Sei sulla pagina 1di 56

Bus Air

Conditioning
Equipment

Models
GR--45
GR--60
(N. A. O.)

T--295

OPERATION AND
SERVICE MANUAL
BUS
AIR CONDITIONING
UNIT

Models
GR--45
GR--60
(N. A. O.)

Carrier Refrigeration Operations


Carrier Transicold Division, Carrier Corporation, P.O. Box 4805, Syracuse, N.Y. 13221 U. S. A.
Carrier Corporation 2000 D Printed in U. S. A. 0300

SAFETY SUMMARY
GENERAL SAFETY NOTICES

The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this
manual. They are recommended precautions that must be understood and applied during operation and maintenance
of the equipment covered herein. A listing of the specific warnings and cautions appearing elsewhere in the manual
follows the general safety notices.
FIRST AID

An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS

Always wear safety glasses.


Keep hands, clothing and tools clear of the evaporator and condenser fans.
No work should be performed on the unit until all circuit breakers and start-stop switches are placed in the OFF
position, and power supply is disconnected.
Always work in pairs. Never work on the equipment alone.
In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS

Beware of unannounced starting of the evaporator and condenser fans. Do not open the unit cover before turning
power off.
Be sure power is turned off before working on motors, controllers, solenoid valves and electrical controls. Tag circuit
breaker and power supply to prevent accidental energizing of circuit.
Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems
with the system should be diagnosed, and any necessary repairs performed, by qualified service personnel.
When performing any arc welding on the unit, disconnect all wire harness connectors from the modules in the control
box. Do not remove wire harness from the modules unless you are grounded to the unit frame with a static-safe wrist
strap.
In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).
SPECIFIC WARNINGS AND CAUTIONS

WARNING
DO NOT USE A NITROGEN CYLINDER WITHOUT A PRESSURE REGULATOR
WARNING
DO NOT USE OXYGEN IN OR NEAR A REFRIGERATION SYSTEM AS AN EXPLOSION MAY
OCCUR.
WARNING
THE FILTER-DRIER MAY CONTAIN LIQUID REFRIGERANT. SLOWLY LOOSEN THE
FLARE NUTS AND AVOID CONTACT WITH EXPOSED SKIN OR EYES.
CAUTION
Do not under any circumstances attempt to service the microprocessor. should a problem develop with
the microprocessor, replace it.
CAUTION
If unit was recently operated, be careful of remaining hot coolant in the hoses when disassembling.

Safety-1

T--295

TABLE OF CONTENTS
PARAGRAPH NUMBER

Page

SAFETY SUMMARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety-1
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1

1.1
1.2

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 Apex Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Condensing Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Evaporator Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.4 Compressor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.5 Fresh Air System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.6 System Operating Controls And Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 REFRIGERATION SYSTEM COMPONENT SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . .
1.4 ELECTRICAL SPECIFICATIONS -- MOTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 ELECTRICAL SPECIFICATIONS -- SENSORS AND TRANSDUCERS . . . . . . . . . . . . . . . . . .
1.6 SAFETY DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7 AIR FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.8 AIR CONDITIONING REFRIGERATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.9 HEATING CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.10 RELAY BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.10.1 Permanent Magnet Motors with 2 speed switching from series to parallel
connection (Option 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.10.2 Electronically Communtated DC Motors with 2--speed Evaporator Input Signal (Option 2) .
1.11 LOGIC BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.12 CONTROL PANEL (Diagnostic Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-9
1-11
1-12
1-13

OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-1

2.1

STARTING, STOPPING AND OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . .


2.1.1 Power to Logic Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2 Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.3 Self-Test and Diagnostics (Check for Errors and/or Alarms) . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.4 Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 PRE--TRIP INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2 Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.3 Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.4 Boost Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.5 Vent Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.6 Fresh Air System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.7 Compressor Unloader Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.8 Evaporator Fan Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.9 Condenser Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.10 Compressor Clutch Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i

1-1
1-2
1-2
1-2
1-3
1-4
1-4
1-4
1-5
1-5
1-5
1-5
1-6
1-6
1-8
1-9

2-1
2-1
2-1
2-1
2-1
2-1
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-4
2-4
2-4

T--295

TABLE OF CONTENTS (Continued)


PARAGRAPH NUMBER

2.3.11
2.3.12
2.4
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5

Page

Alarm Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hour Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MICROPROCESSOR DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4
2-4
2-4
2-4
2-5
2-5
2-5
2-5

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1
3.2

SELF DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYSTEM ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.3 Alarm Queue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.4 Alarm Clear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 System Will Not Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 System Runs But Has Insufficient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.3 Abnormal Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.4 Abnormal Noise Or Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.5 Control System Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.6 No Evaporator Air Flow Or Restricted Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.7 Expansion Valve Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.8 Heating Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1
3-1
3-1
3-1
3-1
3-1
3-1
3-4
3-4
3-4
3-4
3-5
3-5
3-5
3-5

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-1

4.1
4.2
4.3
4.4
4.5

MAINTENANCE SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPENING TOP COVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SUCTION AND DISCHARGE SERVICE VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLING MANIFOLD GAUGE SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMPING THE SYSTEM DOWN OR REMOVING THE REFRIGERANT CHARGE . . . . . . .
4.5.1 System Pump Down For Low Side Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Refrigerant Removal From An Inoperative Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.3 Pump Down An Operable Compressor For Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.4. Removing Entire System Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6 REFRIGERANT LEAK CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7 EVACUATION AND DEHYDRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.3 Procedure for Evacuation and Dehydrating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T--295

ii

4-1
4-1
4-1
4-2
4-2
4-2
4-3
4-3
4-4
4-4
4-4
4-4
4-4
4-4

TABLE OF CONTENTS (Continued)


PARAGRAPH NUMBER

4.8

Page

ADDING REFRIGERANT TO SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.8.1 Checking Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-5
4-5

4.8.2 Adding Full Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.8.3 Adding Partial Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.9 CHECKING FOR NONCONDENSIBLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-5
4-5
4-5

4.10 CHECKING AND REPLACING HIGH PRESSURE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . .


4.11 FILTER-DRIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.11.1 To Check Filter--Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.11.2 To Replace Filter--Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-5
4-6
4-6
4-6

4.12 CONDENSER COIL REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.13 EVAPORATOR COIL REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.14 SERVICING THE HEAT VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.14.1 COIL REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.14.2 INTERNAL PART REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-6
4-7
4-7
4-7
4-7

4.14.3 REPLACE ENTIRE VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.15 SERVICING THE LIQUID LINE SOLENOID VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.15.1 Coil Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.15.2 Internal Part Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.15.3. Replace Entire Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.16 CONDENSER FAN/MOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.16.1 Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.16.2 Inspection And Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.16.3 Brush Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.17 REPLACING EVAPORATOR FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.18 REPLACING RETURN AIR FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.19 THERMOSTATIC EXPANSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.19.1 Valve Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.19.2 Superheat Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-7
4-8
4-8
4-8
4-8
4-8
4-8
4-9
4-9
4-9
4-9
4-9
4-9
4-10

4.20 COMPRESSOR MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-10

4.20.1 Removing the Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.20.2 Transferring Compressor Clutch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-10
4-11

4.20.3 Compressor Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.20.4 Checking Unloader Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.21 TEMPERATURE SENSOR CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.22 PRESSURE TRANSDUCER CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.23 REPLACING SENSORS AND TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-12
4-12
4-13
4-13
4-13

4.24 LOGIC BOARD CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-13

ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-1

5--1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-1

INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii

Index-1
T--295

LIST OF ILLUSTRATIONS
FIGURE NUMBER

Page

Figure 1-1. A/C Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Figure 1-2. Apex Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-3. Condensing Section Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-4. Evaporator Section Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-5. Air Flow Paths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-6. Refrigerant Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-7. Heating Cycle Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-8 Relay Board (Option 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-9 Relay Board (Option 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-10 Logic Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-11. Micromate Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 2-1 Capacity Control Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-1. Opening Top Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-2.Suction or Discharge Service Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-3. Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-4. Low Side Pump Down Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-5. Compressor Service Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-6. System Charge Removal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-7. Checking High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-8. Filter--Drier Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-9. Heat Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-10. Liquid Line Solenoid Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-11. Condenser Fan/Motor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-12. Evaporator Fan Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-13. Thermostatic Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-14.Thermostatic Expansion Valve Bulb and Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-15.Removing Bypass Piston Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-16. Compressor Clutch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-17. Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-18 Transducer Terminal Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5--1. Electrical Wiring Schematic Diagram - Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5--2. Wiring Schematic, Permanent Magnet Motors - Interconnection . . . . . . . . . . . . . . . . . . . . . . .
Figure 5--3. Wiring Schematic, Permanent Magnet Motors - Relays to External Components . . . . . . . . . .
Figure 5--4. Wiring Schematic, Electronically Communtated Motors - Interconnection . . . . . . . . . . . . . . .
Figure 5--5. Wiring Schematic, Electronically Communtated Motors - Relays To External Components . .

T--295

iv

1-1
1-2
1-3
1-4
1-6
1-7
1-8
1-9
1-11
1-12
1-13
2-2
4-1
4-2
4-2
4-3
4-3
4-4
4-6
4-6
4-7
4-8
4-8
4-9
4-9
4-10
4-11
4-11
4-12
4-13
5-2
5-3
5-4
5-5
5-6

LIST OF TABLES
TABLE NUMBER

Page

Table 2-1. Evaporator Fan Speed Relay Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Table 2-2. Controller Test List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2-3. Parameter Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 3-2 Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 3-3 General System Troubleshooting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-1. Temperature Sensor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-2. PressureTransducer Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 4-3. Logic Board Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4
2-5
2-6
3-2
3-4
4-13
4-14
4-14

T--295

SECTION 1
DESCRIPTION
1.1 INTRODUCTION

system, the air conditioning and heating equipment


interfaces with electrical cabling, refrigerant piping,
engine coolant piping (for heating), duct work and other
components furnished by the bus manufacturer.

This manual contains Operating Instructions, Service


Instructions and Electrical Data for the Model GR Air
Conditioning and Heating equipment furnished by
Carrier Transicold Division as shown in Table 1-1.
Model GR systems consists of an Apex Unit, containing
the condenser and evaporator and an engine
compartment mounted compressor. To complete the

Operation of the units is controlled automatically by a


microprocessor based Micromax Controller which
maintains the vehicles interior temperature at the
desired set point.

MODEL

SERIES

Table 1-1. Model


COMPRESSOR

GR45

ROOF MOUNTED
ROOF MOUNTED

05K
05G

GR60

CONDENSER
FANS

EVAPORATOR
FANS

4
6

4
6

MANUAL/FORM NUMBER

Table 1-2. Additional Support Manuals


EQUIPMENT COVERED

TYPE OF MANUAL

62--02491
62--02460
62--02756
T--200

O5K Compressor
O5K Compressor
O5G Compressor
O5G Compressor

Operation and Service


Parts List
Operation and Service
Parts List

13
1.
2.
3.
4.
5.
6.
7.

12

11

Compressor
Refrigerant Lines
Compressor Harness
Heat Valve
Electronics Boards
Apex Unit
Main Harness

10

9
8.
9.
10.
11.
12.
13.

Driver Control
Power Harness
Power Relay
Battery
Alternator
Discharge Check Valve

Figure 1-1. A/C Component Identification


1-1

T--295

1.2 GENERAL DESCRIPTION

section, evaporator section, Micromax electronics, and


the Fresh Air System. All components are accessible by
lifting the top cover. Descriptions of the systems are
provided in the following sub paragraphs.

1.2.1 Apex Unit

The apex unit (see Figure 1-2) includes the condensing

11
10

4
5

6
8

9
1. Top Cover
2. Gas Spring (2)
3. Condenser Section (See Figure 1-3)
4. Evaporator Section (See Figure 1-4)
5. Base
6. Fresh Air System
7. Gas Spring Support (2)
8. Lock (2)
9. Serial Plate

10.
11.

Hinge
Condenser Fan Grille (4-GR45,
6-GR60)
12. Front Drain (2)*
13. Intermediate Drain (2)*
14. Evaporator Rear Drain (2)*
15. Condenser Rear Drain (2)*
* Not Shown

Figure 1-2. Apex Unit Components

(GR-60 Shown)
pressure into a liquid at high temperature and pressure.
The condenser fans circulate ambient air across the
The condensing section (Figure 1-3) includes the
outside of the condenser tubes at a temperature lower
condenser coils, fan and motor assemblies, filter-drier,
than refrigerant circulating inside the tubes; this results
receiver, liquid line solenoid valve, service valves, and
in condensation of the refrigerant into a liquid. The
an ambient temperature sensor.
filter-drier removes moisture and debris from the liquid
The condenser coils provide heat transfer surface for
refrigerant before it enters the thermostatic expansion
condensing refrigerant gas at a high temperature and
valve in the evaporator assembly.
1.2.2 Condensing Section

T--295

1-2

The receiver collects and stores liquid refrigerant. The


receiver is fitted with upper and lower liquid level sight
glasses to enable determining refrigerant liquid level.
The receiver is also fitted with a fusible plug which
protects the system from unsafe high pressure
conditions. The liquid line solenoid valve closes when
system is shut down to prevent flooding of coils with
liquid refrigerant. The service valves enable isolation of
the filter-drier for service. The ambient temperature
1

sensor measures ambient temperature and sends an


electrical signal to the controller.
The discharge check valve is a spring loaded, normally
closed valve that opens with the flow of refrigerant from
the compressor. When the compressor clutch is
disengaged, the discharge check valve will close,
preventing the flow of high pressure liquid from the
condenser back into the compressor.
4

13
7
12

11
1.
2.
3.
4.
5.
6.
7.
8.

10

Condenser Coil (2)


Receiver
Protection Plate
Service Valve
Discharge Line
Precharge Valve
Liquid Line Solenoid Valve
Filter Drier Upper Support

9.
10.
11
12.
13.

Filter Drier
Filter Drier Lower Support
Condenser Fan and Motor Assembly
(4-GR45, 6-GR60)
Condenser Coil Fastener (4)
Condenser Motor Support
(4-GR45, 6-GR60)

Figure 1-3. Condensing Section Components

(GR-60 Shown)
circulating over the outside surface of the tubes, thus
providing heating. The fans circulate the air over the
The evaporator section (Figure 1-4) includes the
coils. The air filters remove dirt particles from the air
evaporator coils, six fan and motor assemblies,
before it passes over the coils. The thermostatic
evaporator/heater coil assemblies, a thermostatic
expansion valve meters flow of refrigerant entering the
expansion valve and condensate drain connections.
evaporator coils. The heat valve controls the flow of
The evaporator coils provide heat transfer surface for
engine coolant water to the heating coils upon receipt of
transferring heat from air circulating over the outside
a signal from the controller. The condensate drain
the coil to refrigerant circulating inside the tubes; thus
connections provide a means for connecting tubing for
providing cooling. The heating coils provide heat
disposing of condensate collected on the evaporator
transfer surface for transferring heat from engine
coils during cooling operation.
coolant water circulating inside the tubes to air
1.2.3 Evaporator Section

1-3

T--295

4
5
6

7
8

1.
2.
3.
4.

Evaporator Coil With Integrated


5. Evaporator Motor (4-GR45,
Heating Coil (2)
6-GR60)
Protection Plate
6. Suction Line
Expansion Valve
7. Heating Lines
Evaporator Motor Fastening Clamps
8. Service Valve
(4-GR45, 6-GR60)
9. Evaporator Harness
Figure 1-4. Evaporator Section Components

(GR-60 Shown)
into the air entering the evaporator coil. For additional
information on air flow, refer to paragraph 1.7.
The compressor assembly includes the refrigerant
compressor, clutch assembly, suction and discharge
1.2.6 System Operating Controls And Components
service valves, high pressure switch, low pressure
switch, suction and discharge servicing (charging) ports
The system is operated by a Carrier Transicold
and electric solenoid unloaders.
Micromax microprocessor controller which consist of a
logic board (Figure 1-10), relay board (Figure 1-8 or
The compressor raises the pressure and temperature of
Figure 1-9), and manual operator switches. The manual
the refrigerant and forces it into the condenser tubes.
operating switches are located on the drivers control and
The clutch assembly provides a means of belt driving
may consist of a single OEM supplied ON/OFF switch,
the compressor by the bus engine. The suction and
additional OEM supplied switches or a Carrier
discharge service valves enable servicing of the
Transicold supplied Micromate control panel
compressor. Suction and discharge servicing (charging)
(Figure 1-11). The logic board regulates the operational
ports mounted on the service valves enable connection
cycles of the system by energizing or de--energizing
of charging hoses for servicing of the compressor, as
relays on the relay board in response to deviations in
well as other parts of the refrigerant circuit. The high
interior temperature. Modes of operation include
pressure switch contacts open on a pressure rise to shut
Cooling, Heat and Vent. On systems fitted with only an
down the system when abnormally high refrigerant
ON/OFF switch and on systems with the Micromate set
pressures occur. The electric unloaders provide a means
in the AUTO mode, the logic board will cycle the
of controlling compressor capacity, which enables
system between the operating modes as required to
control of temperature inside the bus. For more detailed
maintain desired set point temperature.
information on the compressor, refer to manual number
62-02756.
In the vent mode the evaporator fans are operated to
circulate air in the bus interior.
1.2.5 Fresh Air System
The Fresh Air System (6, Figure 1-2) consists of a
In the heat mode the heat valve is opened to allow a flow
damper and damper operator. The damper operator may
of engine coolant through the heat section of the
be controlled by the driver, if a switch is provided. In the
evaporator coil. The evaporator fans operate to circulate
automatic mode, it is controlled by the Micromax to
air over the evaporator coil in the same manner as the
open and close the damper to allow addition of fresh air
vent mode.
1.2.4 Compressor Assembly

T--295

1-4

In the cooling mode the compressor is energized while


the evaporator and condenser fans are operated to
provide refrigeration as required. The compressor is
fitted with cylinder unloaders to match compressor
capacity to the bus requirements. Once interior
temperature reaches the desired set point, the system
may operate in the clutch cycle or reheat mode. A
controller programmed for clutch cycle will
de--energize the compressor clutch and allow the system
to operate in the vent mode until further cooling is
required. A controller programmed for reheat will
maintain compressor operation and open the heat valve
to allow reheating of the return air. In the reheat mode
interior temperature is maintained at the desired set
point while additional dehumidification takes place.

