BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 1 of 13

PT. Perusahaan Gas Negara (Persero) Tbk.

EPC OTSUKA -PURWOSARI GAS DISTRIBUTION PIPELINE PROJECT CP-19

BLOWDOWN ANALISYS REPORT


Contract No.
079800.PK/HK.02/PROYEK/2014

Issued for review

14-10-14

ARD

ILM

DVD

Issued for review

12-09-14

ARD

ILM

DVD

REV

DESCRIPTION

DATE

PRPD CHKD APVD


PT. BRE

PMC

PGN

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT.BINARASANO ENGINEERING

PT. CONNUSA ENERGINDO

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 2 of 13

REVISION CONTROL SHEET

Rev No

Date

Page

Description

12-09-14

All

Issued for review

14-10-14

All

Issued for review

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 3 of 13

TABLE OF CONTENT

REVISION CONTROL SHEET ______________________________________________________ 2


1.

INTRODUCTION _____________________________________________________________ 4
1.1.
General ______________________________________________________________ 4
1.2.
Objection _____________________________________________________________ 4

2.

REFERENCES ______________________________________________________________ 4

3.

DATA SOURCE______________________________________________________________ 5
3.1.
Process Data __________________________________________________________ 5
3.2.
Blowdown Design_______________________________________________________ 6

4.

CALCULATION METHODS _____________________________________________________ 7


4.1.
Upstream Restriction Orifice Calculation _____________________________________ 7
4.2.
Downstream Restriction Orifice Calculation ___________________________________ 9

5.

RESULT __________________________________________________________________ 10

6.

CONCLUSION______________________________________________________________ 11

Figure 1. Blowdown scheme _________________________________________________________ 6


Figure 2. Hysys Depressuring Utilities _________________________________________________ 7
ATTACHEMENT 1 : HYSYS SIMULATION REPORT ____________________________________ 12
ATTACHEMENT 2 : LINE SIZING CALCULATION ______________________________________ 13

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 4 of 13

1. INTRODUCTION
1.1. General
Perusahaan Gas Negara (persero) Tbk. (PGN) is the largest natural gas transmission and
distribution company intens to distribute gas from Otsuka to Purwosari with distance about 15
km. Sectional Valve will be installed at KP 8. The Sectional Valve is composed of a manually
operated 10 Block Valve for Otsuka Purwosari Pipeline and a vent nozzle with connections
for temporary blowdown facility. The blowdown facilities optimized for 3 5 hours of blowdown
duration. For normal condition, 5 MMSCFD of gas will deliver to consummer and it will be
increase to 17 MMSCFD as future. 48 km gas pipeline distribution to Malang shall install as a
future plan
1.2. Objection
This document is provided for size calculation from upstream and downstream of restriction
orifice on the OTSUKA PURWOSARI GAS DISTRIBUTION PIPELINE, East Java. Optimum
Restriction orifice will be determined too for 8 km lenght of pipe.

2. REFERENCES
API RP 521

Guide for Pressure Relieving Depressuring System

API 14E

Recommended Practice for Design and Installation of Offshore


Production Platform Piping Systems

API RP 520

Sizing, Selection, and Installation of Pressure-Relieving Devices in


Reneries

GPSA Section 17

Fluid Flow and Piping

Kepmen LH No.48/1996 Baku Tingkat Kebisingan


Permen Naker
No. PER.13/MEN/X/2011 Nilai Ambang Batas Faktor Fisika dan Faktor Kimia di Tempat Kerja

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT.BINARASANO ENGINEERING

PT. CONNUSA ENERGINDO

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 5 of 13

3. DATA SOURCE
3.1. Process Data
The parameters will be use for calculating hydraulic are showed below:
No

Parameters

Unit

Value

Flow Rate (Q)

MMSCFD

Future Flowrate (Qfuture)

MMSCFD

17

Operating Pressure (P)

barg

16

Max Allowable Operating Pressure (MAOP)

barg

25

Design Pressure

barg

35.9

Operating Temperature (T)

80

Design Temperature

130

Inside Pipe Diameter (D)

inch

10

Pipe Lenght (L)

km

15

10

Spesific Gravity (Sg)

11

Compresibilty Factor (Z)

0.565
0.9634
lb/ft

12

Density ()

1.128

13

Molecular Weight (Mw)

14

Viscosity ()

cP

0.01182

15

Roughness

in

0.001

16.36

Table 1. Standard Parameters

Gas composition is refer to Heat & Material Balances Table (CP19-BRE -3514-PS-BD-004)
COMPOSITION

Mole

CH4 (Methane)

0.9844

CcH6 (Ethane)

0.0050

C3H8 (Propane)

0.0020

i-C4H10 (i-Butane)

0.0006

n-C4H10 (n-Butane)

0.0004

i-C5H12 (i-Pentane)

0.0002

n-C5H12 (n-Pentane)

0.0001

n-C6H14 (n-Hexane)

0.0001

H2S

0.0000

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT.BINARASANO ENGINEERING

PT. CONNUSA ENERGINDO

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 6 of 13

COMPOSITION

Mole

CO2

0.0027

N2

0.0046
TOTAL

1.0000

Table 2. Gas Composition


3.2. Blowdown Design
Blowdown designed for one section ( Section 1 or section 2 ) with assumed lenght 8 km /
section. The calculation performed to 3, 4 and 5 hours duration at maximum operating
pressure (25 barg) for future connection (17 MMSCFD). Final pressure target is 100 psig.
Case

