Section ( VI )

TECHNICAL SPECIFICATIONS
AND SCHEDULES

36

TECHNICAL SPECIFICATION
DISTRIBUTION TRANSFORMERS
1.

General
The distribution transformers are intended for use in outdoor distribution
substations in conjunction with 33 kV or 11 kV load break switches or
cutout fuses and L.V distribution boards, to be supplied separately.
The distribution transformers shall be supplied as specified hereafter
complete and ready for installation and service after completion of the
incoming and outgoing connections.
All equipment shall be easily accessible for maintenance and inspection.
Ease of erection shall be considered in the design .The design shall
incorporate every reasonable precaution and provision for the safety of all
those concerned in its operation and maintenance.
No welding, filling or plugging of defective part will be permitted without
the approval in writing of the EDCO.
Cast iron shall not be used for chambers of oil-filled apparatus or for any
part of the equipment which is in tension or subject to impact stresses except
where it can be shown that service experience has been satisfactory with the
grade of cast iron and duty proposed.
All connection and contacts shall be of ample section and surface for
carrying continuously the specified currents without undue heating, and shall
be secured by bolts or set screws of ample size, fitted with locking devices
of approved type and material.

2.

DESCRIPTION
Three-phase oil immersed transformers, self - cooled, outdoor ground
mounted, or pole mounted with the following technical data: -Rated power on continuous operation in KVA:
1500, 1000, 630,
400, 250, 100
-No load voltage ratio
33/0.415, 11/0.415
-Rated high voltage
33kV or 11kV
-Off - load tap changer with taps for
+ 2x2.5 %
-Rated low voltage
415 V
-Vector group
Dyn11
37

-With outdoor bushings


-With skids, provided that transformers with rated power 100, 250, and
400 KVA must be UChannel Type; suitable for pole mounted
installation on H-Poles (Concrete), as shown in the attached drawing
No. (9-1-E3-0061).
-With conservator tank or sealed
-With pressure relief device
-With complete oil filling
-With contact thermometer range 0 C to 120 C
-With oil level gauge (unbreakable )
-L.V. neutral point solidly earthed .
-Temperature rise of windings at C.M.R. 55 C
-Temperature rise top oil at C.M.R.
50 C
-With H.V bushing equipped with clamps suitable for connection of
Aluminum conductor of 50 mm2 or 100 mm2
-With L.V bushings, the LV bushings shall be equipped with suitable clamps
for connection of single core Cu conductor PVC cables of the following
sizes:
5x300 mm per phase + 3x300 mm per neutral for 1500KVA
3x300 mm per phase + 2x300 mm per neutral for 1000KVA
3x185 mm per phase + 2x185 mm per neutral for 630 KVA
2x185 mm per phase + 1x185 mm per neutral for 400 KVA
1x185 mm per phase + 1x120 mm per neutral for 250 KVA
1x120 mm per phase + 1x120 mm per neutral for 100 KVA
Ditto for 50 KVA
With lifting lugs pulling lugs.
3.

TANKS
Each transformer shall be enclosed in a suitable stiffened welded steel tank
such that the transformer can be lifted and transported without permanent
deformation or oil leakage. The construction shall employ weldable steel of
an approved grade.
The transformer tank shall be vacuum-proof and suitable for outdoor
installation.
Hermetically sealed transformers could be accepted.
The tank shall be equipped with standard accessories as follows :-

Oil drain valve fitted at the lowest point of the tank at one of the narrow
sides.
Oil filter valve located near to the top of the tank.
Oil sampling valve near to the bottom of tank.
38

2 earthing screws.
4 lifting lugs for the cover plates of the active part.
4 pulling lugs.
2 thermometer pockets.
Rating plate and connection diagram.
One dial thermometer for oil temperature indication with maximum demand
indicator.
The tank and cover shall be designed in such a manner as to leave no
external pockets in which water can lodge, no internal pockets in which oil
can remain when draining the tank or in which air can be trapped when
filling the tank and to provide easy access to all external surfaces for
painting .
Each tank cover shall be of adequate strength, shall not distort when lifted
and shall be provided with suitable flanges having sufficient and properly
spaced bolts.
The gasket of the cover plates shall be at least 2mm thick, and shall be of
two fold construction and of such type that its further use shall be possible
after the tank has been opened. A solid earth connection between cover and
tank shall be ensured.

4.

OIL CONSERVATOR TANKS AND BREATHERS


Conservator tanks shall be formed of substantial steel plates and arranged
above the highest point of the oil circulating system. Connections into the
main tank shall be at the highest point to prevent the trapping of air or gas
under the main tank cover.
The oil conservator shall be detachable and arranged at the narrow side of
the transformer tank. The capacity of each conservator tank shall be
adequate for the expansion and contraction of oil in the whole system under
the specified operation conditions Conservator tanks shall be provided with
cleaning door, filling cap, drain valve with captive cap. An oil level indicator
consisting of unbreakable material shall be installed at one end of the oil
conservator tank. A dehydrating breather with silica gel filling shall be fitted
to the air inlet pipe.

5.

