SHORT-CIRCUIT DESIGN FORCES IN POWER LINES AND SUBSTATIONS

1.

INTRODUCTION

Short-circuit currents in power lines and substations induce electromagnetic forces acting on
the conductors. The forces generated by short-circuit forces are very important for highvoltage bundle conductor lines, medium-voltage distribution lines, and substations, where
spacer compression forces and interphase spacings are significantly affected by them.
Power Lines and Substations
Short-circuit mechanical design loads have been a subject of significant importance for
transmission line and substation design for many years, and numerous papers, technical
brochures and standards have been published (Manuzio 1967; Hoshino 1970; Havard et al.
1986; CIGRE 1996; CIGRE 2002; IEC 1993 and 1996; Lilien and Papailiou 2000). Under
short-circuit forces, there are some similarities and some differences between the behavior of
flexible bus and power lines.
For both the power lines and substations, the electromagnetic forces are similar in their origin
and shapes because they come from short-circuit current (IEC 1988). Nevertheless, as listed
below, there are some major differences between short-circuit effects on substation bus
systems and power lines:

Power lines are subjected to short-circuit current intensity, which is only a fraction of the
level met in substation bus systems. The short-circuit level is dependent on short-circuit
location, because longer lengths of lines mean larger impedance and lower short-circuit
level. The level also depends on power station location and network configuration.

Power line circuit configuration may not be a horizontal or vertical arrangement, thus
inducing other spatial components of the forces than in bus systems, and the movement
may be quite different.

Power lines have much longer spans and thus much larger sags than flexible bus and rigid
bus. This induces a very low basic swing frequency of the power line span (a fraction of
one Hz). Therefore the oscillating components of the force at the network frequency (and
its double) have negligible action on power lines.

Power line phase spacings are much larger than those in substations, and this has a
dramatic reduction effect on forces between phases.

Bundle conductors in power lines have much larger subspans than in substations, and
bundle diameter is often larger, too. Sometimes very large bundle diameter and a large
number of subconductors are used compared to bundled substation flexible bus. This has
significant effects on the phenomenon because long subspans reduce the effect of bundle
collapse upon the tension in the subconductors during short circuit conditions. Fig. 1
demonstrates the distortion of the subconductors of a quad bundle around a flexible spacer
during a short-circuit, known as the pinch effect, which causes the tension increase.

Due to differences in structure height and stiffness, power line towers have significantly
lower fundamental natural frequencies than substation structures. One result is that the
substation structures are more likely to respond dynamically to the sudden increase in
tension that results from the pinch effect.

Power line design load includes severe wind action and in some cases heavy ice loads
acting on much larger spans than in substations. Therefore design loads due to short
circuits may be of the same order as design wind and ice loads in substations, but much
less in transmission lines.

Bundle Conductor Lines


For bundle conductor lines, during a fault, the subconductors of the bundle move closer to
each other due to strong attraction forces because of the very short distance between
subconductors (Figure1).
Detailed discussions of this phenomenon were given by Manuzio and Hoshino (Manuzio
1967; Hoshino 1970).
From their initial rest position, the subconductors move towards each other, remaining more
or less parallel in most of the subspan, except close to the spacer (Figures 1 and 2). After first
impact, which for power lines is typically around 40 to 100 ms after fault inception, there is a
rapid propagation of the wave in the noncontact zone near the spacers, sequence c-d-e of
Figure 2. The inward slope of the subconductors at the spacer results in a component of
subconductor tension that tends to compress the spacer. This compressive force, or pinch,
while it is associated primarily with the change in angle, can be further increased by the rise
in tension in the subconductors due to bundle collapse. This jump results from the fact that
subconductor length in the collapsed condition is greater than in the normal condition.
The pinch is maximum when the wave propagation stops towards the spacer, position e in
Figure 2. The triangle of collapse then performs oscillations through positions d-c-d-e-d-c-ed-c and so on as long as electromagnetic force is still on, but with decreasing amplitude. If the
short circuit is long enough, the pinch oscillations result in a permanent oscillating force,
sensibly lower than peak value, typically 50%.
During the fault, the spacer is strongly compressed. The compression is related to maximum
pinch force in the conductor and the angle between the spacer and the subconductor.

Figure 1 Example of quad bundle before and during short-circuit test at 50 kA, showing
distortion of the subconductors. One flexible spacer at mid-span (courtesy Pfisterer/Sefag).
The subconductor movements occur at very high acceleration. For example, a 40 kA fault on a
twin bundle of 620 mm2 conductor, with a separation of 40 cm, may have acceleration up to
several tens of g, depending on the instantaneous current value. Spacers are subjected to
compression forces; and these instantaneous compression loads can be very high.

Upward movement of the whole span follows the rapid contraction of the bundle and reduces
the conductor tension, but does not reduce the maximum forces on the spacers occurring
during initial impact.

