MACH-Zone

Controller
Quick Start Guide

Ideal for low-point applications


where unrestricted programming
and full data acquisition are
required.
Can be networked on the main
network or subnetwork, rendering
easy communication with the full
line of Reliable Controls
products.

The MACH-Zone is a
high-performance,
fully programmable
DDC controller
designed to meet the
needs of unitary
equipment.

Four different models have a


selection of output types and
universal inputs;
Flash EEPROM;
SMART-SensorTM support.
Communication ports include
SMART-NetTM and
EIA-485 Network.

...people and technology

you can rely onTM

2003 Reliable Controls Corporation

MACH-Zone Controller

Document Conventions
Reliable Controls Quick Start Guides use several
conventions to aid in your understanding of the material and
to make information more readily accessible. These
conventions are outlined below.
Software menu items will appear in bold faced type and follow
the form:
Start>Programs>Reliable Controls>RC-Studio
Two symbols are used to draw your attention to items
warranting special attention:

The Attention Symbol is used to


draw your attention to concepts
and particular items that require
caution or thought before
implementation.

The Light Bulb is used to draw your


attention to information and
practices that will make your life
easier.

ii

2003 Reliable Controls Corporation

MACH-Zone Controller

2003 Reliable Controls Corporation


All rights Reserved
Printed in Canada
This manual is for information purposes only. The contents and products
described are subject to change without notice. Reliable Controls
Corporation makes no representation with respect to this manual. In no
event shall Reliable Controls Corporation be liable for damages, direct
or incidental, arising out of or related to the use of this manual. No part of
this document may be reproduced or transmitted in any form or by any
means, without the express written permission of Reliable Controls
Corporation.
Reliable Controls Corporation
207-3375 Whittier Avenue
Victoria, BC, Canada V8Z 3R1
Tel: 250-475-2036
Fax: 250-475-2096
Toll Free: 1-877-457-9301
www.reliable-controls.com

iii

MACH-Zone Controller

iv

2003 Reliable Controls Corporation

MACH-Zone Controller

Contents
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Workstation Connection . . . . . . . . . . . . . . . . . . . . . . . . 11
Peer to Peer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Direct via X-Port Converter . . . . . . . . . . . . . . . . . 12
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Universal Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Universal Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Single Stage Triac Outputs. . . . . . . . . . . . . . . . . . . 20
Dual Stage Triac Outputs . . . . . . . . . . . . . . . . . . . . 21
SETUP-Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
MSet Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SMART-Sensor Connection . . . . . . . . . . . . . . . . . . . . 24
Cable Configuration . . . . . . . . . . . . . . . . . . . . . . . . 24
Workstation Jumper Settings . . . . . . . . . . . . . . . . . 25
Networking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

iv

2003 Reliable Controls Corporation

MACH-Zone Controller

Network Connection . . . . . . . . . . . . . . . . . . . . . . . . 26
End-of-Line Termination . . . . . . . . . . . . . . . . . . . . . 28
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . 30

2003 Reliable Controls Corporation

MACH-Zone Controller

vi

2003 Reliable Controls Corporation

MACH-Zone Controller

vi

2003 Reliable Controls Corporation

MACH-Zone Controller

Package Contents

Package Contents
Your new MACH-Zone controller package should include:
1. The MACH-Zone controller.
2. A package of four mounting screws

2003 Reliable Controls Corporation

MACH-Zone Controller

Getting Started

Getting Started
This guide identifies the physical installation procedure and
connection of the MACH-Zone controller within a
Reliable Controls MACH-System.
There are many important concepts and practices that
accompany the use of the MACH-Zone controller. This
document is intended to provide installation and setup
procedures for first time users. The most important concepts
that are crucial to the reliable operation of the MACH-Zone
are introduced.
Product Overview
The MACH-Zone controller features:

Four user configurable inputs.

Four models with different output configurations.

SMART-Net port.

EIA-485 - Network port.

