Programmable Safety Systems

PSS-Range

Error List
Item No. 19 715

The spirit of safety.

This manual is intended for instruction and should be retained for future reference.
All rights to this manual are reserved by Pilz GmbH & Co. Copies may be made for internal
purposes.
While every effort has been made to ensure that the information in this manual is accurate,
no responsibility can be accepted for errors or omissions contained within it. We reserve the
right to amend specifications without notice. We are grateful for any feedback on the contents
of this manual.
The names of products, goods and technologies used in this manual are trademarks of the
respective companies.

V, 02/02

Contents

Introduction

1-1

FS Error Messages

2-1

Error class F-01


Hardware error in processor A
Error class F-02
Hardware error in processor B
Error class F-03
Hardware error in processor C
Error class F-04
Battery error
Error class F-05
Configuration error
Error class F-06
Module error
Error class F-07
Defective user program
Error class F-08
Selective shutdown error
Error class F-09
Word module error
Error class F-0C
Scan time exceeded
Error class F-12
Process interrupt overflow
Error class F-14
Alarm errors
Error class F-20
Messages
Error class F-21
Addressing error in the user program
Error class F-22
Error accessing data blocks

PSS-Range: Error List

2-1
2-2
2-3
2-4
2-5
2-6
2-14
2-15
2-27
2-28
2-29
2-30
2-31
2-33
2-34

Contents

Error class F-23


Error accessing read-only data blocks
Error class F-24
Error setting parameters for FBs and SBs
Error class F-25
Indirect addressing error
Error class F-26
Block error
Error class F-27
Parameter error
Error class F-28
Block nesting error
Error class F-29
Start/stop FS section through PG
Error class F-70
Operating system error (processor A)
Error class F-71
Synchronisation error (processor A)
Error class F-72
Error in adjacent CPU (processor A)
Error class F-73
Error reading the PII (processor A)
Error class F-74
Configuration error (processor A)
Error class F-75
Programming device error (processor A)
Error class F-76
Compiler error messages (processor A)
Error class F-77
Program load error (processor A)
Error class F-78
Program link error (processor A)
Error class F-79
Error in process image of outputs
System error (processor A)
Error class F-7A
System error (processor A)
Error class F-80
Fatal system error (processor A)
Error class F-81
Operating system call up error

2-38
2-39
2-43
2-46
2-47
2-48
2-49
2-50
2-53
2-54
2-55
2-56
2-60
2-61
2-62
2-64
2-65
2-66
2-67
2-68

PSS-Range: Error List

Error class F-82


Test pulse error (processor A)
Error class F-83
Debug error (processor A)
Error class F-84
Word module match error (processor A)
Error class F-90
Operating system error (processor B)
Error class F-91
Synchronisation error (processor B)
Error class F-92
Error in adjacent CPU (processor B)
Error class F-93
Error reading the PII (processor B)
Error class F-94
Configuration error
Error class F-96
Compiler error messages (processor B)
Error class F-97
Program load error (processor B)
Error class F-98
Program link error (processor B)
Error class F-99
Error in process image of outputs (processor B)
Error class F-A2
Test pulse error (processor B)
Error class F-A3
Debug error (processor B)
Error class F-A4
Word module match error (processor B)
Error class F-B0
Operating system error (processor C)
Error class F-B1
Synchronisation error (processor C)
Error class F-B2
Error in adjacent CPU (processor C)
Error class F-B3
Error reading the PII
Error class F-B4
Configuration error (processor C)

PSS-Range: Error List

2-78
2-79
2-80
2-81
2-82
2-83
2-84
2-85
2-89
2-90
2-92
2-93
2-94
2-95
2-96
2-97
2-98
2-99
2-100
2-101

Contents

Error class F-B6


Compiler error messages (processor C)
Error class F-B7
Program load error (processor C)
Error class F-B9
Error in the PIO
System error (processor C)
Error class F-C2
Test pulse error (processor C)
Error class F-C4
Word module match error (processor C)
Error class F-D0
Information on selective shutdown
Error class F-D1
Selective shutdown acknowledgement error
Error class F-D6
SafetyBUS p bus interface

ST Error Messages
Error class S-01
Hardware error
Error class S-04
Battery error
Error class S-05
Configuration error
Error class S-06
Module error
Error class S-07
User program error
Error class S-08
Program cartridge error
Error class S-0B
Power failure
Error class S-0C
Scan time exceeded
Error class S-0F
Addressable module error

2-105
2-106
2-108
2-109
2-110
2-111
2-112
2-113

3-1

3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8
3-9

PSS-Range: Error List

Error class S-10


Missing program cartridge
Error class S-20
Operating status messages
Error class S-21
Invalid operands in the application program
Error class S-22
Error accessing data blocks
Error class S-23
Error writing to a read-only data block
Error class S-24
Parameter addressing error
Error class S-25
Indirect addressing error
Error class S-26
Block error
Error class S-27
Parameter error
Error class S-28
Block nesting error
Error class S-2A
Timer error
Error class S-76
Compiler error messages
Error class S-77
Program load error
Error class S-80
Fatal error
Error class S-81
Operating system call up error
Error class S-83
Debug error

PSS-Range: Error List

3-10
3-11
3-12
3-13
3-18
3-19
3-24
3-27
3-28
3-29
3-30
3-31
3-35
3-36
3-37
3-38

Contents

SafetyBUS p Error Messages

4-1

Error class F-30


User stop
Error class F-31
Internal error
Error class F-32
Periphery error
Error class F-33
Bus error
Error class F-34
Configuration error

4-2
4-3
4-5
4-6
4-12

Error Messages on Decentralised Modules


Error class F-01
Error class F-02
Error class F-03
Error class F-04
Error class F-05
Error class F-06
Error class F-07
Error class F-08
Error class F-10
Error class F-11
Error class F-12
Error class F-13
Error class F-14
Error class F-15
Error class F-50
Error class F-51
Error class F-52, F-53, F-54
Error class F-55
Error class F-60
Error class F-61
Error class F-62
Error class F-63
Error class F-64
Error class F-65
6

5-1
5-2
5-3
5-4
5-5
5-6
5-7
5-8
5-9
5-10
5-11
5-12
5-14
5-15
5-16
5-17
5-19
5-21
5-22
5-23
5-24
5-25
5-26
5-27
5-28

PSS-Range: Error List

Error class F-66


Error class F-67
Error class F-68
Error class F-69
Error class F-81
Error class F-82
Error class F-83
Error class F-84
Error class F-85
Error class F-88
Error class F-90
Error class F-91
Error class F-92
Error class F-93
Error class F-95
Error class F-D0
Error class F-D1
Error class F-D2, F-D3, F-D4
Error class F-D5
Error class F-E0
Error class F-E1
Error class F-E2
Error class F-E3
Error class F-E4
Error class F-E5
Error class F-E6
Error class F-E7
Error class F-E8
Error class F-E9

PSS(1) AI U5I1 Error Messages

PSS-Range: Error List

5-29
5-30
5-31
5-33
5-34
5-35
5-36
5-37
5-38
5-39
5-40
5-41
5-42
5-44
5-45
5-46
5-48
5-50
5-51
5-52
5-53
5-54
5-55
5-57
5-58
5-59
5-60
5-61
5-63

6-1

Contents

PSS-Range: Error List

Introduction

This manual describes the error messages for the PSS-range of


programmable safety systems. Error messages which specifically relate to
modular block systems, such as MBS eccentric presses, are described in
the relevant operating manuals.
The error list is divided into the following chapters:
1. Introduction
2. FS Error Messages
3. ST Error Messages
4. SafetyBus p Error Messages
5. Error Messages on Decentralised Modules
6. PSS(1) AI U5I1 Error Messages
In each chapter, error messages are assigned to error classes.

PSS-Range: Error List

1-1

Introduction

Notes

1-2

PSS-Range: Error List

FS Error Messages

F-01

Error class F-01 - Hardware error in processor A


Error no.
03
.
.
.
0E
0F
10

11
.
.
.
15
16
17
.
.
.
1A

Description

Remedy

Hardware error

Change PSS CPU

Faulty user program

Download user program


to the PSS
If no remedy helps:
change PSS CPU

Hardware error

Change PSS CPU

Error in power supply

Change PSS power supply

Hardware error

Change PSS CPU

PSS-Range: Error List

2-1

FS Error Messages

F-02

Error class F-02 - Hardware error in processor B


Error no.
01
.
.
.
07
08
09

0A
.
.
.
0C
0D
0E
.
.
.
11

2-2

Description

Remedy

Hardware error

Change PSS CPU

Faulty user
program

Download user program to


the PSS;
If no remedy helps:
change PSS CPU

Hardware error

Change PSS CPU

Error in the power supply

Change power supply

Hardware error

Change PSS CPU

PSS-Range: Error List

F-03

Error class F-03 - Hardware error in processor C


Error no.
01
02
03
04

05
.
.
.
0F
10
11
.
.
.
28

Description
Hardware error

Remedy
Change PSS CPU

Faulty user
program

Download user program


to the PSS;
If no remedy helps:
change PSS CPU

Hardware error

Change PSS CPU

Error in the power supply

Change power supply

Hardware error

Change PSS CPU

PSS-Range: Error List

2-3

FS Error Messages

F-04

Error class F-04 - Battery error


Error no.
01

2-4

Description
Battery is depleted

Remedy
Change battery. Leave voltage
applied until the battery has been
changed.

PSS-Range: Error List

F-05

Error class F-05 - Configuration error


Error parameter:
Error no.
01
02

Description
Configuration error

PSS-Range: Error List

Slot
Remedy
Compare the registered hardware
set up with the actual configuration.
Adjust configuration in configurator
or insert the correct module.

2-5

FS Error Messages

F-06

Error class F-06 - Module error


Error parameter:

Low byte: Slot


High byte: 0 = Whole slot
1 = Upper half
2 = Lower half
Error location: Assigned number of the faulty I/Os
(coded bit by bit)

Error no.
01
.
.

Description

Error on
PSS (1) DIO Z

.
16
17

18

2-6

Error on
PSS (1) DIF

Error on
PSS (1) DIO T

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check alarm conditions e.g. the
alarm must appear for min. 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.

PSS-Range: Error List

F-06

Error no.
19
.

Description

Error on
PSS (1) DO/DOS/DIO T

.
1A
1B
.
.

Error on
PSS (1) DIO T

.
22
23
.
.
.
29
2A
2B

Error on
PSS (1) DO/DOS
Error on PSS (1) DIF

PSS-Range: Error List

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Short circuits at the inputs
or test pulse wiring?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check alarm conditions e.g. the
alarm must appear for min. 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.

2-7

FS Error Messages

Error no.
2C
2D

Description
Error on
PSS (1) DIO T

2E
.
.

Error on
PSS (1) DIF

.
3E
3F
.
.
42
43

2-8

Error on
PSS (1) DI/DI 2

Error on
PSS (1) DIO T

F-06

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator ?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit atthe outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.

PSS-Range: Error List

F-06

Error no.
44

Description

.
.

Error on
PSS (1) DIF/DIO T

46
47

48
.
.
.
51
52
.
.

Error on
PSS (1) DI/DI 2/DIO T

Error on PSS (1) AI or PSS(1)


AI U5I1 (see also chapter entitled
PSS(1) AI U5I1 Error Messages)

Error on
PSS (1) DOR

PSS-Range: Error List

Remedy
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
3.) Does the test pulse wiring
match the allocation in the
configurator?
4.) Short circuits at the inputs
or test pulse wiring?
5.) Short circuit at the outputs
or to 0 V or 24 V (DIO T)?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
4.) Short circuit at the outputs
or to 0 V or 24 V (DIO T)?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read?
If no remedy helps: change module.
Check the supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.

2-9

FS Error Messages

Error no.
61

Description
Error on PSS (1) DIO T

62

Error on PSS (1) DIF

63

Error on an output module

64

Faulty application program

2-10

F-06

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
5.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
If no remedy helps: change module.
Application program attempts to write
to test pulse outputs; remove error
from the application program

PSS-Range: Error List

F-06

Error no.
65

Description
Error on PSS (1) DOR

66
67

Error on PSS (1) DI/DI 2/DIO T

68
.
.
.
70
71

Error on PSS (1) DOS

Error on PSS (1) DI

72
.
.

Error on PSS (1) DIO T

.
.
74

PSS-Range: Error List

Remedy
Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.

2-11

FS Error Messages

Error no.
75
76

Description
Not assigned
Error at the inputs

77

Error in the test pulse


wiring of the inputs

78

Error on PSS (1) DIF

79

Defective signal route between


alarm input and CPU

7B

Error at stated output (DOT)

2-12

F-06

Remedy
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs or test
pulse wiring
If no remedy helps: change PSS.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs or test
pulse wiring
If no remedy helps: change PSS.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 s
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check alarm inputs for interference
2.) On modular PSS: check contacts
between the alarm module, bus back
plane and CPU module?
If no remedy helps: contact Pilz.
Check stated outputs for short
circuits and shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.

PSS-Range: Error List

F-06

Error no.
7C

Description
Error at stated output (DOT)

7D

Error at stated output (DOT)

7E

Error at stated output (DOS)

PSS-Range: Error List

Remedy
Check stated outputs for short
circuits and shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.
Check outputs for short circuits and
shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.
Check stated outputs for short
circuits and shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.

2-13

FS Error Messages

F-07

Error class F-07 - Defective user program


Error no.
01
.
.
05

2-14

Description
User program

Remedy
Clear user program and
reload into PSS ;
.
If no remedy helps: change CPU.

PSS-Range: Error List

F-08

Error class F-08 - Selective shutdown error


Error parameter:

Low byte: Slot


High byte: 0 = Whole slot
1 = Upper half
2 = Lower half
Error location: Assigned number of the faulty I/Os
(coded bit by bit)

Error no.
00

Description
Error on an output module

01

Error on PSS (1) DO module

02

Error on PSS (1) DIF module

PSS-Range: Error List

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.

2-15

FS Error Messages

Error no.
03

Description
Error on CPU
or on all output modules

04

Error on an
output module

05

Module error

06

Error on a word
module

2-16

F-08

Remedy
Check supply voltage to the
modules (voltage interrupt?)
If no remedy helps: if there is only
one output module, change it;
if there are several output modules,
change CPU
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.

PSS-Range: Error List

F-08

Error no.
07

Description
Error on PSS (1) DIO T module

08

Error on PSS (1) DIF module

09

Error on PSS (1) DIO Z module

0A

Error on PSS (1) DOR module

PSS-Range: Error List

Remedy
1.) Check the supply voltage to
the module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator ?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 s
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module

2-17

FS Error Messages

Error no.
0B

Description
Error on the PSS (1) DOS module

0C

Error on the PSS (1) DIO Z


module

0D

Error on an output module

0E
0F

Error on a PSS (1) DIO Z module

2-18

F-08

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
(voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.

PSS-Range: Error List

F-08

Error no.
F-08
10
11

Description

Remedy

Error on a PSS (1) DO/DOS


module

12

Error on a PSS (1) DIO Z module

13
14

Error on a PSS (1) DIO T module

15

Error on PSS (1) DOR module

1.) Check supply voltage to the


(voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
If no remedy helps: change module.
1.) Check supply voltage to the
(voltage interrupt?)
2.) Does test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.

PSS-Range: Error List

2-19

FS Error Messages

Error no.
16

Description
Error on an output module or
on the CPU

17

Error on an output module;


2nd output of an output pair is
defective

18

Error on a PSS (1) DOS module;


2nd error within a group of 8

19

Error on a PSS (1) DIO Z module;


2nd error within a group of 8

2-20

F-08

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Does test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change output
module or CPU.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Does test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.

PSS-Range: Error List

F-08

Error No.
1A

Description
Error on PSS (1) DIF module

1B

Error on an input module

1C

Error at a word module


2nd output segment defective

1D
1E

Error on PSS (1) DIF module

1F

Bit error signalled by


user program
Word error signalled
by user program

20

PSS-Range: Error List

Remedy
1.) Check alarm conditions e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
1.) Check alarm conditions e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
Check user program
and reload into the PSS (SB 255)
Check user progam
and reload into the PSS (SB 255)

2-21

FS Error Messages

Error No.
21
.

Description

.Error on a word module


.
.
25
26
27

Error on an input module

28
29

Error on the CPU


Error on an output module

2A
2B
2C

Error on the CPU


Error on an output module

2D

Error on the CPU

2-22

F-08

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or the signal wiring?
If no remedy helps: change module.
Change CPU module
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
Change CPU module
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
Change CPU module

PSS-Range: Error List

F-08

Error no.
2E

Description

.
Error on an ouput module
.
.
31
34

Error on PSS (1) DIO Z module

35

Error on PSS (1) DOR module

36

Error on PSS (1) DOS module

37

Error on PSS (1) DIO Z module

.
.
.
3C

PSS-Range: Error List

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.

2-23

FS Error Messages

Error no.
3D
.
.
.

Description
Error on a word module

3F
40
41

Error on the CPU

Error on PSS(1) DIF module

.
.
44
45
46

Error on a word module

48
.
.
.
4C

2-24

Error on PSS (1) DIF module

F-08

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
Change CPU module
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 s
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read
(by AI)?
If no remedy helps: change module
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module

PSS-Range: Error List

F-08

Error no.
4D

Description
Error on PSS (1) DIO Z module

4E
4F

Error on PSS (1) DOR module

50
51

Error on PSS (1) DOS module

52

Error on PSS (1) DIO Z module

53
54

Error on an output module

PSS-Range: Error List

Remedy
1.) Check supply voltage to the
module (voltage interrupt?
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator ?
If no remedy helps: change module.
Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.

2-25

FS Error Messages

Error no.
55
56
57
58
59

Description
Configuration error

60
61
62

Error on the CPU

2-26

Error on an output module

Fault at stated inputs


(DIF/DIF2)

F-08

Remedy
Compare true layout with set layout
and either adapt configuration or
change layout
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
Change CPU module
Rectify fault at stated inputs.