Figure 2
Attraction of subconductors of a bundle at a spacer during a short-circuit
(Manuzio 1967).
Interphase Effects and Distribution Lines
The video available on my web site (http://www.tdee.ulg.ac.be/doc-5.html) contains some
short-circuit tests on rigid bus, flexible bus and high-voltage overhead lines and distribution
lines.
Fault currents produce an impulse tending to make the separate phases of a circuit swing away
from each other, independently of whether the phases are bundled. The impulse that causes
this lasts only as long as the fault, so it is brief relative to the fundamental period of the span.
The momentum from the impulse carries the phases outward for a certain distance before their
tension arrests and reverses the motion. They then swing inward. This inward swing may be
4

large enough to cause cable contact and even permanent wrap-up at the middle of the span.
For double-circuit towers, the circuit subjected to the short circuit could force its phases to
come in contact with another circuit, thus causing outages on both circuits. There may also be
sag increases, up to several times the initial sag in distribution lines, due to heating effects
under short circuit, which may significantly affect the amplitude of movements.
Even though the inward swing could be short of interphase contact, if the phase spacing is
less than the critical flashover distance, and the inward swing occurs at the time that voltage is
restored by automatic reclosure, there will be a second fault.
Very large movements may be seen on distribution lines. Figure 3 shows the motion produced
during full-scale testing on an actual line. This is from an actual three-phase short-circuit test
on a 15-kV distribution line near Lige, Belgium (Lilien and Vercheval 1987). The photo
shows an instantaneous position of the conductors taken during the test. The fault current
level was 3 kA. The reduction in phase spacing may be particularly dramatic on mediumvoltage lines, even if the short-circuit level is much lower.

Figure 3 Instantaneous position of the conductors taken during three-phase short-circuit test
on 15-kV distribution line near Lige (Lilien and Vercheval 1987).
Substation with rigid busbars
The behavior of a rigid bus under short-circuit load is very depending of its first natural
eigenmode and eigenfrequency. Indeed electromagnetic forces includes pseudo-continuous
component combined with a 50 Hz and a 100 Hz component.
Some example are shown on the next figure.
The transient response is thus very depending on the voltage as low voltage (say 70 kV)
would have a short bar length and a reduced size tubular bar, when high voltage (typically 400
kV) would have long bar length and large tubes.
Moreover the busbar is installed on supporting insulators which have their own
eigenfrequencies, close to 50 Hz for 150 kV level. So that dynamics of such structures is far
from obvious and case dependent.

Fig xx : rigid busbar response to ta given electromagnetic force similar to a two-phase fault
with asymmetrical component in the short-circuit current. The transient response is given for
different busbar first eigenfrequency between 1.7 Hz and 150 Hz. (extract from CIGRE
brochure N 105, 1996).

Fig xx : a tested rigid bus (all details in CIGRE brochure 105, 1996), Measurement points are
located as S2, I2,C3 (constrains). Short-circuit of 16 kA during 135 ms with automatic
reclosure after 445 ms and a second fault of 305 ms with same amplitude as the first one.

Fig xx test results. The first eigenfrequency of the whole structure is about 3.3 Hz. There is
quasi no effect of the 50 Hz nor of the 100 Hz component of the force. As damping was
negligeable, as time to reclosure was particularly dramatic compared to structure oscillation,
the second fault induced about twice as much constrains compared to the first fault.

2.

FAULT CURRENTS AND INTERPHASE FORCES

A short-circuit current wave shape consists of an AC component and a decaying DC


component due to the offset of the current at the instant of the fault. The AC component
generally is of constant amplitude for the duration of the fault, and although the system
through which the fault passes is multimesh, it can usually be assigned a single global time
constant for the decay of the DC component. In high-voltage lines, and even more in lowvoltage lines, because the ratio X/R, reactance to resistance, is much less at low-voltage level,
the global time constant of the system is rather low, typically 20 to 80 ms, compared to
substations where it is typically 70 to 200 ms.

i1 (t ) 2 I rms (sin(t ) e sin( ))


t

2
2

i2 (t ) 2 I rms (sin(t ) e sin( ))


3
3
t

2
2
i3 (t ) 2 I rms (sin(t ) e sin( ))
3
3

(Amperes)

Where
Irms is the root-mean-square value of the short-circuit current (A).
= 2f is the network pulsation (rad/s) equal to 314 rad/s in Europe and 377 rad/s in the
United States.
is the network time constant (= L/R) at the location of the fault (s).
is an angle depending on the time of fault occurrence in the voltage oscillation (rad).
Asymmetry is very dependent on . In the case of a two-phase fault, it is possible to have no
asymmetry if = 0 rad.

According to the basic physics of electromagnetism for a three- or a two-phase arrangement,


there is always a repulsion force between phases from each other. For a single-phase fault,
only one current is involved. In the case of bundle conductors, it is generally considered that
the short-circuit current is equally divided among all subconductors. The force acting between
subconductors of the same phase is an attractive force, as discussed in Section 3.
In the general case of parallel conductors, the force, Fn(t) in N/m, applied on each of the
phases can be expressed by:

0 i1 (t ).i2 (t ) i1 (t ).i3 (t )
x

2
a
2a

i (t ).i2 (t ) i2 (t ).i3 (t )
F2 (t ) 0 x 1

2
a
a
i (t ).i3 (t ) i2 (t ).i3 (t )
F3 (t ) 0 x 1

2
2a
a

F1 (t )

(N/m)

Where
8

0 is the vacuum magnetic permeability = 410-7 H/m.


a is the interphase distance (m).
The force, being due to current flow, very much depends on phase shift between currents. It
generally includes:

