Sei sulla pagina 1di 4

By FF Courier

th

Ref: BSQ/Y/NR1/E-006

09 April, 2011

To
Mr. Bhownesh Vyas
Shree Mega Power,
A Unit of Shree Cement Limited,
Bangurnagar, Beawar,
Dist. Ajmer, Rajasthan 305 901
Sub: Supply of Leakage Current and Transformer Winding Resistance Meter.
Ref: Your email enquiry dated 08/04/11
Dear Sir,
As you are aware we are the manufacturer of Test & Measuring Instruments having manufacturing facility at Pune.
Our products are mainly used by Power Utilities in their Generation, Transmission & Distribution Divisions. These
are indigenously designed by our R&D Department and are import substitute.
We are supplying our products regularly to all major customers like SEBs, POWER GRID, NTPC, NHPC, NPC,
BBMB, ENRON, TATA Power, Indian Railways and various OEMs like ABB, BHEL, CGL, ALSTOM, SIEMENS,
TELK, JYOTI etc. for past 24 years.
We give below the brief description of our product for your kind consideration.
Leakage Current Analyser for Surge Arrestor, Model SA 30i: It is a State of the Art, Simple, Lightweight,
Portable system for Residual life Assessment of Lightning Arrestors under the hostile electrostatic noise found in
live EHV switchyard. The instrument measures and directly displays the values of resistive and total leakage
current as per IEC 60099-5. Trend analysis software enables the decision to replace the LA considering safety
rd
limits. It measures resistive current with 3 Harmonic and system harmonic compensation method. In built
temperature measurement facility and enables calculation of temperature compensated leakage currents. Results
are displayed on LCD, printed on thermal printer and can be stored in the in-built memory of the instrument. Other
feature includes In-built Rechargeable Battery & built-in Standard Calibration verification source. PC connectivity
is provided for test set up & data download through Windows based software.
Transformer Winding Resistance Meter, TRM 104: A 4 digit Transformer Winding Resistance Meter to
measure the winding resistance as well as current of large inductive windings like HV/EHV transformers, large
rotating machines etc. The innovative, portable design of this meter enables the on - site measurements of these
resistances at good accuracy and repeatability. The open circuit voltage of 30V DC ensures quick stabilisation of
the reading. It provides different current ranges from 100mA to 10A to cover the measurement from 0.1 to
199.99. It has 2 channels, which enable measurement of resistance as well as current of two windings
simultaneously. Any discontinuity in OLTC while changing tap position is also indicated. The meter incorporates
special circuitry to protect itself from back emf of large transformers.
We are enclosing the technical literature of the above mentioned product for your ready reference and kind
consideration.
We are quite confident that addition of these instruments to your testing department will enhance the testing
facilities at your end.
Should you require any further information / clarification, please feel free to contact us.
Thanking you and assuring you our best attention for all the time, we remain,
Yours faithfully,
For SCOPE T&M Pvt. Ltd.

(Pankaj Malakar)
Assistant Manager Marketing
Corporate Office

Works & After Sales

402, Aurus Chambers, Annex A,


S. S. Amrutwar Marg, Worli,
Mumbai 400 013, India.
Phone : +91-22-4344 4244
Fax : +91-22-4344 4242
E-mail : marketing@scopetnm.com
Website : www.scopetnm.com

EL 31/11, J Block,
MIDC Bhosari,
Pune 411 026, INDIA.
Phone : +91-20-27130307, 27130010
FAX : +91-20-27130094
E-mail : works@scopetnm.com
Website : www.scopetnm.com

An ISO 9001 : 2008 Certified Organisation


Regd Off : 1/4 Lokmanyanagar, Pune 411 030

QUOTATION
Ref.: Your email enquiry
Date: 08/04/11

Qotn. No.:
Date:

BSQ/Y/NR1/E-006
09/04/11

To,
Mr. Bhownesh Vyas,
Shree Mega Power,
A Unit of Shree Cement Limited,
Bangurnagar, Beawar,
Dist. Ajmer, Rajasthan305 901
Sr.
No.

Description of the Product

Rate
(Rs)

Qty

Price
(Rs)

1.