PSS-Range: Error List

F-09

Error class F-09 - Word module error


Error parameters:

Low byte: Slot


High byte: 0 = Whole slot
1 = Upper half
2 = Lower half
Error location: Assigned number of the faulty I/Os
(coded bit by bit)

Error no.
01
.
.
.
0E
0F

Description

Error on word module

Word error signalled


from application program

PSS-Range: Error List

Remedy
1.) Tolerance set is too low
2.) Incorrect match algorithm
(e.g. match instead of min.- max.)
if no error is present in the
configuration: change the module
Check application program
and change if necessary

2-27

FS Error Messages

F-0C

Error class F-0C - Scan time exceeded


Error no.
01

Description
Block run time exceeded

02

Maximum scan time exceeded

2-28

Remedy
Increase the block run time in the
configurator or optimise the
user program
Scan time is the same as the
block run times for the FS and ST
user program and the processing
time for the operating system;
optimise user program, e.g. reduce
alarm load

PSS-Range: Error List

F-12

Error class F-12 - Process interrupt overflow


Error parameter:
Error no.
01

Alarm-OB

Description
Too many alarms
(Alarm queue overflow)

PSS-Range: Error List

Remedy
1.) Reduce alarm load
2.) Make the segments shorter
3.) Optimise user program

2-29

FS Error Messages

F-14

Error class F-14 - Alarm errors


Error no.
01

02

03

2-30

Description
Alarm triggered although
no module with alarm
capabilities installed
Alarm source cannot
be determined
Alarm reaction time
exceeded

Remedy
Remove sources of interference
from the working environment.
If no remedy helps: change CPU.
1.) Increase alarm pulse
2.) Remove sources of interference
from the working environment
1.) Increase alarm reaction time in
the configurator
2.) Reduce alarm load
3.) Optimise user program

PSS-Range: Error List

F-20

Error class F-20 - Messages


Error no.
01

Description
Cold start: FS program
starting up

Remedy
---

03

STOP: FS program
switched to STOP
STOP: FS program
switched to "No FS"

---

05

Read error stack and contact


Pilz

06

Minimum scan time


exceeded

07
08

Internal system time exceeded


Error stack cleared

09
0A
0B
0C
0D
0E
0F
10

System error

1.) Increase min. scan time in


the configurator
2.) Optimise user program
--Replace the battery
Leave voltage applied until the
battery has been replaced!
Please contact Pilz

Fleeting voltage drop out


CPU defective

Check mains voltage


Change PSS CPU

System error
Faulty user program

11
12

Alarm source cannot


be detected

13

AS-command in
Alarm-OB
AF-command in
Alarm-OB

Please contact Pilz


Enable alarm at end of cycle
(AF-command)
1.) Increase alarm pulse
2.) Remove sources of interferences
from the working environment
Clear AS-command from Alarm-OB
(not permitted in alarm-OB )
Clear AF-command from Alarm-OB
(not permitted in alarm-OB)

14

PSS-Range: Error List

2-31

FS Error Messages

Error no.
15
16

Description
Deactivation data
cleared

1D
1E
1F
20
22

Start reactivation
Acknowledge reactivation error
Acknowledge reactivation
Reactivation through operator
Maximum scan time
exceeded on start-up
Maximum scan time
exceeded in STOP
Reactivation completed
successfully

23
24

2-32

F-20

Remedy
Replace the battery.
Leave the voltage applied until the
battery is replaced!
---------------

PSS-Range: Error List

F-21

Error class F-21 - Addressing error in the user program


Error parameter:
Error location:
Error no.
13
21
22
32
33

Timer number
Block in which the error occurred

Description
Command SE: timer was
started with a negative value
Byte division by 0
Byte division overflow
Word division overflow
Periphery word access
to pulsed input in alarm-OB

PSS-Range: Error List

Remedy
Enter positive value for
time value
Change user program
Reduce dividend
Reduce dividend
No periphery accesses permitted
in alarm-OBs

2-33

FS Error Messages

F-22

Error class F-22 - Error accessing data blocks


Error parameter:
Error location:
Error no.
01
02
03
04
05
06
09
0A
0D
0E
0F
10
11
12

2-34

Block ID for selected DB


Block in which the error occurred

Description
Command "L DR":
DW lies outside the current DB
Command "L DL":
DW lies outside the current DB
Command "T DR":
DW lies outside the current DB
Command "T DL":
DW lies outside the current DB
Command "AND DR":
DW lies outside the current DB
Command "AND DL":
DW lies outside the current DB
Command "OR DR":
DW lies outside the current DB
Command "OR DL":
DW lies outside the current DB
Command "XOR DR":
DW lies outside the current DB
Command "XOR DL":
DW lies outside the current DB
Command "+ DR":
DW lies outside the current DB
Command "+ DL":
DW lies outside the current DB
Command "- DR":
DW lies outside the current DB
Command "- DL":
DW lies outside the current DB

Remedy
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program

PSS-Range: Error List

F-22

Error no.
13
14
15
16
17
18
19
1A
1B
1C
1F
20
23
24
30
31

Description
Command "* DR":
DW lies outside the current DB
Command "* DL":
DW lies outside the current DB
Command ": DR":
DW lies outside the current DB
Command ": DL":
DW lies outside the current DB
Command "I DR":
DW lies outside the current DB
Command "I DL":
DW lies outside the current DB
Command "D DR":
DW lies outside the current DB
Command "D DL":
DW lies outside the current DB
Command "> DR":
DW lies outside the current DB
Command "> DL":
DW lies outside the current DB
Command "!= DR":
DW lies outside the current DB
Command "!= DL":
DW lies outside the current DB
Command "< DR":
DW lies outside the current DB
Command "< DL":
DW lies outside the current DB
Command "L DW":
DW lies outside the current DB
Command "T DW":
DW lies outside the current DB

PSS-Range: Error List

Remedy
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program

2-35

FS Error Messages

Error no.
32
34
36
37
38
39
3A
3B
3C
3D
3F
41
51
52
53
54

2-36

Description
Command "AND DW":
DW lies outside the current DB
Command "OR DW":
DW lies outside the current DB
Command "XOR DW":
DW lies outside the current DB
Command "+ DW":
DW lies outside the current DB
Command "- DW":
DW lies outside the current DB
Command "* DW":
DW lies outside the current DB
Command ": DW":
DW lies outside the current DB
Command "I DW":
DW lies outside the current DB
Command "D DW":
DW lies outside the current DB
Command "> DW":
DW lies outside the current DB
Command "!= DW":
DW lies outside the current DB
Command "< DW":
DW lies outside the current DB
Actual parameter for
DR is invalid
Actual parameter for
DL is invalid
Command "T =para":
DR lies outside the current DB
Command "T =para":
DL lies outside the current DB

F-22

Remedy
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check actual parameter,
rectify program
Check actual parameter,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program

PSS-Range: Error List

F-22

Error no.
61
62

63
64
65

Description
Command "L =para":
DW lies outside the current DB
Command "T =para":
DW lies outside the current DB

Remedy
Check length of the DB,
rectify program
Check length of the DB,
rectify program

Command "I =para":


DW lies outside the current DB
Command "D =para":
DW lies outside the current DB
Command "A DB"
is missing

Check length of the DB,


rectify program
Check length of the DB,
rectify program
Select a data block with "A DB"
before accessing a data word

PSS-Range: Error List

2-37

FS Error Messages

F-23

Error class F-23 - Error accessing read-only data blocks


Error parameter:
Error location:
Error no.
01
02
11
12
13
20
21
31
32
33

2-38

Block ID for selected DB


Block in which the error occurred

Description
Command "T DR":
transferring to read-only DB
Command "T DL":
transferring to read-only DB
Command "T DW":
transferring to read-only DB
Command "I DW":
transferring to read-only DB
Command "D DW":
transferring to read-only DB
Command "T =para":
transferring DL to read-only DB
Command "T =para":
transferring DR to read-only DB
Command "T =para":
transferring DW to read-only DB
Command "I =para":
transferring DW to read-only DB
Command "D =para":
transferring DW to read-only DB

Remedy
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB

PSS-Range: Error List

F-24

Error class F-24 - Error setting parameters for FBs and SBs
Error parameter:
Error location:
Error no.
01
02
03
13

16

18

19
1A
21

22

23

Call up block
Block called up

Description
Actual parameter (bit)
lies outside the permitted range
Actual parameter (byte)
lies outside the permitted range
Actual parameter (word)
lies outside the permitted range
Command "SE =para":
Actual parameter lies
outside the permitted range
Command "ZV =para":
Actual parameter lies
outside the permitted range
Command "R =para":
Actual parameter lies
outside the permitted range
Command "R =para":
Timer address is incorrect
Command "R =para":
Counter address is incorrect
Command "T =para":
Byte-actual parameter
lies outside the permitted range
Command "I =para":
Byte-actual parameter
lies outside the permitted range
Command "D =para":
Byte-actual parameter
lies outside the permitted range

PSS-Range: Error List

Remedy
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter

2-39

FS Error Messages

Error no.
31

32

33

34

35

36

37
38
39

3A
3B
3C

3D

2-40

Description
Command "T =para":
Word-actual parameter
lies outside the permitted range
Command "I =para":
Word-actual parameter
lies outside the permitted range
Command "D =para":
Word-actual parameter
lies outside the permitted range
Command "A =para":
Actual parameter DB lies
outside the permitted range
Command "T =para":
Actual parameter ZW lies
outside the permitted range
Command "S =para":
Bit-write access to
flag range above the special flag
Command "S =para":
Write access to read-only flags
Command "S =para":
Input bit set is not permitted
Command "R =para":
Bit-write access to flag range
above the special flag
Command "R =para":
Bit-write access to read-only flag
Command "R =para":
Resetting of input bit is not permitted
Command "T =para":
Byte-write access to
flag range above the special flag
Command "T =para":
Byte-write access to read-only flags

F-24

Remedy
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify actual parameter
Only output bit can be set;
rectify parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter

PSS-Range: Error List

F-24

Error no.
3E

3F
40

41
42

43

44
45

46

47
48

49

4A
4B

Description
Command "T =para":
Word-write access to
flag range above the special flags
Command "T =para":
Word write access to read-only flags
Command "I =para":
Byte-write access to
flag range above the special flags
Command "I =para":
Byte write access to read-only flags
Command "I =para":
Incrementing input byte is not
permitted
Command "D =para":
Byte-write access to
flag range above the special flags
Command "D =para":
Byte-write access to read-only flags
Command "D =para":
Decrementing input byte
is not permitted
Command "I =para":
Word-write access to
flag range above the special flag
Command"I =para":
Word-write access to read-only flags
Command "I =para":
Incrementing input word
is not permitted
Command "D =para":
Word-write access to
flag range above the special flag
Command "D =para":
Word write-access to read-only flags
Command "D =para":
Decrementing input word
is not permitted

PSS-Range: Error List

Remedy
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter

Flag range > do not use last special


flag in user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter

Flag range > do not use last special


flag in user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter

Flag range > do not use last special


flag in user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter

2-41

FS Error Messages

Error no.
4C

4D

4F

50

51
52
53

54

55

56

57

58

59

2-42

Description
Command "S =para", "!= =para",
"=N =para": Actual parameter lies
outside the permitted range
Command "R =para", Actual
parameter lies outside the
permitted range
Command "L =para",
XW-address on word module lies
outside the permitted range
Command "T =para",
XW-address on word module lies
outside the permitted range
Command "SE =para": Incorrect
timer address as actual parameter
Command "ZR =para": Incorrect
counter address as actual parameter
Command "ZV =para":
Incorrect counter address
as actual parameter
Command "L =para":
Bit-actual parameter lies outside
the permitted range
Command "L =para":
Timer address lies outside the
permitted range
Command "L =para":
Counter address lies outside the
permitted range
Command "L =para": Byte actual
parameter lies outside
the permitted range
Command "L =para": Word actual
parameter lies outside the
permitted range
Command "L =para":
Counter address lies outside the
permitted range

F-24

Remedy
Check and rectify parameter

Check and rectify pararmeter

Check and rectify pararmeter

Check and rectify pararmeter

Check and rectify actual pararmeter


Check and rectify actual pararmeter
Check and rectify actual pararmeter

Check and rectify actual pararmeter

Check and rectify bit

Check and rectify bit parameter for


counters
Check and rectify byte parameter

Check and rectify word parameter

Check and rectify word parameter


for counters

PSS-Range: Error List

F-25

Error class F-25 - Indirect addressing error


Error parameter:
Error location:
Error no.
01
02
03
04
05
13

16

17

18

19

1A

Flag word in which the indirect address appears


Block in which the error was detected

Description
Indirect address of the flag bit lies
outside the permitted range
Indirect address of the input bit lies
outside the permitted range
Indirect address of the output bit lies
outside the permitted range
Indirect address of the timer bit lies
outside the permitted range
Indirect address of the counter bit
lies outside the permitted range
Command "SE T(...)":
Indirect address of the timer lies
outside the permitted range
Command "ZV Z(...)":
Indirect address of the counter lies
outside the permitted range
Command "ZR Z(...)":
Indirect address of the counter lies
outside the permitted range
Command "R T(...)":
Indirect address of the timer lies
outside the permitted range
Command "R Z(...)":
Indirect address of the counter lies
outside the permitted range
Command "SE T(...)":
Indirect address of the timer lies
outside the permitted range

PSS-Range: Error List

Remedy
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect

2-43

F-25

FS Error Messages

Error no.
21
22
23
24

31
32
33
34

36

50

51

52

2-44

Description
Indirect address of the flag byte lies
outside the permitted range
Indirect addressed of the input byte
ies outside the permitted range
Indirect address of the output byte
lies outside the permitted range
Indirect address of the data
byte-word lies outside the
permitted range
Indirect address of the flag word
lies outside the permitted range
Indirect address of the input word
lies outside the permitted range
Indirect addressed output word
lies outside the permitted range
Indirect address of the counter
word lies outside the
permitted range
Command "L XW(...)":
Indirect address of XW
(word module) lies outside the
permitted range
Command "I MW(...)":
Indirect address of the flag word
lies outside the permitted range
Command "I AW(...)":
Indirect addres of the output word
lies outside the permitted range
Command "D MW(...)":
Indirect address of the flag word
lies outside the permitted range

Remedy
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect

Rectify flag word in the


increment command where
the indirect address is incorrect
Rectify output word in the
increment command where
the indirect address is incorrect
Rectify flag word in the
decrement command where
the indirect address is incorrect

PSS-Range: Error List

F-25

Error no.
53

54

55
56
57
58
59
5A

Description
Command "D AW(...)":
Indirect address of the output word
lies outside the permitted range
Command "A DB(...)":
Indirect address of the DB lies
outside the permitted range
Command "D MW(...)":
Word-write access to read-only flags
Command "I MW(...)":
Word-write access to read-only flag
Indirect bit-write access
to read-only flags
Indirect byte write access
to read-only flags
Indirect word write access to
read-only flags
Command "T XW(...)":
Indirect address of XW
(word module) lies outside the
permitted range

PSS-Range: Error List

Remedy
Rectify output word in the
decrement command where
the indirect address is incorrect
Rectify data block call up where
the indirect address is incorrect
Check and rectify parameter
Check and rectify parameter
Check and rectify parameter
Check and rectify parameter
Check and rectify parameter
Rectify access to word module
where the indirect address is
incorrect

2-45

FS Error Messages

F-26

Error class F-26 - Block error


Error parameter:
Error location:
Error no.
01
.
.
.
14

2-46

Description

Block not loaded

Block ID for missing block


Block which calls up the missing block
Remedy
Please contact Pilz;
Possibly use a new programmng
device in user program
(latest PG version)

PSS-Range: Error List

F-27

Error class F-27 - Parameter error


Error parameter:
Error location:
Error no.
01

Call-up block
Block called up

Description
Remedy
Formal and actual parameters do
Adjust the call-ups to suit the
not match (type, number, sequence) block header.

PSS-Range: Error List

2-47

FS Error Messages

F-28

Error class F-28 - Block nesting error


Error location:
Error no.
01
03
05
07

2-48

Block in which the error occurred

Description
Nesting level exceeded
by starting an OB (CAL OB)
Nesting level exceeded
by starting a PB (CAL PB)
Nesting level exceeded
by starting a FB (CAL FB)
Nesting level exceeded
by starting a SB (CAL SB)

Remedy
Check block nesting levels
and reduce the level
Check block nesting levels
and reduce the level
Check block nesting levels
and reduce the level
Check block nesting levels
and reduce the level

PSS-Range: Error List

F-29

Error class F-29 - Start/Stop FS section through PG


Error no. Description

Remedy

01

FS section stopped through PG

Message solely for information

02

Internal error: unable to start FS section


through PG

Please contact Pilz.

03

Start FS section through PG: invalid


password

Enter correct password

04

Internal error: unable to start FS section


through PG

Please contact Pilz.

05

Start FS section through PG: FS


selector switch at STOP

Switch FS selector switch to RUN.

06

Internal error: unable to start FS section


through PG

Please contact Pilz.

07

Start FS section through PG: start


aborted by user

Message solely for information

08

Internal error: unable to start FS section


through PG

Please contact Pilz.