Pseudo-continuous DC component, with a time-constant decay,


Continuous dc component, sometimes, and
Two oscillating AC components, one at network frequency, with a time-constant decay,
and one at the double of the network frequency, which is not damped.
In the case of a two-phase fault, the force is proportional to the square of the current. Thus it
always has the same directionthat is, a repulsion between the two faulted phases.
In the case of a three-phase fault, it is much more complex. In flat-phase configuration,
illustrated by the top view of Figure 4, the middle phase has a zero mean value, and at least
one of the outer phases has forces similar to those generated by a two-phase fault (Figure 5
left).
The same location in a network gives two different values of current for three- or two-phase
faults with a ratio 0.866 between them. For example, a 34.8 kA three-phase fault would give a
30.1 kA two-phase fault at the same location. Therefore, a three-phase fault has to be
considered for estimation of design forces.
Figures 4 (top) and 5 give examples of currents and forces on horizontal, or purely vertical,
arrangements. In the case of an equilateral triangular arrangement, Figure 4 (bottom), the
forces are similar on all three phases, similar to the force on phase 1 for the horizontal
arrangement.
Figure 5 shows the currents and forces applied to each phase during a three-phase fault with
an asymmetry chosen to create the maximum peak force on one outer phase as calculated
using Equation 2. This is for a horizontal or vertical arrangement of the circuit. The fault
current is 34.8 kA rms with peak currents of 90.4, 79.2, and 61.2 kA. The time constant is 70
ms, and the short-circuit duration is 0.245 seconds. The current frequency is 50 Hz. The loads
shown are per unit length for a = 6 m clearance between phases. The repulsion peak load on
phase 1 is 228 N/m. (= 1.39 rad). The signs convention is positive in the directions shown in
the upper diagram in Figure 4.
But the time dependence of the forces is very different on the outer phases compared to
middle phase. On the outer phases, the force is unidirectional and has a significant continuous
component. On phase 2, the continuous component is zero (except during the asymmetrical
part of the wave).

Figure 4 Two different geometric arrangements for a three-phase circuit and the
electromagnetic force reference directions on each phase corresponding to Equation 2. The
numbers 1, 2, and 3 are phase numbers.
It must be noted that the level of the peak force, about 200 N/m in Figure 5, is far greater than
the conductor weight and is proportional to the square of the current. But the continuous
component is much lower, about 30 N/m in this case, as shown later. Under actual shortcircuit levels and clearances, it is closer to the conductor weight, but acts, in most cases, in the
other direction. See upper right panel in Figure 5.

Figure 5 Example of calculated three-phase short-circuit current wave shape and


corresponding loads on a horizontal or vertical circuit arrangement.

10

Thus the interphase effects, for the case of horizontal or purely vertical arrangement only,
may be summarized as:
1. The design force on the horizontal or vertical three-phase arrangement is the force due to a
three-phase fault considering the outer phase with appropriate asymmetry. Taking into
account the fact that only the continuous dc component has to be considered, the force on
an outer phase can be approximated by Equation 3. This is the horizontal repulsion force
for the horizontal arrangement, or the vertical repulsion force for the vertical arrangement:
F

0.2 2
I 3 (0.75 1.616e 2t / )
a

(N/m)

Where
a is the interphase distance (m).
I3 the rms three-phase fault at that location (kA).

is the network time constant at that location (s).


t is time (s).
2. The forces considered above cannot be directly applied to structure design loads, because
the structural response to these loads has to be taken into account.
The continuous dc component acting after the short transient during the asymmetrical
period of the current is obtained by using t = infinity in Equation 3. For example, in
Figure 5, the continuous dc component after transient is given by:
F

0.2
34.82 x0.75 30.3 N/m
6

11

3.

BEHAVIOR OF BUNDLE CONDUCTORS UNDER SHORT CIRCUITS

Detailed behavior of bundle conductors under short circuit is most easily illustrated through
short-circuit tests in actual bundles. Some results from a program of tests at the Veiki
substation in Hungary are used here for that purpose (Lilien and Papailiou 2000).
The systematic single-phase fault tests on twin conductors were performed in the 1990s on a
power line with a double deadended span, with a length of 60 m, with the following
characteristics (Figure 6):
Span length
60 m
Sub conductor type ACSR CONDOR (455 mm, = 27.7 mm, 1.52 kg/m, UTS 125 kN)
Spacing
0.457 m
Current
35 kA (90 kA peak), Time constant 33 ms
Duration
0.17 to 0.2 s
Sagging tensions
15, 25, or 35 kN (per subconductor)
All cases are single-phase faults; the return path is through the ground
Supporting structure:
Stiffness:
about 8.5 106 N/m
First eigen frequency:
about 14 Hz

Figure 6 Test arrangement applying short circuits to a 60-m span length with one spacer at
mid-span. (Lilien and Papailiou 2000).
60 m

measurement

12

30 m

30 m

measurement
Figure 7 Two test span arrangements for spacer compression tests (Lilien and Papailiou 2000).