2003 Reliable Controls Corporation

MACH-Zone Controller

Getting Started

24VAC 60Hz Power


Outputs

TM

SMART-Net Jumpers
SMART-NetTM Port
EIA-485 Network Port
Inputs

Input Jumpers

MACH-Zone network settings, such as baud


rate, network type, controller address, and last
panel must be configured using the SETUP-Tool
(see SETUP-Tool, Part# MAZ-ST). Alternatively,
RC-Toolkit and the X-Port converter may be
used.

The MACH-Zone controller does not have a Real


Time Clock. The controller receives its time from a
MACH1, MACH2, or MACH-Global controller
or an ETHER-Link portal that is addressed as
number one on the network.

2003 Reliable Controls Corporation

MACH-Zone Controller

Getting Started

The MACH-Zone controller does not have an


EIA-232 port. In order to access a MACH-Zone
controller from a workstation, it is necessary to
connect to a MACH1, MACH2, or MACHGlobal controller, or an ETHER-Link portal on
the same network.

The MACH-Zone controller may be directly


connected to an operator workstation with the aid
of the X-Port converter. Consult the X-Port
Converter Quick Start Guide for complete details.

2003 Reliable Controls Corporation

MACH-Zone Controller

Installation

Installation
The MACH-Zone controller is screw mounted vertically in
an enclosure:

Use the self-tapping


metal Robertson
screws supplied to
mount the controller.

Do not use bevel


headed or wood
screws.

Mount all peripheral


devices in a separate
enclosure.

Ground yourself before touching


the controller to avoid damaging
the electronics. Touch a grounded
metal surface to discharge static
electricity.

This controller is intended to be


installed in accordance with the
National Electric Code or the
Canadian Electric Code, Part1,
and in a manner acceptable to the
local authority having jurisdiction.

Attach power wiring and


I/O wiring.

Ensure that the MACHZone has been


configured with the SETUP-Tool prior to attaching
the network wiring (alternatively use the X-Port
converter and RC-Toolkit).

2003 Reliable Controls Corporation

MACH-Zone Controller

Physical Dimensions

Physical Dimensions

4.2cm
[ 1.62"]

17.0cm
[ 6.75"]

17.0cm
[ 6.75"]
14.3cm
[ 5.62"]

2.5cm
[ 1.0"]

15.7cm
[ 6.19"]

16.0cm
[ 6.25"]

6.6cm
[ 2.62"]
9.0cm
[ 3.5"]

2003 Reliable Controls Corporation

MACH-Zone Controller

Power Wiring

Power Wiring
The MACH-Zone controller
is powered with a Class 2,
24 VAC or 24 VDC power
supply.
One or more controllers can
be powered from the same
source.
24 VAC

Use only a Class 2 transformer.


Refer to the Technical
Specifications at the back of this
document.

The neutral wire of the power must


be grounded.

GND

1. Connect the hot wire to


the 24 VAC connection
at the right side of the
controller.

Do not connect any I/O peripherals


to the same power source as the
MACH-Zone controller.

2. Connect the neutral wire to the GND connection at the


right side of the controller.
3. The neutral wire of the 24 VAC must be connected to
the Earth ground.

2003 Reliable Controls Corporation

MACH-Zone Controller

Power Wiring
MACH-Zone Controller Power Wiring
#1

GND
Neutral of 24 VAC
connected to Earth Ground

#2

#3

120VAC
24VAC
Transformer

2003 Reliable Controls Corporation

MACH-Zone Controller

Status LED

Status LED
The MACH-Zone controller status LED provides power
indication and shows the EIA-485 network activity. The status
LED is located just below the power connection at the top
right side of the controller.
MACH-Zone Controller Status LED

2003 Reliable Controls Corporation

MACH-Zone Controller

Status LED
MACH-Zone Controller Status LED Indication
LED Indication

Panel Activity

On for one second and off


for one second.

Normal operation - port is idle.

Flickers

Normal operation - port is busy.

Flashes four times for one


second, off for half second.