09

Start FS section through PG: FS section Message solely for information


is already in RUN mode

0A

FS section started through PG

PSS-Range: Error List

Message solely for information

2-49

FS Error Messages

F-70

Error class F-70 - Operating system error (processor A)


Error no.
01
.
.
.
0D
0E

0F
.
.
.
13
14
15
.
.
.
18
19
1A
.
.
.
1F
20
21
22
23

2-50

Description

Remedy
Please contact Pilz

Major system error

Switch on processor A is not at


STOP, but an adjacent processor
has registered a STOP

Restart system
If no remedy helps: change CPU
Please contact Pilz

Major system error

Message for internal purposes


Please contact Pilz
Major system error

CRC is incorrect

Transfer program again,


If no remedy helps: change CPU
Please contact Pilz

Major system error

Error in the
programming device
Major system error

Use latest PG version


Please contact Pilz
Message for internal purposes

PSS-Range: Error List

F-70

Error no.
24
25
26
.
.
.
32
33

40
.
.
.
42
43

Description
Major system error

Remedy
Please contact Pilz
Message for internal purposes
Please contact Pilz

Major system error

Incorrect CRC

Transfer program
If no remedy helps: change CPU
Please contact Pilz

Major system error

44

CPUs attempt to call-up


different alarm-OBs
Major system error

Reduce alarm load


If no remedy helps: change CPU
Please contact Pilz

46

Internal table has changed

Transfer program
If no remedy helps: change CPU
Message for internal purposes
Please contact Pilz

47
48
.
.
.
63
64
65
.
.
.
71

Major system error

Error on DIF module

Change DIF module


Please contact Pilz

Major system error

PSS-Range: Error List

2-51

FS Error Messages

Error no.
72
73
.
.
.
7F

2-52

F-70

Description
Too many errors simultaneously

Remedy
Restart PSS

Major system error

Please contact Pilz

PSS-Range: Error List

F-71

Error class F-71 - Synchronisation error (processor A)


Error parameter:
Error no.
01
02

Description
Major system error

PSS-Range: Error List

Synchronisation location
Remedy
Please contact Pilz

2-53

FS Error Messages

F-72

Error class F-72 - Error in adjacent CPU (processor A)


Error no.
01
.
.
.
26
27
28
29
32

2-54

Description

Remedy
Please contact Pilz

Major system error

Defective CPU

Change CPU

Major system error

Please contact Pilz

PSS-Range: Error List

F-73

Error class F-73 - Error reading the PII (processor A)


Error no.
04

Description
PII cannot be determined

05

PII for DIF cannot be determined

06
07

PII cannot be determined

PSS-Range: Error List

Remedy
Increase the number of read
attempts;
If no remedy helps: change input
module
Increase the number of read
attempts; reduce interrupt load;
If no remedy helps: change DIF
module
Increase the number of read
attempts;
If no remedy helps: change input
module

2-55

FS Error Messages

F-74

Error class F-74 - Configuration error (processor A)


Error no.
01
.
.
06
07
08
09

0A
0B

0C
0D
0E
0F
10

12

2-56

Description
Error in the operating
system or programming device
Entry in the configurator
is invalid
Invalid slot entered in the configurator for the test pulse module
Slot entered in configurator as the
slot for test pulse module contains
no pulsed outputs
FS user program
is not loaded
Max. number of test pulses in the
configurator does not match the
number used
Two adjacent inputs are being
tested with the same test pulse
Highest test pulse number used is
not permitted
Alarm-OBs configuration
is not consecutive
Alarm-OB loaded, which
is not configured
Invalid slot number configured for
alarm configuration
Invalid edge configuration, process
alarm-OB must be activated with a
rising and falling pulse edge

Remedy
Check contents of the configurator,
If no remedy helps: use a new
programming device (use latest
PG version)
Rectify basic data in the
configurator
Enter valid slot in the configurator
Check PSS configuration and adjust,
or adjust the entry in the configurator
to the layout
Download FS user program
into PSS
Rectify the number of test pulses
in the configurator
Re-enter the test pulse allocation
in the configurator
Re-enter the number of test pulses
in the configurator
Re-enter alarm-OBs in the
configurator
Check user program
Check PSS configuration and check
the details in the configurator for the
slot for the DIF module
Check alarm-OB configuration

PSS-Range: Error List

F-74

Error no.
13
14
.
.
.
17
18
19
1A

1B

Description
Edge configuration is
invalid
Error in alarm
configuration or the
programming device
Min. scan time is greater than the
max. permitted scan time
Error in the operating
system or programming device

1D

Read segments have been


defined on a slot that does not have
a word module
Start address for read
segments is too high
Read segments overlap

1E

Segment length is invalid

1F

Read segment extends beyond


the module
Alignment algorithm is invalid

1C

20
21
22

Double word read segment lies


outside the double word address
Word modules are not
in ascending order

PSS-Range: Error List

Remedy
Check alarm-OB configuration
Check contents of configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device
Re-enter the minimum scan time in
the configurator
Check contents of configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device
Check the read/write segments in
the configurator
Check the read segments for the
word module in the configurator
Check the read segments for the
word module in the configurator
Check the read segments for that
word module in the configurator
Check the read segments for that
word module in the configurator
Check alignment algorithm for that
word module in the configurator
Check the read segments for that
word module in the configurator
Enter word modules in the
configurator in ascending order

2-57

FS Error Messages

Error no.
23

Description
Alignment point is invalid

24

A word module has an


invalid slot

25

28

Slots for output segments are not


in ascending order
Output segments have been
defined on a slot that has no
word module
Start address for output
segments is too high
Output segments overlap

29

Segment length is invalid

30

Output segment extends


beyond the module
Double word output segment lies
outside the double word address
Word modules are
not in ascending order
Output point is invalid

26

27

31
32
33
34
35
36
37

2-58

Both DI and DIF inputs tested with


the same test pulse
More than 2 DIF in the
set layout configuration
Test module entered
but pulse number is FF
Program cannot be run on this PSS

F-74

Remedy
Check alignment point for the word
module in the configurator
Check configuration, check read and
write segments in the configurator
Check read and write segments in
the configurator
Check read and write segments in
the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Enter the word modules in
configurator in ascending order
Check output point for the word
module in the configurator
Check test pulse allocation
in the configurator
Check configuration, change the
configuration in the configurator
Check configuration or test pulse
allocation in the configurator
Use correct CPU module

PSS-Range: Error List

F-74

Error no.
38
.
.
47
48
49
.
.
4B

Description
Selective shutdown
configuration error
A module is not supported by the
operating system
Selective shutdown
configuration error

PSS-Range: Error List

Remedy
Please contact Pilz;
possibly use new programming
device (use latest version)
Change CPU module
Please contact Pilz;
possibly use new programming
device (use latest version)

2-59

FS Error Messages

F-75

Error class F-75 - Programming device error (processor A)


Error no.
01
.
.
.
04

2-60

Description

Programming device error

Remedy
Please contact Pilz;
possibly use new programming
device (use latest version)

PSS-Range: Error List

F-76

Error class F-76 - Compiler error messages (processor A)


Error parameter:
Error location:
Error no.
01
24
7F

Line number
Block

Description
Programming device error

PSS-Range: Error List

Remedy
Please contact Pilz;
possibly use new programming
device (use latest version)

2-61

FS Error Messages

F-77

Error class F-77 - Program load error (processor A)


Error no.
01
02
03

04

05
06

07
08

09

0A

2-62

Description
Remedy
Too many blocks have been loaded Reduce blocks to a maximum of 511
PG communication error
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
User program damaged
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
PG communication error
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
Message for internal purposes
Memory for the
Clear memory (Flash-EPROM),
application program is full
reload the user program into
the PSS. If no remedy helps: reduce
the size of the application program
PSS program has not
Only load the program created
been loaded
using the programming device for
the PSS
PG communication error
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device

PSS-Range: Error List

F-77

Error no.
0B
0C
0D

Description
Approved block is defective
DB 002 does not have
write-protection

PSS-Range: Error List

Remedy
Obtain block from original disk,
re-link program and transfer
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device

2-63

FS Error Messages

F-78

Error class F-78 - Program link error (processor A)


Error parameter:

Error no.
01
.
.
.

Description

Link error
.

Block

Remedy
Clear user program,
Re-load user program into the
PSS. If no remedy helps, contact
Pilz; change CPU or programming
device

03

2-64

PSS-Range: Error List

F-79

Error class F-79 - Error in the process image of outputs system error
(processor A)
Error no.
01
.
.
.
04

Description

Remedy
Please contact Pilz.

Major system error

PSS-Range: Error List

2-65

FS Error Messages

F-7A

Error class F-7A - System error (processor A)


Error no.
01
.
.
.
07

2-66

Description

Remedy
Please contact Pilz

Major system
error

PSS-Range: Error List

F-80

Error class F-80 - Fatal system error (processor A)


Error parameter:
Error no.
01
.
.
.
04

Description

Adjacent error number


Remedy
Please contact Pilz.

Major system error

PSS-Range: Error List

2-67

FS Error Messages

F-81

Error class F-81 - Operating system call up error


Error no.
01

Description
Too many test slices set

02

Alignment algorithm: (SB 255,


FUNK 21); Slot number is invalid
Alignment algorithm: (SB 255,
FUNK 21); No word module on slot
Alignment algorithm: (SB 255,
FUNK 21); Segment number is
invalid
Alignment algorithm (SB 255,
FUNK 21): Alignment algorithm
number is invalid
Alignment algorithm (SB 255,
FUNK 21): Alignment segment
does not exist
Called up SB 255 with
invalid function
Read segment (SB 255, FUNK 25):
Segment number is invalid
(SB 255, FUNK 25): Alignment
segment does not exist
Read segment (SB 255, FUNK 25):
Segment number is invalid
(SB 255, FUNK 25): Word module
not on slot entered
Write segment (SB 255, FUNK 23):
Segment number is invalid
Write segment (SB 255, FUNK 23):
Write segment does not exist
Write segment (SB 255, FUNK 23):
Slot number is invalid
(SB 255, FUNK 23): Word module
not on slot entered

03
04

05

06

07
08
09
0A
0B
0C
0D
0E
0F

2-68

Remedy
Enter max. 99 test slices in DB 003,
DW 220
Correct the slot number in DB 003
Check configuration;
Correct the slot number in DB 003
Correct match segment number
in DB 003
Correct alignment algorithm number
in DB 003
Correct match segment number
in DB 003
Check function number
Correct read segment number in
DB 003
Correct match segment number
in DB 003
Correct read segment number in
DB 003
Correct slot number in DB003
Correct write segment number in
DB 003
Correct write segment number in
DB 003
Correct slot number in DB 003
Correct slot number in DB 003

PSS-Range: Error List

F-81

Error no.
18
19

1A
1D
1E
1F

20
21
22
23
24
25

27
28
29

Description
Invalid start address for CRCcalculation in SB 001
Invalid end address for CRCcalculation in SB 001
ID-Number for CRC-calculation
is invalid
Call SB 255, FUNK 100, but
selective shutdown is not defined
Call SB 255, FUNK 100:
Selected signal group not available
Call SB 255, FUNK 100:
Selected signal group
not deactivated yet
Call SB 255, FUNK 100: Run time
for deadman timer is too long
Call SB 255, FUNK 101, but
selective shutdown is not defined
Call SB 255, FUNK 101:
Selected signal group not available
Call SB 255, FUNK 102, but
selective shutdown is not defined
Call SB 255, FUNK 102:
Selected signal group not available
Call SB 255, FUNK 102:
Selected signal group
not yet deactivated
Call SB 255, FUNK 103, but
selective shutdown is not defined
Call SB 255, FUNK 103:
No module on slot entered
Call SB 255, FUNK 104, but
selective shutdown is not defined

PSS-Range: Error List

Remedy
Correct input parameter STRT
Choose the address range for CRCchecksum so that the last value is in
the permitted address range

Set selective shutdown in the


configurator or correct the function
Check signal groups
Deactivate the signal group,
then acknowledge with FUNK = 100
Reduce run time for deadman timer
Set selective shutdown in the
configurator or correct the function
Check signal groups
Set selective shutdown in the
configurator or correct the function
Check signal groups
Deactivate the signal groups,
then acknowledge with FUNK = 100
Set selective shutdown in the
configurator or correct the function
Check configuration or correct the
slot number in DB 003
Set selective shutdown in the
configurator or correct the function

2-69

FS Error Messages

Error no.
2A
2B
2C
2D
2E
2F
31
32
33
34
35

36

37

2-70

Description
Call SB 255, FUNK 104:
No module on slot entered
Call SB 255, FUNK 104:
Word module not on slot entered
Call SB 255, FUNK 104:
Segment has not been defined
Call SB 255, FUNK 105, but
selective shutdown is not defined
Call SB 255, FUNK 105,
called up in alarm-OB
Call SB 255, FUNK 106, but
selective shutdown is not defined
Call SB 255, FUNK 106,
Called up in alarm-OB
Call SB 255, FUNK 106:
Called up in OB 120
Call SB 255, FUNK 106, although
reactivation is already active
Call SB 255, FUNK 106:
Selected signal group not available
Call SB 255, FUNK 106:
Selected signal group has not
been deactivated
Call SB 255, FUNK 106:
Reactivation although signal group
type 0 is not to be reactivated
Call SB 255, FUNK 106:
Reactivating a module that
has been shut down, pulsed
inputs, signal group type 1 or
type 2 on faulty module

F-81

Remedy
Check configuration or correct entry
in DB 003
Check configuration or correct entry
in DB 003
Check configuration or read/write
segment in DB 003
Set selective shutdown in the
configurator or correct the function
Do not carry out reactivation
with FUNK 105 in alarm-OB
Set selective shutdown in the
configurator or correct the function
Do not carry out reactivation
with FUNK 106 in alarm-OB
Remove call up from OB120
Correct user program
Check signal groups
Only deactivated signal groups can
be reactivated, check signal
groups
Check user program,
and if required reactivate all
signal groups simultaneously
Check user program,
and if required reactivate all
signal groups simultaneously

PSS-Range: Error List

F-81

Error no.
39
Error class
F-81
3A

Description
Call SB 255, FUNK 107: but
selective shutdown is not defined
Error no. Description

Remedy
Set selective shutdown in the
configurator or correct the function
Remedy

Call SB 255, FUNK 107:


Called up in alarm-OB

Reactivation error acknowledgement


do not carry out with FUNK 107 in
an alarm-OB
Reactivation error acknowledgement
carry out only after a reactivation
error
Reactivation error acknowledgement
carry out only after a reactivation
error
Set selective shutdown in the
configurator or correct the function
Reactivation acknowledgement
should not be carried out with
FUNK 108 in alarm-OB
Reactivation acknowledgement
should only be carried out once
reactivation is complete
Only acknowledge reactivation
if a reactivation error has not
occurred
Carry out reactivation and then
acknowledge

3B

Call SB 255, FUNK 107:


Although reactivation is not active

3C

Call SB 255, FUNK 107:


Although no reactivation
error is present
Call SB 255, FUNK 108: but
selective shutdown is not defined
Call SB 255, FUNK 108:
Called up in alarm-OB

3E
3F

40

Call SB 255, FUNK 108:


Although reactivation is not active

41

Call SB 255, FUNK 108:


Reactivation error

42

Call SB 255, FUNK 108:


Reactivation acknowledgement
although reactivation not complete
Call SB 255, FUNK 109: but
selective shutdown is not defined
Call SB 255, FUNK 109:
Signal group number is invalid
Call SB 255, FUNK 109:
reaction type selected is invalid

44
45
46

PSS-Range: Error List

Set selective shutdown in the


configurator or correct the function
Check signal group number
and correct in DB 003
Correct the reaction type in DB 003

2-71

FS Error Messages

Error no.
47

49
4A
4B
4C

4D

4E
4F

50

52

53

2-72

Description
Call SB 255, FUNK 109:
Deactivation interrupted
as the reaction type
is too large
User interface:
Config. DB too short
User interface:
Send DB too short
User interface:
Receive DB too short
Call SB 255, FUNK 103:
Word module is on the
slot entered
Call SB 255, FUNK 104:
Call-up is invalid
Reactivation prevents self-check,
reactivation is not acknowledged
Error in stated block:
Call SB 255, FUNK 111, invalid
I/O-Group entered
Error in stated block:
Call SB 255, FUNK 111, but
previous call not yet processed
Error in stated block:
Call SB 255, FUNK 115, invalid
I/O-Group entered
Error in stated block:
Call SB 255, FUNK 115, but
previous call not yet processed

F-81

Remedy
Reaction type of the signal group
for the 2nd deactivation must be
smaller than that for the 1st,
change reaction type in DB 003
Check configuration DB
(DB no. must appear in DB 003)
Check send DB
(DB no. must appear in DB 003)
Check receive DB
(DB no. must appear in DB 003)
Check configuration, adjust
parameters; FUNK 103 only for bit
modules
Check user program, only
call-up parameters 0 ... 5 are
permitted (see DB 003/DW 201)
Once reactivation is complete,
acknowledge using FUNK 108
Correct enable parameters

Calls of SB 255, FUNK 111 should


be separate in terms of time. The
time offset should be at least one
cycle.
Correct enable parameters

Calls of SB 255, FUNK 111 should


be separate in terms of time. The
time offset should be at least one
cycle.

PSS-Range: Error List

F-81

Error no. Description

Remedy

55

Error in stated block:


Call SB255, FUNK 118, invalid enable
parameters

Correct enable parameters stated in


code
0 = DB-Number (target)
1 = Device Address (target)
The code is shown on the error stack
display on the PG.

56

Error in stated block:


Call SB255, FUNK 119, invalid enable
parameters

Correct enable parameters stated in


code
0 = DB-Number (source)
1 = Device Adresse (target)
3 = Start-DW (source)
4 = Number of DWs
The code is shown on the error stack
display on the PG.

57

Error in stated block:


Call SB255, FUNK 119, source DB not
available

1.) Check enable parameter DBnumber


2.) Check whether DB is available in the
project

58

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB119, source DB too short
number
2.) Check length of DB

59

Error in stated block: Call SB255, FUNK 1.) Check enable parameter Device
119, Master-LD has no write access to address
the stated device
2.) Check the configuration; the MasterLD must have write access to the I/OGroup containing the stated device

5A

Error in stated block: Call SB255, FUNK Correct enable parameters stated in
122, invalid enable parameters
code
0 = DB-Number (source)
1 = Device Address (target)
The code is shown on the error stack
display on the PG.

PSS-Range: Error List

2-73

FS Error Messages

Error no. Description

F-81

Remedy

5B

Error in stated block: Call SB255, FUNK Correct enable parameters stated in
123, invalid enable parameters
code
0 = DB-Number (source)
1 = Device Adresse (source)
2 = DB-Number (target)
3 = Start-DW (target)
4 = Number of DWs
The code is shown on the error stack
display on the PG.

5C

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB123, target DB not available
number (target)
2.) Check whether DB is available in the
project

5D

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB123, target DB too short
number (target)
2.) Check length of DB

5E

Error in stated block: Call SB255, FUNK Lift write protection on target DB
123, target DB is Read-Only

5F

Error in stated block: Call SB255, FUNK 1.) Check enable parameter Device
123, Master-LD has no read access to address
the stated device
2.) Check the configuration; the MasterLD must have read access to the I/OGroup containing the stated device

60

Error in stated block: Call SB255, FUNK Correct enable parameters stated in
124, invalid enable parameters
code
0 = Domain Number (source)
1 = Device Adresse (source)
The code is shown on the error stack
display on the PG.

2-74

PSS-Range: Error List

F-81

Error no. Description

Remedy

61

Error in stated block: Call SB255, FUNK Correct enable parameters stated in
127, invalid enable parameters
code
0 = DB-Number (source)
2 = DB-Number (target)
3 = Start-DW (target)
4 = Number of DWs
The code is shown on the error stack
display on the PG.