Figure 7 shows installation of rigid spacers and measurement points (bold lines) for the 60-m
subspan (Figure 7 top) and 30-m subspan (Figure 7 bottom). For the 30-m sub-span, two
spacers were installed close to each other so as to receive half the contribution. The
installation of measurement is such that actual load for spacers in power lines would be twice
the measured value.
The following oscillograms were recorded (Figure 8). On the left hand side, the 60-m span
length results are presented, and on the right-hand side, the 30-m span length results are
presented. It should be noted that the actual pinch occurs during the first approximately 0.2
seconds, while the fault current is on, and that the other spikes in the records arise from
subsequent motion of the bundle.
Sagging tension 15 kN - 35/90 kA

Sagging tension 15 kN - 35/90 kA


6000

4000

5000
3000

4000
3000

2000

C
om
pressiveloads(N
)

com
pressiveload(N)

2000
1000

0
0

0,2

0,4

0,6

0,8

1000
0
0

0,2

0,4

0,6

0,8

1,2

1,4

-1000
-1000

-2000
-3000

-2000
time (s)

subspan length 60 m

time (s)
subspan length 30 m

13

Sagging tension 25 kN - 35/90 kA

Sagging tension 25 kN - 35/90 kA


8000

8000

6000

6000

4000

Compressive load (N)

Compressive loads (N)

4000

2000

0
0

0,2

0,4

0,6

0,8

1,2

2000

0
0

1,4

0,2

0,4

0,6

0,8

1,2

1,4

1,6

-2000

-2000

-4000

-4000

time (s)

time (s)

subspan length 30 m

subspan length 60 m

Sagging tension 35 kN - 30/90 kA


7000

Sagging tension 35 kN - 30/90 kA

6000

6000

5000

5000

4000

4000

3000

Compressive loads (N)

7000

Compressive loads (N)

3000
2000
1000

2000
1000
0
0

0
0

0,2

0,4

0,6

0,8

1,2

1,4

0,2

0,4

0,6

0,8

1,2

1,4

-1000

-1000

-2000
-2000

-3000
-3000

time (s)
time(s)
subspan length 60 m

subspan length 30 m

Figure 8 Typical tests results on spacer compression on 60-m and 30-m subspan length, at 35
kA on twin-bundle line 2x Condor, with different sagging tensions. Half of the compression is
given. The drawings are covering short-circuit and significant after short-circuit time to better
see the wave propagation effects after the end of the short circuit. (Courtesy Pfisterer/Sefag).

After the short circuit, the subconductors separate from each other during a long transient,
with wave propagation along each subspan (as can be seen in the video that accompanies this
book and in Figure 8). During that transient, significant tensile forces (the opposite of
compression) are applied on the spacers, the level of which reach about 50% of the maximum
compression load. In spite of their smaller magnitude, the effect of these tension forces on the
spacer must be considered separately, because some spacer attachments are not as strong in
tension as they are in compression. A particular example is the attachment using an open or
saddle clamp, with helical rods to capture the subconductor. These loads are repeated with
every passage of the wave up and down the span. Note the shorter repetition time in the 30-m
span. These loads decay very slowly, so that many repeated such loads have to be taken into
account.
The graphs in Figure 8 show the effect of gradually increasing initial tension before the fault
from 15 kN (12.5% EDS) to 35 kN (28% EDS). The effect on propagation speed can be seen
in the after short-circuit peaks, but the influence on maximum pinch is limited in actual range,
as predicted by Manuzio (the pinch being proportional to the square root of the tension), and it

14

is particularly valid for long subspans, as used in power lines and as validated by Manuzios
test arrangements (Manuzio 1967).
In case of spring-type dampers, which could be compressed by the pinch, there could be a
large increase of these tensile loads acting on spacer attachment as the relaxation of energy
stored in spring compression during short-circuit is released after the end of the short circuit.
Depending on the configurations of the spacer and spacer dampers, the short-circuit forces
could cause large bending moment in the conductor and the elements of the spacer.

Figure 9 Typical tension oscillogram in one subconductor during and after the fault, for the
60-m span length configuration (15 kN initial). Irms 35 kA (peak 90 kA), 0.18 s courtesy
Pfisterer/Sefag).

In these tests, limited to one-phase fault, there is no interphase effect but, due to the increment
in tension caused by the pinch, the whole phase jumps up after short-circuit inception and
falls down afterwards. This behavior induces some tension changes in the conductors, as can
be seen in Figures 9 and 10. It is notable that the pinch effect (the first peak during the fault in
the first 0.18 s) in the conductor has a smaller tension rise than that which occurs, at 0.9
seconds, as the phase falls. In both cases, the latter is limited to 1.8 times the initial static
sagging tension.

15

Figure 10 Typical tension oscillogram in one subconductor during and after the fault for the 2
x 30-m span length configuration (15 kN initial). Irms 35 kA (peak 90 kA), 0.18 s. (courtesy
Pfisterer/Sefag).

Subspan Length Effect


Bundle pinch is very much related to subspan length. There exists a critical subspan length
under which no contact is possible and over which contact occurs on a significant part of the
subspan. Of course, that length depends on short-circuit level and some other parameters.
That critical value corresponds to extreme loading (for pinch effect in substations [El Adnani
1987; Lilien and El Adnani 1986]). For the power lines with typical subspan lengths,
subconductors experience contact in all cases except in jumpers.
Subconductor Separation Effect
A closer bundle spacing results in a smaller increment in subconductor tension. In fact, initial
electromagnetic force are stronger, but the tension increment is generated by conductor
deformation into the triangles of Figure 2 after contact, and most of deformation is located in
those triangles. Smaller conductor separation thus leads to less deformation in that area. At the
limit, if conductors are in contact all along the span, there is no increment in tension.

