Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Part 7
Control
1. Option List of Controllers.....................................................................561
2. DAIKIN Building Air Conditioning Control System (D-BACS) .............562
2.1
2.2
2.3
2.4
3. Control System....................................................................................568
3.1
3.2
3.3
3.4
3.5
3.6
4. Control Devices...................................................................................590
4.1
4.2
4.3
4.4
4.5
4.6
5. Adaptor................................................................................................677
5.1 <DCS302A52> Unification Adaptor for Computerized Control.............677
5.2 <KRP2A61 / KRP2A62 / KRP2A53>
Wiring Adaptor for Electrical Appendices (1)........................................681
5.3 <KRP4A51 / KRP4A52 / KRP4A53 / KRP4A54>
Wiring Adaptor for Electrical Appendices (2)........................................688
5.4 <DTA102A52> Interface Adaptor for SkyAir Series .............................694
5.5 <DTA107A55> Central Control Adaptor Kit..........................................697
5.6 <DTA103A51> Wiring Adaptor for Other Air Conditioners ...................701
5.7 <DTA104A61 / DTA104A62 / DTA104A53> External Control Adaptor for
Outdoor Unit (Must be Installed on Indoor Units) ................................705
5.8 <KRP1B61 / KRP1B56 / KRP1B59> Adaptor for Wiring......................711
5.9 <KRP1C3> Adaptor for Wiring .............................................................713
5.10 <KRCS01-1> Remote Sensor ..............................................................714
5.11 <DTA109A51> DIII NET Expander Adaptor.........................................715
Control
559
16
ED34-762
560
Control
ED34-762
Type
Item
Wireless
C/O
FXCQ-M
FXFQ-M
BRC7C67
BRC7E65
FXDQ-P
FXKQ-MA FXDQ-N(A)
FXUQ-MA
BRC4C63
BRC4C64
FXSQ-M
BRC7C529W
BRC4C64
Remote
controller
Simplified remote
controller
KRP1B61
KRP1B59
KRP1B61
6-1
KRP2A61
KRP2A62
6-2
KRP4A51
KRP4A53
Remote sensor
KRCS01-1
Note 2, 3
KRP1B96
Note 2, 3
KRP1D98
9-1
KJB311A
10
DCS301BA61
10-1
KJB212A
10-2
KEK26-1
Wired
11
Schedule timer
12
13
FXMQ-MA
FXHQ-MA
FXAQ-MA
FXLQ-MA
FXNQ-MA
BRC7E66
BRC7E619
BRC4C64
BRC1C62
BRC1D61
Note 8
BRC2C51
Note 8
BRC2C51
BRC3A61
BRC3A61
KRP1B56
KRP1B61
KRP1C3
KRP1B61
KRP2A61
KRP2A53
KRP2A62
KRP2A61
KRP2A62
KRP2A61
KRP2A61
KRP4A51
KRP4A54
KRP4A53
KRP4A51
KRP4A52
KRP4A51
KRP4A51
Note 3
KRP1C93
Note 2, 3
KRP4A93
DTA104A62
DTA104A61
DTA104A61
Note 8
BRC2C51
BRC3A61
KRCS01-1
Note 4, 6
KRP1B101
KRP1B97
Note 5
KRP4A91
DCS302CA61
DST301BA61
DTA104A61
DTA104A62
DTA104A61
DTA104A53
Note 7
DTA102A52
DTA104A61
Note:
1. Installation box (No.8) is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box (No. 8) is necessary for second adaptor.
6. Installation box (No. 8) is necessary for each adaptor.
7. This adaptor is required when connecting with optional controller for centralized control.
8. BRC2A51 is also available.
Various PC Boards
No.
Part name
Model No.
KRP1B56
KRP1B57
KRP1B59
KRP1B61
KRP1C3
DTA109A51
Function
PC board when equipped with auxiliary electric heater in the indoor unit.
Up to 1,024 units can be centrally controlled in 64 different groups.
Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of
branches: 16) apply to each adaptor.
16
Control
561
ED34-762
Independent
and centralized
control of HRV
is possible.
Connectable number of
centralized control
equipment
Central remote
contoroller
2 units
Unified ON /OFF
8 units
contoroller
Schedule timer
1 unit
Forced
shut-down
input
Central control
adaptor kit
(DTA107A55).
Central remote
controller
(DCS302CA61)
Wiring adaptor
for other airconditioners
(DTA103A51)
Outdoor-air
processing
unit can be
connected.
Up to 2 units
connectable
6 cores
Schedule timer (DST301BA61)
1 unit connection possible ;
8 weekly schedule control patterns possible
No.
Part Name
7 cores max.
Model No.
Function
Central Remote
Controller
DCS302CA61
Up to 64 groups of indoor units (128 units) can be connected, and on/off, temperature
setting and monitoring can be accomplished individually or simultaneously. Connectable up
to 2 sets into one system.
Unified ON/OFF
Controller
DCS301BA61
Schedule Timer
DST301BA61
Programmed time weekly schedule can be controlled by unified control for up to 64 groups
of indoor units (128 units). Can turn units on/off twice per day.
Used to combine host computer monitor panel and central remote controller (on/off,
display).
DTA102A52
Used to connect SkyAir series with optional controllers for centralized control.
DTA103A51
Used to connect with other air-conditioners other than VRV system or SkyAir series with
optional controllers for centralized control.
Note:
Installation box for adaptor must be procured on site.
562
Control
ED34-762
2.2
intelligent Touch
Controller
(DCS601C51)
Independent
and centralized
control of HRV
is possible.
Up to 2 units
connectable
Forced OFF
input
System without remote control is also available.
Wiring adaptor
for other airconditioners
(DTA103A51)
Central control
adaptor kit
(DTA107A55).
Outdoor-air
processing
unit can be
connected.
6 cores
No.
1
Part Name
intelligent Touch
Controller
Control
7 cores max.
Model No.
DCS601C51
Function
Up to 64 groups of indoor units (128 units) can be connected, and on/off, temperature
setting and monitoring can be accomplished individually or simultaneously. Connectable up
to 2 sets into one system.
563
16
2.3
ED34-762
System Configuration
By combining the various control equipment flexibly, you can construct the sophisticated
central control system to meet any size and design of the building.
ACC Center
Telephone Line
Building Control System
Air Conditioning
Network Service System
(There are restrictions in applicable
areas and release times, therefore
please consult us separately for
details.)
(Optional Maintenance Service)
D-BACS System
Interface
Adaptor for
Air-Conditioner
Control /
Connection
Interface
VRV
DAM602B51/52
BMS
(Field Supply)
Interface for use in LOW WORKS
(DMS504B51)
HRV unit
D -NET
(High Speed Multiple
Transmission)
Parallel Interface
Interface Adaptor
for R.A.
Interface Adaptor
for Sky Air Series
SkyAir
Unification adaptor
for computerized
control
Controllers for
Centralized
Control
ACC
Center
Telephone
Line
Central Remote
Controller
Packaged
Air-conditioner
Central Control
Adaptor Kit
DIII-NET Line
RS232 Line or BACnet / Ethernet
or LON
Contact Signal Line
The DIII-NET system provides for:
Close control and monitoring by integrating a
wide variety of air-conditioners in the entire
building.
Saving the in-building cabling using non-polar,
two-wire cables. Easier wiring work with
tremendously fewer wiring errors.
Additional setups readily up and running. An
extendable cabling up to 2 km in total.
Different control equipment flexibly joined in
the system for hierarchical risk diversification.
Daikin's total heat exchangers and other
devices under integral control.
intelligent
Touch
Controller
Schedule Timer
Wiring Adaptor
for Other
air-conditioners
Unified ON/OFF
Controller
External control adaptor
for outdoor unit
Caution
Control functions may be different from model to model.
For trouble-free control systems, it is advisable to discuss your projects at hand. Please contact us at your planning stage.
564
Room Air-Conditioner
VRV
(V2299)
Control
ED34-762
System Configuration
No.
Part name
Model No.
Function
DCS302CA61
Up to 64 groups of indoor units (128 units) can be connected, and ON/OFF, temperature
setting and monitoring can be accomplished individually or simultaneously. Connectable up
to 2 controllers in one system.
DCS301BA61
Schedule timer
DST301BA61
Programmed time weekly schedule can be controlled by unified control for up to 64 groups
of indoor units (128 units). Can turn units ON/OFF twice per day.
DCS302A52
Interface between the central monitoring board and central control units
DTA102A52
DTA107A55
DTA103A51
Adaptors required to connect products other than those of the VRV System to the highspeed DIII-NET communication system adopted for the VRV System.
To use any of the above optional controllers, an appropriate adaptor must be installed on
the product unit to be controlled.
DIII-NET
Expander adaptor
DTA109A51
Mounting plate
KRP4A92
Note:
Installation box for adaptor must be procured on site.
Part name
intelligent Touch
Controller
1
1-1
1-2
1-3
2-1
Option
3
3-1
3-2
Communication
Line
2-2
6
7
8
9-1
9-2
13
Contact/Analog signal
Model No.
DCS601C51
DCS601A52
DCS002C51
DCS004A51
KJB411A
DAM602B52
DAM602B51
DAM602B51x2
DAM602B51x3
DAM602B51x4
DAM002A51
DAM003A51
DAM101A51
DMS502A51
DAM411A1
Optional Di board
DAM412A1
DMS504B51
Basic unit
Function
Parallel
interface
1-4
basic
intelligent
Hardware Touch
Controller
DIII-NET
Hardware
plus adaptor
P.P.D.
Software
Web
DPF201A51
Temperature measurement
units
DPF201A52
DPF201A53
DCS302A52
KRP2A53, 61, 62
KRP4A51-54
DTA104A53, 61,
62
Interface between the central monitoring board and central control units
Simultaneously controls air-conditioning control computer and up to 64 groups of
indoor units.
To control the group of indoor units collectively, which are connected by the
transmission wiring of remote controller.
Cooling/Heating mode change over. Demand control and Low noise control are
available between the plural outdoor units.
Note:
2. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE).
Control
565
16
2.4
ED34-762
Various PC Boards
Besides the central control system and building control system of the previous page, you can enhance control
function by mounting various PC boards on indoor and outdoor units.
Adaptor for Wiring
The model of adaptor for wiring depends on the type of indoor unit.
566
Part Name
Model No.
Function
KRP1B56, 57,
59, 61
KRP1C3
PC board when equipped with auxiliary electric heater or humidifier in the indoor unit.
Control
ED34-762
16
Control
567
Control System
ED34-762
3. Control System
3.1
Control Method
Objective / Use
Function
1 remote controller
controls 1 indoor unit
Remote operation For control from
of remote
distant place
controller
BRC1C62
2 remote control
2 BRC2C51
Group control 1
Operational functions
Start/Stop (ON/OFF)
Operation Mode Selection
Temperature setting
Timer setting (Settings in units of 1 hour up to
a maximum of 72 hours)
Air flow setting
Air flow direction adjustment (Swing flap)
Ventilation Mode Selection
Ventilation Air flow Selection
Indication function
Operating display
Program dry function display
Defrost/Hot start display
Filter sign
Temperature setting display
Timer display
Air flow display
Abnormal operation display
In case of group control all the indoor units in
the system are set to the same value and
each unit is controlled individually by its
internal thermostat. (Not by the thermostat
equipped in remote controller) In commond
case of double remote control the last
command priority. (Selection between main
and sub controller is essential)
Connected to
indoor units
For group
control it is
1
connected to 1
Group control by 2 For above control
unit out of the
from distant place.
remote controllers
group
In the case of
control by 2
remote
controllers both
controllers are
connected to
Forced OFF for
the indoor unit
Forced OFF
forgetting to turn
command from
equipment off, or
outside
in times of an
emergency.
Operation of other
Combining control equipment
by remote
combined with the
controller
operation of
indoor unit
568
2 remote controllers
control 1 indoor unit
1 remote controller
controls up to 16 indoor
units simultaneously
2 remote controllers
control up to 16 indoor
units from 2 different
places simultaneously
In case of group control, the remote controller used as master control must be selected with auto-swing function
(BRC1A61). When the group has cassette (FXC (Q)), FXF (Q)) or ceiling suspended (FXH (Q)) or cassette
corner (FXK (Q)) or wall mounted (FXA (Q)) models.
In case of using BRC2A51 (Simplified Remote Controller) to Heat Recovery Series, be sure not to use this
independently. Use with other remote controllers (BRC1A51 52, BRC1C62 or KRC19-26A or DCS302A51).
Control
ED34-762
Control System
Outline of System
Relevant
Page
Number
590
590
590
591
591
591
591
Control
569
16
Control System
Control Method
ED34-762
Objective / Use
DCS601C51
intelligent Touch
Controller
Function
DST301BA61
Schedule timer
DCS302CA61
Central Control
Central remote
controller
DCS301BA61
Unified ON/OFF
controller
Controls up to 64 groups of
indoor units with one
central remote controller.
Max. 128 units
Controls up to 16 groups of
indoor units with one
unified ON/OFF controller.