JOINTS AND GASKETS


All joint faces shall be machined or ground and arranged to prevent the
ingress of water or leakage of oil with a minimum of gasket surface exposed
to the action of oil or air.

39

Oil resisting synthetic rubber gaskets are not permissible except where the
synthetic rubber is used as a bonding medium for cork or similar material or
where metal inserts are provided to limit compression.
6.

PRESSURE RELIEF DEVICE


An approved pressure relief device of sufficient size for the rapid release of
any pressure that may be generated in the tank and designed to operate at a
static pressure lower than the hydraulic test pressure shall be provided.
If a diaphragm is used, it shall be of approved design and material and
located above the maximum oil level.
A pressure-equalizing pipe shall be provided between the pressure relief
device and the oil conservator.

7.

MAGNETIC CIRCUITS
The design of the magnetic circuit shall be such as to avoid static discharge
development of short circuit paths internally or to the earthed clamping
structure and the production of flux components normal to the plans or the
laminations. Each lamination shall be insulated with a material stable under
the action of pressure and hot oil.
The winding structure and major insulation shall be designed to permit an
unobstructed flow of cooling oil through core cooling ducts to ensure
efficient core cooling.
The magnetic circuit shall be insulated from all structural parts, and shall be
capable of withstanding a test voltage to core bolts and to the frame of 2000
volts r.m.s. for one minute .
Cores shall be constructed from cold rolled grain oriented steel sheets. The
flux density under the most onerous conditions in any part of the magnetic
circuit shall not exceed 1.9 tesla.
The top main core clamping structure shall be connected to the tank body by
a copper strap and the bottom main core clamping structure shall be earthed.
The magnetic circuit shall be earthed to the clamping structure at one point
only beneath an inspection opening in the tank cover and which, by
disconnection will enable the insulation between the core and clamping
plates, etc. to be tested at voltages up to 2.5 kV for the purpose of checking
deterioration during service.
The connection to the link shall be on the same side of the core as the main
earth connection .
Magnetic circuits having an insulated sectional construction shall be
provided with a separate link for each individual section. Where oil ducts or
40

8.

insulated barriers parallel to the plane of the laminations divide the magnetic
circuit into two or more electrically separate parts , the ducts and insulating
barriers which have a thickness greater than 0.25 mm are to be bridged with
tinned copper strips so inserted as to maintain electrical continuity .
WINDINGS
The windings shall be completely short-circuit proof. The H.V winding shall
be subdivided into a suitable number of single coils and shall be composed
of individual discs. Design of the windings must provide unrestricted
cooling ducts ensuring free circulation of oil, proper heat dissipation and
preventing accumulation of heat.
Tapped coils shall be placed at the center of the winding. The end windings
shall be suitably insulated to withstand impulse voltages.
The windings and leads of all transformers shall be braced to withstand the
shocks, which may occur through rough handling and vibration during
transport, switching and other transient service conditions.
The windings shall be thoroughly dried out and vacuum impregnated, during
which time they shall be shrunk under pressure to eliminate shrinkage in
service.

9.

OFF-LOAD TAP CHANGERS


Off-load tap changers shall be short circuited proof. They shall be manually
operated while the transformer is de-energized by means of a special
spindle.
The design shall ensure that the tap selectors on all three phases operate
simultaneously. An external operating handle shall be located on the cover,
register plates clearly indicating tapping in use must be fixed to the external
operating handle and provision shall be made for securing the switches in
any working position to prevent operation by unauthorized persons.

10.

TERMINAL BUSHING

(I) General: -

(II) Porcelain: -

The transformer shall be provided with outdoor type bushing


insulators for phase and neutral terminals. The bushings shall
have a minimum creepage distance of 32 mm/kV and to be
provided with adjustable arcing horns. All bushings shall meet
the requirements of IEC 60137 or equivalent standards.
All porcelain shall be sound, free from defects and
thoroughly Vitrified. The glaze must not be depended upon for
insulation. The glaze shall be smooth and hard and shall cover
completely all exposed parts of the insulator. Outdoor insulators
and fittings shall be unaffected by atmospheric conditions. All
porcelain insulators shall be of the anti-fog type, designed to
41

facilitate cleaning. Each porcelain bushing or insulator shall


have marked upon it the manufacturer identification mark and
to be marked to indicate the date of firing.
The bushings terminals both for HV and LV shall be supplied
with the necessary clamps to fit the aluminum conductor
connection to the HV bushings and the single core PVC, CU or
Al cable to the LV bushings.
Some transformers shall be provided with cable boxes at
both HV & LV sides as specified in schedules.

(III)

11.

OIL
Oil shall be refined petroleum product suitable for use as an insulator and
cooling medium. It shall be type shell Diala D or equivalent. Three copies
of certified test reports of oil shall be submitted to the employer.

12.

SURFACE TREATMENT
Transformer and all metal parts shall be protected by one primary and two
finishing coats of appropriate paint prior to delivery. The finishing coat shall
be of aluminum colour subject to the Employer Approval.
The interior of the tank and the oil conservator shall be painted with two
coats of varnish.

