Sei sulla pagina 1di 26

JACK LOAD ANALYSIS

MIP No.:

8112593

Model:

115 37

Course
Being Lifted

08 Jack System Wind


Velocity

06 Jack System Wind


Velocity

30

30

30

30

30

30

30

28

30

30

24

30

30

22

30

30

20

30

28

20

28

The values listed above indicate the maximum wind velocities (MPH) at which
the designated structure course may be lifted.

CONDITIONS:
> Tank is ground supported.
> Wind speed is determined at 33 feet above the tank floor.
> A jack is positioned at each vertical seam.

Note:

Model 18 Jack System Wind Velocity

This information is proprietary to


CST Storage and shall not be used nor
reproduced without the express written consent of the Company.
All Rights Reserved 2011, CST Storage.

JACK LOAD ANALYSIS


MIP No.:

8112593

Model:

115 37

Course
Being Lifted

08 Jack System Wind


Velocity

06 Jack System Wind


Velocity

30

30

30

30

30

30

30

30

30

30

30

30

28

28

The values listed above indicate the maximum wind velocities (MPH) at which
the designated structure course may be lifted.

CONDITIONS:
> Tank is ground supported.
> Wind speed is determined at 33 feet above the tank floor.
> A jack is positioned at alternate vertical seams.
> A strut is positioned at each vertical seam.

Note:

Model 18 Jack System Wind Velocity

This information is proprietary to


CST Storage and shall not be used nor
reproduced without the express written consent of the Company.
All Rights Reserved 2011, CST Storage.

Project Name:

GUAYAQUIL ECAPAG CIUDAD VICTORIA 10,000M3

Project Location:

GUAYAQUIL, ECUADOR

Dealer: Florida Aquastore Latin America


4722 NW Boca Raton Blvd.; Suite C-102
Boca Raton, Florida, 33431-6358
Phone: (561) 994-2400 Fax: (561) 994-2444
Project Number:

8112593

Submittal Release.No.:

Aquastore Glass Fused to Steel Bolted Storage Tank


115' diameter (nom.) x 37' high (nom.) Model 11537
Short Starter Foundation
Shell panel interior coating:
Vitrium fused glass with Edgecoat process

Shell panel exterior coating:


Fused glass
Shell Exterior Color:

Cobalt Blue

Roof Exterior Color:

N/A

Date: December 16, 2011

EQuote # 8112593 rev. 2


Construction Method: Jack

24 pages.
This document consists of ______
Submitted by:

Date:

12/20/11

Date:

Expires:

Date:

Tank Project Drawing Index


Document Number

Document Title

8112593-001

Tank Drawing

8112593-010

Tank Calculations & Design Formulas

8112593-011

Tank General Notes

8112593-012

Tank Fastener Schedule

8112593-013

Tank Schematic

8112593-014

Tank Parts List

Foundation Project Index


8112593-002

Short Starter Foundation Drawing

8112593-003

Anchor Bolt & Leveling Plate Placement

8112593-020

Foundation Calculations

8112593-021

Foundation General Notes

8112593-022

Foundation Concrete and Gravel Schedule

8112593-023

Foundation Parts List

8112593-024

Foundation Fastener Schedule

8112593-025

Manufacturers Warranty

DOCUMENT NUMBER: 8112593-010

TITLE: TANK CALCULATIONS

PAGE: 1

REL.: 1
DATE: December 16, 2011
BY:

RA

SUMMARY OF TANK DESIGN INPUT DATA


STRUCTURE MODEL

115 37

FOUNDATION TYPE

Short Starter

SPECIFIC GRAVITY

1.000

H/V PRESSURE RATIO

1.000

FREEBOARD

6.000 in

ROOF TYPE

Temcor Aluminium Dome

ROOF WEIGHT

2.300 psf

11.229 kg/m2

SC ROOF HEIGHT

0.000 in

0.000 mm

DC ROOF PROJ AREA

1443.300 sq ft

134.087 sq m

DC ROOF CENTROID

89.100 in

2263.140 mm

TOTAL ROOF HEIGHT

219.372 in

5572.049 mm

ROOF SNOW LOAD

15.000 psf

0.718 kPa

WIND DESIGN

ASCE 7-05/ESPCI*(5.82 psf)*

EXPOSURE FACTOR

IMPORTANCE FACTOR

1.000

WIND SPEED

80.000 mph

WIND STIFFENER ANALYSIS

ASCE 7-05/ESPCI*(5.82 psf)*

SEISMIC DESIGN

AWWA D103 97 (EFFECTIVE MASS)