62

Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
127 not permitted
127 may only be called in OB131 of the
Slave-LD

63

Error in stated block: Call SB255, FUNK Check enable parameter DB-number
127, DB-Number (source) does not
(source)
match the DB received

64

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB127, target DB not available
number (target)
2.) Check whether DB is available in the
project

65

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB127, target DB too short
number (target)
2.) Check length of DB

66

Error in stated block: Call SB255, FUNK Lift write protection on target DB
127, target DB is Read-Only

68

Error in stated block: Call SB255, FUNK Correct enable parameters


131, invalid DB-Number

69

Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
131 not permitted
131 may only be called in OB131 of the
Slave-LD

6A

Error in stated block: Call SB255, FUNK Check enable parameter DB-number
131, DB-Number (source) does not
(source)
match the DB received

PSS-Range: Error List

2-75

FS Error Messages

Error no. Description

F-81

Remedy

6B

Error in stated block: Call SB255, FUNK Correct enable parameters


135, invalid DB-Number

6C

Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
135 not permitted
135 may only be called in OB131 of the
Slave-LD

6D

Error in stated block: Call SB255, FUNK Check enable parameter DB-number
135, DB-Number (source) does not
(source)
match the DB received

6E

Error in stated block: Call SB255, FUNK Correct enable parameters stated in
139, invalid enable parameters
code
0 = DB-Number (source)
3 = Start-DW (source)
4 = Number of DWs
The code is shown on the error stack
display on the PG.

6F

Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
139 not permitted
139 may only be called in OB132 of the
Slave-LD

70

Error in stated block: Call SB255, FUNK Check enable parameter DB-number
139, DB-Number (source) does not
(source)
match the DB received

71

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB139, source DB not available
number (source)
2.) Check whether DB is available in the
project

72

Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB139, source DB too short
number (source)
2.) Check length of DB

74

Error in stated block: Call SB255, FUNK Check enable parameters


143, invalid DB-Number

2-76

PSS-Range: Error List

F-81

Error no. Description

Remedy

75

Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
143 not permitted
143 may only be called in OB132 of the
Slave-LD

76

Error in stated block: Call SB255, FUNK Check enable parameter DB-number
143, DB-Number (source) does not
(source)
match the DB received

77

Error in stated block: Call SB255, FUNK Correct enable parameters


147, invalid DB-Number

78

Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
147 not permitted
147 may only be called in OB132 of the
Slave-LD

79

Error in stated block: Call SB255, FUNK Check enable parameter DB-number
147, DB-Number (source) does not
(source)
match the DB received

7A

Error in stated block: Call SB255, FUNK Correct enable parameters


02, invalid slot

7B

Error in stated block: Call SB255, FUNK 1.) Check enable parameters
02, slot is unoccupied
2.) Amend configuration

7C

Error in stated block: Call SB255, FUNK In the enable parameters, a slot has
02, power-up test cannot be deactivated been entered that contains no outputs
on which the power-up test can be
deactivated.

PSS-Range: Error List

2-77

FS Error Messages

F-82

Error class F-82 - Test pulse error (processor A)


Error parameter:

Pulse number coded bit by bit

Error no.
01
.

Description

Error on PSS (1) DIO T

.
03

2-78

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the output
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.

PSS-Range: Error List

F-83

Error class F-83 - Debug error (processor A)


Error no.
01
.
.
.
7F

Description

Remedy
Please contact Pilz

Debug error

PSS-Range: Error List

2-79

FS Error Messages

F-84

Error class F-84 - Word module match error (processor A)


Error parameter:

Error no.
01
.
.
.
0E

2-80

High byte: Slot number


Low byte: Number of read segments

Description
Error on word module

Remedy
1.) Tolerance set is too low
2.) Incorrect alignment algorithm
(e.g. match instead of min.- max.)
if there is no error in the
configuration: change module

PSS-Range: Error List

F-90

Error class F-90 - Operating system error (processor B)


Error no.
01
.
.
.
10
11

12
.
.
.
20
21
22
25
.
.
.
33
34
35
.
.
.
37
38
.
.
.
7C

Description

Remedy
Please contact Pilz

Major system error

Switch on processor B is not at


STOP, but an adjacent processor
has registered a STOP

Restart system
If no remedy helps: change CPU
Please contact Pilz

Major system error

Internal table error

Reload program into the PSS,


If no remedy helps: contact Pilz
Please contact Pilz

Major system error

Internal table error

Message for internal purposes


Reload program into the PSS,
If no remedy helps: contact Pilz

Please contact Pilz


Major system error

PSS-Range: Error List

2-81

FS Error Messages

F-91

Error class F-91 - Synchronisation error (processor B)


Error parameter:
Error no.
00

2-82

Synchronisation location

Description
Error within the operating
system

Remedy
Please contact Pilz

PSS-Range: Error List

F-92

Error class F-92 - Error in adjacent CPU (processor B)


Error no.
00
.
.
.
36

Description

Remedy
Please contact Pilz

Major system error

PSS-Range: Error List

2-83

FS Error Messages

F-93

Error class F-93 - Error reading the PII (processor B)


Error no.
00

Description
PII cannot be
determined

01

PII for DIF cannot be


determined

04
05

PII cannot be
determined

06

PII for DIF cannot be


determined

2-84

Remedy
Increase number of read attempts
If no remedy helps: change input
module
Increase number of read attempts;
reduce interrupt load
If no remedy helps: change DIF
module
Increase number of read attempts
If no remedy helps: change input
module
Increase number of read attempts;
reduce interrupt load
If no remedy helps: change DIF
module

PSS-Range: Error List

F-94

Error class F-94 - Configuration error


Error no.
01
.
.
.
03
04
05
06

07
08

09
0A

0B
0C
0D

Description
Programming device error

Memory range for read/write


DBs is full
Programming device error

Invalid slot has been entered in the


configurator for test pulse module
Slot entered for the test output
module contains no pulsed
outputs
FS application program
has not been loaded
Max. number of test pulses in the
configurator does not correspond
with those used
Two adjacent inputs are tested
with the same test pulse
Highest test pulse number used
is not permitted
Configuration of alarmOB is not consecutive

PSS-Range: Error List

Remedy
Check contents of the configurator
If no remedy helps: contact Pilz.
possibly use new programming
device (use latest PG version)
Reduce the number of read/write
data blocks
Check contents of the configurator
If no remedy helps: contact Pilz.
possibly use new programming
device (use latest PG version)
Enter valid slot in the
configurator
Check PSS configuration and
adjust or amend the entry in the
configurator to suit the configuration
Download user program into
PSS
Correct the number of test pulses
in the configurator
Correct the test pulse allocation in
the configurator
Correct the test pulse allocation in
the configurator
Enter alarm-OBs in the configurator
consecutively

2-85

FS Error Messages

Error no.
0E

Description
Alarm-OB has been loaded
which has not been configured

0F

Invalid slot number has been


entered for the alarm configuration

10

Slot entered for the DIF


in the configurator does
not contain a DIF module
Edge configuration is invalid,
process alarm OB must be
activated with a rising and falling
pulse edge
Invalid edge configuration

11

12

F-94

Remedy
Check user program
If no remedy helps: contact Pilz;
possibly use new programming
device
Check PSS configuration,
check the slot for the PSS DIF
in the configurator
Check PSS configuration,
check the slot for the PSS DIF
in the configurator
Check the configuration for the
alarm OBs

13
.
.
.
16
17

Alarm configuration error

Check the configuration for the


alarm OBs
Check contents of configurator
If no remedy helps: contact Pilz;
possibly use new programming
device

Min. scan time is greater than the


max. permitted scan time

Correct minimum scan time in the


configurator

18
19

Programming device error

1A

Read segments defined for a slot


on which a word module is not
located
Start address for read
segments is too large

Check contents of configurator,


If no remedy helps: contact Pilz;
possibly use new programming
device
Check read segments in the
configurator

1B

2-86

Check read segment for the word


module in the configurator

PSS-Range: Error List

F-94

Error no.
1C

Description
Read segments overlap

1D

Segment length is invalid

1E

Write segment extends


beyond the module
Alignment algorithm is invalid

1F
20
21
22
23

Double word read segment begins


with an uneven (odd) address
Word modules are not
in ascending order
Alignment point is invalid

27

Slot for the word module


is invalid
Slots for the write segments are
not in ascending order
Write segments have been
defined on a slot that has no
word module
Start address for read
segments is too large
Write segments overlap

28

Segment length is invalid

29

Write segment extends


beyond the module
Double-word write segment lies
outside the double-word address

24
25

26

2A

PSS-Range: Error List

Remedy
Check read segment for the word
module in the configurator
Check read segment for the word
module in the configurator
Check read segment for the word
module in the configurator
Check alignment algorithm for the
word module in the configurator
Check read segments for
word modules
Enter word modules in ascending
order in the configurator
Check alignment point for the
word module in the configurator
Check configuration, check read and
write segments in the configurator
Check write segments in the
configurator
Check write segments in the
configurator
Check write segments for the word
module in the configurator
Check write segments for the word
module in the configurator
Check write segments for the word
module in the configurator
Check write segments for the word
modules in the configurator
Check write segment for the word
module in the configurator

2-87

FS Error Messages

Error no.
2B
2C
2D
2E
2F
30

31
.
.
.

Description
Word modules have not
been entered in ascending order
Output time point is invalid
The same pulse is testing
the DI and DIF inputs
More than 2 DIF in the
set layout
Pulse module entered,
but pulse number = FF
Operating system
version is invalid

Error in selective
shutdown configuration

F-94

Remedy
Enter the word modules in the
configurator in ascending order
Check output time point for the word
module in the configurator
Check test pulse allocation in the
configurator
Check configuration, amend set
layout in the configurator
Check configuration or test pulse
allocation in the configurator
Use correct PSS CPU,
program cannot be executed using
this PSS.
Check configuration
If no remedy helps: contact Pilz
support; possibly use new
programming device
(use latest PG version)

49

2-88

PSS-Range: Error List

F-96

Error class F-96 - Compiler error messages (processor B)


Error parameter:
Error location:
Error no.
01
.
.
.
0D

Description

Programming device error

PSS-Range: Error List

Line number
Block
Remedy
Please contact Pilz; possibly
use new programming device
(use latest PG version)

2-89

FS Error Messages

F-97

Error class F-97 - Program load error (processor B)


Error no.
01
02

Description
Programming device error

03

Too many blocks have


been loaded
Memory range for
application program is full

04

05

Faults/interference
affecting the download
cable

06

P10 block was loaded

07
08

Programming device error

09

Configuration error

0A

Programming device error

0B

Program error

2-90

Remedy
Please contact Pilz; possibly
use new programming device
(use latest PG version)
Reduce the number of blocks to a
maximum of 511
Clear the memory (Flash-EPROM),
Transfer user program again
If no remedy helps: reduce the
size of the user program
Reload user program into
the PSS, rectify error
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
To program the PSS only use a
programming device suitable for
the PSS (not a P10 PG)
Please contact Pilz; possibly
use a new programming device
(use latest PG version)
See additional error messages in the
error stack
Please contact Pilz; possibly
use a new programming device
(use latest PG version)
See error stack

PSS-Range: Error List

F-97

Error no.
0C
0D

Description
Major system error

0E
10
11

Program error
An approved block
is defective

12
0D

Error in the programming device

PSS-Range: Error List

Remedy
Please contact Pilz; possibly use
new programming device
(use latest PG version)
See error stack
Obtain the block from the original,
disk, relink the program and
transfer to PSS
Please contact Pilz; possibly use
new programming device
(use latest PG version)

2-91

FS Error Messages

F-98

Error class F-98 - Program link error (processor B)


Error parameter:
Error no.
01
.

Description

Link error

Block
Remedy
Clear user program,
Reload user program into the PSS
If no remedy helps: contact Pilz;
possibly use new CPU module
or new programming device

.
03

2-92

PSS-Range: Error List

F-99

Error class F-99 - Error in process image of outputs (processor B)


Error no.
01
.
.
.
09

Description

Remedy
Please contact Pilz

Major system error

PSS-Range: Error List

2-93

FS Error Messages

F-A2

Error class F-A2 - Test pulse error (processor B)


Error parameter:
Error no.
01

Pulse number coded bit by bit

Description

.
Error on PSS (1) DIO T
.
.
03

2-94

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs or
the test pulse wiring?
If no remedy helps: change module

PSS-Range: Error List

F-A3

Error class F-A3 - Debug error (processor B)


Error no.
01

Description
Debug error

PSS-Range: Error List

Remedy
Please contact Pilz.

2-95

FS Error Messages

F-A4

Error class F-A4 - Word module match error (processor B)


Error parameter:

Error no.
01
.
.
.
0D

2-96

High byte: Slot number


Low byte: Number of read segments

Description
Error on word module

Remedy
1.) Tolerance set is too low
2.) Incorrect alignment algorithm
(e.g. match instead of min.- max.)
if there is no error in the
configuration: change module

PSS-Range: Error List

F-B0

Error class F-B0 - Operating system error (processor C)


Error no.
01
.
.
.
17
18

19
.
.
.
1C
1D
1E
.
.
.
26
27
28
.
.
.
30
31
32
.
.
.
5D

Description

Remedy
Please contact Pilz

Major system error

Switch on processor C is not at


STOP, but an adjacent processor
has registered a STOP

Restart system
If no remedy helps: change CPU
Please contact Pilz

Major system error

Message for internal purposes


Please contact Pilz
Major system error

Message for internal purposes


Please contact Pilz
Major system error

Block not available

Reload program into PSS


If no remedy helps: change CPU
Please contact Pilz

Major system error

PSS-Range: Error List

2-97

FS Error Messages

F-B1

Error class F-B1 - Synchronisation error (processor C)


Error parameter:
Error no.
00
.
.
.
2C

2-98

Description

Synchronisation location
Remedy
Please contact Pilz.

Major system error

PSS-Range: Error List

F-B2

Error class F-B2 - Error in adjacent CPU (processor C)


Error no.
00
.
.
.
06
07
.
.
.
19
1A
1C
.
.
.
20
21
22
23

Description

Remedy
Please contact Pilz.

Major system error

Please contact Pilz.


Major system error

Error on word module

Change word module


Please contact Pilz.

Major system error

Cause of the alarm


cannot be determined
Major system error

PSS-Range: Error List

Alarms must appear for a


minimum of 1.5 ms
Please contact Pilz.

2-99

FS Error Messages

F-B3

Error class F-B3 - Error reading the PII


Error no.
00

Description
PII cannot be determined

02

PII for DIF cannot be determined

05
06
0B

Test time for DI module is too short

32
33

PII cannot be determined

34

PII for DIF cannot be determined

2-100

Major system error

Remedy
Increase number of read attempts;
If no remedy helps: change input
module
Increase number of read attempts;
If no remedy helps: change DIF
module
Increase test time in the configurator;
If no remedy helps: contact Pilz
Please contact Pilz.
Increase rnumber of read attempts;
If no remedy helps: change input
module
Increase number of read attempts;
If no remedy helps: change DIF
module

PSS-Range: Error List

F-B4

Error class F-B4 - Configuration error (processor C)


Error no.
01
02
03
.
.
.
08
09

Description
Major system error

Remedy
Please contact Pilz.

Programming device
error

Check contents of the configurator,


If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)

Too many read/write


DBs have been loaded

0A
Programming device
error
0B
0C
0D
.
.
.
17
18
19

Input in the configurator is invalid


Min. scan time is greater
than the max. scan time
Programming device
error

Incorrect CRC checksum


Programming device error
(alarm-OB is missing)

PSS-Range: Error List

Reduce the number of read/writeDBs


Check contents of the configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Check contents of the configurator
Correct scan time in the configurator
Check contents of the configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Transfer program again
Check contents of the configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)

2-101

FS Error Messages

Error no.
1A
1B
1C
1D
1E

Description
DIF has been
configured incorrectly
Alarm-OB has been configured for a
slot that contains no DIF
More alarm-OBs configured than
inputs on DIF
Edge configuration is invalid

1F

Alarm configuration is not entered


in ascending order

20

Slot number for the


alarm configuration is invalid

21

Alarm-OBs are not


configured consecutively
Alarm-OB loaded which
was not configured
Slot entered in the configurator for
the pulse module is invalid
Pulse module not in the
slot entered in the configurator

22
23
24

25
26

27
28

2-102

Number for the highest


test pulse used is invalid
Highest test pulse used does not
match the highest test pulse
entered in the configurator
Two adjacent inputs are tested with
the same test pulse
Word module is not on the slot
entered in the configurator

F-B4

Remedy
Check contents of the configurator,
check user program
Check the configuration for the
alarm-OBs and the layout
Check the configuration for the
alarm-OBs
Check the configuration for the
alarm-OBs
Enter the slots for alarm processing
in the configurator in ascending
order
Check the PSS configuration, check
the slots defined for the DIF in the
configurator
Enter alarm-OBs in the configurator
consecutively
Check user program
Enter a slot in the configurator that
is valid
Check the PSS configuration and
adjust or amend the entry in the
configurator to match the
configuration
Correct the number of the test pulse
in the configurator
Correct the entry for the test pulse
number in the configurator
Correct the test pulse allocation in
the configurator
Check configuration and enter the
slot number correctly in the
configurator

PSS-Range: Error List

F-B4

Error no.
29

Description
Slot number for the word module
is invalid

Remedy
Enter the slot number correctly in
the configurator

2A

Slots for the read segments are not


in ascending order

Check read segments in the


configurator

2B

Read segment length is too long

2C

Address range for word


module exceeded

2D
2E

Segment with 2 words is not at a


double word address
Read segments overlap

2F

Alignment algorithm is invalid

30

Compare alignment algorithm, but


but the tolerance does not = 0
Read-in point is invalid

Correct the read segment length in


the configurator (1 or 2 words)
Check address range in the
configurator (max. offset + segment
length)
Change offset in the configurator,
the offset must be divisible by 4
Check read segments in the
configurator
Check alignment algorithm in the
configurator
Set tolerance to 0 in the configurator

31
32

33
34
35
36
37
38

Write segment for a slot has been


defined, but no word module
on the slot
Slot number for the
word module is invalid
Write segments are not
in ascending order
Length of the write is
segment is too long
Address range for the
word modules exceeded
Segment with 2 words
starts with an unequal address
Write segments overlap