13.

LOSSES AND EVALUATION OF LOSSES


The tenderer shall state in the Schedule of Particulars and Guarantees the
guaranteed values for component losses ( i.e., no-load loss, load loss at
C.M.R. and auxiliary loss (input to cooling equipment if any ) of the total
loss which shall be as low as is consistent with transport restrictions,
reliability and economic use of materials.
Tenderers will be assessed on the basis of the capital cost plus Present Worth
of guaranteed losses as follows:
C = Co + 2553 Fe + 812 Cu
Where: C is the cost of assessment in JDS.
Co is the tender price of transformer in JDS.
Fe-is the no load loss expressed in kilowatts, as shown in the
Schedule Particulars.

42

Cu-is the full load copper loss expressed in kilowatts, as shown in


the Schedule of Particulars.
The acceptance of transformers yielding component losses higher than
the guaranteed values shall be governed by either of the following:(a)

Component losses in excess of guaranteed values but within the


tolerance permitted under IEC 60076.
Transformers shall be acceptable subject to full compliance with all
other technical particulars including temperature rises at C.M.R. and
subject to the Tenderer accepting the imposition of penalty charges
for each KW or part thereof component losses in excess of the
guaranteed values, at the above loss evaluation rates.

(b)

Component losses in excess of guaranteed values and exceeding the


tolerance permitted under IEC 60076.
The acceptance of transformers shall be entirely at the discretion of
the employer and subject to the Tenderer accepting the imposition of
penalty charges for each KW or part thereof of component losses in
excess of the guaranteed values, at the above loss evaluation rates.

In the event of transformers yielding component and total losses, which are
either equal to or below the guaranteed values, the Tenderer will not be
entailed to any premium in respect of reduction in losses below the
guaranteed values.
14.

INSPECTION AND TESTING


All transformers shall be subjected to inspection and testing in accordance
with IEC 60076. The Purchaser may attend these tests.
Adequate notice shall be given when the transformers are ready for
inspection or test and every facility shall be provided by the supplier to
enable the Purchaser to carry out the necessary inspections and tests.
Before the transformers are packed or dispatched all tests called for shall
have been successfully carried out.
No passing of plant or materials by the Engineers shall relieve the
Contractor from his responsibility.
The contractor shall also be responsible for proper carrying out of all test of
work and of plant and material carried out or supplied by a sub-contractor to

43

the same extent as if the work, were carried out or supplied by the contractor
himself.
If, due to the Contract works and / or component materials not complying
with these specifications further tests are necessary, the Contractor shall pay
all additional costs which may be incurred in re-testing.
The following tests shall be carried out: 14.1 TRANSFORMERS
A)

Routine Tests
All transformers shall be subjected to the following Routine tests in
accordance with IEC 60076:
1- Measurement of winding resistance.
2- Ratio, Polarity and phase relationships.
3- Impedance voltage.
4- Load loss
5- No load loss and no load current.
6- Induced over voltage withstand
7- Separate source voltage withstand.
8- Insulation resistance.

B)

Type Tests
The Tenderer should submit with his offer complete Type test
certificates including short- circuit tests, according to IEC standard
from an independent & international recognized testing laboratory
such as KEMA , CESI , or IPH, for Transformers as an evidence of his
capability to manufacturer such materials. In case of unavailability of
such type test certificates or dissatisfaction of laboratories, the
manufacturer (Tenderer) shall filled and provide the cost of the tests
that mentioned in Schedule (B-2) at page 52.
Temperature-rise test: The test shall be in accordance with IEC.60076 and
shall be carried out on one transformer of ten of each size and type.
Temperature-rise test shall be conducted on the tapping corresponding to the
maximum losses.
Impulse-voltage withstand tests:
These shall be made on one of ten of each size and type of transformers
and shall include the following requirements:
The transformers shall have been subjected to the above routine tests
prior to the impulse voltage withstand tests and those transformers
subjected to the temperature-rise test shall be impulse tested as soon as
practicable thereafter.
44

The procedure shall be as required by IEC.60076 the impulse test voltages


being applied successively to each line terminal.
Negative polarity is to be used throughout the tests.
The sequence of voltage applications shall be:
A) Impulse calibration test at 75 per cent of the specified full wave voltage
B) One 100 per-cent full wave voltage application.
C) Two 100 per-cent minimum chopped wave voltage applications.
D) One 100 per-cent full wave voltage applications.
Oscillographic records of the applied voltage and neutral current and/or
transferred voltage are to be taken and included in the records.
Films of the oscillographic records are to be made available to the engineer
at the time of the tests for his examination.
External flashover of the bushings during the chopped wave tests is not
permitted
14.2 ZERO PHASE SEQUENCE IMPEDANCE MEASUREMENT:
This test shall be in accordance with IEC. 60076 and shall be carried out on
each transformer.
14.3 VOLTAGE CONTROL EQUIPMENT
Routine Tests: Each finished tap changer is to be subjected to the mechanical
and dielectric routine tests specified in IEC.60214.
14.4 MAGNETIC CIRCUIT
Routine Tests:
Each core completely assembled is to be tested for one minute at 2500 volt
a.c. between core and bolts, side plates, structural steel work and core and
coils stage.
/After the transformer is tanked and completely assembled, a further test is
to be applied at 500 V d.c. between the core and the earthed structural steel
work to prove that the core is earthed through the removable link, at one
point only as required in this specification.
14.5

COMPLETE OUTDOORS BUSHING ASSEMBLIES WITH


PORCELAIN INSULATORS.
45

Routine test to include :A)


B)

Voltage test.
Power factor-voltage measurements.