SEISMIC ZONE

USE FACTOR, I

1.000

SITE AMPLIFICATION FACTOR

1.000

ALLOWABLES USED

ESPCI

152.400 mm

36.000 m/s

SUMMARY OF INTERNALLY ASSIGNED PARAMETERS


BOLT DIAMETER

0.500 in

12.700 mm

HOLE DIAMETER

0.562 in

14.288 mm

TOP COURSE EDGE DIST

1.000 in

25.400 mm

CONCRETE IN FNDN

0.000 in

0.000 mm

DIST T/FTG TO B/FLR

0.000 in

0.000 mm

TOTAL FNDN THICKNESS

0.000 in

0.000 mm

SHEET DENSITY

590.000 pcf

9451 kg/m3

STEEL ELASTIC MODULUS

30000000 psi

206843 MPa

CONCRETE DENSITY

0 pcf

0 kg/m3

NET SHEET WIDTH

105.462 in

2679.000 mm

NET STANDARD SHEET HT.

54.990 in

1397.000 mm

OTHER STANDARD SHEET HT.

44.415 in

1128.000 mm

STARTER PANEL HEIGHT

10.170 in

258.000 mm

INVENTORY USED

wse(1121)

DOCUMENT NUMBER: 8112593-010

TITLE: TANK CALCULATIONS

PAGE: 2

115 37 AQUASTORE STRUCTURE DESIGN SUMMARY (41 FULL LENGTH SHEETS PER RING/COURSE)

COURSE
NUMBER

THICK
In.

THICK mm

GEOM
CODE

MAT
CODE

LIMITING
FACTOR(S)

0.132

3.4

1201

[21, 38]

0.164

4.2

1201

[]

0.197

5.0

1201

[15]

0.228

5.8

1301

[15]

0.293

7.4

1301

[17, 15]

0.322

8.2

1301

[15]

0.354

9.0

1401

[17, 15, 45]

0.438

11.1

1504

[15]

FND

0.5

12.7

5520

[]

WIND STIFFENERS REQUIRED:


NONE

STRUCTURE DIAMETER

114.70 ft

34959.38 mm

HEIGHT OF STRUCTURE TO EAVE

36.71 ft

11189.08 mm

SLOSHING WAVE HEIGHT

1.23 ft

375.83 mm

VOLUME OF STRUCTURE TO EAVE

379286 cu ft

10740 m3

VOLUME OF CONTENTS

374120 cu ft

10594 m3

VOLUME OF CONTENTS

2798612 gal

10593898 L

VOLUME OF CONCRETE FND.

0 cu ft

0 m3

WEIGHT OF EMPTY CYLINDER ABOVE FLOOR

173429 lb

78666 kg

WEIGHT OF ROOF

23764 lb

10779 kg

SNOW (LIVE) LOAD

154981 lb

70298 kg

WEIGHT OF CONTENTS

23345086 lb

10589144 kg

FOUNDATION WEIGHT

0 lb

0 kg

TOTAL WEIGHT ON FOOTING

23697260 lb

10748888 kg

WIND SHEAR AT TOP OF FOOTING

32879 lb

146255 N

WIND MOMENT AT TOP OF FOOTING

819877 ft-lb

1112 kN-m

SEISMIC SHEAR AT TOP OF FOOTING

2293381 lb

10201468 N

SEISMIC MOMENT AT TOP OF FOOTING

33561457 ft-lb

45509 kN-m

DOCUMENT NUMBER: 8112593-010

TITLE: TANK CALCULATIONS

PAGE: 3

---- STRESS-PSI ----

HOOP STRESS ANALYSIS


Course
Number

Depth
(ft)

Press
(PSI)

