cable for special
application in forced movement guidance, e.g. continuously moving machine parts
(track chain application) for
indoor and outdoor applications. Available in fixed
lengths, preassembled with
4 BFOC connectors.
Optical Networks/OLM
Network components
Glass FOC (duplex cable) for PROFIBUS
Technical specifications
Cable type
Fiber-optic
standard cable
INDOOR fiber-optic
indoor cable
Applications
Delivery unit
Type of cable
(standard code)
AT-VYY 2G62.5/125
3.1B200+0.8F600 F
T-VHH 2G62.5/125
3.2B200 + 0.9F600 F TB3 OR FRNC
Fiber type
Attenuation at 850 nm
Attenuation at 1300 nm
3.1 dB/km
0.8 dB/km
3.5 dB/km
1.0 dB/km
Number of fibers
Cable construction
Core type
Compact conductor
Solid core
PVC, gray
Kevlar fibers and impregnated
glass fibers
PVC, black
(3.5 0.2) mm
(6.3 9.8) 0.4 mm
approx. 65 kg/km
500 N (short time)
100 mm
over flat side only
Materials
Basic element
Strain relief
Outer sheath/cable color
Mechanical characteristics
Dimensions of basic element
Cable dimensions
Cable weight
Permissible tensile load
Bending radius
(2.9 0.1) mm
(3.9 6.6) 0.2 mm
Approx. 27 kg/km
800 N (short time)
50 mm (during installation)
30 mm (in operation)
over flat side only
10,000 N/10 cm (short time) 1)
2,000 N/10 cm (continuous) 2)
1.5 Nm/20 impacts/12.5 mm
5 C to +50 C
25 C to +60 C
25 C to +70 C
10 C to +50 C
20 C to +60 C
20 C to +70 C
Behavior in fire
Halogen-free
No
Yes
UL license
No
No
Silicone-free
Yes
Yes
energy/No./hammer wheel )
Perm. ambient conditions
Installation and mounting temperature
Operating temperature
Storage temperature
Siemens IK PI 2002/2003
3/73
Optical Networks/OLM
Network components
Glass FOC (duplex cable) for PROFIBUS
Technical specifications
Cable type
Flexible fiber-optic
trailing cable
SIENOPYR 3)
Marine duplex fiber-optic cable
Application
Delivery unit
Type of cable
(standard code)
MI-VHH 2G 62.5/125
3.1B200 + 0.8F600 + 2 x 1CU 300 V
Fiber type
Attenuation at 850 nm
Attenuation at 1300 nm
3.1 dB/km
0.8 dB/km
3.1 dB/km
0.8 dB/km
Number of fibers
Cable construction
Core type
PUR, black
Aramide fibers,
also GRP central element
PUR, black
Polyolefin
Aramide fibers
(3.5 0.2) mm
13.4 0.4 mm
(outer diameter)
approx. 135 kg/km
2000 N (short time)
1000 N (continuous)
150 mm
min. 100.000 bending cycles
(2.9 0.2) mm
13.3 0.5 mm
Materials
Basic element
Strain relief
Outer sheath/cable color
Mechanical characteristics
Dimensions of basic element
Cable dimensions
Cable weight
Permissible tensile load
Bending radius
30 C to +60 C
30 C to +60 C
Storage temperature
30 C to +70 C
Behavior in fire
Halogen-free
No
Yes
UL license
No
No
Silicone-free
Yes
Yes
3/74
Siemens IK PI 2002/2003
Optical Networks/OLM
Network components
Glass FOC (duplex cable) for PROFIBUS
Ordering data
Order No.