Blowdown Duration

Flowrate

Pressure

3 hours

17 MMSCFD

25 barg

4 hours

17 MMSCFD

25 barg

5 hours

17 MMSCFD

25 barg

Table 3. Blowdown Case

Blowdown Area

SECTION 2

SECTION 1

Figure 1. Blowdown Scheme


Upstream Pipe of Restriction Orifice Design Criteria
a. Maximum Velocity

= 60 ft/s refer to API RP 521

b. P (psi/100ft)

= 0.486 psi/100ft

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 7 of 13

Downstream Restriction Orifice Design Criteria


a. Beta ratio

= 0.2 0.75

b. Maximum Velocity

= 500 fps refer to API 14E

c. Noise

= 55 dB refer to Kepmen LH No.48/1996


85 dB refer to Permen Naker No. PER.13/MEN/X/2011

4. CALCULATION METHODS
This calculation is performed using HYSYS simulation and MS Excel by input data. Methodology
being used for calculation below :
4.1. Upstream Restriction Orifice Calculation
a. Depressurization simulation using HYSYS
Depressurization simulation performed using HYSYS 7.3 with Peng-Robbinson as fluid
package. The stage are belowed:
1. Gas composition and parameters condition input to stream data.
2. Assumed the vessel orientation is horizontal. Pipe lenght and diameter input to vessel
parameters as a diameter and height. The figure showed below.

Figure 2. Hysys Depresssuring Utilities

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 8 of 13

3. Input the ambient data into heat flux and chose adiabatic for operating mode.
4. For valve parameters chose a supersonic in vapour flow equation and assumed discharge
co-efficient is 0.975.
5. Set depressuring time and final pressure at Operating Condition.
6. run the simulation.

b. Determine friction factor (MS. EXCEL) refer to API 14E


-

Trial diameter (D) using gas velocity Equation (API 14E )

v
-

Calculate Reynold number (Re)


R

c. Determine the value of (/D) and Re from the picture below to get (fm)

d. Determine Pressure Drop using Darcy formula

Where:
vg

: Gas Velocity (fps)

: Gas Compresibility

: Molar flowrate (MMSCFD)

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

: Temperature inlet (oR)

: Pressure inlet ( psia )

: Diameter blowdown pipe (in)

: Density (lb/ft3)

: Viscosity (cP)

: Mass Flowrate (lb/hr)

fm

: Frition factor

Date
14/10/2014

Page 9 of 13

4.2. Downstream Restriction Orifice Calculation


a. Orifice Diameter Calculation refer to GPSA section 17
- FTP initial value set = 1
- Determining critical flow ( YCR) by :

- Determining orifice diameter (d) :

b. Estimation noise by Lighthill's Theory :

Where:
OASPL

Overall sound pressure level of regenerated noise (dB)

Inside diameter of vent stack (m)

C0

Sonic Velocity (Velocity of sound in atmosphere) (m/s)

vg

Exit velocity of vented gas (m/s)

Density of atmosphere (kg/m3)

Density of vented gas (kg/m3)

Distance from vent (m)

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT.BINARASANO ENGINEERING

PT. CONNUSA ENERGINDO

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 10 of 13

5. RESULT

The result of calculations are below :


a. Case 1: 3 Hours Blowdown Duration
DOWNSTREAM
Option

ID (in)

Velocity (fps)

UPSTREAM
Mach Number

P (psi/100ft)

Noise 1

Noise 2

Status

Option 1

71.818

1.265

6.213

110.272

88.933

NOT OK

Option 2

31.919

0.562

0.769

85.619

64.280

NOT OK

Option 3

17.954

0.316

0.176

68.128

46.789

OK

Option 4

7.980

0.141

0.022

43.475

22.136

OK

Table 4. Blowdown Case 1 Result

b. Case 2 : 4 Hours Blowdown Duration


DOWNSTREAM
Option

ID (in)

Velocity (fps)

UPSTREAM
Mach Number

P (psi/100ft)

Noise 1

Noise 2

Status

Option 1

54.391

0.958

3.565

100.625

79.286

NOT OK

Option 2

24.174

0.426

0.441

75.972

54.633

OK

Option 3

13.598

0.240

0.101

58.480

37.141

OK

Option 4

6.043

0.106

0.013

33.828

12.489

OK

Table 5. Blowdown Case 2 Result

c. Case 3 : 5 Hours Blowdown Duration


DOWNSTREAM
Option

ID (in)

Velocity (fps)

UPSTREAM
Mach Number

P (psi/100ft)

Noise 1

Noise 2

Status

Option 1

43.557

0.767

2.285

92.895

71.556

NOT OK

Option 2

19.359

0.341

0.277

68.242

46.904

OK

Option 3

10.889

0.192

0.066

50.751

29.412

OK

Option 4

4.840

0.085

0.008

26.098

4.759

OK

Table 6. Blowdown Case 3 Result

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT.BINARASANO ENGINEERING

PT. CONNUSA ENERGINDO

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 11 of 13

d. Restriction Orifice Calculation Result


No

Calculation steps

3 Hours

4 Hours

5 Hours

Relief Load (W) (kg/h)