Net
Tensile

Allowable
Tensile

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

4.2

1.8

12821

31594

19905

67500

6691

30000

8.7

3.8

21671

31594

33644

67500

14051

30000

13.3

5.8

27491

31594

42680

67500

21411

30000

17.9

7.8

28717

31010

41561

67500

24130

30000

22.5

9.7

28063

31010

40614

67500

30303

40000

27.1

11.7

30737

31010

44484

67500

36476

40000

31.7

13.7

31505

31949

35772

67500

32247

40000

35.4

15.3

28391

32743

24583

67500

27418

40000

FND

36.2

15.7

25510

32754

21992

67500

28001

40000

---- STRESS-PSI ----

AXIAL STRESS ANALYSIS


Course
Number

Axial
Compressive

Allowable
Compressive

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

332

381

3334

67500

1121

30000

286

473

2872

67500

1199

30000

257

567

2580

67500

1294

30000

241

655

2417

67500

1404

30000

206

839

2070

67500

1544

40000

206

921

2072

67500

1699

40000

206

1011

2073

67500

1869

40000

182

1246

1828

67500

2039

40000

FND

163

1418

1636

67500

2083

40000

DOCUMENT NUMBER: 8112593-010

TITLE: TANK CALCULATIONS

PAGE: 4

---- STRESS-PSI ----

WIND STRESS ANALYSIS


Course
Number

Axial
Comp

Wind
Bending

Total
Comp

Allowable
Comp

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

60

67

508

673

90000

226

40000

67

76

630

760

90000

317

40000

75

10

85

756

852

90000

427

40000

83

12

95

874

956

90000

555

40000

84

12

96

1119

960

90000

717

53333

95

14

109

1228

1092

90000

895

53333

105

15

121

1348

1211

90000

1092

53333

100

15

115

1661

1152

90000

1285

53333

FND

91

13

104

1891

1049

90000

1335

53333

---- STRESS-PSI ----

SEISMIC STRESS ANALYSIS


Course
Number

Axial
Comp

Seismic
Bending

Total
Comp

Allowable
Comp

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

60

66

508

662

90000

222

40000

67

30

98

630

979

90000

409

40000

75

82

157

756

1577

90000

791

40000

83

165

248

874

2491

90000

1446

40000

84

244

328

1119

3296

90000

2459

53333

95

375

470

1228

4719

90000

3869

53333

105

528

633

1348

6354

90000

5728

53333

100

579

679

1661

6820

90000

7606

53333

FND

91

541

632

1891

6352

90000

8087

53333

DOCUMENT NUMBER: 8112593-010

TITLE: TANK CALCULATIONS

PAGE: 5

SEISMIC STRESS ANALYSIS CONTINUED


---- STRESS-PSI ----

Course
Number

Hydro-Dynamic
Hoop

Total
Hoop

Allowable
Tensile

3776

16597

42125

5921

27592

42125

6936

34427

42125

7398

36115

41347

6603

34666

41347

6561

37298

41347

6278

37783

42599

5165

33556

43658

FND

4531

30042

43672

DOCUMENT NUMBER: 8112593-011

REL:1

TITLE: TANK GENERAL NOTES

PAGE: 1

TANK DESIGN SPECIFICATIONS


This tank is designed in accordance with the ESPCI Specification.
See page 1 of Document 8112593-010 for Summary of Tank Design Input Data.

COATINGS SPECIFICATIONS
Coatings used on components of this tank are in compliance with the appropriate sections of AWWA
Standard D103.

STRUCTURE BOLT SPECIFICATIONS


Structure bolts are carbon steel, zinc mechanically deposited per the latest revision of ASTM B695,
class 50,type 1;with 1/2"-13 UNC-2A thread, and conform to AWWA D103,Section 2.2.1, as noted below.
A. 1 inch long and 1-1/4 inch long bolts conform to the mechanical properties of SAEJ429, Grade 5
- equivalent to the mechanical properties of ASTM A325.
B. 1-1/2 inch long and longer bolts conform to the mechanical properties of SAEJ429, Grade 8
- equivalent to the mechanical properties of ASTM A490.
Unless noted, all tank structure connections are bearing type connections, snug-tight condition, per
ANSI/AISC 360-05. Tank manufacturer does not require special inspection per IBC, Section 1704.