Max. 128 units
DST301BA61
Schedule timer
Central remote
controller
Unified ON/
OFF controller
DCS302CA61
DCS301BA61
For controlling all
indoor units from
one place
Adaptor for
connection with
optional
controllers for
centralized control
570
Unification
adaptor for
computerized
control
DCS302A52
Interface
adaptor for
SkyAir series
DTA102A52
Wiring adaptor
for other air
conditioners
DTA103A51
Simultaneously controls
by one unification
adaptor for
Unification adaptor for computerized control
computerized control,
allows you to simultaneously turn indoor units
all indoor units
connected to the central remote controller on
connected to a central
or off or display at the central monitor panel,
remote controller.
etc.
Controls one indoor unit
Interface adaptor for SkyAir series, wiring
by one interface adaptor
adaptor for other air conditioners and wiring
for SkyAir series, wiring
adaptor for H indoor unit are for connection of
adaptor for other air
optional controllers for centralized control.
conditioners, and wiring
adaptor for G(J) indoor
unit.
Control
ED34-762
Control System
Outline of System
Relevant
Page
Number
643
632
597
624
16
640
677
694
701
Control
571
Control System
Control Method
ED34-762
Objective / Use
Function
With remote
temperature
setting
Remote Control
For control by
operation
command from
building control
room
KRP4A51
KRP4A52
KRP4A53
KRP4A54
Built into indoor
unit
With remote
temperature
setting
Wiring adaptor for
electrical
appendices (1)
Standard Number of
Controllers
1 PC board controls 1
indoor unit.
Normally open or momentary open type
contactor
12~24 VDC or no-voltage
Various control methods available by mode
select switch
Voltage, no-voltage selector switch
Alarm and operation display signal (novoltage)
Selector switch of zone/individual of alarm
display
Remote temperature setting (resistance input
of 0~135)
Selector switch for remote controller
temperature setting enable/inhibit
1 PC board
simultaneously controls 1
group of indoor units (max.
16 units).
1 PC board
simultaneously controls 64
groups (total of 128 units).
Wiring Modification
KRP2A53
KRP2A61
KRP2A62
Built into indoor
unit
Scheduled Control
Building Control
System
Wired remote
controller with
weekly schedule
timer
572
When controlling
operation with
optional
accessories
added inside
indoor units, the
Built into indoor
status is displayed unit KRP1B56,
outside.
57, 59, 61
KRP1C3
Building control
computer,
air-conditioning
control computer
and control
system for
air-conditioning
are carried out by
communication
and contact
signal.
Desired Weekly
Scheduled
Operation of ON/
OFF and
Temperature's
Set-back
Parallel interface
board
Carries out operation and monitoring function
DAM411A1
of each indoor unit by contact and analog
Optional Di
signal.
Board
DAM412A1
Interface for use in LONWORKS
Parallel
The LON Gateway functions as the interface for
interface
a building monitoring system and cannot be wDPF201A51, 52, 53
installed on the DIII-NET along with following
Interface for
equipment / devices that have similar functions.
use in LON
WORKS
DMS504B51
BRC1D61
Control
ED34-762
Control System
Relevant
Page
Number
Outline of System
Individual Control (Controls Indoor Units Individually.)
KRP1B61,KRP1C3,KRP2A61,62
and KRP4A51,52,53 can be builtin together into the indoor units
688
Group Unified Control (Controls group controlled indoor units all at once and
simultaneously.)
681
711
713
574
579
16
Control
Remote controller
Remote controller
Be sure to provide a master
remote controller.
This scheduled operation cannot
be used in both cases at control
by two remote controllers and at
the connection of a group remote
control adaptor.
657
573
Control System
3.2
ED34-762
Name
Functions
Interface unit to allow communications between VRV and BMS. Operation and
monitoring of air-conditioning systems through BACnet communications.
Central control panel for simple operation by ON/OFF switch and LED display. Also
functions as a backup just as with the central remote controller.
Provided in each room. Used for operating, setting and monitoring air-conditioning
equipment.
Note:
1. A group consists of several indoor units that can be started or stopped simultaneously. As shown in the figure
above, a group consists of several indoor units wired to the same remote controller. For units without a remote
controller, each unit is treated as a group.
2. Several groups are registered as a zone with the central remote controller. By pushing 1 button of the central
remote controller, all groups within the same zone can be turned on or off simultaneously.
574
Control
ED34-762
Control System
Building management 1 system controls and monitors air-conditioning equipment by the block. A block consists of 1
or more groups (max. 16), and can be set without regard for the zones mentioned above. You must, however, take
the following things into consideration.
(1) If the air-conditioning mode is switched, as a premise, permission for cool/heat selection for indoor units (by
remote controller or central remote controller) must be designated within the program.
(2) Program status is basically monitored by observing the data of a representative unit. The contents which can be
monitored are therefore restricted if the representative unit is designated as an adaptor, etc.
Block registration is accomplished through signal transmission from the building control system to the coolerconditioning system. Because configuration can be changed while receiving power even after operating,
maintenance from the maker of the air-conditioning equipment is not required when changing the configuration.
Malfunction
of unit
16
C : 1P056362A
Control
575
Control System
ED34-762
Interface
Adaptor for
SkyAir Series
(SA Heat Pump)
HRV
Wiring Adaptor
for Other AirConditioners
Air-Conditioner Error
Notification
Air-Conditioning Mode
Setting and Monitoring
Thermostat Status
Monitoring
Compressor Operation
Status Monitoring
{ 2
Forced Thermostat On
Setting and Monitoring
{ 2
{ 2
Function
Remarks
Note:
1. Remote controller mode is for acceptance or rejection of on/off operation, temperature setting and airconditioning mode setting by remote controller.
2. If set locally, the host is not notified. Thus, monitoring cannot be accomplished from the host.
3. The meaning of {, are as follows
{ : Possible Functions
: Impossible Functions
576
Control
ED34-762
Control System
Unified
ON / OFF
Controller
Schedule
Timer
Wiring
Adaptor for
Electrical
Appendices
Parallel
Interface
Interface for
use in
BACnet
intelligent
Manager
Schedule Timer 1
Parallel Interface
intelligent Manager
1
2
3
4
5
The schedule timer cannot be used by itself. Use in combination with the central remote controller or unified ON
/ OFF controller.
May be used in combination if control range differs (up to 4 units).
May be used in combination if control range differs
(up to 8 units: Up to 16 units in the double central control mode).
May be used in combination if control range differs
(up to 2 units: Up to 4 units in the double central control mode).
The meaning of {, , are as follows
{: Possible Functions
: Impossible Functions
: No Functions
If using in combination with central control equipment, the relation between them is last command priority.
If using in combination with central control equipment, the remote control mode is decided by the setting of the
highest priority item in the priority rank shown in the table below.
Priority Ranking of Remote Control Mode Settings
Interface for use
in BACnet
Priority Ranking
intelligent Touch
Controller
Unified ON/OFF
Controller
Schedule Timer
16
Control
577
Control System
ED34-762
#1
Sub
#2
#3
#1
Combination
578
#4
#2
1-00~4-15
Main/
Sub
Impossible
intelligent Touch
Controller
Impossible
#3
5-00~5-15
Main/
Sub
Main
intelligent Touch
Controller
intelligent Touch
Controller
Main
Impossible
intelligent Touch
Controller
Impossible
#4
1-00~4-15
Main/
Sub
5-00~5-15
Main/
Sub
Main
intelligent Touch
Controller
Sub
intelligent Touch
Controller
Sub
intelligent Touch
Controller
Main
intelligent Touch
Controller
Sub
Central Remote
Controller
Sub
Main
intelligent Touch
Controller
Main
Central Remote
Controller
Sub
intelligent Touch
Controller
Sub
intelligent Touch
Controller
Main
intelligent Touch
Controller
Main
Central Remote
Controller
Sub
Central Remote
Controller
Sub
Impossible
intelligent Touch
Controller
Main
Central Remote
Controller
Main
intelligent Touch
Controller
Sub
intelligent Touch
Controller
Sub
Impossible
intelligent Touch
Controller
Main
Central Remote
Controller
Main
intelligent Touch
Controller
Sub
Central Remote
Controller
Sub
Impossible
intelligent Touch
Controller
Main
Central Remote
Controller
Main
Central Remote
Controller
Sub
intelligent Touch
Controller
Sub
Impossible
intelligent Touch
Controller
Main
Central Remote
Controller
Main
Central Remote
Controller
Sub
Central Remote
Controller
Sub
Impossible
Central Remote
Controller
Main
intelligent Touch
Controller
Main
intelligent Touch
Controller
Sub
intelligent Touch
Controller
Sub
Impossible
Central Remote
Controller
Main
intelligent Touch
Controller
Main
intelligent Touch
Controller
Sub
Central Remote
Controller
Sub
Impossible
Central Remote
Controller
Main
intelligent Touch
Controller
Main
Central Remote
Controller
Sub
intelligent Touch
Controller
Sub
Impossible
Central Remote
Controller
Main
intelligent Touch
Controller
Main
Central Remote
Controller
Sub
Central Remote
Controller
Sub
Impossible
Central Remote
Controller
Main
Central Remote
Controller
Main
intelligent Touch
Controller
Sub
intelligent Touch
Controller
Sub
Impossible
Central Remote
Controller
Main
Central Remote
Controller
Main
intelligent Touch
Controller
Sub
Central Remote
Controller
Sub
Impossible
Central Remote
Controller
Main
Central Remote
Controller
Main
Central Remote
Controller
Sub
intelligent Touch
Controller
Sub
Possible
Central Remote
Controller
Main
Central Remote
Controller
Main
Central Remote
Controller
Sub
Central Remote
Controller
Sub
Possible
Central Remote
Controller
Main
Central Remote
Controller
Sub
Possible
intelligent Touch
Controller
Main
intelligent Touch
Controller
Sub
Possible
Central Remote
Controller
Main
intelligent Touch
Controller
Sub
Possible
intelligent Touch
Controller
Main
Central Remote
Controller
Sub
Possible
Central Remote
Controller
Main
Possible
intelligent Touch
Controller
Main
Control
ED34-762
Control System
Operation/
Setting
Monitoring
Host System
On/Off Operation
Off command is detected and all indoor units on the same line are turned off.
Temperature Setting
Control
Alteration of the temperature setting is detected, and if within the range of 1.6
to 3.2V, the command is sent to applicable group of indoor units.
Setting by local remote controller or central remote controller is impossible
when in this range only. (Central Control is displayed on the local remote
controller.)
Normal/Error Status
(Note 1)
Filter Sign
Present status is output when at least 1 group among the control target groups
is lit.
Note:
1. The various output conditions are as follows.
On: At least 1 air-conditioner in the group is operating.
Off: All air-conditioners in the group are turned off.
Error: An error has occurred for at least 1 air-conditioner in the group.
Normal: All air-conditioners in the group are operating normally.
Control
579
16
Control System
3.3
ED34-762
<Example>Section of cord
Vinyl cab tire round cord
JISC3306
VCTF
JISC3401
Vinyl insulated, vinyl sheathed cable for control CVV
JISC3401
Round vinyl sheathed cable for control
CVS
JISC3342
Round vinyl insulated, vinyl sheathed cable
VVR
JISC3312
VCT
600V vinyl cab tire cable
CPEV()
Polyethylene insulated vinyl sheathed cable
MVVS()
Mesh insulated cable
When the shield wire is used, be sure to ground the one side of the shield
wire.
Do not use the shield wire with other type of wire in the same system.
<Cautions>
1. Never use a 3 or more core of cord or cable.
2. The size of wire should be 0.75~1.25mm.
3. Never bundle the cable or cord of transmission line.
4. Be sure to keep the transmission wiring distant from power wiring as shown below to prevent electrical
noise.
Capacity of power wiring
10A or less
220V or less
50A or less
100A or less
100A or more
Other air-conditioners
300mm or more
500mm or more
1000mm or more
1500mm or more
Note:
1. 1 .....VRV system, SkyAir series and other air-conditioner.
2. 2 .....VRV system or other Daikin air-conditioner produces less electrical noise, so that the distance of 50mm or
more is sufficient.
3. For control wiring, never use the shield wire together with other sheathed vinyl cord in the same system, which
may cause the malfunction in transmission.
[Example]
580
Control
ED34-762
3.4
Control System
Wiring Example
Example of Control Wiring
Be sure to connect the wiring of the central controller to A or B.
(Connect to B, if it is possible.)
Be sure to limit the number of indoor units within the limitation for each system.
Never connect the wire between the controllers, which are connected to the different circuit. (Be careful)
In order to prevent the connection of three wires on the same terminal, connect to the terminal unit of A or B, or
use the relay terminal (local supply).
16
Control
581
Control System
ED34-762
582
Control
ED34-762
3.5
Control System
In the above system, the longest extension of wiring is 900m between (A) and (C), which satisfies the limit of
1000m. And the total length is 1100m, that is the total of 900m between (A) and (C) and 200m between (B) and
(C), which also satisfies the limit of 2000m. The central controller functions properly, only when both the longest
extension and the total length of wiring satisfies the limitation, as shown above.
Caution
When designing the system, be sure to check both the longest extension and the total length of wiring. If it exceeds
the limitation, there is no other way but to split into several systems.
16
Control
583
Control System
3.6
ED34-762
Branch Wiring
Wiring methods (You can select from the following 3 types of wiring.)
3.6.1 Series Method
3.6.2 Bus Method (Up to 16 branches is possible. Never diverge the sub-branch from the
branch line.)
3.6.3 Star Method (Up to 16 branches is possible. Never diverge the sub-branch from the
branch line.)