ECDC*
p
Evaporator
Motor
27.5
VDC

Horsepower (kW)
Full Load Amps
(FLA)
Operating Speed
High/Low (RPM)
Bearing Lubrication

Horsepower (kW)
Full Load Amps
(FLA)
Operating Speed
High/Low (RPM)
Bearing Lubrication

1.3 REFRIGERATION SYSTEM COMPONENT


SPECIFICATIONS

14.3 lb (6.5 kg)

Compressor
No of Cylinders
Weight - Dry
Oil Charge

GR45

GR60

05K
4
108 lbs
(49 kg)
5.5 pints
(2.6 liters)

05G
6
137 lbs
(62 kg)
6.75 pints
(3.2 liters)

1/8 (.09)
9
18

1.5 ELECTRICAL SPECIFICATIONS -- SENSORS


AND TRANSDUCERS
a. Suction and Discharge Pressure Transducer

Supply Voltage: 4.5 to 5.5 vdc (5 vdc nominal)


Supply current: 8 mA maximum
Output Range: 8K ohms minimum
Input Range: --6.7 to 450 psig (--0.46 to 30.62 bar)
Output Current: -1.5 mA minimum to
1.5 mA maximum
Output Voltage: vdc = 0.0098 x psig + 0.4659
(See Table 4-2 for calculations.)

Oil Level:
Level in sight glass between Min.--Max marks on
compressor crankcase (curbside)
Approved Compressor Oils - R-134a:
Castrol: Icematic SW68C
Mobil: EAL Arctic 68
ICI: Emkarate RL68H

b. Temperature Sensors

Input Range: --52.6 to 158F (--47 to 70C)


Output: NTC 10K ohms at 77F (25C)
(See Table 4-1 for calculations.)

c. Thermostatic Expansion Valve:

Superheat Setting (Non-externally adjustable):


10 to 12F
MOP Setting (Nonadjustable): 55 4 psig (3.74
2.27 bar)

1.6 SAFETY DEVICES

System components are protected from damage caused


by unsafe operating conditions with safety devices.
Safety devices with Carrier Transicold supplied
equipment include high pressure switch (HPS), low
pressure switch (LPS), circuit breakers and fuses.

d. High Pressure Switch (HPS):

Opens at: 300 10 psig (20.41 0.68bar)


Closes at: 200 10 psig (13.61 0.68bar)

a. Pressure Switches

High Pressure Switch (HPS)


During the A/C mode, compressor operation will
automatically stop if the HPS switch contacts open due
to an unsafe operating condition. Opening HPS contacts
de-energizes, through the controller, the compressor
clutch shutting down the compressor. The high pressure
switch (HPS) is installed in the center head of the
compressor.

e. Low Pressure Switch (LPS)

Opens at: 6 3psig (0.41 0.20 bar)


Closes at: 25 3 psig (1.7 0.20 bar)
1.4

0.15(.11)
7

Permanent
Magnet
24 VDC 12 VDC

4252/
4200/
NA
1850
Factory Lubricated (additional grease not required)
* Electronically Communicated Direct Current

a. Refrigerant Charge

b. Compressor
UNIT MODEL

1/8 (.09)
9.5
19

4252/
4200/
3165
1850
Factory Lubricated (additional grease not required)

b. Condenser Fan Motor


ECDC*
Condenser Motor
24 VDC

Controls may also be provided to allow manual


operation of the evaporator fans in low or high speed
and manual control of the fresh air damper in the open or
closed position.

R--134a

0.34(.25)
8.4

Permanent
Magnet
24 VDC 12 VDC

ELECTRICAL SPECIFICATIONS -- MOTORS

a. Evaporator Fan Motor


1-5

T--295

Low Pressure Switch (LPS)


The low pressure switch is installed in the compressor
and opens on a pressure drop to shut down the system
when a low pressure condition occurs. In addition, if the
control monitors a pressure less than 10 psig (0.68
bar)by the suction pressure transducer mounted in the
evaporator section, the system will be shut down for at
least one minute.

The compressor raises the pressure and the temperature


of the refrigerant and forces it into the condenser tubes.
The condenser fan circulates surrounding air (which is
at a temperature lower than the refrigerant) over the
outside of the condenser tubes. Heat transfer is
established from the refrigerant (inside the tubes) to the
condenser air (flowing over the tubes). The condenser
tubes have fins designed to improve the transfer of heat
from the refrigerant gas to the air; this removal of heat
causes the refrigerant to liquefy, thus liquid refrigerant
leaves the condenser and flows to the receiver.

b. Fuses and Circuit Breakers

The Relay Board is protected against high current by an


OEM supplied 150 amp fuse. Independent 15 amp
circuit breakers protect each motor while the output
circuits are protected by an additional 15 amp circuit
breaker. During a high current condition, the breaker (or
OEM fuse) may open. When power is removed from a
device, a breaker alarm will be generated.

The receiver serves as a liquid refrigerant reservoir so


that a constant supply of liquid is available to the
evaporators as needed, and acts as a storage space when
pumping down the system. The receiver is equipped
with sight glasses to observe the refrigerant for
restricted flow and correct charge level.

c. Ambient Lockout

The refrigerant leaves the receiver and passes through


the receiver outlet/service valve, through a filter-drier
where an absorbent keeps the refrigerant clean and dry.

The ambient temperature sensor located in the


condenser section measures the condenser inlet air
temperature. When the temperature is below the cut out
set point the compressor is locked out until the
temperature rises above the cut in setting. The set points
may be programmed to cut out at 45F 7.2C) and cut in
at 50F 10C) or cut out at 25 F --3.9C) and cut in at
45F 7.2C) in accordance with bus purchase
specification. This setting protects the compressor from
damage caused by operation at low pressures.

From the filter-drier, the liquid refrigerant then flows


through the liquid line solenoid valve to the
thermostatic expansion valve. the thermal expansion
valve reduce pressure and temperature of the liquid and
meters the flow of liquid refrigerant to the evaporator to
obtain maximum use of the evaporator heat transfer
surface.
The low pressure, low temperature liquid that flows into
the evaporator tubes is colder than the air that is
circulated over the evaporator tubes by the evaporator
fans (fans). Heat transfer is established from the
evaporator air (flowing over the tubes) to the refrigerant
(flowing inside the tubes). The evaporator tubes have
aluminum fins to increase heat transfer from the air to
the refrigerant; therefore the cooler air is circulated to
the interior of the bus. Liquid line solenoid valve closes
during shutdown to prevent refrigerant flow.

1.7 AIR FLOW

The paths for ambient air through the condenser and


coach air through the evaporator are illustrated in
Figure 1-5.
1.8 AIR CONDITIONING REFRIGERATION
CYCLE

When air conditioning (cooling) is selected by the


controller, the unit operates as a vapor compression
system using R-134a as a refrigerant (see Figure 1-6).
The main components of the system are the
reciprocating compressor, air-cooled condenser coils,
receiver, filter-drier, thermostatic expansion valve,
liquid line solenoid valve and evaporator coils.

The transfer of heat from the air to the low temperature


liquid refrigerant in the evaporator causes the liquid to
vaporize. This low temperature, low pressure vapor
passes through the suction line and returns to the
compressor where the cycle repeats.

CONDENSER AIR FLOW


3. THROUGH FAN

4. RETURN TO AMBIENT

2. THROUGH CONDENSER
1. FROM DAMPER
(IF ACTIVE)

1. FROM AMBIENT

2. FROM COACH
3. THROUGH EVAPORATOR
4. THROUGH FAN
5. RETURN TO COACH
Figure 1-5. Air Flow Paths
T--295

1-6

EVAPORATOR
AIR
FLOW

7
8
9
10
11

12
13

16

11
A

14

RECEIVER

16
DISCHARGE
LIQUID
SUCTION

DISCHARGE

SUCTION

15

17
MAIN ENGINE
RADIATOR

18
VIEW A-A
COMPRESSOR

1.
2.
3.
4.
5.
6.
7.
8.
9.

Condenser Fan Assembly


Evaporator Fan Assembly
Expansion Valve
Expansion Valve Equalizer Line
Liquid Line
Precharge Valve
Expansion Valve Bulb
Pressure Transducer, Low Side
Service Port, Low Side

10.
11.
12.
13.
14.
15.
16.
17.
18.

Pressure Transducer, High Side


Service Valve With Port
Liquid Line Solenoid Valve
Filter Drier
Service Port, High Side
Discharge Check Valve
Receiver
Refrigerant Sight Glass
Moisture Indicator

Figure 1-6. Refrigerant Flow Diagram

(GR60 Shown)
1-7

T--295

HEAT
VALVE
BOOST
PUMP
SUPPLY
RETURN
MAIN ENGINE
RADIATOR

COMPRESSOR

Figure 1-7. Heating Cycle Flow Diagram

(GR60 Shown)
inside the bus. Engine coolant (glycol solution) is
circulated through the heating circuit by the engine and
Heating circuit (Figure 1-7) components furnished by
Carrier Transicold include the integral evaporator coil
an auxiliary boost water pump. When the heat valve
heater cores and a solenoid operated heat valve.
solenoid is energized, the valve will open to allow
engine coolant to flow through the heater coil. The valve
Components furnished by the bus manufacturer include
auxiliary heater and boost water pump. The controller
is normally closed so that if a failure occurs, the system
automatically controls the heat valve during the heating
will be able to cool.
and reheat modes to maintain required temperatures
1.9 HEATING CYCLE

T--295

1-8

1.10 RELAY BOARD

CB 11
K3

CB 1

CB 5

K7

K15

K16

D2 D6

K4

K8
K6

D14 D17

CB 4

K11

K10

K20

K19

K13

K12 D85

CB 9
D26 D30

K18

JP4

K5

CF1 CF2

D38 D41

CB 10

4 5 6
2 3
1

CB 3

CB 8

JP3

K2

CB 6

EF1 EF2

4 5
2 3
1

CB 12
CB 2

2 3
1

EF3 EF4

EF6

EF5

CF6

CF3 CF4
K24

D57
D54

K17

K9

CB 7

JP5

K1

K14

3 4
1 2

CB 13

JP6

1.10.1 Permanent Magnet Motors with 2 speed switching from series to parallel connection (Option 1)

D63
D60
D72
D66
D51
D69

CF5
JP1

K22

K21

K23

JP2

Figure 1-8 Relay Board (Option 1)


low speed.
a. Relays
K1 Energizes evaporator fans 1 & 2 in high speed
K12 Connects the negative side of condenser fan
or evaporator fans 1,2,3 & 4 in low speed.
5 to ground in high speed. Connects the
K2 Energizes evaporator fans 3 & 4 in high speed
negative side of condenser fan 5 to
(not energized in low speed).
the positive side of condenser fan 6 in
K3 Energizes evaporator fan 5 in high speed or
low speed.
evaporator fans 5 & 6 in low speed.
K13 Energizes the A/C clutch.
K4 Energizes evaporator fan 6 in high speed (not
K14 Energizes unloader 1.
energized in low speed).
K15 Energizes unloader 2.
K5 Connects the negative side of evaporator fans
K16 Energizes the fresh air damper.
1 & 2 to ground in high speed. Connects the
K17 Energizes the heat valve.
negative side of evaporator fans 1 & 2 to
K18 Energizes the fault light output.
positive side of evaporator fans 3 & 4 in
K19 Energizes the Boost Pump.
low speed
K20 Energizes the spare output.
K6 Connects the negative side of evaporator fan
K21 Is energized by the logic board to turn the
5 to ground in high speed. Connects the
evaporator fans on high. The contacts of this
negative side of evaporator fan 5 to
relay energize the coils of relays K1, K2,
positive side of evaporator fan 6 in
K3 & K4.
low speed
K22
Is
energized by the logic board to turn the
K 7 Energizes condenser fans 1 & 2 in high speed
evaporator fans on low. The contacts of this
or condenser fans 1,2,3 & 4 in low speed
relay energize the coils of relays K1, K3,
K 8 Energizes condenser fans 3 & 4 in high speed
K5 & K6.
(not energized in low speed).
K23
Is
energized by the logic board to turn the
K 9 Energizes condenser fan 5 in high speed or
condenser fans on high. The contacts of this
condenser fans 5 & 6 in low speed.
relay energize the coils of relays K7, K8,
K10 Energizes condenser fan 6 in high speed
K9 & K10.
(not energized in low speed).
K24 Is energized by the logic board to turn the
K11 Connects the negative side of condenser fans
condenser fans on low. The contacts of this
1 & 2 to ground in high speed. Connects the
relay energize the coils of relays K7, K9,
negative side of condenser fans 1 & 2 to
K11 & K12.
the positive side of condenser fans 3 & 4 in
1-9

T--295

b. Thermal Circuit Breakers


CB 1 Evaporator Fan #1. 15 Amp.
CB 2 Evaporator Fan #2. 15 Amp.
CB 3 Evaporator Fan #3. 15 Amp.
CB 4 Evaporator Fan #4. 15 Amp.
CB 5 Evaporator Fan #5. 15 Amp.
CB 6 Evaporator Fan #6. 15 Amp.
CB 7 Condenser Fan #1.
15 Amp.
CB 8 Condenser Fan #2.
15 Amp.
CB 9 Condenser Fan #3.
15 Amp.
CB10 Condenser Fan #4.
15 Amp.
CB11 Condenser Fan #5.
15 Amp.
CB12 Condenser Fan #6.
15 Amp.
CB13 A/C clutch, Unloaders 1&2,
Fresh Air Damper, Heat Valve,
Fault Output and Spare
output.
15 Amp

JP6 Unloaders 1 & 2.


d. LEDS
D 2 Relay K1 output active (evaporator fans 1,2,3 &
4 energized)
D 6 Will be brightly lit if evaporator fans 1, 2, 3 & 4
are on high. Will be at half intensity of they are on low.
D14 Relay K3 output active (evaporator fans 5 & 6
energized).
D17 .Will be brightly lit if evaporator fans 5 &6 are
on high. Will be at half intensity of they are on low.
D26 Relay K7 output active (condenser fans 1, 2, 3
& 4 energized).
D30 Will be brightly lit if condenser fans 1, 2, 3 & 4
are on high. Will be at half intensity of they are on low.
D38 Relay K9 output active (condenser fans 5 & 6
energized).
D41 Will be brightly lit if condenser fans 5 &6 are on
high. Will be at half intensity of they are on low.
D51 A/C clutch output active.
D54 Unloader 1 output active.
D57 Unloader 2 output active.
D60 Fresh air output active.
D63 Heat valve output active.
D66 Fault output active.
D69 Boost pump output active.
D72 Spare output active.

c. Connectors
EF1-EF6 Evaporator fans.
CF1-CF4 Condenser fans.
JP1 External evaporator & condenser fan
thermal overload connections.
JP2 Logic board connector.
JP3 Boost pump.
JP4 A/C clutch, fault output, compressor high
pressure switch.
JP5 Spare output, fresh air output, heat valve.