Lightening Arrestor Leakage Current Analyser, Model SA 30i as per 7,15,000=00 1 No 7,15,000=00
attached technical literature. This will include the following:
- Basic Instrument in hard carrying case
- Test Lead Sets in soft carrying bag containing Clamp-on CT, Field
Probe with extendable mounting arrangement, Other test leads,
Communication cable, Battery Charging cable etc.
- Thermal Paper Roll
- Factory Test & Calibration Certificate
- Instruction Manual

2.

TRM 104:
4 digit Transformer Winding Resistance Meter for 2,03,500=00 1 No 2,03,500=00
measurement of resistance as well as current of HV/EHV transformer
windings, windings of large rotating machines etc. This has two
resistance & current channels to measure the HV/LV winding resistance,
currents simultaneously & displays it separately on 4 line 20 Character
backlit LCD. This is supplied with set of test leads of 15 meter length.

Commercial Terms & Conditions:


1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

11.
12.
13.
14.
15.
16.
17.

Price
Freight
Insurance
CENVAT (ED)
Education Cess
Sec.& Higher.EC
Sales Tax

:
:
:
:
:
:
:

Firm, Ex. works Pune.


Extra, @ 1%.
Extra, @ 1%.
This will be charged extra as applicable at the time of delivery. Present rate is 10%.
Extra, @ 2% on actually charged Excise Duty.
Extra, @ 1% on actually charged Excise Duty.
This will be charged extra as applicable at the time of delivery. Present rate is @ 2%
against Form C otherwise it is @ 12.5%.
Octroi
: If any, will be extra as applicable. To your account.
Entry Tax / Special : If any, will be extra as applicable. To your account.
Entry Tax
Payment Terms
: 100% in advance against Proforma Invoice before dispatch.
Payment will be made only by a) ECS or, b) Crossed Demand Draft in favour of
SCOPE T&M Pvt Ltd payable at Pune. Bank Charges will be borne by us. Or, c) At
Par Cheque.
Delivery Period
: Within 3 Months from the date of receipt of your clear & confirmed purchase order.
Validity of Offer
: 3 Months.
Mode of Dispatch : By Road / Rail transport on freight paid basis.
Road Permit or
If required, will be issued by you along with your confirmed Order.
Way Bill
Warranty
: 12 Months from the date of dispatch.
ST Reg. No.
: VAT RC NO.:411030S1663
VAT TIN : 27410002778V
CST RC NO.:411030C1108
CST TIN : 27410002778C
Jurisdiction
: Subject to Pune Jurisdiction.

For SCOPE T&M Pvt. Ltd.

(Pankaj Malakar)
Assistant Manager Marketing
Corporate Office

Works & After Sales

402, Aurus Chambers, Annex A,


S. S. Amrutwar Marg, Worli,
Mumbai 400 013, India.
Phone : +91-22-4344 4244
Fax : +91-22-4344 4242
E-mail : marketing@scopetnm.com
Website : www.scopetnm.com

EL 31/11, J Block,
MIDC Bhosari,
Pune 411 026, INDIA.
Phone : +91-20-27130307, 27130010
FAX : +91-20-27130094
E-mail : works@scopetnm.com
Website : www.scopetnm.com

An ISO 9001 : 2008 Certified Organisation


Regd Off : 1/4 Lokmanyanagar, Pune 411 030

SA 30i LEAKAGE CURRENT METER FOR SURGE ARRESTERS


SA 30i the leakage current meter from SCOPE is a State of the Art on-line test system for Residual
Life Assessment of Surge Arresters. The instrument measures and directly displays the values of
resistive and total leakage current.
The SA 30i can be pre-loaded with the identity (Asset number, make, year, Serial number etc.) and
tests conducted on the same ID of the Arresters are saved under its own folder. A trend analysis
software, SAdata picks up this data and files them in a similar fashion on a PC. This analysis
software enables the user to take a decision to repair/replace the arresters considering safety
limits.
SA 30i is designed to work under the hostile electrostatic noise found in live EHV switchyards.