PSS-Range: Error List

Correct read-in point in the


configurator
Check read segments in the
configurator
Check write segment in the
configurator
Enter write segments in the
configurator in ascending order
Correct length of the write segments
in the configurator (1 or 2 words)
Correct address range (max. offset
+ segment length) in the configurator
Change the offset in the configurator,
offset must be divisible 4
Check write segments in the
configurator

2-103

FS Error Messages

Error no.
39

Description
Output point is invalid

3B
3C
3D

FS application program
is not loaded
A pulse is testing DI and
DIF inputs configurator
More than 2 DIF modules
in the set layout
Pulse module entered,
but pulse number = FF
Operating system
version is invalid

3E
3F
40
41
42
.
.
.
4E
4F
50

51

2-104

Error in the configuration


for selective shutdown

Operating system error


DO outputs have not been
allocated a reaction type 12

Selective shutdown DB
is not read-only

F-B4

Remedy
Correct the output point in the
configurator
Reload the FS user program
Check the test pulse allocation
Check configurator, amend the set
configuration in the configurator
Check configuration or test pulse
allocation in the configurator
Use correct CPU-module,
program cannot be run on this PSS
Check configuration,
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Change PSS CPU
Check configuration
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Check configuration
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)

PSS-Range: Error List

F-B6

Error class F-B6 - Compiler error messages (processor C)


Error parameter:
Error location:
Error no.
01
.
.
.
27

Line number
Block

Description
Programming device error

PSS-Range: Error List

Remedy
Please contact Pilz.
Possibly use new programming
device (use latest PG version)

2-105

FS Error Messages

F-B7

Error class F-B7 - Program load error (processor C)


Error no.
01
.
.
.
04
05

Description
Communication/transfer
error on the programming
device or system error

Remedy
Reload user program and
transfer to the PSS
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)

Communication/transfer
error on the programming
device

Reload user program and


transfer to the PSS
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
To program the PSS, only use a
programming device suitable for
a PSS (not P10 PG)
Reload user program and
transfer to the PSS
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Clear memory (Flash-EPROM) ,
reload user program
If no remedy helps: reduce the size of
the user program
Reduce the number of blocks to max.
511

06

P 10 block was loaded

07

Programming device error

08

Memory range for


application program is full

09

Too many blocks have


been loaded

2-106

PSS-Range: Error List

F-B7

Error no.
0A
.
.
.
0E
0F
10

11
12
13

Description
PG transfer error

Remedy
Reload user program and
transfer to the PSS
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Adjacent CPU has detected an error See error stack
Memory range for user program
Clear memory (Flash-EPROM) ,
is full
reload user program
If no remedy helps: reduce the size of
the user program
Approved block is defective
Obtain the block from the original
disk, relink and transfer to the PSS
DB002 is not read only
Ensure DB 002 is read only

PSS-Range: Error List

2-107

FS Error Messages

F-B9

Error class F-B9 - Error in the PIO system error (processor C)


Error no.
00
.
.
.
07

2-108

Description

Remedy
Please contact Pilz

Major system error

PSS-Range: Error List

F-C2

Error class F-C2 - Test pulse error (processor C)


Error parameter:

Pulse number coded bit by bit

Error no.
01

Description

Error on PSS (1) DIO T

.
.
03

PSS-Range: Error List

Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module

2-109

FS Error Messages

F-C4

Error class F-C4 - Word module match error (processor C)


Error parameter:

Error no.
01
.
.
.
0D

2-110

Description
Word module error

High byte: Slot number


Low byte: Number of read segments
Remedy
1.)Tolerance has been set too low
2.) Incorrect alignment algorithm
(e.g. match instead min.- max.)
if there are no errors in the
configuration: change the module

PSS-Range: Error List

F-D0

Error class F-D0 - Information on selective shutdown


Error parameter:
Error location:
Error no.
01
02
03
04
05
06
07

Reaction type for deactivation


Signal group number

Description
Signal group deactivated,
error or deadman timer has elapsed
Deadman timer has elapsed
Error timer elapsed
Signal group has been
deactivated by the user
Signal group is to be deactivated
with the same reaction type
Signal group has been
deactivated by the user
Error timer for signal
group is disabled

PSS-Range: Error List

Remedy
For infomation only
For infomation only
For infomation only
For infomation only
For infomation only
For infomation only
For infomation only

2-111

FS Error Messages

F-D1

Error class F-D1 - Selective shutdown acknowledgement error


Error parameter:
Error location:
Error no.
01

2-112

Description
Acknowledgement error
during deactivation

Signal group number


Deactivation-OB
Remedy
Acknowledge deactivation in a
deactivation-OB

PSS-Range: Error List

F-D6

Error class F-D6 - SafetyBUS p bus interface


Error parameter:
Error location:

Device Address, Item (not on all errors)


Block (not on all errors)

Error no. Description

Remedy

00

SafetyBUS p: PIO cannot be written to


the decentralised outputs

Restart PSS
If message appears regularly: increase
FS and/or ST block run time, reduce
bus load.
If no remedy helps: contact Pilz.

01

SafetyBUS p: internal error

Please contact Pilz.

02

SafetyBUS p: decentralised inputs


unable to read PII

Restart PSS
If message appears regularly: increase
FS and/or ST block run time, reduce
bus load.
If no remedy helps: contact Pilz.

03

SafetyBUS p, error in stated block: the


command L PB cannot be executed

1.) Reduce the number of changes in


the input signal (possibly interference
on the inputs)
2.) Reduce bus load
If no remedy helps: change CPU
module/compact PSS.

04

SafetyBUS p, error in stated block: the


command L PW cannot be executed

1.) Reduce the number of changes in


the input signal (possibly interference
on the inputs)
2.) Reduce bus load
If no remedy helps: change CPU
module/compact PSS.

PSS-Range: Error List

2-113

FS Error Messages

F-D6

Error no. Description

Remedy

05

SafetyBUS p, error in stated block: the


command T PB cannot be executed

1.) Reduce the number of changes in


the output signal
2.) Reduce bus load
If no remedy helps: change CPU
module/compact PSS.

06

SafetyBUS p, error in stated block: the


command T PW kann nicht ausgefhrt
werden

1.) Reduce the number of changes in


the output signal
2.) Reduce bus load
If no remedy helps: change CPU
module/compact PSS.

07
08

SafetyBUS p: internal error

Change CPU module/compact PSS

09

SafetyBUS p: internal error

Please contact Pilz.

0B
0C

SafetyBUS p: internal error

Change CPU module/compact PSS

0E

SafetyBUS p: internal error

Please contact Pilz.

0F

SafetyBUS p: bus overload

Increase FS and/or ST block run time,


reduce bus load
If no remedy helps: contact Pilz.

10
11

SafetyBUS p: internal error

Change CPU module/compact PSS

12
.
.
15

SafetyBUS p: internal error

Please contact Pilz.

18

SafetyBUS p: internal error

Please contact Pilz.

19
1A

SafetyBUS p: internal error

Change CPU module/compact PSS

1B

SafetyBUS p: internal error

Please contact Pilz.

2-114

PSS-Range: Error List

F-D6

Error no. Description

Remedy

1C
.
.
1E

SafetyBUS p: internal error

Change CPU module/compact PSS

1F

SafetyBUS p: internal error

Please contact Pilz.

20

SafetyBUS p: internal error

Change CPU module/compact PSS

21

SafetyBUS p: internal error

Please contact Pilz.

22

SafetyBUS p can be restarted by


transferring PSS from STOP-RUN.

Message for information only

23
.
.
29

SafetyBUS p: internal error

Please contact Pilz.

2A

SafetyBUS p: internal error

Change CPU module/compact PSS

PSS-Range: Error List

2-115

FS Error Messages

Notes

2-116

PSS-Range: Error List

ST Error Messages

S-01

Error class S-01 - Hardware error


Error no.
01

Description
Error has occurred while
clearing the program cartridge

02
03

Error has occurred while


writing to the program cartridge

04

Real-time clock defective

PSS-Range: Error List

Remedy
Clear user program
If no remedy helps: if present, change
program cartridge, otherwise change
CPU module or PSS.
Clear user program
If no remedy helps: if present, change
program cartridge, otherwise change
CPU module or PSS.
Change CPU module

3-1

ST Error Messages

S-04

Error class S-04 - Battery error


Error-OB: OB 029
Error no.
01

3-2

Description
Battery is depleted

Remedy
Replace battery.
When replacing the battery, ensure
data is not lost. The PSS-CPU may
be powered down for a max. 5 min.,
before data is lost.

PSS-Range: Error List

S-05

Error class S-05 - Configuration error


Error parameter:
Error no.
01
02

Slot

Description
Module configuration error

PSS-Range: Error List

Remedy
1.) Is the correct module inserted?
2.) Using the programming device,
check the set/true configuration and
either change the module or adjust
the set layout to the true layout
If no remedy helps: change module.

3-3

ST Error Messages

S-06

Error class S-06 - Module error


Error parameter:
Error no.
01
.
.
.
04

3-4

Slot

Description
Error on expansion module

Remedy
Check supply voltage to the
expansion rack
If no remedy helps: change module.

PSS-Range: Error List

S-07

Error class S-07 - User program error


Error parameter:

Block ID

Error no.
01

Description
Error detected in at
least one block

02

End of the block table could not be


found
Unknown block ID found in block
table
Unknown block number found in
block table
Block has been loaded twice

03
04
05
06

Remedy
Clear defective block(s) and
reload: start program
If error message continues:
clear program cartridge and
download all blocks again
Clear all blocks and transfer again
Clear all blocks and transfer again
Clear all blocks and transfer again
Clear all blocks and transfer again

Clear all blocks and transfer again

09

Number of blocks found is


no longer correct
Valid program cartridge
does not exist
Program cartridge is not available

0A

Error found in user program

See entry in the error stack

07/08

PSS-Range: Error List

Clear all blocks and transfer again

Insert program cartridge

3-5

ST Error Messages

S-08

Error class S-08 - Program cartridge error


Error no.
04

Description
Program cartridge was removed

05

Incorrect programming
adapter plugged in
Incorrect program
cartridge type plugged in
No flash-program cartridge in
PSS programming adapter
PSS program cartridge is not valid

06
07
08
09

3-6

Error with the structure of the data


block table

Remedy
Insert program cartridge and
restart standard section
Use programming adapter
suitable for PSS
Use correct program cartridge
type
Insert flash-program cartridge into
PSS programming adapter
Program cartridge has been
formatted due to clearing
Program cartridge has been
formatted due to clearing

PSS-Range: Error List

S-0B

Error class S-0B - Power failure


Error no.
02

Description
Power supply(s) for expansion
rack not ready for operation in time
for the start of the program

03

Power failure on the expansion


module rack has been detected
during a cycle change

PSS-Range: Error List

Remedy
1.) Check power-LEDs for all power
supplies and switch on those that
are switched off
2.) Check mains voltage
If no remedy helps: change the PSS
standard power supply(s) on the
the expansion rack
1.) Check power-LEDs for all power
supplies and switch on those that
are switched off
2.) Check mains voltage
If no remedy helps: change the PSS
standard power supply(s) on the
the expansion rack

3-7

ST Error Messages

S-0C

Error class S-0C - Scan time exceeded


Error location: Block in which the scan time is exceeded
Error no.
01
02

Description
Scan time for the ST application
program has been exceeded

03

Scan time exceeded


OB 020/OB 022

3-8

Remedy
Search the ST application program
section which has caused the error
and optimise or accelerate the
program. The application program
may be caught in a loop
Optimise or accelerate the ST
application program

PSS-Range: Error List

S-0F

Error class S-0F - Addressable module error


Error parameter:

Low byte: Slot number with lower address


High byte: Slot number with higher address or
access address

Error no.
01

Description
There is no XW-module
at the given XW-address

04

Addressable module registers an


invalid address width
(XW module)
Address range of an addressable
module lies outside the permitted
address range
The number of addressable
modules is invalid
The address range for two
addressable modules overlap
Two addressable modules have
the same base address
Base address of an addressable
module is not a common multiple
of the assigned address range

05

06
07
09
0A

PSS-Range: Error List

Remedy
Check the configuration of XW
module with the configuration error
and correct if required or
check the ST user program
for incorrect access address and
corrrect if necessary.
If no remedy helps: change module
Please contact Pilz;
Possibly change the module
Check base address of the module
and correct in DB 005
Limit number of addressable
modules
Check base address of the module
and correct in DB 005
Check the base address for the
modules and correct in DB 005
Check base address of the modules
and correct in DB 005

3-9

S-10

ST Error Messages

Error class S-10 - Missing program cartridge


Error no.
01

3-10

Description
Program cartridge is missing

Remedy
Insert program cartridge

PSS-Range: Error List

S-20

Error class S-20 - Operating status messages


Error no.
01
02
13

Description
ST application program was started
ST application program was
stopped
Non-volatile data is invalid

14

Reset was carried out

PSS-Range: Error List

Remedy
For information only
For information only
PSS carries out a general reset and
all non-voltatile data is cleared
Change battery in power supply
For infomation only

3-11

S-21

ST Error Messages

Error class S-21 - Invalid operands in the application program


Error location: Block in which the invalid operand occurred
Low byte:
Block number
High byte:
Block type
Error no.
01
02
21
22
31
32

3-12

Description
Invalid operand with DEF-command
Invalid operand with DUF-command
Division by 0 during a byte
operation
Dividend too high during a byte
division command
Division by 0 during a word division
command
Dividend too high during a word
division command

Remedy
Rectify ST application program
Rectify ST application program
Rectify ST application program
Reduce dividend
Rectify ST application program
Reduce dividend

PSS-Range: Error List

S-22

Error class S-22 - Error accessing data blocks


Error parameter:
Error location:

Error no.
01

02

03

04

05

06

09

0A

0D

Number of the data block selected


Block in which the incorrect access occurred
Low Byte: Block number
High Byte: Block type

Description
Command "L DR": Data word lies
outside the current DB

Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Command "L DL": Data word lies
Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "T DR": Data word lies
Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "T DL": Data word lies
Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "AND DR": Data word
Check the length of the current DB,
lies outside the current DB
rectify ST application program
or set correct DB
Command "AND DL": Data word
Check the length of the current DB,
lies outside the current DB
rectify ST application program
or set correct DB
Command "OR DR": Data word lies Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "OR DL": Data word lies Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "XOR DR": Data word
Check the length of the current DB,
lies outside the current DB
rectify ST application program
or set correct DB

PSS-Range: Error List

3-13

ST Error Messages

Error no.
0E

Description
Command "XOR DL": Data word
lies outside the current DB

0F

Command "+ DR": Data word


lies outside the current DB

10

Command "+ DL": Data word


lies outside the current DB

11

Command "- DR": Data word


lies outside the current DB

12

Command "+ DL": Data word


lies outside the current DB

13

Command "* DR": Data word


lies outside the current DB

14

Command "* DL": Data word


lies outside the current DB

15

Command ": DR": Data word


lies outside the current DB

16

Command ": DL": Data word


lies outside the current DB

17

Command "I DR": Data word


lies outside the current DB

18

Command "I DL": Data word


lies outside the current DB

3-14

S-22

Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB

PSS-Range: Error List

S-22

Error no.
19

Description
Command "D DR": Data word
lies outside the current DB

1A

Command "D DL": Data word


lies outside the current DB

1B

Command "> DR": Data word


lies outside the current DB

1C

Command "> DL": Data word


lies outside the current DB

1F

Command "!= DR": Data word


lies outside the current DB

20

Command "!= DL": Data word


lies outside the current DB

23

Command "< DR": Data word


lies outside the current DB

24

Command "< DL": Data word


lies outside the current DB

30

Command "L DW": Data word


lies outside the current DB

31

Command "T DW": Data word


lies outside the current DB

32

Command "AND DW": Data word


lies outside the current DB

PSS-Range: Error List

Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB

3-15

ST Error Messages

Error no.
34

Description
Command "OR DW": Data word
lies outside the current DB

36

Command "XOR DW": Data word


lies outside the current DB

37

Command "+ DW": Data word


lies outside the current DB

38

Command "- DW": Data word


lies outside the current DB

39

Command "* DW": Data word


lies outside the current DB

3A

Command ": DW": Data word


lies outside the current DB

3B

Command "I DW": Data word


lies outside the current DB

3C

Command "D DW": Data word


lies outside the current DB

3D

Command "> DW": Data word


lies outside the current DB

3F

Command "!= DW": Data word


lies outside the current DB

41

Command "< DW": Data word


lies outside the current DB

3-16

S-22

Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB

PSS-Range: Error List

S-22

Error no.
51
52
53

Description
Actual parameter for DR
is invalid
Actual parameter for DL
is invalid
Command "T =para":
DR lies outside the current DB

54

Command "T =para":


DL lies outside the current DB

61

Actual parameter for DW


is invalid

62

Command "T =para":


Data word lies outside
the current DB
Command "I =para":
Data word lies outside
the current DB
Command "D =para":
Data word lies outside
the current DB
Command "A DB" is missing

63

64

65

PSS-Range: Error List

Remedy
Check actual parameter
rectify ST application program
Check actual parameter
rectify ST application program
Check length of current DB,
rectify ST application program
or set correct DB
Check length of current DB,
rectify ST application program
or set correct DB
Check the length of current DB,
rectify ST application program
or set correct DB
Check the length of current DB,
rectify ST user program
or set correct DB
Check the length of current DB,
rectify ST application program
or set correct DB
Check the length of current DB,
rectify ST application program
or set correct DB
Always select a DB with "A DB"
before the first data word access;
rectify ST application program

3-17

ST Error Messages

S-23

Error class S-23 - Error writing to a read-only data block


Error parameter:
Error location:

Error no.
01
02
03
04
05
06
11
12
13
21
31
32
33

3-18

Number of data block selected


Block in which the incorrect access occurred
Low byte: Block number
High byte: Block type

Description
Command "T DR":
transferring to read-only DB
Command "T DL":
transferring to read-only DB
Command "I DR":
access to read-only DB
Command "I DL":
access to read-only DB
Command "D DR":
access to read-only DB
Command "D DL":
access to read-only DB
Command "T DW":
access to read-only DB
Command "I DW":
access to read-only DB
Command "D DW":
access to read-only DB
Command "T =para":
byte access to read-only DB
Command "T =para":
word access to read-only DB
Command "I =para":
word access to read-only DB
Command "D =para":
word access to read-only DB