T--295

1-10

JP6

1.10.2 Electronically Communtated DC Motors with 2--speed Evaporator Input Signal (Option 2)

CB 11
CB 1

K5

K3

K7

CB 5

CB 7

K11

K15

K16

K17

K18

K19

K20

K13

K9

JP5

K1

K14

EF1 EF2

CB 4

EF6

JP4

CF1 CF2

D26 D30 CB 10

EF HIGH SIGNAL

EF5

D38 D41

CF6

CF3 CF4
K24

CF HIGH SIGNAL

D57
D54

D63
D60
D72
D66
D51
D69

2 3
1

EF3 EF4

D14D17

CB 9

4 5 6
2 3
1

D81

D85

K10

K8

K4
CB 3

JP3

K2

D2 D6

CB 8

CB 6

4 5
2 3
1

CB 12
CB 2

3 4
1 2

CB 13

CF5
JP1

K22

K21

K23

JP2

Figure 1-9 Relay Board (Option 2)


a Relays
K23 or K24 Is energized by the logic board to
K1 Energizes evaporator fans 1 & 2
turn the condenser fans on high. The contacts
K2 Energizes evaporator fans 3 & 4.
of these relays energize the coils of relays K7,
K3 Energizes evaporator fan 5.
K8, K9 & K10.
K4 Energizes evaporator fan 6.
b Thermal Circuit Breakers
K5 Provides evaporator fan high output signal.
Refer to paragraph 1.10.1b.
(Motors are in low speed when K5
is de--energized)
c. Connectors
Refer to paragraph 1.10.1c.
K6 Not Used
EF HIGH SIGNAL Output to the evaporator fans
K 7 Energizes condenser fans 1 & 2.
to operate on high.
K 8 Energizes condenser fans 3 & 4.
CF HIGH SIGNAL Output to the condenser fans
K 9 Energizes condenser fan 5
to operate on high.
K10 Energizes condenser fan 6.
K13 Energizes the A/C clutch.
d. LEDS
K14 Energizes unloader 1.
Refer to paragraph 1.10.1d.
K15 Energizes unloader 2.
D81 Evaporator fans on high
K16 Energizes the fresh air damper.
D85 Condenser fans on high
K17 Energizes the heat .
K18 Energizes the fault light output.
K19 Energizes the Boost Pump.
K20 Energizes the spare output.
K21 or K22 Is energized by the logic board to
turn the evaporator fans on. The contacts
of these relays energize the coils of relays K1,
K2, K3 & K4.

1-11

T--295

1.11 LOGIC BOARD

J1
J2
J3
J4

Logic board power in.


Display interface.
Manual control inputs.
Interlock Inputs
(WTS, low side pressure switch etc.)
J5 Relay board interface.
J6 Sensor inputs (Thermistors, etc.).

J7 Diagnostics interface (RS232, DB9).


D2 Blinks once per second in normal operation.
On steady to indicate alarms detected.
D3 Off In normal operation, blinks out alarm
codes (2 digits each) when alarms detected.
A-P Configuration Jumpers
Figure 1-10 Logic Board

T--295

1-12

1.12 CONTROL PANEL (Diagnostic Module)

11

1.
2.
3.
4.
5.
6.

10

Display
DOWN Button -- decrease selection
UP Button -- increase selection
VENT (Only) Button
AUTO Button (Automatic Control)
COOLING (Only) Button

7.
8.
9.
10.
11.

HEAT (Only) Button


FAN SPEED Button
FRESH AIR Button
TEMPERATURE ( Inside / Outside)
Button
ON/OFF Button

Figure 1-11. Micromate Control Panel

1-13

T--295

SECTION 2
OPERATION
2.1 STARTING, STOPPING AND OPERATING
INSTRUCTIONS

4 If low or high speed evaporator fan speed is desired,


press the FAN SPEED button to illuminate the indicator light and bring speed to the desired level.

2.1.1 Power to Logic Board

Before starting, electrical power must be available from


the bus power supply. The system components receive
power from two sources:
a. 24 vdc power for the microprocessor electronics is
supplied through the bus multiplex module.
b. 24 vdc, 125 amp, power from a fuse in the battery
compartment supplies power for the, clutch, compressor unloader solenoids, evaporator and condenser assemblies; this power is controlled by the Logic
Board.
2.1.2 Starting

5 To open or close the fresh air damper, press the


FRESH AIR button to illuminate the indicator light
and bring the damper to the desired position.
6 To read interior or exterior temperature, press the
TEMPERATURE button to illuminate the indicator
light and bring the display to the desired temperature
reading. After a short delay, the display will return to
the default set point or return air temperature reading.
7 Setpoint may be changed by pressing the UP or
DOWN arrow button. The UP button will increase
the setpoint temperature and the DOWN button will
decrease the setpoint temperature.
8 For additional Micromate operating data refer to
paragraph 2.4.

a. If the engine is not running, start the engine.


b. OEM SUPPLIED SWITCHES
Actual start sequence depends on the operating controls supplied. If only an ON/OFF switch is supplied,
place the switch in the ON position to start the system
in the automatic mode. If additional OEM switches
are supplied, refer to the following Micromate control description for operating instructions.
c. MICROMATE CONTROL PANEL
It is suggested the system be started in the automatic
mode.
1 The Micromate Control Panel Display (see
Figure 1-11) may be programmed to display the set
point temperature or return air temperature. To determine which display temperature is programmed,
press the TEMPERATURE button so that the OUT
SIDE AIR indicator is illuminated. If the controller
cycles back to the INSIDE AIR indicator, than the
controller is programmed to display return air temperature. If the controller does not automatically
cycle back to the return air indicator, than the controller is programmed to display set point temperature.
2 To start the system, press the I/O button to illuminate
the indicator light and signal the Logic Board to perform start up. Ensure the AUTO button indicator is
illuminated. If not, press the AUTO button to place
the system in the automatic mode. After the pre--trip
inspection is completed, the switches may be set in
accordance with the desired control modes.
3 If cooling only, heating only or ventilation only is
desired, press the corresponding button (refer to
Figure 1-11) to illuminate the indicator light and
place the system in that mode of operation.
2-1

2.1.3 Self-Test and Diagnostics (Check for Errors


and/or Alarms)

Self-test of the main Logic Board electrical circuit is


automatically initiated when the system is powered up.
If there is an error in the circuit, an alarm will be
indicated by flashing LEDs on the Logic Board. If a
Micromate is connected to the Logic Board, the error
code can also be read on the display. If there are no errors
in the circuit, system will operate normally and flash the
status LED at a one second interval. During normal
operation, the Logic Board monitors system operating
parameters for out of tolerance conditions. If an out of
tolerance condition occurs, ALARM will be indicated
through the code LED or on the Micromate display.
Refer to section 3 for definition of system errors and
alarms and general troubleshooting procedures.
2.1.4 Stopping

Placing the ON/OFF switch in the OFF position or


pressing the Micromate ON/OFF button will stop the
system operation by removing power to the Logic
Board.
2.2 PRE--TRIP INSPECTION

After starting system, allow system to stabilize for ten to


fifteen minutes and check for the following:
a. Listen for abnormal noises in compressor or fan motors.
b. Check compressor oil level. (Refer to section 4.20.3)
c. Check refrigerant charge. (Refer to section 4.8.1 )
d. Ensure that self-test has been successfully performed
and that there are no errors or alarms indicated. (Refer
to section 2.1.3.)
T--295

AUTO MODE REHEAT


COOL
HIGH SPEED
LOADED

3F

HEAT MODE

AUTO MODE CYCLE


COOL
HIGH SPEED
LOADED

3F

2F

COOL
HIGH SPEED
4 CYLINDERS

2F

COOL
HIGH SPEED
4 CYLINDERS

1F

COOL
LOW SPEED
2 CYLINDERS

1F

COOL
LOW SPEED
2 CYLINDERS

2F

1F

SETPOINT
VENT
--1F

SETPOINT

SETPOINT
REHEAT 100%
DUTY CYCLE
LOW SPEED
4 CYLINDERS

--1F

VENT
--2F
--1F
HEAT
--3F

--2F

--2F
HEAT

--3F

--3F

--4F
HEAT

COOLING MODE
REHEAT
3F

COOL
HIGH SPEED
LOADED

COOLING MODE
CYCLE
COOL
HIGH SPEED
LOADED

3F

2F

COOL
HIGH SPEED
4 CYLINDERS

2F

COOL
HIGH SPEED
4 CYLINDERS

1F

COOL
LOW SPEED
2 CYLINDERS

1F

COOL
LOW SPEED
2 CYLINDERS

SETPOINT

SETPOINT

VENT
--1F

--2F

REHEAT 100%
DUTY CYCLE
LOW SPEED
4 CYLINDERS

--1F

--2F

Figure 2-1 Capacity Control Diagram


T--295

2-2

2.3 MODES OF OPERATION

2.3.4 Boost Pump

The system is operated by a Carrier Transicold


Micromax microprocessor controller which consists of
a logic board (Figure 1-10), relay board (Figure 1-8 or
Figure 1-9), and manual operator switches. The logic
board regulates operational cycles of the system by
energizing or de--energizing Relay Board relays in
response to deviations in interior temperature. Modes of
operation include Cooling, Heat and Vent. Refer
toFigure 2-1 and the following paragraphs for a
description of each mode.
Figure 2-1 shows the Logic Board actions at various
temperature deviations from setpoint. On rising
temperature, changes occur when the temperature rises
above Logic Board setpoints, On falling temperature,
changes occur when temperatures falls below Logic
Board set point. The system will operate in these modes
unless pressures override the Logic Board settings.
2.3.1 Temperature Control

Temperature is controlled by maintaining the return air


temperature measured at the return air grille.
2.3.2 Cooling Mode

Cooling is accomplished by energizing the compressor


and condenser fans, opening the liquid line solenoid
valve and closing the heating valve. Once interior
temperature reaches the desired set point, the system
may operate in the clutch cycle or reheat mode.
Selection of clutch cycle or reheat is factory
programmed in accordance with the bus purchase
specification.
A controller programmed for clutch cycle will
de--energize the compressor clutch and allow the system
to operate in the vent mode until further cooling is
required.
A controller programmed for reheat will maintain
compressor operation and cycle the heat valve to allow
reheating of the return air. In the reheat mode interior
temperature is maintained at the desired set point while
additional dehumidification takes place.

When the unit is in heat the boost pump relay is


energized, providing 24 VDC to activate the boost
pump.
2.3.5 Vent Mode

In the vent mode the evaporator fans are operated to


circulate air in the bus interior.
2.3.6 Fresh Air System

The fresh air damper is opened to allow entrance of


ambient air into the air entering the evaporator coil. The
damper is operated by the controller to open when return
air temperature is within +/--5F (+/--2.8C) of set point.
2.3.7 Compressor Unloader Control

When operating in cooling, the unloaders are used to


reduce system capacity as return air temperature
approaches set point. Operation of the unloaders
balances system capacity with the load and thereby
prevents overshoot from set point.
Relay Board mounted unloader outputs control the
capacity of the compressor by energizing or
de-energizing unloader solenoid valves. The model
05K (GR45) has two banks of two cylinders each while
the model 05G compressor (GR60) has three banks of
two cylinders each. Energizing a valve de-activates a
bank of cylinders. The 05K right cylinder bank (looking
at the pump end) and the outboard cylinder banks of the
05G are equipped with unloader valves (UV1 and, for
the 05G, UV2), each controlling two cylinders; this
allows the 05K to be operated with two or four cylinders
and the 05G to be operated with two, four or six
cylinders.
Whenever the compressor is started, the unloaders are
energized for thirty seconds to reduce starting torque.
After thirty seconds, unloaders may be de-energized.
Any subsequent changes between energizing and
de-energizing the unloaders for temperature control
must be staged with a thirty second delay. Once an
unloader is energized for pressure control, it remains
energized for two seconds to prevent short cycling.
Only one unloader may change state at a time when
staging is required. Operating parameters for
temperature control, suction pressure control and
discharge pressure control are as follows.
a. Temperature Control

2.3.3 Heating Mode

In the heat mode the liquid line solenoid is closed and


the compressor and condenser fans are shut down. The
heat valve is opened to allow a flow of engine coolant
through the heat section of the evaporator coil. The
evaporator fans speed is varied as required to circulate
air over the evaporator coil based on the temperature
difference from setpoint.
Heating will not start until the water temperature switch
(WTS) closes. The WTS is located on the block of the
vehicle and is provided by the OEM. It senses the engine
coolant temperature and closes on temperature rise at
105F . The switch prevents the circulation of cooler air
throughout the vehicle as the engine comes up to
temperature.
2-3

The unloaders are used to control system capacity by


controlling compressor capacity.
1 Compressor Unloader UV1 Relay. When return air
temperature falls to less than 2F (1.1C) above set
point unloader UV1 is energized. If temperature
rises to greater than 3F (1.7C) above set point,
UV--1 will be de--energized to place the compressor
at 100% capacity.
2 Compressor Unloader UV2 Relay. When return air
temperature falls to less than 1F (0.6C) above set
point unloader UV2 is energized. If temperature
rises to greater than 2F (1.1C) above set point,
UV--2 will be de--energized to place the compressor
(GR60 only) at 66% capacity.
b. Suction Pressure
T--295

The unloaders are used to control suction pressure and


thereby prevent coil frosting:
1 Compressor Unloader UV1 Relay. When the suction
pressure decreases below 26 psig (1.77 bar), unloader UV1 is energized unloading a cylinder bank (two
cylinders); this output will remain energized until
the pressure increases to above 34 psig (2.31 bar).
2 Compressor Unloader UV2 Relay. When suction
pressure decreases below 23 psig (1.56 bar) [on a
GR60], unloader UV2 is energized unloading the
second compressor cylinder bank; this output will
remain energized until the pressure increases to
above 31 psig (2.11 bar).
c. Discharge Pressure

Discharge pressure is also controlled by the unloaders:


1 Compressor Unloader UV1 Relay. When the discharge pressure increases above 275 psig (18.71
bar), unloader UV1 is energized; this output will remain energized until the pressure decreases below
220 psig (14.97 bar). Staging is ignored during discharge pressure override.
2 Compressor Unloader UV2 Relay. When the discharge pressure increases above 285 psig (19.39
bar),unloader UV2 is energized; this output will remain energized until the pressure decreases below
225 psig(15.31 bar).
2.3.8 Evaporator Fan Speed Selection

Temperature control is the primary method of


determining the fan speed selection. The following
table indicates relay operational status for the various
fan motor states while Figure 2-1 provides Logic Board
speed selections at various deviations form set point..
Table 2-1. Evaporator Fan Speed Relay Operation
STATE

Off
Low
High

HIGH
SPEED
RELAYS

EVAP FAN
RELAY

Off
Off
On

Off
On
On

2.3.10 Compressor Clutch Control

A belt driven electric clutch is employed to transmit


engine power to the air conditioning compressor.
De-energizing the clutch electric coil disengages the
clutch and removes power from the compressor. The
clutch will be engaged when in cooling and disengaged
when the system is off, in heating or during high and low
pressure conditions.
The clutch coil is prevented from engagement when the
ambient temperature is below 45F (7.2C).
The clutch coil will be de-energized if the discharge
pressure rises to the 300 psig (20.41 bar) cutout setting
of the compressor mounted high pressure switch. The
clutch coil will energize when the discharge pressure
falls to 200 psig (13.61 bar).
The clutch coil will be de-energized if the suction
pressure decreases below 10 psig (0.68 bar).
2.3.11 Alarm Description

Alarm descriptions and troubleshooting procedures are


provided in section 3.
2.3.12 Hour Meters

Hour meter readings are available in the parameter code


list of the Micromate. The hour meters record the
compressor run time and the total time the evaporator
fans are on. The maximum hours is 999,999. Refer to
paragraph 2.4.3 for instructions on reading parameter
codes.
2.4

MICROPROCESSOR DIAGNOSTICS

The Micromate allows the user to interface with the


microprocessor based control. This allows system
parameters, alarms and settings to be viewed and
modified. On systems with OEM supplied operating
switches, a Micromate may be connected as a service
tool using a special harness. The following instructions
supplement those provided in paragraph 2.1.2. Once a
Micromate is connected as a service tool, the following
instructions are applicable.
2.4.1 Connecting

2.3.9 Condenser Fan Control

The condenser fans are energized when the compressor


clutch output is energized. The fans are started in low
speed and will remain in low speed until the discharge
pressure increases to 225 psig (15.31 bar). The fans will
remain in high speed until discharge pressure decreases
below 190 psig (12.93 bar). The fans will also be

T--295

activated if a high pressure alarm has been activated and


operation has not been locked out (refer to Table 3-3).

2-4

Connect the Micromate harness to the service port


located in the return air section of the A/C system. When
the Micromate is connected, the panel lights will be
energized and the currently stored setpoint will be
displayed. If any alarm is active, the reading will be
A##, where A indicates that the alarm is active and ##
indicates the alarm number.

