1/30
Presentation (continued)
Soft starters
for asynchronous motors
Applications
The Altistart 48 soft start - soft stop unit is a controller with 6 thyristors which is used
for the torque-controlled soft starting and stopping of three-phase squirrel cage
asynchronous motors in the power range between 4 and 1200 kW.
It offers soft starting and deceleration functions along with machine and motor
protection functions as well as functions for communicating with control systems.
These functions are designed for use in state-of-the-art applications in centrifugal
machines, pumps, fans, compressors and conveyors, which are primarily to be found
in the construction, food and beverages and chemical industries. The highperformance algorithms of the Altistart 48 contribute significantly to its robustness,
safety and ease of setup.
The Altistart 48 soft start - soft stop unit is a cost-effective solution which can:
b reduce machine operating costs by reducing mechanical stress and improving
machine availability,
b reduce the stress placed on the electrical distribution system by reducing line
current peaks and voltage drops during motor starts.
The Altistart soft start - soft stop unit offer comprises 2 ranges:
b three-phase voltages 230 to 415 V, 50/60 Hz,
b three-phase voltages 208 to 690 V, 50/60 Hz.
In each voltage range, the Altistart soft start - soft stop units are dimensioned for
standard and severe applications.
Functions
The Altistart 48 soft start - soft stop unit ( 1 ) is supplied ready for use in a standard
application with motor protection class 10 (see page 1/73).
It comprises a built-in terminal ( 2 ) which can be used to modify programming,
adjustment or monitoring functions in order to adapt and customise the application to
meet individual customer requirements.
b Drive performance functions:
v exclusive Altistart torque control (patented by Schneider Electric),
v constant control of the torque supplied to the motor during acceleration and
deceleration periods (significantly reducing pressure surges),
v facility for adjusting the ramp and the starting torque,
v the starter can be bypassed using a contactor ( 3 ) at the end of the starting period
whilst maintaining electronic protection (by-pass function),
v wide frequency tolerance for generator set power supplies,
v the starter can be connected to the motor delta terminals in series with each
winding.
b
v
v
v
v
v
b
v
v
v
v
v
Options
A remote terminal ( 4 ) can be mounted on the door of a wall-fixing or floor-standing
enclosure.
PowerSuite advanced dialogue solutions:
b PowerSuite Pocket PC with PPC type terminal ( 5 ),
b PowerSuite software workshop ( 6 ).
A range of wiring accessories for connecting the starter to PLCs via a Modbus
connection ( 7 ).
Bus communication and Ethernet, Fipio, DeviceNet and Profibus DP network
communication options.
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
1/31
1.3
Characteristics
Soft starters
for asynchronous motors
Environment characteristics
Conforming to standards
e marking
The electronic starters have been developed and performance tested in accordance with
international standards, in particular with the starter product standard EN/IEC 60947-4-2
Products have e marking in accordance with the harmonised standard EN/IEC 60947-4-2.
Product certifications
UL, CSA, DNV, C-Tick, GOST, CCC, NOM 117, SEPRO, TCF
Degree of protection
Vibration resistance
Shock resistance
52
58
50
54
55
60
Natural convection
Forced convection. The fans are activated automatically when a temperature threshold
is reached.
For flow rate: see page 1/53
Level 3 , conforming to IEC 60664-1
Relative humidity
1.3
Fans
Ambient temperature
around the device
dBA
dBA
dBA
dBA
dBA
dBA
Operation
Storage
- 10...+ 40 without derating (between + 40 and + 60, derate the nominal current of the
Altistart by 2 % for each C)
- 25...+ 70, conforming to IEC 60947-4-2
1000 without derating (above this, derate the nominal current of the Altistart by 2.2 % for
each additional 100 m). Limit to 2000 m
Operating position
Maximum permanent angle in relation to the normal vertical
mounting position
Electrical characteristics
Operating category
Three-phase supply voltage
ATS 48pppQ
ATS 48pppY
Frequency
Nominal starter current
ATS 48pppQ
ATS 48pppY
Motor power
ATS 48pppQ
ATS 48pppY
Voltage indicated on the motor ATS 48pppQ
rating plate
ATS 48pppY
Starter control circuit supply ATS 48pppQ
voltage
ATS 48pppY
Maximum control circuit
consumption
(with fans operating)
W
W
W
30
50
80
Presentation:
pages 1/30 and 1/31
1/32
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
Characteristics (continued)
Soft starters
for asynchronous motors
Protection
Thermal
Line protection
Current settings
Starting mode
Stopping mode
Freewheel stop
Controlled stop on torque ramp
Braked stop
Test levels
Examples
(sources of interference)
b Power factor correction capacitors can only be used upstream of the Altistart and only powered up at the end of starting.
b The starter must be earthed to conform to the regulations concerning leakage currents (y 30 mA). When the use of an upstream "residual
current device" for protection is required by the installation standards, an AS-Interface type device must be used. Check its compatibility with
the other protective devices. If the installation involves several starters on the same line supply, each starter must be earthed separately.
Presentation:
pages 1/30 and 1/31
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
1/33
1.3
Characteristics (continued)
Soft starters
for asynchronous motors
Torque characteristics
Curves indicating changes in the torque depending on the starting current of a threephase asynchronous motor.
Curves 1: direct line starting.
Curves 2: starting in current limiting mode.
Torque curve Ts1 indicates the total torque range available depending on the limiting
current Is1.
Limiting the starting current Is to a preset value Is1 will reduce the starting torque Ts1
to a value which is almost equal to the square of currents Is1/Is.
Example:
for motor characteristics: Ts = 3 Tn for Is = 6 In,
limit the current to Is1 = 3 In (0.5 Is)
resulting in a starting torque Ts1 = Ts x (0.5) = 3 Tn x 0.25 = 0.75 Tn
1.3
Starting current
I/In
Id1
0
0
0,25
0,5
0,75
1
N/Ns
Starting torque
1 Direct line starting torque
2 Starting torque with current limited
to Is1
C/Cn
6
1
3
2
2
Cr
Cd1
1
0
0
Presentation:
pages 1/30 and 1/31
1/34
References:
pages 1/40 to 1/43
0,25
Dimensions:
pages 1/48 to 1/53
0,5
0,75
Schemes:
pages 1/54 to 1/59
1
N/Ns
Characteristics (continued)
Soft starters
for asynchronous motors
I/In
4
N/Ns
1
1
3
1.3
2
0,5
2
1
0
t
I/In
4
N/Ns
1
0,5
2
1
0
t
Presentation:
pages 1/30 and 1/31
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
1/35
Selection criteria
Soft starters
for asynchronous motors
Altistart 48 soft start - soft stop units
b Two line power supply voltage ranges are available for selection:
v three-phase a.c. voltage: 230 - 415 V,
v three-phase a.c. voltage: 208 - 690 V.
b The power and the nominal current indicated on the motor name plate.
b The type of application and the operating cycle.
To simplify selection, the applications are categorised into 2 types:
v standard applications,
v severe applications.
Standard or severe applications define the limiting values of the current and the cycle
for motor duties S1 and S4.
1.3
Standard application
In standard applications, the Altistart 48 is designed to provide:
b Starting at 4 In for 23 seconds or at 3 In for 46 seconds from a cold state
(corresponding to motor duty S1).
b Starting at 3 In for 23 seconds or at 4 In for 12 seconds with a load factor of 50 %
and 10 starts per hour or a an equivalent thermal cycle (corresponding to motor
duty S4).
The motor thermal protection must conform to protection class 10 (see page 1/72).
Example: centrifugal pump.
Severe application
In severe applications, the Altistart 48 is designed to provide:
b Starting at 4 In for 48 seconds or at 3 In for 90 seconds from a cold state
(corresponding to S1 motor duty).
b Starting at 4 In for 25 seconds with a load factor of 50 % and 5 starts per hour or
a an equivalent thermal cycle (corresponding to S4 motor duty).
The motor thermal protection must conform to protection class 20 (see page 1/72).
Example: grinder.
Motor duties
S1 motor duty corresponds to starting followed by operation at constant load
enabling the thermal equilibrium to be reached.
S4 motor duty corresponds to a cycle comprising starting, operation at constant load
and an idle period.
This cycle is characterised by a load factor of 50 %.
Selecting the starter
Once the appropriate application has been selected from the following page, select
the starter from pages 1/40 to 1/43 according to the supply voltage and the motor
power.
Caution:
if the Altistart 48 is installed inside an enclosure, observe the mounting and derating
recommendations (see page 1/53).
1/36
Soft starters
for asynchronous motors
Application areas
Depending on the type of machine, the applications are categorized as standard or severe based on the starting characteristics, which are
given as examples only, in the table below.
Type of machine
Application
Centrifugal pump
Standard
Piston pump
Standard
350
5 to 10
Fan
Standard
Severe if > 30 s
300
10 to 40
Cold compressor
Standard
300
5 to 10
Screw compressor
Standard
300
3 to 20
Centrifugal compressor
Standard
Severe if > 30 s
350
10 to 40
Piston compressor
Standard
350
5 to 10
Conveyor, transporter
Standard
300
3 to 10
Lifting screw
Standard
300
3 to 10
Drag lift
Standard
400
2 to 10
Lift
Standard
350
5 to 10
Standard
Severe if > 30 s
300
10 to 60
Severe
400
3 to 10
Agitator
Standard
350
5 to 20
Mixer
Standard
350
5 to 10
Grinder
Severe
450
5 to 60
Crusher
Severe
400
10 to 40
Refiner
Standard
300
5 to 30
Press
Severe
400
20 to 60
1.3
1/37
Selection criteria
(continued)
Soft starters
for asynchronous motors
Special uses
Other criteria can influence the selection of the Altistart 48:
1.3
This type of installation only permits freewheel stopping and is not compatible with
the cascade and preheating functions.
ATS 48pppQ
Motor
Note: the nominal current and limiting current settings as well as the current
displayed during operation are on-line values (so do not have to be calculated by the
user).
Caution: for this type of installation, observe the wiring scheme and the associated
recommendations on page 1/56.
Starter bypassed by a contactor
(see the recommended application diagram on page 1/55)
The starter can be bypassed by a contactor at the end of starting (to limit the heat
dissipated by the starter). The bypass contactor is controlled by the starter and the
current measurements and protective mechanisms remain active when the starter is
bypassed.
The starter is selected on the basis of the 3 main criteria and one of the following
criteria:
b If the starter is bypassed at the end of starting, the motor is always started from
cold state and the starter can be oversized by one rating.
Example: select an ATS 48D17Q for an 11 kW motor in a standard 400 V application.
b If the starter must be able to operate without the bypass contactor at the end of
starting, it does not have to be derated.
Example: select an ATS 48D17Q for a 7.5 kW motor in a standard 400 V application.