6XV1 820-5AH10
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
6XV1 820-5BH10
6XV1 820-5BH20
6XV1 820-5BH30
6XV1 820-5BH40
6XV1 820-5BH50
6XV1 820-5BN10
6XV1 820-5BN15
6XV1 820-5BN20
6XV1 820-5BN30
6XV1 820-5BN40
6XV1 820-5BN50
6XV1 820-5BN55
6XV1 820-5BN60
6XV1 820-5BN65
6XV1 820-5BN70
6XV1 820-5BN75
6XV1 820-5BN80
6XV1 820-5BT10
6XV1 820-5BT12
6XV1 820-5BT13
6XV1 820-5BT15
6XV1 820-5BT20
6XV1 820-5BT25
6XV1 820-5BT30
6XV1 820-7AH10
Preferred lengths 1)
0.5 m
1m
2m
3m
5m
10 m
15 m
20 m
25 m
50 m
75 m
100 m
SIENOPYR
marine duplex
fiber-optic cable
FOC for installation on-board
ships and offshore units
sold by the meter
max. consignment 1000 m
}
}
}
}
}
}
}
}
}
}
}
}
}
6XV1 820-7BH05
6XV1 820-7BH10
6XV1 820-7BH20
6XV1 820-7BH30
6XV1 820-7BH50
6XV1 820-7BN10
6XV1 820-7BN15
6XV1 820-7BN20
6XV1 820-7BN25
6XV1 820-7BN50
6XV1 820-7BN75
6XV1 820-7BT10
6XV1 830-0NH10
Order No.
FLEXIBLE FIBER-OPTIC CABLE 2)
trailing cable, splittable
}
sold by the meter
delivery consignment max. 2000 m
minimum order quantity 20 m
Preassembled with 4 BFOC connectors
Preferred lengths 1)
1m
2m
3m
5m
10 m
15 m
20 m
30 m
50 m
75 m
100 m
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
6XV1 820-6AH10
6XV1 820-6BH10
6XV1 820-6BH20
6XV1 820-6BH30
6XV1 820-6BH50
6XV1 820-6BN10
6XV1 820-6BN15
6XV1 820-6BN20
6XV1 820-6BN30
6XV1 820-6BN50
6XV1 820-6BN75
6XV1 820-6BT10
6GK1 901-0DA20-0AA0
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
Siemens IK PI 2002/2003
3/75
Optical Networks/OLM
Network components
Plastic and PCF FOC for PROFIBUS
Electrical isolation of
PROFIBUS devices and
PROFIBUS segments
Overview
Protection of transmission
line against electromagnetic
interference
Cable lengths of up to
80 m with plastic fiber-optic
cables and up to 400 m with
PCF fiber-optic cables
Application
Design
Plastic FOC,
standard cable
Rugged round cable with
violet PVC outer casing and
kevlar strain elements as
well as two plastic fibers with
a rugged polyamide inner
casing. For indoor applications with cable lengths of
up to 80 m.
PCF FOC,
standard cable
Rugged round cable with
violet PVC outer casing and
kevlar strain elements for
indoor applications with
cable lengths up to 400 m.
3/76
Siemens IK PI 2002/2003
Optical Networks/OLM
Network components
Plastic and PCF FOC for PROFIBUS
Technical specifications
Cable type
Application
Delivery unit
Type of cable
(standard code)
Fiber type
Attenuation
at wavelength
230 dB/km
660 nm
230 dB/km
660 nm
Number of fibers
Materials
Fiber core
Cladding
Inner sheath/color
Outer sheath/color
Strain relief
Polymethylmethacrylate (PMMA)
Special fluoridated polymer
PVC, gray
Polymethylmethacrylate (PMMA)
Special fluoridated polymer
PA, black or orange
PVC, violet
Kevlar fibers
980 m
1000 m
2.2 0.01 mm
2.2 4.4 mm
0.01 mm
7.8 kg/km
980 m
1000 m
2.2 0.01 mm
7.8 0.3 mm
50 N
Not suitable for continuous strain
100 N
Not suitable for continuous strain
30 mm
50 mm (over flat side only)
35 N/10 cm
100 mm
150 mm
100 N/10 cm
Conditionally resistant
Conditionally resistant
Conditionally resistant
Not UV resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
30 C to +70 C
35 C to +85 C
0 C to +50 C