APPURTENANCE AND PIPING ORIENTATION


Orientation of all appurtenances and piping connections shall be established in the field.

THROUGH-THE-SHEET PENETRATIONS
All openings through the tank side wall greater than 4 inches (102mm) in diameter shall be reinforced in
accordance with AWWA D103, Section 3.11. All openings through sheets having less than 24 inches (610
mm) between horizontal bolt lines, or having less than 24 inches (610 mm) of available sheet space from
the floor surface up to the first horizontal bolt line shall not exceed a diameter of 4 inches (102 mm).
These openings of 4 inches (102 mm) and less shall be reinforced in accordance with AWWA D103,
Section 3.11.

LADDER SPECIFICATIONS
The ladder system is manufactured in compliance with AWWA Standard D103 Section 5.4. In addition,
the tank ladder side rails are fabricated from 6061-T6 aluminum while the ladder rungs are fabricated
from 6061-T4 aluminum.

DOCUMENT NUMBER: 8112593-011

REL:1

TITLE: TANK GENERAL NOTES

PAGE: 2

CATHODIC PROTECTION SPECIFICATIONS


This tank is equipped with a cathodic protection system conforming to NACE RP0196-2004. This system
is designed to protect the items described below.
Entire submerged portion of tank sidewall and floor area including appurtenances supplied by the tank
manufacturer. Submerged uncoated metal objects not supplied by the tank manufacturer totaling: 0 sq. ft.
Submerged coated metal objects not supplied by the tank manufacturer totaling: 0 sq. ft.
This system is suitable for use in liquid having a resistivity of 4000 - 5000 ohm-centimeters.
Field verification of liquid resistivity is required after the tank is placed into service.
The performance of the cathodic protection system may be adversely affected if the system is operated
outside the resistivity range above.
The presence of submerged uncoated metallic items, for which cathodic protection has not been provided
by the tank supplier, may also adversely affect the performance of the cathodic protection system.
Electrical isolation and/or the determination of the cathodic protection requirements for such submerged
items shall be the responsibility of the owner or the owner's designated agent.
Tank warranty issues may also be affected.
For further information, refer to the instructions provided with the cathodic protection system.

10

DOCUMENT NUMBER: 8112593-012

REL:1

TITLE: TANK FASTENER SCHEDULE

PAGE: 1

Structure bolt quantities at (H)orizontal and (V)ertical seams


Thru the sheet fasteners

BOLT LENGTHS:

1"
25.40

SEAM Wide H 1
SEAM

V 1

1 1/4"

1 1/2"

1 3/4"

31.75

38.10

44.45

Truss Fasteners

2"
50.80

2 1/4"

2 1/2"

57.15

63.50

1 1/4"
31.75

2 1/4"

3"

3 1/2"

57.17

76.20

C.S.

C.S.

C.S.

88.90
C.S.

612

126

492

2009

SEAM Wide H 2

902

SEAM

2091

V 2

SEAM Wide H 3

820

82

SEAM

2091

V 3

SEAM Wide H 4

816

86

SEAM

2419

SEAM Wide H 5

818

82

SEAM

2419

SEAM Wide H 6

818

84

SEAM

2419

SEAM Wide H 7

779

123

SEAM

3239

SEAM Wide H 8

779

123

SEAM

3403

SEAM Fnd. H 9

777

123

ACCESS DOOR

V 4

V 5

V 6

V 7

V 8

REINF. PLT.
Total:

2009

10569

6731

8856

248

123

11

DOCUMENT NUMBER: 8112593-013

REL:1

TITLE: TANK SCHEMATIC

PAGE: 1

Note: All brackets located at top of specified ring.


Ring are identified from top of tank to foundation
Ring #

Sheet
Thick.

Bracket Type

Bracket
Quantity

Vertical Bolt
Line

Shell Sheet Part


No.