1/38
Soft starters
for asynchronous motors
1/39
1.3
References
Soft starters
106762
230 V
kW
4
5.5
7.5
9
11
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
355
ATS 48D17Q
106761
1.3
400 V
kW
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
315
355
400
500
630
17
22
32
38
47
62
75
88
110
140
170
210
250
320
410
480
590
660
790
1000
1200
14.8
21
28.5
35
42
57
69
81
100
131
162
195
233
285
388
437
560
605
675
855
1045
59
74
104
116
142
201
245
290
322
391
479
580
695
902
1339
1386
1731
1958
2537
2865
3497
Weight
kg
ATS 48D17Q
ATS 48D22Q
ATS 48D32Q
ATS 48D38Q
ATS 48D47Q
ATS 48D62Q
ATS 48D75Q
ATS 48D88Q
ATS 48C11Q
ATS 48C14Q
ATS 48C17Q
ATS 48C21Q
ATS 48C25Q
ATS 48C32Q
ATS 48C41Q
ATS 48C48Q
ATS 48C59Q
ATS 48C66Q
ATS 48C79Q
ATS 48M10Q
ATS 48M12Q
4.900
4.900
4.900
4.900
4.900
8.300
8.300
8.300
8.300
12.400
12.400
18.200
18.200
18.200
51.400
51.400
51.400
51.400
115.000
115.000
115.000
ATS 48C14Q
106758
1/40
Weight
kg
3
5.5
12
14.8
46
ATS 48D17Q
4.900
4
7.5
17
21
59
ATS 48D22Q
4.900
5.5
11
22
28.5
74
ATS 48D32Q
4.900
7.5
15
32
35
99
ATS 48D38Q
4.900
9
18.5
38
42
116
ATS 48D47Q
4.900
11
22
47
57
153
ATS 48D62Q
8.300
15
30
62
69
201
ATS 48D75Q
8.300
18.5
37
75
81
245
ATS 48D88Q
8.300
22
45
88
100
252
ATS 48C11Q
8.300
30
55
110
131
306
ATS 48C14Q
12.400
37
75
140
162
391
ATS 48C17Q
12.400
45
90
170
195
468
ATS 48C21Q
18.200
55
110
210
233
580
ATS 48C25Q
18.200
75
132
250
285
695
ATS 48C32Q
18.200
90
160
320
388
1017
ATS 48C41Q
51.400
110
220
410
437
1172
ATS 48C48Q
51.400
132
250
480
560
1386
ATS 48C59Q
51.400
160
315
590
605
1731
ATS 48C66Q
51.400
355
660
675
2073
ATS 48C79Q
115.000
220
400
790
855
2225
ATS 48M10Q
115.000
250
500
1000
1045
2865
ATS 48M12Q
115.000
(1) Value indicated on the motor rating plate.
(2) Corresponds to the maximum permanent current in class 10. IcL corresponds to the starter
rating.
(3) Corresponds to the maximum permanent current in class 20.
(4) The factory setting current corresponds to the value of the nominal current of a standard
4-pole, 400 V, class 10 motor (standard application). Adjust the settings in accordance with
the motor nominal current.
ATS 48M12Q
Presentation:
pages 1/30 and 1/31
400 V
kW
Characteristics:
pages 1/32 to 1/35
Dimensions:
pages 1/48 and 1/49
Schemes:
pages 1/54 to 1/59
References (continued)
Soft starters
ATS 48pppQ
Motor
Figure 1
Special use:
starter connected to the motor delta
terminal in series with each winding
230 V
kW
400 V
kW
7.5
9
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
315
355
500
15
18.5
22
30
45
55
55
75
90
110
132
160
220
250
315
355
400
500
630
710
29
38
55
66
81
107
130
152
191
242
294
364
433
554
710
831
1022
1143
1368
1732
2078
14.8
21
28.5
35
42
57
69
81
100
131
162
195
233
285
388
437
560
605
675
855
1045
59
74
104
116
142
201
245
290
322
391
479
580
695
902
1339
1386
1731
1958
2537
2865
3497
Weight
kg
ATS 48D17Q
ATS 48D22Q
ATS 48D32Q
ATS 48D38Q
ATS 48D47Q
ATS 48D62Q
ATS 48D75Q
ATS 48D88Q
ATS 48C11Q
ATS 48C14Q
ATS 48C17Q
ATS 48C21Q
ATS 48C25Q
ATS 48C32Q
ATS 48C41Q
ATS 48C48Q
ATS 48C59Q
ATS 48C66Q
ATS 48C79Q
ATS 48M10Q
ATS 48M12Q
4.900
4.900
4.900
4.900
4.900
8.300
8.300
8.300
8.300
12.400
12.400
18.200
18.200
18.200
51.400
51.400
51.400
51.400
115.000
115.000
115.000
400 V
kW
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
Dimensions:
pages 1/48 and 1/49
Weight
kg
5.5
11
22
14.8
46
7.5
15
29
21
59
9
18.5
38
28.5
74
15
22
55
35
99
18.5
30
66
42
116
22
45
81
57
153
30
55
107
69
201
37
55
130
81
245
45
75
152
100
252
55
90
191
131
306
75
110
242
162
391
90
132
294
195
468
110
160
364
233
580
132
220
433
285
695
160
250
554
388
1017
220
315
710
437
1172
250
355
831
560
1386
400
1022
605
1731
315
500
1143
675
2073
355
630
1368
855
2225
710
1732
1045
2865
(1) Value indicated on the motor rating plate.
(2) Corresponds to the maximum permanent current in class 10.
(3) Corresponds to the maximum permanent current in class 20.
(4) For this type of connection, the factory setting current must be
the nominal motor current.
ATS 48D17Q
ATS 48D22Q
ATS 48D32Q
ATS 48D38Q
ATS 48D47Q
ATS 48D62Q
ATS 48D75Q
ATS 48D88Q
ATS 48C11Q
ATS 48C14Q
ATS 48C17Q
ATS 48C21Q
ATS 48C25Q
ATS 48C32Q
ATS 48C41Q
ATS 48C48Q
ATS 48C59Q
ATS 48C66Q
ATS 48C79Q
ATS 48M10Q
ATS 48M12Q
4.900
4.900
4.900
4.900
4.900
8.300
8.300
8.300
8.300
12.400
12.400
18.200
18.200
18.200
51.400
51.400
51.400
51.400
115.000
115.000
115.000
Schemes:
pages 1/54 to 1/59
1/41
1.3
References (continued)
Soft starters
106762
Starter 208/690 V
Nominal Factory
current setting
(IcL)
current
(4)
208 V 230 V 460 V 575 V (2)
HP
HP
HP
HP
A
A
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
350
400
ATS 48D17Y
106761
1.3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
450
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400
500
600
800
1000
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400
500
600
800
1000
1200
17
22
32
38
47
62
75
88
110
140
170
210
250
320
410
480
590
660
790
1000
1200
14
21
27
34
40
52
65
77
96
124
156
180
240
302
361
414
477
590
720
954
1170
- 50/60 Hz
Power
Reference
dissipated
at nominal
load
kg
W
59
74
104
116
142
201
245
290
322
391
479
580
695
902
1339
1386
1731
1958
2537
2865
3497
Weight
ATS 48D17Y
ATS 48D22Y
ATS 48D32Y
ATS 48D38Y
ATS 48D47Y
ATS 48D62Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48C66Y
ATS 48C79Y
ATS 48M10Y
ATS 48M12Y
4.900
4.900
4.900
4.900
4.900
8.300
8.300
8.300
8.300
12.400
12.400
18.200
18.200
18.200
51.400
51.400
51.400
51.400
115.000
115.000
115.000
ATS 48C14Y
106758
1/42
kg
2
3
7.5
10
12
14
46
ATS 48D17Y
4.900
3
5
10
15
17
21
59
ATS 48D22Y
4.900
5
7.5
15
20
22
27
74
ATS 48D32Y
4.900
7.5
10
20
25
32
34
99
ATS 48D38Y
4.900
10
25
30
38
40
116
ATS 48D47Y
4.900
15
30
40
47
52
153
ATS 48D62Y
8.300
15
20
40
50
62
65
201
ATS 48D75Y
8.300
20
25
50
60
75
77
245
ATS 48D88Y
8.300
25
30
60
75
88
96
252
ATS 48C11Y
8.300
30
40
75
100
110
124
306
ATS 48C14Y
12.400
40
50
100
125
140
156
391
ATS 48C17Y
12.400
50
60
125
150
170
180
468
ATS 48C21Y
18.200
60
75
150
200
210
240
580
ATS 48C25Y
18.200
75
100
200
250
250
302
695
ATS 48C32Y
18.200
100
125
250
300
320
361
1017
ATS 48C41Y
51.400
125
150
300
350
410
414
1172
ATS 48C48Y
51.400
150
350
400
480
477
1386
ATS 48C59Y
51.400
200
400
500
590
590
1731
ATS 48C66Y
51.400
200
250
500
600
660
720
2073
ATS 48C79Y 115.000
250
300
600
800
790
954
2225
ATS 48M10Y 115.000
350
350
800
1000
1000
1170
2865
ATS 48M12Y 115.000
(1) Value indicated on the motor rating plate.
(2) Corresponds to the maximum permanent current in class 10. IcL corresponds to the starter
rating.
(3) Corresponds to the maximum permanent current in class 20.
(4) The factory setting current corresponds to the value of the nominal current of a standard motor
according to NEC, 460 V, class 10 (standard application). Adjust the settings in accordance
with the motor nominal current.
ATS 48M12Y
Presentation:
pages 1/30 and 1/31
Weight
Characteristics:
pages 1/32 to 1/35
Dimensions:
pages 1/48 and 1/49
Schemes:
pages 1/54 to 1/59
References (continued)
Soft starters
230 V
kW
400 V
kW
440 V
kW
500 V
kW
525 V
kW
660 V
kW
690 V
kW
4
5.5
7.5
9
11
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
355
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
315
355
400
500
630
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
220
250
355
400
500
630
710
9
11
18.5
22
30
37
45
55
75
90
110
132
160
220
250
315
400
500
630
800
9
11
18.5
22
30
37
45
55
75
90
110
132
160
220
250
315
400
500
630
800
11
15
22
30
37
45
55
75
90
110
132
160
220
250
355
400
560
630
710
900
15
18.5
22
30
37
45
55
75
90
110
160
200
250
315
400
500
560
630
710
900
Power
dissipated
at nominal
load
Reference
Weight
kg
17
22
32
38
47
62
75
88
110
140
170
210
250
320
410
480
590
660
790
1000
1200
14
21
27
34
40
52
65
77
96
124
156
180
240
302
361
414
477
590
720
954
1170
59
74
104
116
142
201
245
290
322
391
479
580
695
902
1339
1386
1731
1958
2537
2865
3497
ATS 48D17Y
ATS 48D22Y
ATS 48D32Y
ATS 48D38Y
ATS 48D47Y
ATS 48D62Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48C66Y
ATS 48C79Y
ATS 48M10Y
ATS 48M12Y
Power
dissipated
at nominal
load
Reference
4.900
4.900
4.900
4.900
4.900
8.300
8.300
8.300
8.300
12.400
12.400
18.200
18.200
18.200
51.400
51.400
51.400
51.400
115.000
115.000
115.000
230 V
kW
400 V
kW
440 V
kW
500 V
kW
525 V
kW
660 V
kW
690 V
kW
Weight
kg
3
5.5
5.5
7.5
7.5
9
11
12
14
46
ATS 48D17Y
4.900
4
7.5
7.5
9
9
11
15
17
21
59
ATS 48D22Y
4.900
5.5
11
11
11
11
15
18.5
22
27
74
ATS 48D32Y
4.900
7.5
15
15
18.5
18.5
22
22
32
34
99
ATS 48D38Y
4.900
9
18.5
18.5
22
22
30
30
38
40
116
ATS 48D47Y
4.900
11
22
22
30
30
37
37
47
52
153
ATS 48D62Y
8.300
15
30
30
37
37
45
45
62
65
201
ATS 48D75Y
8.300
18.5
37
37
45
45
55
55
75
77
245
ATS 48D88Y
8.300
22
45
45
55
55
75
75
88
96
252
ATS 48C11Y
8.300
30
55
55
75
75
90
90
110
124
306
ATS 48C14Y
12.400
37
75
75
90
90
110
110
140
156
391
ATS 48C17Y
12.400
45
90
90
110
110
132
160
170
180
468
ATS 48C21Y
18.200
55
110
110
132
132
160
200
210
240
580
ATS 48C25Y
18.200
75
132
132
160
160
220
250
250
302
695
ATS 48C32Y
18.200
90
160
160
220
220
250
315
320
361
1017
ATS 48C41Y
51.400
110
220
220
250
250
355
400
410
414
1172
ATS 48C48Y
51.400
132
250
250
315
315
400
500
480
477
1386
ATS 48C59Y
51.400
160
315
355
400
400
560
560
590
590
1731
ATS 48C66Y
51.400
355
400
630
630
660
720
2073
ATS 48C79Y
115.000
220
400
500
500
500
710
710
790
954
2225
ATS 48M10Y
115.000
250
500
630
630
630
900
900
1000
1170
2865
ATS 48M12Y
115.000
(1) Value indicated on the motor rating plate.