2.4.2 Control

2.4.4 System Parameters

Pressing the up/down arrow keys will allow the user to


scroll up or down through the parameters. If no key is
pressed for 30 seconds this mode is exited and the
display will revert back to the default display. Pressing
the on/off key any time will exit this mode and the
display will again indicate the default. The parameters
are shown in Table 2-3. When scrolling through the
parameters, the current parameter will be displayed for
two seconds. After two seconds, the display will show
the data for the current parameter. When the last
parameter is reached, the list will wrap back to P1.

NOTE
1

This procedure should be performed by an


HVAC technician who has been trained on
Carrier Model GR system design. Control
configuration is preset by the manufacturer
and resetting of the parameters should not
be required. It is recommended that Carrier
Service or Engineering is contacted before
any control configuration is changed.
Carrier can not be responsible for failures or
damage resulting from unauthorized
changes.

2.4.5 Test Mode

If a replacement Logic Module is installed,


it is necessary to match the configuration
jumpers (see Figure 1-10) to the original
board. Refer to paragraph 4.24.

a. Turn the A/C main power switch (located in the drivers area) to OFF.
b. Connect the Micromate to the service port located in
the return air section.
c. Unplug the logic board connector J3.
d. Turn the A/C main power switch back to the ON position.
e. Activate the system by pressing the 1/0 key on the
Micromate panel.
NOTE
Be sure to reconnect J3 when testing is completed or the system will fail to operate when
the Micromate is disconnected.

With the system in normal operation, the controller may


be placed in the test mode, by doing the following:
a. Enter the diagnostic mode by pressing the up and
down arrow keys simultaneously for 5 seconds. Enter
the test mode by pressing the COOL key five times.
b. In the test mode, the display will read T## where
## indicated the test number that is currently running.
c. The initial indication will be T00. This indicates
the controller is in the test mode and all relays are de-energized. Press the arrow keys to scroll through and
perform each test When the highest test number is
reached, the display will increment back to the lowest
test number. A listing of tests is provided in
Table 2-2.
d. To terminate testing, press the I/0 key.
Table 2-2. Controller Test List
OUTPUT
STATE
TEST

NOTE
When modifying the setpoint temperature for
diagnostic purposes, be sure to reset the setpoint when testing is complete.
2.4.3 Diagnostic Mode

Diagnostic mode can be entered by pressing the up and


down arrow keys simultaneously for 5 seconds.
Diagnostic mode allows alarms and system parameters
to be viewed. If there are any alarms stored, the most
recent alarm will be shown. To view additional alarm
information, refer to section 3. Press the up and down
arrow keys to view parameters.

2-5

T00
T01
T02
T03
T04
T05
T06
T07
T08
T09
T10
T11
T12

All Relays
Evaporator High
Evaporator Low
Condenser High
Condenser Low
Compressor
Unloader Valve 1
Unloader Valve 2
Fresh Air Damper
Heat
Fault
Boost
Spare/Motor Input

Off
On
On
On
On
On
On
On
On
On
On
On
On

T--295

Table 2-3. Parameter Codes


CODE

CODE NAME

DESCRIPTION

P1

Return Air
Temperature

This value is the temperature measured by the return air sensor. If the sensor is
shorted it will display CL. If it is open circuited it will display OP.

P2

Coil Temperature

This value is the coil temperature measured by the evaporator temperature sensor. If the sensor is shorted it will display CL. If it is open circuited it will display OP.

P3

Ambient Temperature

This value is the outside temperature measured by the ambient temperature


sensor. If the sensor is shorted it will display CL. If it is open circuited it will
display OP.

P4

Suction Line Temperature

Not used.

P5

Suction Pressure

This value is the suction pressure measured by the suction pressure transducer.
If the sensor is shorted it will display CL If it is open circuited it will display
OP.

P6

Discharge Pressure

This value is the discharge pressure measured by the discharge pressure transducer. If the sensor is shorted it will display CL and if it is open circuited it
will display OP.

P7

Superheat

Not used.

P8

Analog Set Point


Temperature

Not used.

P9

A/C Control Window


#1

This is the number of degrees F above setpoint at which the unloaders will be
both energized. This value can be modified between 0 and 10 degrees F. The
default value is 1 degree F.

P10

A/C Control Window


#2

This is the number of degrees F above AC control window one at which the
first unloader will be energized. This value can be modified between 0 and 10
degrees F. The default value is 1 degree F.

P11

A/C Control Window


#3

This is the number of degrees F above AC control window two at which the
evaporator fan speed will be set to low. This value can be modified between 0
and 10 degrees F. The default value is 1 degree F.

P12

Heat Control Window This is the number of degrees F below setpoint before the heat valve is energized. This value can be modified between 0 and 10 degrees F. The default value
is 2 degree F for heat and 4 degrees F for reheat.

P13

Compressor Safety
Off Delay

This number is the minimum time in minutes that the compressor must be off
after a high or low pressure alarm before it can be restarted. This value can be
modified between one and five minutes. The default value is 1.

P14

Fan Delay

This is the minimum time (in seconds) that the fans must run at a particular
speed before changing to another speed. This value can be modified between
one and 60 seconds. The default value is two seconds.

P15

Unloader/Heat Valve
Delay

This is the minimum time (in seconds) that the unloaders and heat valve must
be in a particular state (open /closed) before changing to another state. This
value can be modified between 1 and 60 seconds. The default value is 2 seconds.

P16

Compressor High
Pressure Switch

This is the current state of the compressor high pressure switch input. CL
will be displayed if it is closed and OP will be displayed if it is open.

P17

Condenser Fan Speed


Switch

Not used.

T--295

2-6

Table 2-3. Parameter Codes -- Continued


Code

Code Name

Description

P18

Maximum Setpoint

This is the maximum value that the operator will be allowed to set the setpoint
temperature. The value can be modified in degrees with the up and down keys
to a value between 60F and 80F.

P19

Minimum Setpoint

This is the minimum value that the operator will be allowed to set the setpoint
temperature. The value can be modified in degrees with the up and down keys
to a value between 60F and 80F.

P20

Compressor Hours
High

This is the number of hours of operation that the compressor has run with the
clutch energized in thousands

P21

Compressor Hours
Low

This is the number of hours of operation that the compressor has run with the
clutch energized in hundreds, tens and ones.

P22

Evaporator Hours
High

This is the number (in thousands) of hours of operation with the evaporator
fans energized.

P23

Evaporator Hours
Low

This is the number (in hundreds, tens and ones) of hours of operation with the
evaporator fans energized.

P24

Maintenance 1 Hour
High

This is the value of compressor hours high (P20) at which maintenance alarm
#1 will be activated. This value can be modified by the up and down arrow
keys. If both high and low values are zero the alarm is disabled.

P25

Maintenance 1 Hour
Low

This is the value of compressor hours low (P21) at which maintenance alarm
#1 will be activated. This value can be modified by the up and down arrow
keys. If both high and low values are zero the alarm is disabled.

P26

Maintenance 2 Hours
High

This is the value of evaporator fan hours high (P22) at which maintenance
alarm #2 will be activated. This value can be modified by the up and down arrow keys. If both high and low values are zero the alarm is disabled.

P27

Maintenance 2 Hours
Low

This is the value of evaporator fan hours low (P23) at which maintenance alarm
#2 will be activated. This value can be modified by the up and down arrow
keys. If both high and low values are zero the alarm is disabled.

P28

Freeze Alarm Setting

This is the value at which the freeze alarm will be activated. The default value
is 32F. This value can be modified between 20F and 40F in one degree increments by using the arrow keys

P29

Relay Module Voltage This is the voltage being supplied to the relay module.

P30

Main Board Software


Version

This is the software version of the logic board.

P31

Display Software
Version

This is the software version of the display module.

P32

Ki

Not used.

P33

Kp

Not used.

P34

Default Display

This is the value displayed on the Micromate control panel. It is set to OFF to
display set point temperature or set to ON to display return air temperature.
This feature is available in software revision 1.9 and later.

P33
to
P34

Not Defined

Not used. These codes will show in software revision 1.9 and later.

2-7

T--295

SECTION 3
TROUBLESHOOTING
CAUTION
Do not under any circumstances attempt to service the microprocessor. should a problem develop with
the microprocessor, replace it.
3.1 SELF DIAGNOSTICS

error codes can be read by counting the number of times


that the Logic Board STATUS and CODE LEDs (see
Figure 1-10) flash simultaneously. The Micromate
display will indicate errors with the code ER-#, where
ER is the error prefix and # is the error number.

A self test is performed by the Micromax Logic Board


each time the board is powered up. Errors, if any, will be
indicated and the unit will not be allowed to start. The

Table 3-1 Error Codes


CODE

NAME

DESCRIPTION

ER 1

Data Memory

Logic board data memory failure.

ER 2

Program Memory

Logic board program memory failure.

ER 3

A/D

A/D and multiplexer failure.

ER 4

Communication Failure

Failure in communication between the logic board and MDST.

ER 5

Program Memory

Display program memory failure.

3.2 SYSTEM ALARMS

3.2.2 Activation

When alarms are detected, they are placed in an alarm


queue in the order at which they initiated unless the
alarm is already present. Each alarm recorded will also
capture an evaporator hour meter reading corresponding
to the activation time. If the AUTO key is pressed while
an alarm is displayed, the activation time capture will be
shown.

3.2.1 Alarm Codes

The Micromax Logic Board continuously monitors


system parameters and will generate an ALARM if a
parameter exceeds preset limits. Alarms are indicated
and the controller will respond in accordance with the
information provided in Table 3-2. The alarm codes can
be read by counting the number of times that the Logic
Board CODE LED (see Figure 1-10) flashes. Each
alarm code is a two digit number, the first set of flashes
is the first digit and (after a slight pause) the second set
of flashes is the second digit. The Micromate display
will indicate alarms with the code A-## or i--##, where
A is an active alarm prefix, i is an inactive alarm
prefix and ## is the error number. If multiple alarms are
present the user can scroll through each alarm by
pressing the ARROW keys. When the end of the alarm
list is reached the display will show ------. If the auto
key is held down for five seconds while ------ is
displayed all inactive alarms are cleared. A listing of
alarm codes is provided in Table 3-2.

T-295

3.2.3 Alarm Queue

The alarm queue consist of 10 alarm locations. When


the alarm queue is full the Logic Board will take the
required action but the alarm will not be recorded. When
this situation occurs, an Alarm Queue Fullalarm will
be generated. When the alarms are viewed this will be
the first alarm to be shown.
3.2.4 Alarm Clear

The user may clear inactive alarms using the Micromate


keypad. Refer to paragraph 3.2.1.
3.3 TROUBLESHOOTING

General procedures for system troubleshooting are


provided in Table 3-3

3-1

Table 3-2 Alarm Codes


ALARM
NO.

TITLE

CAUSE

REMEDY

CONTROLLER
RESPONSE

A11

Coil Freeze

Coil temperature is
Check causes of coil
less than 32F and the freezing. (Refer to
compressor is operat- section 3.3.6)
ing.

An alarm will be generated and the system will


shutdown. The evaporator fans will remain running while the compressor is off.

A12

High Voltage

The battery voltage is


greater than 32 volts.

Check, repair or replace alternator.

The system is shut down


until the voltage returns
to normal levels.

A13

Low Voltage

The battery voltage is


less than 17 volts.

Check, repair or replace wiring or alternator.

The system is shut down


until the voltage returns
to normal levels.

A14

Return Air Probe Failure

Return air temperature Ensure all connectors


sensor failure or wir- are plugged in. Check
ing defective.
sensor resistance or
wiring. Refer to paragraph 4.21. Replace
sensor or repair wiring.

A15

Suction Pressure
Transducer Failure

Suction pressure
transducer failure or
wiring defective.

Ensure all connectors Both unloaders are enerare plugged in. Check gized.
sensor voltage or wiring. Replace sensor or
repair wiring.

A16

Discharge Pressure
Transducer Failure

Discharge pressure
transducer failure or
wiring defective.

Ensure all connectors One unloader is enerare plugged in. Check gized.
sensor voltage or wiring. Replace sensor or
repair wiring.

A17

Low Pressure Shutdown

Low suction pressure


switch open or wiring
defective.

Check cause of low


suction pressure. (Refer to section 3.5.3)

The clutch is de-energized for the minimum


off time. The evaporator
fans will remain running
during this period. After
the compressor cycles
off three times in 30
minutes all outputs will
be de-energized and the
system is locked out until the power is cycled or
the alarm is reset.

A21

High Discharge Pressure

High discharge pressure switch open or


wiring defective.

Check discharge pressure transducer reading, wiring or cause of


high discharge pressure. (Refer to section
3.3.3)

The clutch is de-energized for the minimum


off time. The condenser
and evaporator fans will
remain running during
this period. After the
compressor cycles off
three times in 30 minutes all outputs will be
de-energized and the
system is locked out until the power is cycled or
the alarm is reset.

3-2

All outputs except the


evaporator fans will be
de-energized.

T--295

Table 3-2 Alarm Codes -- Continued


TITLE

ALARM
NO

CAUSE

REMEDY

CONTROLLER
RESPONSE

A22

Breaker Trip Alarm

A23

Evaporator Fan Overload Evaporator fan overload jumper is open.

Ensure connector is
plugged in or repair
wiring.

Alarm will be generated.

A24

Condenser Fan Overload

Condenser fan overload jumper is open.

Ensure connector is
plugged in or repair
wiring.

Alarm will be generated.

A25

Motor Failure

A brushless motor has Replace motor, or cor- Alarm displayed and the
not reached full oper- rect pressure shutmotor fail output is enerating speed or a motor down.
gized.
failure.

A26

Not used

A31

Maintenance Alarm 1

The compressor hour


meter is greater than
the value in Maintenance Hour Meter 1.

Reset the maintenance Alarm will be generated.


hour meter.

A32

Maintenance Alarm 2

The evaporator hour


meter is greater than
the value in Maintenance Hour Meter 2.

Reset the maintenance Alarm will be generated.


hour meter.

A99

Alarm Queue Full

All locations of the


alarm queue are currently full and no
more alarms can be
saved.

Record and clear


alarm queue.

T-295

A breaker on the relay Check breakers for


Alarm will be generated.
board has tripped or a tripped device. Repair
fan relay has failed.
short and reset breaker.

3-3

Alarm will be generated.

Table 3-3 General System Troubleshooting Procedures


INDICATION/
TROUBLE
3.3.1 System Will Not Cool

Compressor will not run

Electrical malfunction

POSSIBLE CAUSES

Active system alarm


V-Belt loose or defective
Clutch coil defective
Clutch malfunction
Compressor malfunction
Coach power source defective
Circuit Breaker/safety device open

REFERENCE
SECTION

3.2
Check
Check/Replace
Check/Replace
See Table 1-2.
Check/Repair
Check/Reset

3.3.2 System Runs But Has Insufficient Cooling

Compressor
Refrigeration system

Restricted air flow


Heating system

V-Belt loose or defective


Compressor valves defective
Abnormal pressures
No or restricted evaporator air flow
Expansion valve malfunction
Restricted refrigerant flow
Low refrigerant charge
Service valves partially closed
Safety device open
Liquid solenoid valve stuck closed
No evaporator air flow or restriction
Heat valve stuck open

Check
See Table 1-2.
3.3.3
3.3.6
3.3.7
4.11
4.8
Open
1.6
Check
3.3.6
3.3.8

Discharge transducer failure


Refrigerant overcharge
Noncondensable in system
Condenser motor failure
Condenser coil dirty
Discharge transducer failure
Compressor valve(s) worn or broken
Low refrigerant charge
Compressor valve(s) worn or broken
Suction service valve partially closed
Filter-drier inlet valve partially closed
Filter-drier partially plugged
Low refrigerant charge
Expansion valve malfunction
Restricted air flow
Suction transducer failure
Compressor valve defective

Replace
4.8.1
Check
Check
Clean
See Note.
See Table 1-2.
4.8
See Table 1-2.
Open
Check/Open
4.11
4.8
3.3.7
3.3.6
Replace
See Table 1-2.