2885

2185

1749

Set Initial Value of FTP

Critical Flow Function, YCR

0.701

0.701

0.701

Orifice Diameter, d (mm)

27.17

23.65

21.16

Beta Ratio,

0.267

0.233

0.208

FTP Calculated

1.0012

1.0007

1.0004

Critical Pressure, (kPa)

Reynold Number

Flow Region

10

Flow Behaviour

420.81

420.60

420.50

63442.49

48047.83

38477.69

Turbulent - OK

Turbulent - OK

Turbulent - OK

Critical Flow

Critical Flow

Critical Flow

Table 7. RO calculation result

6. CONCLUSION
a. Based on calculation, the selected downstream diameters thats suitable of criteria is 4 inch
with 0.176 psi/100ft as maximum pressure drop , 0.316 as mach number and maximum gas
velocity calculated is 17.954 fps.
b. For upstream, diameter selected is 4 inch with maximum noise is 68.128 dB.
c. For diameter 4 inch, RO diameter caclulated is 27.17 mm at 3 hours with beta ratio value is
0.267.

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

Page 12 of 13

ATTACHEMENT 1 : HYSYS SIMULATION REPORT

1
2

LEGENDS
Burlington, MA
USA

3
4
5

Case Name:

BLOW DOWN 3 HOURS 8KM .HSC

Unit Set:

NewUser4a113

Date/Time:

Sun Sep 14 09:44:31 2014

Depressuring - Dynamics: BD 1

7
8
9

DESIGN

10
11

Connections

12
13

Inlet

14

Vessel Volume

(ft3)

1.431e+004

FEED-2

15

Liquid Volume

(ft3)

7156

16
17

Vessel Orientation

18

Flat End Vessel Volume

Horizontal

19

Height

(m)

8000 *

20

Diameter

(m)

0.2540 *

21

Metal Mass in Contact with Vapour

(lb)

(ft3)

1.431e+004

---

22

(ft3)

0.0000

Cylindrical Area

(ft2)

6.870e+004

Top Head Area

(ft2)

0.5453

Bottom Head Area

(ft2)

0.5453

(lb)

---

(ft2)

6.870e+004

Metal Mass in Contact with Liquid

Heat Flux

23
24

Initial Liquid Volume

Operating Mode :

Adiabatic

25
26

Heat Loss Model : Simple

27

Overall U

28

Ambient Temperature

(Btu/hr-ft2-F)

2.642

(F)

29

Valve Parameters

30
31

Vapour Flow Equation

32

Cd

33

Area

34

Vapour Back Pressure

35

Valve Equation Units

Supersonic

Liquid Flow Equation

(No Flow)

0.9750 *
(in2)

0.1933 *

(bar_g)

0.0000

Liquid Back Pressure

(bar_g)

0.0000

lb/hr

36

Options

37
38

Overall Heat Transfer Area

82.00 *

PV Work Term Contribution

(%)

39

80.00 *

Operating Conditions

40
41

Operating Pressure

42

Time Step Size

(bar_g)

43

Vapour Outlet Solving Option

44

Initial Cv Estimate

25.00

Depressuring Time

(seconds)

1.080e+004 *

Final Pressure

(bar_g)

6.895 *

Solved Pressure

(bar_g)

--Calculate Cv
0.9750 *

45

---

WORKSHEET

46
47

Properties

48
49

Name

50

Vapour Fraction

51

Temperature

52

Pressure

53

Actual Vol. Flow

54

Mass Enthalpy

55

Mass Entropy

56

Molecular W eight

57

FEED-2
1.0000
(F)
(bar_g)

80.00 *
25.00 *

(barrel/day)

1.157e+005

(Btu/lb)

-1997

(Btu/lb-F)

2.281

Molar Density

(lbmole/ft3)

6.894e-002

58

Mass Density

(lb/ft3)

1.128

59

Std Ideal Liq Mass Density

(lb/ft3)

18.99

60

Liq Mass Density @Std Cond

(lb/ft3)

4.332e-002

61

Molar Heat Capacity

(Btu/lbmole-F)

9.324

62

Mass Heat Capacity

(Btu/lb-F)

0.5698

63

Thermal Conductivity

(Btu/hr-ft-F)

2.073e-002

64

Viscosity

(cP)

1.182e-002

65

Surface Tension

66

Specific Heat

67

Z Factor

68

Vap. Frac. (molar basis)

69

Aspen Technology Inc.


Licensed to: LEGENDS

16.36

(dyne/cm)

---

(Btu/lbmole-F)

9.324
0.9450
1.0000

Aspen HYSYS Version 7.3 (25.0.0.7336)

Page 1 of 2
* Specified by user.