(2) Corresponds to the maximum permanent current in class 10. IcL corresponds to the starter rating.
(3) Corresponds to the maximum permanent current in class 20.
(4) The factory setting current corresponds to the value of the nominal current of a standard motor according to NEC, 460 V, class 10 (standard application). Adjust
the settings in accordance with the motor nominal current.
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
Dimensions:
pages 1/48 and 1/49
Schemes:
pages 1/54 to 1/59
1/43
1.3
Presentation
Soft starters
for asynchronous motors
Altistart 48 soft start - soft stop units
Options: remote terminal, line chokes and DNV kits
Remote terminal
The terminal can be mounted on the door of a wall-fixing or floor-standing enclosure.
It has the same signalling display and configuration buttons as the terminal
integrated in the starter. A switch to lock access to the menu is located at the rear of
the terminal.
1.3
1
ESC
ENT
Line chokes
The use of line chokes is recommended in particular when installing several
electronic starters on the same line supply. The values of the chokes are defined for
a voltage drop between 3% and 5% of the nominal line voltage.
Install the line choke between the line contactor and the starter.
DNV kits
These kits enable ATS 48D62p to 48M12p starters to meet the requirements of the
DNV certification body.
Each kit consists of the fixing pins and all the parts necessary for mounting the starter
(when mounting using the VW3 G48107 kit a sling must be used, which is not
included).
ATS 48D17p to 48D47p starters are DNV certified and it is not necessary to add an
optional kit.
References:
page 1/45
1/44
Dimension:
pages 1/50 to 1/52
References
Soft starters
for asynchronous motors
106770
Remote terminal
Description
Reference
Remote terminal
VW3 G48101
Weight
kg
0.200
Line chokes
For starters
Nominal
current
Degree of Reference
protection
ATS 48D17p
Value
of the
choke
mH
1.7
Weight
A
15
IP 20
VZ1 L015UM17T
kg
2.100
ATS 48D22p
0.8
30
IP 20
VZ1 L030U800T
4.100
0.6
40
IP 20
VZ1 L040U600T
5.100
0.35
70
IP 20
VZ1 L070U350T
8.000
0.17
150
IP 00
VZ1 L150U170T
14.900
0.1
250
IP 00
VZ1 L250U100T
24.300
ATS 48C32p
0.075
325
IP 00
VZ1 L325U075T
28.900
0.045
530
IP 00
VZ1 L530U045T
37.000
0.024
1025
IP 00
VZ1 LM10U024T
66.000
ATS 48M12p
0.016
1435
IP 00
VZ1 LM14U016T
80.000
524102
VW3 G48101
Nota : line chokes with IP 00 degree of protection must be fitted with a protective bar to protect
personnel against electrical contact.
DNV kits
For starters
Reference
VW3 G48106
Weight
kg
0.600
VW3 G48107
0.680
VW3 G48108
3.400
VW3 G48109
4.400
VW3 G48106
Number of covers
per set
6 (1)
LA9 F702
Format
Reference
A5
VVD ED 301066
Weight
kg
0.150
A5
VVD ED 302023
0.150
0.150
Reference
Weight
kg
0.250
Documentation
Description
LA9 F702
Presentation:
page 1/44
Dimensions:
pages 1/50 to 1/52
1/45
1.3
Presentation
Soft starters
1
2 3
6 4 6 5
1 PLC (1)
2 Modbus cable depending on the type
of controller or PLC
3 Modbus splitter block LU9 GC3
4 Modbus drop cable VW3 A8 306 Rpp
5 Line terminators VW3 A8 306 RC
6 Modbus T-junction box
VW3 A8 306 TFpp (with cable)
5
4
1.3
ATS 48
1
2
ATS 48
2
3
ATS 48
1 To network
2 Communication modules
3 Cables VW3 A8 306 Rpp,
VW3 P07 306 R10 or
VW3 A8 306 D30
4 Modbus splitter block LU9 GC3
5 Modbus drop cable VW3 A8 306 Rpp
6 Line terminator VW3 A8 306 RC
6
5
ATS 48
(1) Please consult our "Modicon Premium automation platform" and "Modicon TSX Micro
automation platform" catalogues.
References:
page 1/47
1/46
References
Soft starters
Unit reference
TSX SCA 50
Weight
kg
0.520
TSX SCA 62
0.570
LU9 GC3
0.500
R = 120 , C = 1 nF
VW3 A8 306 RC
0.200
R = 150
VW3 A8 306 R
0.200
R = 120 , C = 1 nF
0.200
R = 150
VW3 A8 306 DR
0.200
Junction box
3 screw terminals, RC line terminator
To be connected using cable VW3 A8 306 D30
Subscriber sockets
2 x female 15-way SUB-D connectors
and 2 screw terminals, RC line terminator
To be connected using cable VW3 A8 306
Modbus splitter block
8 RJ45 type connectors and 1 screw terminal
TSX SCA 50
Line
terminators
(1)
For RJ45
connector
For screw
terminals
TSX SCA 62
Connecting cables
Description
Cables for
Modbus bus
Length
m
3
Connectors
Reference
Weight
kg
0.150
0.3
1 RJ45 connector
VW3 A8 306 D30
and one end stripped
1 RJ45 connector and 1male VW3 A8 306
15-way SUB-D connector for
TSX SCA 62
2 RJ45 connectors
VW3 A8 306 R03
2 RJ45 connectors
0.050
2 RJ45 connectors
0.150
2 RJ45 connectors
0.050
0.150
0.050
Cables for
1
Profibus DP
RS 485 double 100
shielded twisted
pair cables
200
500
Cables
to be connected
VW3 A8 306 D30
Reference
LUF P1
0.240
DeviceNet/Modbus gateway
(3)
LUF P9
0.240
LA9 P307
0.240
LUF P7
0.240
Ethernet/Modbus bridge
with 1 x Ethernet 10baseT port
(RJ45 type)
Fipio/Modbus gateway
(3)
LUF P1
LA9 P307
Weight
kg
174 CEV 300 10 (2)
0.500
Presentation:
page 1/46
1/47
1.3
Dimensions
Soft starters
for asynchronous motors
270
290
275
M6
M6
190
100
1.3
=
M6
235
160
190
Maximum connection capacity:
Earth connections: 10 mm2 (AWG 8)
Power terminals: 16 mm2 (AWG 8)
159
4x 7
3/L2
5/L3
14
1
340
320
1/L1
10
5
5
116,5
38
162
9x 8
M6
62
62
200
265
136,5
M10
9x 12
3/L2
5/L3
4x 9
18
380
350
1/L1
10
250
5
5
136,5
196,5
265
Presentation:
pages 1/30 and 1/31
1/48
70
20
90
M10
90
320
Characteristics:
pages 1/32 and 1/33
References:
pages 1/40 to 1/43
Schemes:
pages 1/54 to 1/59
10
150
4x 7
260
M6
6,6
4x 7
Dimensions (continued)
Soft starters
for asynchronous motors
300
115
120
=
115
127
165
20
4x 9
69
M10
3L2
5L3
1.3
610
670
1L1
5
5
1,5
40
58
165
216
300
0,25
M10
50,25
40
115
115
400
350
350
257
129
26
164
6x 9
209,5
26
18x 14
M10
26
20
170
26
223,5
180
850
228
204
26
26
26
24
26
5
5
116,5
196,5
60
M10
26
890
155
60
95
188
315
770
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 and 1/33
References:
pages 1/40 to 1/43
Schemes:
pages 1/54 to 1/59
1/49
Dimensions (continued)
Soft starters
for asynchronous motors
DNV Kits
VW3 G48106 for soft start/soft stop units ATS 48D62p to ATS 48C17p
4x 5,3
10
60
49,2
49,2
24,6
60
24,6
1.3
G
36
For ATS 48
G
150
160
D62p to C11p
C14p to C17p
H
270
320
VW3 G48107 for soft start/soft stop units ATS 48C21p to ATS 48C32p
14
4x 5,3
24,6
49,2
60,5
49,2
24,6
350
60,5
250
33
Presentation:
pages 1/30 and 1/31
1/50
Characteristics:
pages 1/32 and 1/33
References:
pages 1/40 to 1/43
Schemes:
pages 1/54 to 1/59
Dimensions (continued)
Soft starters
for asynchronous motors
49
98
120
2x 9
85
49
610
1.3
300
56
VW3 G48109 for soft start/soft stop units ATS 48C79p to ATS 48M12p
350
350
7,5
49
98
120
2x 9
49
850
85
56
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 and 1/33
References:
pages 1/40 to 1/43
Schemes:
pages 1/54 to 1/59
1/51
Dimensions (continued)
Soft starters
for asynchronous motors
Altistart 48 soft start - soft stop units
Line chokes and remote terminal
Line chokes
VZ1-L015UM17T to L070U350T
VZ1-L150U170T to LM14U016T
c1
G
1.3
H
c1
VZ1L015UM17T
L030U800T
L040U600T
L070U350T
a
120
150
180
180
b
150
180
215
215
c
80
120
130
150
c1
75
100
100
130
G
60/80.5
75/106.5
85/122
85/122
H
52
76
76
97
6
7
7
7
VZ1L150U170T
L250U100T
L325U075T
L530U045T
LM10U024T
LM14U016T
a
270
270
270
380
400
420
b
240
240
240
410
410
490
c
170
220
240
225
310
340
c1
140
160
175
140
170
170
G
105/181
105/181
105/181
310
310
310
Remote terminal
VW3 G48101
52
79.6
55.6
24
Presentation:
pages 1/30 and 1/31
1/52
Characteristics:
pages 1/32 and 1/33
References:
pages 1/40 to 1/43
Schemes:
pages 1/54 to 1/59
H
96
125
138
95
125
125
11.5
11.5
11.5
9
9
9
Soft starters
for asynchronous motors
Mounting recommendations
100 mm
50
mm
100 mm
50
mm
1.3
Mounting in a metal wall-fixing or floor-standing enclosure with degree of protection IP 23 or IP 54
b Observe the mounting recommendations above.
b To ensure proper air circulation in the starter:
v fit ventilation grilles,
v ensure that there is sufficient ventilation. If there is not, install forced ventilation
with a filter ; the openings and/or fans must provide a flow rate at least equal to that
of the starter fans (see the table below).
b Use special filters with IP 54 protection.