Remedy
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB

PSS-Range: Error List

S-24

Error class S-24 - Parameter addressing error


Error parameter:
Error location:

Error no.
01
02
03
13

16

17

18

21

22

23

Block ID for the call up block


Block ID for the block called up
Low byte: Block number
High byte: Block type

Description
Actual parameter (bit)
lies outside the permitted range
Actual parameter (byte)
lies outside the permitted range
Actual parameter (word)
lies outside the permitted range
Command "SE =para":
Actual parameter lies outside
the permitted range
Command "ZV =para":
Actual parameter lies outside
the permitted range
Command "ZR =para":
Actual parameter lies outside
the permitted range
Command "R =para":
Actual parameter lies outside
the permitted range
Command "T =para":
Byte-actual parameter lies outside
the permitted range
Command "I =para":
Byte-actual parameter lies outside
the permitted range
Command "D =para":
Byte-actual parameter lies outside
the permitted range

PSS-Range: Error List

Remedy
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program

3-19

ST Error Messages

Error no.
31

32

33

34

40

41

42

43
44

45

46
47
48

3-20

Description
Command "T =para":
Word-actual parameter lies outside
the permitted range
Command "I =para":
Word-actual parameter lies outside
the permitted range
Command "D =para":
Word-actual parameter lies outside
the permitted range
Command "A =para":
Actual parameter lies outside
the permitted range
Command "R =para":
Timer number lies outside
the permitted range
Command "R =para":
Counter number lies outside
the permitted range
Command "T =para":
Word-actual parameter lies outside
the permitted range
Command "S =para":
Bit-write access to a reserved range
Command "S =para":
Bit-write access to a
write-protected flag
Command "S =para":
Setting input bit is not permitted

S-24

Remedy
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program

Only output bit can be set,


check actual parameter and
rectify ST application program
Command "R =para":
Check actual parameter and
Bit-write access to a reserved range rectify ST application program
Command "T =para":
Check actual parameter and
Bit write access to a read-only flag rectify ST application program
Command "R =para":
Only output bit can be reset,
Resetting input bit is not permitted
check actual parameter and
rectify ST application program

PSS-Range: Error List

S-24

Error no.
49
4A
4B

4C

4D
4E

4F

50
51

52

53

54

Description
Command "T =para": Byte
write access to a reserved range
Command "T =para": Byte
write access to a read-only range
Command "T =para": Word
write access to a reserved range

Remedy
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program

Command "T =para": Word


write access to a read-only flag
range
Command "I =para": Byte
write access to a reserved range
Command "I =para": Byte
write access to a read-only flag
range
Command "I =para":
Incrementing input byte is not
permitted

Check actual parameter and


rectify ST application program

Command "D =para": Byte


write access to a reserved range
Command "D =para":
Byte write access to
read-only flag range
Command "D =para":
Decremeting input byte
is not permitted
Command "I =para":
Word-write access to
a reserved range
Command "I =para":
Word write access to a
read-only flag range

PSS-Range: Error List

Check actual parameter and


rectify ST application program
Check actual parameter and
rectify ST application program
Only an output byte can be
incremented, check actual
parameter and rectify ST application
program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Only an output byte can be
decremented, check actual
parameter and rectify
ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST user program

3-21

ST Error Messages

Error no.
55

Description
Command "I =para":
Incrementing input word
is not permitted

56

Command "D =para": Word


write access to a reserved range
Command "D =para": Word
write access to a read-only flag
range
Command "D =para":
Decrementing input word
is not permitted

57

58

59

5A

5B

5C

5D

5E

5F

3-22

Invalid contents in the actual


parameter of a bit-command
(S, =, =N, or =para)
Command "R =para":
Bit-actual parameter lies outside
the permitted range
Command "L =para":
XW-address on word module
lies outside the permitted range
Command "T =para":
XW-address on word module
lies outside the permitted range
Command "SE =para":
Incorrect timer address as
actual parameter
Command "ZR =para":
Incorrect counter address
as actual parameter
Command "ZV =para":
Incorrect counter address
as actual parameter

S-24

Remedy
Only an output word can be
decremented, check actual
parameter and rectify
ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Only an output word can be
decremented, check actual
parameter and rectify ST application
program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program

PSS-Range: Error List

S-24

Error no.
60

61

62

63

64

65

Description
Command "L =para":
Bit-actual address lies outside
the permitted range
Command "L =para":
Timer address lies outside
the permitted range
Command "L =para":
Counter address lies outside
the permitted range
Command "L =para":
Byte-actual address lies outside
the permitted range
Command "L =para":
Word-actual address lies outside
the permitted range
Command "L =para":
Counter address lies outside
the permitted range

PSS-Range: Error List

Remedy
Check bit-parameter and
rectify ST application program
Check bit actual parameter and
rectify ST application program
Check bit actual parameter for
rectify ST application program
Check byte parameter and
rectify ST application program
Check word parameter and
rectify ST application program
Check word actual parameter for
rectify ST application program

3-23

S-25

ST Error Messages

Error class S-25 - Indirect addressing error


Error parameter:
Error location:

Error no.
01

02

03

04

05

13

16

17

18

3-24

Flag in which the indirect address appears


Block in which the error occurred
Low byte: Block number
High byte: block type

Description
An indirect address of
a flag bit lies outside
the permitted range
An indirect address of
a input bit lies outside
the permitted range
An indirect address of
a output bit lies outside
the permitted range
An indirect address of
a timer bit lies outside
the permitted range
An indirect address of
a counter bit lies outside
the permitted range
Command "SE T(...)":
Indirect address of a timer lies
outside the permitted range
Command "ZV Z(...)":
Indirect address of a counter
lies outside the permitted range
Command "ZR Z(...)":
Indirect address of a counter
lies outside the permitted range
Command "R T(...)":
Indirect address of a timer
lies outside the permitted range

Remedy
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program

PSS-Range: Error List

S-25

Error no.
19

20

22

23

31

32

33

35

50

51

Description
Command "R Z(...)":
Indirect address of the counter
lies outside the permitted range
An indirect address of a flag byte
lies outside the permitted range

Remedy
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
An indirect address of an input byte Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of an output byte Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of a flag word
Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of an input word Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of an output
Check which indirect address is
word lies outside the permitted
incorrect and rectify the
range
ST application program
An indirect address for a counter
Check which indirect address
word lies outside the permitted
is incorrect for the counter word and
range
rectify the ST application program
Command "I MW(...)":
Check which indirect address
Indirect address for a flag
is incorrect for the flag word in the
word lies outside the permitted
increment command and rectify the
range
ST application program
Command "I AW(...)":
Check which indirect address
Indirect address for an output
is incorrect for the flag word in the
word lies outside the permitted
increment command and rectify the
range
ST application program

PSS-Range: Error List

3-25

ST Error Messages

Error no.
52

Description
Command "D MW(...)":
Indirect address for a flag word
lies outside the permitted range

53

Command "D AW(...)":


Indirect address for an output word
lies outside the permitted range

54

Command "D MW(...)":


Word-write access to read-only
flag range

55

Command "I MW(...)":


Word-write access to read-only
flag range

56

Indirect bit-write access


to read-only flags

57

Indirect byte-write access to a


a read-only flag

58

Indirect word-write access to a


a read-only flag

59

Command "L XW(...)":


Indirect address of an XW-module
lies outside the permitted range
Command "T XW(...)":
Indirect address of an XW-module
lies outside the permitted range

60

3-26

S-25

Remedy
Check which indirect address
is incorrect for the flag word in the
decrement command and rectify
the ST application program
Check which indirect address
is incorrect for the flag word in the
decrement command and rectify
the ST application program
Check which indirect address
is incorrect for the flag word in the
decrement command and rectify
the ST application program
Check which indirect address
is incorrect for the flag word in the
increment command and rectify
the ST application program
Check which indirect address is
incorrect and rectify ST application
program
Check which indirect address is
incorrect and rectify ST
application program
Check which indirect address is
incorrect and rectify ST
application program
Check which indirect address is
incorrect for the XW-module and
rectify the ST application program
Check which indirect address is
incorrect for the XW-module and
rectify the ST application program

PSS-Range: Error List

S-26

Error class S-26 - Block error


Error parameter:
Error location:

Block ID for missing block


Block which calls up the missing block

Error no.
01

Description
OB to be called up is not loaded.

03

PB to be called up is not loaded.

05

FB to be called up is not loaded.

07

SB to be called up is not loaded.

11

A selected DB does not exist.

12

A DB selected through
parameters does not exist.
An DB selected indirectly
does not exist.

13

PSS-Range: Error List

Remedy
Reload the OB or
remove the block call-up
Reload the PB or
remove the block call-up
Reload the FB or
remove the block call-up
Reload SB or
remove the block call-up
Reload DB or
remove block call-up
Reload DB or
remove block call-up
Reload DB or
remove block call-up

3-27

S-27

ST Error Messages

Error class S-27 - Parameter error


Error parameter:
Error location:
Error no.
02

06

3-28

Call up block
Block called up

Description
When "CAL FB" was called up,
the formal and actual parameters
do not match (type, number,
sequence)
When "CAL SB" was called up,
the formal and actual parameters
do not match (type, number,
sequence)

Remedy
Adapt call ups to suit the amended
block header

Adapt call ups to suit the amended


block header

PSS-Range: Error List

S-28

Error class S-28 - Block nesting error


Error location:
Error no.
01
03
05
07

Block in which the error has occurred

Description
Nesting level exceeded
by starting an OB (CAL OB)
Nesting level exceeded
by stating a PB (CAL PB)
Nesting level exceeded
by starting an FB (CAL FB)
Nesting level exceeded
by starting an SB (CAL SB)

PSS-Range: Error List

Remedy
Check the block nesting levels
Reduce the block nesting levels
Check the block nesting levels
Reduce the block nesting levels
Check the block nesting levels
Reduce the block nesting levels
Check the block nesting levels
Reduce the block nesting levels

3-29

ST Error Messages

S-2A

Error class S-2A - Timer error


Error parameter:
Error location:

Error no.
01

3-30

Timer number
Block in which the timer is used
Low byte: Block number
High byte: Block type

Description
A timer was started with a
negative value entered in the
accumulator

Remedy
Load a positive value into the
accumulator before the SEcommand

PSS-Range: Error List

S-76

Error class S-76 - Compiler error messages


Error parameter:
Error location:

Line number
BLock ID
Low byte: Block number
High byte: Block type

Error no.
01

Description
Undefinedcode

02

Undefined parameters

03

Input address is invalid

04

Output address is invalid

05

Flag address is invalid

06

Input byte address is invalid

07

Output byte address is invalid

PSS-Range: Error List

Remedy
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz

3-31

ST Error Messages

Error no.
08

Description
Flag byte address is invalid

09

Input word address is invalid

0A

Output word address is invalid

0B

PW address is invalid

0C

XW-addresses are invalid

0D

Flag word address is invalid

0E
0F

Address indicator for indirect


addressing is invalid
Flag (byte or word) is read-only

11

Segment number is invalid

3-32

S-76

Remedy
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz

PSS-Range: Error List

S-76

Error no.
12

Description
Data block is invalid

13

Undefined parameters

14

16

Too many parameters


with block call up
Internal compiler error while
calculating the target address
for a jump
Segment is not available

17

Undefined time base

18

Undefined timer number

19

Undefined counter number

1A

BE-command is missing

15

PSS-Range: Error List

Remedy
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz

3-33

ST Error Messages

Error no.
1B
1C
1D
1E
1F

Description
Undefined operating
system call up
Link table overflow
Overflow of the execite code
buffer for the ST processor
Too many jumps in the block

24

Max. possible number of open


brackets has been reached
")"-command, although no more
brackets are open
Command cannot be used within
bracketed expression
Undefined program block
called up
Parameter size is not
bit, byte or word
PB address is invalid

7F

Command not implemented

20
21
22
23

3-34

S-76

Remedy
Remove operating system call-up
from the application program
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Reduce number of jumps
Reduce number of bracket
commands "("
Remove ")"-command
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz

PSS-Range: Error List

S-77

Error class S-77 - Program load error


Error parameter:
Error no.
01
02

03
04

Block ID

Description
Too many blocks have been loaded
into the program cartridge
Block length in the block header
does not match the number in the
the data transferred
Block is not an ST block

07

The DB has a reserved


DB-number which may
not be loaded
DB 004 or DB 005 does not match
its set length
CRC-checksum for the
block is incorrect
ST user program memory is full

08

Operating system call up is invalid

09

OB, FB or PB created
in assembler code
Read/Write DB-range is full

05
06

0A

PSS-Range: Error List

Remedy
Reduce the number of blocks in
the program
Transfer the block again
If no remedy helps: contact Pilz
Create block with ST programming
device and re-send
Rename DB,
create block with ST programming
device and re-send
Set DB to correct length
Remove the interferences from the
transfer cable and re-send
Clear program cartridge and transfer
project once more; possibly reduce
the application program or use
a larger program cartridge
Please contact Pilz.
Create block in PSS code
Reduce the number of read/write
DBs

3-35

ST Error Messages

S-80

Error class S-80 - Fatal error


Error parameter:
Error no.
01

3-36

Fatal error number

Description
ST section has detected a fatal
error in the operating system

Remedy
Please contact Pilz

PSS-Range: Error List

S-81

Error class S-81 - Operating system call up error


Error class
S-81
01

Error no. Description

Remedy

ST application program
transferred an invalid parameter to
SB 254

Rectify ST application program

PSS-Range: Error List

3-37

ST Error Messages

S-83

Error class S-83 - Debug error


Error parameter:
Error no.
01

02

03

3-38

Status of start-up manager

Description
A module called up by the start-up
the start-up manager never issues
ready signal
A module called up by the start-up
manager does not keep to the
time conditions
The start-up manager was offset
to an invalid status

Remedy
Increase ST-block run time
If no remedy helps: contact Pilz
Increase ST block run time
If no remedy helps: contact Pilz
Please contact Pilz

PSS-Range: Error List

SafetyBUS p Error Messages

This chapter describes SafetyBUS p errors. Errors can occur in individual


bus subscribers as well as on the bus system as a whole. The error
parameter will indicate on which bus subscriber the error has occurred.
The error description for the device error (bus subscriber) is stored in the
local error stack for the device and must be read using the PG. Device
errors are described in the chapter entitled Error Messages on
Decentralised Modules.
Up to two parameters are assigned to each device error. The parameters
contain the error location. Two error locations can be displayed, for example,
in error class 31, error number 0: a device address and an I/O-Group
number. In this example the device address in parameter 2 determines the
device which caused the I/O-Group stated in parameter 1 to STOP. If only
one parameter is required to locate an error, it is the second parameter that
is used. The first parameter remains unused. In addition, there are errors
which are managed without parameters. Please note, if you are displaying
errors on the CPU-display, always display both parameters using the error
stack button.

PSS-Range: Error List

4-1

SafetyBUS p Error Messages

F-30

Error class F-30 User stop


Error no. Error parameter

Description

Remedy

00

I/O-GroupNo.Device-Adr.

Stop via user program or


operating the FS selector
switch RUN/STOP

01

I/O Group stopped due to too


many alarms

In the user program reduce the


number of alarms to be
processed

4-2

PSS-Range: Error List

F-31

Error class F-31 Internal error


Error no. Error parameter

Description

Remedy

00

I/O-Group-No.
Device-Adr.

MD, LD or I/O D caused a


STOP of the given I/O-Group

Display error stack of the


Device in the PG, see error
description for the device

01

I/O-Group-No.
Device-Adr.

Error in the LD (PSS caused all Display PSS error stack, see
assigned I/O-Groups to STOP) PSS FS error messages for
error description

02

System error no. Internal system error in LD


Device-Adr.
(PSS)

Change PSS or PSS CPU

03

System error no. Internal system error in LD


Device-Adr.
(PSS)

Change PSS or PSS CPU

04

05

System error no. Internal system error in LD


Device-Adr
(PSS)

06

Not assigned

07

Not assigned

08

Item No.* 1
Device-Adr.

Write access via indirect or


parameterised address on a
non-configured Device-Adr.

09

System error no. Domain request from an


Device-Adr.
address that is not configured
or invalid

0A

System error no. Domain-transfer to LD which is Check parameter in call up of


Device-Adr.
not a master or is an invalid
SB 255,
address range
permitted addresses: 32
95

0B
.
.
0C

*1

Not assigned
Change PSS or PSS CPU

Check addressing in the user


program
Check parameter in call up of
SB 255,
permitted addresses: 32
95

Internal system error


Contact Pilz technical support

0: I/OD A, 1: I/OD B

PSS-Range: Error List

4-3

F-31

SafetyBUS p Error Messages

Error no. Error parameter

Description

Remedy

0D

Error in LD (PSS)

Display previous entry in the


PSS error stack, see PSS FS
error messages

4-4

PSS-Range: Error List

F-32

Error class F-32 Periphery error


Error no. Error parameter

Description

Remedy

00

MD, LD or I/O D caused a


STOP of the given I/O-Group

Display error stack of the


device in the PG, see error
description for the device

I/O-Group-No.
Device-Adr.

PSS-Range: Error List

4-5

SafetyBUS p Error Messages

F-33

Error class F-33 Bus error


Error no. Error parameter

Description

Remedy

00

I/O-Group-No.
Device-Adr.

MD, or I/O D caused a STOP


of the given I/O-Group

Display error stack of the


Device in the PG, see error
description for the device

01

Device-Adr.

No message from the LD as


Cycle-Timeout is too short or
there is an error in the LD
(PSS)

Change Cycle-Timeout in the


configurator or display the
PSS error stack, see PSS
FS-error messages

02

Device-Adr.

No message from the LD or


I/OD, as Cycle-Timeout is too
short or there is an error in the
device

Change Cycle-Timeout in the


configurator or display the
PSS error stack, see PSS FS
error messages or device
error messages

03

Device-Adr.

Unknown or defective device on Display device error stack,


the bus
see device error messages or
remove the unit from the bus

04

Device-Adr.

Unknown or defective device on Display device error stack,


the bus
see device error messages or
remove the unit from the bus

05

Device-Adr

Internal system error

Change PSS or PSS CPU

06

Item No.* 1
Device-Adr.