Use tapered spacer at top horizontal seam


RING # : 1

0.132'' (3.4mm)

BRKT

2V

260690-1200

RING # : 2

0.164'' (4.2mm)

BRKT

2V

256050-0500

RING # : 3

0.197'' (5.0mm)

NONE

2V

256050-1300

RING # : 4

0.228'' (5.8mm)

BRKT

3V

261016-1400

Use 41 tapered insert(s) at this horizontal seam


RING # : 5

0.293'' (7.4mm)

BRKT

3V

261016-1500

RING # : 6

0.322'' (8.2mm)

BRKT

3V

261016-1600

RING # : 7

0.354'' (9.0mm)

NONE

4V

262120-1700

BRKT

5V

268529-2600

BRKT

5V

See fnd. parts list

Use 41 tapered insert(s) at this horizontal seam


RING # :8 (44 inch)

0.438'' (11.1mm)

Use 41 tapered insert(s) at this horizontal seam


FND. :

0.5'' (12.7mm)

12

DOCUMENT NUMBER: 8112593-014


Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

Quantity

REL:1

TITLE: TANK PARTS LIST

Part No.

Description

1
1

8112593-001
8112593-002

TANK ASSEMBLY
FOUNDATION ASSEMBLY

85

265777-203

SEALER 98, CARTONS (BLACK)

1
1
1

264082-000
258446-001
264769-000

SHORT LADDER ASSEMBLY


LADDER W/CAGE, W/PLATFORM
LADDER DOOR ASSEMBLY

1
1

277650-000
271272-1300

GASKET, 24"
REINFORCING PLATE, .197"

41
41
41
123

261256-115
260577-005
084373-000
084374-000

STIFFENER ANGLE
SPLICE ANGLE
TAPERED SPACER
TAPERED INSERT

2009
10569
6731
8856
248
123

262000-001
262000-002
262000-003
262000-004
262000-006
262000-007

STRUCTURE BOLT, 1"


STRUCTURE BOLT, 1 1/4"
STRUCTURE BOLT, 1 1/2"
STRUCTURE BOLT, 1 3/4"
STRUCTURE BOLT, 2"
STRUCTURE BOLT, 2 1/4"

28536
28536

252275-000
262416-001

WASHER, 1/2"
HEX. NUT, 1/2" HDZ

PAGE: 1

13

DOCUMENT NUMBER: 8112593-014


Item
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118

Quantity

REL:1

TITLE: TANK PARTS LIST

Part No.

Description

28536
8
1

081816-000
264913-000
276534-000

PROTECTIVE COVER
BUSS BAR
AQUASTORE CP LIT. PACK

13

266680-000

CATHODIC PROT. SYSTEM - MAG.

2
1
1
1
3
3

262778-002
257249-002
266182-000
271220-002
262166-002
260581-002

DANGER DECAL
INFORMATION SIGN
NAMEPLATE
OPERATORS MANUAL
IMPORTANT DECAL
TANK MOD. WARNING DECAL

268364-000

LADDER BRACKET ASSY. (LONG)

1
1
40
1

260813-1204
271273-2650
260690-1200
271268-120

AQUASTORE TRADENAME SHEET


24" ROUND ACCESS DOOR SHEET
TOP RING SHEET
24" ACCESS DOOR

41
41
41

256050-0500
256050-1300
261016-1400

SHELL SHEET 0.164" HSLA


SHELL SHEET 0.197" HSLA
SHELL SHEET 0.228" HSLA

41
41
41

261016-1500
261016-1600
262120-1700

SHELL SHEET 0.293" HSLA


SHELL SHEET 0.322" HSLA
SHELL SHEET 0.354" HSLA

40

268529-2600

SHELL SHEET 0.438" HSLA

PAGE: 2

14

TANK DESIGNATION:
INPUT:

8112593 Rel 1

Tank Diameter (ft):


Contents Height (ft):
Slab Thickness (in):
Slab O.D. (ft):
Foundation Depth (in):
Footer Depth (in):
Footer Width (in):
Allowable soil pressure (psf)
Wind Shear (lbs):
Wind Moment (ft-lb):
Seismic Shear (lbs):
Seismic Moment (ft-lb):
Sloshing Wave Height (ft):
Weight of Tank (lbs):
Weight of Roof (lbs):
Snow Load (psf):