1
2

LEGENDS
Burlington, MA
USA

3
4
5

Case Name:

BLOW DOWN 3 HOURS 8KM .HSC

Unit Set:

NewUser4a113

Date/Time:

Sun Sep 14 09:44:31 2014

Depressuring - Dynamics: BD 1 (continued)

7
8
9

Properties

10
11

Vap. Frac. (mass basis)

12

Vap. Frac. (Volume Basis)

1.0000

13

Molar Volume

(ft3/lbmole)

14.51

14

Act.Gas Flow

(ACFM)

451.3

15

Act.Liq.Flow

16

1.0000

(USGPM)

---

Std.Liq.Vol.Flow

(barrel/day)

3.014e+006

17

Std.Gas Flow

(MMSCFD)

16.97

18

Watson K

19

Kinematic Viscosity

(cSt)

0.6543

20

Cp/Cv

21

Lower Heating Value

(Btu/lbmole)

3.463e+005

22

Mass Lower Heating Value

(Btu/lb)

2.116e+004

23

Liquid Fraction

24

Partial Pressure of CO2

(bar_g)

-0.9439

25

Avg.Liq.Density

(lbmole/ft3)

1.161

26

Heat Of Vap.

27

Mass Heat Of Vap.

19.27
1.381

0.0000

(Btu/lbmole)

3033

(Btu/lb)

185.3

28

COMPOSITIONS

29

FEED-2

30
31

Methane

0.9844 *

32

Ethane

0.0050 *

33

Propane

0.0020 *

34

i-Butane

0.0006 *

35

n-Butane

0.0004 *

36

i-Pentane

0.0002 *

37

n-Pentane

0.0001 *

38

n-Hexane

0.0001 *

39

H2S

0.0000 *

40

CO2

0.0027 *

41

Nitrogen

0.0046 *

42

Results

43
44

Initial Pressure

(bar_g)

25.00

Vessel Fluid Final Temperature - Liquid Phase

(F)

79.19

45

Final Pressure

(bar_g)

6.896

Vessel Fluid Minimum Temperature - Liquid Phase

(F)

79.19

46

Depressuring Time

1.080e+004 *

Valve Outlet Initial Temperature - Liquid Phase

(F)

57.19

47

Vapour Cv

0.9750 *

Valve Outlet Final Temperature - Liquid Phase

(F)

57.65

48

Liquid Cv

Valve Outlet Minimum Temperature - Liquid Phase

(F)

57.19

49

Vessel Fluid Initial Temperature - Vapour Phase

(F)

80.42

Inner W all Initial Temperature - Liquid Phase

(F)

---

50

Vesssel Fluid Final Temperature - Vapour Phase

(F)

79.19

Inner W all Final Temperature - Liquid Phase

(F)

---

51

Vessel Fluid Minimum Temperature - Vapour Phase

(F)

79.19

Inner W all Minimum Temperature - Liquid Phase

(F)

---

52

Valve Outlet Initial Temperature - Vapour Phase

(F)

57.19

Initial Mass of Vapour

(lb)

1.615e+004

53

Valve Outlet Final Temperature - Vapour Phase

(F)

78.87

Final Mass of Vapour

(lb)

4593

54

Valve Outlet Minimum Temperature - Vapour Phase

(F)

57.19

Peak Vapour Flow Through Valve

55

Inner W all Initial Temperature - Vapour Phase

(F)

---

Initial Mass of Liquid

56

Inner W all Final Temperature - Vapour Phase

(F)

---

Final Mass of Liquid

57

Inner W all Minimum Temperature - Vapour Phase

(F)

---

Peak Liquid Flow Through Valve

58

Vessel Fluid Initial Temperature - Liquid Phase

(F)

80.42

(seconds)

---

(lb/hr)

6360

(lb)

0.0000

(lb)

0.0000

(lb/hr)

0.0000

59
60
61
62
63
64
65
66
67
68
69

Aspen Technology Inc.


Licensed to: LEGENDS

Aspen HYSYS Version 7.3 (25.0.0.7336)

Page 2 of 2
* Specified by user.

1
2

LEGENDS
Burlington, MA
USA

3
4
5

Case Name:

BLOW DOWN 4 HOURS 8KM.HSC

Unit Set:

NewUser4a113

Date/Time:

Sun Sep 14 09:49:37 2014

Depressuring - Dynamics: BD 1

7
8
9

DESIGN

10
11

Connections

12
13

Inlet

14

Vessel Volume

(ft3)

1.431e+004

FEED-2

15

Liquid Volume

(ft3)

7156

16
17

Vessel Orientation

18

Flat End Vessel Volume

Horizontal

19

Height

(m)

8000 *

20

Diameter

(m)

0.2540 *

21

Metal Mass in Contact with Vapour

(lb)

(ft3)

1.431e+004

---

22

(ft3)

0.0000

Cylindrical Area

(ft2)

6.870e+004

Top Head Area

(ft2)

0.5453

Bottom Head Area

(ft2)

0.5453

(lb)

---

(ft2)

6.870e+004

Metal Mass in Contact with Liquid

Heat Flux

23
24

Initial Liquid Volume

Operating Mode :

Adiabatic

25
26

Heat Loss Model : Simple

27

Overall U

28

Ambient Temperature

(Btu/hr-ft2-F)

2.642

(F)

29

Valve Parameters

30
31

Vapour Flow Equation

32

Cd

33

Area

34

Vapour Back Pressure

35

Valve Equation Units

Supersonic

Liquid Flow Equation

(No Flow)

0.9750 *
(in2)

0.1446 *

(bar_g)

0.0000

Liquid Back Pressure

(bar_g)