Type test to include:A)


B)
C)
D)
E)
F)

Dry withstand and flashover voltage tests.


Visible Corona test.
Wet voltage withstand test.
Wet flashover test.
Impulse voltage test.
Flashover under oil test.

14.6 TANKS
Routine Test
A)

Oil Leakage:
All tanks, conservators and oil filled compartments which are
subjected in service or during maintenance to oil pressure are to
withstand without leakage, a hydraulic pressure test equal to 69
KN/m2 or the normal pressure plus 34 KN/m2 whichever is the
greater, for 24 hr during which time no leakage or oil ingress into
normally oil free space shall occur.

Type Tests
Unless type test certificates can be produced for tests carried out on
similar equipment, the following tests are to be included for tanks,
conservators and pressure relief devices.
A)

Vacuum Test :The equipment is to withstand a vacuum of 508 mm of Mercury when


empty of oil. The permanent deflection of plates or stiffeners on
removal of vacuum is not to exceed the following values.
Length of Plate

Permanent Deflection
46

Less than 1300 mm


1300 to 2500 mm
Greater than 2500 mm

3.17 mm
9.5 mm
12.7 mm

Pressure Test:-

B)

The equipment is to withstand a pressure corresponding to 69 KN/m2 or


the normal pressure plus 34 KN/m2 whichever is the greater.
The permanent deflection of plates or stiffeners on removal to pressure is
not to exceed the value stated in respect of the vacuum test in the
preceding paragraph.
15 PACKING
All transformers shall be packed by means of nylon sheets and shipped
by top open containers.
16. DRAWINGS AND MAINTENANCE INSTRUCTIONS
Drawings for approval shall be submitted in duplicates as paper prints
and, after having been approved, the contractor shall supply six further
copies, one copy at least being a reproduction on a tracing cloth as
specified in this specification
The following is the drawing, which shall be submitted by the Bidder:a)

General arrangement of transformers showing high and low voltage


sides

b)

End elevation of transformer

c)

Plan of tank and terminal gear

d)

General arrangement of tap equipment

e)

Detail drawing of HV and LV bushings

47

The following is a list of drawings to be submitted by the contractor for


approval within one month from the Commencement Date or such other
period as may be agreed with the Purchaser: a)

Drawings corresponding to all drawings submitted by the supplier


with his Tender

b)

Outline, general arrangement, sectional and detail drawings of each


transformer.

c)

Drawings showing the construction of the transformer tank, tank


cover and terminal arrangements with details of all accessories .

d)

Diagram of connections of the transformer, showing the polarity of


the windings.

e)

Details of cable boxes and fittings

f)

Instruments scales.

MAINTENANCE INSTRUCTIONS
Before the specified completion date of the Contract works, the Supplier
shall submit maintenance instructions. Diagrams and record drawings for
approval by the Engineers, and shall supply six further copies of the final
approved form.

48

SCHEDULES AND GUARANTEES

SCHEDULE NO.

DESCRIPTION

SCHEDULE OF REQUIREMENTS

PRICE SCHEDULE

GUARANTEED DELIVERY PERIODS


SCHEDULE

MANUFACTURER AND PLACES OF


MANUFACTURE, TESTING AND
INSPECTION SCHEDULE

LIST OF TYPE TEST CERTIFICATES

LIST OF SERVICE EXPERIENCE

DEVIATIONS FROM
SPECIFICATIONS SCHEDULE

49

SCHEDULE (A)
SCHEDULE OF REQUIREMENTS
Item
No.

Description

1.

11/0.415
kV,
DISTRIBUTION
SPECIFIED.

2.

DITTO BUT 400 KVA.

Stock Code

250
KVA,
3
PHASE 61200001705
TRANSFORMER
AS

Unit
Item

Quantity
Required

NO.

61200001992

NO.

10

3.

DITTO BUT 1500 KVA; provided with Cable 61200001713


Box on MV and LV sides.

NO.

4.

33/0.415
kV,
DISTRIBUTION
SPECIFIED.

No.

55

5.

DITTO BUT 250 KVA.

61200001755

No.

70

6.

DITTO BUT 400 KVA.

61200001740

No.

40

7.

DITTO BUT 630 KVA.

61200001757

No

10

8.

DITTO BUT 630 KVA; provided with Cable 61200001763


Box on MV and LV sides.

No

9.

DITTO BUT 1500 KVA; provided with Cable 61200001761


Box on MV and LV sides.

No

10.

RECOMMENDED LIST OF SPARE PARTS.