ATS 48 starter
ATS48 D32p and D38p
ATS48 D47p
ATS48 D62p to C11p
ATS48 C14p and C17p
ATS48 C21p to C32p
ATS48 C41p to C66p
ATS48 C29p to M12p
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 and 1/33
References:
pages 1/40 to 1/43
Schemes:
pages 1/54 to 1/59
1/53
Schemes
Soft starters
for asynchronous motors
13
Recommended application diagram for non-reversing unit with line contactor, type 1 and type 2
coordinations
14
Q1
Q1
Emergency stop
T1
S2
KM1
14
13
S1
R1A
A1
(2)
R1C
KM1
A1
1.3
Q3
KM1
A2
(1)
R3C
R3A
R2C
R2A
R1C
PTC2
R1A
PTC1
COM
AO1
LO2
LO1
LO+
CL2
CL1
+24V
LI4
53
LI3
5/L3
6/T3
RUN
3/L2
4/T2
STOP
1/L1
A1
2/T1
(3)
W1
V1
U1
54
KM1
M1
3
Select the components to connect, according to the descriptions on page 1/55, from the association tables on pages 1/60 to 1/69.
(1) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.
(2) Assign relay R1 as the "isolating relay". Beware of the operating limits of the contacts (see characteristics page 1/32), for example when connecting to high rating
contactors.
(3) Insert a transformer if the line voltage is different to that defined for the control circuit (see characteristics page 1/32).
Types of coordination
The standard defines tests for different current levels which are designed to expose the device to extreme conditions.
Based on the state of the components after a short-circuit test, the standard defines 2 types of coordination.
b Type 1 coordination: damage to the contactor and the starter is acceptable under 2 conditions:
v no risk is posed to the operator,
v elements other than the contactor and the starter are not damaged.
Maintenance must be carried out after a short-circuit.
b Type 2 coordination: minor soldering of the contactor contacts is permissible if they can be separated easily. The starter must not be damaged beyond repair.
The protection and control devices remain operational after type 2 coordination tests.
Once the fuses have been replaced, check the contactor.
Nota: the starter will protect the motor and the cables against overloads. If this protection function is disabled, external thermal protection must be provided.
Presentation:
pages 1/30 and 1/31
1/54
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes (continued)
Soft starters
for asynchronous motors
Q1
14
13
Recommended application diagram for non-reversing unit with starter line and bypass contactors, type 1
and type 2 coordinations
Q1
6
5
T1
R2C
R1C
A1
R1A
(2)
KM1
2
R2A
A1
Q3
A2
KM1
A2
KM3
(1)
1.3
A1
4
3
Emergency stop
CL2
CL1
5/L3
5
6
3/L2
3
4
A1
1/L1
1
2
(3)
R3C
R3A
R2C
R2A
R1C
R1A
PTC2
PTC1
COM
AO1
LO2
LO1
LO+
+24V
LI4
LI3
RUN
STOP
2/T1
A2
4/T2
B2
6/T3
C2
KM3
S2
S1
+ 24 V
STOP
+ 24 V
RUN
STOP
M1
3
W1
V1
U1
S1
Select the components to connect, according to the descriptions below, from the association tables on pages 1/60 to 1/69.
(1) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.
(2) Assign relay R1 as the "isolating relay". Beware of the operating limits of the contacts (see characteristics page 1/32), for example when connecting to high rating
contactors.
(3) Insert a transformer if the line voltage is different to that defined for the control circuit (see characteristics page 1/32).
(4) 2-wire or 3-wire control (see page 1/76).
Presentation:
pages 1/30 and 1/31
Description
Motor
Starter (standard applications and severe applications)
Circuit-breaker or switch/fuse
3 FA fuses
Contactors
Control (separate parts XB2 or XB2 M)
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
1/55
Schemes (continued)
Soft starters
for asynchronous motors
14
- Q1
Emergency stop
- S3
6
5
4
3
- Q1
- T1
R2A
A1
R1A
(3)
R2C
R1C
- KM1
2
(1)
13
Recommended application diagram for connection to the motor delta terminals, non-reversing, freewheel
stop, with starter line and bypass contactors, type 1 and type 2 coordinations
Q3
A2
- KM1
R3C
R3A
R2C
R2A
R1C
R1A
PTC2
PTC1
AO1
COM
LO2
LO1
CL2
LO+
+24V
LI4
LI3
RUN
2/T1
A2
4/T2
B2
6/T3
C2
- KM3
STOP
CL1
5/L3
5
6
3/L2
3
4
1/L1
1
2
(4)
A2
- KM3
(2)
A1
A1
A1
1.3
S2
S1
U2
V2
M1
3a
+24V
STOP
+24V
U1
RUN
W2
STOP
V1
W1
S1
Select the components to connect according to the descriptions on page 1/57 and the association tables on pages 1/60 to 1/69.
(1) A line contactor must be used in the sequence.
(2) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.
(3) R1 must be assigned as the "isolating relay" to control contactor KM1. Beware of the operating limits of the contacts (see characteristics page 1/32), for example
when connecting to high rating contactors.
(4) Insert a transformer if the line voltage is different to that defined for the control circuit (see characteristics page 1/32).
(5) 2-wire and 3-wire controls (see page 1/76).
Types of coordination
The standard defines tests for different current levels which are designed to expose the device to extreme conditions.
Based on the state of the components after a short-circuit test, the standard defines 2 types of coordinations.
b Type 1 coordination: damage to the contactor and the starter is acceptable under 2 conditions:
v no risk is posed to the operator,
v elements other than the contactor and the starter are not damaged.
Maintenance must be carried out after a short-circuit.
b Type 2 coordination: minor soldering of the contactor contacts is permissible if they can be separated easily. The starter must not be damaged beyond repair.
The protection and control devices remain operational after type 2 coordination tests.
Once the fuses have been replaced, check the contactor.
Nota: the starter will protect the motor and the cables against overloads. If this protection function is disabled, external thermal protection must be provided.
Presentation:
pages 1/30 and 1/31
1/56
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes (continued)
Soft starters
for asynchronous motors
Recommended application diagram for LSP/HSP motor, non-reversing with starter line and bypass
contactors
- Q1
- T1
220
- KM1
1.3
Q3
(1)
R3C
R3A
R2C
R2A
R1C
R1A
PTC2
PTC1
COM
AO1
LO2
LO1
LO+
+24V
CL2
LI4
CL1
LI3
2/T1
A2
4/T2
B2
6/T3
C2
RUN
- KM3
STOP
5/L3
5
6
3/L2
3
4
A1
1/L1
1
2
(2)
(3)
KA1
- KM5
KM2
- KM2
U2
V2
W2
U1
V1
M1
3
W1
Select the components to connect, according to the descriptions below, from the association tables on pages 1/60 to 1/69.
(1) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.
(2) Insert a transformer if the line voltage is different to that defined for the control circuit (see page characteristics 1/32).
(3) Assign logic input LI3 to "activate the adjustment functions of the 2 nd motor".
(4) Assign relay R1 as the "isolating relay". Beware of the operating limits of the contacts (see characteristics page 1/32), for example when connecting to high rating
contactors.
220 V
KM1
Emergency stop
Q1
A1
R2A
S1
(4)
R2C
S4
KM5
KM2
A1
R1A
S2
(4)
KA1
KA1
KM5
R1C
S3
KM1
KM2
KM2
KM5
KM3
S4 : 1 = low speed
S4 : 2 = high speed
Description
Motor
Starter (standard applications and severe applications)
Circuit-breaker or switch/fuse
3 FA fuses
Contactors and relays
Control (separate parts XB2 or XB2 M)
Characteristics:
pages 1/32 to 1/35
References
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
1/57
Schemes (continued)
Soft starters
for asynchronous motors
Recommended application diagram for starting and decelerating several motors cascaded with a single
Altistart 48, non-reversing and line contactor
The diagram is given as an example only. For more details, refer to the Altistart 48 user's manual.
KA
KALI
KAT
KALIT
KALIT
STOP
LI3
- T1
RUN
(2)
- KM1
1.3
CL2
4
3
A1
CL1 +24V
2
1
- Q1
B
- Q3
M1
6
5
4
3
M2
Vn
Mi
3
Motor 1
Wn
2
Un
6
W2
2
U2
V2
- Qn1
W1
2
U1
- KMn2
6
5
4
3
- KMn1
- Q21
1
2
1
6
5
4
3
- KM22
V1
- Q11
- KM21
2
- KM12
- KM11
6/T3 5/L3
4/T2 3/L2
A1
2/T1 1/L1
(1)
Mn
3
Motor 2
3
Motor i
Motor n
Select the components to connect, according to the designations below, from the association tables on pages 1/60 to 1/69.
(1) For type 2 coordination (according to IEC 60947-4-2), install fast-acting fuses to ensure that the starter will be protected in the event of a short-circuit.
(2) Insert a transformer if the line voltage is different to that defined for the control circuit (see page characteristics 1/32).
Important:
b One Altistart 48 logic input must be configured as a "cascading" input.
b In the event of a fault, it will not be possible to decelerate or brake any motors that may be running at that time.
b Adjust the thermal protection of each circuit-breaker Qn1 for the corresponding nominal motor current.
Presentation:
pages 1/30 and 1/31
1/58
Description
Motors
Starter (standard applications and severe applications)
Contactors
Circuit-breaker or switch/fuse
3 FA fuses
Thermal magnetic circuit-breakers
Control (separate parts XB2 or XB2 M)
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes (continued)
Soft starters
for asynchronous motors
Recommended application diagram for starting and decelerating several motors cascaded with a single
Altistart 48, non-reversing and line contactors (continued)
Motor n control
A...
(n-1) contacts
KM11
KM21
ARn
SHUNT
KT
1.3
KMi1
KMn1
BPMn
KAT
ACDEC
KMn2
BPAn
BPAn
KAMn
KMn2
KMn1
KAMn
KMn2
SHUNT
ART
ARn
KAMn
ARn
KMn1
ARn
KMn1
KMn2
B...
Cascade control
n contacts
MST
KM1
MHT
AR1
AR2
ARi
ARn
Q11
n contacts
n contacts
Q21
A1
K
KA
KALI
R1C
KALIT
KT
KALIT
ART
KAMi
KAMn
Qi1
R2C
(1)
R1A
KAT
KAM1 KAM2
ACDEC
R2A
SHUNT
Qn1
KM1
KA
KALI
(1) Assign relay R1 as the "isolating relay". Beware of the operating limits of the contacts (see Characteristics page 1/32), for example when connecting to high
rating contactors.