114.70
36.21
7
117.25
12
15
27
3,000
32879
819,877
2293381
33,561,457
1.23
173,429
23,764
15

Engineer: TSM

12/19/2011

Design per:
Tank Type:
Embedded sheet thickness (in):
Embedment depth (in):

ACI 318-05
Embedded
0.5
6.75

Self or Center Supported Roof :


Specific Gravity of Contents:
Subgrade Modulus - ks (pci):
Coeff. Active pressure - Ka:
Concrete strength - f'c
(psi):
(ksi):
Yield strength of steel - fy

Self
1.00
83
0.3
3,000
60

17

TANK DESIGNATION:
RESULTS:

8112593 Rel 1

Engineer: TSM

Soil Pressure:
dead plus live load:
dead plus live plus wind load:
dead plus live plus seismic load:
dead minus wind load:
dead plus live minus seismic load:

2663 psf
2692 psf
3930 psf
385 psf
1193 psf

<=
<=

<=

3000 psf (Allowable)


4000 psf (4/3 * Allowable)
4000 psf (4/3 * Allowable)
No Uplift
No Uplift

Shear stress at inside of footer =

68 psi

<=

82 psi

Shear Strength

F.S .Overturning - Seismic w/ 45 line:


F.S. Overturning - Seismic (AWWA):
F.S. Overturning - Wind:

3.41
2.26
89.30

>=
>=
>=

1
1
1.5

Required
Required
Required

As - foundation (both ways)


layer at mid-height:

0.56

sq.in./ft

[# 7 @ 12'' o.c.]

As - curb area:
As - footer bottom layer:
As - hoop steel:

3.38
1.98
1.45

sq.in.

[2 - # 11]

sq.in.

[3 - # 8]

sq.in.

[2 - # 8]

As - vertical tie bars ( 2 legs):


As - suppl. tie bars:

0.27
0.17

sq.in./ft
sq.in./ft

[# 4 @ 17.5'' o.c.]
[# 5 @ 17.5'' o.c.]

12/19/2011

18

DOCUMENT NUMBER: 8112593-021

REL:1

TITLE: FND. GENERAL NOTES

PAGE: 1

Minimum guidelines and specifications are given below. The owner or the owner's designated agent
may amend or modify these guidelines and specifications, but in no case shall the requirements be
less than those given below
FOUNDATION DESIGN
See Tank Foundation Design Input Data Sheet for foundation design data.
SITEWORK
1. Clear the site of all vegetation, organic materials, rubbish, debris, and other foreign or
objectionable materials above the ground surface. Remove all stumps, large roots, buried
logs, and other objectionable materials below the ground surface.
2. Soil beneath the entire tank shall have a minimum bearing capacity of 3000 PSF (143641
Pa) and shall be suitable in all respects to properly support the tank as determined by a
qualified professional retained by the owner or the owner's designated agent.
3. Compact the subsoil to site specifications.
4. Orientation of connecting piping shall be established in the field.
5. Place all underground piping. Backfill and compact to site specifications. Inlet/outlet piping
may penetrate ring walls provided the hole size is less than or equal to one half the wall
height; all details of reinforcement cushioning needs, thrust blocks, and encasement shall
be provided by others. Otherwise, all piping must pass beneath the footing unless the
footing/foundation system has been designed and fully detailed by others to accommodate
both a pipe passing through it and the proper transfer of tank loads to the supporting soil.
6. If conditions exist which require footing and/or floor design details differing from those
shown on the drawings herein, such new design and details shall be provided by the
owner or the owner's designated agent. CST Storage can not
show details on its drawings other than those derived as a result of the design efforts of its
own Engineering Department.