100
KVA,
3
PHASE 61200001753
TRANSFORMER
AS

50

SCHEDULE (B-1)
PRICES SCHEDULES
References shown are those under Schedule of Requirements schedule A.
The total prices entered below whether or not they are fully described, shall include
everything necessary to provide the equipment complete and in working order in accordance
with the provisions of the contract. A price must be entered for each individual item.

VARIATION PRICE
PRICE VARIATION DATA

COPPER PRICES

COPPER
U.S. Dollar per Ton
Basic Prices for copper on which
the quoted prices are based

3500

Authorised source responsible for the publication of current market price


London Metal Exchange (LME).
LME PRICE ADJUSTMENT FORMULA SHALL BE PROVIDED BY THE
BIDDER.

51

ITEM
NO.

QTY
AND
UNIT

DESCRIPTION

UNIT PRICE &


CURRENCY
()
FOB

C&F
AQABA

1.

11/0.415 kV, 250 KVA, 3 PHASE


DISTRIBUTION TRANSFORMER AS
SPECIFIED.

8 No.

2.

DITTO BUT 400 KVA.

10 No.

3.

DITTO BUT 1500 KVA; provided with


Cable Box on MV and LV sides.

2 No.

4.

33/0.415 kV, 100 KVA, 3 PHASE


DISTRIBUTION TRANSFORMER AS
SPECIFIED.

55 No.

5.

DITTO BUT 250 KVA.

70 No.

6.

DITTO BUT 400 KVA.

40 No.

7.

DITTO BUT 630 KVA.

10 No.

8.

DITTO BUT 630 KVA; provided with


Cable Box on MV and LV sides.

3 No.

9.

DITTO BUT 1500 KVA; provided with


1 No.
Cable Box on MV and LV sides.
TOTAL PRICE C&F AQABA ITEMS (1-9)
( must be appeared in Tender form)
COST FOR ONE ENGINEER FROM EDCO TO ATTEND FACTORY
SPECIFIED TESTS.

9.

TOTAL
PRIC
E
C&F
AQABAJORDAN

IMPORTANT NOTE:
(EDCO) HAS THE RIGHT TO ACCEPT PARTIAL OFFERS AND TO
AWARD PART OF THE ITEMS OR QUANTITIES WITHOUT ANY LIMIT
OR NOTICE.

52

The following table shows the rise or fall in the quoted prices given in:U.S. Dollar per Ton rises or falls in the price of copper from the basic prices
stated above.
No.

TYPE of TRANSFORMER

1.

11/0.415 kV, 250 KVA, 3 PHASE


DISTRIBUTION TRANSFORMER AS
SPECIFIED.

2.

DITTO BUT 400 KVA.

3.

DITTO BUT 1500 KVA; provided with


Cable Box on MV and LV sides.

4.

33/0.415 kV, 100 KVA, 3 PHASE


DISTRIBUTION TRANSFORMER AS
SPECIFIED.

5.

DITTO BUT 250 KVA.

6.

DITTO BUT 400 KVA.

7.

DITTO BUT 630 KVA.

8.

DITTO BUT 630 KVA; provided with


Cable Box on MV and LV sides.

9.

DITTO BUT 1500 KVA; provided with


Cable Box on MV and LV sides.

53

VARIATION IN PRICE
PER TRANSFORMER

SCHEDULE (B-2)
PRICES SCHEDULES
DETAILED REQUIREMENTS OF SPARE PARTS
The quantities in this Schedule should be estimated by the Bidder which might be
needed during the life time of the transformers. The Purchaser (EDCO) has the
right to award part of these items or all of them or none of them.
ITEM
NO.

QTY
AND
UNIT

DESCRIPTION

UNIT PRICE &


CURRENCY

FOB
10.

SPARE PARTS AS RECOMMENDED BY


MANUFACTURER, AND AS DETAILED
BELOW :

10.1

33 KV BUSHINGS FOR:

10.2

100 KVA Transformers.


250 KVA Transformers.
400 KVA Transformers.
630 KVA Transformers.
1000 KVA Transformers.
1500 KVA Transformers.

pcs
pcs
pcs
pcs
pcs
pcs

11 KV BUSHINGS FOR:
100 KVA Transformers.
250 KVA Transformers.

pcs
54

C&F
AQABA

TOTAL
PRICE
C&F
AQABA
JORDAN

pcs
pcs
pcs
pcs
pcs

400 KVA Transformers.


630 KVA Transformers.
1000 KVA Transformers.
1500 KVA Transformers.

SCHEDULE (B-2) Cont.


PRICES SCHEDULES
DETAILED REQUIREMENTS OF SPARE PARTS
ITEM
NO.