0.0000

lb/hr

36

Options

37
38

Overall Heat Transfer Area

82.00 *

PV Work Term Contribution

(%)

39

80.00 *

Operating Conditions

40
41

Operating Pressure

42

Time Step Size

(bar_g)

43

Vapour Outlet Solving Option

44

Initial Cv Estimate

25.00

Depressuring Time

(seconds)

1.440e+004 *

Final Pressure

(bar_g)

6.895 *

Solved Pressure

(bar_g)

--Calculate Cv
0.9750 *

45

---

WORKSHEET

46
47

Properties

48
49

Name

50

Vapour Fraction

51

Temperature

52

Pressure

53

Actual Vol. Flow

54

Mass Enthalpy

55

Mass Entropy

56

Molecular W eight

57

FEED-2
1.0000
(F)
(bar_g)

80.00 *
25.00 *

(barrel/day)

1.157e+005

(Btu/lb)

-1997

(Btu/lb-F)

2.281

Molar Density

(lbmole/ft3)

6.894e-002

58

Mass Density

(lb/ft3)

1.128

59

Std Ideal Liq Mass Density

(lb/ft3)

18.99

60

Liq Mass Density @Std Cond

(lb/ft3)

4.332e-002

61

Molar Heat Capacity

(Btu/lbmole-F)

9.324

62

Mass Heat Capacity

(Btu/lb-F)

0.5698

63

Thermal Conductivity

(Btu/hr-ft-F)

2.073e-002

64

Viscosity

(cP)

1.182e-002

65

Surface Tension

66

Specific Heat

67

Z Factor

68

Vap. Frac. (molar basis)

69

Aspen Technology Inc.


Licensed to: LEGENDS

16.36

(dyne/cm)

---

(Btu/lbmole-F)

9.324
0.9450
1.0000

Aspen HYSYS Version 7.3 (25.0.0.7336)

Page 1 of 2
* Specified by user.

1
2

LEGENDS
Burlington, MA
USA

3
4
5

Case Name:

BLOW DOWN 4 HOURS 8KM.HSC

Unit Set:

NewUser4a113

Date/Time:

Sun Sep 14 09:49:37 2014

Depressuring - Dynamics: BD 1 (continued)

7
8
9

Properties

10
11

Vap. Frac. (mass basis)

12

Vap. Frac. (Volume Basis)

1.0000

13

Molar Volume

(ft3/lbmole)

14.51

14

Act.Gas Flow

(ACFM)

451.3

15

Act.Liq.Flow

16

1.0000

(USGPM)

---

Std.Liq.Vol.Flow

(barrel/day)

3.014e+006

17

Std.Gas Flow

(MMSCFD)

16.97

18

Watson K

19

Kinematic Viscosity

(cSt)

0.6543

20

Cp/Cv

21

Lower Heating Value

(Btu/lbmole)

3.463e+005

22

Mass Lower Heating Value

(Btu/lb)

2.116e+004

23

Liquid Fraction

24

Partial Pressure of CO2

(bar_g)

-0.9439

25

Avg.Liq.Density

(lbmole/ft3)

1.161

26

Heat Of Vap.

27

Mass Heat Of Vap.

19.27
1.381

0.0000

(Btu/lbmole)

3033

(Btu/lb)

185.3

28

COMPOSITIONS

29

FEED-2

30
31

Methane

0.9844 *

32

Ethane

0.0050 *

33

Propane

0.0020 *

34

i-Butane

0.0006 *

35

n-Butane

0.0004 *

36

i-Pentane

0.0002 *

37

n-Pentane

0.0001 *

38

n-Hexane

0.0001 *

39

H2S

0.0000 *

40

CO2

0.0027 *

41

Nitrogen

0.0046 *

42

Results

43
44

Initial Pressure

(bar_g)

25.00

Vessel Fluid Final Temperature - Liquid Phase

(F)

79.08

45

Final Pressure

(bar_g)

6.898

Vessel Fluid Minimum Temperature - Liquid Phase

(F)

79.08

46

Depressuring Time

1.440e+004 *

Valve Outlet Initial Temperature - Liquid Phase

(F)

57.19

47

Vapour Cv

0.9750 *

Valve Outlet Final Temperature - Liquid Phase

(F)

57.65

48

Liquid Cv

Valve Outlet Minimum Temperature - Liquid Phase

(F)

57.19

49

Vessel Fluid Initial Temperature - Vapour Phase

(F)

80.42

Inner W all Initial Temperature - Liquid Phase

(F)

---

50

Vesssel Fluid Final Temperature - Vapour Phase

(F)

79.08

Inner W all Final Temperature - Liquid Phase

(F)

---

51

Vessel Fluid Minimum Temperature - Vapour Phase

(F)

79.08

Inner W all Minimum Temperature - Liquid Phase

(F)

---

52

Valve Outlet Initial Temperature - Vapour Phase

(F)

57.19

Initial Mass of Vapour

(lb)

1.615e+004

53

Valve Outlet Final Temperature - Vapour Phase

(F)

78.80

Final Mass of Vapour

(lb)

4606

54

Valve Outlet Minimum Temperature - Vapour Phase

(F)

57.19

Peak Vapour Flow Through Valve

55

Inner W all Initial Temperature - Vapour Phase

(F)

---

Initial Mass of Liquid

56

Inner W all Final Temperature - Vapour Phase

(F)

---

Final Mass of Liquid

57

Inner W all Minimum Temperature - Vapour Phase

(F)

---

Peak Liquid Flow Through Valve

58

Vessel Fluid Initial Temperature - Liquid Phase

(F)

80.42

(seconds)

---

(lb/hr)

4818

(lb)

0.0000

(lb)

0.0000

(lb/hr)

0.0000

59
60
61
62
63
64
65
66
67
68
69

Aspen Technology Inc.


