Description
Ash slurry pump start permit
First pump Start Permit :Slurry sump level normal.
Seal water pump header pressure normal.
Suction valve is open.
Fluid coupling service water pressure is Normal.
Fluid coupling oil temperature is normal.
Fluid coupling oil pressure is normal.
Second pump Start Permit :First Slurry pump is running
Third pump Start Permit :Open discharge valve.
Second slurry pump is running.
Auto start sequence
open Suction valve
Start seal water pump and ensure pressure is normal.
Open the seal water valve of first pump and ensure pressure is normal,
Open service water valve for fluid coupling and ensure pressure is normal
Start fluid coupling oil pump and and ensure pressure is normal.
Start first slurry pump.
Open seal water valve of the second pump.
Start second slurry pump.
Open seal water valve of the third pump.
Open Discharge valve.
Start third ash slurry pump.
Auto Stop Sequence
Alarm
Trip
5
3
3
3
After 20 sec. to pump
start
After 20 sec. to pump
start
After 5 Secs.
After 15 sec.
After 15 sec.
After 15 sec.
After 15 sec.
After 10 sec.
5
5
5
5
& Interlocks
Permissive
Alarm
Trip
15
80
5
5
5
5
5
5
30
5
35
30
30
30
Permissive
Alarm
Trip
Time Delay
(Sec)
10
3
10
30
3
10
Permissive
OR
Alarm
Trip
Time
Delay
(Sec)
Permissiv
e
Alarm
Trip
Time
Delay
(Sec)
10
Permissive
AND
Alarm
Trip
Time
Delay
(Sec)
Description
Start Permissive
LP water pump is running
Stand by pump Start Logic
Running Pump Trips
Common Header pressure low(Running pump will
trip after getting ON feed back of S/B pump)
Level alarm
High level
Low level
OR
Alarm
Trip
Time
Delay
(Sec)
s
Permissive
Alarm
Trip
Time
Delay
(Sec)
Permissive
Alarm
Trip
Time
Delay
(Sec)
Permissive
Alarm
Trip
Time
Delay
(Sec)
Permissive
Alarm
Trip
Time
Delay
(Sec)
AND
AND
AND
AND
AND
essor
Permissive
Alarm
80oC
Trip
Time
Delay
(Sec)
120oC
20-30 Sec
90-150 mm hg >325 mm hg
20 sec
AND
OR
AND
20 sec