QTY
AND
UNIT

DESCRIPTION

UNIT PRICE &


CURRENCY

FOB
10.3

0.415 KV BUSHINGS FOR:

10.4

10.6

pcs
pcs
pcs
pcs
pcs
pcs

COMPLETE SET OF GASKET FOR:

10.5

100 KVA Transformers.


250 KVA Transformers.
400 KVA Transformers.
630 KVA Transformers.
1000 KVA Transformers.
1500 KVA Transformers.

100 KVA Transformers.


250 KVA Transformers.
400 KVA Transformers.
630 KVA Transformers.
1000 KVA Transformers.
1500 KVA Transformers.

Set
Set
Set
Set
Set
Set

SILICA GEL

KG

BREATHER COMPLETE FOR:


100 KVA Transformers.
55

C&F
AQABA

TOTAL
PRICE
C&F
AQABA
JORDAN

Set
Set
Set
Set
Set
Set

250 KVA Transformers.


400 KVA Transformers.
630 KVA Transformers.
1000 KVA Transformers.
1500 KVA Transformers.

GLASS FOR BREATHERS


10.7

pcs
TOTAL PRICE FOR ALL ABOVE SPARE PARTS

SCHEDULE (B-3)
PRICES SCHEDULES
DETAILED REQUIREMENTS OF TYPE TESTS
ITEM
NO.

DESCRIPTION

PRICE & CURRENCY

Complete Type Tests:


1.

Temperature-Rise Test (IEC 60076-2)

2.

Dielectric Type Test (IEC 60076-3)


Complete Special Test:

3.

Short-Circuit Withstand Test (IEC 60076-5)

4.

Determination of Sound Levels (60076-10)


TOTAL PRICE ITEMS (1-4)

IMPORTANT NOTE:
THE ITEMES (1-4) SHALL BE FILLED BY THE MANUFACTURER
(TENDERER) IF YHE EMPLOYER REQUIRES ANY TEST IN THE

56

KEMA-NETHERLAND HV TESTING LABORATORY IN ACCORDING


TO CLAUSE 14.1.B (TYPE TEST) AT PAGE 44.

SCHEDULE (C)
GUARANTEED DELIVERY PERIODS IN WEEKS

ITEM
NO.

DELIVERY
PERIOD FOB
PORT OF
LOADINGSPECIFY PORT

DESCRIPTION

1.

11/0.415 kV, 250 KVA, 3 PHASE


DISTRIBUTION TRANSFORMER AS
SPECIFIED.

2.

DITTO BUT 400 KVA.

3.

DITTO BUT 1500 KVA; provided with


Cable Box on MV and LV sides.

4.

33/0.415 kV, 100 KVA, 3 PHASE


DISTRIBUTION TRANSFORMER AS
SPECIFIED.

5.

DITTO BUT 250 KVA.

6.

DITTO BUT 400 KVA.

7.

DITTO BUT 630 KVA.

8.

DITTO BUT 630 KVA; provided with Cable


Box on MV and LV sides.
57

DELIVERY
PERIOD TO
AQABA PORTJORDAN

9.

DITTO BUT 1500 KVA; provided with


Cable Box on MV and LV sides.

10.

RECOMMENDED LIST OF SPARE PARTS.

IMPORTANT NOTE:
DELIVERY TIME IS IMPORTANT FACTOR IN THE EVALUATION AND
PRIORITY WILL BE GIVEN TO SHORTER DELIVERY PERIOD OF
LESS THAN (25) WEEKS C&F AQABA FOR ALL ITEMS FROM THE
DATE OF RECEIPT OF PURCHASING ORDER.

SCHEDULE (D)
TECHNICAL PARTICULARS AND GUARANTEES FOR
(11/0.415)kV DISTRIBUTION TRANSFORMERS
The tenderer shall complete this schedule, and the particulars and guarantees will
be binding on the contractor.
REQUIREMENTS

Maximum continuous site rating


(ONAN)
Number of phases
Normal ratio of transformation
Frequency
Type of cooling
Vector group reference IEC 76
Type of transformation ratio control.

Unit

ITEM
(1)

ITEM
(2)

ITEM
(3)

KVA

250

400

1500

3
11/0.415
50
ONAN
Dyn11
OFFLOAD
+5

3
11/0.415
50
ONAN
Dyn11
OFFLOAD
+5

2.5

2.5

Range of transformation ratio HV/LV

3
11/0.415
50
ONAN
Dyn11
OFFLOAD
+5

Size of transformation ratio steps.

2.5

PARTICULARS AND GUARANTEES


Impedance at 75 C on principal tapping

KV
Hz

58

Maximum flux density in core at normal TESLA


voltage and frequency
Type of core steel
Thickness of laminations
mm.
Insulation of laminations
Type of paper insulation on conductors
No load losses at normal ratio and 50 Hz KW
Load losses at CMR,75 C and normal
KW
ratio
-Efficiency at :Full load unity P.F.
%
Full load 0.8 P.F.
%
3/4 Full load unity P.F %
3/4 Full load 0.8 P.F. %
1/2 Full load unity P.F %
1/2 Full load 0.8 P.F. %

REQUIREMENTS

Unit

R.M.S. Exciting current at normal


Amps
voltage on principal tap (H.V-side)
-R.M.S Fundamental current
Amps
-R.M.S 3rd harmonic current
Amps
-R.M.S 5th harmonic current
Amps
-R.M.S 7th harmonic current
Amps
Maximum current density In windings at
CMR on Normal tap :(a) H.V windings
Amps/
mm2
(b) L.V windings
Amps/
mm2
Impedance voltage at 75C (at CMR of
lower voltage winding) between HV and
LV winding.
Temperature rise of windings at CMR