SPECIAL FEATURES
q
Simple, lightweight, portable, feature-rich, affordable
q
Measures 3rd harmonic resistive current with system
harmonic compensation, and the total leakage current.
q
In built temperature measurement facility enables
calculation of temperature compensated leakage currents.
q
Date and time stamp on test data
q
Results are displayed on LCD, printed on thermal printer and
can be stored in the in-built memory of the instrument. 1000
test records can be stored.
q
The SA 30i is powered by easily available re-chargeable SLA
batteries. It works for a days testing needs on a single
charge.
q
The SA 30i is a switchyard compatible instrument. This
makes the instrument extremely convenient to use.
q
Built-in standard calibration source and self-calibration check
facility.
q
Serial communication port to transfer data to PC and
Windows
based data management software.
q
Data Management, Analysis and Trending through SAdata
software.

THE MEASUREMENT
A special low-noise clamp-on CT is used to read leakage current
in the earthing conductor of the Arrester. The field probe is a
non-contact, remote sensing device employed to take the
reference signal from the HV line to the Arrester, for
measurement of phase and system harmonics.
The SA 30i measures 3rd harmonic resistive and total leakage
current by compensating the harmonics present in the system
as per IEC 60099-5 B2 or without system harmonic
compensation as per IEC 60099-5 B1

STANDARD ACCESSORIES
q
Specially designed low noise, clamp-on CT
q
Field probe with extendable mounting arrangement
organised in a light-weight carrying case
q
Test lead set, suitable for testing EHV class SAs
q
Thermal paper roll
q
SAdata software
q
Instruction Manual

www.scopetnm.com
Head Office & Works
EL 31/11, 'J' BLOCK,
MIDC Bhosari,
Pune 411 026, INDIA
Phone : +91 20 2712 3007 / 8010
FAX : +91 20 2712 3094
e-mail : works@scopetnm.com
X-03-01

SPECIFICATIONS
Range

: Total leakage current 100 m


A to 10 mA
Resistive leakage current 1 m
A to 10 mA
Field Probe current 10 m
A to 1 mA

Resolution

:1m
A for both resistive & total currents

Accuracy
: 5% for both currents
Inputs
: External Clamp-on CT, Field Probe, External PT (110V AC)
Outputs
: Self-calibration output
Display
: 4 line X 20 character large backlit LCD
Keyboard
: 5 keys
Measurement : Total current, Resistive current
Compensation : Automatic, for Noise, System Harmonics & Temperature
Temperature
: In-built silicon thermometer for compensation
Power
: 12 V DC, 2.4 AH SLA rechargeable battery
Battery Charging: 230 V AC + 15%, 50 Hz + 10%
Environment
: 0 to 50 C, 95% RH (Non- condensing), Typical EHV
Switchyard
Dimensions
: 415 X 330 X 200 mm
Weight
: 7.5 Kg, instrument

Simple sol utions for difficult measurements

Marketing Office
402, Aurus Chamber, Annex - A,
S. S. Amrytwar Marg, Worli,
Mumbai 400 013, INDIA
Phone : +91 22 4344 4244
FAX : +91 22 4344 4242
e-mail : marketing@scopetnm.com

Specifications subject to change for product improvement

SCOPE

T&M Pvt Ltd

TRM 104 TRANSFORMER RESISTANCE METER


Winding resistance values of large transformers upto 500 MVA and rotating machines are directly displayed.
The TRM104 is a portable winding resistance meter, designed to work in live EHV switchyards.
The meter is protected against the back emf offered by large inductive windings.
A backlit 4 line LCD with a user-friendly menu sets up the instrument for the test. Winding resistances and
safety messages are also shown on this display.
It is possible to measure the resistance of two windings simultaneously.
The meter contains a special power source for rapid stabilisation of test results.

THE INSTRUMENT
A 30V DC, 10 Amp power source, controlled strategically by digital means passes the selected current through the windings.
Precision instrumentation amplifiers read voltage developed across the windings and the ohmic values are directly displayed.
Use of the classical Kelvin's 4-wire method ensures reliable measurement. Specially designed thermal management of
power source enables measurement over longer periods, when delta connected generator transformers are tested.
The TRM is capable of identifying the interruption of injected current during tap change of OLTC.
A beeper alarm during current injection ensures operator safety during measurement.