Note:
Though a previous figure shows a case in use of a central remote controller, the wiring form which even other central
remote controllers are the same as can be done.
584
Control
ED34-762
Control System
16
Caution
As shown above, the central remote controllers should be connected to the wiring between the outdoor units,
wherever possible. (If connected to the control wiring between indoor unit and the outdoor unit, it may not be able to
control the units even on the normal circuit if the circuit connected to the central controller is out of order.)
Control
585
Control System
ED34-762
Caution
As shown above, if the central remote controllers are connected to the control wiring between indoor unit and outdoor
unit, it may not be able to control the units even on the normal circuit, if the circuit connected to the central controller
is out of order. Be sure to connect the central controllers to the control wiring between the outdoor units.
586
Control
ED34-762
Control System
Number
of Units
(Note 2)
Indoor Unit
Outdoor Unit
VRV system
SkyAir series
(Interface adaptor for SkyAir
is required.)
HRV unit
Packaged air-conditioner
(FD, UAT, etc.)
(Wiring adaptor for other air- Outdoor unit for VRV system
conditioner is required.)
Room air-conditioner
(Wiring adaptor for other airconditioner is required.)
BS unit (Note 3)
Wiring adaptor
Up to 128 units (Note 5)
Up to 10 units (Note 4)
Other Adaptors
Up to 10 units
Note:
1. When you have a 2 central control system (to control one system from 2 central locations), 2 intelligent Touch
Controllers, 4 central remote controllers and 16 unified ON/OFF controllers can be connected. However, a
maximum of 128 units can only be controlled.
2. When you connect 8 or more central control equipment, it is required to satisfy the following conditions. (The
following conditions are not required to be considered when the number of controller is 7 or less.)
Central control equipment + Indoor units + Outdoor units + other adaptors 160 units
Central Conversion number of central control equipment () + Indoor units + Outdoor units + other
adaptors 200 units
(Note: () is converted one central control equipment except unified ON/OFF controller as 10 units.)
3. When BS unit is installed, BS unit is not counted in the number. However, the indoor units after BS unit should be
counted.
4. The outdoor unit is limited up to a maximum of 10 units and the total rated capacity should be 280kW (100HP) or
less, and also the number of function units is also limited up to 5. However, if the sequential start setting is
possible, up to 10 function units can be connected.
5. When the parallel interface is connected, the number of indoor units are limited up to 64 groups (128 units). When
you judge whether the number of the connectable units is possible, refer to the flow chart on the next page.
16
Control
587
Control System
ED34-762
588
Control
ED34-762
Control System
Note:
1. When one system is to be controlled from two locations, up to two intelligent Touch Controller (In case of
combining the intelligent Touch Controller and Central Remote Controller, it is restricted to combine two
Controllers in total), four Central Remote Controller and 16 unified ON/OFF Controller can be connected.
However, the maximum number of units that can be controlled is 128.
2. When a BS unit is used, the indoor units used in its downstream are not counted.
3. One port of one Interface for use in BACnet can have up to 64 groups (64 master indoor units with address). In
case of adopting group controlling, the circuit covered by the data station can have up to 128 indoor units
including main and sub units.
16
Control
589
Control Devices
ED34-762
4. Control Devices
4.1
590
Control
ED34-762
Control Devices
Wiring for remote controller group control has no polarity, P1 and P2 can be switched.
All indoor units within the group have the same setting, and each indoor unit is controlled individually by its own
built-in thermostat.
Because automatic address is used, address does not have to be set by remote controller for group control.
Note:
Only remote controller wiring is shown.
For Connection unit series
Although group control in Connection unit series is possible, however, group control with other series is
impossible.
Control
591
16
Control Devices
ED34-762
2. Contents of operation
Operation is as given in the table on the right for input A of forced OFF and ON/OFF control.
3. How to select forced OFF and ON/OFF control
Select input by remote controller after turning on the power supply.
Set to the field set mode by remote controller.
After entering the field set mode, select mode No. 12, set the first code No. to 1, and set the second code No. to
01 for forced OFF, or to 02 for ON/OFF control.
(Factory setting is set to forced OFF.)
592
Wiring specifications
Wiring thickness
0.75~1.25 mm
Wiring length
Max. 100 m
Control
ED34-762
Control Devices
4.1.6 Dimensions
BRC1C62
For FXC(Q), FXF(Q), FXK(Q), FXD(Q), FXS(Q), FXM(Q), FXH(Q), FXA(Q), FXL(Q), FXUQ-M(A)
Unit (mm)
DU820-226
16
Control
593
Control Devices
4.2
ED34-762
FXCQ
BRC7C67 ... For Cooling Only
Unit (mm)
3D007588A
FXFQ
BRC7E65 ...... For Cooling Only
Unit (mm)
3D034088A
594
Control
ED34-762
Control Devices
FXKQ
BRC4C63 ... For Cooling Only
Unit (mm)
3D007898A
FXHQ
BRC7E66 ...... For Cooling Only
Unit (mm)
16
3D028963B
Control
595
Control Devices
ED34-762
FXAQ
BRC7E619 ... For Cooling Only
Unit (mm)
3D034905B
FXUQ
BRC7C529W.. For Cooling Only
Unit (mm)
3D014035A
596
Control
ED34-762
4.3
Control Devices
Remark
SkyAir series
Interface adaptor for SkyAir series is required for each indoor unit.
Room air-conditioner
Wiring adaptor for other air-conditioning is required for each indoor unit.
Other air-conditioner
Wiring adaptor for other air-conditioning is required for each indoor unit.
HRV unit
16
Control
597
Control Devices
ED34-762
The group means the indoor units connected by the same control wiring for remote controller (connected to
terminal P1 and P2) and all the unit in group have the same setting and the same operation.
The indoor units in the group are controlled by the remote controller for indoor unit.
The number of indoor units in one group is up to 16 units.
Zone control
The zone means the indoor units connected by the same control wiring for central remote controller (connected to
terminal F1 and F2) and all the unit in zone have the same setting.
The zone control of the indoor unit is operated by the central remote controller.
From 1 up to 64 zones can be controlled by the central remote controller.
The number of groups you can set in one zone is from 1 up to 64 groups.
Up to 16 units can be set in one group, and up to 64 groups (up to 128 units) can be connected.
598
Control
ED34-762
Control Devices
16
Note:
The following setting cannot be made by the sub side. Be sure to set by the main side.
Operation code setting
Combined operation between indoor unit and HRV unit.
Control
599
Control Devices
ED34-762
Caution for wiring of BEV unit system with Central Remote Controller
When the BEV unit system, such as FXAQ/FXLQ-M(A)V1, FXUQ-M(A)V1, and FUYP-BV1 are connected to the
Central Remote Controller, the wiring becomes more complicated than that of general VRV system.
Please take care as follows when wiring.
[NG Example]
(NOTE)
[Central
R/C]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
[Indoor unit]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
[Indoor unit]
[Central
R/C]
F1, F2
[BEV]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
F1, F2
[Interface ADP
for SkyAir]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
[Indoor unit]
[Indoor unit]
(NOTES)
1. When 3 or more wirings are branched from the
same terminal block, use a relaying terminal
block of field supply.
[Indoor unit]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
[Indoor unit]
600
[Central
R/C]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
[Indoor unit]
[Indoor unit]
F1, F2
[BEV]
F1, F2
[Interface ADP
for SkyAir]
[Indoor unit]
Control
ED34-762
Control Devices
Power consumption
Max. 8W
Weight (Mass)
Approx. 420 g
Dimensions
DCS302CA61
Unit (mm)
3D050340
Control
601
16
Control Devices
ED34-762
DISPLAY
(VENTILATION CLEANING
DISPLAY)
DISPLAY (OPERATION
MODE)
Displays operating state.
UNIFIED OPERATION
BUTTON
Press to operate all indoor
units.
DISPLAY
(COOLING/HEATING SELECTION
PRIVILEGE NOT SHOWN)
ALL
INDIVIDUALLY
(ZONE SETTING)
OPTION
TEST
12
F
C
SET
DISPLAY (OPERATION
MONITOR)
NOT
T
L H HH
AVAILABLE FRESH UP
No..
CODE
UNIT No.
ALL
OPERATION MONITOR
DISPLAY
SET
DISPLAY
(TIME TO CLEAN)
DISPLAY (REFRIGERANT
SYSTEM DISPLAY)
(PRESET
TEMPERATURE)
L H HH
FRESH UP
DISPLAY (VENTILATION
STRENGTH/SET FAN
STRENGTH DISPLAY)
DISPLAY
(MALFUNCTION CODE)
DISPLAY (FAN
DIRECTION SWING DISPLAY)
CODE
UNIT No.
DISPLAY (OPERATION
CODE AND UNIT NUMBER
DISPLAY)
DISPLAY (TIME TO
CLEAN AIR CLEANER ELEMENT/
TIME TO CLEAN AIR FILTER)
TEST DISPLAY
(INSPECTION/TEST)
Control Section
ON/OFF BUTTON
ALL/INDIVIDUAL BUTTON
Pressing this button scrolls through
the "all screen", "zone screen", and
"individual screen".
FAN DIRECTION
ADJUSTMENT BUTTON
OPERATION MODE
SELECTOR BUTTON
VENTILATION STRENGTH
ADJUSTMENT BUTTON
This button is pressed to switch the
ventilation strength ("fresh up") of
the total enthalpy heat exchanger.
SET BUTTON
Sets control mode and time No.
TEMPERATURE
ADJUSTMENT BUTTON
(ZONE NUMBER BUTTON)
602
Control
ED34-762
Control Devices
Basic functions
Individual/Zone control
Unified ON/OFF
Malfunction code display
Connection of unification adaptor for
computerized control
Remote control acceptance/rejection
2 central controllers
Descriptions of outline
Up to 64 groups (Max. 128 units and max. 16 units per group) of indoor units and HRV
units can be controlled by individually or by zone.
ON/OFF can be set for each zone, and can be controlled simultaneously for entire
system by push button or by contact signal from outside.
The status of each group is always displayed, such as ON/OFF, error, etc. If the error
occurs, it displays the contents of error by malfunction code through the self-diagnosis
function.
By connecting the unification adaptor for computerized control (option), it can be linked
with the central monitoring panel and etc. by contact signal, which enables you to
operate ON/OFF simultaneously or monitor the operating status.
It is possible to restrict the function of local remote controller.
(Only ON operation rejection, or ON/OFF operation rejection)
By connecting two central remote controllers, the same air-conditioner can be controlled
from 2 locations (By tenant or administration office.)
Zone register
Zone setting
Control
Descriptions of outline
The zone function is a function to control one or more group of air-conditioner, and the
operation setting such as ON/OFF etc. can be made by zone.
Up to 64 zones (64 groups for each zone) can be set. However, the group setting
spreading over the plural zone cannot be set.
When the power is supplied first time, each group is registered in each respective zone.
If you can simply register the several groups in the same zone by switch, so that you can
have simultaneous operation of the units in that zone immediately. (The operation of
temperature setting and etc. is also controlled by zone simultaneously.)
By adding the zone setting function (Zone 0) from the central remote controller, you
can set the same setting for all the zone registered by single operation.
For example, if there are three groups in one room and if you register these three groups
as one zone, you can operate these three groups simultaneously by single operation
(ON/OFF, temperature setting etc.).
You still can operate each group individually by local remote controller.
Even if the power is turned off, the zone configurations set are maintained semipermanently. (saved in non-volatile memory)
The cool/heat changeover can be made by zone. However, it is required to have a
master group for Cool/Heat changeover in that zone.
The same setup is possible at one operation to all the groups registered on the "All" screen.
Even if there is no local remote controller, you can still perform the same operation.
There is no problem even if no remote controller is connected. (However, in this case,
each one air-conditioner consists of one group.)
You can also combine with a unified ON/OFF controller and a schedule timer.
(Refer to the system configuration for details.)
You can also combine with an Interface for use in BAC net and a data station in order
to connect to the central monitoring panel. A parallel interface can also be connected.
603
16
Control Devices
ED34-762
Note:
Be sure that if timer No. is registered by the sub central remote controller, [Timer mode acceptance for local remote
controller (mode no. 8,9,18, and 19)] for the same units set by the Main remote controller becomes meaningless
(operates when time comes.).
<Explanation of the above figure>
If you operate the central remote controller in the sequence of c and d, the indoor unit is set for cooling /
temperature setting 24C.
However, the display of zone setting of the master remote controller remains at heating / temperature setting at 27C.
<Cautions>
Operation code cannot be set by the sub central remote controller.
Combined zone operation can only be set by zone registration of the main central remote controller.
Both main and sub central remote controller are operated by a Last priority command for the functions other than
the above.
However, the display on the central remote controller cannot be changed by each other. (On the display for the
group, you can monitor the present operation status.)
604
Control
ED34-762
Control Devices
Sequential Start
<Operation command from central control equipment>
Each unit operates in sequence. For example, if you set the simultaneous operation by the central remote controller,
which controls 1-00 ~ 4-15 and 5-00 ~ 8-15 groups, two outdoor units start simultaneously.
Registering Zone
It is possible to set multiple groups as one zone and control each zone separately.
No zones are registered when the unit is shipped from the factory.
Zone registration can be done in the individual screen, all screen, or zone screen.