16

4.

INTERPHASE EFFECTS UNDER SHORT CIRCUITS

Maximum Tensile Loads during Movement of the Phases


Figure 11 shows a typical response of a bundle conductor two-phase fault in a horizontal
arrangement (CIGRE 1996). Both cable tension versus time (Figure11 left) and phase
movement in a vertical plane at mid-span (Figure 11 right) are shown. On the cable tension
curve, three maxima (and their corresponding time on the abscissa) have been indicated,
which is discussed below. On the phase movement curve at mid-span, the curve has been
marked by dots every 0.1 s to get an idea of the cable speed, and in particular to show that the
short circuit ends before there is significant movement of the phase.
Typical maximum loads (Figures 11 and 12) that could influence design appear when total
energy (including a large input during short circuit) has to be mainly transformed to
deformation energy.
Peak design load could occur under the following three conditions:
1. Maximum swing-out Ft (at time tt in Figure 11left and square 1 in Figure 11 right): very
little kinetic energy (cable speed close to zero) and potential energy with reference to
gravity, so that a large part is converted in deformation energythat is, increase of
tension. In power lines, tt occurs always after the end of the short circuit (the cable
position at the end of the short circuit (0.1 s) is indicated in Figure 11 right).
2. Maximum Ff at the extreme of downward motion (at time t f in Figure 11 left and square 2
in Figure 11 right): generally more critical because of a loss of potential energy of gravity
due to the cable position at that moment. tf always occurs after the end of the short circuit.
3. The pinch effect Fpi (at a very short time after short-circuit inception at t pi). The pinch
effect only occurs with bundle conductors, when subconductors come close to each other:
tpi always occurs during short circuit.

Figure 11 Left Figure: Tensile force (left) time evolution of a typical twin-bundle span during
two-phase short circuit between horizontal phases. Three maxima: F pi at time Tpi (so-called
pinch effect, due to bundle collapse), Ft at time Tt (the maximum of the force due to maximum
swing of the span represented by circle point 1 on the right figure), and F f at time Tf (the
maximum of the force due to cable drop represented by circle 2 in the right figure. Typically,
Tpi -40 ms, Tt +1.2 s and Tf = 4 s

17

Right figure: Movement of one phase (right) in a vertical plane at mid-span (X and Z are the
two orthogonal axes taken in the vertical plane at mid-span, perpendicular to the cable. Z is
vertical, -10 m is the initial point showing sag, and X is horizontal and transverse to the
cable). Such movement has been calculated for a two-phase fault of 63 kA (duration 0.1 s end
of short circuit being noted on the figure) on a 2 X 570 mm 2 ASTER on a 400-m span length
(sag 10 m) (Lilien and Dal Maso 1990).
It is interesting to compare the level of these loads with typical overhead line design loads
related to wind or ice problem (Electra 1991). Figure 11 shows results of such a case
calculated by simulation on a typical 400-kV overhead line configuration. Figure 12 shows
cable tension versus time in different dynamic loading conditions, as explained in the legend.
It can be seen that cable tensions due to short-circuit currents are significantly smaller than
other causes such as ice shedding.

Figure 12 Simulated longitudinal loads applied on attachment point on a cross arm on a


Beaubourg tower (the circuit configuration is shown by points T, R, and S in Figure 13) for
loading conditions (Lilien and Dal Maso 1990):
1. three-phase fault of 72.3 kA
2. two-phase fault of 63 kA
3. initial wind of 60 km/h followed by a gust at 100 km/h for 5 seconds on a quarter of the
span
4. shedding of ice sleeve of 6 kg/m
Reduction in Phase Spacing
After the initial outward swing, the phases move towards each other. For the case illustrated in
Figure 11, this inward movement exceeds 4 m per phase. That means a phase-spacing
reduction of more than 8 m. Other cases are shown in Figures 13 and 14 (only the rectangular
envelope of the movement is given) for different configurations and short-circuit level.
The timing of this inward swing may be such that the phase spacing is less than the critical
flashover distance at the time that voltage is restored by automatic reclosure. That would
induce a second fault with the dramatic consequence of a lock-out circuit breaker operation,
with all its consequences (power outage).

18

Figure 13 Calculated envelopes of phase-conductor movements for three types of loading


conditions on a Beaubourg tower (the figure is drawn in a vertical plane located at midspan: R, S, and T are their phase locations in still conditions) (Lilien and Dal Maso 1990):
1. two-phase short-circuit 63 kA either RT, RS, or TS
2. three-phase short-circuit 72.3 kA
3. initial wind speed of 60 km/h followed by a wind gust at 100 km/h during 5 s on a quarter
of the span.