Licensed to: LEGENDS

Aspen HYSYS Version 7.3 (25.0.0.7336)

Page 2 of 2
* Specified by user.

1
2

LEGENDS
Burlington, MA
USA

3
4
5

Case Name:

BLOW DOWN 5 HOURS 8KM.HSC

Unit Set:

NewUser4a113

Date/Time:

Sun Sep 14 09:53:08 2014

Depressuring - Dynamics: BD 1

7
8
9

DESIGN

10
11

Connections

12
13

Inlet

14

Vessel Volume

(ft3)

1.431e+004

FEED-2

15

Liquid Volume

(ft3)

7156

16
17

Vessel Orientation

18

Flat End Vessel Volume

Horizontal

19

Height

(m)

8000 *

20

Diameter

(m)

0.2540 *

21

Metal Mass in Contact with Vapour

(lb)

(ft3)

1.431e+004

---

22

(ft3)

0.0000

Cylindrical Area

(ft2)

6.870e+004

Top Head Area

(ft2)

0.5453

Bottom Head Area

(ft2)

0.5453

(lb)

---

(ft2)

6.870e+004

Metal Mass in Contact with Liquid

Heat Flux

23
24

Initial Liquid Volume

Operating Mode :

Adiabatic

25
26

Heat Loss Model : Simple

27

Overall U

28

Ambient Temperature

(Btu/hr-ft2-F)

2.642

(F)

29

Valve Parameters

30
31

Vapour Flow Equation

32

Cd

33

Area

34

Vapour Back Pressure

35

Valve Equation Units

Supersonic

Liquid Flow Equation

(No Flow)

0.9750 *
(in2)

0.1155 *

(bar_g)

0.0000

Liquid Back Pressure

(bar_g)

0.0000

lb/hr

36

Options

37
38

Overall Heat Transfer Area

82.00 *

PV Work Term Contribution

(%)

39

80.00 *

Operating Conditions

40
41

Operating Pressure

42

Time Step Size

(bar_g)

43

Vapour Outlet Solving Option

44

Initial Cv Estimate

25.00

Depressuring Time

(seconds)

1.800e+004 *

Final Pressure

(bar_g)

6.895 *

Solved Pressure

(bar_g)

--Calculate Cv
0.9750 *

45

---

WORKSHEET

46
47

Properties

48
49

Name

50

Vapour Fraction

51

Temperature

52

Pressure

53

Actual Vol. Flow

54

Mass Enthalpy

55

Mass Entropy

56

Molecular W eight

57

FEED-2
1.0000
(F)
(bar_g)

80.00 *
25.00 *

(barrel/day)

1.157e+005

(Btu/lb)

-1997

(Btu/lb-F)

2.281

Molar Density

(lbmole/ft3)

6.894e-002

58

Mass Density

(lb/ft3)

1.128

59

Std Ideal Liq Mass Density

(lb/ft3)

18.99

60

Liq Mass Density @Std Cond

(lb/ft3)

4.332e-002

61

Molar Heat Capacity

(Btu/lbmole-F)

9.324

62

Mass Heat Capacity

(Btu/lb-F)

0.5698

63

Thermal Conductivity

(Btu/hr-ft-F)

2.073e-002

64

Viscosity

(cP)

1.182e-002

65

Surface Tension

66

Specific Heat

67

Z Factor

68

Vap. Frac. (molar basis)

69

Aspen Technology Inc.


Licensed to: LEGENDS

16.36

(dyne/cm)

---

(Btu/lbmole-F)

9.324
0.9450
1.0000

Aspen HYSYS Version 7.3 (25.0.0.7336)

Page 1 of 2
* Specified by user.

1
2

LEGENDS
Burlington, MA
USA

3
4
5

Case Name:

BLOW DOWN 5 HOURS 8KM.HSC

Unit Set:

NewUser4a113

Date/Time:

Sun Sep 14 09:53:08 2014

Depressuring - Dynamics: BD 1 (continued)

7
8
9

Properties

10
11

Vap. Frac. (mass basis)

12

Vap. Frac. (Volume Basis)

1.0000

13

Molar Volume

(ft3/lbmole)

14.51

14

Act.Gas Flow

(ACFM)

451.3

15

Act.Liq.Flow

16

1.0000

(USGPM)

---

Std.Liq.Vol.Flow

(barrel/day)

3.014e+006

17

Std.Gas Flow

(MMSCFD)

16.97

18

Watson K

19

Kinematic Viscosity

(cSt)

0.6543

20

Cp/Cv

21

Lower Heating Value

(Btu/lbmole)

3.463e+005

22

Mass Lower Heating Value

(Btu/lb)

2.116e+004

23

Liquid Fraction

24

Partial Pressure of CO2

(bar_g)

-0.9439

25

Avg.Liq.Density

(lbmole/ft3)

1.161

26

Heat Of Vap.