19

DOCUMENT NUMBER: 8112593-021

REL:1

TITLE: FND. GENERAL NOTES

PAGE: 2

CONCRETE WORK
Concrete work shall conform to the requirements of ACI 301-05, published by the American Concrete
Institute, Farmington Hills, Michigan, except as modified by the supplemental requirements noted
below.
1. Concrete shall attain an ultimate 28 day compressive strength of 3000 PSI ( 20684 KPa).
2. Reinforcing bars shall conform to ASTM A615, grade 60. Welding of bars is not permitted.
Field bending of partially embedded reinforcing bars shall conform to Section 3.3.2.8.
3. Cement shall conform to ASTM C150, Type I or Type II with air entraining admixture per
ASTM C260 added at the mixer to achieve 4-6% by volume of entrained air at the point of
concrete placement.
4. Maximum aggregate size shall be 1 1/2" (38 mm). Fine and coarse aggregate shall
conform to ASTM C33, and the restrictions on reactive materials specified in ASTM C33,
paragraphs 7.3 and 11.2, shall apply.
5. Ready mixed concrete shall conform to ASTM C94, Option A. The supplier shall be
responsible for determining the proportions used in the concrete mix.
6. Earth cuts may be used as formwork for footings only, provided the footing depth does not
exceed 48" (1219 mm).
7. Finished surfaces
A. Rough form finish is acceptable for vertical surfaces.
B. Floated finish is required for the floor surface.
8. The following sections of ACI 301-05 do not apply:
6 - Architectural Concrete
7 - Lightweight Concrete
8 - Mass Concrete
9 - Prestressed Concrete
10 - Shrinkage-compensating Concrete

20

DOCUMENT NUMBER: 8112593-022

REL:1

TITLE: Foundation Concrete and Gravel Sched.

PAGE: 1

These materials are to be furnished by the builder. Quantities are estimated.

CONCRETE AND GRAVEL REQUIREMENTS:


CONCRETE IN FLOOR:Per 7'' depth (177.8 mm)

248.1 cu. yds

189.7 m3

2.5 cu. yds

1.9 m3

CONCRETE IN FOOTING:Per 1'' depth (25.4 mm)

21

DOCUMENT NUMBER: 8112593-023


Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49

Quantity

REL:1

TITLE: FND. PARTS LIST

Part No.

Description

1
41
41
41
82

8112593-002
268552-2700
257573-115
273882-001
261067-004

SS FOUNDATION ASSEMBLY
0.5" FND. SHT. HSLA
FOUNDATION ANGLE
SPLICE ANGLE
TAPERED SPACER

164
328
328
82

013713-003
013542-005
013543-006
257516-000

FOUNDATION BOLT, 3/4"


WASHER,STD., 3/4"
HEX. NUT, 3/4"
LEVELING PLATE

82

019030-000

ANCHOR ROD, 1/2"

42
18

252488-000
265777-203

SEAL STRIP
SEALER 98, CARTONS (BLACK)

22

266030-000

BENTONITE SEAL STRIP

253730-002

SEALER PRIMER

861

081816-000

PROTECTIVE COVER

82

017500-086

CAP SCREW 1/2" X 1 3/4"

615
1353
123
2337
2419

262000-003
262000-004
262000-006
262416-001
252275-000

STRUCTURE BOLT 1 1/2"


STRUCTURE BOLT 1 3/4"
STRUCTURE BOLT 2"
HEX NUT, 1/2" HDZ
WASHER, 1/2"

PAGE: 1

22

DOCUMENT NUMBER: 8112593-024

REL:1

TITLE: FND. FASTENER SCHEDULE

1 1/4"

1 1/2"

1 3/4"

25.40

31.75

38.10

44.45

50.80

ANCHOR
RODS

VERTICAL

1189

82

HORIZONTAL

615

164

123

BOLT LENGTHS:

1"

2"

PAGE: 1

23

24

345 Harvestore Drive


DeKalb, Illinois 60115-9607 U.S.A.
815-756-1551 Phone, 815-756-7821 Fax

LIMITED WARRANTY

MANUFACTURERS

IN NO EVENT SHALL CST STORAGE BE LIABLE (WHETHER


FOR BREACH OF WARRANTY OR CONTRACT, FOR STRICT
LIABILITY OR NEGLIGENCE, OR OTHERWISE) FOR ANY
SPECIAL, INCIDENTAL, PUNITIVE OR CONSEQUENTIAL
DAMAGES, INCLUDING, BUT NOT LIMITED TO, DAMAGES
FOR LOSS OF CONTENTS OR LOSS OF PROFITS, OR FOR
THE CONDITION OR QUALITY OF LIQUID STORED IN THE
TANK, OR FOR ANY INABILITY OF OWNER TO PROVIDE
PRODUCT OR SERVICE TO ANY CUSTOMER OF OWNER.