No firmware is loaded.

Is on or off continuously.

Panel is defective or not powered on.

Continuous rapid flashing,


(6 flashes / second).

Self check failure.


(Service required)

Continuous, very rapid


flashing (at 96 Hz).

Network error.
(Holding network token)

On for half second, off for


half second (2 flashes/
second).

Network error.
(Check connections and settings)

10

2003 Reliable Controls Corporation

MACH-Zone Controller

Workstation Connection

Workstation Connection
Peer to Peer
The MACH-Zone controller is designed to be programmed
using a workstation running the RC-Studio software. The
workstation must be connected to a MACH1, MACH2,or
MACH-Global controller, or ETHER-Net portal that
resides on the same system as the MACH-Zone controller.
No EIA-232 port is available on the MACH-Zone controller.
Alternative access to the
MACH-Zone controller is
available with the use of the XA MACH1, MACH2, MACHPort converter. Consult the
X-Port converter Quick Start Global controller, or ETHERLink portal must be configured
Guide for complete connection as address one in the system (See
details.
MACH-Zone Real Time Clock).

Peer to Peer Communications

Operator Workstation

MACH1

2003 Reliable Controls Corporation

MACH-Zone

11

MACH-Zone Controller

Workstation Connection
Direct via X-Port Converter
If direct communication is absolutely necessary between a
workstation and the MACH-Zone controller, an X-Port
converter can be used. Consult the X-Port Converter Quick
Start Guide for complete details.
MACH-ZoneTM Controller

X-PortTM Converter
EIA-485

EIA-232

Operator Workstation

12

2003 Reliable Controls Corporation

MACH-Zone Controller

Models

Models
The MACH-Zone controller is manufactured in four models
providing flexibility for diverse applications. Each model has
four universal inputs and four outputs which are configured
based on the model ordered. The output types are Universal,
Single Stage Triac, and Dual Stage Triac. The different
configurations are shown below:

MACH-Zone Universal - offers four universal inputs


and four universal outputs.

2003 Reliable Controls Corporation

13

MACH-Zone Controller

Models

MACH-Zone 3TRIAC - offers four universal inputs


and three triac outputs as well as one universal
output.

MACH-Zone 4TRIAC - offers four universal inputs


and four triac outputs.

MACH-Zone Roof Top - offers four inputs that share


two common grounds. The output configuration
consists of one triac output, two dual stage triac
outputs, and one universal output.

All triacs are capable of switching


24 VAC at 1 Ampere.

14

2003 Reliable Controls Corporation

MACH-Zone Controller

Inputs

Inputs
The MACH-Zone controller is designed with four user
configurable universal inputs.
Universal Inputs
Inputs one through four (IN1, IN2, IN3, IN4) are universal
inputs that can be configured as digital (binary) or analogue
(modulating).

Each universal input can be


connected to a two-wire input
device (temperature sensor,
pressure transducer, etc.).
Connect the input signal to
the positive (+) terminal and
the input common to the
corresponding negative (-)
terminal.

MACH-Zone UNIVERSAL

IN1+
IN1 IN2+
IN2 IN3+
IN3 IN4+
IN4 -

The MACH-Zone roof top model (RT) has two common


grounds for the four inputs as seen below.
MACH-Zone Roof Top

IN1+
GND
IN2+
IN3+
GND
IN4+

2003 Reliable Controls Corporation

The maximum voltage measured


by an input is 5 VDC.

15

MACH-Zone Controller

Inputs
Jumper Settings
The input type, for inputs IN1, IN2, IN3, and IN4, is selected
using jumper shunts J1, J2, J3, and J4 respectively. Three
different input types can be set using the jumper shunts:
1. 0-5 VDC
Thermistor setting is a 10k Ohm
pullup to +5 VDC.