5
6
4
7
Registration
1. 1 Pressing the "ALL/INDIVIDUAL" button for four seconds. 2 Displays ZONE SET.
Zone Number 1 will be displayed, and if there are any groups already registered in the displayed zone, a
will light up on the operation monitor.
2. 3 Select the Zone Number to be registered using the "ZONE NUMBER" button.
Keeping the button pressed down will move it rapidly.
3. 5 "
"to the group you wish to 4 register using the arrow keys.
Keeping the button pressed down will move it rapidly.
4. 6 Press the "SELECT" button to register that group to the zone.
The "
" display lights up on all the selected units.
7
Pressing the "RESET" button removes the group from that zone, and "
" goes off.
Repeat steps 3 and 4 until all the units you wish to register to the zone have been added.
16
In this example, a screen is shown with units 1-00, 1-02, 1-03, and 2-00 registered to Zone Number 1.
5. Repeat steps 2 to 4 to register to the next zone.
6. Once zone registration is complete, 1 press the "ALL/INDIVIDUAL" button to turn off "ZONE SET"
display and return to the individual screen.
The display returns to the normal screen if nothing is done for one minute when in zone registration mode.
(NOTE)
It is impossible to register one group to several different zones.
If this is done, the last zone registered to will be valid.
3P124623-3A
Control
605
Control Devices
ED34-762
9
Pressing the "ALL
" for at least four seconds while 8 pressing the "FILTER SIGN RESET"
button when 2 "ZONE SET" is displayed will delete all zone registrations.
The zone registrations for all units will be lost.
3P124623-3A
Zone setting
Set the screen of [Zone 0] on the display, and if you set the following mode, you can set to the all zone registered on
the central remote controller by one operation.
Operation mode
Control mode
Room temperature setting
Time NO.
606
Control
ED34-762
Control Devices
Zone 1
Central Remote
Controller
Indoor Unit
1-00
2-00
Zone 3
HRV
1-01
Zone 4
1-02
3-00
4-00
1-03
1-04
1-05
1-06
1-07
1-08
Operation Code
Timer No.
Temp. Display
Zone 1
1-00
1-00
1-00
1-00
N/A
Zone 2
1-03
1-03
1-03
1-03
1-05
Zone 3
1-06
1-06
1-07
1-07
1-06
Zone 4
2-00
2-00
N/A
N/A
2-00
Operation Mode
Ventilation Mode
If the system is operated on the Zone screen, one and the same setting will be made on all indoor units registered
with the zone.
On the Zone screen, ventilation mode is only monitored. In order to change ventilation mode, be sure to use the
Individual screen.
On the Batch screen, operating and monitoring is also enabled, thus monitoring an indoor unit with a lower address
within the scope of control.
16
Control
607
Control Devices
ED34-762
4
INDIVIDUALLY
C
L
3
6
[Registration]
1. 1 Press the "ALL/INDIVIDUAL button" to enter the 2 individual screen.
The unit will enter the individual screen automatically if nothing is done for one minute.
2. 3 Using the arrow keys, 4 move the "
" to select the units to fan direction adjustment or fan
strength adjustment.
Keeping the button pressed down will move it rapidly.
3. 5 Press the "FAN DIRECTION ADJUSTMENT" button.
This sets "fixed" or "swing" for the fan direction.
6
Press the "FAN STRENGTH ADJUSTMENT" button.
Pressing this button scrolls through "
Depending on the indoor unit, only "
L
L
", "
HH
".
The functions included in the indoor units may vary.Pressing a button for a function which is not available will cause
"NOT AVAILABLE" to be displayed.
3P124623-3A
2
4
INDIVIDUALLY
H
FRESH UP
[Registration]
1. 1 Press the "ALL/INDIVIDUAL button" to enter the 2 individual screen.
The unit will enter the individual screen automatically if nothing is done for one minute.
2. 3 Using the arrow keys, 4 move the "
" to select the units to ventilation mode or ventilation
strength adjustment.
Keeping the button pressed down will move it rapidly.
3. 5 Press the "VENTILATION MODE" button.
It will scroll through "
608
" "
" "
" "
".
Control
ED34-762
Control Devices
" "
" "
L
FRESH UP
" "
" "
H
FRESH UP
".
The fresh up function may not be available depending on the connected unit model.
The functions included in the indoor units may vary.Pressing a button for a function which is not available will cause
"NOT AVAILABLE" to be displayed.
Ventilation Mode and Amount
If these are changed using the remote controller depending on the unit model, they cannot be displayed on the
central remote controller.
To monitor the ventilation mode and amount, check the values on the remote controller.
3P124623-3A
INDIVIDUALLY
1
No.
C
L
[Registration]
1. 1 Pressing the "TIMER NO." button causes the number set for timer number 1 to blink.
If no timer setting has been made " " will be displayed.Select the desired timer number by pressing the
1
"TIMER NO." button.
1
No.
2.
2
Once the desired timer number is displayed, press the "SET" button.
Press the 2 "SET" button within 10 seconds after the timer number is displayed.
The display will return to how it was after 10 seconds.
The display for timer number 1 will stop blinking and then timer number 2 will start blinking.
16
No.
3.
1
Select the desired timer number by pressing the "TIMER NO." button.
Once the desired timer number is displayed, 2
press the "SET" button.
The display for timer number 2 will stop blinking.
No..
No
Control
609
Control Devices
ED34-762
610
Control
ED34-762
Control Devices
2. Bus method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
3. Star method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
Control
611
16
Control Devices
ED34-762
1.
2.
3.
4.
5.
6.
MODE NO.
SECOND
CODE NO.
FIRST
CODE NO.
FIELD
SET
MODE
UNIT NO.
SETTING
.
1 7
TEST
(V0292)
<Cautions>
Even in the system without remote control, connect the remote controller once to set group No. for central control
equipment and remove the remote controller after setting.
When you set the group No., be sure to supply the power to the central remote controller, the unified ON/OFF
controller and the indoor unit.
<Example of group setting>
Cautions
When the power is supplied, all the display appears once on the remote controller and then the display changes to
612
Control
ED34-762
Control Devices
[88] for about one minute and during that time the remote controller does not function. However, this is not a
malfunction of remote controller.
16
Control
613
Control Devices
ED34-762
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation by remote
controller (at time of
unified operation by
centralized control)
Temperature
control by
remote
controller
Stop by
remote
controller
Operation
mode setting
by remote
controller
The control
mode is 1 .
[Rejection]
[Rejection]
[Rejection]
[Acceptance]
[Acceptance]
Stop
Temperature Operation
control
mode setting
Rejection
ON/OFF control
impossible by
remote controller
Rejection
(Example)
Rejection
(Example)
Rejection
Rejection
(Example)
Acceptance
(Example)
Acceptance
Rejection
Centralized
Acceptance
Acceptance
Acceptance
Rejection
Individual
Acceptance
Acceptance
Timer operation
possible by
remote controller
Acceptance
(During timer at
ON position only)
Rejection
(During timer at OFF
position)
Rejection
Acceptance
Control
mode
Acceptance
Rejection
10
Acceptance
(Example)
1 (Example)
Rejection
11
Acceptance
Rejection
12
Acceptance
Rejection
13
Acceptance
Rejection
14
Acceptance
Rejection
15
Acceptance
Rejection
16
Acceptance
Rejection
17
Acceptance
Rejection
18
Acceptance
Rejection
19
C : 3P171361-1
614
Control
ED34-762
Control Devices
ON Time
OFF
On
Off
DCS302C(A)61
Command
ON
OFF
ON
ON
OFF
ON
OFF ON
OFF
Remote Controller
Command
On
Off
Rejection
Acceptance
Schedule Timer
OFF Time
ON
DCS302C(A)61
ON
OFF
ON
OFF
Remote Controller
Command
Indoor Units Status
On
Off
Rejection
Acceptance
Operation by Central
Remote Controller
16
Schedule
OFF Time
ON Time
Schedule
OFF Time
Remote Controller
Permission Timer
Last command
priority
Schedule Timer
Operation by Central
Remote Controller
ON OFF
DCS302C(A)61
Command
ON
ON
ON OFF
OFF
ON
ON OFF
OFF ON
OFF ON
Acceptance
Rejection
ON
OFF
Remote Controller
Command
Indoor Units Status
On
Off
615
Control Devices
ED34-762
Unified ON/OFF
Controller
1 to 4
1 to 16
Schedule Timer
1
1
Unified ON/OFF
Controller
Schedule Timer
Not used
Not used
(Remove this connector when using this controller in conjunction with power consumption counting unit, parallel
interface, and data station.)
(2) Address setting
Two central remote controllers can be used as shown in SYSTEM CONFIGURATION to control anywhere up to
a max. 128 groups of indoor units. In this case, group address must be set. This is done with the switch for setting
each address (SS3).
One of the two central remote controllers (1) (2) is set to MAIN while the other is set to SUB
(4) Setting of the sequential operation function
The central remote controller is equipped with a sequential operation function that sequentially turns indoor units
on in 2-second intervals during unified operation. (Sequential operation is factory set to ON.) To switch
sequential operation ON or OFF, set as follows.
Note:
The sequential operation function is designed to reduce the load on the power supply equipment, but does not
guarantee that compressors will not be started simultaneously. You cannot therefore count on a capacity reduction
effect by power supply equipment breaker selection.
616
Control
ED34-762
Control Devices
C: 2P162816
16
Note:
Do not connect the power supply wiring (100 to 240V) to the control terminal strip. If connected by mistake, it may
damage or burn electrical parts of optional controllers for centralized control and indoor unit. It may result in serious
danger. Be sure to check wirings before turning the power ON.
C: 2P162816
Control
617
Control Devices
ED34-762
5
button for a minimum of 4 seconds.
The remote controller will enter the FIELD SET
MODE.
3. Select the MODE No.
with the
button.
4. Use the
button to select the group No. for each group.
(Group numbers increase in the order of 1-00, 1-01, ...1-15, 2-00, ... 8-15.)
5. Press
to set the selected group No.
6. Press
to return to the NORMAL MODE.
MODE NO.
UNIT NO.
FIELD SET
MODE
SETTING
TEST
2,6
Note:
For simplified remote controller, see the installation table.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
SET
1.5
Setting Procedure
1. Press and hold the INSPECTION/TEST RUN button for a period of four seconds or more to set the system to
FIELD SETTING mode.
2. Use the TEMPERATURE ADJUSTMENT button to select a desired Mode No.
: Press to increase the Mode No. : Press to decrease the Mode No.
3. Press the CONTROL MODE (CODE No.) button to select a "Switch Setting No.".
4. Press the SET button to determine the content of the setting changed.
Upon determination, the blinking the "Switch Setting No." will turn ON.
5. Press the INSPECTION/TEST RUN button to return the system to NORMAL mode.
In this case, power supply is not needed to turn ON again.
618
Control
ED34-762
Control Devices
Example: In case of no restriction items from the sub central remote controller while in double central control, make
setting of the Mode No. to "02" and the Switch Setting No. to "0".
Setting Contents and Setting No.
Mode No.
Setting contents
00
NO
YES
01
NO
YES
02
Disabled
Enabled
03
Forced thermostat
OFF with the scope
of control
04
1
Low
Factory default
10
High
Items indicated by boldface represent the factory set for the No. of Switch Setting.
Do not make setting of any items not listed in the table above.
Refresh function
This function is used to automatically send "OPERATION MODE" and "TEMPERATURE SETTING" from the central
control system while in operation. In order to disable the refresh function, set the "No. of Switch Setting" to "0".
Restriction items from sub central remote controller while in double central control function
While in double central control function, no settings of zone interlock and operation code can be made from the
sub central remote controller. In order to disable the refresh function from the sub central remote controller, set
the "No. of Switch Setting" to "0".
Setting of area designation for forced OFF
In order to stop all indoor units within the scope of control as a single unit using the entry of T1 and T2, set the
"No. of Switch Setting" to "1".
In order to stop all indoor units within the scope of control with forced thermostat OFF using the entry of T1 and
T2, set the "No. of Switch Setting" to "2". With this parameter set to "2", no forced stop can be made on any
indoor unit.
Cooling Mode
Cooling 28 C
Fan Mode
Fan Operation
It depends on the setting of outdoor systems that an indoor unit setting is "Temperature control" or "Temperature
setting"
In case of Refreshed operation is "ON"
When setting is changed by DCS302CA61, it operates by this setting from the next operation.
If it sets up with 26 C in cooling by DCS302CA61, "in the case of the equipment which has not carried out zone
setting by a central remote controller, it operates from next with the mode of operation and preset temperature
which were set up on the individual screen."
In the case of the equipment which carried out zone setting, it operates from next with the mode of operation
and preset temperature which were set up on the zone screen.
(Priority is given over the mode of operation and preset temperature which were set up on the zone setting
screen).
When it sets up all at once, it operates from next with the mode of operation and preset temperature which were
set up last time on the individual screen (Equipment which has not carried out zone registration), or the zone
screen.
If a setting change is made with 26 C of cooling by a central remote controller on an individual screen
(Equipment which has not carried out zone setting)" next operation will also be operated at 26 C in cooling.
(Even if it has changed into heating operation, fan only operation with wired or wireless remote control, it
operates at 26 C in cooling.)