BPMn: "Run" button motor n
BPAn: "Stop" button motor n
MST: General "Run" button
MHT: General "Stop" button
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
1/59
Combinations
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
1.3
A1
11.5
ATS 48D17p
ATS 48D22p
5.5
20
ATS 48D22p
ATS 48D32p
7.5
27
ATS 48D32p
ATS 48D38p
32
ATS 48D38p
ATS 48D47p
11
39
ATS 48D47p
ATS 48D62p
15
52
ATS 48D62p
ATS 48D75p
18.5
64
ATS 48D75p
ATS 48D88p
22
30
37
45
55
75
90
110
132
160
75
103
126
150
182
240
295
356
425
520
ATS 48D88p
ATS 48C11p
ATS 48C14p
ATS 48C17p
ATS 48C21p
ATS 48C25p
ATS 48C32p
ATS 48C41p
ATS 48C48p
ATS 48C59p
ATS 48C11p
ATS 48C14p
ATS 48C17p
ATS 48C21p
ATS 48C25p
ATS 48C32p
ATS 48C41p
ATS 48C48p
ATS 48C59p
ATS 48C66p
220
250
355
700
800
ATS 48C66p
ATS 48C79p
ATS 48M10p
ATS 48C79p
ATS 48M10p
ATS 48M12p
Q1
GV2 L20
NS80H MA
GV2 L20
NS80H MA
GV2 L22
NS80H MA
GV2 L32
NS80H MA
GK3 EF40
NS80H MA
GK3 EF65
NS80H MA
GK3 EF65
NS80H MA
GK3 EF80
NS80H MA
NS100p MA (2)
NS160p MA (2)
NS160p MA (2)
NS250p MA (2)
NS250p MA (2)
NS400p MA (2)
NS400p MA (2)
NS630p MAE (2)
NS630p MAE (2)
NS630bp (2)
Micrologic 5.0
C801p (2)
STR35 ME
NS800p (2)
Micrologic 5.0
C801p (2)
STR35 ME
NS800p (2)
Micrologic 5.0
C801p (2)
STR35 ME
NS1000p (2)
Micrologic 5.0
C1001 p (2)
STR35 ME
NS1250p (2)
Micrologic 5.0
C1251 p (2)
STR35 ME
18
12.5
18
25
25
25
32
50
40
50
65
50
65
80
80
80
100
150
150
220
220
320
320
500
500
630
Size
LS1 D32
LS1 D32
LS1 D32
LS1 D32
LS1 D32
LS1 D32
GK1 EK
GK1 EK
GK1 EK
GK1 EK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GS1 L
GS1 N
GS1 N
GS1 QQ
GS1 QQ
GS1 S
GS1 S
GS1 S
DF2 CA16
DF2 CA16
DF2 CA16
DF2 CA16
DF2 CA25
DF2 CA25
DF2 EA32
DF2 EA32
DF2 EA40
DF2 EA40
DF2 FA50
DF2 FA50
DF2 FA80
DF2 FA80
DF2 FA80
DF2 FA80
DF2 FA100
DF2 FA125
DF2 GA1161
DF2 HA1201
DF2 HA1201
DF2 JA1251
DF2 JA1311
DF2 KA1401
DF2 KA1501
DF2 KA1631
DF3 EA32
DF3 EA32
DF3 EA40
DF3 EA40
DF3 FA50
DF3 FA50
DF3 FA80
DF3 FA80
DF3 FA80
DF3 FA80
DF3 FA100
DF4 FA125
DF4 GA1161
DF4 HA1201
DF4 HA1201
DF4 JA1251
DF4 JA1311
DF4 KA1401
DF4 KA1501
DF4 KA1631
10 x 38
10 x 38
10 x 38
10 x 38
10 x 38
10 x 38
14 x 51
14 x 51
14 x 51
14 x 51
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
0
1
1
2
2
3
3
3
16
16
16
16
25
25
32
32
40
40
50
50
80
80
80
80
100
125
160
200
200
250
315
400
500
630
800
LC1 F630
GS1 S
DF2 KA1631
DF4 KA1631
630
800
LC1 F800
GS1 S
DF2 KA1631
DF4 KA1631
630
800
LC1 F800
GS1 S
DF2 KA1631
DF4 KA1631
630
800
LC1 F800
GS1 V
DF2 LA1801
DF4 LA1801
800
800
LC1 F800
GS1 V
DF2 LA1801
DF4 LA1801
800
1000
LC1 BM33
GS1 V
DF2 LA1101
DF4 LA1101
1000
1000
LC1 BM33
GS1 V
DF2 LA1101
DF4 LA1101
1000
1250
LC1BP33
DF2 LA1251
DF4 LA1251
1250
1250
LC1BP33
DF2 LA1251
DF4 LA1251
1250
Presentation:
pages 1/30 and 1/31
1/60
Characteristics:
pages 1/32 to 1/35
Rating
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Icu (kA)
100
50
Icu (kA)
N
85
50
50
85
85
H
100
70
70
100
100
L
150
150
150
Schemes:
pages 1/54 to 1/59
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
pages 1/54 to 1/59) circuit-breakers, contactors, fast-acting fuses, starters
Combination: circuit-breaker, contactor, starter
Motor
Starter (1)
Class 10
Class 20
kW
A
Standard applications
Severe applications
M1
A1
3
11.5
ATS 48D17p
4
14.5
ATS 48D17p
5.5
20
ATS 48-D22p
7.5
27
ATS 48D32p
32
ATS 48D38p
11
39
ATS 48D47p
15
52
ATS 48D62p
18.5
64
ATS 48D75p
22
30
37
45
55
75
90
110
132
160
200
220
250
355
75
103
126
150
182
240
295
356
425
520
626
700
800
1115
ATS 48D88p
ATS 48C11p
ATS 48C14p
ATS 48C17p
ATS 48C21p
ATS 48C25p
ATS 48C32p
ATS 48C41p
ATS 48C48p
ATS 48C59p
ATS 48C66p
ATS 48C79p
ATS 48M10p
ATS 48M12p
Characteristics:
pages 1/32 to 1/35
Rating
A
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Type of contactor
Q1
KM1, KM2, KM3
GV2 L20
18
LC1 D40
NS80H MA
12.5
LC1 D40
ATS 48D22p
GV2 L20
18
LC1 D40
NS80H MA
25
LC1 D40
ATS 48D32p
GV2 L22
25
LC1 D40
NS80H MA
25
LC1 D40
ATS 48D38p
GV2 L32
32
LC1 D80
NS80H MA
50
LC1 D80
ATS 48D47p
GK3 EF40
40
LC1 D80
NS80H MA
50
LC1 D80
ATS 48D62p
GK3 EF65
65
LC1 D80
NS80H MA
50
LC1 D80
ATS 48D75p
GK3 EF65
65
LC1 D80
NS80H MA
80
LC1 D80
ATS 48D88p
GK3 EF80
80
LC1 D80
NS80H MA
80
LC1 D80
100
LC1 D115
ATS 48C11p
NS100 p MA (2)
ATS 48C14p
NS160 p MA (2)
150
LC1 D115
150
LC1 D150
ATS 48C17p
NS160 p MA (2)
220
LC1 F185
ATS 48C21p
NS250 p MA (2)
ATS 48C25p
NS250 p MA (2)
220
LC1 F225
320
LC1 F265
ATS 48C32p
NS400 p MA (2)
ATS 48C41p
NS400 p MA (2)
320
LC1 F330
500
LC1 F400
ATS 48C48p
NS630 p MAE (2)
500
LC1 F500
ATS 48C59p
NS630 p MAE (2)
ATS 48C66p
NS630bL Micrologic 5.0
630
LC1 F630
ATS 48C79p
NS800L Micrologic 5.0
800
LC1 F800
ATS 48M10p
NS800L Micrologic 5.0
800
LC1 F800
ATS 48M12p
NS1000L Micrologic 5.0
1000
LC1 BM33
1250
LC1 BP33
Presentation:
pages 1/30 and 1/31
Type of circuit-breaker
Telemecanique
Merlin Gerin
I2t
kA2.s
2.3
5.6
12
45
82
120
490
490
900
1200
1600
4100
Schemes:
pages 1/54 to 1/59
1/61
1.3
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
1.3
A1
11
7.5
ATS 48D22p
11
21
ATS 48D22p
ATS 48D32p
15
ATS 48D38p
ATS 48D17p
18.5 35
ATS 48D38p
ATS 48D47p
22
42
ATS 48D47p
ATS 48D62p
30
57
ATS 48D62p
ATS 48D75p
37
69
ATS 48D75p
ATS 48D88p
45
55
75
90
110
132
160
220
250
315
81
100
131
162
195
233
285
388
437
560
ATS 48D88p
ATS 48C11p
ATS 48C14p
ATS 48C17p
ATS 48C21p
ATS 48C25p
ATS 48C32p
ATS 48C41p
ATS 48C48p
ATS 48C59p
ATS48C11p
ATS 48C14p
ATS 48C17p
ATS 48C21p
ATS 48C25p
ATS 48C32p
ATS 48C41p
ATS 48C48p
ATS 48C59p
ATS 48C66p
355
400
500
630
605
675
855
ATS 48C66p
ATS 48C79p
ATS 48M10p
1045 ATS48M12p
ATS 48C79p
ATS 48M10p
ATS 48M12p
Q1
GV2 L20
NS80H MA
GV2 L20
NS80H MA
GV2 L22
NS80H MA
GV2 L32
NS80H MA
GK3 EF40
NS80H MA
GK3 EF65
NS80H MA
GK3 EF65
NS80H MA
GK3 EF80
NS80H MA
NS100p MA (2)
NS160p MA (2)
NS160p MA (2)
NS250p MA (2)
NS250p MA (2)
NS400p MA (2)
NS400p MA (2)
NS630p MAE (2)
NS630p MAE (2)
NS630bp (2)
Micrologic 5.0
C801p (2)
STR35ME
NS800p (2)
Micrologic 5.0
C801p (2)
STR35ME
NS800p (2)
Micrologic 5.0
C801p (2)
STR35ME
NS1000p (2)
Micrologic 5.0
C1001p (2)
STR35ME
NS1250p (2)
Micrologic 5.0
C1251p (2)
STR35ME
Presentation:
pages 1/30 and 1/31
1/62
Characteristics:
pages 1/32 to 1/35
18
12.5
18
25
25
25
32
50
40
50
65
50
65
80
80
80
100
150
150
220
220
320
320
500
500
630
LS1 D32
LS1 D32
LS1 D32
LS1 D32
LS1 D32
LS1 D32
GK1 EK
GK1 EK
GK1 EK
GK1 EK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GK1 FK
GS1 L
GS1 N
GS1 N
GS1 QQ
GS1 QQ
GS1 S
GS1 S
GS1 S
DF2 CA16
DF2 CA16
DF2 CA16
DF2 CA16
DF2 CA25
DF2 CA25
DF2 EA32
DF2 EA32
DF2 EA40
DF2 EA40
DF2 FA50
DF2 FA50
DF2 FA80
DF2 FA80
DF2 FA80
DF2 FA80
DF2 FA100
DF2 FA125
DF2 GA1161
DF2 HA1201
DF2 HA1201
DF2 JA1251
DF2 JA1311
DF2 KA1401
DF2 KA1501
DF2 KA1631
DF3 EA32
DF3 EA32
DF3 EA40
DF3 EA40
DF3 FA50
DF3 FA50
DF3 FA80
DF3 FA80
DF3 FA80
DF3 FA80
DF3 FA100
DF4 FA125
DF4 GA1161
DF4 HA1201
DF4 HA1201
DF4 JA1251
DF4 JA1311
DF4 KA1401
DF4 KA1501
DF4 KA1631
Size
Rating
A
10 x 38
10 x 38
10 x 38
10 x 38
10 x 38
10 x 38
14 x 51
14 x 51
14 x 51
14 x 51
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
22 x 58
0
1
1
2
2
3
3
3
16
16
16
16
25
25
32
32
40
40
50
50
80
80
80
80
100
125
160
200
200
250
315
400
500
630
800
LC1 F630
GS1 S
630
800
LC1 F800
GS1 V
DF2 LA1631
DF4 LA1631
630
800
LC1 F800
GS1 V
DF2 LA1631
DF4 LA1631
630
800
LC1 F800
GS1 V
DF2 LA1801
DF4 LA1801
800
800
LC1 F800
GS1 V
DF2 LA1801
DF4 LA1801
800
1000
LC1 BM33
GS1 V
DF2 LA1101
DF4 LA1101
1000
1000
LC1 BM33
GS1 V
DF2 LA1101
DF4 LA1101
1000
1250
LC1 BP33
DF2 LA1251
DF4 LA1251
1250
1250
LC1 BP33
DF2 LA1251
DF4 LA1251
1250
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
pages 1/54 to 1/59) circuit-breakers, contactors, fast-acting fuses, starters
Combination: circuit-breaker, contactor, starter
Motor
Starter (1)
Class 10
Class 20
kW
A