No message from the LD or


I/OD as the Event-Timeout is
too short or there us an error in
the device

Change Event-Timeout in the


configurator or display the
PSS error stack, see PSS FS
error messages or device
error messages

07

Device-Adr.

Internal system error

Change PSS or PSS CPU

*1
4-6

0: I/OD A, : I/OD B

PSS-Range: Error List

F-33

Error no. Error parameter

Description

08

I/O-Group-No.
Device-Adr.

Domain-Timeout from the LD or Change Domain-Timeout in


I/OD too short or an error in the the configurator or display the
device
device error stack, see device
error messages

09

I/O-Group-No.
Device-Adr.

Domain-Timeout from the LD or Change Domain-Timeout in


I/OD too short or an error in the the configurator or display the
Device
device error stack, see device
error messages

0A

Domain No.
Device-Adr.

Domain-Timeout from the LD or Change Domain-Timeout in


I/OD too short or an error in the the configurator or display the
Device
device error stack, see device
error messages

0B

Domain No.
Device-Adr.

Domain-Timeout from the LD or Change Domain-Timeout in


I/OD too short or an error in the the configurator or display the
Device
device error stack, see device
error messages

0C

Device-Adr

Error in the LD

Display device error stack,


see device error messages.

0D

Device-Adr

Error in the MD

Display device error stack,


see device error messages

0E

Device-Adr

LD (PSS) cannot send

Check whether: Short-circuit


on the bus cable, correct
termination, unknown device
on the bus; if no remedy helps
Change PSS

0F

-Device-Adr

2 MDs on the bus

Only one MD permitted.


Configure 2nd MD as LD

10

Device-Adr

2 LDs on the bus have the


same address

Change address of the given


LD or remove LD from the
bus.

PSS-Range: Error List

Remedy

4-7

F-33

SafetyBUS p Error Messages

Error no. Error parameter

Description

Remedy

11

Device-Adr.

Error when transferring a


project

Check configuration, delete


the PSS program memory,
transfer user program, if no
remedy helps: change PSS or
PSS CPU

12

Device-Adr.

Domain-Timeout of the MD
(PSS) too short or an error in
the MD (PSS)

Increase Domain-Timeout in
the configurator or display the
PSS error stack, see PSS
FS-error messages

13

Device-Adr.

Bus configuration in the LD


does not correspond with the
configuration of the MD

Change configuration, delete


PSS program memory,
transfer user program

Device-Adr.

Internal system error

Change PSS.

21

Not assigned

22

Device-Adr.

2 LDs or I/ODs on the bus have Display device error stack or


the same address
disconnect the device

Device-Adr.

Internal system error

14
.
.
.
20

23
.
.
.
25
26

4-8

Device-Adr.

Change PSS

Bus configuration is incorrect or Check configuration, delete


the MD or LD is defective
the PSS program memory,
transfer user program, if no
remedy helps: change the
PSS or PSS CPU

PSS-Range: Error List

F-33

Error no. Error parameter

Description

Remedy

27
.
.
.
29

Too many PSS systems


switched on simultaneously or
an internal system error

Switch on PSS sytems


consecutively or before the
start of the program, initialise
a group start once only (with
LD FE, with MD FF); if
there is no remedy:
change PSS or PSS CPU

2A

2B
.
.
.
30

Device-Adr.

Device-Adr.

Device-Adr.

Bus configuration is incorrect or Check configuration, delete


the PSS program memory,
the MD or LD is defective
transfer user program, if no
remedy helps: change PSS or
PSS CPU
Check configuration, delete
Error when transferring a project the PSS program memory,
in the LD
transfer user program, if no
remedy helps: change PSS or
PSS CPU

31

Device-Adr.

Internal system error

Change PSS or PSS CPU

32

Device-Adr.

I/O-Group configuration is
incorrect or the LD is defective

Check configuration, delete


the PSS program memory,
transfer user program, if no
remedy helps: change PSS or
PSS CPU

33

Device-Adr.

Internal system error

Change PSS or PSS CPU

34

Not assigned

35

Device-Adr.

Internal system error

36

Not assigned

37

Not assigned

38

Device-Adr.

Internal system error

PSS-Range: Error List

Change PSS or PSS CPU

Change PSS or PSS CPU

4-9

SafetyBUS p Error Messages

Error no. Error parameter

Description

F-33

Remedy

39

Device-Adr.

Telegram has not transferred


or internal system error

3A

Device-Adr.

LD or I/OD are no longer on the Read from the device error


stack; if no remedy helps:
bus or are defective
change the device

3B

Device-Adr.

2 LDs or I/ODs on the bus have Display device error stack or


the same address
remove the device from the
bus.

3C
.
.
.
44

Device-Adr.

45
Device-Adr.

46
.
.
.
4C

Device-Adr.

Repeat group start, read from


the device error stack, if no
remedy helps: change the
device

Internal system error

Change PSS or PSS CPU

MD configured incorrectly or is
defective

Check configuration, delete


the PSS program memory,
transfer user program, if no
remedy helps: change PSS or
PSS CPU

Internal system error

Change PSS or PSS CPU

Display PSS error stack, see


PSS FS error messages

4D

I/O-Group-No.
Device-Adr.

Error in the MD

4E
4F

I/O-Group-No.
Device Adr.

Several devices are on the bus Remove all the devices from
without a device addresss
the bus, connect one device
and establish the address;
then connect the next one,
establish the address etc.

4-10

PSS-Range: Error List

F-33

Error no. Error parameter


50
.
.
.
58

Domain-No.
Device-Adr.

PSS-Range: Error List

Error parameter

Remedy

Unknown or defective device


on the bus

Display the device error stack,


see the error messages or
remove the device from the
bus

4-11

SafetyBUS p Error Messages

Error class F-34 - Configuration error


Error no. Error parameter

Description

00

Not assigned

01
.
.
.
03

Check configuration, delete


Error during program transfer or the PSS program memory,
transfer user program, if no
program memory is defective
remedy helps: change PSS or
PSS CPU

04

Not assigned

05

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if no
remedy helps: change PSS or
PSS CPU

06

Not assigned

07
.
.
.
0D

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if no
remedy helps: change PSS or
PSS CPU

0E
.
.
.
0F

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if no
remedy helps: change PSS or
PSS CPU

10

Not assigned

11

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if no
remedy helps: change PSS or
PSS CPU

4-12

Remedy

PSS-Range: Error List

F-34

Error no. Error parameter

Description

12
.
.
.
1C

Not assigned

1D

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if
remedy does not help: change
PSS or PSS CPU

1E
.
.
.
2F
30
.
.
.
35

Remedy

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if
remedy does not help: change
PSS or PSS CPU

Error during program transfer

Delete PSS program memory,


transfer user program; if
remedy does not help; change
PSS or PSS CPU

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if
remedy does not help: change
PSS or PSS CPU

46
.
.
.
48

Error during program transfer


or program memory is
defective

Check configuration, delete


the PSS program memory,
transfer user program, if
remedy does not help: change
PSS or PSS CPU

49

Internal system error

Change PSS or PSS CPU

36
.
.
.
45

PSS-Range: Error List

4-13

SafetyBUS p Error Messages

F-34

Error no. Error parameter

Description

4A
.
.
.
4B

Check configuration, delete


Error during program transfer or the PSS program memory,
program memory is defective
transfer user program, if
remedy does not help: change
PSS or PSS CPU

Rectify Timeout-values, delete


PSS program memory,
transfer user program; if
remedy does not help; change
the device

4C
.
.
.
4F
50

Timeout values are incorrect

Transfer rate is not permitted


-

Remedy

Rectify transfer rate, delete


PSS program memory,
transfer user program; if
remedy does not help; change
the device

51

52
.
.
.
5B

5C

Error during program transfer or Check and rectify


program memory is defective
configuration, delete the PSS
program memory, transfer
user program, if remedy does
not help: change PSS or PSS
CPU

5D

Device-Adr.
Bus version no.

Device does not support a


transfer rate of 500 kBit

4-14

Error during program transfer or Check and rectify


program memory is defective
configuration, delete the PSS
program memory, transfer
user program, if remedy does
not help: change PSS or PSS
CPU
Error during program transfer

Delete PSS program


memory, transfer user
program; if remedy does not
help; change PSS or PSS
CPU

Change the device (for


permitted transfer rates, refer
to the device's operating
manual

PSS-Range: Error List

Error Messages on Decentr. Modules

This chapter describes the error messages on the decentralised modules,


e.g. PSS SB DI8O8 and PSS SB DI16. The error messages can be read
via a PSS using the PG.
Most errors contain error parameters that can be used to locate the error.
These parameters can be displayed using the error display in the PG.
Many of these parameters have no relevance to you the user. However,
they help Pilz engineers to determine the cause of the error. If you require
support from Pilz or need to send the device back to rectify the error,
please quote the error parameter(s).

PSS-Range: Error List

5-1

Error Messages on Decentr. Modules

F-01

Error class F-01


Error no. Description

Remedy

00
.
.
.
04

Internal error

Please contact Pilz.

0A

Internal error

Please contact Pilz.

0C
.
.
.
10

Internal error

Please contact Pilz.

12
.
.
.
14

Internal error

Please contact Pilz.

5-2

PSS-Range: Error List

F-02

Error class F-02


Error no. Description

Remedy

00
.
.
.
05

Internal error

Please contact Pilz.

09
.
.
.
18

Internal error

Please contact Pilz.

PSS-Range: Error List

5-3

Error Messages on Decentr. Modules

F-03

Error class F-03


Error no. Description

Remedy

00
.
.
.
05

Internal error

Please contact Pilz.

06

Internal error

Change device.

07

Internal error

Please contact Pilz.

08
.
.
.
0A

Internal error

Change device.

0B

Internal error

Please contact Pilz.

0D
.
.
.
0E

Internal error

Please contact Pilz.

5-4

PSS-Range: Error List

F-04

Error class F-04


Error no. Description

Remedy

00

Memory defective

Please contact Pilz.

03

Internal error

Change device.

04

EEPROM defective

Change device.

05

Internal error

Change device.

0A

Internal error

Change device.

0B

EEPROM defective

Change device.

PSS-Range: Error List

5-5

Error Messages on Decentr. Modules

F-05

Error class F-05


Error no. Description

Remedy

00
.
.
.
01

Internal error

Please contact Pilz.

03
:
.
.
04

Internal error

Please contact Pilz.

5-6

PSS-Range: Error List

F-06

Error class F-06


Error no. Description

Remedy

00

Internal error

Change device

01

Internal error

Please contact Pilz.

02
.
.
.
03

Internal error

Change device.

04

Noise due to voltage swings.

Check earth connection; check supply voltage


Supply and supply voltage for the load Load
Supply

05

Internal error

Please contact Pilz.

PSS-Range: Error List

5-7

Error Messages on Decentr. Modules

F-07

Error class F-07


Error no. Description

Remedy

01

Internal error

Change device.

0D
.
.
.
0E

Internal error

Change device.

5-8

PSS-Range: Error List

F-08

Error class F-08


Error no. Description

Remedy

00

Device switched on

Message is shown only for information.

01

Internal error

Change device.

05

Internal error

Change device.

06

Internal error

Please contact Pilz.

09

Device switched on

Message is shown only for information.

PSS-Range: Error List

5-9

Error Messages on Decentr. Modules

F-10

Error class F-10


Error no. Description

Remedy

01
.
.
.
02

Internal error

Please contact Pilz.

04
.
.
.
06

Internal error

Please contact Pilz.

07

Unable to establish the current Check bus cabling: all specifications in the
transmission rate
SafetyBUS p Installation Manual must be
fulfilled.
If no remedy helps: contact Pilz.

08

Internal error

5-10

Please contact Pilz.

PSS-Range: Error List

F-11

Error class F-11


Error no. Description

Remedy

00
.
.
.
01

Please contact Pilz.

Internal error

PSS-Range: Error List

5-11

Error Messages on Decentr. Modules

F-12

Error class F-12


Error no. Description

Remedy

00

Domain-Timeout

Check and rectify the time entered for the


Domain-Timeout in the configuration, clear the
program memory and reload the application
program.
If no remedy helps: contact Pilz.

01

Stated I/O-Group is configured Check and rectify the I/O-Group configuration,


incorrectly
clear the program memory and reload the
application program.
If no remedy helps: contact Pilz.

02
.
.
.
03

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

04

Cycle-Timeout because bus


connection interrupted, LD for
I/O-Group no longer available
or bus overloaded

Check and rectify the time entered for the


Cycle-Timeout in the configuration, clear the
program memory and reload the application
program. If necessary, reduce the bus load.
If no remedy helps: contact Pilz.

05

Bus error

If message appears frequently: contact Pilz.

06
.
.
.
07

I/O-Group was stopped via the Evaluate error stack of the stated device.
stated Device

5-12

PSS-Range: Error List

F-12

Error no. Description

Remedy

08

Cycle-Timeout because bus


connection interrupted, MD no
longer available or bus
overloaded

Check and rectify the time entered for the


Cycle-Timeout in the configuration, clear the
program memory and reload the application
program. If necessary, reduce the bus load.
If no remedy helps: contact Pilz.

09

Bus error

Please contact Pilz.

0A

Domain-Timeout

Check and rectify the time entered for the


Domain-Timeout in the configuration, clear the
program memory and reload the application
program.
If no remedy helps: contact Pilz.

0B

Event-Timeout

Check and rectify the time entered for the


Event-Timeout in the configuration, clear the
program memory and reload the application
program.
If no remedy helps: contact Pilz.

0C

The Device-Address of this


Device is also being used by
another Device

Check bus cabling; check whether the address


setting on the devices matches the address
configuration. If no remedy helps: contact Pilz.

0D

Bus error

If message appears frequently: contact Pilz.

0E

Stated I/O-Group is configured Check and rectify the I/O-Group configuration,


incorrectly
clear the program memory and reload the
application program.
If no remedy helps: contact Pilz.

0F

The stated I/O-Groups were


Evaluate error stack of the stated device.
stopped via the stated Device.

10

Bus error

PSS-Range: Error List

If message appears frequently: contact Pilz.

5-13

Error Messages on Decentr. Modules

F-13

Error class F-13


Error no. Description

Remedy

00

Please contact Pilz.

5-14

Internal error

PSS-Range: Error List

F-14

Error class F-14


Error no. Description

Remedy

00

Too many telegrams received. If message appears frequently: Reduce bus


load.

01

Telegram lost because bus


load is too high

PSS-Range: Error List

If message appears frequently: Reduce bus


load.

5-15

Error Messages on Decentr. Modules

F-15

Error class F-15


Error no. Description

Remedy

00

Change device.

01
.
.
.
05
06

5-16

Internal error

Telegram traffic is disrupted

Device-Address was altered


during operation.

Check bus cabling: all specifications in the


SafetyBUS p Installation Manual must be
fulfilled.
If no remedy helps: contact Pilz.
If this message appears frequently, even
though the Device-Address has not been
changed manually: Change device.

PSS-Range: Error List

F-50

Error class F-50


Error no. Description

Remedy

01
.
.
.
06

Please contact Pilz.

Internal error

07
.
.
.
08

Incorrect configuration data

0A
.
.
.
0B

Internal error

Please contact Pilz.

0D

Internal error

Please contact Pilz.

0F

Internal error

Please contact Pilz.

16

Internal error

Please contact Pilz.

18
.
.
.
19

Internal error

Please contact Pilz.

1C

Incorrect configuration data

Check and rectify configuration, clear the


program memory and reload the application
program.
If no remedy helps: contact Pilz.

1D
.
.
.
20

Internal error

Please contact Pilz.

PSS-Range: Error List

Check and rectify configuration, clear the


program memory and reload the application
program.
If no remedy helps: contact Pilz.

5-17

Error Messages on Decentr. Modules

Error no. Description

F-50

Remedy

21

Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.

22
.
.
.
.
23

Incorrect configuration data

24

Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.

5-18

PSS-Range: Error List

Check and rectify the device type and version


in the configuration, clear the program memory
and reload the application program.
If no remedy helps: contact Pilz.

F-51

Error class F-51


Error no. Description

Remedy

01

Internal communication error

Reduce the changes in process data (PIO).


If no remedy helps: contact the device
manufacturer.

02

Internal communication error

Please contact the device manufacturer.

04

Internal communication error

Reduce the changes in process data (PIO/PII).


If no remedy helps: contact the device
manufacturer.

05
.
.
.
06

Internal communication error

Please contact the device manufacturer.

08
.
.
.
09

Internal communication error

Please contact the device manufacturer.

0C

Internal communication error

Please contact the device manufacturer.

10
.
.
.
.
11

Incorrect configuration data

Check and rectify the device type and version


in the configuration, clear the program memory
and reload the application program.
If no remedy helps: contact Pilz.

Internal communication error

Please contact the device manufacturer.

12
.
.
.
1B

PSS-Range: Error List

5-19

Error Messages on Decentr. Modules

F-51

Error no. Description

Remedy

1C

Internal communication error

Reduce the changes in process data (PIO).


If no remedy helps: contact the device
manufacturer.

1D
.
.
.
1E

Internal communication error

Please contact the device manufacturer.

1F

Internal error

Please contact Pilz.

20
.
.
.
22

Internal communication error

Please contact the device manufacturer.

24

Incorrect configuration data

Check and rectify the device type and version


in the configuration, clear the program memory
and reload the application program.
If no remedy helps: contact Pilz.

25
.
.
.
26

Internal communication error

Please contact the device manufacturer.

27

Internal communication error

Reduce the changes in process data (PII).


If no remedy helps: contact the device
manufacturer.

28
.
.
.
2A

Internal communication error

Please contact the device manufacturer.

5-20

PSS-Range: Error List

F-52, F-53, F-54

Error class F-52, F-53, F-54


Errors of this class should be documented in the devices operating
manual. If this is not the case, please contact the device manufacturer.

PSS-Range: Error List

5-21

F-55

Error Messages on Decentr. Modules

Error class F-55


Error no. Description

Remedy

00

I/O-Group was started.

Message is shown only for information.

01

Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.

02

Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.

03

Internal error

5-22

Change device

PSS-Range: Error List

F-60

Error class F-60


Error no. Description

Remedy

00
.
.
.
06

Please contact Pilz.

Internal error

PSS-Range: Error List

5-23

Error Messages on Decentr. Modules

F-61

Error class F-61


Error no. Description

Remedy

00
.
.
.
01

Change device.