30 C to +70 C
30 C to +70 C
0 C to +50 C
Behavior in fire
Silicone-free
Yes
Core cross-section
Mechanical characteristics
Diameter of fiber core
Outer diameter of cladding
Diameter of inner sheath
Cable dimensions
Cable weight
65 kg/km
Short-time
Continuous
Bending radius
Once without tensile load
Repeatedly with tensile load
Transverse compressive strength
per 10 cm cable length (briefly)
Resistance to
Mineral oil ASTM No. 2
Mineral grease
Water
UV radiation
Perm. ambient conditions
Operating temperature
Transport/storage temperature
Laying and installation temperature
Siemens IK PI 2002/2003
3/77
Optical Networks/OLM
Network components
Plastic and PCF FOC for PROFIBUS
Technical specifications
Cable type
Core cross-section
Application
Delivery unit
Type of cable
(standard code)
Fiber type
Attenuation
at wavelength
10 dB/km
660 nm
Number of fibers
Materials
Fiber core
Cladding
Inner sheath/color
Outer sheath/color
Strain relief
Quartz glass
Special fluoridated polymer
1)
PVC, violet
Kevlar fibers
Mechanical characteristics
Diameter of fiber core
Outer diameter of cladding
Diameter of inner sheath
Cable dimensions
Cable weight
Maximum permissible tensile load
Short-time
Continuous
Bending radius
200 m
230 m
4.7 0.3 mm
22 kg/km
500 N
100 N
(only on strain-relief, 50 N
on plug or single core)
75 mm
75 mm
750 N/10 cm
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
20 C to +70 C
30 C to +70 C
5 C to +50 C
Behavior in fire
Silicone-free
Yes
3/78
Siemens IK PI 2002/2003
Optical Networks/OLM
Network components
Plastic and PCF FOC for PROFIBUS
Ordering data
Order No.
6XV1 821-0BH10
6XV1 821-0BH20
6XV1 821-0BH50
6XV1 821-0BN10
6XV1 821-0BN15
6XV1 821-0BN20
6XV1 821-0BN25
6XV1 821-0BN30
6XV1 821-0BN50
6XV1 821-0BN65
6XV1 821-0BN80
6GK1 905-6PA10
6GK1 905-1PA00
6GK1 905-6PB00
}
PROFIBUS plastic fiber-optic,
polishing kit BFOC
Polishing kit for grinding and polishing
the BFOC plug face for PROFIBUS
plastic fiber-optic cables with OLM/P..
Order No.
PROFIBUS PCF fiber-optic
standard cable
PCF fiber-optic cable with 2 cores,
PVC outer casing, for bridging large
distances up to 400 m, preassembled
with 2 2 BFOC connectors,
each with tag length of 20 cm,
with insertion aid fitted to one end,
for connecting OLM/P..
Preferred lengths 1)
75 m
}
100 m
}
150 m
}
200 m
}
250 m
}
300 m
}
400 m
}
6XV1 821-1BN75
6XV1 821-1BT10
6XV1 821-1BT15
6XV1 821-1BT20
6XV1 821-1BT25
6XV1 821-1BT30
6XV1 821-1BT40
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
}
}
}
6GK1 975-1AA00-3AA0
6GK1 905-6PS00
Siemens IK PI 2002/2003
3/79
Optical Networks/OLM
Network components
PROFIBUS OLM (Optical Link Module)
Overview
Assembly of optical
PROFIBUS networks (line,
star, ring) with glass, PCF
and plastics FO cables
Application
Design
3/80
Siemens IK PI 2002/2003
Optical Networks/OLM
Network components
PROFIBUS OLM (Optical Link Module)
Functions
Configuration
OLM
OLM
OLM
OLM
S7-400
S7-300
Drive
ET 200S
FOC
Bus cable
for PROFIBUS
Fig. 3/33
G_IK10_deP0059s
PC with WinCC
Siemens IK PI 2002/2003
3/81
Optical Networks/OLM
Network components
PROFIBUS OLM (Optical Link Module)
Technical specifications
Ordering data
Order No.