2. 4-20 mA
3. Thermistor (dry contact)

J-1
J-2
J-3
J-4

16

2003 Reliable Controls Corporation

MACH-Zone Controller

Inputs
MACH-Zone Controller Input Jumper Settings
Jumper

Selection

No Jumper

0-5 VDC

Inside Jumper*

Thermistor

Outside Jumper

4-20 mA

* Factory Default (shown above)

4-20 mA

Thermistor

0-5 VDC

2003 Reliable Controls Corporation

17

MACH-Zone Controller

Outputs

Outputs
The MACH-Zone controller is designed with four outputs,
which can be ordered in four different configurations.
1. MACH-Zone - U: 4 universal outputs.
2. MACH-Zone - 3T: 3 triac outputs, 1 universal
output.
3. MACH-Zone - 4T: 4 triac outputs.
4. MACH-Zone - RT: 2 dual stage triac outputs, 1
single stage triac output, and 1 universal output.
Universal Outputs
Universal outputs can be configured as digital (binary) or
analogue (modulating).

The maximum voltage provided by


an output is 12 VDC. The
maximum current sourced by an
output is 75 mA.

18

Each universal output can


be connected to a twowire output device (relay,
motor, etc.)

Connect the output signal


to the positive (+) terminal
and the output common
to the corresponding
negative (-) terminal

2003 Reliable Controls Corporation

MACH-Zone Controller

Outputs
.

Universal outputs
OUT1+
OUT1 OUT2+
OUT2 OUT3+
OUT3 OUT4+
OUT4 -

Only consider relays approved by


Reliable Controls when selecting
relays for output connection.

Before powering up for the first


time, ensure that no voltage (AC or
DC) can be read on the outputs.

2003 Reliable Controls Corporation

19

MACH-Zone Controller

Outputs
Single Stage Triac Outputs
The MZ-3T, MZ-4T, and MZ-RT controller models contain at
least one single stage triac.

Single stage triac outputs are


capable of switching 24 VAC at 1
ampere.

Triac outputs are


configured as digital
(binary).

Each output can be


connected to a load or
switching device (relay).

Triacs switch AC voltage only.

Connect the device as shown


in the diagram below.

LOAD

TRIAC 1
RTN-T1

120 VAC 24 VAC


Transformer

LOAD

TRIAC 2
RTN-T2

LOAD

TRIAC 3
RTN-T3
OUT4+
OUT4-

20

2003 Reliable Controls Corporation

MACH-Zone Controller

Outputs
Dual Stage Triac Outputs
The MZ-RT model contains two dual stage triacs. Each dual
stage triac can be connected to a two stage load.

Both triac stages are


OFF when the
output is
commanded to 0
volts.

Dual Stage Triac States


Voltage

T1

T2

OFF

OFF

ON

OFF

10

ON

ON

The first stage triac


(T1) is ON when the
output is commanded to 5 volts.

Both triac stages (T1 & T2) are ON when the


output is commanded to 10 volts.

Connect the two stages as shown in the diagram below.


MACH-Zone Roof Top
TRIAC 1
RTN-T1

STAGE 1
120 VAC 24 VAC
Transformer

STAGE 2
STAGE 1
STAGE 2

DS1-T1
DS1-T2
RTN-DS1
DS2-T1
DS2-T2
RTN-DS2
OUT 4+
OUT 4-

2003 Reliable Controls Corporation

21

MACH-Zone Controller

SETUP-Tool

SETUP-Tool
The SETUP-Tool is a specially designed SMART-Sensor
used to configure the MACH-Zone controller. Each
MACH-Zone controller must have the baud rate, network
type, controller address, and last panel configured with the
SETUP-Tool prior to connection to the network or
programming. The SETUP-Tool requires a voice cable
connection between the SETUP-Tool and the SMART-Net
port on the MACH-Zone controller. The SETUP -Tool is
powered by the MACH-Zone controller and does not
require a separate external power supply.
The SETUP-Tool has two modes of operation, MSET and
Flow mode. Mode selection is achieved with the rocker switch
on the bottom of the tool. MSet mode is discussed below.
Flow mode is user configurable, refer to the SETUP-Tool
Quick Start Guide for further information.