Figure 14 Calculated envelope of phase-conductor movements for two-phase faults of


different rms amplitude (Lilien and Dal Maso 1990).
Distribution Lines
As mentioned earlier, very large movements may be seen on distribution lines (Figure 3).
Figure 15 shows a case of two circuits on the tower, where the faulted circuit forces some of
its phases to get in contact with the second (healthy) circuit, inducing a fault in the other
circuit so that both circuits trip out.
How to estimate the required interphase spacing is discussed further in Section 5 (Equation 8)

19

Figure 15 Three-phase short-circuit on 15-kV line (left circuit), with autoreclosure. a = fault
inception, b = 0.1 s, end of the first fault, c =0.4 s, time of reclosing, and d = 1.4 s end of the
second fault and definitive removal of the voltage on the line. Short-circuit of 2700 A on a
165-m span length, conductor 93.3 mm2 AAAC (Lilien and Vercheval 1987).

20

5.

ESTIMATION OF DESIGN LOADS

The most critical effects on power lines are:


1. For bundle conductors: spacer compression (Equation 4).
2. For power lines in general, but particularly for distribution lines: reduction in phase
spacing (Equation 8 for high-voltage line).
3. To a much lesser extent, and generally having negligible effect compared to other kind of
loading: tension increase generating longitudinal and transverse loads (Equation 7 for
longitudinal load due to interphase effect).
The loads under no. 3 above due to short circuits should be considered by line designers by
including them in the loading schedule for structures. Since there are three ways to have one
phase fault, three to have a two-phase fault, and one to have a three-phase fault, there may be
seven different loading conditions. They must, of course, be taken separately, since these
events cannot occur simultaneously.
Advanced calculation methods (Lilien 1983, El Adnani 1987, Wendt et al 1996, Declercq
1998, Stein et al 2000) may be used for any situation.
Bundle Conductors in Transmission Lines
Manuzio developed a simple method for spacer compression effect in bundle conductors
(Manuzio 1967).

Fc kI Fst log10 ( s / s ) (N)

Where:
Fst is initial sagging tension for each subconductor (N).
k is a correction factor depending on the number of subconductors.
ktwin = 1.57.
ktripple= 1.44.
kquad = 1.27.
I is the rms short-circuit value/phase (kA).
s is the bundle diameter, related to subconductor separation as by the formula (n = number
as
of subconductors): s
(m)
5
sin(180 / n)
s is the subconductor diameter (m).
Example:
21

Consider a case of a short circuit of 35 kA (rms/phase) acting on a twin ACSR Condor (27.7
mm diameter) conductor with 0.457 m conductor separation, tensioned at 25
kN/subconductor. Equation 4 gives a spacer compression force of:
Fc 1.57 x35 25000 x log10 (0.457 / 0.0277) 9586 N
However, in the analysis by Manuzio (Manuzio 1967), short-circuit current asymmetry was
neglected.
That has been taken into account in IEC 60865 for evaluating the maximum tension in the
conductor during fault. But IEC 60865 gives no recommendation for spacer compression.
Other methods to estimate spacer compression forces have been proposed (Hoshino 1970;
Pon et al. 1993; Lilien and Papailiou 2000). Some tests performed in Canada (Pon et al. 1993)
on spacer dampers for power-line-estimated spacer-compression design load up to 20 kN for
typical configurations and anticipated short-circuit levels.
Manuzios method can be safely applied to faults with maximum asymmetry through a correction
factor of 25% (multiply all k factors by 1.25). In fact, Manuzios method is very simple to apply
compared to other methods. It may not be accurate enough for use with respect to substation
flexible bus.
Alternatively, if we define Fpi (as shown in Figure 11) as the maximum tensile load in one
subconductor during the bundle pinch, another best fit would be to use Manuzio method (without
correction factor), but using Fpi pinch value instead of initial static pull. F pi can be evaluated by IEC
60685 method.
Fpi increases linearly (and not with the square) with short-circuit current. That is because a stronger
short-circuit current will increase contact length, thus reducing acting parts of the conductors.

Note: In the use of IEC method 60865 to evaluate Fpi, there is a need to introduce the socalled supporting structure stiffness. In this application, that stiffness is not simply the
static stiffness of supporting structure, but must take into account insulator chain movement
during the first tens of milliseconds of the fault to arrive at an equivalent stiffness (which in
fact would permit evaluation of span end movement, from short-circuit inception up to the
maximum pinch value, after about 40 to 90 ms. An heuristic evaluation indicates that a good
estimate for such equivalent stiffness may be to consider in most of the practical cases a value
of 105 N/m.
Despacering as a Means to Limit Pinch Effect
Despacering (removal of spacers) is an antigalloping measure (see Section 4.5) for some
power lines. It has been used up to the 245-kV level for twin bundles of limited diameter. In
such cases, the bundle is turned in vertical or slightly oblique position, and conductor
separation is increased compared to a spacered bundle. Moreover, it has been recommended
to use larger subconductor spacing at the middle of the span (compared to end of the span)
for example, 0.6 m at ends and 0.8 m at mid-span.
Such configurations may suffer from the kissing phenomenon under high electrical load,
because electromagnetic forces also act under load current. At such current levels,
nevertheless, the electrostatic repulsion (due to voltage) cannot be neglected. It can be shown
22

that, at surge impedance loading (SIL), equilibrium exists between attraction and repulsion
forces. Power flows are often several times (up to four times) the SIL, so that attraction forces
are generally stronger than repulsion. One of the major problems of such configurations is
linked to possible sticking of the subconductors following a perturbation. As electromagnetic
forces depend on distances, there exists a distance under which the subconductors always
come together and stick together, and it is very difficult to separate them without opening the
circuit. Sticking induces large permanent noise and increase in corona. To avoid such
problems, line designers have developed several proposals like the hoop spacer (see Section
4.5).
Under short circuit, these configurations result in clashing between subconductors and, as
subspan length (= span length in this case) is very large, there is little increment in tension.
But, in the case of hoop spacers or similar, the conductor clashing destroys these light spacers
beyond a certain level of short-circuit current.