Control
619
16
Control Devices
ED34-762
Central Remote
Controller
Outdoor Unit
System 1
1-00
1-01
1-02
1-03
1-04
1-05
2-02
2-03
2-04
2-05
Zone 1
Outdoor Unit
System 2
2-00
2-01
Installation
(1) Open the upper part of remote controller.
Insert a screwdriver (2 locations) into the recess between the upper part and the lower part of remote controller
and twist the screwdriver lightly.
screwdriver
(2 locations)
PC board is attached with both the upper and lower part of remote
controller. Do not damage the board with the screwdriver.
(2) Open the upper part of remote controller and install the Electric parts box with the attached installation screws
(M4 16).
Installation screws
(4)
Electric parts box
(KJB311A)
Weak current
electric wire
NOTE) Suitable length of the electric wire is about 160mm. (from electric parts box) If it is difficult to contain a long
wiring, strip the sheathed part of the wiring.
Conduit tube
Approx. 160mm
Electric parts box
C: 2P162816
620
Control
ED34-762
Control Devices
00 01 02 03
2
3
[Registration]
1. 1 Press the ARROW KEY BUTTON to call up the group that has stopped due to malfunction.
2
C
L
Operation
lamp
Maintenance
display
Unit No.
UNIT No.
Malfunction
code
Error content
64
65
68
6A
6A
6F
6H
94
A0
A1
A1
A3
A6
A7
A9
Indoor unit BEV unit, electric expansion valve motor (20E) error
AF
AH
AJ
16
3P124623-3A
Control
621
Control Devices
Operation
lamp
ED34-762
Maintenance
display
Unit No.
Malfunction
code
C4
C5
C9
CA
Error content
Indoor unit Liquid piping thermistor (Th2) Error (faulty connection, cut wire, short circuit, fault)
Indoor unit BEV unit, gas piping thermistor (Th3) Error (faulty
connection, cut wire, short circuit, fault)
Indoor unit Intake air thermistor (Th1) Error (faulty connection,
cut wire, short circuit, fault)
Indoor unit Outlet air thermistor (Th4) Error (faulty connection,
cut wire, short circuit, fault)
CJ
E0
E1
E1
E3
E4
E9
EC
EF
F3
H3
H4
H9
H9
HC
HF
Ice thermal storage unit error, ice thermal storage controller error,
error in outdoor unit during ice thermal storage operation
HJ
J1
J3
J3
J5
J6
J6
J7
JA
JC
JF
JH
L0
L4
L5
622
Control
ED34-762
Control Devices
Operation
lamp
Maintenance
display
Malfunction
code
Error content
L6
L8
L9
LA
LC
or
M1
or
M8
or
MA
or
MC
P0
P1
P4
U0
U1
Unit No.
U2
U4
U5
U5
U6
U7
U7
U8
U9
UA
UC
UE
UF
UH
System fault
16
error codes (in outline font) do not display maintenance and the system will run, but please check the content
of the display and contact your dealer.
3P124623-3A
Control
623
Control Devices
4.4
ED34-762
(This optional accessory can not be used in conjunction with wiring adaptor for electrical appendices (optional
accessory).)
The groups of indoor units are as follows:
1. One indoor unit without remote controller
624
Control
ED34-762
Control Devices
C: 1P162827
Wiring Outline
Wiring Specification
Type
Size
H05VV-U3G
(Note 1)
Transmission Wiring
0.75-1.25mm2
Notes:
1. The size of power supply wiring must comply with the applicable national and local codes.
2. Allowable length of transmission wiring is as follows.
Max. 1000m (Total wiring length: 2000m)
Connect the wiring between indoor and outdoor units, indoor/outdoor units and power supply, and indoor units and
remote controllers.
For details, refer to the installation manuals of indoor and outdoor units.
Control
625
16
Control Devices
ED34-762
Note:
1. No branching is allowed after branching.
2. Use a relay terminal board (field supplied) to branch more than 3 control wires from the same terminal board.
626
Control
ED34-762
Control Devices
Note:
Do not connect the power supply wiring (100 to 240V) to the control terminal strip. If connected by mistake, it may
damage or burn electrical parts of optional controllers for centralized control and indoor unit. It may result in serious
danger. Be sure to check wirings before turning the power ON.
C: 1P162827
4.4.3 Dimension
Unified ON/OFF Controller
DCS301B(A)61
Unit (mm)
16
3D050339
Control
627
Control Devices
ED34-762
4.4.4 Installation
1. Open the upper part of remote controller.
Insert a minus screwdriver (2 locations) into the recess between the upper part and the lower part of remote
controller and twist the screwdriver lightly.
PC board is attached with both the upper and lower part of remote
controller. Do not damage the board with the screwdriver.
2. Open the upper part of remote controller and install the electrical box (part to be procured in the field) with the
attached installation screws (M416).
Note:
Suitable length of the electric wire is about 160mm from the inlet of the electrical box. If it is difficult to contain a long
wiring, strip the sheathed part of the wiring.
C: 1P162827
628
Control
ED34-762
Control Devices
1 to 16
Central Remote
Controller
Schedule
Timer
Unified ON/OFF
Controller
Central Remote
Controller
Schedule
Timer
1 to 4
(Note)
Not used
1 to 4
(Note)
Not used
Note:
For instructions on how to set the connector for setting master controller on the central remote controller, see the
installation manual provided with the central remote controller.
2. Switch for Setting Each Address (DS1)
These switches are used to set group control address.
Groups Nos. 1-00 through 1-15 are grouped in the same control group when the unit is shipped from the factory.
After setting, attach the number seal applicable to respective control range of the attached switch display sticker, as
shown in the diagram below.
(Example)
In The Case of 1-00 to 1-15, Attach .
16
Control
629
Control Devices
ED34-762
One of the two unified ON/OFF controllers (1) (2) is set to MAIN while the other is set to SUB.
4. Setting of the Sequential Operation Function
The unified ON/OFF controller is equipped with a sequential operation function that sequentially turns indoor units
on in 2-second intervals during unified operation. (Sequential operation is factory set to ON.) To switch
sequential operation ON or OFF, set as follows.
Note:
The sequential operation function is designed to reduce the load on the power supply equipment, but does not
guarantee that compressors will not be started simultaneously. You cannot therefore count on a capacity reduction
effect by power supply equipment breaker selection.
5. Control Mode Selector (DS2)
The following four patterns of control mode can be set.
Control Mode Individual
Centralized
Content
Operation/stop is controlled
by unified ON/OFF controller
only. (This unit can not be
operated/stopped by remote
controller.)
Operation/stop is
controlled by both unified
ON/OFF controller and
remote controller.
DS2 Setting
(Factory set)
Note:
Indicates the position of switches.
Set control mode before turning power supply ON.
When used in conjunction with central remote controller, the control modes of the central remote controller has
the priority.
6. Forced Reset Switch (SS1)
When changing the setting of the connector for setting master controller, etc., you can reset simply by setting it to
the reset side once and returning to the normal side, without turning the power OFF.
(For normal operation, set the switch to the normal side.)
C: 1P162827
630
Control
ED34-762
Control Devices
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
MODE
SETTING
TEST
2,6
Note:
For simplified remote controller, see the installation table.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
16
Control
631
Control Devices
4.5
ED34-762
If using the schedule timer alone, you dont have to set the centralized control group No. for group control.
Transmission Wiring
<Indoor Unit Wiring>
1. If using the schedule timer alone:
For the schedule timers power supply, connect the schedule timer (D1, D2) with the connector (X18A) on the
indoor unit PC board by crimped style terminal with the attached electric wire.
Transmission wiring for control: 0.75~1.25 mm2 sheathed vinyl cord or cable (2 wire) ..... Max. 1,000 m
(Total Max. 2,000 m)
<Transmission Wiring Connection Example>
1 series wiring, 2 bus wiring, and 3 star wiring are the same as with the central remote controller.
632
Control
ED34-762
Control Devices
4 6
7
8
DST301BA61
10
11
Fig. 1
12
15
14
16
17
16
DST301BA61
13
18
19
20
Fig. 2
3P124623-5C
Control
633
Control Devices
ED34-762
12
Press this button to select time No..
13
UNIFIED STOP BUTTON
2
(TIME NO.)
15
Press this button to select the day of the week.
HOUR/MINUTE BUTTON
TIMER ON BUTTON
18
Press this button to set holidays.
7
Flashes below the day of the week programmed.
19
DISPLAY
8
(MALFUNCTION CODE)
(PRESENT TIME)
9
Displays the present day of the week and time.
DISPLAY
(PROGRAMMED TIME OF
SYSTEM
START)
10
Displays the time programmed to start.
DISPLAY
(PROGRAMMED TIME OF
11 SYSTEM OFF)
Displays the time programmed to stop.
3P124623-5C
634
Control
ED34-762
Control Devices
4.5.4 Dimension
Schedule Timer
DST301BA61
Unit (mm)
3D049544
16
Attach the lower part to the electrical box (part to be procured in the field) with the provided installation screws.
(Select a flat face as an installation place. Do not tighten the installation screws excessively not to damage the
lower part of the remote controller.)
For part to be procured in the field electrical box, use KJB211A (optional accessory).
C: 3P162015A
Control
635
Control Devices
ED34-762
2. Initial Setting
1. Setting connector for individual use (X1A) (Factory set : OFF) (Set for individual use only)
For individual use of schedule timer
Insert the connector attached with the body case on the PC board.
For combined use with other optional controllers for centralized control
Do not change the factory setting.
2. Control mode selector (SS2) (Set for individual use only)
By changing the switch, setting mode of individual and centralized operation is available.
Note:
When used with other optional controllers, control mode of central remote controller and unified ON/OFF controller
have the priority.
3. Setting of the sequential operation function
The schedule timer is equipped with a sequential operation function that sequentially turns indoor units on in 2second intervals during unified operation.
(Sequential operation is factory set to ON.)
To switch sequential operation ON or OFF, set as follows.
Note:
The sequential operation function is designed to reduce the load on the power supply equipment, but does not
guarantee that compressors will not be started simultaneously. You cannot therefore count on a capacity reduction
effect by power supply equipment breaker selection.
4. Forced Reset Switch (SS1)
When changing the setting of the connector for individual use, etc., the switch can be reset simply by setting it to
the reset side once and returning to the normal side. This procedure enables to reset without turning off the
power. (Set the normal side at normal operation.)
C: 3P162015A
636
Control
ED34-762
Control Devices
3. Transmission Wiring
In case of individual use of schedule timer
Connect terminals of the schedule timer (F1, F2) with terminals of the indoor unit (F1, F2). Connect terminals of
the schedule timer (D1, D2) and the connector on the indoor unit PC board, using the attached electric wire and
crimp style terminals.
Prevent the connection part of crimp style terminal from getting out of the electric parts box of indoor unit.
In case of combined use with other optional controllers for centralized control
Connect terminals of the schedule timer (F1, F2, D1, D2) and the terminals of the central remote controller (or
unified ON/OFF controller).
Wiring Specifications
F1, F2
D1, D2
Wiring
Gauge
0.75-1.25mm2
0.75-1.25mm2
Length
Max. 1000m
Max. 150m
16
NOTES:
1. Electrical box and transmission wiring are not attached.
2. Do not touch the PC board with your hand.
3. Keep transmission wiring at least 50 mm away from power supply wiring to avoid malfunctions.
C: 3P162015A
Control
637
Control Devices
ED34-762
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
MODE
SETTING
TEST
2,6
Note:
For simplified remote controller, see the installation table.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
This schedule timer is provided with the malfunction diagnosing function. The malfunction code flashes if there
occurs any malfunction in communication, etc. between and among the optional controllers for centralized control. In
addition, the operation lamp also flashes if there occurs any malfunction in communication with the indoor unit. Check
the contents of the display and contact your DAIKIN dealer because the signals give you the idea of the trouble area.
638
Control
ED34-762
Control Devices
Operation lamp
Malfunction code
Contents of malfunction
Turn off
M1
Turn on or off
M8
Turn on or off
MA
Turn on or off
MC
Flash
UE
Malfunction of transmission between indoor unit and optional controllers for centralized
control.
Fixes
Inspect all indoor units which are displaying an error (e.g., power supply, transmission
wiring, etc.).
Flash
Malfunction in indoor unit (Refer to the malfunction codes of the indoor remote controller,
while also read the CAUTION FOR SERVICING attached to the indoor unit.)
3P124623-5C
16
Control
639
Control Devices
4.6
ED34-762
Independent
and centralized
control of HRV
is possible.
Connectable number of
centralized control
equipment
Central remote
contoroller
2 units
Unified ON/OFF
8 units
contoroller
Schedule timer
1 unit
Forced
shut-down
input
Central remote
controller
(DCS302CA61)
Central control
adaptor kit
(DTA107A55).
Wiring adaptor
for other airconditioners
(DTA103A51)
Outdoor-air
processing
unit can be
connected.
Up to 2 units
connectable
6 cores
Schedule timer (DST301BA61)
1 unit connection possible ;
8 weekly schedule control patterns possible
640
7 cores max.
Control
ED34-762
Control Devices
You can freely combine the central controllers within the limitation of the following number of each controller; 1~4
units of central remote controllers, one unit of schedule timer and 1~16 units of unified ON/OFF controllers.
However, the maximum number of the indoor units to be controlled is 128 units for one system in any combination of
the central controllers.