ADDRESS

LAST

MTR-CAL

UPDATE

Flow

22

BAUD

SUBNET

MSet

2003 Reliable Controls Corporation

MACH-Zone Controller

SETUP-Tool
MSet Mode
With the SETUP-Tool in MSet
mode, the buttons are used to
change the address, baudEach MACH-Zone controller
rate, network type, and last
must be MSet using either the
panel settings.
1. Select the parameter to
change
2. Use the Up or Down
arrows to change the
default value
3. When all changes are
complete press the
Update button and use
the Up arrow to
change the value from
No to Yes. This sends
the changes to the
controller. Changes are
complete when the
value changes back to
No.

The MACH-Zone does not


support a Baud rate of 57,600 bps.

2003 Reliable Controls Corporation

SETUP-Tool or an X-Port
converter and RC-Toolkit.
Consult the X-Port converter
Quick Start Guide for complete
details.

Refer to the SETUP-Tool Quick


Start Guide for user information.

The SETUP-Tool utilizes power


from the MACH-Zone controller
and does not require a separate
power supply.

To ensure the controller has


retained the new settings, turn the
unit off and then on and check
that the settings have remained.

23

MACH-Zone Controller

SMART-Sensor Connection

SMART-Sensor Connection
The MACH-Zone controller supports up to four
SMART-Sensors. The SMART-Sensors are ideal for
measuring space/zone temperatures and providing user level
adjustments to temperature set points.
See the SMART-Sensor Quick Start Guide for installation
details.
Cable Configuration

MACH-Zone

Ensure that the SMART-Sensor


voice cable is connected to the
Smart-Net port.

Voice Cable

SMART-Sensors need to be
properly addressed using the
configurable internal jumpers.

Data Cable

24

SMART-Sensors

2003 Reliable Controls Corporation

MACH-Zone Controller

SMART-Sensor Connection
Workstation Jumper Settings
The MACH-Zone controller (Rev. D and later) includes
jumpers J9 and J10 which are used to connect the SMARTNet port to the EIA-485 network.

Panels are shipped with the jumpers installed to


indicate the correct orientation. Remove the jumpers
in the event that no workstation access to the EIA-485
network through a SMART-Sensor connection is
required. This minimizes network stubs.

In the event that workstation access to the EIA-485


network through a SMART-SensorTM connection is
required, then leave jumpers J9 and J10 installed.
Refer to the SMART-Sensor Quick Start Guide for
workstation connection details.

Power Connection

EIA-485 Jumpers installed

EIA-485 Jumpers
SMART-NetTM Port
EIA-485 Network Port

2003 Reliable Controls Corporation

EIA-485 Jumpers not installed

25

MACH-Zone Controller

Networking

Networking
The Reliable Controls MACH-System can be networked in a
variety of ways, which are discussed in the Networking the
Reliable Controls MACH-System document.
When employing EIA-485 networks with the MACH-Zone
controller, the next three sections are relevant.
Network Connection
The MACH-Zone controllers network connector is located
on the middle right of the controller.

Connect one conductor to the A terminal and the


other to the B terminal.

When shielded cable is used, ground the shielding in


one place only and join the shields together using a
wire nut (marrette) where appropriate.

Try to Daisy-Chain the network cable as shown below.


Avoid Star and Stub connections.

26

2003 Reliable Controls Corporation

MACH-Zone Controller

Networking
Shielded Network cable Connections
Panel #1

Panel #2

Panel #3

Network

JP2
EOL

JP2
EOL

EOL

JP1

JP1

EOL

JP2
EOL

JP1
EOL

EOL Jumper
Shunts Removed

/////
//////// ////////////

///////

///////

///////

///////

//////////////////

///////

EOL Jumper
Shunts Installed

Shield
Grounded

Network
//////
//////// ////

Network
Shields Connected
with Marrette

EOL Jumper
Shunts Installed

Glowing network bulbs indicate a


problem which could be either the
network wiring (A & B) are crossed
between two panels or the class 2
power is crossed (24 VAC & GND)
between two panels.

