Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Product Overview
36 kV Indoor Vacuum Circuit Breaker
4
Compartmentalized Panel with built in base frame & ramp.
4
CG make highly reliable vacuum interrupters & protection relays.
4
Tested for extended mechanical endurance of M2 class ensuring
10,000 operating sequences.
4
SCADA compatible control system.
4
The optional features like draw-out type PT, Powerpack, Integral
earth switch, series trip arrangement for unmanned substation
(without auxiliary supply) shall be provided.
4
Internal arc tested as per IEC 62271-200.
The GCB is a time tested product a unique dead tank design which
offers highly safe operation. The product is suitable for installation at
high altitude. The SF6 GCB is best suitable for low inductive &
capacitive currents. It employs continuous supervision of SF6 gas
pressure.
Earthing Device
Salient Features
4
Floor rolling type breaker with horizontal isolation & horizontal
draw-out.
4
Portable earthing truck
4
Fully type tested product at renowned testing laboratories like
KEMA - Netherlands, KERI Korea, CPRI / ERDA - India.
4
Integral Earth Switch
4
Inaccessible live parts & rack in/out with door closed condition
VCB
SF6 GCB
Felix Truck
Technical Data
Units
VCB
GCB
Rated Voltage
Characteristics
kV
Upto 36 (Felix)
Upto 36
Rated Current
Amp
630 to 2000
No of poles
nos
Frequency
Symmetrical Breaking Capacity
Making Capacity
Power Frequency Withstand Voltage
Impulse Withstand
Hz
50/60
26.3 / 31.5 / 40
kApk
kV rms
70
kVpk
Operating Duty
cycles
TotalBreak Time
cycles
Make Time
cycles
< 50%
DC Component
O-0.3sec-CO-3min-CO
O-3min-CO-3min-CO
Degree of protection
IP 4X (std) / IP 5X (optional)
Applicable Standard
SWING PANEL
BUSBAR
FIXED
PT
CB TRUCK
FEEDER SPOUT
CABLE
TERMINATION
D/W
PT
PT SPOUT
CT
CT
EARTHING
SIDE VIEW
FRONT VIEW
Dimensions
CB Type
Variant
W x D x H (mm)
Felix
GCB
Ordering Information
Please furnish the following details while making an enquiry / order
Parameters
Value
Application
Site Conditions
Rated Voltage
(Range: 22 to 36 kV)
Rated current
Frequency
50/60 Hz
System Earthing
Copper / Aluminium
CT Details
PT Details
Protection Relay
Meters
Note: All other accessories shall be provided as per our standard. Please specify for any specific accessory requirement.