Connection Pattern for Optional Controller for Centralized Control
Central Remote Controller
DCS302CA61
1~16
1~4
The maximum number of indoor units is based on one unit in each zone and is also under the double central control
system.
F1F2
Power Supply
220~240VAC
F1F2
T1T2 D1D2
No.3
F1F2
HRV
F1F2
P1P2
Unified ON/OFF
Controller
F1F2
P1P2
P1 P2
Power Supply
220~240VAC
F1F2
Remote
Controller
P1 P2
F1F2
F1F2
P1P2
Unified ON/OFF
Controller
F1F2
P1P2
P1 P2
Power Supply
220~240VAC
P1 P2
F1F2
T1T2 D1D2
No.2
Remote
Controller
F1F2
P1P2
56
F1F2
P1P2
Remote Controller
F1F2
F1F2
T1T2 D1D2
No.1
F1F2
F1F2
P1P2
Unified ON/OFF
Controller
F1F2
P1P2
F1F2
P1P2
F1F2
P1P2
Interface
Adaptor
for SkyAir
Series
F1F2
F1F2
Wiring adaptor
for other air
conditioners
F1F2
Power Supply
220~240VAC
Remote Controller
16
F1F2
D1D2
Schedule Timer
Power Supply
220~240VAC
D1D2
T1T2
F1F2
X2A
Note) Diagram with an outdoor unit omitted for air-conditioners for Sky Air installation.
Control
641
Control Devices
ED34-762
642
Control
ED34-762
4.7
Control Devices
4.7.1 Feature
This controller is a central remote controller offering higher functions than those of the previous controller
DCS302C(A)61, and easier operation.
Up to 64 groups of indoor units may be connected to 1 unit of this controller.
This controller aims to be a product positioned between the current central
controlling device (central controller DCS302CA61) and the controller
D-BIPS for large scale buildings (in both the viewpoints of application area
and functional grade), and is a central controller most suitable for middle
and small size buildings.
< Products Features >
1. High Level Functions
Annual schedule control
Electricity proportional distribution function (option)
Air net function (DCS601C51 only)
2. Easy Operation
Color liquid crystal
Icon display
Touch panel application
Air conditioner name and zone name input available
3. D-III NET 1 line (64 units)
4. Saving expenses
Controlling personnel not required (saving control expenses)
Energy saving schedule
Functions equal to those of a compact monitor panel
(V2318)
Operation Menu
intelligent Touch Controller is capable of starting/stopping of the operation by the group or zone. Collective
starting/stopping is also available.
Air Conditioner Detail Setup
Temperature setting, switching between temperature control modes, switching of speed and direction of wind and
remote control mode setting are available by the group, by the zone or collectively.
Monitoring of Various Information on Indoor Units
Information on operation such as the operation mode and temperature setting of the indoor units, maintenance
information including the filter or element cleaning sign, troubleshooting information such as error codes can be
displayed by the group or the zone.
Diversified Operation Modes
Operation can be controlled both with the main unit and the remote control to provide diversified operation
management. Setting with the main unit allows the following remote control settings by the group, by the zone or
collectively:
1. Start/Stop
2. Operation Mode
3.Temperature Setting
:(Remote control) Inhibited
:(Remote control) Inhibited
:(Remote control) Inhibited
:(Remote control) Permitted
:(Remote control) Permitted
:(Remote control) Permitted
:Priority
Zone Control Simplifying Complicated Setting Operations
Up to 64 groups can be controlled with the intelligent Touch Controller.
More than one group can be consolidated into a zone, which can be registered, to allow the following settings by
the zone. This eliminates the need for repeating the same setting operation for each group. Function to allow
collective setting for all groups is also available.
Start/stop
Temperature setting
Switching between operation modes
Setting of direction and fan speed Disabling/enabling the remote control
Detailed Scheduled Operation Control
The intelligent Touch Controller allows detailed scheduled operation by the group, by the zone or collectively. Up
to 8 options for annual schedule can be set. Each schedule can include four types of plans : for Monday,
Tuesday... Sunday, Special day 1~10, Special days 1 and Special days 2. Each of the plans allows setting of up
to 16 operations.
Handy Automated Control
The intelligent Touch Controller can do the following.
Change Over Settings : automatically switches between cooling and heating according to the room
temperature.
Temperature Limit Setting : prevents the temperature from rising too high or too low in unmanned rooms.
Heating Optimization Settings : stops uncomfortable hot air from blowing when the heating the thermo is off.
Control
643
16
Control Devices
ED34-762
Indoor unit
or
Remote control
No remote control
Remote control
Remote control
Up to 16 units
Up to 16 units
Zone 2
Zone 3
Zone 4
Zone 5
One setting makes the same setting for all of the units in one zone.
Up to 128 zones can be set with one intelligent Touch Controller.
(The maximum number of groups in one zone is 64.)
Groups can be zoned at will with the intelligent Touch Controller.
Units in one group can be divided into more than one zone.
3P073677-12R
Outdoor unit
In-Out Out-Out
F1, F2 F1, F2
Outdoor unit
In-Out Out-Out
F1, F2 F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
Up to 16
Remote control
Note
Up to 64 groups
When the optional power distribution function
is used, up to 64 indoor units can be connected.
644
Control
ED34-762
Control Devices
4.7.4 Options
Connecting Unification adaptor allows using the contact for normal and abnormal operation signal and collective
start/stop with a contact. For details, contact the vendor you purchased the product from.
Also, by connecting DIII NET-plus adapter, it is possible to operate and monitor the indoor units of 64 groups (intelligent
Touch Controller plus DIII NET-plus adapter-128 groups in total) additionally.
Monitoring from PC is possible by Web E-mail functions.
(Optional intelligent Touch Controller Web Software is necessary)
Outdoor unit
F1,F2
F1,F2
F1,F2
Up to 16 units maximum
LAN F1,F2
CN2
Up to 64 groups maximum
(The number of connectable indoor units is up to 64
units maximum, where the Power Proportional
Distribution Card as option is used.)
Fuse(10A) switch
L
N
Power supply
Grounding work 100 - 240 VAC
LN
RS-232C
50/60 Hz
Force stop command
Outdoor unit
F1,F2
F1,F2
F1,F2
Up to 16 units maximum
Up to 64 groups maximum
(The number of connectable indoor units is up to 64
units maximum, where the Power Proportional
Distribution Card as option is used.)
3P073677-12R
4.7.5 Specification
Specification
Power
Power consumption
10 W maximum
Normally-open contact
Contact current approximately 10 mA
Operating temperature
range
Ambient temperature
0C~40C
Ambient humidity
Storage temperature
range
Ambient temperature
-10C~50C
Ambient humidity
Size
230147107 (WHD)
Weight (Mass)
1.2kg
16
Dimension
50
57
90
147
230
The specification and appearance of the product may be modified for improvement without prior notice.
C : 3P073677-12R
Control
645
Control Devices
ED34-762
Touch Pen
NOTE
Be sure to use the touch pen for operation of the touch panel of the intelligent Touch Controller.
Operating with an object other than the touch pen provided may cause damage and failure.
3P073677-12R
LINE
PHONE
RS-232C
LAN
COM Dil
F2
F1
L0
N
L
100 - 240V
When monitoring and operating the indoor units using the optional Web and
E-mail function software sold separately, connect to LAN via Ethernet cable.
Terminal block for watt hour meter and force stop input of indoor units
This is used when distributing the power supply to indoor units using optional Power Proportional
Distribution software sold separately and when stopping the indoor units compulsorily by contact input.
The size of terminal block is M3.5.
3P073677-12R
646
Control
ED34-762
Control Devices
Filter/Element Sign
Displayed when there is any air conditioner
showing a filter or element sign in the zone
or the group.
Zone/Group Name
Set the names in the Group Registration or
Zone Registration in the System Setup
Mode.
Description of Zone/Group
Set the names in the Group Registration or
Zone Registration in the System Setup Mode.
16
Scroll Buttons
Up/Down scroll button used when monitoring zone/group which are not currently displayed.
Left/Right scroll button used when monitoring temperature and errors etc.
Which are not currently displayed.
EM04A055A
Control
647
Control Devices
Filter/Element Sign
ED34-762
Zone/Group Name
Set the names in the Group
Registration or Zone Registration
in the System Setup Mode.
Cool 20.0 C
Room 16.7 C
Cool 20.0 C
Room 16.4 C
Cool 20.0 C
Room 16.4 C
Cool 20.0 C
Room 16.4 C
Cool 20.0 C
Room 16.7 C
Cool 20.0 C
Room 16.4 C
Cool 20.0 C
Room 16.4 C
Cool 20.0 C
Room 16.4 C
Scroll Buttons
648
Control
ED34-762
Control Devices
List
Contents of the List Currently Displayed
When Group List is displayed
Zone: Zone Name
When Zone List is displayed
Zone List
Zone/Group Name
Set the names in the Group
Registration or Zone Registration
in the System Setup Mode.
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Filter/Element Sign
Displayed when there is any air
conditioner showing a filter or
element sign in the zone or the
group.
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
Cool
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
20.0 C
16
Scroll Buttons
Control
649
Control Devices
ED34-762
1P153198C
650
Control
ED34-762
Control Devices
16
1P153198C
Control
651
Control Devices
ED34-762
1P153198C
652
Control
ED34-762
Control Devices
16
1P153198C
Control
653
Control Devices
ED34-762
Main Functions
Power proportional distribution results data can be saved for 12 months. (max. 12 months and 30 days)
Per intelligent Touch Controller, power proportional distribution can be calculated for 64 indoor units at maximum.
When DIII-NET Plus Adaptor is connected, power proportional distribution can be calculated for more 64 indoor
units at maximum (a total of 128).
3 Electric power meters at maximum can be connected to an intelligent Touch Controller.
When DIII-NET Plus Adaptor is connected, more 3 Electric power meters at maximum (a total of 6) can be connected.
Power proportion distribution results data can be saved into a PCMCIA card.
Data is saved CSV format generally applied to personal computers, so bills can be issued by use of a general
purpose table calculation software package in easy manners.
(A personal computer and a general purpose table calculation software package can be available separately.)
Precautions
This system calculates electricity consumptions by size of indoor units, run time, expansion valves open gap, suction rate
and the number of pulses from the power meters installed at the Outdoor Units.
This method is not calculated by direct measurement alone.
Electric power meter (with pulse output)
123
123
123
Outdoor
unit
DIII-NET1
Indoor unit
PCMCIA card slot
Power Proportional
Distribution Card
123
An existent personal
computer of a user
can be available.
Bills
Maximum of 64
Indoor unit
123
Maximum of 3 Electric
power meter
123
Outdoor
unit
DIII-NET1
Indoor unit
Maximum of 64
Indoor unit
EM04A056
654
Control
ED34-762
Control Devices
Checking Attachments
Power Proportional Distribution Card includes the following attachments.
Software ID
EM04A056
How to Connect
To activate the power proportional distribution function, it is necessary to set the
program by use of the attached PCMCIA card and carry out a trial operation.
Before use, consult your supplier.
EM04A056
16
Control
655
Control Devices
ED34-762
3PA34878C
656
Control
ED34-762
4.8
Control Devices
BRC1D61
4.8.1 Dimension
Wired Remote Controller with Weekly Schedule Timer BRC1D61(9)
Unit (mm)
16
3D048117
Control
657
Control Devices
ED34-762
3P107422-3D
658
Control
ED34-762
Control Devices
3P107422-3D
16
Control
659
Control Devices
ED34-762
3P107422-3D
660
Control
ED34-762
Control Devices
3P107422-3D
16
Control
661
Control Devices
ED34-762
4.8.5 Installation
3P107422-4D
662
Control
ED34-762
Control Devices
16
3P107422-4D
Control
663
Control Devices
ED34-762
3P107422-4D
664
Control
ED34-762
Control Devices
3P107422-4D
Control
665
16
Control Devices
4.9
ED34-762
Data indication
System Setting
Operation / Stopped
Basic Setup
Air-Conditioning
Network Service System
(Optional Maintenance Service)
Printing
History
Statistics
Setting info.
Remote Access
Remote connection
WatchDOG
Multiple Language
Operation (individual / group)
Start / Stop
Setting
(Operation mode / Fan speed /
Remote Ct'rl mode /
Maintenance mode / Filter sign
clear / Fan direction)
Indication
Manage group (Cell display)
Control group (Cell display)
Visual Navigation
(Graphical display)
Table
English
French
Automatic Controls
Schedulel
Interlocking
(standard / Emergency stopr )
Eco Mode
Power Limit Control
Auto change over
Sliding temperature (External kit
required)
Temperature limit
Power Failure control
Italian
German
Spanish
Chinese
other
Security (30 users Max / Flexible access Authority )
History(realtime data / saved data )
Set point limitation
Multiple PC (accessible from
different PCs)
OnLine Help
Compatibility with Windows 2000
Measurement
Accurate operate time
Number of switching times
Consumption power
Room temperature
Outdoor temperature
666
Control
ED34-762
Control Devices
Remote
Manager
Remote Access
Via Modem
Remote Monitoring
Via Modem
Remote Access
Remote Monitoring
Via LAN
Air-Conditioning
Network Service System1
Optional Maintenance
Service
Via Internet
Ethernet
Contact Signal
DAM602B512
DAM602B512
DAM602B512
Security
DAM602B512
Fire alarm
iPU
Outdoor
Unit
NEW
Di Unit DEC101A51
Dio Unit DEC102A51
Indoor Unit
Remote
Controller
NEW
HRV
Light
2
3
Fan
DAM101A51
Daikin Central
Air Conditioning System
[Air-conditioning systems]
Pump
Maximum of 64 Groups
Wiring adaptor required for
connection with other
equipment not compatible
with
D Ai unit
There are restrictions in applicable areas and release times, therefore please consult us separately for details.