3.3.3 Abnormal Pressures

High discharge pressure

Low discharge pressure


High suction pressure
Low suction pressure

Suction and discharge pressures


tend to equalize when system is
operating

3.3.4 Abnormal Noise Or Vibrations

Compressor

Loose mounting hardware


Worn bearings
Worn or broken valves
Liquid slugging
Insufficient oil
Clutch loose, rubbing or is defective
V-belt cracked, worn or loose
Dirt or debris on fan blades

3-4

Check/Tighten
See Table 1-2.
SeeTable 1-2.
3.3.7
4.20.3
Check
Check/Adjust
Clean

T--295

Table 3-3 General System Troubleshooting Procedures -- Continued


INDICATION/
TROUBLE

POSSIBLE CAUSES

REFERENCE
SECTION

3.3.4 Abnormal Noise Or Vibrations -- Continued

Condenser or evaporator fans

Loose mounting hardware


Defective bearings
Blade interference
Blade missing or broken

Check/Tighten
Replace
Check
Check/Replace

3.3.5 Control System Malfunction

Will not control

Sensor or transducer defective


Relay(s) defective
Microprocessor controller malfunction
Logic Board J3 connector unplugged

4.21 or 4.22
Check
Check

3.3.6 No Evaporator Air Flow Or Restricted Air Flow

Air flow through coil blocked


No or partial evaporator air flow

Coil frosted over


Dirty coil
Dirty filter
Motor(s) defective
Motor brushes defective
Evaporator fan loose or defective
Fan damaged
Return air filter dirty
Icing of coil
Fan relay(s) defective
Safety device open
Fan rotation incorrect

Defrost coil
Clean
Clean/Replace
Repair/Replace
Replace
Repair/Replace
Repair/Replace
Clean/Replace
Clean/Defrost
Check/Replace
1.6
Check

3.3.7 Expansion Valve Malfunction

Low suction pressure with high


superheat

Low superheat and liquid slugging in the compressor


Side to side temperature difference (Warm Coil)

Low refrigerant charge


Wax, oil or dirt plugging valve orifice
Ice formation at valve seat
Power assembly failure
Loss of bulb charge
Broken capillary tube
Bulb is loose or not installed.
Superheat setting too low
Ice or other foreign material holding valve open
Wax, oil or dirt plugging valve orifice
Ice formation at valve seat
Power assembly failure
Loss of bulb charge
Broken capillary

4.8
Check
4.6
Replace
Replace
4.19
4.19
4.19
Check
4.7
Replace
Replace
4.19

3.3.8 Heating Malfunction

Insufficient heating

No Heating

Continuous Heating

T-295

Dirty or plugged heater core


Coolant solenoid valve(s) malfunctioning or plugged
Low coolant level
Strainer(s) plugged
Hand valve(s) closed
Water pumps defective
Auxiliary Heater malfunctioning.
Coolant solenoid valve(s) malfunctioning or plugged
Controller malfunction
Pump(s) malfunctioning
Safety device open
Coolant solenoid valve stuck open

3-5

Clean
Check/Replace
Check
Clean
Open
Repair/Replace
Repair/Replace
Check/Replace
Replace
Repair/Replace
1.6
Replace

SECTION 4
SERVICE

WARNING
BE SURE TO OBSERVE WARNINGS LISTED IN THE SAFETY SUMMARY IN THE FRONT OF
THIS MANUAL BEFORE PERFORMING MAINTENANCE ON THE HVAC SYSTEM

NOTE
Following completion of all maintenance or service activities, the alarm queue should be cleared of any original alarms and any alarms generated during service. Refer to paragraph 3.2.1
4.1 MAINTENANCE SCHEDULE
SYSTEM
ON

REFERENCE
SECTION

SYSTEM

OFF

a. Daily Maintenance
X
X

Pre-trip Inspection -- after starting


Check tension and condition of V-belt

2.2
None

b. Weekly Inspection
X
X
X
X

Perform daily inspection


Check condenser, evaporator coils and air filters for cleanliness
Check refrigerant hoses and compressor shaft seal for leaks
Feel filter-drier for excessive temperature drop across drier

See above
None
4.6
4.11

c. Monthly Inspection and Maintenance


X
X
X
X
X
X

Perform weekly inspection and maintenance


Clean evaporator drain pans and hoses
Check wire harnesses for chafing and loose terminals
Check fan motor bearings
Check compressor mounting bolts for tightness
Check fan motor brushes

4.2 OPENING TOP COVER

See above
None
Replace/Tighten
None
None
None

4.3 SUCTION AND DISCHARGE SERVICE VALVES

To open the top cover, push in on the latches and pull


forward as the cover is lifted . (See Figure 4-1.)

The suction and discharge service valves (Figure 4-2)


are provided with a double seat and a gauge port, which
allows servicing of the compressor and refrigerant lines.
Turning the valve stem counterclockwise (all the way
out) will backseat the valve to open the line to the
compressor and close off the gauge port. In normal
operation, the valve is backseated to allow full flow
through the valve. The valve should always be
backseated before removing the gauge port cap.

1
PUSH IN ON LATCHES

PULL & LIFT

Turning the valve stem clockwise (all the way forward)


will frontseat the valve to isolate the compressor line
and open the gauge port.

To measure suction or discharge pressure, midseat the


valve by opening the valve clockwise 1/4 to 1/2 turn.
With the valve stem midway between frontseated and
backseated positions, the suction or discharge gauge
port is open to both the compressor and the line.

Figure 4-1. Opening Top Cover


4-1

T-295

e. Frontseat (clockwise) both manifold gauge hand


valves.
f. Turn the service valve connected to the discharge
gauge port toward frontseat (clockwise) approximately 1/4 to 1/2 turn.
g. Slowly turn the manifold discharge hand valve toward backseat (counterclockwise) approximately
one turn.
h. Tighten charging hose onto dummy fitting.

VALVE CAP

TO DISCHARGE OR
FROM SUCTION
LINE

SERVICE
PORT

PORT TO
COMPRESSOR
Service Valve
Frontseated
(clockwise)

VALVE
STEM

i. Slowly turn the manifold suction hand valve toward


backseat (counter--clockwise) to remove air from
line.
j. Tighten suction hose at the service valve port.
k. Frontseat (close) both manifold hand valves.

Service Valve
Backseated
(counterclockwise)

Figure 4-2.Suction or Discharge Service Valve

l. Turn the service valve connected to the suction gauge


port toward frontseat (clockwise) approximately 1/4
to 1/2 turn.

4.4 INSTALLING MANIFOLD GAUGE SET

A manifold gauge set (Figure 4-3) can be used to


determine system operating pressures, add charge,
equalize or evacuate the system.
Suction
Pressure
Gauge

4.5 PUMPING THE SYSTEM DOWN OR REMOVING THE REFRIGERANT CHARGE

NOTE
To avoid damage to the earths ozone layer, use
a refrigerant recovery system whenever removing refrigerant.

Discharge
Pressure
Gauge

4.5.1 System Pump Down For Low Side Repair

Hand Valve
(Backseated)
A.
B.
C.

To service or replace the filter--drier, thermostatic


expansion valve, suction line or evaporator coils, pump
the refrigerant to the condenser and receiver as follows:
a. Install manifold gauge set. Refer to Figure 4-4

Hand Valve
(Frontseated)

Connection to Low Side of System


Connection to High Side of System
Connection to Vacuum Pump, Refrigerant
Cylinder, Oil Container or Evacuation Line

b. Frontseat the filter--drier inlet service valve by turning clockwise. Disconnect suction pressure transducer and install a jumper on the compressor mounted
low pressure switch.
c. Start the system and run in cooling. Stop the unit
when suction reaches 10 /hg (25.4 cm/hg) vacuum.

Figure 4-3. Manifold Gauge Set

When the suction pressure hand valve is frontseated


(turned all the way in), the suction (low) pressure can be
read. When the discharge pressure hand valve is
frontseated, discharge (high) pressure can be read.
When both valves are open (turned counterclockwise),
high pressure vapor will flow into the low side. When
only the low pressure valve is open, the system can be
charged or evacuated. To install a manifold gauge set,
do the following (refer to Figure 4-4, Figure 4-5 or
Figure 4-6 as applicable).

d. Frontseat compressor suction service valve to trap refrigerant in the high side of the system between the
compressor suction service valve and the filter--drier
inlet valve. Wait 5 minutes to verify that system remains in a vacuum. If system pressure rises above
vacuum, open compressor suction service valve and
repeat steps c and d until system remains in vacuum.
e. Service or replace necessary components.
f. Leak check connections and replace filter--drier. Refer to paragraph 4.6.
g. Using refrigerant hoses designed for vacuum service,
evacuate and dehydrate the low side of the system by
connecting a vacuum pump to center connection of
manifold gauge set. Evacuate system to 500 microns.
Close off pump valve, isolate vacuum gauge and stop
pump. Wait 5 minutes to verify that vacuum holds.
h. Recharge low side to 20 to 30 psig (1.36 to 2.04 bar)
by admitting vapor from the refrigerant cylinder.

a. Remove the service valve stem caps and backseat


(counterclockwise) both valves. Remove the service
port caps.
b. Connect the discharge side hose tightly to the service
valve port.
c. Connect the suction side hose loosely to the other service valve port.
d. Loosen charging (center) hose at dummy fitting of
manifold set.
T-295

4-2

f. Check refrigerant level. Refer to paragraph 4.8.1. It


may be necessary to clear any alarms that have been
generated.

3
S D

5
S D

10

9
1

2
1
1. Filter-Drier Inlet
Service Valve
2. Thermostatic
Expansion Valve
3. Manifold Gauge
Set
4. Thermistor Vacuum
Gauge

5
7

5.
6.
7.
8.
9.

Vacuum Pump
Refrigerant Cylinder
Reclaimer
Filter-Drier
Liquid Solenoid
Valve
10. Filter-Drier Outlet
Service Valve

6
1. Discharge Service
Valve and Port
2. Suction Service
Valve and Port
3. Manifold Gauge
Set

4.
5.
6.
7.

Vacuum Pump
Reclaimer
Refrigerant Cylinder
Thermistor Vacuum
Gauge

Figure 4-4. Low Side Pump Down Connections


Figure 4-5. Compressor Service Connections

i. Re--connect suction pressure transducer and remove


low pressure switch jumper. If required, clear any
alarms that have been generated during this procedure.

4.5.3 Pump Down An Operable Compressor For


Repair

To service an operable compressor, pump the refrigerant


into the condenser coil and receiver as follows:
a. Install manifold gauge set. Refer to Figure 4-5.
b. Frontseat the compressor suction service valve by
turning clockwise.
c. Place a jumper on the low pressure switch. Start the
unit and run in cooling until 10 /hg (25.4 cm/hg) of
vacuum is reached. Shut the system down.
d. Frontseat the compressor discharge service valve and
wait 5 minutes to verify vacuum is maintained. If the
pressure rises above vacuum, open the compressor
discharge service valve and repeat steps c and d until a
vacuum is maintained.
e. Service or replace components as required and leak
check the compressor.
f. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of manifold gauge set. Evacuate system to 500 microns.
Close off pump valve, isolate vacuum gauge and stop
pump. Wait 5 minutes to verify that vacuum holds.
g. Once vacuum is maintained, re--connect low pressure
switch, disconnect manifold gauge set and open compressor service valves.
h. Check refrigerant level. Refer to paragraph 4.8.1. It
may be necessary to clear any alarms that have been
generated.

j. Open service valves and check refrigerant level. Refer to paragraph 4.8.1.
4.5.2 Refrigerant Removal From An Inoperative
Compressor.

To remove the refrigerant from a compressor that is not


operational, do the following:
a. Attach a manifold gauge set as shown in Figure 4-5
and isolate the compressor by frontseating the suction
and discharge valves.
b. Recover refrigerant with a refrigerant reclaimer. If the
discharge service valve port is not accessible, it will
be necessary to recover refrigerant through the suction service valve port only.
c. Service or replace components as required and leak
check the compressor.
d. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump to center connection of manifold gauge set. Evacuate system to 500 microns.
Close off pump valve, isolate vacuum gauge and stop
pump. Wait 5 minutes to verify that vacuum holds.
e. Once vacuum is maintained, recharge low side to 20
to 30 psig (1.36 to 2.04 bar) by admitting vapor from
the refrigerant cylinder. Disconnect manifold gauge
set and backseat compressor service valves.
4-3

T-295

c. Add sufficient nitrogen to raise system pressure to


150 to 200 psig (10.21 to 13.61 bar).
d. Check for leaks. The recommended procedure for
finding leaks in a system is with an electronic leak detector. Testing joints with soapsuds is satisfactory
only for locating large leaks.
e. Remove test gas and replace filter--drier.
f. Evacuate and dehydrate the system. (Refer to paragraph 4.7.)
g. Charge the unit. (Refer to paragraph 4.8.)
h. Ensure that a Logic Board self-test has been performed and that there are no errors or alarms indicated. (Refer to paragraph 2.1.3.)

4
S D

3
1

4.7 EVACUATION AND DEHYDRATION


6
8

4.7.1 General

1. Suction Service
Valve and Port
2. Discharge Line
Service Port
3 Check Valve
4. Manifold Gauge

5.
6.
7.
8.

The presence of moisture in a refrigeration system can


have many undesirable effects. The most common are
copper plating, acid sludge formation, freezing-up of
metering devices by free water, and formation of acids,
resulting in metal corrosion.

Set
Vacuum Pump
Reclaimer
Refrigerant Cylinder
Thermistor Vacuum
Gauge

4.7.2 Preparation

NOTE
Using a compound gauge for determination of
vacuum level is not recommended because of
its inherent inaccuracy.

Figure 4-6. System Charge Removal Connections


4.5.4. Removing Entire System Charge

To remove the entire refrigerant charge, do the


following:
a. Connect a manifold gauge set to the system as shown
in Figure 4-6.

a. Evacuate and dehydrate only after pressure leak test.


(Refer to paragraph 4.6)
b. Essential tools to properly evacuate and dehydrate
any system include a good vacuum pump with a minimum of 5 cfm (8.5 m 3/hr) volume displacement,
(CTD P/N 07-00176-01), and a good vacuum indicator (available through Robinair Manufacturing,
Montpelier, Ohio, Part Number 14010).
c. Keep the ambient temperature above 60F (15.6C)
to speed evaporation of moisture. If ambient temperature is lower than 60F (15.6C), ice may form before
moisture removal is complete.

b. Connect a reclaimer to the center manifold gauge set


connection.
c. Recover refrigerant in accordance with reclaimer
manufacturers instructions.
4.6 REFRIGERANT LEAK CHECK

A refrigerant leak check should always be performed


after the system has been opened to replace or repair a
component.

4.7.3 Procedure for Evacuation and Dehydrating


System

To check for leaks in the refrigeration system, perform


the following procedure:

a. Remove refrigerant using a refrigerant recovery system. Refer to paragraph 4.5.4


b. The recommended method is connecting lines (3/8
OD copper tubing or refrigerant hoses designed for
vacuum service) as shown in Figure 4-6.
c. Make sure vacuum pump valve is open.
d. Start vacuum pump. Slowly open valves halfway and
then open vacuum gauge valve.
e. Evacuate unit until vacuum gauge indicates 1500 microns Hg vacuum. Close gauge valve, vacuum pump
valve, and stop vacuum pump.
f. Break the vacuum with clean dry refrigerant. Use refrigerant that the unit calls for. Raise system pressure
to approximately 2 psig (0.14 bar).

NOTE
It must be emphasized that only the correct refrigerant should be used to pressurize the system. Use of any other refrigerant will contaminate the system, and require additional
evacuation.
a. Ensure the liquid line service and solenoid valves are
open.
b. If system is without refrigerant, charge system with
refrigerant vapor to build up pressure between 20 to
30 psig (1.36 to 2.04 bar).
T-295

4-4

4.8.3 Adding Partial Charge

g. Remove refrigerant using a refrigerant recovery system.

a. Install manifold gauge set at the compressor suction


service valve and service port above the discharge
line check valve. See figure Figure 4-6.
b. Place appropriate refrigerant cylinder on scales. Prepare to charge vapor refrigerant by connecting charging hose from container to center connection on
gauge manifold . Purge air from hoses.
c. Run unit in cool mode for 15 minutes. With suction
service valve midseated open cylinder valve and add
vapor charge until refrigerant level appears in the
lower receiver sight glass. Under the above conditions, the system is properly charged when the refrigerant liquid level is at 1/2 to 3/4 of the lower receiver
sight glass. If it is not at the proper level, add or remove refrigerant to bring it to the proper level. Refrigerant level should not appear in the upper sight
glass, as this would indicate an overcharge.
d. Backseat suction service valve. Close vapor valve on
refrigerant drum and note weight. Remove manifold
gauge set and replace all valve caps.

h. Start vacuum pump and open all valves. Dehydrate


unit to 500 microns Hg vacuum.
i. Close off pump valve, and stop pump. Wait five minutes to see if vacuum holds.
j. Charge system. Refer to paragraph 4.8.2
4.8 ADDING REFRIGERANT TO SYSTEM
4.8.1 Checking Refrigerant Charge

The following conditions must be met to accurately


check the refrigerant charge.
a. Coach engine operating at high idle.
b. Unit operating in cool mode for 15 minutes.
c. Head pressure at least 150 psig (10.21 bar). (It may be
necessary to block condenser air flow to raise head
pressure.)