C
above specified design ambient temp.
Temperature rise of top oil at CMR
C
above specified design ambient
Temperature rise of core at CMR and
rated voltage
Impulse withstand voltage of complete
transformer :59

ITEM
(1)

ITEM
(2)

ITEM
(3)

Phase connections
(I) 1.2 /50 Microsecond full wave
(II) 1.2 /50 Microsecond chopped wave

kV
(peak)
kV
(peak)

-Thickness of Transformer tank :A- Sides


B- Bottom
C- Cooling tubes
Total oil required
Weight of complete transformer
(including oil)

mm.
mm.
mm.
Liters

REQUIREMENTS

Unit

Kg

H.V. BUSHING INSULATORS


Make
Type
Voltage rating
Current rating
Length of insulator (Overall)
Weight of insulator
Total creepage distance of bushing
(min 32/mm/kV of rated system voltage )
Protected creepage distance of bushing
Dry withstand power frequency voltage
without arcing horns
Routine power frequency test voltage
(1 minute)
Impulse withstand voltage
(1.2/50 microsecond full wave):
(A) Positive
(B) Negative
Wet withstand power Frequency voltage
without arcing horn
Maximum diameter of bushing when
passing through tank top

KV
Amps
mm.
Kg
mm.
mm.
KV
KV

KV
mm.
60

ITEM
(1)

ITEM
(2)

ITEM
(3)

Penetration of bushing into tank measured


from bottom of fixing flange
Overall dimensions of complete
transformer:Length
Width
Height
Manufacturer name and place

mm.

mm.
mm.
mm.

Testing Authority name and Place

SCHEDULE (D) (CONTD)


TECHNICAL PARTICULARS AND GUARANTEES FOR
(33/0.415)KV DISTRIBUTION TRANSFORMERS

REQUIREMENTS

Maximum continuous site rating


(ONAN)
Number of phases
Normal ratio of transformation
Frequency
Type of cooling
Vector group reference IEC 76
Type of transformation ratio control.

Unit

ITEM
(4)

ITEM
(5)

ITEM
(6)

KVA

100

250

400

3
33/0.415
50
ONAN
Dyn11
OFFLOAD
+5

3
33/0.415
50
ONAN
Dyn11
OFFLOAD
+5

2.5

2.5

Range of transformation ratio HV/LV

3
33/0.415
50
ONAN
Dyn11
OFFLOAD
+5

Size of transformation ratio steps.

2.5

PARTICULARS AND GUARANTEES


Impedance at 75 C on principal tapping
Maximum flux density in core at normal

KV
Hz

%
TESLA
61

voltage and frequency


Type of core steel
Thickness of laminations
Insulation of laminations
Type of paper insulation on conductors
No load losses at normal ratio and 50 Hz
Load losses at CMR,75 C and normal
ratio
-Efficiency at :Full load unity P.F.
%
Full load 0.8 P.F.
%
3/4 Full load unity P.F %
3/4 Full load 0.8 P.F. %
1/2 Full load unity P.F %
1/2 Full load 0.8 P.F. %

REQUIREMENTS

mm.

KW
KW

Unit

R.M.S. Exciting current at normal


Amps
voltage on principal tap (H.V-side)
-R.M.S Fundamental current
Amps
-R.M.S 3rd harmonic current
Amps
-R.M.S 5th harmonic current
Amps
-R.M.S 7th harmonic current
Amps
Maximum current density In windings at
CMR on Normal tap :(a) H.V windings
Amps/
mm2
(b) L.V windings
Amps/
mm2
Impedance voltage at 75C (at CMR of
lower voltage winding) between HV and
LV winding.
Temperature rise of windings at CMR

C
above specified design ambient temp.
Temperature rise of top oil at CMR
C
above specified design ambient
Temperature rise of core at CMR and
rated voltage
Impulse withstand voltage of complete
transformer :62

ITEM
(4)

ITEM
(5)

ITEM
(6)

Phase connections
(I) 1.2 /50 Microsecond full wave
(II) 1.2 /50 Microsecond chopped wave

kV
(peak)
kV
(peak)

-Thickness of Transformer tank :A- Sides


B- Bottom
C- Cooling tubes
Total oil required
Weight of complete transformer
(including oil)

REQUIREMENTS

mm.
mm.
mm.
Liters
Kg

Unit

H.V. BUSHING INSULATORS


Make
Type
Voltage rating
Current rating
Length of insulator (Overall)
Weight of insulator
Total creepage distance of bushing
(min 32/mm/kV of rated system voltage )
Protected creepage distance of bushing
Dry withstand power frequency voltage
without arcing horns
Routine power frequency test voltage
(1 minute)
Impulse withstand voltage
(1.2/50 microsecond full wave):
(A) Positive
(B) Negative
Wet withstand power Frequency voltage
without arcing horn
Maximum diameter of bushing when

KV
Amps
mm.
Kg
mm.
mm.
KV
KV

KV

63

ITEM
(4)

ITEM
(5)

ITEM
(6)

passing through tank top


Penetration of bushing into tank measured
from bottom of fixing flange
Overall dimensions of complete
transformer:Length
Width
Height
Manufacturer name and place

mm.
mm.

mm.
mm.
mm.