Baud rates
6GK1 502-2CA10
Signal delay
6 bit times
PROFIBUS OLM/P11
Optical Link Module with 1 x RS 485
and 1 x plastic FOC interface (2 BFOC
sockets), with signal contact and measuring output without BFOC connector
PROFIBUS OLM/P12
Optical Link Module with 1 x RS 485
and 2 x plastic FOC interface (4 BFOC
sockets), with signal contact and measuring output without BFOC connector
6GK1 502-3CA10
PROFIBUS OLM/G11
Optical Link Module with 1 x RS 485and 1 x glass FOC interface
(2 BFOC sockets),
for standard distances,
with signal contact and measuring
output
6GK1 502-2CB10
PROFIBUS OLM/G12
Optical Link Module with 1 x RS 485
and 2 x glass FOC interface
(4 BFOC sockets),
for standard distances up to 3000 m,
with signal contact and measuring
output
6GK1 502-3CB10
PROFIBUS OLM/G12-EEC
Optical Link Module with 1 x RS 485
and 2 x glass FOC interface
(4 BFOC sockets),
for standard distances up to 3000 m,
for extended temperature range
20 C to +60 C,
with signal contact and measuring
output
6GK1 502-3CD10
PROFIBUS OLM/G11-1300
Optical Link Module with 1 x RS 485
and 1 x glass FOC interface
(2 BFOC sockets),
1300 nm wavelength for long distances
up to 15 km, with signal contact and
measuring output
6GK1 502-2CC10
PROFIBUS OLM/G12-1300
Optical Link Module with 1 x RS 485
and 2 x glass FOC interface
(4 BFOC sockets),
1300 nm wavelength for long distances
up to 15 km, with signal contact and
measuring output
6GK1 502-3CC10
Interfaces
Connection for bus segment,
station or OLM
Port for power supply
and signal contact
Connection for FOC
Measuring instrument connection
Optical interfaces
OLM/P11 and OLM/P12
Plastic FOC
980/1000 m
230 dB/km
0 to 80 m
PCF FOC
200/230 m
10 dB/km
0 to 400 m
Glass FOC
Optical interfaces
OLM/G11, OLM/G12 and OLM/G12-EEC 62.5/125 m
3.5 dB/km
Wavelength
860 nm
Transmitter power
13 dBm
Receiver sensitivity
28 dBm
Permissible FOC line attenuation
12 dB
(system reserve 3 dB)
FOC line length
0 to 3000 m
Glass FOC
50/125 m
3 dB/km
860 nm
15 dBm
28 dBm
10 dB
Optical interfaces
OLM/G11-1300, and OLM/G12-1300
Glass FOC
62.5/125 m
1 dB/km
1310 Nm
17 dBm
29 dBm
10 dB
Glass FOC
10/125 m
0.5 dB/km
1310 Nm
19 dBm
29 dBm
8 dB
0 to 10 km
0 to 15 km
Wavelength
Transmitter power
Receiver sensitivity
0 to 3000 m
24 V DC (18 V to 30 V DC)
Supply voltage
Current consumption
(at rated voltage)
max. 200 mA
Power consumption
max. 6 W
Mounting
0 C to +60 C
max.
20 C to +60 C
40 C to +70 C
95% at +25 C
Design
Dimensions (W H D) in mm
Weight
approx.
Degree of protection
IP 40
}
}
}
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
3/82
Siemens IK PI 2002/2003
Overview
Protection of transmission
line against electromagnetic
interference
Cable lengths of up to 50 m
with plastic fiber-optic cable
and up to 300 m with PCF
fiber-optic cable
Application
Design
PCF FOC,
standard cable
Rugged round cable with
violet PVC outer casing and
kevlar strain elements for
indoor applications with
cable lengths up to 300 m.
ECOFAST fiber-optic
hybrid cable
The rugged and trailing-type
hybrid cable contains two
plastic fiber-optic cables for
the data transfer and four
copper conductors
(1.5 mm2) for the power
supply to DESINA1) stations.