Model no varies upon the system size.
Interfacing requirements vary depending on model, and some systems may not be suitable. Please contact your distributor for details.
IM-128
IM-256
IM-512
IM-768
IM-1024
128
256
512
768
1024
20
40
80
120
160
DAM602B513
DAM602B514
Local Procurement
DAM602B52
DAM602B511
DAM602B512
Yes 2
1 Products name is recognized as an order number. This includes hardware, software and field engineering work
as a package.
2 kWh meters to be locally supplied.
3 With the PPD system, data is transferred from the indoor units and compared with reference data on the
standard power consumption of air conditioning equipment under normal conditions.
The results are used to estimate the power consumption of each indoor unit. Note, however, that this
measurement method is exclusive to Daikin and has no legal basis.
Control
667
16
Control Devices
ED34-762
<Use of Printers>
1. Standard Setting: With only the page printer: Parallel port connection
- Printing of daily, monthly, annual reports and cost calculations: Automatically prints at the set time
- Display of errors and changes of states etc.: Printer at error or at determined build up of data, or freely.
2. 2 Units of Page Printer and Line Printer (Optional)
* Page printer: Network connection
- Daily, monthly, annual reports: Automatically prints at the set time
- Cost calculation
Connecting to iPU
Wiring varies according to the equipment to be connected, as shown below.
* DIII-NET Compatible Air Conditioners
668
Control
ED34-762
Control Devices
16
Control
669
Control Devices
ED34-762
1P177851A
670
Control
ED34-762
Control Devices
1P177851A
16
Control
671
Control Devices
ED34-762
1P177853
672
Control
ED34-762
Control Devices
1P177853
Control
673
16
Control Devices
ED34-762
System Diagram
6
1
HUB
iPU
(It is provided from DIL)
Outdoor
Unit
8
WHM
10
7
Indoor
Unit
3
AC
PC
UPS
UPS
Recommendations
We recommend makers such as
IBM, Compaq or Dell, etc.
APC
SU700, SU1000 Series
+ Relay I/O
module(AP9610)
WHM
other 10
674
Requirement Specifications
1 [Hardware]
CPU : Pentium 300MHz minimum,
500MHz or above recommended
Memory : 64MB or above
HDD : 4GB minimum, 8GB or above
Keybord/Mouse
Network : 10Base/T
SVGA (800600)
Monitor (15,17)
Sound & Speaker
[Software]
Windows NT 4.0 (SP4)
Windows 2000
Windows XP
[Other equip.]
LBP (not indispensable.)
2
- It must be supported by WindowsNT.
- Require A4 size paper
Network 6
Equip. 7
Indoor
Unit
D3network cables
Remarks
In the case of an
alternative maker,
correct operation should
be checked before
shipment.
Control
ED34-762
Control Devices
4.9.7 Functions
Local Functions
Item
Description
Monitoring
Operation status monitoring for a maximum of 1,024 indoor units(160 outdoor units), when
4 iPUs are connected;
Air Conditioning Network Service System: Air conditioner failure prediction (optional);
Continuous operation time monitoring (per management point); Power failure monitoring
Control, Operation,
and Settings
Login setting; Individual control; group switching/ setting of control group (200 groups);
Schedule control (200 programs); Fire emergency stop control (32 programs); Power
failure/ release control
(selected from 5 power restoration modes); Air conditioner centralized control
Display
Management point name/icon/list display; Control group list display; Screen scroll function;
Operation time display; Integrated switching number display; History display
(malfunctions, alarms, control)
Measurements
Operation time integration; Switching number integration; Meter reading (through Pi port
on iPU);
Power proportional reading
Management
Operational history management; Generation of daily, monthly and yearly reports; VRV
power proportional distribution
Data Storage/
Report
Warning
If exceeding the stated number of outdoor units, Dlll-NET Expander Adapter <DTA109A51> allows easy system
connection as long as restrictions are observed.
16
Control
675
Control Devices
ED34-762
WHM
VRV K series
WHM
VRVII MA series
Subject Model
DCS601C51
DCS002C51
DAM602B51, 52
DAM002A51
WHM
VRV K series
Heat Recovery
WHM
VRVII M series
Heat Recovery
WHM
VRV L-series
WHM
VRVIII P series
Reason
Such equipments as i-touch-Controller implementing PPD cannot distinguish heat
recovery type from energy saving type to which they are connected. Therefore, if the
capacity of each indoor unit is the same, the result of proportional distribution becomes
the same as that of other VRV.
(No effect of energy saving is reflected on the calculation result.)
676
Control
ED34-762
Adaptor
5. Adaptor
5.1
5.1.1 Function
When connected to the central remote controller, this kit enables unified display (operation/malfunction) and unified
control (operation/stop).
1. Unified Display
2. Unified Control
16
C : 2PA53489
Control
677
Adaptor
ED34-762
5.1.3 Installation
Securely install the adaptor inside the electric panel box (field supplied) with the 4 attached screws.
Install the adaptor in a place within 5 m from the central remote controller to enable cable connection.
Note
1. Do not damage the PC board with your screwdriver, etc.
2. Install the adaptor inside an electric panel box to protect from electromagnetic waves and dust.
C : 2PA53489
678
Control
ED34-762
Adaptor
2PA53489
16
Control
679
Adaptor
ED34-762
Input A
OFF ON: Unified Operation
Input A
Input B
(3) Do not set the switch to position 1. This switch can be set at any time.
3. Fetching the Display Signal
Terminals W1 - W4 are non voltage contacts used in normal operation to output operation display (W1 and W2) and
malfunction display (W3 and W4) signals.
(The allowable current per contact is 10 mA - 3A.)
Note:
When using a 200-240 V power supply, keep power supply wiring away from wiring of input side.
Output conditions are indicated as below.
When Ry1 and Ry2 are OFF
All indoor units are stopped.
680
Control
ED34-762
5.2
Adaptor
Per group
Note:
1. Individual indoor units connected to the centralized line cannot be displayed individually.
2. For wiring adaptor for electrical appendices (2) <KRP4A51, 52, 53, 54>, refer to page 688.
16
C : 1PA63641G
Control
681
Adaptor
ED34-762
1PA63641G
5.2.3 Installation
Ceiling Mounted Cassette Corner Type
FXC(Q)
FXYCP
FXK(Q)
FXYKP
FXF(Q)
(KRP2A62)
C : 1PA63641G
682
Control
ED34-762
Adaptor
FXM(Q)200 250
FXYMP200 250
FXM(Q)40~125
FXYMP40~125
FXS(Q)
FXYSP
FXYB
FXH(Q)
FXYHP
Note :
Installation box is necessary for second adaptor (FXS (Q)) .
FXD(Q)
FXL(Q), FXYLP
FXN(Q), FXYLMP
16
FXA(Q)
KRP2A61
C : 1PA63641G
Control
683
Adaptor
ED34-762
1PA63642B
684
Control
ED34-762
Adaptor
Function
Function
Central priority
16
Note:
Input B is for forced-OFF. When ON, stop + remote controller is rejected, and input A is ignored. When OFF, even
if A is ON, the contents of when input A is ON, are not achieved. Input A must therefore be re-input.
C : 1PA63642B
Control
685
Adaptor
ED34-762
Function
Contents of Input A
Function of Input B
Function
Central Priority
Remote Controller
Acceptance/Rejection
Note:
Doing constant input A with position 7-A, it will be forced OFF function (input A is ignored).
Constant input cannot use for input B with position B.
1PA63642B
686
Control
ED34-762
Adaptor
Temperature setting corresponds to resistance values in the range of 0 to 135. Their relationship is as shown below.
Temperature Setting
(C)
16
17
18
19
20
21
22
23
24
Resistance ()
0.0~3.4
5.0~11.6
13.8~20.0
22.4~28.4
31.0~36.4
39.4~44.8
48.2~52.8
56.6~61.2
65.2~69.4
Temperature Setting
(C)
25
26
27
28
29
30
31
32
Resistance ()
73.8~77.8
82.4~85.8
91.0~94.0
99.4~102.2
108.6~110.4
117.2~119.2
125.8~127.4
134.2~140.0
Note:
Wiring resistance included in above figures.
(Wiring specifications)
Wiring ... Sheathed wire
Gauge ... 1.25~2.00 mm
Length ... Max. 70 m
(IMPORTANT)
Keep transmission wiring at least 50 mm away from power supply wiring to avoid malfunctions.
Note:
If using a 220~240V power supply, keep transmission wiring at least 50 mm away from incoming power supply wiring.
Output
System
Ry1 only ON
At least one unit running normally, no
malfunction
Ry2 only ON
Even 1 unit stopped due to malfunction
or malfunction of transmission between
adaptor and indoor unit
Control
687
16
Adaptor
5.3
ED34-762
Note:
1. This adaptor cannot be used together with central control equipment and data station.
2. The model of adaptor differs according to the type of indoor unit to be installed.
Applied Model
Remark Note
SkyAir Series
Room Air-Conditioner
Other Air-Conditioner
VRV II Series
HRV Unit
Note:
1. Marked
shows wiring adaptor for electrical
appendices.
2. Marked
indicates the same control range.
3. The wiring adaptor for electrical appendices (2) can
control simultaneously the group of the units (Max. 16
units) connected to the remote control wiring line (P1,
P2). In another words, all the units connected between
P1 and P2 terminal have the same control.
688
Point of wiring
Control
ED34-762
Adaptor
Note:
1. This is valid only for the indoor unit, which has a temperature setting function.
2. Terminal No. X18A is for the indoor unit of VRV system. For SkyAir series and other air-conditioner, connect to
the relevant terminal for each units.
16
The normal operation output terminals (W1, W2) and error output terminals (W3, W4) are non-voltage output
contacts. (Permissive current is 10mA~3A per contact.)
Control
OFF
689
Adaptor
ED34-762
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
0.0
~
3.4
5.0
~
11.6
13.8
~
20.0
22.4
~
28.4
31.0
~
36.4
39.4
~
44.8
48.2
~
52.8
56.6
~
61.2
65.2
~
69.4
73.8
~
77.8
82.4
~
85.8
91.0
~
94.0
99.4
~
102.2
108.6
~
110.4
117.2
~
119.2
125.8
~
127.4
134.2
~
140.0
Note:
The value of resistance includes the resistance of wiring.
The setting temperature is limited within the setting range of indoor unit. If you set the temperature outside of the
range by the adaptor, it controls at the nearest setting range.
Setting of Control Mode Selector Switch (RS1)
Description of Operation by Input Mode A and B
Position
Functions
Input A (Between B1~Bc)
Input Ignored
Central Priority
Start/Stop (Repeats)
Start at ON
Stop at ON.
Stop at ON
(remote control rejection)
Start at ON
(remote control acceptance)
The same as position 7
(Only stop is accepted by remote controller)
Start at ON
(remote control acceptance)
The same as position 7
(remote control acceptance all the time)
Stop at ON
(remote control rejection),
Input A acceptance at OFF
Note:
1. When constant input is used for input B at position 7~A, the system is shut-down forcibly (Ignored input A).
Constant input cannot be used for input B at position B.
2. Refer to the followings for the outline of above functions.
690
Control
ED34-762
Adaptor
when you want to turn ON only by the central remote controller, and
2. Remote controller OFF Only Accepted ...... For
turn OFF only by remote controller for indoor unit.
when you want to turn ON only by the central remote controller, and
3. Central Priority ............................................... For
during the set time, turn ON/OFF freely by remote controller for indoor unit.
For when you want to turn ON/OFF by both central remote controller and
4. Individual Priority (Last command priority) ... remote
controller for indoor unit.
For when you want to turn ON/OFF by remote controller for indoor unit
5. Remote Controller Permission Timer ........... during set time, and you want to start the operation by remote controller for
indoor unit at the programmed time of system start.
<Example when the control mode selector switch is set at position 6>
The following is the time chart for the command by remote controller and the indoor unit against input signal.
16
Control
691
Adaptor
ED34-762
Note :
Installation box is necessary for second adaptor (FXS) .
Note:
The above shows the installation for VRV indoor unit. For the SkyAir series and other air-conditioner, it may be
different from the ones showed above and refer to its engineering data for the details.
C : 1PA59889H
692
Control
ED34-762
Adaptor
Note:
The above shows the installation for VRV indoor unit. For the SkyAir series and other air-conditioner, it may be
different from the ones showed above and refer to its engineering data for the details.
C : 1PA59889H
16
Control
693
Adaptor
5.4
ED34-762
5.4.1 Accessories
Check if the following accessories are included in the kit.
Adaptor
Relay Harness
x1
x1
PC Board Support
x4
Tie Wrap
x2
Installation Manual
x1
Note:
1. Wiring specifications ... Use a 0.75 - 1.25 mm sheathed vinyl cord or cable (2 wire).
2. For details on compatible systems and how to connect to optional controllers, see the instruction manual of the
optional controller and technical reference materials.