Testing Authority name and Place

SCHEDULE (D) CONTD

REQUIREMENTS

Maximum continuous site rating


(ONAN)
Number of phases
Normal ratio of transformation
Frequency
Type of cooling
Vector group reference IEC 76
Type of transformation ratio control.

Unit

ITEM
(7)

ITEM
(8)

ITEM
(9)

KVA

630

630

1500

3
33/0.415
50
ONAN
Dyn11
OFFLOAD
+5

3
33/0.415
50
ONAN
Dyn11
OFFLOAD
+5

2.5

2.5

Range of transformation ratio HV/LV

3
33/0.415
50
ONAN
Dyn11
OFFLOAD
5

Size of transformation ratio steps.

2.5

KV
Hz

PARTICULARS AND GUARANTEES


64

Impedance at 75 C on principal tapping


%
Maximum flux density in core at normal TESLA
voltage and frequency
Type of core steel
Thickness of laminations
mm.
Insulation of laminations
Type of paper insulation on conductors
No load losses at normal ratio and 50 Hz KW
Load losses at CMR,75 C and normal
KW
ratio
-Efficiency at :Full load unity P.F.
%
Full load 0.8 P.F.
%
3/4 Full load unity P.F %
3/4 Full load 0.8 P.F. %
1/2 Full load unity P.F %
1/2 Full load 0.8 P.F. %
REQUIREMENTS

Unit

R.M.S. Exciting current at normal


Amps
voltage on principal tap (H.V-side)
-R.M.S Fundamental current
Amps
-R.M.S 3rd harmonic current
Amps
-R.M.S 5th harmonic current
Amps
-R.M.S 7th harmonic current
Amps
Maximum current density In windings at
CMR on Normal tap :(a) H.V windings
Amps/
mm2
(b) L.V windings
Amps/
mm2
Impedance voltage at 75C (at CMR of
lower voltage winding) between HV and
LV winding.
Temperature rise of windings at CMR

C
above specified design ambient temp.
Temperature rise of top oil at CMR
C
above specified design ambient
Temperature rise of core at CMR and
rated voltage
Impulse withstand voltage of complete
transformer :65

ITEM
(7)

ITEM
(8)

ITEM
(9)

Phase connections
(I) 1.2 /50 Microsecond full wave
(II) 1.2 /50 Microsecond chopped wave

kV
(peak)
kV
(peak)

-Thickness of Transformer tank :A- Sides


B- Bottom
C- Cooling tubes
Total oil required
Weight of complete transformer
(including oil)

mm.
mm.
mm.
Liters

REQUIREMENTS

Unit

Kg

H.V. BUSHING INSULATORS


Make
Type
Voltage rating
Current rating
Length of insulator (Overall)
Weight of insulator
Total creepage distance of bushing
(min 32/mm/kV of rated system voltage )
Protected creepage distance of bushing
Dry withstand power frequency voltage
without arcing horns
Routine power frequency test voltage
(1 minute)
Impulse withstand voltage
(1.2/50 microsecond full wave):
(A) Positive
(B) Negative
Wet withstand power Frequency voltage
without arcing horn
Maximum diameter of bushing when

KV
Amps
mm.
Kg
mm.
mm.
KV
KV

KV

66

ITEM
(7)

ITEM
ITEM
(8)
(9)
Cable Box Cable Box

passing through tank top


Penetration of bushing into tank measured
from bottom of fixing flange
Overall dimensions of complete
transformer:Length
Width
Height
Manufacturer name and place

mm.
mm.

mm.
mm.
mm.

Testing Authority name and Place

SCHEDULE (E)
LIST OF TYPE TEST CERTIFICATES FOR TEST EQUIPMENT
Tenderers shall provide the information required below for the type test
certificates from a recognized testing station covering the equipment offered to
IEC recommendations & shall be submitted with the tender.
Failure to provide copies of type test certificates/reports will result in
rejection of the tender.
TYPE TEST MADE ON IDENTICAL
DESIGNS OF EQUIPMENT TO
THOSE OFFERED

67

CERTIFICATE
NO.

CERTIFICATE
AUTHORITY

SCHEDULE (F)
SERVICE EXPERIENCE OF TRANSFORMERS
Tenderers shall provide the information required below for the service experience
of transformers.
CUSTOMER

NO. OF UNITS
SUPPLY

68

RATED
POWER &
VOLTAGE

NO. OF
YEARS IN
SERVICE

SCHEDULE (G)
DEVIATIONS FROM SPECIFICATION IF ANY
TO BE COMPLETED BY THE TENDERER
ITEM
NO.

BREIF DESCRIPTION

69

DEVIATIONS