Standard applications
Severe applications
M1
A1
5.5
11
ATS 48D17p
Type of circuit-breaker
Telemecanique
Merlin Gerin
Rating
A
Q1
KM1, KM2, KM3
GV2 L20
18
LC1 D40
NS80H MA
12.5
LC1 D40
7.5
14.8
ATS 48D17p
ATS 48D22p
GV2 L20
18
LC1 D40
NS80H MA
25
LC1 D40
11
21
ATS 48D22p
ATS 48D32p
GV2 L22
25
LC1 D40
NS80H MA
25
LC1 D40
15
28.5
ATS 48D32p
ATS 48D38p
GV2 L32
32
LC1 D80
NS80H MA
50
LC1 D80
18.5
35
ATS 48D38p
ATS 48D47p
NS80H MA
50
LC1 D80
22
42
ATS 48D47p
ATS 48D62p
NS80H MA
50
LC1 D80
30
57
ATS 48D62p
ATS 48D75p
NS80H MA
80
LC1 D80
37
69
ATS 48D75p
ATS 48D88p
NS80H MA
80
LC1 D80
100
LC1 D115
45
81
ATS 48D88p
ATS 48C11p
NS100 p MA (2)
55
100
ATS 48C11p
ATS 48C14p
NS160 p MA (2)
150
LC1 D115
150
LC1 D150
75
131
ATS 48C14p
ATS 48C17p
NS160 p MA (2)
90
162
ATS 48C17p
ATS 48C21p
NS 250 p MA (2)
220
LC1 F185
220
LC1 F225
110
195
ATS 48C21p
ATS 48C25p
NS 250 p MA (2)
132
233
ATS 48C25p
ATS 48C32p
NS400 p MA (2)
320
LC1 F265
320
LC1 F330
160
285
ATS 48C32p
ATS 48C41p
NS400 p MA (2)
500
LC1 F500
220
388
ATS 48C41p
ATS 48C48p
NS630 p MAE (2)
250
437
ATS 48C48p
ATS 48C59p
NS630 p MAE (2)
500
LC1 F500
315
560
ATS 48C59p
ATS 48C66p
NS630bL Micrologic 5.0
630
LC1 F630
355
605
ATS48C66p
ATS48C79p
NS800L Micrologic 5.0
800
LC1 F800
400
675
ATS48C79p
ATS48M10p
NS800L Micrologic 5.0
800
LC1 F800
500
855
ATS48M10p
ATS48M12p
NS1000L Micrologic 5.0
1000
LC1 BM33
1250
LC1 BP33
630
1045
ATS48M12p
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Type of contactor
Schemes:
pages 1/54 to 1/59
1/63
1.3
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
1.3
A1
10.4
ATS 48D17Y
7.5
ATS 48D22Y
11
ATS 48D32Y
15
ATS 48D38Y
ATS 48D47Y
22
39
ATS 48D47Y
ATS 48D62Y
30
37
45
55
75
90
110
132
160
220
250
355
52
64
76
90
125
150
178
215
256
353
401
549
ATS 48D62Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48C66Y
400
611
ATS 48C66Y
ATS 48C79Y
500
780
ATS 48C79Y
ATS 48M10Y
630
710
965
ATS 48M10Y
ATS 48M12Y
Q1
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS80H MA
NS80H MA
NS100p MA (1)
NS100p MA (1)
NS160p MA (1)
NS250p MA (1)
NS250p MA (1)
NS250p MA (1)
NS400p MA (1)
NS630p MAE (1)
NS630p MAE (1)
NS630bp (1)
Micrologic 5.0
NS630bp (1)
Micrologic 5.0
NS800p (1)
Micrologic 5.0
C801p (1)
STR35ME
NS1000p (1)
Micrologic 5.0
C1001L
STR35ME
NS1250p (1)
Micrologic 5.0
C1251p (1)
STR35ME
Presentation:
pages 1/30 and 1/31
1/64
Characteristics:
pages 1/32 to 1/35
12.5
Size
Rating
A
DF2 CA16
10 x 38
16
25
LC1 D18
LS1 D32
DF2 CA16
10 x 38
16
25
LC1 D25
GK1 EK
DF2 EA25
DF3 EA25
14 x 51
25
50
LC1 D32
GK1 EK
DF2 EA32
DF3 EA32
14 x 51
32
50
LC1 D40
GK1 EK
DF2 EA40
DF3 EA40
14 x 51
40
50
LC1 D40
GK1 FK
DF2 FA50
DF3 FA50
22 x 58
50
80
80
100
100
150
220
220
220
320
500
500
630
LC1 D65
LC1 D65
LC1 D115
LC1 D115
LC1 D150
LC1 F185
LC1 F225
LC1 F265
LC1 F265
LC1 F400
LC1 F400
LC1 F630
GK1 FK
GK1 FK
GK1 FK
GS1 L
GS1 L
GS1 N
GS1 N
GS1 QQ
GS1 QQ
GS1 S
GS1 S
GS1 V
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF3 FA80
DF3 FA80
DF3 FA100
DF4 GA1121
DF4 GA1161
DF4 HA1201
DF4 HA1251
DF4 JA1311
DF4 JA1401
DF4 KA1501
DF4 KA1501
DF4 LA1801
22 x 58
22 x 58
22 x 58
0
1
1
1
2
2
3
3
4
80
80
100
125
160
200
250
315
315
500
500
800
630
LC1 F630
GS1 V
800
800
LC1 BM33
GS1 V
800
800
LC1 BM33
GS1 V
800
1000
LC1 BP33
GS1 V
1000
1000
LC1 BP33
GS1 V
1000
1250
LC1 BP33
DF2 LA1251
1250
1250
LC1 BP33
DF2 LA1251
1250
FA80
FA80
FA100
GA1121
GA1161
HA1201
HA1251
JA1311
JA1401
KA1501
KA1501
LA1801
(1) Replace p with N, H or L, according to the breaking capacity (see table below).
(2) DF2 CA, DF p EA, DFp FA: sold in lots of 20.
DF p GA, DF p KA: sold in lots of 3.
DF p LA: sold in lots of 1.
Breaking capacity of circuit-breakers according to standard IEC 60947-2
440 V
Icu (kA)
GV2 L20, GV2 L22, GV2 L32
20
GK3 EF40
30
GK3 EF65, GK3 EF80
25
NS80
65
440 V
Icu (kA)
N
H
L
NS100
25
65
130
NS160, NS250
35
65
130
NS400, NS630
42
65
130
NS800, NS1000
50
65
130
NS1250
50
65
C801, C1001
42
65
150
C1251
42
65
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
pages 1/54 to 1/59) circuit-breakers, contactors, fast-acting fuses, starters
Combination: circuit-breaker, contactor, starter
Motor
Starter
Class 10
Class 20
kW
A
Standard applications
Severe applications
M1
A1
5.5
10.4
ATS 48D17Y
Type of circuit-breaker
Telemecanique
Merlin Gerin
Rating
A
Q1
KM1, KM2, KM3
NS80H MA
12.5
LC1 D40
12.5
LC1 D80
NS100 p MA (1)
7.5
13.7
ATS 48D17Y
ATS 48D22Y
NS80H MA
25
LC1 D40
25
LC1 D80
NS100 p MA (1)
11
20.1
ATS 48D22Y
ATS 48D32Y
NS80H-MA
25
LC1 D40
25
LC1 D80
NS100 p MA (1)
50
LC1 D80
15
26.5
ATS 48D32Y
ATS 48D38Y
NS100 p MA (1) NS80H MA
50
LC1 D80
18.5
32.8
ATS 48D38Y
ATS 48D47Y
NS100 p MA (1) NS80H MA
22
39
ATS 48D47Y
ATS 48D62Y
NS100 p MA (1) NS80H MA
50
LC1 D80
100
LC1 D80
30
52
ATS 48D62Y
ATS 48D75Y
NS100 p MA (1)
NS80H MA
80
LC1 D80
100
LC1 D80
37
64
ATS 48D75Y
ATS 48D88Y
NS100 p MA (1)
NS80H MA
80
LC1 D80
100
LC1 D115
45
76
ATS 48D88Y
ATS 48C11Y
NS100 p MA (1)
100
LC1 D115
55
90
ATS 48C11Y
ATS 48C14Y
NS100 p MA (1)
75
125
ATS 48C14Y
ATS 48C17Y
NS160 p MA (1)
150
LC1 D150
150
LC1 D150
90
150
ATS 48C17Y
ATS 48C21Y
NS160 p MA (1)
110
178
ATS 48C21Y
ATS 48C25Y
NS250 p MA (1)
220
LC1 F185
320
LC1 F265
132
215
ATS 48C25Y
ATS 48C32Y
NS400 p MA (1)
320
LC1 F265
160
256
ATS 48C32Y
ATS 48C41Y
NS400 p MA (1)
220
353
ATS 48C41Y
ATS 48C48Y
NS630 p MAE (1)
500
LC1 F400
500
LC1 F500
250
401
ATS 48C48Y
ATS 48C59Y
NS630 p MAE (1)
355
549
ATS 48C59Y
ATS 48C66Y
NS630bL Micrologic 5.0
630
LC1 F630
400
611
ATS 48C66Y
ATS 48C79Y
NS800L Micrologic 5.0
800
LC1 F800
500
780
ATS 48C79Y
ATS 48M10Y
NS800L Micrologic 5.0
800
LC1 F800
630
965
ATS 48M10Y
ATS 48M12Y
NS1000L Micrologic 5.0
1000
LC1 BP33
1250
LC1 BP33
710
1075
ATS 48M12Y
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Type of contactor
Schemes:
pages 1/54 to 1/59
1/65
1.3
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
1.3
12
A1
ATS 48D17Y
14
ATS 48D17Y
ATS 48D22Y
11
ATS 48D32Y
ATS 48D38Y
22
33
ATS 48D38Y
ATS 48D47Y
30
45
ATS 48D47Y
ATS 48D62Y
37
45
55
75
90
110
132
160
220
250
315
400
55
65
80
105
130
156
207
257
310
360
460
540
ATS 48D62Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48C66Y
450
630
ATS 48C66Y
ATS 48C79Y
500
680
ATS 48C79Y
ATS 48M10Y
630
800
850
ATS 48M10Y
ATS 48M12Y
Q1
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS100p MA (1)
NS100p MA (1)
NS160p MA (1)
NS160p MA (1)
NS250p MA (1)
NS250p MA (1)
NS400p MA (1)
NS630p MAE (1)
NS630p MAE (1)
NS630p MAE (1)
NS630bp (1)
Micrologic 5.0
NS630bp (1)
Micrologic 5.0
NS800p MA (1)
Micrologic 5.0
C1001p (1)
STR35 ME
NS1000p (1)
Micrologic 5.0
C1001p (1)
STR35 ME
NS1250p (1)
Micrologic 5.0
C1251p (1)
STR35 ME
12.5
Size
Rating
A
DF2 CA16
10 x 38
16
25
LC1 D18
LS1 D32
DF2 CA16
10 x 38
16
25
LC1 D25
GK1 EK
DF2 EA25
DF3 EA25
14 x 51
25
50
LC1 D32
GK1 EK
DF2 EA32
DF3 EA32
14 x 51
32
50
LC1 D40
GK1 EK
DF2 EA40
DF3 EA40
14 x 51
40
50
LC1 D50
GK1 FK
DF2 FA50
DF3 FA50
22 x 58
50
100
100
100
150
150
220
220
320
500
500
500
630
LC1 D65
LC1 D80
LC1 D80
LC1 D115
LC1 D150
LC1 F185
LC1 F265
LC1 F265
LC1 F400
LC1 F400
LC1 F500
LC1 F630
GK1 FK
GK1 FK
GK1 FK
GS1 L
GS1 L
GS1 N
GS1 N
GS1 QQ
GS1 QQ
GS1 S
GS1 S
GS1 V
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF2
DF3 FA80
DF3 FA80
DF3 FA100
DF4 GA1121
DF4 GA1161
DF4 HA1201
DF4 HA1251
DF4 JA1311
DF4 JA1401
DF4 KA1501
DF4 KA1631
DF4 LA1801
22 x 58
22 x 58
22 x 58
0
0
1
1
2
2
3
3
4
80
80
100
125
160
200
250
315
400
500
630
800
630
LC1 F800
GS1 V
800
800
LC1 BL33
GS1 V
800
1000
LC1 BL33
GS1 V
800
1000
LC1 BP33
GS1 V
1000
1000
LC1 BP33
GS1 V
1000
1250
LC1 BP33
DF2 LA1251
1250
1250
LC1 BP33
DF2 LA1251
1250
FA80
FA80
FA100
GA1121
GA1161
HA1201
HA1251
JA1311
JA1401
KA1501
KA1631
LA1801
(1) Replace p with N, H or L, according to the breaking capacity (see table below).
