Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
GA S
TRAINING MODULE
ELECTRICAL
TITLE
:
MODULE NO :
Upon completion of this module, the technician would be able to demonstrate knowledge
and understanding on the following:
1. Electrical Fundamentals on earthing and lightning protection system
2 General principles on earthing and lightning protection system installation
3 Importance of earthing and lightning protection system in an electrical installation
4 Different types of earthing arrangement
5 Basic materials used in earthing system and lightning protection system installation
6 Requirements in earthing system installation
7 Maintenance and inspection for earthing and lightning protection system
8 Periodic maintenance and inspection on the installation
9 Different tests and testing instruments for earthing and lightning protection system
10 Earth resistance measurement
11 How to improve earthing system
12 Different means of protection against lightning surges
13 Principle of protection of Surge Arrester
14. Earthing and lightning protection system installed in the plant.
Page 2 of 42
TABLE OF CONTENTS
Section Topic
Page
Page 3 of 42
Page 4 of 42
Page 5 of 42
Page 6 of 42
19. TT system - a system having one point of the source of energy directly earthed, the exposedconductive-parts of the installation being connected to earth electrodes independent of the earth
electrodes of the source.
20. IT system - a system having no direct connection between live parts and Earth, the exposedconductive parts of the electrical installation being earthed.
21. System grounding (earthing) - intentional connection of neutral point to ground.
22. Equipment grounding (earthing) - refers to the connection of noncurrent carrying parts to earth
(ground).
Page 7 of 42
Page 8 of 42
L1
L2
L3
E
Ex. Grounded distribution system: Grounded Neutral
Accidental grounds in a grounded system generally cause the opening of breakers or the blowing
of fuses. However, the best protection against damage due to a ground fault may be obtained with a
ground-sensing relay that operates a tripping coil in the breaker. In the absence of a ground relay, the trip
setting of the breaker should be set as low as possible; however, the trip setting must be high enough to
prevent false tripping that may be caused by motor starting current.
Page 9 of 42
L1
N
L2
L3
Metallic
Enclosure
E
Ex. Equipment Earthing System
The framework of all electrical equipment, large or small, should be connected with lowresistance metallic conductors to a common point, usually the earth. Such connections eliminate the
shock hazard to operating personnel caused by normal leakage current and normal capacitive effects, and
reduce the hazard to personnel if an insulation fault should occur within the apparatus. ..
The equipment grounding conductors under normal conditions carry no current. The only time
they carry current is under abnormal conditions when the electrical equipment is faulty and has become a
shock or fire hazard. Under a fault condition, the earthing conductor that is connected to the outer sheet of
the equipment must be able to provide a very low resistance path back to the source of power so that
enough current will flow causing a breaker or fuse to open the circuit and automatically disconnect the
hazard from the system. It is not the purpose of this equipment earthing system to send current through
Page 10 of 42
the ground. The only time the current is intentionally sent into the earth is during a lightning strike or line
surge due to a nearby lightning strike.
3.2.1 CONNECTION OF ELECTRICAL EQUIPMENT TO EARTHING SYSTEM
Apparatus
Parts to be earthed
Method of connection
Power transformer
Transformer tank
Support of bushing
insulators, lightning arrester,
fuse, etc.
Isolator
Shunt reactor
Neutral, tank
Page 11 of 42
Page 12 of 42
marked in
Page 13 of 42
70 mm2
2. To metallic enclosures of LV electrical equipment having a supply cable with a conductor cross
section of 35 mm2 and more
70 mm2
3. To metallic enclosures of LV electrical equipment having a supply cable cross-sectional area less
than 35 mm2
25 mm2
25 mm2
5. To non-electrical equipment exposed to lightning, e.g. Tanks, columns and tall structures
70 mm2
25 mm2
EARTHING BAR
Page 14 of 42
energy for a TN-S system, by the supply undertaking to the neutral of the source of electrical energy for a
TN-C-S system, and connected by an earthing conductor to an earth electrode for a TT or IT system.
The main earthing terminal shall be accessible, to enable the earthing conductor to be
disconnected for test purposes. The joint shall be mechanically strong, reliably maintain electrical
continuity, and be capable of disconnection only by means of a tool.