2003 Reliable Controls Corporation

27

MACH-Zone Controller

Networking
End-of-Line Termination
On all EIA-485 networks it is necessary to add end-of-line
(EOL) terminators to prevent reflected noise returning into the
network. The EOL terminators must be installed on the
controllers at the extremities of the network. To determine
the network extremities, calculate the maximum network
length between any two controllers. The controllers at the
extremities must be terminated.
To terminate a MACH-Zone
controller, install EOL jumper
shunts on JP1 and JP2 as
shown in the diagram below.

If the network is not terminated


correctly, the controller may fail to
network properly.

EOL

JP1

EOL

JP2

EOL
Terminators

28

2003 Reliable Controls Corporation

MACH-Zone Controller

Networking
Real Time Clock
The MACH-Zone controller does not contain a Real Time
Clock (RTC) chip.

To access real time functions using the MACHZone controller, it is necessary to network the
MACH-Zone controller to a controller or portal
that has RTC capabilities, (e.g. MACH1,
MACH2, MACH-Global controllers or ETHERLink portal)

The MACH-Zone controller acquires time from


the device addressed as #1 on the network. If
controller address #1 is not on line or does not
have an RTC the system time will remain virtual.

The controller with the RTC must


be configured as address #1.

2003 Reliable Controls Corporation

29

MACH-Zone Controller

Technical Specifications

Technical Specifications
Specifications
Processor

16-bit embedded microprocessor

Memory

32k RAM

Firmware

64k Flash EEPROM

Software

RC-Studio
Power

Supply Voltage

24 VAC Class 2

Power Rating

12 VA maximum power consumption


5 VA nominal power consumption

Maximum Energy
Consumption

12 VA/12 W

Connector

2-pole K1 connector (24 VAC, GND)

Indication

One LED, green


Communications

EIA-485 Serial

Connector, 2-pin, 76.8 kbps max.

SMART-Net

RJ-11 connector, 6 pin

30

2003 Reliable Controls Corporation

MACH-Zone Controller

Technical Specifications

Ambient Limits
Operating Temperature

-18C to 40C (0F to 120F)

Shipping Temperature

-20C to 60C (-40F to 140F)

Humidity

10% to 90% RH non-condensing


Physical Specifications

Dimensions

9 cm L x 17 cm W x 4.2 cm H
(3.5 L x 6.75 W x 1.62 H)

Weight

0.7 kg (1.8 lb)

Cover

Cold rolled steel, powder coat finish

Mounting

Four mount holes provided

2003 Reliable Controls Corporation

31

MACH-Zone Controller

Technical Specifications

Inputs
Quantity

Three universal inputs

Converter

10-bit A-D

Analogue Input

0-5 VDC, 4-20 mA, thermistor

Digital Input

Dry contact

Input Impedance

15 k on 0-5 VDC range

Input Type Selection

Jumper configurable

Pulse counting

40 Hz maximum

Overload protection

24 VAC over-voltage protection

32

2003 Reliable Controls Corporation

MACH-Zone Controller

Universal Outputs
Quantity

Four universal outputs

Converter

8-bit D-A

Analogue Output

0-12 VDC, scalable in software

Digital Output

0-12 VDC

Output Power

75 mA, 12 VDC maximum

Overload Protection

24 VAC over-voltage and short protection

Single & Dual Stage Triac Outputs


Quantity

Based on model

Output Power

24 VAC, 1 A maximum,
24 VAC, 20 mA minimum

Output
Characteristics

Digitally controlled switch

2003 Reliable Controls Corporation

33

MACH-Zone Controller

MACH-Zone Rev 1.5 PLC 05/03

207-3375 Whittier Ave., Victoria, BC, Canada, V8Z 3R1


Toll Free 1(877)475-9301 Tel (250) 475-2036 Fax (250) 475-2096
www.reliable-controls.com