Siemens IK PI 2002/2003
3/83
Application
Delivery unit
Type of cable
(standard code)
Fiber type
Attenuation
at wavelength
230 dB/km
660 nm
230 dB/km
660 nm
Number of fibers
Polymethylmethacrylate (PMMA)
Special fluoridated polymer
PVC, gray
Polymethylmethacrylate (PMMA)
Special fluoridated polymer
PA, black or orange
PVC, violet
Kevlar fibers
300 V
10 A
1.5 mm2
PVC, black
980 m
1000 m
2.2 0.01 mm
2.2 4.4 mm 0.01 mm
7.8 kg/km
980 m
1000 m
2.2 0.01 mm
7.8 0.3 mm
65 kg/km
50 N
Not suitable for continuous strain
100 N
Not suitable for continuous strain
30 mm
50 mm (over flat side only)
35 N/10 cm
100 mm
150 mm
100 N/10 cm
Conditionally resistant
Conditionally resistant
Conditionally resistant
Not UV resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
30 C to +70 C
35 C to +85 C
0 C to +50 C
30 C to +70 C
30 C to +70 C
0 C to +50 C
Behavior in fire
Silicone-free
Yes
Yes
Core cross-section
Materials
Fiber core
Cladding
Inner sheath/color
Outer sheath/color
Strain relief
Copper conductors
rated voltage
current load
rated cross section
casing material/color
Mechanical characteristics
Diameter of fiber core
Outer diameter of cladding
Diameter of inner sheath
Cable dimensions
Cable weight
Maximum permissible tensile load
short-time
continuous
Bending radius
once without tensile load
repeatedly with tensile load
Transverse compressive strength
per 10 cm cable length (briefly)
Resistance to
mineral oil ASTM No. 2
mineral grease
water
UV radiation
Perm. ambient conditions
Operating temperature
Transport/storage temperature
Laying and installation temperature
3/84
Siemens IK PI 2002/2003
Application
DESINA-compliant devices,
e.g. for ET 200X
Delivery unit
Type of cable
(standard code)
Fiber type
Attenuation
at wavelength
10 dB/km
660 nm
280 dB/km
660 nm
Number of fibers
2 FO cables, 4 copper
Quartz glass
Special fluoridated polymer
1)
PVC, violet
Kevlar fibers
Polymethylmethacrylate (PMMA)
Special fluoridated polymer
PA, black, orange
PUR, violet
300 V
10 A
1.5 mm2
PVC, black
200 m
230 m
4.7 0.3 mm
22 kg/km
980 m
1000 m
2.2 0.01 mm
10.6 mm
146 kg/km
500 N
100 N
(only on strain-relief, 50 N
on plug or single core)
60 N
75 mm
75 mm
750 N/10 cm
110 mm
100 N/10 cm
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
Conditionally resistant
No
20 C to +70 C
30 C to +70 C
5 C to +50 C
+5 C to +70 C
30 C to +70 C
+5 C to +70 C
+160 C (max. 5 sec)
Behavior in fire
Silicone-free
Yes
Yes
Core cross-section
Materials
Fiber core
Cladding
Inner sheath/color
Outer sheath/color
Strain relief
Copper conductors
rated voltage
current load
rated cross section
casing material/color
Mechanical characteristics
Diameter of fiber core
Outer diameter of cladding
Diameter of inner sheath
Cable dimensions
Cable weight
Maximum permissible tensile load
short-time
continuous
Bending radius
Siemens IK PI 2002/2003
3/85
Order No.
6GK1 901-0FB00-0AA0
6GK1 905-6PA10
Order No.
ECOFAST fiber optic
hybrid cable (DESINA-compliant)
Trailing-type cable with 2 plastic FOCs
and 4 copper conductors, 1.5 mm2 only
for use with DESINA-compliant devices
Sold by the meter
Non-preassembled
20 m
50 m
100 m
6XV1 830-6CH10
}
}
}
6XV1 830-6CN20
6XV1 830-6CN50
6XV1 830-6CT10
}
}
}
}
}
6XV1 830-6DH15
6XV1 830-6DH30
6XV1 830-6DH50
6XV1 830-6DN10
6XV1 830-6DN15
Preassembled
(Hanbrid plug)
}
}
6GK1 905-0BA00
6GK1 905-0BB00
6XV1 821-1CN50
6XV1 821-1CN75
6XV1 821-1CT10
6XV1 821-1CT15
6XV1 821-1CT20
6XV1 821-1CT25
6XV1 821-1CT30
Plug adapter
for installation of the plastic simplex
plug in connection with
IM 467 FO, CP 342-5 FO,
IM 151 FO and IM 153-2 FO,
50 pcs.