A protective conductor (minimum cross-sectional area shall not be less than 2.5 mm2 copper),
may consist of one or more of the following:
1) a single core cable
2) a conductor in a cable
3) an insulated or bare conductor in a common enclosure with insulated live conductors
4) a fixed bare or insulated conductor
5) a metal covering, for example, the sheath, screen or armouring of a cable
6) a metal conduit or other enclosure or electrically continuous support system for conductors
7) an extraneous-conductive-part like suitable structural metalwork
Page 15 of 42
M
M
3
E
T
Legend: 1,2,3,4
1
2
3
4
B
M
C
P
T
E
= protective conductors
= circuit protective conductor
= main equipotential bonding conductor
= earthing conductor
= supplementary equipotential bonding conductors (where required)
= main earthing terminal
= exposed-conductive-part
= extraneous-conductive-part
= main metallic water pipe
= earth electrode (TT and IT systems)
= other means of earthing (TN systems)
Page 16 of 42
L1
L2
L3
combined
protective and
neutral conductor
PEN
consumers'
installations
source
of earth
equipment
in
installation
additional
source earth
exposed
conductive
parts
L1
consumers'
installations
source
of earth
L2
L3
N
protective
conductor (PE)
equipment
in
installation
exposed
conductive
parts
Page 17 of 42
TN-S system.
Separate neutral and protective conductors throughout the system.All exposed-conductive parts of
an installation are connected to this protective conductor via the main earthing terminal of the installation.
The protective conductor (PE) is the metallic covering of the cable supplying the installations or separate
conductor.
For a TN-S system, means shall be provided for the main earthing terminal of the installation to be
connected to the earthed point of the source of energy. Part of the connections may be formed by the
suppliers lines and equipment.
6.1.3 TN-C-S SYSTEM
source of energy
L1
L2
L3
combined
protective and
neutral conductor
PEN
consumers'
installations
source
of earth
equipment
in
installation
additional
source earth
exposed
conductive
parts
Neutral and protective functions combined in a single conductor in a part of the system.
The usual form of a TN-C-S is as shown, where the supply is TN-C and the arrangement in the
installation is TN-S. The supply system PEN conductor is earthed at several points and an earth electrode
may be necessary at or near a consumers installation.
All exposed-conductive-parts of an installation are connected to the PEN conductor via the main
earthing terminal and the neutral terminal, these terminals being linked together.
For a TN-C-S system means shall be provided for the main earthing terminal of the installation to
be connected by the supplier to the neutral of the source of energy.
Page 18 of 42
6.1.4 TT SYSTEM
source of energy
L1
L2
L3
N
consumers'
installations
source
of earth
equipment
in
installation
exposed
conductive
parts
installation
earth
electrode
installation
earth
electrode
L1
L2
L3
earthing
impedance
consumers'
installations
equipment
in
installation
source
of earth
exposed
conductive
parts
installation
earth
electrode
installation
earth
electrode
Page 19 of 42
IT system.
All exposed-conductive-parts of an installation are connected to an earth electrode.
The source is either connected to Earth through a deliberately introduced earthing impedance or is
isolated from Earth.
For a IT system, the main earthing terminal shall be connected via an earthing conductor to an
earth electrode.
Page 20 of 42
Solid Grounding
- Low earth fault current
- No sustained earth fault
- Easy fault detection
- Easy protection
- Higher safety
Solid Grounding
- Fault currents limited by fault resistance
- No rotating machines connected at this voltage
Page 21 of 42
The earthing system usually consists of an earthing grip of copper wires or strips. In order to
avoid the interference with installations for corrosion prevention, the grid shall consists of insulated wires
or strips instead of bare conductors, whilst earthing electrodes should be of suitable material.
The earthing path may include solidly connected metallic conduit, metallic piping, one-piece
copper conductor of appropriate size, the steel structure of a building, the hull of a ship, etc..
The connection to earth may be accomplished by connection to a metallic underground watersupply system or to driven earth electrodes using unpainted galvanized pipes, rods, or metal plates. The
pipes (3/4 inch in diameter) or rods (5/8 inch in diameter) should be driven to a depth of at least 8 feet.