Interphase Effects: Estimation of Tension Increase and Reduction in Phase Spacing

The following discussion pertains to the case of horizontal/vertical configuration and neglects
temperature heating effects (Lilien and Dal Maso 1990). Only one span is considered.
a = interphase distance (m).
m = mass per unit of length of one phase (kg/m).
Irms = root mean square of the three phase short-circuit current/phase (kA).
= time constant of the short-circuit asymmetric component decay (s).
tcc = duration of the fault (= time of first fault + time of second fault if auto-reclosing) (s).
L = span length (m).
Tst = phase conductor static tension before the fault condition (N).
EA/L = conductor extensional stiffness (product of Young modulus times cross section divided
by span length) (N/m).
K = tower stiffness (N/m) (order of amplitude 105 N/m).
f = initial sag (m).
R = maximum displacement (m).

1. The energy imparted to the conductor is given by:

23

2
(tcc )
1 0.2 I rms
E0 m

2
a.m

3L
(Joules)
4

2. The maximum tension in the conductor during movements:


Tmax Tst2

2 E0
L
2

EA K

3. The maximum displacement of one phase (zero to peak):

E0
2
R2 f
f
2

mgL

That maximum may be observed in the case when the conductors are moving away from
each other. But phase spacings can be critical when the phases move back towards each
other, in which case there is generally lower displacement (say, 80% of the separation
movement). In this case, the clearances may be reduced (the most dramatic case being a
two-phase fault) by 2 x 0.8 x R or 1.6 R.

24

The combined values of Tmax and R result in a transverse load on the suspension tower in
the case of a horizontal arrangement, for example.
There is very limited experimental validation of these formulas, because full-scale tests on
power lines have not been conducted.
It must be noted that advanced methods (finite elements) can be used to evaluate these
effects (details are given in CIGRE brochure 214-2002).
It is estimated that these formulas give results with 20% precision on the conservative
side.
Example:
For example, consider the following:
Short-circuit current at 63 kA during 100 ms (with time constant 60 ms) on a twin ASTER
570 mm2 (m = 2 x 1.55 = 3.1 kg/m) with interphase distance a = 8.5 m, span length of 400
m and initial sagging tension of 2 x 31000 = 62000 N:
Energy imparted to the conductor using Equation 6:

2
(tcc )
1 0.2 I rms
E0 m

2
a.m

0.2 x 632 (0.100 0.060)


3L 1
.
3.1

4 2
8.5 x3.1

3 x 400
10803 Joule
4

s
With conductor Young modulus = 5.6 x 1010 N/m2 and tower stiffness of K= 5 x 105 N/m,
the maximum conductor tension is calculated as:
Tmax 620002

2 x10803
77127
400
2
Newtons

10
6
5
510
2 x5.610 x57010

Assuming an initial sag of 9.8 m, the maximum displacement of one phase is :

E0
10803
R2 f
f 2 9.8

2
2

mgL
3.1x9.81x 400

3
3

9.82 27.88 means R = 5.2 m

Thus the reduction in phase spacing is 2 x 0.8 x 5.2 = 8.32 m.


It means that the remaining clearance is 8.5 - 8.3 = 0.2 m.
For the same case at 45 kA, the results are:
E0 = 2812 Joules
Tmax = 66270 N

25

Remaining clearance = 4.3 m


It can be noted that that energy varies as the fourth power of the short-circuit current.
This is due to the fact that short-circuit forces vary with the square of the current, so the speed
of the conductor at the end of the short-circuit also varies with the square of the current, and
energy in the system varies with the square of that speed.
The Case of Jumpers
At deadend structures, jumpers are used to connect the adjacent spans. These jumpers also
react during short circuit:
Interphase forces may cause jumper swing with possible drastic reduction of clearance with
tower legs or cross arms. Such effects may easily be limited by installation of appropriate
hold-down weights.
In case of bundle configuration, subspan length in the jumper cannot be large. Thus, the pinch
effect may cause the jumpers to bound upward toward the tower cross arms. Use of short
subspans in jumpers may be recommended to avoid clashing. Their use in substations may be
of interest in that connection.
Reference (CIGRE 1996) explains how to choose short subspans to avoid conductor clashing.

Interphase Spacers as a Mean to Limit Clearances Problem Linked with Short Circuit
Interphase spacers have been proposed to solve the phase-clearance problem during short
circuits (Declercq 1998). Experience has shown that appropriate installation of such devices
may effectively maintain appropriate clearances since conductor movement is restricted at
some location in the span.
A major challenge is defining the design load on these interphase spacers. Tests can be
performed, and some are available on the video accompanying this book. Advanced
calculation methods may also help to define these loads. Interphase spacers may be subjected
to bending stresses induced by conductor movements.