Manual for PROFIBUS networks 3)
Paper version
Network architecture, configuring,
network components, installation
German
English
}
}
}
6ES7 195-1BE00-0XA0
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
3/86
Siemens IK PI 2002/2003
Overview
Application
Design
Functions
Connection of a PROFIBUS
DP station with RS 485 interface through 830-1T connecting cable or PROFIBUS
cable with bus connectors
(terminated both ends) or an
RS 485 segment
Provision of an electrical
connection point to an optical line (e.g. programming
connector for commissioning and diagnosis)
Siemens IK PI 2002/2003
3/87
Configuration
ET 200S
with IM 151 FO
ET 200M
with IM 153-2 FO
DP station
without integrated optic
OBT
Connecting
cable 830-1T
Other
stations
Technical specifications
Ordering data
Baud rates
Interfaces
Connection for DP stations
or a DP RS 485 segment
Connection for power supply
Connection for FOC
Optical interfaces
Plastic FOC
980/1000 m
640..660 nm
5.9 dBm
20 dBm
13 dB
Supply voltage
24 V DC (18 V DC to 30 V DC)
Wavelength
Transmitter power
Receiver sensitivity
Current consumption
(at rated voltage)
max. 200 mA
Power loss
6W
Mounting
max.
0 C to +60 C
40 C to +70 C
95% at +25 C
Design
Dimensions (W H D) in mm
Weight
approx.
50.5 138 78
400 g
Degree of protection
IP 30
PCF FOC
200/230 m
640..660 nm
16 dBm
22 dBm
3 dB
Order No.
}
PROFIBUS OBT
Optical bus terminal for connecting a
PROFIBUS station or an RS 485 segment without integrated optical interface
to the optical PROFIBUS;
without simplex connector
6GK1 500-3AA00
6XV1 830-1CH15
6XV1 830-1CH30
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
}
}
}
6GK1 975-1AA00-3AA0
3/88
Siemens IK PI 2002/2003
G_IK10_deP0107s
Wireless Link
Network components
PROFIBUS ILM (Infrared Link Module)
Wireless PROFIBUS link
suitable for all protocols
Overview
Application
Design
Functions
A reduction in transmission
quality is indicated by an
LED and signal contact
before the data transmission
is aborted
The infrared link module
(ILM) can be used in daylight thanks to an integrated
filter which protects against
stray lighting. When mounting the Infrared Link Module,
make sure that there is an
uninterruptible visible connection between the modules
Replacement of worn
systems, e.g. slip rings,
conductors
An ILM illuminates a circle
of 4 m in diameter from a
distance of 11 m.
Siemens IK PI 2002/2003
3/89
Wireless Link
Network components
PROFIBUS ILM (Infrared Link Module)
Configuration
Master e.g. SPS
ILM
ILM
ILM
ILM
ILM
ILM
ILM
FTS
0
3/90
Siemens IK PI 2002/2003
Slave e.g.
ET 200S
Connection to mobile stations
G_IK10_deP0028s
Wireless Link
Network components
PROFIBUS ILM (Infrared Link Module)
Technical specifications
Ordering data
Baud rate
Interfaces
2 connections for bus segments
24 V DC
Power loss
7.5 W
Mounting
2 fixing holes
Degree of protection
IP 65
IR wave length
880 nm
Minimum range
0.5 m
Maximum range
15 m
0 C to +60 C
40 C to +70 C
95% at +25 C
max.
Design
Dimensions (W H D) in mm
Weight
approx.
Order No.
PROFIBUS ILM
Infrared link module for connecting
PROFIBUS stations and segments
without the need for wires
Manual for PROFIBUS networks 1)
Paper version
Network architecture, configuring,
network components, installation
German
English
SIMATIC NET manual collection
Electronic manuals for
communication systems,
protocols, products
on CD-ROM
German/English
}
}
}
6GK1 503-0AA00
6GK1 970-5CA20-0AA0
6GK1 970-5CA20-0AA1
6GK1 975-1AA00-3AA0
175 80 57
800 g
1) Additional language versions and manuals
can be found for the various products at:
http://www.siemens.de/automation/csi/net
Siemens IK PI 2002/2003
3/91