Each plate electrode should be at least inch thick and have a cross-sectional area of at least 2 sq. ft.
Where over one electrode is used, spacing between them should be no less than 6 feet.
Earthing electrodes are spotted throughout the grid to provide a low enough earthing resistance.
Generally a resistance of the entire grid below 4 (four) ohms will be satisfactory.
Example of typical solid grounding installation
Page 22 of 42
In order to limit the fault current on transformers with a wye connected secondary, neutral
grounding resistors or reactors are often used on medium voltage systems from 1000 volts to 15,000 volts
phase to phase. These current limiting devices are connected in series with the transformer secondary
neutral. In the event of a phase-to-ground fault, the current will flow through, and be limited by, the
neutral resistor or reactor.
The three electrical ratings required to select a grounding resistor are: Voltage Rating, Current
Rating, and Time Rating.
Voltage Rating: based on the system phase-to-neutral voltage (phase-to-phase voltage divided by
square root of 3.
Current Rating: Low Resistance Grounded Systems, generally the range is from 25 to 600 amps.
High Resistance Grounded Systems, the current is limited to 10 amps or less
Page 23 of 42
Time Ratings: Standard Time Ratings are : Ten seconds, One minute, Ten minutes and Extended
Time
When a system has protective relays which will trip the circuit if a ground fault occurs, a
grounding resistor with a 10 second rating is often specified, because the relays will trip the system in less
than 10 seconds. However, one minute or ten minute ratings are sometimes used for an extra margin of
safety, even though the cost will be greater.
Page 24 of 42
Page 25 of 42
The most remote electrode must be placed a minimum of 5 times the distance of the length of the
ground rod being tested. It is preferable the most remote electrode be placed a distance equal to 10 times
the length of the rod under test. During the test the neutral must not be connected to the ground rod. The
neutral ground bond must be disconnected as the current flow on the neutral will invalidate the test results
and not all the test instrument will provide an accurate reading.
8.2.2 DIRECT MEASUREMENT BY THE USE OF CLAMP-ON-METER
There are test situations where fall-of-potential will be difficult at best. Examples are hilly terrain
and deep driven rods and places where 5 or 10 times the rod length may be difficult or what if you
cannot disconnect the neutral/ground bond.
possible substitute is by the use of Clamp-On Ground Resistance Tester. While not as accurate, but very
close to the accuracy of the fall-of-potential method.
The Clamp-On Ground Resistance Testers measure ground rod and grid resistance without the use
of auxiliary ground rods. The instrument take advantage of the connection between the ground and the
utility neutral. The clamp-on tester jaws contain two current transformers (CTs). One CT induces a high
frequency, fixed voltage into the conductor. If a continuous circuit exists, a resulting
current flows. The second CT then senses and measures the flowing current. The
instrument already knows the amount of voltage induced, and it can calculate the
resistance in Ohms and display the results.
Page 26 of 42
the protective device. The circuit would remain connected and energized and the fault current would
continue to flow. This could result in damage to equipment or the installation, and severe or fatal electric
shock to personnel in contact with grounded equipment.
Earth Loop Impedance Testing is used to determine the total alternating current of the circuit that
would be involved under fault conditions. Loop testing is required to ensure that the earth path is adequate
for the maximum possible fault current.
The test is conducted by using a ground loop impedance tester. The tester places a limited fault
current (about 20 amps) on the circuit under test for a limited time (about 20 ms). By measuring the
voltage drop across a reference resistor, the tester indicates the ohmic value of the fault loop. Digital loop
testers are available and are designed for a quick, accurate and reliable testing.
Loop impedance tests should be used to identify circuits with high resistance. The high resistance
may denote poor connections or excessive conductor length.
Example of Ground Loop Impedance Testing
R lo o p
V s u p p ly
V test
R test
I
Circuit with the loop tester on
Loop impedance R lo o p = (Vs u p p l y Vt e s t )/I
Page 27 of 42
Page 28 of 42
Page 29 of 42
20-30 m
20-30 m
R
3m
MEGGER
RP
CURRENT
SPIKE (C)
POTENTIAL
SPIKE(P)
ELECTRODE
UNDER TEST ( X )
3m
DET62D
EARTH
TESTER
RC
NOISE
BRUI T
ME ASUR E R
READING NO.1
Ohms
READING NO.2
Ohms
READING NO.3
Ohms
AVERAGE
Ohms
EARTH TESTER
Page 30 of 42
Page 31 of 42
Page 32 of 42
2. Circuit continuity is checked between earthing devices and earthed elements. Open circuit and
poor contact shall not be admitted.