(2) DF2 CA, DF p EA, DFp FA: sold in lots of 20.
DF p GA, DF p KA: sold in lots of 3.
DF p LA: sold singly.
Breaking capacity of circuit-breakers according to standard IEC 60947-2
500 V
Icu (kA)
GV2 L20, GV2 L22, GV2 L32
10
GK3 EF40
20
GK3 EF65, GK3 EF80
15
NS80
25
500 V
Icu (kA)
N
H
L
NS100
18
50
100
NS160, NS250, NS630
30
50
70
NS400
30
50
100
NS800, NS1000, C801, C1001
40
50
100
NS1250, C1251
40
50
Presentation:
pages 1/30 and 1/31
1/66
Characteristics:
pages 1/32 to 1/35
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Schemes:
pages 1/54 to 1/59
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
pages 1/54 to 1/59) circuit-breakers, contactors, fast-acting fuses, starters
Combination: circuit-breaker, contactor, starter
Motor
Starter
Class 10
Class 20
kW
A
Standard applications
Severe applications
M1
A1
7.5
12
ATS 48D17Y
9
14
ATS 48D17Y
11
18.4
ATS 48D22Y
18.5
22
30
37
45
55
75
90
110
132
160
220
250
315
400
450
500
630
800
28.5
33
45
55
65
80
105
130
156
207
257
310
360
460
540
630
680
850
1100
ATS 48D32Y
ATS 48D38Y
ATS 48D47Y
ATS 48D62Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
ATS 48C66Y
ATS 48C79Y
ATS 48M10Y
ATS 48M12Y
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
Type of circuit-breaker
Telemecanique
Merlin Gerin
Rating
A
Q1
KM1, KM2, KM3
NS80H MA
12.5
LC1 D40
12.5
LC1 D80
NS100 p MA (1)
ATS 48D22Y
NS80H MA
25
LC1 D40
25
LC1 D80
NS100 p MA (1)
ATS 48D32Y
NS80H MA
25
LC1 D40
25
LC1 D80
NS100 p MA (1)
50
LC1 D80
ATS 48D38Y
NS100 p MA (1) NS80H MA
50
LC1 D80
ATS 48D47Y
NS100 p MA (1) NS80H MA
ATS 48D62Y
NS100 p MA (1) NS80H MA
50
LC1 D80
100
LC1 D80
ATS 48D75Y
NS100 p MA (1)
ATS 48D88Y
NS100 p MA (1)
100
LC1 D80
100
LC1 D115
ATS 48C11Y
NS100 p MA (1)
150
LC1 D115
ATS 48C14Y
NS160 p MA (1)
ATS 48C17Y
NS160 p MA (1)
150
LC1 D150
220
LC1 F185
ATS 48C21Y
NS250 p MA (1)
ATS 48C25Y
NS250 p MA (1)
220
LC1 F265
320
LC1 F400
ATS 48C32Y
NS400 p MA (1)
ATS 48C41Y
NS400 p MA (1)
320
LC1 F400
500
LC1 F500
ATS 48C48Y
NS630 p MAE (1)
500
LC1 F500
ATS 48C59Y
NS630 p MAE (1)
ATS 48C66Y
NS630bL Micrologic 5.0
630
LC1 F630
ATS 48C79Y
NS630bL Micrologic 5.0
630
LC1 F800
ATS 48M10Y
NS800L Micrologic 5.0
800
LC1 BL33
ATS 48M12Y
NS1000L Micrologic 5.0
1000
LC1 BP33
1250
LC1 BP33
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Type of contactor
Schemes:
pages 1/54 to 1/59
1/67
1.3
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
1.3
A1
12.1
ATS 48D17Y
15
ATS 48D22Y
ATS 48D32Y
22
ATS 48D38Y
30
33
ATS 48D38Y
ATS 48D47Y
37
40
ATS 48D47Y
ATS 48D62Y
45
55
75
90
110
160
200
250
315
400
500
49
58
75.5
94
113
165
203
253
321
390
490
ATS 48D62Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48D75Y
ATS 48D88Y
ATS 48C11Y
ATS 48C14Y
ATS 48C17Y
ATS 48C21Y
ATS 48C25Y
ATS 48C32Y
ATS 48C41Y
ATS 48C48Y
ATS 48C59Y
560
630
710
900
950
549
605
694
880
ATS 48C59Y
ATS 48C66Y
ATS 48C79Y
ATS 48M10Y
ATS 48C66Y
ATS 48C79Y
ATS 48M10Y
ATS 48M12Y
Q1
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS80H MA
NS100p MA (1)
NS100p MA (1)
NS100p MA (1)
NS160p MA (1)
NS160p MA (1)
NS250p MA (1)
NS400p MA (1)
NS400p MA (1)
NS630p MAE (1)
NS630p MAE (1)
NS630bp (1)
Micrologic 5.0
C801p (1)
STR35 ME
NS630bp (1)
Micrologic 5.0
C801p (1)
STR35 ME
NS800p (1)
Micrologic 5.0
C801p (1)
STR35 ME
NS800p (1)
Micrologic 5.0
C801p (1)
STR35 ME
NS1000p (1)
Micrologic 5.0
C1001L
STR35 ME
NS1250p (1)
Micrologic 5.0
C1251p (1)
STR35 ME
12.5
12.5
25
25
50
50
50
50
50
50
50
50
100
100
100
150
150
220
320
320
500
500
630
1/68
Characteristics:
pages 1/32 to 1/35
Rating
A
DF2 FA16
DF3 FA16
22 x 58
16
LC1 D25
GK1 FK
DF2 FA20
DF3 FA20
22 x 58
20
LC1 D32
GK1 FK
DF2 FA25
DF3 FA25
22 x 58
25
LC1 D40
GK1 FK
DF2 FA32
DF3 FA32
22 x 58
32
LC1 D40
GK1 FK
DF2 FA40
DF3 FA40
22 x 58
40
LC1 D65
GK1 FK
DF2 FA50
DF3 FA50
22 x 58
50
LC1 D80
LC1D-115
LC1D-115
LC1D-150
LC1D-150
LC1F-265
LC1F-330
LC1F-400
LC1F-500
LC1 F630
LC1 BL33
800
LC1 BL33
630
LC1 BL33
800
LC1 BL33
800
LC1 BP33
800
LC1 BP33
800
LC1 BP33
800
LC1 BP33
1000
LC1 BR33
1000
LC1 BR33
1250
LC1 BR33
1250
LC1 BR33
(1) Replace p with N, H or L, according to the breaking capacity (see table below).
(2) DF p FA: sold in lots of 10.