27

Mass Heat Of Vap.

19.27
1.381

0.0000

(Btu/lbmole)

3033

(Btu/lb)

185.3

28

COMPOSITIONS

29

FEED-2

30
31

Methane

0.9844 *

32

Ethane

0.0050 *

33

Propane

0.0020 *

34

i-Butane

0.0006 *

35

n-Butane

0.0004 *

36

i-Pentane

0.0002 *

37

n-Pentane

0.0001 *

38

n-Hexane

0.0001 *

39

H2S

0.0000 *

40

CO2

0.0027 *

41

Nitrogen

0.0046 *

42

Results

43
44

Initial Pressure

(bar_g)

25.00

Vessel Fluid Final Temperature - Liquid Phase

(F)

79.07

45

Final Pressure

(bar_g)

6.904

Vessel Fluid Minimum Temperature - Liquid Phase

(F)

79.07

46

Depressuring Time

1.800e+004 *

Valve Outlet Initial Temperature - Liquid Phase

(F)

57.19

47

Vapour Cv

0.9750 *

Valve Outlet Final Temperature - Liquid Phase

(F)

57.65

48

Liquid Cv

Valve Outlet Minimum Temperature - Liquid Phase

(F)

57.19

49

Vessel Fluid Initial Temperature - Vapour Phase

(F)

80.42

Inner W all Initial Temperature - Liquid Phase

(F)

---

50

Vesssel Fluid Final Temperature - Vapour Phase

(F)

79.07

Inner W all Final Temperature - Liquid Phase

(F)

---

51

Vessel Fluid Minimum Temperature - Vapour Phase

(F)

79.07

Inner W all Minimum Temperature - Liquid Phase

(F)

---

52

Valve Outlet Initial Temperature - Vapour Phase

(F)

57.19

Initial Mass of Vapour

(lb)

1.615e+004

53

Valve Outlet Final Temperature - Vapour Phase

(F)

78.78

Final Mass of Vapour

(lb)

4615

54

Valve Outlet Minimum Temperature - Vapour Phase

(F)

57.19

Peak Vapour Flow Through Valve

55

Inner W all Initial Temperature - Vapour Phase

(F)

---

Initial Mass of Liquid

56

Inner W all Final Temperature - Vapour Phase

(F)

---

Final Mass of Liquid

57

Inner W all Minimum Temperature - Vapour Phase

(F)

---

Peak Liquid Flow Through Valve

58

Vessel Fluid Initial Temperature - Liquid Phase

(F)

80.42

(seconds)

---

(lb/hr)

3857

(lb)

0.0000

(lb)

0.0000

(lb/hr)

0.0000

59
60
61
62
63
64
65
66
67
68
69

Aspen Technology Inc.


Licensed to: LEGENDS

Aspen HYSYS Version 7.3 (25.0.0.7336)

Page 2 of 2
* Specified by user.

PT.PERUSAHAAN GAS NEGARA


(Persero) Tbk

PT. CONNUSA ENERGINDO

PT.BINARASANO ENGINEERING

BLOWDOWN ANALYSIS REPORT


Document No.
CP19-BRE-3514-PS-CA-002

Rev.
B

Date
14/10/2014

ATTACHEMENT 2 : LINE SIZING CALCULATION

Page 13 of 13

LINE SIZING
1. Upstream RO
Design Data

Design Criteria

Pressure

= 377.3

psia

Max. Velocity = 60 ft/s

Temperature

= 80

P (psi/100 ft) = 0,486 psi/100 ft

= 540

Density

= 1.128

lb/ft3

Molecular Weight

Mw

= 16.36

Viscosity

= 0.01182

Compressibility Factor

= 0.945

Roughness

= 0.001

Pipe Material

= Carbon Steel

cP
in

Calculation Methode
1. Determine friction factor refer to API 14E
- Trial diameter (D) using gas velocity Equation (API 14E )

V =

- Calculate Reynold number (Re)

R =

2. Determine the value of (/D) and Re from the picture below to get (fm)

3. Determine Pressure Drop using Darcy formula

0,000336

Refer to API RP 521

Calculation Result
- Depressuring time

= 3

hours

- Molar Flowrate (Q)

= 3.54

MMSCFD

from HYSYS

- Mass Flowrate (W)

= 6360

lb/hr

from HYSYS

Option

D(in)

(/D)

Option 1

0.0005

Option 2

Option 3

Option 4

Gas Velocity (fps)

Re
1699710.084

0.0165

0.000333333

31.919

1133140.056

0.00025

17.954

849855.042

0.000166667

7.980

566570.028

= 4

hours

- Molar Flowrate (Q)

= 2.681

MMSCFD

from HYSYS

- Mass Flowrate (W)

= 4818

lb/hr

from HYSYS

D(in)

(/D)

Gas Velocity (fps)

Option 1

0.0005

Option 2

0.000333333

Option 3

0.00025

Option 4

0.000166667

6.043

54.391

Re

NOT OK

0.0155

0.769

NOT OK

0.015

0.176

OK

0.0145

0.022

OK

fm

P (psi/100ft)