4.9 CHECKING FOR NONCONDENSIBLES

d. Under the above conditions, the system is properly


charged when the refrigerant liquid level is at 1/2 to
3/4 of the lower receiver sight glass. If it is not at the
proper level, add or remove refrigerant to bring it to
the proper level. Refrigerant level should not appear
in the upper sight glass, as this would indicate an
overcharge.

To check for noncondensibles, proceed as follows:


a. Stabilize system to equalize pressure between the
suction and discharge side of the system.
b. Check temperature at the condenser and receiver.
c. Check pressure at the compressor discharge service
valve.
d. Check saturation pressure as it corresponds to the
condenser/receiver temperature using the Temperature-Pressure Chart, Table 4-4.
e. If gauge reading is 3 psig (0.20 bar) or more than the
saturation pressure in step d, noncondensibles are
present.
f. Remove refrigerant using a refrigerant recovery system.
g. Evacuate and dehydrate the system. (Refer to paragraph 4.7.)
h. Charge the unit. (Refer to paragraph 4.8.2.)

4.8.2 Adding Full Charge

a. Install manifold gauge set at the compressor suction


service valve and service port above the discharge
line check valve. See figure Figure 4-6.
b. Evacuate and dehydrate system. (Refer to paragraph
4.7)
c. Place appropriate refrigerant cylinder on scales. Prepare to charge liquid refrigerant by connect charging
hose from container to center connection on gage
manifold . Purge air from hoses.
d. Note weight of refrigerant and cylinder.

4.10 CHECKING AND REPLACING HIGH PRESSURE SWITCH

e. Open cylinder valve, backseat discharge valve on


gauge manifold and allow liquid refrigerant to flow
into the high side of the system

WARNING
DO NOT USE A NITROGEN CYLINDER
WITHOUT A PRESSURE REGULATOR

f. When correct charge has been added, refer to paragraph 1.3, close cylinder valve and frontseat manifold discharge valve. At this point, the high side of
the system has been charged but the low side is still in
a vacuum because the liquid line solenoid is normally
closed.

WARNING
DO NOT USE OXYGEN IN OR NEAR A
REFRIGERATION SYSTEM AS AN EXPLOSION MAY OCCUR.

g. Prepare the cylinder as required to allow vapor charging. Backseat the manifold suction valve and charge
vapor to build 20 to 30 psig (1.36 to 2.04 bar) pressure on the manifold suction gauge. Close cylinder
valve and frontseat suction manifold set.

a. Disconnect wiring and remove switch from unit. All


units are equipped with a schrader valve at the high
pressure switch connection.
b. Connect switch to a cylinder of dry nitrogen. (See
Figure 4-7.)

h. Check charge level in accordance with the procedures


of paragraph 4.8.1.
4-5

T-295

4.11.2 To Replace Filter--Drier

a. Perform a low side pump down. Refer to paragraph


4.5.1.

4
5

b. Turn the drivers A/C switch to OFF position.


6

c. Frontseat the filter--drier outlet service valve and


place a new filter-drier near the unit for immediate
installation.

1.
2.
3.
4.
5.
6.

WARNING
THE FILTER-DRIER MAY CONTAIN
LIQUID REFRIGERANT. SLOWLY
LOOSEN THE FLARE NUTS AND AVOID
CONTACT WITH EXPOSED SKIN OR
EYES.

Cylinder Valve and Gauge


Pressure Regulator
Nitrogen Cylinder
Pressure Gauge (0 to 400 psig = 0 to 27.22 bar)
Bleed-Off Valve
1/4 inch Connection

d. Using two open end wrenches, slowly crack open the


flare nuts on each side of the filter-drier. Remove the
filter-drier.

Figure 4-7. Checking High Pressure Switch

e. Remove seal caps from the new filter-drier. Apply a


light coat of compressor oil to the flares.

c. Connect an ohmmeter across switch terminals.

f. Assemble the new filter-drier to lines ensuring that


the arrow on the body of the filter-drier points in the
direction of the refrigerant flow (refrigerant flows
from the receiver to the evaporator). Finger tighten
flare nuts.

d. Set nitrogen pressure regulator higher than switch


cutout setting. (refer to paragraph 1.3.)
e. Close cylinder valve and open bleed--off valve. Open
cylinder valve and slowly close bleed--off valve. The
switch should open, (no continuity) with in required
cut out tolerance.

g. Tighten filter-drier flare nuts using two open end


wrenches.

f. Close cylinder valve and release pressure through the


bleed-off valve. As pressure drops, switch should
close, (continuity) within required cut in tolerance.

h. Evacuate the filter--drier and lines by connecting a


vacuum pump as shown in Figure 4-4. Evacuate to
500 microns.

g. Replace or re--install switch (as required) and reconnect wiring.

i. Backseat (fully close) both service valve ports and replace valve caps.

4.11 FILTER-DRIER

j. Test filter-drier for leaks.


k. Check refrigerant level.
4.12 CONDENSER COIL REPLACEMENT

1
1.
2.
3.
4.

Filter-Drier Inlet
Service Valve
Valve Service Port
Flare Nut
Filter-Drier

3
5
6.

a. Place the drivers A/C switch in the OFF position and


tag to prevent unintentional starting.

b. Remove the refrigerant charge. Refer to paragraph


4.5.4.

Liquid Line
Solenoid Valve
Filter-Drier Outlet
Service Valve

c. Remove the connection access covers to gain access


to the mounting screws. Remove the mounting
screws in the connection compartment and at the rear
of the unit next to the receiver supports.
d. Remove the filter--drier mounting screws and remove
the filter--drier. Disconnect the discharge hose.

Figure 4-8. Filter--Drier Removal


4.11.1 To Check Filter--Drier

e. Begin to lift the coil assembly at the left rear. Lift to


clear the service valve then push to the right to clear
the precharge valve. Continue to lift towards the front
to clear the sight glasses and remove from the unit.

The filter--drier (see Figure 4-8) must be changed if the


receiver mounted moisture indicator shows high
moisture content or the drier is partially restricted.
Check for a restriction by feeling the inlet and outlet
lines of the filter--drier. If the outlet side feels cooler than
the inlet side, then the filter--drier should be changed
T-295

f. To install the coil assembly, reverse the removal procedure.


4-6

4.13 EVAPORATOR COIL REPLACEMENT

b. Place main battery disconnect switch in OFF position


and lock.
c. Disconnect wire leads to coil.
d. Remove coil retaining screw and nameplate.
e. Lift burned-out coil from enclosing tube and replace.
f. Connect wire leads and test operation.

a. If refrigerant remains in the system, perform a low


side pump down to remove refrigerant from the evaporator coils.
CAUTION
If unit was recently operated, be careful of
remaining hot coolant in the hoses when disassembling.

4.14.2 Internal Part Replacement

a. Place main battery disconnect switch in OFF position


and lock.
b. Open the vent fitting at the top of the outlet header of
the heater coil.
c. Drain coil by opening the drain-cock on the inlet tube.
d. Disassemble valve and replace defective parts.
e. Assemble valve, refill and bleed coolant lines.

b. Remove fresh air intake.


c. Drain heater coil by removing the required coolant
from the engine cooling system.
d. Remove 12 mounting screws, 4 each at the receiver
support, at the front of the unit and at the return air
opening.
e. Remove the electronic board and harness.
f. Remove the filter--drier.
g. Disconnect suction line hose and lift coil out of unit.
h. To install the coil assembly, reverse the removal procedure.

4.14.3 Replace Entire Valve

a. Place main battery disconnect switch in OFF position


and lock.
b. Drain coolant from lines as previously described and
disconnect hoses to valve .
c. Disconnect wire leads to coil.
d. Remove valve assembly from bracket.
e. Install new valve and re-connect hoses. It is not necessary to disassemble the valve when installing.
f. Refill and bleed coolant lines.
g. Connect wire leads and test operation.
1
2

4.14 SERVICING THE HEAT VALVE

The heat valve (Figure 4-9) requires no maintenance


unless a malfunction to the internal parts or coil occurs.
This may be caused by foreign material such as: dirt,
scale, or sludge in the coolant system, or improper
voltage to the coil.
There are only three possible valve malfunctions: coil
burnout, failure to open, or failure to close.
Coil burnout may be caused by the following:

1 Improper voltage.
2 Continuous over-voltage, more than 10% or Undervoltage of more than 15%.
3. Incomplete magnetic circuit due to the omission of
the coil housing or plunger.

1 Coil burned out or an open circuit to coil connections.

5
6
7
8
9

2 Improper voltage.
3 Torn diaphragm.
4 Defective plunger or deformed valve body assembly.

10

4. Mechanical interference with movement of plunger


which may be caused by a deformed enclosing tube.
Failure to open may be caused by the following:

Failure to close may be caused by the following:


1. Coil Retaining Screw
2. Nameplate
3. Coil Housing
Assembly
4. Enclosing Tube &
Bonnet Assembly

1 Defective plunger or deformed valve body assembly.


2 Foreign material in the valve.
3 Torn diaphragm.
4.14.1 Coil Replacement

a. It is not necessary to drain the coolant from the system.

5.
6.
7.
8.
9.
10.

Kick-Off Spring
Plunger
Closing Spring
Diaphragm
O-Ring
Valve Body

Figure 4-9. Heat Valve


4-7

T-295

4.15 SERVICING THE LIQUID LINE SOLENOID


VALVE

2
The Liquid line solenoid valve (Figure 4-10) is very
similar to the heat valve. It requires no maintenance
unless a malfunction to the internal parts or coil occurs.
This may be caused by foreign material such as: dirt,
scale, or sludge in the refrigeration system, or improper
voltage to the coil.

There are only three possible valve malfunctions: coil


burnout, failure to open, or failure to close.

4
5

Coil burnout may be caused by the following:

1 Improper voltage.

2 Continuous over-voltage, more than 10% or undervoltage of more than 15%.

7
8

3 Incomplete magnet circuit due to the omission of the


coil hosing or plunger.

1. Snap Cap
2. Coil Assembly
3. Enclosing Tube
Assembly
4. Plunger Assembly

4 Mechanical interface with movement of plunger


which may be caused by a deformed enclosing tube.
Failure to open may be caused by the following:

1 Coil burned out or an open circuit to coil connections.

5.
6.
7.
8.

Gasket
Piston Assembly
Body
Bracket Adapter

Figure 4-10. Liquid Line Solenoid Valve


4.15.3.Replace Entire Valve

2 Improper voltage.

a. Perform a low side pump down, remove coil and


plunger assembly and un--braze valve from lines.
b. Remove valve assembly from bracket.
c. Disconnect wire leads to coil.
d. Disassemble new valve, to protect internal parts, and
solder to lines.
e. Assemble and leak check valve.
f. Evacuate low side and re--open system.
g. Connect wire leads and test operation.

3 Defective plunger or deformed valve body assembly.


Failure to close may be caused by the following:

1 Defective plunger or deformed valve body assembly.


2 Foreign material in the valve.
4.15.1 Coil Replacement

a. It is not necessary to remove the refrigerant charge


from the system.
b. .Place main battery disconnect switch in OFF position and lock.

4.16 CONDENSER FAN/MOTOR ASSEMBLY

c. Disconnect wire leads to coil.

a. Place main battery disconnect switch in OFF position


and lock.
b. Unlatch motor draw latches. See Figure 4-11.
c. Disconnect motor wire harness and lift motor out of
unit.

4.16.1 Removal

d. Remove coil retaining clip and nameplate.


e. Lift burned-out coil from enclosing tube and replace.
f. Connect wire leads and test operation

4.15.2 Internal Part Replacement

a. Place main battery disconnect switch in OFF position


and lock.

b. Perform a low side pump down. Refer to paragraph


4.5.1.

c. Slowly loosen enclosing tube assembly to bleed any


remaining pressure from the valve. Disassemble
valve and replace defective parts.

1. Motor Support
2. Draw Latch
3. Fan/Motor Assembly

d. Assemble valve and leak check.


e. Evacuate low side and re--open system.
T-295

4. Motor
5. Brush

Figure 4-11. Condenser Fan/Motor Assembly


4-8

4.16.2 Inspection And Cleaning

d. To reassemble, reverse procedure.

a. At regular maintenance periods, remove brush covers, examine and clean motor interior.

4.18 REPLACING RETURN AIR FILTERS

The return air filters are located behind the return air
grill, inside the vehicle.
The filters should be checked for cleanliness
periodically depending on operating conditions. A dirty
filter will restrict air flow over the evaporator coil which
may cause insufficient cooling or heating and possible
frost buildup on the coil. To remove the filters, do the
following.
a. Place main battery disconnect switch in OFF position
and lock.
b. Remove the return air grille.
c. Loosen filter retaining clips and remove the filter
from the grille.
d. Reverse procedure to install new filters.

b. Place main battery disconnect switch in OFF position


and lock.
c. Remove all foreign material. such as dirt and carbon
dust with dry moderately compressed air. Clean by
suction if possible to avoid blowing foreign matter
into the motor.
d. Confirm free movement of brushes to prevent binding.
e. Examine brush wear and general condition. If broken, cracked chipped or worn to 1/3 the original
length, replace. Refer to paragraph 4.16.3.
f. Examine the condition of the brush springs. A discolored spring is a sign of overheating which may weaken the spring. If discolored, replace.
g. Observe condition of communtator and armature
coils

4.19 THERMOSTATIC EXPANSION VALVE

The thermostat expansion valve (Figure 4-13) is an


automatic device which maintains constant superheat of
the refrigerant gas leaving the evaporator regardless of
suction pressure. The valve functions are: (a) automatic
control of refrigerant flow to match the evaporator load
and (b) prevention of liquid refrigerant entering the
compressor. Unless the valve is defective, it seldom
requires any maintenance.

4.16.3 Brush Replacement

a. Place main battery disconnect switch in OFF position


and lock.
b. Remove condenser motor, refer to paragraph 4.16.1.
c. Remove brush covers, remove and inspect brush assemblies. Replace if required.

d. Replace brush covers and reinstall condenser motor.


e. To reassemble, reverse the above procedure. Ensure
motor is properly seated in support.
f. Verify the proper operation of motor.

2
3
4
5
4

6
MOUNTING
CLIP

7
1. Power Head
Assembly
2. Equalizer Connection
3. Bulb

4.
5.
6.
7.

Gasket
Cage Assembly
Body Flange
Cap screw

Figure 4-13. Thermostatic Expansion Valve


4.19.1 Valve Replacement

Figure 4-12. Evaporator Fan Removal

a. Pump down low side of the unit. (Refer to paragraph


4.5.1)
b. Remove insulation from expansion valve bulb. (See
Figure 4-13 and Figure 4-14.)
c. Loosen retaining straps holding bulb to suction line
and detach bulb from the suction line.
d. Loosen flare nuts on equalizer line and disconnect
equalizer line from the expansion valve.

4.17 REPLACING EVAPORATOR FAN

a. Place main battery disconnect switch in OFF position


and lock.
b. Disconnect wire leads to the motor. Mark leads for
proper reassembly.
c. Remove motor by lifting the mounting clip (see
Figure 4-12) up and out. Slide motor from unit.
4-9

T-295

e. Remove capscrews and lift off power head and cage


assemblies and gaskets.

c. Loosen one TXV bulb clamp and make sure area under clamp is clean.

f. Check, clean and remove any foreign material from


the valve body, valve seat and mating surfaces. If required, replace valve body.

d. Place temperature thermocouple in contact with the


suction tube and parallel to the TXV bulb, and then
secure loosened clamp making sure both bulb and
thermocouple are firmly secured to suction line.
(SeeFigure 4-14.) Reinstall insulation around the
bulb.

NOTE
Do not adjust the new replacement expansion
valve. Valves are preset at the factory.

e. Connect an accurate low pressure gauge to the low


pressure port (9, Figure 1-6)
f. Close top cover being careful to route thermocouple
sensing wire and gauge hose outside the unit.

g. Using new gaskets, install new cage and power head


assemblies.

g. Start bus and run on fast idle until unit has stabilized,
about 20 to 30 minutes.

h. Leak check the new valve and evacuate and dehydrate


low side. (Refer to paragraph 4.7.)