MEASURING WITH TRM 104

SPECIFICATIONS

n
Isolate

the test object from both sides and provide earthing


n
Connect the TRM as shown
n
Remove earthing from both sides
n
Switch on the instrument
n
Using the Menu and keyboard, select range to capture
expected ohmic value
n
Select Start from the Menu and confirm TEST
n
TRM will issue beeps to indicate the flow of current.
Test current and winding resistances will be displayed.
n
STOP the measurement. Transformer will be automatically discharged.
n
The display will show safety status of discharge to enable
removal of test cables

CONNECTIONS

Display
Keyboard
Channels
CPU
Test Current Ranges
Resistance Range
Resolution
Accuracy
Open Circuit Voltage
Output power
Over Temperature
Current flow alert
Test Leads
Environment

230 V AC

MASTER
EARTHING

Fuse
3 A SloBlo

POWER

Warning !
Read Instructions before using the instrument.
Provide Earthing on at least one side of winding before
connecting voltage and current leads.
Remove Earthing from both sides before measurement.

Tr
an
Re sfor
sis m
ta er
n W
TR ce M ind
ete in
M
r g

Discharge the test object fully before removing connections.


Do not obstruct air inlet and outlet of instrument ventilation.

V+

Channel 1

ANALOG
PORT

10

C+

Current
Output

Power
Dimensions
Construction
Weight

: One backlit 4 Lines x 20 Character


LCD, for Current, Resistance and Menu
: 5 key menu sensitive
: Two, for simultaneous measurement on 2 Windings
: Atmel make 89C52
: 10, 5, 1, and 0.1 Amp DC
: 0.1
to 200
: 0.1
maximum
: Value 0.5 % 2 digits.
: 30 V DC
: More than 300 VA on 10 Amp range
: Protection by solid state sensor
: Beeper
: 20 m long with Ck Clamps for 4 Wire
Connections
: Upto 50 C, 95 % RH non-condensing,
Live switchyard upto 400 kV
: 230 VAC 15 %, 50 Hz 10 %, 400 VA
: 475 x 405 x 230 mm
: Industrial grade robust aluminum case
: 15 Kg, instrument

V+

Channel 2

SCOPE
T&M Pvt Ltd

DISCHARGE !

EL 31/11J, MIDC BHOSARI, PUNE 411 026, INDIA

ORDERING INFORMATION
Part No

Current Range
10A

5A

1A

100 mA

Resistance Range
2000
20 m
200 m
2
4m
40 m
400 m
4
20 m
200 m
2
20
200 m
2
20
200

www.scopetnm.com
Head Office & Works
EL 31/11, 'J' BLOCK,
MIDC Bhosari,
Pune 411 026, INDIA
Phone : +91 20 2712 3007 / 8010
FAX : +91 20 2712 3094
e-mail : works@scopetnm.com
X-03-01

Resolution
0.1
1
10
100
1
10
100
1 m
1
10
100
1m
10
100
1m
10 m

2313.08.01

Description

Std Qty

Transformer Resistance Meter, Model TRM 104 complete


with standard accessories

1 set

STANDARD ACCESSORIES
1 set
2304.05.06 Test Cables 20 m long, with Ck clamps, 75 mm opening
2304.05.07 Shorting lead, 10 m long, with Ck clamps, 75 mm opening 1 set
3000.23.05 Master Earthing Cable, 7 m long
1 set
3000.23.06 Mains C ord, 3 m long
1 no.
2304.05.26 Spare fuses
1 set
2304 Ax550 Carrying case for Test Lead Set
1 no.
2304.24.01 Instruction manual
1 no.
Note: Calibration Certificate having traceability to NPL is supplied
OPTIONAL ACCESSORIES
2304 45.01 Test Cables 20 m long, with Ck clamps of 100 mm opening 1 set
2304 45.02 Test Cables 20 m long, with Ck clamps of 150 mm opening 1 set

Simple sol utions for difficult measurements

Marketing Office
402, Aurus Chamber, Annex - A,
S. S. Amrytwar Marg, Worli,
Mumbai 400 013, INDIA
Phone : +91 22 4344 4244
FAX : +91 22 4344 4242
e-mail : marketing@scopetnm.com

Specifications subject to change for product improvement

SCOPE