3. The earthing system resistance shall be checked.
4. Cross-sectional areas of earth conductors should be checked.
10.3.1 INSPECTION OF EARTHING SYSTEM INSTALLATION
1. Disconnect each earthing electrode, measure the earthing resistance of each electrode. Earth
electrode must have a resistance of 25 ohms or less.
2. Measure the earthing resistance of the grid only.
3. Connect all electrodes to the grid and measure earthing resistance. Generally a resistance of the
entire grid below 4 (four) ohms will be satisfactory.
4. Connections and clamps are to be inspected as fas possible. At least a number of spot checks
shall be made of the buried connections.
5. Check the protective measures against mechanical damage of the grid and the earthing
electrodes.
10.3.2 TYPICAL CHECKLIST FOR INSPECTION OF EARTHING SYSTEM
Location: _____________________________________________________
Number of Electrodes: __________________________________________
Type of Electrodes: _____________________________________________
Type of Conductors: ____________________________________________
CHECK LIST
Actions
Check
Mark
Remarks
Page 33 of 42
Direct or induced
voltages caused by lightning strokes can cause a high-voltage wave to travel along a power line. Unless
this high surge voltage is reduced before reaching the terminals of an electrical machine, severe damage
will result.
Page 34 of 42
Where applied
Surge Arresters
Rod gaps
Horn gaps
Remarks
Protect buildings against
direct strokes.
Diverts over voltages to
earth without causing shortcircuit
Page 35 of 42
Surge Arrester (Lightning Arrester) is a device designed to protect electrical equipment from high
voltage surges and to limit the duration and amplitude of the discharge current. The arrester holds the
voltage across its terminals below the protective level and therefore the voltage appearing across surge
arrester terminals and on the terminal of the protected equipment does not exceed the protective level.
Page 36 of 42
surge-wave traveling along the overhead line comes to arrester, the gap breaks down. The resistance
offered being low, the surge is diverted to the earth. Thus the high voltage surge is discharged to earth.
Hence the insulation of the equipment connected to the line is protected. After a few microseconds, the
surge vanishes and normal power frequency voltage is set up across the arrester. The resistance offered by
resistor to this voltage is very high, therefore the arc current reduces and voltage across the gap is no more
sufficient to maintain the arc. The current flowing to the earth is automatically interrupted and normal
condition is restored.
12.2.2 GAP LESS ARRESTERS (METAL OXIDE VARISTORS SURGE ARRESTERS)
In another type of surge arresters, the active components are metal oxide resistors. They are
arranged in one stack and installed in an airtight sealed porcelain casing with sheds of high insulation
resistance. Metal-oxide resistors are highly nonlinear, i.e. They have a sharply kinked voltage-current
characteristic, with the result that below a certain voltage value only a small leakage current flows
through the arrester.
The arresters are so designed that under normal continuous voltage conditions only leakage
current flows, since the resistance value is several hundred megaohms. With lightning or switching over
Earthing and Lightning Protection System-Module No. E 02
Page 37 of 42
voltages, the resistors become conductive so that a surge current can flow to earth and the over voltage is
reduced to the value of the voltage drop across the arrester. The surge currents have values up to 1 kA
with switching over voltages, and of 1...10...20 kA with lightning over voltages.
BUS
ROTATING
MACHINE
DISTRIBUTION
LINE
BUS
TRANSFORMER
OVERHEAD LINE
1
SURGE
DIVERTER
1.
2.
3.
4.
Page 38 of 42
Page 39 of 42
Page 40 of 42
Page 41 of 42
References:
IEE Wiring Regulations
Handbook on the IEE Wiring Regulations
Preventive Maintenance of Electrical Equipment by Charles I. Hubert
Testing, Commissioning, Operation and Maintenance of Electrical Equipment by S. Rao
Page 42 of 42