1PA59896
694
Control
ED34-762
Adaptor
5.4.5 Installation
Installation differs according to models as shown below.
Do not bundle low and high voltage wires together.
Bundle any excess wires with the attached tie wraps so as to keep loose wirings off the indoor unit PC board.
16
C : 1PA59896
Control
695
Adaptor
ED34-762
Indoor PC Board
Control Box
Adaptor
PC Board Support
(V2438)
C : 1PA59896
696
Control
ED34-762
5.5
Adaptor
2P042157
16
Control
697
Adaptor
ED34-762
2P042157
698
Control
ED34-762
Adaptor
16
2P042158A
Control
699
Adaptor
ED34-762
2P042158A
700
Control
ED34-762
5.6
Adaptor
5.6.1 Function
This kit contains an I/O interface adaptor for optional controller for centralized control, used when there is a nonconnectable air conditioner. When connected to the central control line, this adaptor enables operation/stop and
display of operation/error monitors from the optional controller.
5.6.3 Installation
Securely install the adaptor with the attached installation screw.
Note:
Install the adaptor inside a control box of outer dimensions: 230W 230D 60H.
Supply a control box at site with outer dimensions equal to or larger than those shown below. 230W 230D 60H.
16
1. Wire between the adaptor and central control equipment (F1, F2)
2. Wire to the connected units and set all switches. ... For details, refer to WIRING TO CONNECTED UNITS.
3. Wire to the power supply. ... For details, refer to POWER SUPPLY WIRING.
C : 2PA53853
Control
701
Adaptor
ED34-762
<General Instructions>
All wiring, components and materials to be procured on the site must comply with the applicable local and national
codes.
Use copper conductors only.
All field wiring and components must be provided by licensed electrician.
Unit shall be grounded in compliance with the applicable local and national codes.
Fit the power supply wiring with a fuse and a switch.
After wiring work, check power to the equipment shuts OFF when the switch is shut OFF.
<Wiring Specification>
Type
Size
H05VV-U3G
(Note 1)
Transmission Wiring
(Note 2)
0.75 - 1.25 mm
Note:
1. Select the size in electric wire in accordance with the local and national standards.
2. You can use the shielded wire, sheathed vinyl cord or cable (2 conductors). See the installation manual of the
optional controllers for centralized control to be connected for further details.
Max. current
Min. Current
1~50Hz 220-240V
1~60Hz 220V
2A
1mA
5-24V
3A
1mA
Output modes include instantaneous output and constant output. Mode is changed at the contactor switch (SS4).
(Factory set: INS)
C : 2PA53853
702
Control
ED34-762
Adaptor
Monitor Input
Wire as explained here following, depending on whether input carries a voltage (VOLT.) or not (NON VOLT.). Make
the VOLT/NON VOLT. setting at the monitor input changeover switch (SS1).
c Switch the malfunction signal switch (SS3) according to needs (Factory set: W/O [OFF]). Set the switch to W (ON)
to display errors even if no operation feedback from the indoor unit is available, for example, when power to the
indoor unit is OFF. Together, set the individual switch (SS2) to OFF (ON).
Note:
This switch is ineffective when SS2 is set to ON (OFF).
The optional controller display will change, as shown on the right, depending on the monitor input state and the
malfunction signal switch (SS3) setting.
After switching the optional controller from stop to operation, it will take from 10 to 30 seconds before the optional
controller display will indicate an error.
Optional Controller Display at Command Output
(SS3) Malfunction
Signal
W
W/O
Operation Display
Error Input ON
16
2PA53853
Control
703
Adaptor
ED34-762
d Set the group No. at the central control group No. setting switches (RS1 and RS2). Refer to the below table to set
group No. Group No. increases in the order of 1-00, 1-01 ... 1-15, 2-00, ... 4-15. Refer to the installation manual of
the optional controller.
RS1 Switch Setting and Upper Group No. Position
Position
Group No.
Group No.
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Note:
Ground wires as shown in the figure on the right.
The adaptor may malfunction or be damaged if improperly wired.
The fuse is designed for short-circuit protection (Overcurrent protection).
Therefore, it may not offer sufficient protection against improper voltage.
2PA53853
704
Control
ED34-762
5.7
Adaptor
53
16
C : 1PA63164D
Control
705
Adaptor
ED34-762
C : 1PA63164D
BS Unit
706
Control
ED34-762
Adaptor
16
C : 1PA63164D
Control
707
Adaptor
ED34-762
Note:
Installation box for adaptor PCB is required to install the adaptor.
C : 1PA63164D
708
Control
ED34-762
Adaptor
16
Control
709
Adaptor
ED34-762
[Input signal]
Constant a contact
Input current is approx. 10 mA per contact.
For the relay contact, use a weak current contact.
[Outside wiring specifications]
Recommended wiring: 0.75-2 mm2 sheathed wire
Wiring length:
Within 150 m
Keep a minimum 50 mm from power supply wiring to prevent malfunction.
Demand input terminal
Short circuit between (Demand 1) - (C)...As a guideline, demand should be about 70%.
Short circuit between (Demand 2) - (C)...As a guideline, demand should be about 40%.
Short circuit between (Demand 3) - (C)...Forced thermo OFF
Low-noise input terminal
When terminals are short-circuited during cooling, capacity save (outdoor unit fan low-speed turn, compressor
frequency control) is carried out.
use only at night when load is slight.
How to set demand control in the field
1. Outdoor unit field setting
Setting mode 1...Turn ON low noise control as explained in the outdoor units service manual.
Setting mode 2...Match low noise and demand addresses to the external control adaptor address.
2. External control adaptor settings
Function switch (SS1)
Set SS1 to either BOTH or DE.
Address setting switch (DS1,DS2)
Match DS1 and DS2 to the low noise and demand addresses of the outdoor unit.
710
Control
ED34-762
5.8
Adaptor
16
C : 2PA61563C
Control
711
Adaptor
712
ED34-762
Control
ED34-762
5.9
Adaptor
16
JC : 2PA58148A
Control
713
Adaptor
ED34-762
3P011730B
714
Control
ED34-762
Adaptor
1P013360
Control
715
16
Adaptor
ED34-762
1P013360
716
Control
ED34-762
Adaptor
16
C : 1P013360
Control
717
Control Functions
ED34-762
6. Control Functions
6.1
C : 3P171361-1
BRC1C62
Model
Type
R-410A
FXCQ
FXFQ
FXKQ
FXHQ
FXAQ
FXUQ
FXDQ
FXSQ
FXMQ
FXLQ
FXNQ
Notes
1 : BRC1C62...Kits for General Market
718
Control
ED34-762
1. On/off button
Press the button and the system will start. Press the
button again and the system will stop.
2. Operation lamp (red)
The lamp lights up during operation.
3. Display
(changeover under control)
It is impossible to changeover heat/cool with the remote
controller which display this icon.
4. Display
(air flow flap)
5. Display
(ventilation/air cleaning)
This display shows that the ventilation unit are in
operation. (these are optional accessories)
6. Display
C (set temperature)
This display shows the temperature you have set.
7. Display
(operation
mode)
This display shows the current operation mode.
8. Display
(programmed time)
This display shows the programmed time of the system
start or stop.
TEST (inspection/test operation)
9. Display
When the inspection/test operation button is pressed,
the display shows the mode in which the system
actually is.
10. Display
(under centralized control)
When this display shows, the system is under
centralized control. (This is not a standard
specification.)
11. Display
(fan speed)
This display shows the fan speed you have selected.
12. Display
(time to clean air filter)
13. Display
(defrost/hot start)
14. Timer mode start/stop button
15. Timer on/off button
16. Inspection/test operation button
This button is only used by qualified service persons for
maintenance purposes.
Control Functions
C : 3P171361-1
16
Control
719
Control Functions
ED34-762
720
Control
ED34-762
Control Functions
Notes:
1. Setting is carried out in the group mode. however, if the mode number inside the parentheses is selected, indoor
units can also be set individually.
2. The SECOND CODE number is set to
when shipped from the factory.
3. Not displayed if the indoor unit is not equipped with that function.
4. When returning to the normal mode. 88 may be displayed in the LCD in order for the remote controller to initialize
itself.
5. : Setting the static pressure selection for FXD (Q)
SECOND CODE NO.
01 (Factory Setting)
FXD
20 Pa
49 Pa
FXDQ
15 Pa
44 Pa
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
MODE
SETTING
TEST
2,6
Note:
For simplified remote controller, see the following.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
16
Control
721
Control Functions
ED34-762
Measure: Notify your Daikin dealer and inform him/her of the display.
2. If the system does not properly operate except for the above mentioned case, and none
of the above mentioned malfunctions is evident, investigate the system according to the
following procedures.
1. If the system does not operate at all.
Check if there is a power failure.
If power failure occurs during operation, the system automatically restarts immediately after the power supply
recovers.
2. The system goes into FAN OPERATION, but as soon as it goes into HEATING or COOLING OPERATION, the
system stops
Check if the air inlet or outlet of outdoor or indoor unit is blocked by obstacles.
Check if the remote controller display shows
(TIME TO CLEAN AIR FILTER). Ask a qualified service
person to clean the air filters.
3. The system operates but it does not sufficiently cool or heat.
Check the below matters.
If the thermostat setting is too high or too low.
If the air inlet or outlet of the indoor or the outdoor unit is blocked with obstacles.
If the doors or the windows are open.
If the FAN SPEED button is set to LOW SPEED
.
If there are too many occupants in the room during cooling operation.
If the heat source of the room is excessive.
If direct sunlight enters the room.
722
Control
ED34-762
Control Functions
16
Control
723
Control Functions
ED34-762
The PC board is mounted in the upper part of remote controller. Be careful not to
damage the board with the minus screwdriver.
For the field supplied switch box, use optional accessories KJB111A or KJB211A.
Note:
Choose the flattest place possible for the mounting surface. Be careful not to distort the shape of the lower part of
remote controller by over-tightening the mounting screws.
2PA52602C
724
Control
ED34-762
Control Functions
Wiring Specifications
Wiring Type
Size
0.75 - 1.25 mm
Note:
1. Peel the shield and sheath for the part that is to pass through the inside of the remote controller case, as shown in
the figure below.
2. Treat the terminal for the wire to be connected to the remote controller so the shielded part doesnt touch any
other part.
16
4. Reattach the Upper Part of Remote Controller
Be careful not to pinch the wiring when attaching.
Note:
1. The switch box and wiring for connection are not included.
2. Do not directly touch the PC board with your hand.
C : 2PA52602C
Control
725
Control Functions
6.2
ED34-762
Signal receiver of
indoor units
Model Name
Applied Model
BRC7E65
BRC7C67
BRC7E66
BRC7E619
BRC7C529W
Applied Model
BRC4C64
BRC4C63
BRC7E65
BRC7C67
BRC7E619
BRC7E66
BRC4C63
BRC4C153
BRC4C64
BRC4C154
1-3
COOL/HEAT CHANGEOVER
REMOTE CONTROL SWITCH
(V2444)
C : 3PA63363-13G
726
Control
ED34-762
Control Functions
16
C : 3PA63363-13G
Control
727
Control Functions
ED34-762
When you use two remote controllers, be sure to set the wired remote controller of indoor unit as Main.
It is not possible to use two wireless remote controller.
The wiring between the separate type signal receiver and the indoor unit should not exceed 200 m.
6.2.4 Functional Comparison between Wired and the Wireless Remote Controller
Function/Display
Operation Lamp
ON/OFF BUTTON
OPERATION MODE
SELECTOR BUTTON
Filter sign can be reset by this button after cleaning Filter sign can be reset by this button after cleaning
the air filter. It is displayed on the LCD of the signal
the air filter.
receiver.
The operation and the setting by other operational button (Temperature setting, fan speed control, timer,
inspection/test operation, and group No. setting) are the same for both wireless and wired remote controller.
Function/Display
Display of TIME TO
CLEAN AIR FILTER
Display of
VENTILATION
Display of DEFROST/
HOT START
This display is shown when the unit is in defrost/hot Displayed on the LED of the receiver.
start operation
Display of UNDER
CENTRALIZED
CONTROL
Display of
CHANGEOVER
This display is shown when the remote controller
UNDER CENTRALIZED cannot changeover heat/cool.
CONTROL
728
Thermostat on the
Remote Controller
Yes
No
Ventilation Mode
Yes
No
Control
ED34-762
6.3
Control Functions
16
C : 2PA52942
Note:
1. Following functions are not including in this controller.
Auto swing function.
Timer setting function.
Display of time to clean air filter.
2. For setting, refer to page 730.
3. For BRC2C51
Equipped with a thermostat sensor in the remote controller that makes possible more comfortable room
temperature control.
Complied with the RoHS directive.
Control
729
Control Functions
ED34-762
If not using any remote controllers, connect a remote controller for group No. setting, set the group No. for
centralized control, and then disconnect the remote controller after setting.
Group No. setting example
730
Control
ED34-762
6.4
Control Functions
16
C : 3PA61137
Control
731
Control Functions
732
ED34-762
Control
ED34-762
Part 8
Guide Specifications
1. Guide Specifications ...........................................................................734
1.1 Guide Specifications.............................................................................734
17
Guide Specifications
733