In the event of any failure of any Aquastore brand liquid storage


tank to perform as warranted in the Limited Warranty, the sole and
exclusive obligation of CST Storage shall be, at its sole option,
either to repair the tank or repair or replace (FOB factory) any part
of the tank which is defective.

Limitation of Remedies

d. The CST Storage Limited Warranty shall become void and


terminate if the tank is not used, operated and maintained in
accordance with the requirements stated in the CST Storage
Operating Manual(s) supplied with the tank, or if the tank is
damaged or subject to any abuse, misuse or vandalism.

c. The CST Storage Limited Warranty shall become void and


terminate if any alterations are made to the tank without the prior
written approval of CST Storage.

b. The CST Storage Limited Warranty


does not cover damage caused by
shipping, handling or tank erection, or
damage caused by operating or maintenance
activities. CST Storage makes no warranty about and
shall not be responsible for any defects in erection or installation of
a tank.

a. The CST Storage Limited Warranty


shall remain in effect only as long as
the tank is used for the storage of
municipal potable water or
municipal sewage waste water.
T h e C S T St o r a g e L i m i t e d
Warranties shall become void and
terminate should the tank be used
for storage of any other liquid.

The CST Storage Limited Warranty is subject to


the following limitations and conditions:

Limitations and Conditions

CST Storage warrants that an Aquastore brand liquid storage


tank will be free from defects in workmanship and materials, under
normal and proper use, maintenance and operation, during the
period expiring on the earlier of (i) five years after liquid is first
introduced into the tank or (ii) 62 months after shipment from the
factory, if the tank is purchased with an Aquastore brand cathodic
protection system.

Five-Year Warranty

Aquastore is the registered trademark of CST Storage


Copyright 2011 CST Storage Printed in U.S.A.
CST P/N 267233-000 Rel. 3 ECN 11005

This Limited Warranty and related limitations and disclaimers


cannot be modified or amended by a CST Storage Authorized
Dealer, and can be modified or amended only by written document
signed by an authorized CST Storage employee.

The CST Storage Authorized Dealers are independent contractors


and are not agents or employees of CST Storage. No statement
by any CST Storage Authorized Dealer or any CST Storage
employee shall constitute an understanding, agreement,
representation or warranty by CST Storage. CST Storage makes
no warranty with respect to goods manufactured by others, even if
sold by a CST Storage Authorized Dealer.

EXCEPT FOR THE LIMITED WARRANTY SET FORTH ABOVE,


T H E R E A R E N O U N D E R S TA N D I N G S , A G R E E M E N T S ,
REPRESENTATIONS OR WARRANTIES, EITHER EXPRESS OR
IMPLIED, RESPECTING THE AQUASTORE BRAND LIQUID
STORAGE TANK CST STORAGE EXPRESSLY DISCLAIMS THE
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE.

Disclaimers

Any Warranty claim shall be made to CST Storage in writing. Once


a claim has been made, CST Storage shall have the right to
perform on-site inspections of the tank. If CST Storage chooses to
do repair work (which, for purposes of this paragraph, shall include
repairing or replacing defective parts) on the tank, CST Storage
shall be granted permission to perform such work with
its own service personnel or personnel of
others, and under nonunion conditions
unless CST Storage otherwise agrees.
Any repairs made to a tank before
CST Storage is notified of a claim
shall be at the Owner's expense.
Preparation for inspection or
repair of a tank (such as
removing the contents and
obstructive equipment in the tank)
shall be the sole responsibility and
expense of Owner. Preparation of
the tank for use after repair shall be
the sole responsibility and expense of
the Owner.

Any action against CST Storage for breach of warranty or contract ,


or for strict liability, negligence or otherwise relating to a tank, must
be commenced within one year after such cause of action accrues.

Potrebbero piacerti anche