NOTE
When conducting this test, the suction pressure
must be at least 6 psig (0.41 bar) below the expansion valve maximum operating pressure
(MOP). Refer to paragraph 1.3 for MOP.

i. The thermal bulb is installed below the center of the


suction line (four or eight oclock position). This area
must be clean to ensure positive bulb contact. Strap
thermal bulb to suction line. Ensure that retaining
straps are tight and renew insulation.
j. Fasten equalizer line to the expansion valve.

h. From the temperature/pressure chart (Table 4-4), determine the saturation temperature corresponding to
the evaporator outlet pressure.

k. Open filter-drier inlet service valve and compressor


service valves.
l. Run the coach for approximately 30 minutes on fast
idle.

i. Note the temperature of the suction gas at the expansion valve bulb. Subtract the saturation temperature
from this temperature. The difference is the superheat
of the suction gas.

m.Check refrigerant level. (Refer to paragraph 4.8.1)


n. Check superheat. (Refer to paragraph 4.19.2.)

j. The superheat may cycle from a low to high reading.


Monitor the superheat taking readings every 3--5
minutes for a total of 5--6 readings. Calculate the superheats, add the readings and divide by the number
of readings taken to determine average superheat.
The superheat should be 10F to 12F.

4.19.2 Superheat Measurement

NOTE
All readings must be taken from the TXV bulb
location and out of the direct air stream.

k. If superheat is not within tolerance, replace the valve.


4.20 COMPRESSOR MAINTENANCE
4.20.1 Removing the Compressor

If compressor is inoperative and the unit still has


refrigerant pressure, isolate the compressor and remove
the refrigerant. Refer to paragraph 4.5.2. If compressor
is operative, perform a pump down. Refer to paragraph
4.5.3.

5
1

1. Suction Line
(section view)
2. TXV Bulb Clamp
3. Nut & Bolt (clamp)

a. Place main battery disconnect switch in OFF position


and lock.

4. Thermocouple
5. TXV Bulb (Shown
in the 4clock
position)

b. Loosen bolts at suction and discharge service valve


flanges and break seal to be sure pressure is released.
remove bolts.
c. Tag and disconnect wiring to the high pressure and
low pressure switch, unloaders and clutch.

Figure 4-14.Thermostatic Expansion Valve Bulb


and Thermocouple

d. Remove four bolts holding compressor to base

a. Open top cover. Refer to paragraph 4.2.

e. Attach sling or other device to the compressor and remove compressor from the coach through the rear access door.

b. Remove Presstite insulation from expansion valve


bulb and suction line.
T-295

4-10

ate compressor to 500 microns. Front seat both manifold valves to isolate the pump.
l. Start unit and check refrigerant level (refer to paragraph 4.8.1).
m.Check compressor oil level (refer to paragraph
4.20.3). Add or remove oil if necessary.
n. Check compressor unloader operation.
o. Remove manifold gauge set.

NOTES
1

Service replacement compressors are sold


without service valves. Valve pads are
installed in their place. The optional
unloaders are not supplied, as the cylinder
heads are shipped with plugs. Customer
should retain the original unloader valves
for use on the replacement compressor.

The piston plug that is removed from the


replacement compressor head must be
installed in the failed compressor if
returning for warranty or core credit.

4.20.2 Transferring Compressor Clutch

To remove a clutch (see Figure 4-16) from a compressor


and install on a replacement compressor, do the
following:

Do not interchange allen-head capscrews


that mount the piston plug and unloader,
they are not interchangeable.

1
2
3

Check oil level in service replacement


compressor. (Refer to paragraphs 1.3 and
4.20.3.)

f. Remove the three socket head capscrews from the


cylinder head(s) that have unloader valves installed.
See Figure 4-15. Remove the unloader valve and bypass piston assembly, keeping the same capscrews
with the assembly. The original unloader valve must
be transferred to the replacement compressor. The
plug arrangement removed from the replacement is
installed in the original compressor as a seal. If piston
is stuck, it may be extracted by threading a socket
head capscrew into top of piston. A small Teflon seat
ring at the bottom of the bypass piston plug must be
removed.

1.
2.
3.
4.

Compressor (typical)
Seal Cover
Coil
Rotor

5.
6.
7
8.

Rotor Nut
Armature
Spacer Nuts
Snap Ring

Figure 4-16. Compressor Clutch


GASKET
COMPRESSOR
HEAD

SPRING
FLANGE
COVER

a. Using a wrench on the armature flats to keep it from


turning, remove the special bolt holding it to the
shaft.
b. Using special tool (CTD Part Number 07--00242
--01), remove the rotor nut and rotor. Retain original
key.
c. Noting the position of the wire, remove the three bolts
holding the coil to the compressor.
d. Remove every other bolt from the seal cover of the
new compressor in the same manner as the original
compressor. Mount the coil assembly with the wire in
the same orientation as it was mounted on the original
compressor. Tighten the mounting bolts to 45 lbs/ft
(6.2 mkg).
e. Mount rotor on shaft with rotor nut. Be sure pulley
turns freely without binding.
f. Install armature on shaft using original key and tighten mounting bolt to 20 ft/lbs (2.8 mkg).
g. Perform a check of the air gap between the inside face
of the armature and the mating face of the rotor. The
air gap should be measured with a minimum of 50
psig (3.4 bar) in the crankcase. A preliminary check
may be performed before the crankcase is pressurized
but a final check must be performed before the clutch
is operated. The gap should be between 0.016 and

CAPSCREWS
BYPASS
PISTON
PLUG

(NOT INTERCHANGEABLE WITH


CONTROL VALVE SCREWS)

Figure 4-15.Removing Bypass Piston Plug

g. Remove the pressure switches and install on replacement compressor after checking switch operation (refer to paragraph 4.10).
h. Remove clutch assemble and retain original clutch
key. Install on replacement compressor. Refer to
paragraph 4.20.2.
i. Install compressor in unit by performing the removal
steps in reverse. It is recommended that new locknuts
be used when replacing compressor. Install new gaskets on service valves and tighten bolts uniformly.
j. Leak check connections and replace filter--drier. Refer to paragraph 4.6.
k. Using refrigerant hoses designed for vacuum service,
connect a vacuum pump (see Figure 4-5) and evacu4-11

T-295

0.030 inch (0.41 to 0.76 mm). If required, remove the


eight armature spacer nuts and spacer. Add or remove
shims to adjust gap. Reinstall spacer nuts and tighten
to 7--8 ft/lbs(1.0 to 1,1 mkg).

3. Evacuate compressor to 500 microns. Backseat


compressor suction and discharge valves, start system and recheck oil level.
4. Remove manifold gauge set.

h.Reconnect wiring and test clutch operation.

12

4.20.3 Compressor Oil Level

To check, and if required correct, the compressor oil


level do the following:

11

a. Operate the coach for at least one--half hour at fast


idle speed, with the temperature controls at the coolest setting, and the compressor fully loaded. It may be
necessary to pre--heat the coach and/or operate the
system in the reheat mode to keep the compressor fully loaded throughout this procedure

10

b. Ensure the system is fully charged (refer to paragraph


4.8.1) and the compressor crankcase is warm to the
touch after fifteen minutes of operation.

3
4

8
6

05G - GR60

c. Shut off the system and immediately record the oil


level in the compressor sight glass. See Figure 4-17.
If the compressor is not level, an average between the
sight glass levels will have to be made to determine
level.

11
12

d. The proper oil level is between the marks on the compressor crankcase (05G compressors) or between 1/4
and 1/2 of the sight glass (05K compressors). Refer to
Figure 4-17. If the oil level is correct, release the
coach into service. If the level is above the required
amount, proceed to step e.. If the level is below the
required amount proceed to step f.

3
2

9
7

e. To remove oil and bring the level to the proper


amount, do the following:

8
05K - GR45

1. Pump down the compressor until only a slight positive pressure remains in the crankcase. Refer to paragraph 4.5.3.

1.
2.

2. Shut off the coach engine and ensure the compressor


discharge and suction service valves are frontseated.
Reclaim the remaining refrigerant in the compressor
crankcase.

3.

Electric Unloader
Valve
Suction Service
Valve Charging Port
Suction Service
Valve
Clutch
Oil Fill Plug

6.
7.
8.
9.
10.
11

Bottom Plate
Oil Drain Plug
Oil Level Sight Glass
Oil Pump
O-ring
.Discharge Service
Valve
12 .Service Port

3. Drain or pump out compressor oil until the level is


brought to the minimum for this compressor.

4.
5.

4. Evacuate the compressor to 500 microns. Backseat


the compressor service valves and repeat the oil level
check procedure.

Figure 4-17. Compressors


4.20.4 Checking Unloader Operation

To check unloader operation do the following:


a. Install a manifold gauge set as shown in Figure 4-6.
Ensure both manifold valves are frontseated and center connection is tight on blank fitting.
b. Midseat compressor suction service valve.
c. At the bus roof, disconnect the suction pressure transducer (8, Figure 1-6). This will force the controller to

f. To add oil to the compressor crankcase, do the following:


1. With the system off, connect a manifold gauge set to
the compressor suction and discharge service valves
(See Figure 4-5) and reclaim the refrigerant to below
atmospheric pressure. Shut off the reclaimer and
verify the pressure does not rise. If the pressure rises,
continue reclaiming until the pressure remains below atmospheric.

energize the unloader(s).

d. Start the bus and run in cooling lower set point if required to ensure system remains in full speed cooling.
e. Locate the unloader connector at the compressor. Observe manifold suction gauge while unplugging the

2. Add oil to compressor crankcase slowly, through the


oil fill plug opening (see Figure 4-17) to bring level
to mid range of allowed levels.
T-295

4-12

connector. Pressure should decrease 3 to 5 psi (0.2 to


0.4 bar) when the unloader is unplugged and increase
the same amount as the plug is reconnected. repeat
test for second unloader if fitted.

c. At least one sensor lead must be disconnected from


the controller before any reading can be taken. Not
doing so will result in a false reading. Two preferred
methods of determining the actual test temperature at
the sensor are an ice bath at 32F (0C) and/or a calibrated digital temperature meter.

f. If pressures do not react as described, check unloader


coil or repair unloader mechanism as required.

4.22 PRESSURE TRANSDUCER CHECKOUT

g. When testing is complete, reconnect transducer and


unloader connectors and remove manifold gauge set.

NOTE
System must be operating to check transducers.

h. Disconnection of the suction pressure transducer will


cause an A15 alarm. Once the transducer is reconnected, the alarm will go to inactive and can then be
cleared.

a. With the system running use the driver display or


manifold gauges to check suction and/or discharge
pressure(s).
b. Use a digital volt-ohmmeter measure voltage across
the transducer at terminals A & C. See Figure 4-18.
Compare to values in Table 4-2. A reading within two
percent of the values in the table would be considered
good.

Table 4-1. Temperature Sensor Resistance


Temperature
F
C

--20
--10
0
10
20
30
32
40
50
60
70
77
80
90
100
110
120

--28.9
--23.3
--17.8
--12.2
-- 6.7
-- 1.1
0
4.4
10.0
15.6
21.1
25
26.7
32.2
37.8
43.3
48.9

Resistance In Ohms

165,300
117,800
85,500
62,400
46,300
34,500
32,700
26,200
19,900
15,300
11,900
10,000
9,300
7,300
5,800
4,700
3,800

C
A

Figure 4-18 Transducer Terminal Location


4.23 REPLACING SENSORS AND TRANSDUCERS

a. Place main battery disconnect switch in OFF position


and lock.
b. Tag and disconnect wiring from defective sensor or
transducer.
c. Remove and replace defective sensor or transducer.
d. Connect wiring to replacement sensor or transducer.
e. Checkout replacement sensor or transducer. (Refer to
section 4.21 or 4.22, as applicable.)
f. Repair or replace any defective component(s), as required.

4.21 TEMPERATURE SENSOR CHECKOUT

a. An accurate ohmmeter must be used to check resistance values shown in Table 4-1.

4.24 LOGIC BOARD CONFIGURATION

b. Due to variations and inaccuracies in ohmmeters,


thermometers or other test equipment, a reading
within two percent of the chart value would be considered accaptable. If a sensor is bad, the resistance
value would usually be much higher or lower than the
value given in Table 4-1 .

If a replacement Logic Board is installed, it is necessary


to match the configuration jumpers (see Figure 1-10) to
the original board. Table 4-3 provides a list of jumper

functions

4-13

T-295

Table 4-3. Logic Board Configuration

Table 4-2. PressureTransducer Voltage


/hg

Voltage

Psig

Voltage

Psig

Voltage

20
10

0.369
0.417

Psig

Voltage

0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95

0.466
0.515
0.564
0.614
0.663
0.712
0.761
0.810
0.858
0.907
0.956
1.007
1.054
1.103
1.152
1.204
1.250
1.299
1.348
1.397

100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
175
180
185
190
195
200
205
210

1.446
1.495
1.544
1.593
1.642
1.691
1.740
1.789
1.838
1.887
1.936
1.985
2.034
2.083
2.132
2.181
2.230
2.279
2.328
2.377
2.426
2.475
2.524

215
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325

2.573
2.622
2.671
2.720
2.769
2.818
2.867
2.916
2.965
3.014
3.063
3.112
3.161
3.210
3.259
3.308
3.357
2.406
3.455
3.504
3.553
3.602
3.651

T-295

Jumper

4-14

Description

A.

High Reheat -- Selects fan speed

B.

High Vent -- Selects fan speed

C.

Dry Heat -- Selects re--heat configuration

D.

Reheat/Cycle -- Selects clutch cycle

E.

Transducers -- Selects transducer configuration

F.

Refrigerant -- Selects refrigerant

G.

Unit Type -- Selects software configuration

H.

Unit Type -- Selects software configuration

I.

Factory -- Reserved for the manufacturer.

J.

Invert H2O -- Selects temperature switch


configuration

K.

Voltage -- Selects unit voltage

L.

Factory -- Reserved for the manufacturer.

M.

Psig/Bars -- Selects display configuration

N.

C/F -- Selects display configuration

O.

Loaded Start -- Selects start--up configuration

P.

PI Reheat -- Selects reheat algorithm

Table 4-4. R-134a Temperature - Pressure Chart


Temperature

Vacuum

Temperature

F
--40
.35

C
--40
.37

/hg

14.6
12.3

49.4
41.6

37.08
31.25

0.49
0.42

--30
--25

--34
--32

9.7
6.7

32.8
22.7

24.64
17.00

0.33
0.23

--20

--29

3.5

11.9

8.89

0.12

--18
--16

--28
--27

2.1
0.6

7.1
2.0

5.33
1.52

0.07
0.02

Temperature

F
--14
--12
--10
--8
--6
--4
--2
0
2
4
6
8
10
12
14
16
18
20
22
24
26

C
--26
--24
--23
--22
--21
--20
--19
--18
--17
--16
--14
--13
--12
--11
--10
--9
--8
--7
--6
--4
--3

cm/hg kg/cm@@

F
28
30
32
34
36
38
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155

bar

Pressure
psig

kPa

kg/cm@@

bar

0.4
1.2
2.0
2.9
3.7
4.6
5.6
6.5
7.6
8.6
9.7
10.8
12.0
13.2
14.5
15.8
17.1
18.5
19.9
21.4
22.9

1.1
8.3
13.8
20.0
25.5
31.7
36.6
44.8
52.4
59.3
66.9
74.5
82.7
91.0
100.0
108.9
117.9
127.6
137.2
147.6
157.9

0.03
0.08
0.14
0.20
0.26
0.32
0.39
0.46
0.53
0.60
0.68
0.76
0.84
0.93
1.02
1.11
1.20
1.30
1.40
1.50
1.61

0.03
0.08
0.14
0.20
0.26
0.32
0.39
0.45
0.52
0.59
0.67
0.74
0.83
0.91
1.00
1.09
1.18
1.28
1.37
1.48
1.58

4-15

C
--2
--1
0
1
2
3
4
7
10
13
16
18
21
24
27
29
32
35
38
41
43
46
49
52
54
57
60
63
66
68

Pressure
psig

kPa

kg/cm@@

bar

24.5
26.1
27.8
29.6
31.3
33.2
35.1
40.1
45.5
51.2
57.4
64.1
71.1
78.7
86.7
95.3
104.3
114.0
124.2
135.0
146.4
158.4
171.2
184.6
198.7
213.6
229.2
245.6
262.9
281.1

168.9
180.0
191.7
204.1
215.8
228.9
242.0
276.5
313.7
353.0
395.8
441.0
490.2
542.6
597.8
657.1
719.1
786.0
856.4
930.8
1009
1092
1180
1273
1370
1473
1580
1693
1813
1938

1.72
1.84
1.95
2.08
2.20
2.33
2.47
2.82
3.20
3.60
4.04
4.51
5.00
5.53
6.10
6.70
7.33
8.01
8.73
9.49
10.29
11.14
12.04
12.98
13.97
15.02
16.11
17.27
18.48
19.76

1.69
1.80
1.92
2.04
2.16
2.29
2.42
2.76
3.14
3.53
3.96
4.42
4.90
5.43
5.98
6.57
7.19
7.86
8.56
9.31
10.09
10.92
11.80
12.73
13.70
14.73
15.80
16.93
18.13
19.37

T-295

SECTION 5
ELECTRICAL
5--1 INTRODUCTION

This section includes electrical wiring schematics. The schematic shown in this section provides information for all
unit models and optional configurations. For model GR45 units, which are fitted with four evaporator and condenser
fans, the components used to control the fifth and sixth fans are not energized. For applications with OEM supplied
operating switches, the switches are wired to Logic Board connector J3 as shown. For units with a Micromate as the
operators control, there is no wiring to the Logic Board J3 connector. The Micromate is hard wired to the Logic Board
connector J2 in the same manner as shown for service port use.