Breaking capacity of circuit-breakers according to standard IEC 60947-2
690 V
GV2 L20, GV2 L22, GV2 L32
GK3 EF40, GK3 EF65, GK3 EF80, NS80
690 V
NS100
NS160, NS250
NS400
NS630
NS800, NS1000
NS1250
C801, C1001
C1251
Presentation:
pages 1/30 and 1/31
Size
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Icu (kA)
4
6
Icu (kA)
N
8
8
10
10
30
30
25
25
H
10
10
20
20
42
42
40
40
L
75
20
75
35
25
60
Schemes:
pages 1/54 to 1/59
Combinations (continued)
Soft starters
for asynchronous motors
Components for use together in accordance with standards IEC 60947-4-1 and IEC 60947-4-2 (see schemes on
pages 1/54 to 1/59) circuit-breakers, contactors, fast-acting fuses, starters
Combination: circuit-breaker, contactor, starter
Motor
Starter
Class 10
kW
A
Standard applications
M1
A1
11
12.1
15
16.5
ATS 48D17Y
18.5
20.2
ATS 48D22Y
22
24.2
ATS 48D32Y
30
33
ATS 48D38Y
37
40
ATS 48D47Y
45
49
ATS 48D62Y
55
58
ATS 48D75Y
75
75.5
ATS 48D88Y
90
94
ATS 48C11Y
110
113
ATS 48C14Y
160
165
ATS 48C17Y
200
203
ATS 48C21Y
250
253
ATS 48C25Y
315
321
ATS 48C32Y
400
390
ATS 48C41Y
500
490
ATS 48C48Y
560
549
ATS 48C59Y
630
605
ATS 48C66Y
710
694
ATS 48C79Y
900
880
ATS 48M10Y
950
1000
ATS 48M12Y
Presentation:
pages 1/30 and 1/31
Characteristics:
pages 1/32 to 1/35
Class 20
Severe applications
Type of circuit-breaker
Telemecanique
Merlin Gerin
Rating
A
Q1
KM1, KM2, KM3
12.5
LC1 D80
ATS 48D17Y
NS100 p MA (1)
ATS 48D22Y
NS100 p MA (1)
25
LC1 D80
50
LC1 D80
ATS 48D32Y
NS100 p MA (1)
ATS 48D38Y
NS100 p MA (1)
50
LC1 D80
50
LC1 D80
ATS 48D47Y
NS100 p MA (1)
ATS 48D62Y
NS100 p MA (1)
50
LC1 D80
100
LC1 D115
ATS 48D75Y
NS100 p MA (1)
100
LC1 D115
ATS 48D88Y
NS100 p MA (1)
ATS 48C11Y
NS100 p MA (1)
100
LC1 D115
320
LC1 F265
ATS 48C14Y
NS400 p MA (1)
ATS 48C17Y
NS400 p MA (1)
320
LC1 F265
320
LC1 F265
ATS 48C21Y
NS 400 p MA (1)
320
LC1 F400
ATS 48C25Y
NS400 p MA (1)
ATS 48C32Y
NS400 p MA (1)
320
LC1 F500
500
LC1 F500
ATS 48C41Y
NS630 p MAE (1)
ATS 48C48Y
NS630 p MAE (1)
500
LC1 F630
ATS 48C59Y
NS630bL Micrologic 5.0
630
LC1 BL33
ATS 48C66Y
NS630bL Micrologic 5.0
630
LC1 BL33
ATS 48C79Y
NS800L Micrologic 5.0
800
LC1 BP33
ATS 48M10Y
NS800L Micrologic 5.0
800
LC1 BP33
ATS 48M12Y
NS1000L Micrologic 5.0
1000
LC1 BR33
1250
LC1 BR33
References:
pages 1/40 to 1/43
Dimensions:
pages 1/48 to 1/53
Type of contactor
Schemes:
pages 1/54 to 1/59
1/69
1.3
Functions
Soft starters
Summary of functions
1.3
See page
1/70
See pages
1/71
1/71
1/71
1/71
1/71
See pages
1/72
1/72
1/72
1/72
1/73
1/73
1/73
1/73
1/73
1/73
1/73
See pages
1/74
1/74
1/74
1/74
1/74
1/74
1/74
1/74
1/75
1/75
1/75
1/75
See pages
1/76
1/76
1/76
1/76
1/76
1/76
1/76
1/76
1/76
1/77
1/77
1/77
1/70
The starter is supplied ready for use in most applications. The main functions
enabled and the default function values are as follows:
- nominal motor current (depends on the starter rating),
- limiting current: 400%,
- acceleration ramp time: 15 s,
- initial starting torque: 20%,
- selection of the type of stop: freewheel stop,
- motor thermal protection: class 10,
- time before restarting: 2 s,
- motor phase loss threshold: 10%,
- line frequency: automatic,
- RUN and STOP logic inputs: 2-wire or 3-wire control via wiring,
- logic input LI3: forced freewheel stop,
- logic input LI4: local mode control (serial link disabled),
- logic output LO1: thermal motor alarm,
- logic output LO2: motor powered,
- relay output R1: fault relay,
- relay output R3: motor powered,
- analogue output: motor current.
Functions (continued)
Soft starters
Adjustment functions
b Nominal motor current (maximum permanent current)
The nominal current of the starter can be adapted to the nominal motor current
indicated on the rating plate.
Adjustment range: 0.4 to 1.3 times the starter nominal current.
b Limiting current
The maximum starting current can be adjusted.
Adjustment range: 150% to 700% of the nominal motor current set and limited to
500% of the maximum permanent current defined for the starter rating.
b Acceleration ramp time
During the starting phase, the Altistart 48 applies a torque ramp to the motor. The
time (ACC) set corresponds to the time taken by the ramp to reach the nominal
torque (starting at 0). Adjustment range: 1 to 60 s.
% Cn
100
80
60
tq0 = 40
40
20
0
0
ACC
% Cn
100
80
End
deceleration
Fin of
decontrolled
dclration
controle
60
EdC
40
20
0
dEC
Decelerated stop by torque control during time dEC with
threshold Edc for changing to freewheel stop mode
Edc = 40% of nominal motor torque
100 %
brc = 20
brc = 100
20 %
0
T1
T2
1/71
1.3
Functions
(continued)
Soft starters
Protection functions
t(s)
10000
The Altistart 48 offers functions for protecting the motor and the machine.
1
1000
100
1.3
Class
30
25
20
15
10
10
10 A
1
0,5
1,12
2,00
3,00
4,00
5,00
6,00
7,00
Id/In
8,00
t(s)
10000
100
Class
10
30
25
20
15
10
10 A
2,00
3,00
4,00
5,00
1/72
1000
0,5
1,12
6,00
7,00
2 Id/In
8,00
b Starter ventilation
The cooling fan on the starter is switched on as soon as the heatsink temperature
reaches 50 C. It is switched off when the temperature returns to 40 C.
b Starter thermal protection
The starter is protected against thermal overloads by an analogue thermal probe.
Functions (continued)
Soft starters
C
(Cn) 100 %
LUL + 10 %
LUL
t < tUL
tUL
20 %
ULL t
I
300 %
LOC
LOC -10 %
50 %
t < tOL
tOL
t
OIL
1/73
1.3
Functions
(continued)
Soft starters
C
100 %
Un
Cd
Torque ramp
1.3
50 %
Un
100 ms
1/74
Functions (continued)
Soft starters
Communication functions
The Altistart 48 is supplied with an RS 485 multidrop serial link with Modbus protocol
as standard. The serial link is configured in the Communication menu using:
v the address of the starter, which can be set between 0 and 31,
v the communication speed, which can be set at: 4800, 9600 or 19200 bps,
v the format of the communication data. The following formats can be selected:
- 8 data bits, odd parity, 1 stop bit,
- 8 data bits, even parity, 1 stop bit,
- 8 data bits, no parity, 1 stop bit,
- 8 data bits, no parity, 2 stop bits.
v the time-out, which can be set between 1 and 60 s.
1/75
1.3
Functions
(continued)
Soft starters
1.3
b 2 logic inputs (RUN and STOP) are reserved for run/stop commands which
can be sent in the form of stay-put contacts or as pulsed contacts.
v 2-wire control: starting and stopping are controlled by a single logic input. State
1 of the logic input controls starting and state 0 controls stopping.
v 3-wire control: starting and stopping are controlled by 2 separate logic inputs.
A stop is obtained on opening (state 0) the STOP input.
The pulse on the RUN input is stored until the stop input opens.
1/76
b 2 logic inputs (LI3 and LI4) can be configured with the following functions:
v Freewheel stop: when combined with a braked stop or decelerated stop
command, activating the logic input will stop the motor in freewheel mode.
v External fault: enables the starter to detect an external user fault (level, pressure,
etc). When the contact is open, the starter changes to fault mode.
v Motor preheating: used to prevent the motor from freezing or to prevent
temperature variations which may cause condensation. When the logic input is
activated, an adjustable current flows through the motor after a time delay which can
be set between 0 and 999 s. This current heats the motor without causing it to rotate.
This function is not compatible with the following functions: connection to the motor
delta terminal and cascading.
v Force to local control mode: if a serial link is used, this function can be used to
change from line mode (control via serial link) to local mode (control via the terminal).
v Inhibit all protection: enables the forced operation of the starter in an emergency
by overriding the main faults (smoke extraction system for example).
Warning: this type of use invalidates the starter warranty.
v Reset motor thermal fault: enables the fault to be reset remotely.
v Activation of the cascade function: in this case, the motor thermal protection is
disabled and relay R1 is configured as the fault isolation relay. Can be used to start
and decelerate several motors one after the other with a single starter (see
application diagram on pages 1/58 and 1/59).
v Reset all faults: enables all faults to be reset remotely.
v Second set of motor parameters: enables a second set of parameters to be
selected to start and decelerate two different motors with a single starter.
Functions (continued)
Soft starters
Decelerating
stop
Dynamic
braking stop
Forced
freewheel
stop
Decelerating stop
Dynamic braking
stop
Forced freewheel
stop
Thermal protection
Motor phase loss
detection
Connection to the
motor delta terminal
Tests on low power
motor
Cascaded motors
Motor preheating
Thermal
protection
(1)
Cascaded
motors
Motor
preheating
(1)
(1)
(1)
(2)
(1)
Compatible functions
Incompatible functions
Not applicable
(1) Motor phase loss not detected.
(2) Thermal protection is not provided during motor preheating.
1/77
1.3
Curves
Soft starters
Conventional starting
of three-phase asynchronous motors
Direct starting
I/In
C/Cn
2,5
1,5
0,5
Cr
1.3
N/Ns
Starting current
b
v
v
v
v
v
Characteristics:
motor with 3 terminals, low and medium power,
on-load starting,
high current peak and voltage drop,
simple device,
sudden starting for the mechanism.
b No parameter adjustment.
0
N/Ns
Starting torque
"Star-delta" starting
2,5
1,5
0,5
N/Ns
0
C/Cn
3
I/In
6
0,25 0,5
0,75
Starting current
Cr
b
v
v
v
v
v
Characteristics:
motor with 6 terminals,
no-load or low resistive torque starting,
high current peaks and torque when changing to "star-delta" mode,
a device requiring maintenance,
subject to mechanical stress when starting.
b No parameter adjustment.
0
0,25
0,5 0,75
N/Ns
Starting torque
2,5
1,5
0,5
C/Cn
3
I/In
6
0,25 0,5
0,75
N/Ns
Starting current
Cr
b
v
v
v
v
v
Characteristics:
motor with 3 terminals, high power,
starting with increasing resistive torque,
high current peak,
a large, bulky device requiring maintenance,
subject to mechanical stress when starting.
b No parameter adjustment.
0
0,25
0,5 0,75
N/Ns
Starting torque
C/Cn
I/In
3
2,5
1,5
0,5
0
0
Starting current
1/78
N/Ns
Characteristics:
motor with 3 terminals, high power,
large voltage drop and current peak when connected at full voltage,
a complex, bulky device requiring maintenance,
subject to mechanical stress when starting.
Cr
b No parameter adjustment.
0
0
0,25 0,5
0,75
Starting torque
N/Ns
Curves (continued)
Soft starters
Progressive starting
of three-phase asynchronous motors
v Depending on the firing time and angle of the thyristors, it can be used to supply
a voltage which will gradually increase at a fixed frequency.
v The gradual increase in the output voltage can either be controlled by the
acceleration ramp, or by the value of the limiting current, or linked to both
parameters.
Schematic diagram
1.3
Firing angle
b Figure 1 shows the behaviour of the torque in relation to the starting current.
b Limiting the starting current Is to a preset value Is1 will reduce the starting torque
Ts1 to a value which is almost equal to the ratio of the square of currents Is and Is1.
Example
On a motor with the following characteristics: Ts = 2 Tn for Is = 6In, current limiting
at Is1= 3 In or 0.5 Is results in a starting torque: Ts1 = Ts x (0.5)2 = 2 Tn x 0.25 = 0.5 Tn.
Id
Id1
Cd
Cr
Cd1
0
N/Ns
0
0.25 0.5
0.75
Figure 1
U
0.85 U
Cr
0.6 U
N/Ns
0
0.25
0.5
0.75
Figure 2
1/79