Status

3.565

NOT OK

24.174

858177.540

0.0155

0.441

OK

13.598

643633.155

0.015

0.101

OK

429088.770

0.0145

0.013

OK

= 5

hours

= 2.147

MMSCFD

from HYSYS

- Mass Flowrate (W)

= 3857

lb/hr

from HYSYS

(/D)

6.213

0.0165

- Molar Flowrate (Q)

D(in)

Status

1287266.309

- Depressuring time

Option

P (psi/100ft)

71.818

- Depressuring time

Option

fm

Gas Velocity (fps)

Re

fm

P (psi/100ft)

Status

Option 1

0.0005

43.557

1030869.364

0.0165

2.285

NOT OK

Option 2

0.000333333

19.359

687246.243

0.0152

0.277

OK

Option 3

0.00025

10.889

515434.682

0.0152

0.066

OK

Option 4

0.000166667

4.840

343623.121

0.0145

0.008

OK

Selected Pipe Size


Based on calculation result that suitable of criteria :
D

0.176

psi/100ft

in

Gas Velocity

17.954

fps

Depressuring time

hours

2. Downstream RO
Design Data
Pressure

Design Criteria
P

Pressure Tip
Downstream Pressure

Pd

Temperature

= 100

psig

Beta ratio

0.2 - 0.75

= 790.8

kPa

Max. Velocity

500 fps

Noise

= 0

psig

= 14.7

psia

= 1

bar

= 82.5

= 301.2

K
lb/ft

Density

= 1.128

Spesific Gravity

SG

= 0.565

Molecular Weight

Mw

= 16.36

Viscosity

= 0.01182

Compressibility Factor

= 0.945

Specific Heat Ratio

Cp/Cv

Refer to API 14E

85 dB

Refer to Kepmen LH No.48/1996

55 dB

Refer to Kepmen Naker No.51/1999

cP

= 1.381

Roughness

= 0.001

in

= 4

in

Piping Data
Upstream Diameter

101.6

mm

Restriction Orifice Data


Discharge Coeficient Constant

= 0.975

Calculation
Estimation noise by Lighthill's Theory :

= 61,8 + 10 log

OASPL

20 log

= Overall sound pressure level of regenerated noise (dB)

= Inside diameter of vent stack (m)

C0

= Sonic Velocity (Velocity of sound in atmosphere) (m/s)

Vg

= Exit velocity of vented gas (m/s)

0
g

= Density of atmosphere (kg/m3)


= Density of vented gas (kg/m3)

= Distance from vent (m)

No

Calculation steps

3 Hours

4 Hours

5 Hours

1 Relief Load (W) (kg/h)

2885

2185

1749

2 Set Initial Value of FTP

3 Critical Flow Function, YCR

0.701

0.701

0.701

4 Orifice Diameter, d (mm)


5 Beta Ratio,

27.17
0.267

23.65
0.233

21.16
0.208

6 FTP Calculated

1.0012

1.0007

1.0004

420.81
63442.49

420.60
48047.83

420.50
38477.69

7 Critical Pressure, (kPa)


8 Reynold Number
9 Flow Region
10 Flow Behaviour

Turbulent - OK

Turbulent - OK

Turbulent - OK

Critical Flow

Critical Flow

Critical Flow

Noise
Sonic Velocity
Wind Velocity

= 459.861987 m/s
=

6 knots

3.084 m/s

Air Density

= 1.27605002 kg/m3

Vapour Density

= 0.70028956 kg/m3

Note :
Noise 1

85 dB

Distance

3m

Noise 2

55 dB

Distance

35 m

Blowdown Time
Option

Refer to Kepmen LH No.48/1996


Refer to Kepmen Naker No.51/1999

3 Hours
ID Downstream (in)

Mach Number

Noise 1

Status

Noise 2

Option 1

1.265

110.272

88.933

NOT OK

Option 2

0.562

85.619

64.280

NOT OK

Option 3

0.316

68.128

46.789

OK

Option 4

0.141

43.475

22.136

OK

Blowdown Time
Option

4 Hours
ID Downstream (in)

Mach Number

Noise 1

Status

Noise 2

Option 1

0.958

100.625

79.286

NOT OK

Option 2

0.426

75.972

54.633

OK

Option 3

0.240

58.480

37.141

OK

Option 4

0.106

33.828

12.489

OK

Blowdown Time
Option

5 Hours
ID Downstream (in)

Mach Number

Noise 1

Status

Noise 2

Option 1

0.767

92.895

71.556

NOT OK

Option 2

0.341

68.242

46.904

OK

Option 3

0.192

50.751

29.412

OK

Option 4

0.085

26.098

4.759

OK

Selected RO Size
Blowdown Time

3 Hours

ID Downstream

4 in

Mach Number

0.316

Beta Ratio

0.267

Orifice Diameter

27.17 mm
1.070 in

Reference
1. API RP 521 - "Guide for Pressure Relieving - Depressuring System"
2. API 14E - "Recommended Practice for Design and Installation of Offshore Production Platform Piping Systems"
2. API RP 520 - "Sizing, Selection, and Installation of Pressure-Relieving Devices in Reneries"
4. GPSA Section 17 - " Fluid Flow and Piping"