26

6.

REFERENCES

Manuzio C. 1967. An investigation of forces on bundle conductor spacers under fault


conditions. IEEE Trans. On Power Apparatus and Systems, Vol. 86, N2, 1967, pp166-185.
Serizawa, 1967. Y. Behaviour of dead-end suspension double-conductor bus during shortcircuit. The Journal of the Institute of Electrical Engineers of Japan, Vol 87, N11, Nov 1967,
pp 100-111
H. Hoshino, 1970. Estimate of forces exerted against spacers when faulty condition occurs.
IEEE Trans on Power Apparatus and Systems, Vol. 89, N7, pp 1475-1484
Lilien, J.L 1983., Contraintes et consquences lectromcaniques lies au passage du courant
dans les structures en cables. PhD 1983. Collections des publications de la Facult des
Sciences Appliques de lUniversit de Lige, N87
Tsanakas, D.; Papadias, B.1983. Influence of short-circuit duration on dynamic stresses in
substations. IEEE Trans. Power App. Syst. 102 (1983), pp 492-501
El Adnani, M. 1987. Efforts lectrodynamiques dans les liaisons haute tension constitues
de faisceaux de conducteurs. PhD 1987. Collections des publications de la Facult des
Sciences Appliques de lUniversit de Lige, N112.
Lilien, J.L., El Adnani M., 1986. Faisceaux de conducteurs et efforts lectrodynamiques. Vers
une approche numrique fiable. Proceedings of IEEE Montech86 Conference on AC Power
Systems. Pp 79-84
J.L. Lilien, P. Vercheval. 1987. Problems linked to changes in the arrangement of double
circuit line conductors. International Conference on Electricity Distribution. CIRED 1987,
session 3 (cable and overhead lines). Proceedings , report d.04 (6 pages).
IEC 60909 1988. Short-circuit current calculation in three-phase a. c. systems. Geneva: IEC,
1988
Loading and strength of overhead transmission lines. ELECTRA n137. 1991 (published by
WG 06 of SC 22).
M.Bulot, L.Demoulin 1992 . Contribution of Reliability analyses to the study of the effects of
short-circuit, Proceedings of the 5th International symposium on short-circuit currents in
power system.
M.Gaudry, Y.Maugain 1992. Influence of the wind on the mechanical design of transmission
structures against short-circuits, Proceedings of the 5th International symposium on shortcircuit currents in power system
C. Pon, A. Goel, S. Krishnasamy, H. Grad. 1993. Compressive loads on spacer-dampers due
to short-circuit currents. CEA report. Transmission Section, line hardware subsection, March
30, 1993, Montral, Qubec.

27

IEC 60865-1 1993. Short-circuit currents - Calculation of effects. Part 1: Definitions and
calculation method, Geneva: IEC, 1993
EN 60865-1 1993. Short-circuit currents - Calculation of effects. Part 1: Definitions and
calculation method. Brussels: CENELEC, 1993
IEC 60865-2 1994. Short-circuit currents - Calculation of effects. Part 2: Examples of
calculation. Genve: IEC, 1994.
G. de Wendt, T. Tietz, A:M. Miri, R. Ahlers, N. Stein 1996 Dynamic and Static Case Stress
Analysis of a HV Substation with Stranded Conductors (Test-Results- Calculation).
Proceedings of the 7th Int. Symposium on short-circuit currents in Power Systems, 1996.
CIGRE-105 1996. The mechanical effects of short-circuit currents in open-air substations
(Rigid and flexible bus-bars). Paris: CIGR, technical brochure N105. 2 volumes (180
pages).
Declercq, G.1998. Tests with droppers and interphase spacers. Proceedings of the 8th
International Symposium on Short-Circuit Currents in Power Systems, Brussels (Belgium), 810 October 1998, Proceedings pp. 143-148
Stein, N.; Meyer, W.; Miri, A.M. 2000. Tests and Calculation of Short-Circuit Forces and
Displacements in High Voltage Substations with Strained Conductors and Droppers. ETEP 10
(2000) No. 3 , pp 131138
J.L. Lilien, E. Hansenne, K.O. Papailiou. J. Kempf.2000. Spacer Compression for a tripple
conductor arrangement. IEEE Trans. On Power Delivery, Vol. 15, N1, pp 236-241, January
2000.
J.L. Lilien, K.O. Papailiou. 2000. Calculation of Spacer Compression for Bundle Lines under
Short-Circuit . IEEE Trans. On Power Delivery, Vol 15, N2, pp839-845.
CIGRE-214 2002. The mechanical effects of short-circuit currents in open-air substations
(Rigid and flexible bus-bars) (Part II) CIGR, technical brochure N214. 2 volumes (200
pages).
J.L. Lilien and F. Dal Maso, 1990. Contribution to Line Design by Accurate Predetermination
of Severe but Occasional Stresses. CIGRE Plenary session, 1990, Paris, Report 22-103.
D.G. Havard, C.J.Pon, H.A.Ewing,G.D.Dumol and A.C. Wong, 1986, Probabilistic
Short Circuit uprating of Station Bus System-Mechanical Aspects, IEEE PES