SPECIFICATION DATA
Eagle Quantum
Fire and Gas
Detection/Releasing System
APPLICATION
Eagle Quantum combines a flame detection/extinguishing agent release system with a hazardous gas
monitoring system, integrated on a fault tolerant digital communication network. The system continuously
monitors analog process signals such as combustible
or toxic gas concentrations as well as flame detectors
and discrete contact closure type devices such as
manual fire alarm call boxes and heat detectors. The
sensor outputs are communicated to the control unit
for executing the fire suppression logic, controlling
the extinguishing agent release, signaling and annunciating output actuation, and communicating with an
external operator interface station for system configuration, monitoring, and event logging purposes.
SYSTEM DESCRIPTION
The Eagle Quantum system consists of three basic
components (see Figure 1):
1. Local Control Unit (LCU)
2. Local Output Unit (LIOU)
3. Intelligent field devices on the Local Operating
Network/Signaling Line Circuit (LON/SLC).
FEATURES
Agent release capability for fire suppression
Up to 244 detection nodes and 32,800 feet (10,000
meters) of wiring on the network
Accommodates a variety of devices with 4 to 20 ma
or dry contact type inputs
Fault tolerant communication loop
Non-volatile memory for alarm and calibration logging
Built-in diagnostics
Programmable logic
Complies with ANSI/NFPA-72 National Fire Alarm
Code
Programmable relays with SPDT dry contacts
9/01
90-1126-02
FIRE DETECTION
FLAME
DETECTORS
GAS DETECTION
CONTACT
CLOSURE
DEVICE
GAS SENSOR
OR OTHER
4 20 MA INPUT
IDC'S
DCU'S
FIRE RESPONSE
AGENT
RELEASE
MODULES
FIRE
SUPPRESSION
SIGNAL
AUDIBLE
MODULES
VISUAL/
AUDIBLE
INDICATORS
LOGIC
CONTROLLER
GATEWAY
ISOLATION
MODULE
OIS
PLC/DCS
DRY CONTACT
INTERFACE
LOCAL
OUTPUT
UNIT
(LIOU)
VISUAL/AUDIBLE
INDICATORS
The LIOU is part of the fire detection portion of the Eagle Quantum
system and performs functions
such as fire suppression agent
release and notification. The
LIOU consists of a card rack containing up to six output modules, mounted in a NEMA 4 enclosure.
The Release Module provides signaling and agent release capability. Its supervised outputs include
one programmable release circuit
The logic controller performs both fixed and user programmable logic operations.
and three Style Y signaling circuits. The release circuit is compatible with a variety of solenoid or initiator
based suppression systems.
Alarm/Calibration Log
Each network device maintains an alarm log in nonvolatile memory, recording the time and date for the
last 8 alarms. In addition, the DCU keeps a calibration log that can be used by the operator to evaluate
the remaining life of the sensor. This log includes the
zero, span, date and time for each successful calibration.
Each device on the LON/SLC contains both the hardware and software necessary to isolate and re-route
communication in the event of a network wiring fault.
When a problem occurs somewhere within the network wiring, the gateway annunciates the fault, while
the fault isolation circuitry in the affected nodes isolates the section of the network where the fault has
occurred. Communication is thereby ensured and will
continue over the network. See Figure 2.
WIRING FAULT
NODE 4
NODE 5
NODE 3
NODE 2
NODE 1
NODE 6
PATH A
PATH B
LCU
NODE 7
NODE 8
A1890
90-1126
RED BY UL AN
D
STE
B
GI
SI
RE
RM
FI
E RE D F
T E ED
R
82
.A
I
R EG
ST
REG
IR M
ISO 9001
230
5 N O.
25
ORDERING INFORMATION
For additional information or for assistance in designing
a system to meet the needs of a specific application,