5-1

T--295

LEGEND

CONNECTOR LEGEND

SYMBOLS
SYMBOL

DESCRIPTION

ATS
BPS

AMBIENT TEMPERATURE SENSOR


BOOST PUMP SIGNAL

CB1

CIRCUIT BREAKER, EF1

GROUND

CB2
CB3

CIRCUIT BREAKER, EF2


CIRCUIT BREAKER, EF3

FACTORY WIRING

CB4
CB5

CIRCUIT BREAKER, EF4


CIRCUIT BREAKER, EF5

OEM WIRING

CB6
CB7

CIRCUIT BREAKER, EF6


CIRCUIT BREAKER, CF1

CB8

CIRCUIT BREAKER, CF2

CB9
CB10
CB11
CB12
CB13

CIRCUIT BREAKER, CF3


CIRCUIT BREAKER, CF4
CIRCUIT BREAKER, CF5
CIRCUIT BREAKER, CF6
CIRCUIT BREAKER, MISC

CF1

COND MOTOR 1

CF2
CF3

COND MOTOR 2
COND MOTOR 3

CF4

COND MOTOR 4

CF5
CF6

COND MOTOR 5
COND MOTOR 6

CTH
D2

COMPRESSOR CLUTCH
EF1/2 LED ASSEMBLY

D6
D14

EF3/4 LED ASSEMBLY


EF5 LED ASSEMBLY

D17
D26
D30

EF6 LED ASSEMBLY


CF1/2 LED ASSEMBLY
CF3/4 LED ASSEMBLY

D38
D41
D51

CF5 LED ASSEMBLY


CF6 LED ASSEMBLY
CLUTCH LED ASSEMBLY

D54
D57

UV1 LED ASSEMBLY


UV2 LED ASSEMBLY

D60

FRESH AIR VALVE LED ASSEMBLY

D63

RSV LED ASSEMBLY

D66
D72
DPT
EM1

ALARM LED ASSEMBLY


SPARE LED ASSEMBLY
DISCHARGE PRESSURE TRANSDUCER
EVAP MOTOR 1

EM2
EM3

EVAP MOTOR 2
EVAP MOTOR 3

EM4
EM5

EVAP MOTOR 4
EVAP MOTOR 5

EM6
F
FAV

CONNECTOR TERMINAL

GROUND STUD
POWER STUD
CONNECTOR

NORMALLY OPEN CONTACT

CONNECTOR, POSITON A

LAMP

DIODE

FUSE

COIL

MOTOR (EF or CF)

PRESSURE SENSOR

LED ASSEMBLY

FTS

EVAP MOTOR 6
FUSE
FRESH AIR VALVE
FREEZE TEMPERATURE SENSOR

HV

HEAT VALVE

K1

EF1/2 RELAY

K2
K3

EF3/4 REALY
EF5 RELAY

K4
K7

EF6 RELAY
CF1/2 RELAY

K8

CF3/4 RELAY

RELAY COIL

K9
K10

CF5 RELAY
CF6 RELAY

MANUAL SWITCH

K13
K14
K15
K16

CLUTCH RELAY
UV1 RALAY
UV2 RELAY
FRESH AIR RELAY

K17
K18

HEAT RELAY
FAULT RELAY

K19
K20

BOOST RELAY
SPARE RELAY

K21
K22
K23
K24

EVAP. FAN HIGH RELAY


EVAP. FAN LOW RELAY
COND. FAN HIGH RELAY
COND. FAN LOW RELAY

LPS

LOW PRESSURE SWITCH

LLS
RAS
SPT
UV1
UV2
WTS

LIQUID LINE SOLENOID


RETURN AIR SENSOR
SUCTION PRESSURE TRANSDUCER
UNLOADER SOLENOID VALVE #1
UNLOADER SOLENOID VALVE #2
WATER TEMPERATURE SWITCH

PRESSURE SWITCH

TEMPERATURE SENSOR

MANUAL RESET BREAKER

POLY SWITCH

TEMPERATURE SWITCH

MULTI--PLEX MODULE

RIBBON CABLE

SYMBOL

DESCRIPTION

J1

LOGIC POWER

J3
J4

ON/TEST
INPUT

J5
J6

RELAY BOARD INTERFACE


SENSOR

J7
JP1

DIAGNOSTIC LINK
MOTOR OVERLOAD

JP2
JP3

LOGIC BOARD INTERFACE


BOOST PUMP

JP4
JP5

CLUTCH
HEAT/FAIL

JP6

UNLOADER

W_ATS

AMBIENT TEMPERATURE SENSOR

W_COMP
W_FAV
W_HPS
W_LPS
W_LLS

COMPRESSOR
FRESH AIR VALVE
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
LIQUID LINE

W_WTS

WATER TEMPERATURE SWITCH

Figure 5--1. Electrical Wiring Schematic Diagram - Legend


T--295

5-2

Figure 5--2. Wiring Schematic, Permanent Magnet Motors - Interconnection

5-3

T--295

VENT

HEAT

COOL

LOW

SPEED

SPEED

DPT

SPT

105F

WTS

SPA

23

21

20

(--)

19

(+)

24

J6

J4

22

W_ATS

W_ATS

W_LPS

GND

DATA

LPS

SPA

SPD

DATA

12V

24VDC

SPD

SPC

SPB

SERVICE
PORT

(--)

(+)

ATS

FTS

RAS

SPB
SPC

W_LPS

J2

MICROMATE

AUTO/ON

HIGH

GROUND (--)

24VDC

24VDC

24VDC

24VDC

24VDC

24VDC

DIM
SIGNAL

ALTERNATOR
SIGNAL
24VDC

J3

J2

J1

J5

J1

LOGIC BOARD

13

12

11

10

18

JP2

JP2

JP2

JP2

JP2

13

JP2

12

JP2

11

JP2

JP2

JP2

10

JP2

JP2

18

JP2

JP2

86

EVAP FAN HIGH RELAY


86
K21

K20

JP4

COND FAN HIGH RELAY


86
K23

COND FAN LOW RELAY


86
K24
85

85

EVAP FAN LOW RELAY


86
K22
85

85

SPARE
85

BOOST RELAY
86
85
K19

FAULT RELAY
86
85
K18

HEAT RELAY
86
85
K17

FRESH AIR
86
85
K16

UV2 RELAY
86
85
K15

UV1 RELAY
86
85
K14

CLUTCH RELAY
86
85
K13

24V

W_HPS

HPS

W_HPS
1
JP4

24V

JP1

JP1

JP1

JP1

JP1

JUMPER

JP1

JUMPER

JP1

JUMPER

JP1

JUMPER

RELAY BOARD

86

86

86

86

86

86

86

86

86

86

86

86

K12

K9

K10

K11

K7

K8

K6

K3

K4

K5

K1

K2

85

85

85

85

85

85

85

85

85

85

85

85

D90

D48

D47

D82

D89

D46

D45

D81

D88

D24

D23

D80

D87

D22

D21

D79

K24
LOW

K23
HIGH

K22
LOW

K21
HIGH

F(150A)

POWER
CABLE

+24VDC

CB1

K1

1--120
(NOVA)

CB2

D2

CB3

K2

CB4

D6

CB5

K3

EF1
2

EM1

EF1
1

EF2
2

EM2

EF2
1

EF3
2

EM3

EF3
1

EF4
2

EM4

EF4
1

EF5
2

EM5

EF5
1

EF6
2

EM6

EF6
1

CF1
2

CF1

CF1
1

CF2
2

CF2

CF2
1

CF3
2

CF3

CF3
1

CF4
2

CF4

CF4
1

CF5
2

CF5

CF5
1

CF6
2

CF6

CF6
1

K5

K6

D14

CB6

K4

D17
CB7

K7

D26

CB8

CB9

K8

D30

CB10

CB11

K9

K11

K12

D38

CB12

K10

1--121 (NOVA)

D41
POWER CABLE (--)
MOTOR CONNECTION
MARKING

CB13

JP5
2

K16

TYPICAL ALL MOTORS


A

JP5
4

W_FAV
W_FAV
A
FAV
B

D60

JP5

K20

SPARE

D72
CIRCUIT BREAKER
CONNECTION MARKING

K14

JP6
2

W_COMP
W_COMP
C
D
UV1

JP6
4

JP6
1

W_COMP
W_COMP
F
E
UV2

JP6
3

TYPICAL ALL BREAKERS


D54

K15
ALL BREAKERS 15 AMP
D57
RELAY CONNECTION
MARKING
30

JP4
2

K13
D51

87
RELAYS K5, K6
K11 &K12

JP5
3

K17
D63

87A

87

ALL OTHERS

LLS
A
W_LLS
A
W_CTRL2
JP4
3

K18
30

W_COMP
W_COMP JP4
A
CTH
B
4

D66
K19

B
W_LLS
A

HV

A/C FAIL
C
W_CTRL2

JP3
3

F(15A)

JP3
3

W_CTRL2
B

+24VDC

D69

BPM +
FLOOR HEATERS

Figure 5--3. Wiring Schematic, Permanent Magnet Motors - Relays to External Components
T--295

5-4

Figure 5--4. Wiring Schematic, Electronically Communtated Motors - Interconnection

5-5

T--295

VENT

HEAT

COOL

LOW

SPEED

SPEED

DPT

SPT

105F

WTS

ATS

FTS

RAS

GND

DATA

23

21

20

(--)

19

(+)

24

22

J6

J4

W_ATS

W_ATS

(SEE FOLLOWING DIAGRAM)

MOTOR FAIL SIGNAL

W_LPS

12V
DATA

LPS

SPA

SPD

SPC

SPB

SERVICE
PORT

(--)

(+)

SPA

24VDC

SPD

SPC

SPB

W_LPS

J2

MICROMATE

AUTO/ON

HIGH

GROUND (--)

24VDC

24VDC

24VDC

24VDC

24VDC

24VDC

DIM
SIGNAL

ALTERNATOR
SIGNAL
24VDC

J3

J2

J1

J5

J1

LOGIC BOARD

13

12

11

10

18

JP2

JP2

JP2

JP2

JP2

13

JP2

12

JP2

11

JP2

JP2

JP2

10

JP2

JP2

18

JP2

JP2

86

EVAP FAN HIGH RELAY


86
K21

K20

JP4

COND FAN HIGH RELAY


86
K23

COND FAN LOW RELAY


86
K24
85

85

EVAP FAN LOW RELAY


86
K22
85

85

SPARE
85

BOOST RELAY
86
85
K19

FAULT RELAY
86
85
K18

HEAT RELAY
86
85
K17

FRESH AIR
86
85
K16

UV2 RELAY
86
85
K15

UV1 RELAY
86
85
K14

CLUTCH RELAY
86
85
K13

24V

W_HPS

HPS

W_HPS
JP4

1
24V

JP1

JP1

JP1

JP1

JP1

JUMPER

JP1

JUMPER

JP1

JUMPER

JP1

JUMPER

RELAY BOARD

K4

86

85
K10

86

CF6 RELAY

CF5 RELAY
85
86
K9

CF3/4 RELAY
85
86
K8

CF1/2 RELAY
85
86
K7

85

EF6 RELAY

EF5 RELAY
85
86
K3

EF3/4 RELAY
85
86
K2

EF1/2 RELAY
85
86
K1

EF HIGH RELAY
85
86
K5

D48

D47

D46

D45

D24

D23

D22

D21

D79

K24
COND FAN LOW

K23
COND FAN HIGH

K22
EVAP FAN LOW

K21
EVAP FAN HIGH

F (125A)

POWER

+24VDC K7

CABLE

CB7
D26

K8
D30

CB8

CF1
2

CF1

CF1
1

CF2
2

CF2

CF2
1

CB9

CF3
2

CF3

CF3
1

CB10

CF4
2

CF4

CF4
1

TO J4--5

SEE PRECEEDING DIAGRAM

C
C

C
CB11

K9

CF5
2

CF5

CF5
1
C

D38
CB12

K10

CF6
2

CF6

CF6
1

D41

C
C
CB1

K1
D2

CB2

EF1
2

EF1

EF1
1

EF2
2

EF2

EF2
1
C

D
D
CB3

K2
D6

CB4

EF3
2

EF3

EF3
1

EF4
2

EF4

EF4
1

CB5

EF5
2

CF5

D14
EF6
2

EF6

D17

EF HIGH

K5

EF6
1
C

MOTOR CONNECTION
MARKING
TYPICAL ALL MOTORS

CF5
1
D

CB6

K4

D
K3

D81
CB13

JP5
2

K16

JP5
4

W_FAV
W_FAV
A
FAV
B

D60
JP5
1

K20
CIRCUIT BREAKER
CONNECTION MARKING
TYPICAL ALL BREAKERS
2

K14

JP6
2

W_COMP
W_COMP
UV1
C
D

JP6
4

JP6
1

W_COMP
W_COMP
UV2
E
F

JP6
3

D54

ALL BREAKERS 15 AMP


K15
RELAY CONNECTION
MARKING

D57
JP4
2

K13
30

SPARE

D72

87
D51

TYPICAL ALL RELAYS

JP5
3

K17

W_COMP
W_COMP JP4
CTH
4
A
B
LLS
A
W_LLS

B
W_LLS
A

HV

D63
JP4
3

K18

A/C FAIL

D66
K19

JP3
3

F(15A)

JP3
3

W_CTRL2
B

+24VDC

D69
BPM +
FLOOR HEATERS

Figure 5--5. Wiring Schematic, Electronically Communtated Motors - Relays To External Components
T--295

5-6

INDEX

Air Filters, 4-9

Filter--Drier, 4-6

Alarm, 2-4, 3-1

Fresh Air System, 1-4, 2-3

Alarm Clear, 3-1

Fuse, 1-6

Alarm Codes, 3-1


Alarm Queue, 3-1

Ambient Lockout, 1-6


Apex Unit, 1-2

Heat Valve, 4-7


Heating Cycle, 1-8

Heating Mode, 2-3


High Pressure Switch, 1-5, 4-5

Boost Pump, 2-3

Hour Meter, 2-4

Circuit Breaker, 1-6, 1-10, 1-11


Clutch, 2-4, 4-11

Liquid Line Solenoid, 4-8

Compressor, 1-4, 1-5, 4-10

Logic Board, 1-12, 2-1, 4-13

Condenser Coil, 4-6

Low Pressure Switch, 1-5, 1-6

Condenser Fan, 1-5, 2-4, 4-8

Condensing Section, 1-2


Control Panel, 1-13
Cooling Mode, 2-3

Maintenance Schedule, 4-1


Manifold Gauge Set, 4-2
Modes Of Operation, 2-3

DESCRIPTION, 1-1

Diagnostics, 2-1, 2-4, 2-5


Discharge Pressure, 2-4

Noncondensibles, 4-5

E
ELECTRICAL, 5-1

Oil Charge, 4-12

Evacuation, 4-4

Operating Controls, 1-4

Evaporator, 1-3

Operating Instructions, 2-1

Evaporator Coil, 4-7

OPERATION, 2-1

Evaporator Fan, 1-5, 2-4, 4-9

Index-1

T-- 295

INDEX -- Continued

Pre--Trip Inspection, 2-1

Temperature Control, 2-3

Pressure Transducer, 1-5, 4-13

Temperature Pressure Chart, 4-15

Pump Down, 4-2, 4-3

Temperature Sensor, 1-5, 4-13


Thermostatic Expansion Valve, 1-5, 4-9

R
Refrigerant Charge, 1-5, 4-2, 4-4, 4-5

Top Cover, 4-1


TROUBLESHOOTING, 3-1

Refrigerant Removal, 4-3, 4-4


Refrigeration Cycle, 1-6

Relay Board, 1-9

Unloaders, 2-3

SAFETY, i
Self Diagnostics, 3-1

Vent Mode, 2-3

SERVICE, 4-1
Service Valves, 4-1

Starting, 2-1
Stopping, 2-1

Wiring Schematics, 5-1

Suction Pressure, 2-3


Superheat, 4-10
System Parameters, 2-5

T-- 295

Index-2

Potrebbero piacerti anche