5-24

Internal error

PSS-Range: Error List

F-62

Error class F-62


Error no. Description

Remedy

00
.
.
.
03

Please contact Pilz.

Internal error

PSS-Range: Error List

5-25

Error Messages on Decentr. Modules

F-63

Error class F-63


Error no. Description

Remedy

00

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

02

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

03

Incorrect application program. Check and rectify application program, clear


There was an attempt to
program memory and reload application
access non-existing outputs.
program.

04

Incorrect application program. Insert standard function block SB250.


Written to outputs in the stated
I/O group, although the I/Ogroup on the other end of the
Bridge is in a STOP condition.

05

Incorrect application program. Insert standard function block SB250.


Written to the stated Bit
(14,15, 30 or 31), although this
Bit is reserved.

06

Internal error

07

Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.

08

Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.

5-26

PSS-Range: Error List

Please contact Pilz.

F-64

Error class F-64


Error no. Description

Remedy

00

Error while testing inputs with


test pulses.

Check inputs/outputs for short circuits; check


connection between inputs and test pulses.
If no remedy helps: Change device.

01

Status of output is not as


expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

02

Status of output during output


test is not as expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

03

I/O-Group warm start is not


possible due to a previous
major output error

Check inputs/outputs for short circuits; check


connection between inputs and test pulses;
switch voltage to Device off/on.
If no remedy helps: Change device.

04

Error while testing inputs with


test pulses.

Check inputs/outputs for short circuits; check


connection between inputs and test pulses.
If no remedy helps: Change device.

05

Status of output is not as


expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

06

Status of output during output


test is not as expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

PSS-Range: Error List

5-27

Error Messages on Decentr. Modules

F-65

Error class F-65


Error no. Description

Remedy

00
.
.
.
12

Change device.

5-28

Internal error

PSS-Range: Error List

F-66

Error class F-66


Error no. Description

Remedy

00
.
.
.
03

Internal error

Please contact Pilz.

04

Internal error

Change device.

05
.
.
.
07

Internal error

Please contact Pilz.

0A
.
.
.
0D

Internal error

Please contact Pilz.

PSS-Range: Error List

5-29

Error Messages on Decentr. Modules

F-67

Error class F-67


Error no. Description
00
.
.
.
01

5-30

Load supply is missing

Remedy

Check earth connection; check load supply


voltage.

PSS-Range: Error List

F-68

Error class F-68


Error no. Description

Remedy

00
.
.
.
01

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

02

Overflow of the telegram


buffer.
The changes in signal status
on the opposite end of the
Bridge cannot be processed
quickly enough.

1.) Reduce difference in transmission rates of


both SafetyBUS p networks.
2.) Reduce number of signal status changes
at the opposite end of the bridge.
3.) Signals on which the status changes
frequently should be distributed evenly on
I/OD A and I/OD B.
4.) Increase bus speed in the network on this
end of the bridge: Increase transmission rate,
increase value for the Cycle-Timeout or
reduce the bus load.
5.) Assign this end of the Bridge a lower
Device-Address (telegrams from the Bridge
will then have a higher priority).

03

Overflow of the telegram


buffer.
Signal status at the inputs
changes too often.

1.) Reduce number of signal status changes


at the inputs.
2.) Signals on which the status changes
frequently should be distributed evenly on
I/OD A and I/OD B.
3.) Increase bus speed: Increase transmission
rate, increase value for the Cycle-Timeout or
reduce the bus load.
4.) Assign the Device a lower Device-Address
(telegrams from the Device will then have a
higher priority).

PSS-Range: Error List

5-31

Error Messages on Decentr. Modules

F-68

Error no. Description

Remedy

04

1.) Reduce difference in transmission rates of


both SafetyBUS p networks.
2.) Reduce number of signal status changes
on this end of the bridge.
3.) Signals on which the status changes
frequently should be distributed evenly on
I/OD A and I/OD B.
4.) Increase bus speed in the network on the
opposite end of the bridge: Increase
transmission rate, increase value for the
Cycle-Timeout or reduce the bus load.
5.) Assign the opposite end of the Bridge a
lower Device-Address (telegrams from the
Bridge will then have a higher priority).

5-32

Overflow of the telegram


buffer.
The changes in signal status
on this end of the Bridge
cannot be processed quickly
enough.

PSS-Range: Error List

F-69

Error class F-69


Error no. Description

Remedy

00

I/O-Group was started.

Message is shown only for information.

01

Bridge communication error

Evaluate the error stack on the opposite end


of the bridge.
If no remedy helps: Change device.

02

Internal error

Change device

03

I/O-group has been stopped


Restart I/O group
because the I/O-group on the
opposite end of the bridge was
stopped.

04

Different number of I/O-groups Amend configuration, clear program memory


and reload the application program.
on the opposite end of the
bridge

05

Value for Event Timeout is too Amend the time entered for the Event-Timeout
in the configuration to > 10 ms, clear the
low.
program memory and reload the application
program.

06

Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.

PSS-Range: Error List

5-33

Error Messages on Decentr. Modules

F-81

Error class F-81


Error no. Description

Remedy

00
.
.
.
09

Internal error

Please contact Pilz.

13
.
.
.
14

Internal error

Please contact Pilz.

5-34

PSS-Range: Error List

F-82

Error class F-82


Error no. Description

Remedy

00
.
.
.
08

Internal error

Please contact Pilz.

15

Internal error

Please contact Pilz.

19
.
.
.
1A

Internal error

Please contact Pilz.

PSS-Range: Error List

5-35

Error Messages on Decentr. Modules

F-83

Error class F-83


Error no. Description

Remedy

00
.
.
.
05

Internal error

Please contact Pilz.

06

Internal error

Change device.

0C
.
.
.
10

Internal error

Please contact Pilz.

5-36

PSS-Range: Error List

F-84

Error class F-84


Error no. Description

Remedy

00

Memory defective

Please contact Pilz.

01
.
.
.
02

Internal error

Change device.

05

Internal error

Change device.

PSS-Range: Error List

5-37

Error Messages on Decentr. Modules

F-85

Error class F-85


Error no. Description

Remedy

00
.
.
.
02

Please contact Pilz.

5-38

Internal error

PSS-Range: Error List

F-88

Error class F-88


Error no. Description

Remedy

05

Change device.

Internal error

PSS-Range: Error List

5-39

Error Messages on Decentr. Modules

F-90

Error class F-90


Error no. Description

Remedy

01
.
.
.
02

Internal error

Please contact Pilz.

04
.
.
.
06

Internal error

Please contact Pilz.

5-40

PSS-Range: Error List

F-91

Error class F-91


Error no. Description

Remedy

00
.
.
.
01

Please contact Pilz.

Internal error

PSS-Range: Error List

5-41

Error Messages on Decentr. Modules

F-92

Error class F-92


Error no. Description

Remedy

00

Domain-Timeout

Check and rectify the time entered for the


Domain-Timeout in the configuration, clear the
program memory and reload the application
program.
If no remedy helps: contact Pilz.

01

Stated I/O-Group is configured Check and rectify the I/O-Group configuration,


incorrectly
clear the program memory and reload the
application program.
If no remedy helps: contact Pilz.

02
.
.
.
03

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

04

Cycle-Timeout because bus


connection interrupted, LD for
I/O-Group no longer available
or bus overloaded

Check and rectify the time entered for the


Cycle-Timeout in the configuration, clear the
program memory and reload the application
program. If necessary, reduce the bus load.
If no remedy helps: contact Pilz.

05

Bus error

If message appears frequently, please contact


Pilz.

06
.
.
.
07

I/O-Group was stopped via the Evaluate error stack of the stated device.
stated Device

5-42

PSS-Range: Error List

F-92

Error no. Description

Remedy

08

Cycle-Timeout because bus


connection interrupted, MD no
longer available or bus
overloaded

Check and rectify the time entered for the


Cycle-Timeout in the configuration, clear the
program memory and reload the application
program. If necessary, reduce the bus load.
If no remedy helps: contact Pilz.

09

Bus error

Please contact Pilz.

0A

Domain-Timeout

Check and rectify the time entered for the


Domain-Timeout in the configuration, clear the
program memory and reload the application
program.
If no remedy helps: contact Pilz.

0B

Event-Timeout

Check and rectify the time entered for the


Event-Timeout in the configuration, clear the
program memory and reload the application
program.
If no remedy helps: contact Pilz.

0D

Bus error

If message appears frequently: contact Pilz.

0E

Stated I/O-Group is configured Check and rectify the I/O-Group configuration,


incorrectly
clear the program memory and reload the
application program.
If no remedy helps: contact Pilz.

0F

The stated I/O-Groups were


Evaluate error stack of the stated device.
stopped via the stated Device.

10

Bus error

PSS-Range: Error List

If message appears frequently: contact Pilz.

5-43

Error Messages on Decentr. Modules

F-93

Error class F-93


Error no. Description

Remedy

00

Please contact Pilz.

5-44

Internal error

PSS-Range: Error List

F-95

Error class F-95


Error no. Description
05

Device-Address was altered


during operation

PSS-Range: Error List

Remedy
If this message appears frequently, even
though the Device-Address has not been
changed manually: Change device.

5-45

Error Messages on Decentr. Modules

F-D0

Error class F-D0


Error no. Description

Remedy

01
.
.
.
06

Please contact Pilz.

Internal error

07
.
.
.
08

Incorrect configuration data

0A
.
.
.
0B

Internal error

Please contact Pilz.

0D

Internal error

Please contact Pilz.

0F

Internal error

Please contact Pilz.

16

Internal error

Please contact Pilz.

18
.
.
.
19

Internal error

Please contact Pilz.

1C

Incorrect configuration data

Check and rectify configuration, clear the


program memory and reload the application
program.
If no remedy helps: contact Pilz.

1D
.
.
.
20

Internal error

Please contact Pilz.

5-46

Check and rectify configuration, clear the


program memory and reload the application
program.
If no remedy helps: contact Pilz.

PSS-Range: Error List

F-D0

Error no. Description

Remedy

21

Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.

22
.
.
.
.
23

Incorrect configuration data

24

Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.

PSS-Range: Error List

Check and rectify the device type and version


in the configuration, clear the program memory
and reload the application program.
If no remedy helps: contact Pilz.

5-47

Error Messages on Decentr. Modules

F-D1

Error class F-D1


Error no. Description

Remedy

01

Internal communication error

Reduce the changes in process data (PIO).


If no remedy helps: contact the device
manufacturer.

02

Internal communication error

Please contact the device manufacturer.

04

Internal communication error

Reduce the changes in process data (PIO/PII).


If no remedy helps: contact the device
manufacturer.

05
.
.
.
06

Internal communication error

Please contact the device manufacturer.

08
.
.
.
09

Internal communication error

Please contact the device manufacturer.

0C

Internal communication error

Please contact the device manufacturer.

10
.
.
.
.
11

Incorrect configuration data

Check and rectify the device type and version


in the configuration, clear the program memory
and reload the application program.
If no remedy helps: contact Pilz.

Internal communication error

Please contact the device manufacturer.

12
.
.
.
1B

5-48

PSS-Range: Error List

F-D1

Error no. Description

Remedy

1C

Internal communication error

Reduce the changes in process data (PIO).


If no remedy helps: contact the device
manufacturer.

1D
.
.
.
1E

Internal communication error

Please contact the device manufacturer.

1F

Internal error

Please contact Pilz.

Internal communication error

Please contact the device manufacturer.

23

Incorrect configuration data

Check and rectify overall Device configuration,


clear the program memory and reload the
application program.
If no remedy helps: contact Pilz.

24

Incorrect configuration data

Check and rectify the device type and version


in the configuration, clear the program memory
and reload the application program.
If no remedy helps: contact Pilz.

25
.
.
.
26

Internal communication error

Please contact the device manufacturer.

27

Internal communication error

Reduce the changes in process data (PII).


If no remedy helps: contact the device
manufacturer.

28
.
.
2A

Internal communication error

Please contact the device manufacturer.

20
.
.
22

PSS-Range: Error List

5-49

Error Messages on Decentr. Modules

F-D2, F-D3, F-D4

Error class F-D2, F-D3, F-D4


Errors of this class should be documented in the devices operating
manual. If this is not the case, please contact the device manufacturer.

5-50

PSS-Range: Error List

F-D5

Error class F-D5


Error no. Description

Remedy

03

Change device

Internal error

PSS-Range: Error List

5-51

Error Messages on Decentr. Modules

F-E0

Error class F-E0


Error no. Description

Remedy

00
.
.
.
01

Internal error

Please contact Pilz.

03
.
.
.
07

Internal error

Please contact Pilz.

5-52

PSS-Range: Error List

F-E1

Error class F-E1


Error no. Description

Remedy

00
.
.
.
01

Change device.

Internal error

PSS-Range: Error List

5-53

Error Messages on Decentr. Modules

F-E2

Error class F-E2


Error no. Description

Remedy

00

Internal error

Please contact Pilz.

02
.
.
.
04

Internal error

Please contact Pilz.

5-54

PSS-Range: Error List

F-E3

Error class F-E3


Error no. Description

Remedy

00

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

01

Internal error

Please contact Pilz.

02

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

03

Incorrect application program. Check and rectify application program, clear


There was an attempt to
program memory and reload application
access non-existing outputs.
program.

04

Incorrect application program. Insert standard function block SB250.


Written to outputs in the stated
I/O group, although the I/Ogroup on the opposite end of
the Bridge is in a STOP
condition.

05

Incorrect application program. Insert standard function block SB250.


Written to the stated Bit
(14,15, 30 or 31), although this
Bit is reserved.

06

Internal error

07

Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.

PSS-Range: Error List

Please contact Pilz.

5-55

Error Messages on Decentr. Modules

Error no. Description

F-E3

Remedy

08

Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.

5-56

PSS-Range: Error List

F-E4

Error class F-E4


Error no. Description

Remedy

00

Error while testing inputs with


test pulses.

Check inputs/outputs for short circuits; check


connection between inputs and test pulses.
If no remedy helps: Change device.

01

Status of output is not as


expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

02

Status of output during output


test is not as expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

03

I/O-Group warm start is not


possible due to a previous
major output error

Check inputs/outputs for short circuits; check


connection between inputs and test pulses;
switch voltage to Device off/on.
If no remedy helps: Change device.

04

Error while testing inputs with


test pulses.

Check inputs/outputs for short circuits; check


connection between inputs and test pulses.
If no remedy helps: Change device.

05

Status of output is not as


expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

06

Status of output during output


test is not as expected

Check outputs for shorts between contacts


and short circuits; check load supply voltage.
If no remedy helps: Change device.

PSS-Range: Error List

5-57

Error Messages on Decentr. Modules

F-E5

Error class F-E5


Error no. Description

Remedy

00

Internal error

Change device.

02
.
.
.
12

Internal error

Change device.

5-58

PSS-Range: Error List

F-E6

Error class F-E6


Error no. Description

Remedy

00
.
.
.
03

Internal error

Please contact Pilz.

04

Internal error

Change device.

05
.
.
.
0D

Internal error

Please contact Pilz.

PSS-Range: Error List

5-59

Error Messages on Decentr. Modules

F-E7

Error class F-E7


Error no. Description
00
.
.
.
01

5-60

Load supply is missing

Remedy

Check earth connection; check load supply


voltage.

PSS-Range: Error List

F-E8

Error class F-E8


Error no. Description

Remedy

01

Incorrect device configuration

Check and rectify Device configuration, clear


the program memory and reload the
application program.
If no remedy helps: contact Pilz.

02

Overflow of the telegram


buffer.
The changes in signal status
on the opposite end of the
Bridge cannot be processed
quickly enough.

1.) Reduce difference in transmission rates of


both SafetyBUS p networks.
2.) Reduce number of signal status changes at
the opposite end of the bridge.
3.) Signals on which the status changes
frequently should be distributed evenly on
I/OD A and I/OD B
4.) Increase bus speed in the network on this
end of the bridge: Increase transmission rate,
increase value for the Cycle-Timeout or
reduce the bus load
5.) Assign this end of the Bridge a lower
Device-Address (telegrams from the Bridge
will then have a higher priority).

03

Overflow of the telegram


buffer.
Signal status at the inputs
changes too often.

1.) Reduce number of signal status changes at


the inputs.
2.) Signals on which the status changes
frequently should be distributed evenly on
I/OD A and I/OD B.
3.) Increase bus speed: Increase transmission
rate, increase value for the Cycle-Timeout or
reduce the bus load.
4.) Assign the Device a lower Device-Address
(telegrams from the Device will then have a
higher priority).

PSS-Range: Error List

5-61

Error Messages on Decentr. Modules

F-E8

Error no. Description

Remedy

04

1.) Reduce difference in transmission rates of


both SafetyBUS p networks.
2.) Reduce number of signal status changes
on this end of the bridge.
3.) Signals on which the status changes
frequently should be distributed evenly on
I/OD A and I/OD B
4.) Increase bus speed in the network on the
opposite end of the bridge: Increase
transmission rate, increase value for the
Cycle-Timeout or reduce the bus load
5.) Assign the opposite end of the Bridge a
lower Device-Address (telegrams from the
Bridge will then have a higher priority).

5-62

Overflow of the telegram


buffer.
The changes in signal status
on this end of the Bridge
cannot be processed quickly
enough.

PSS-Range: Error List

F-E9

Error class F-E9


Error no. Description

Remedy

01

Bridge communication error

Evaluate the error stack on the opposite end


of the Bridge.
If no remedy helps: Change Device.

02

Internal error

Change Device

03

I/O-group has been stopped


Restart I/O-Group.
because the I/O-group on the
opposite end of the bridge was
stopped.

PSS-Range: Error List

5-63

Error Messages on Decentr. Modules

Notes

5-64

PSS-Range: Error List

PSS(1) AI U5I1 Error Messages

An error on the module PSS(1) AI U5I1 is displayed (as with all module
errors) using the error class 06. The error numbers 48 ... 51 in this error class
relate to the AI module (see also PSS FS error messages).
If an error occurs, an additional parameter is given for the PSS(1) AI U5I1
that describes the error in more detail. The meaning of these parameters is
described in this chapter.

PSS-Range: Error List

6-1

PSS(1) AI U5I1 Error Messages

Error class 06
Error
no.

48
.
.
.
51

6-2

Error parameter

Description

Remedy

01... 03

Parameter is invalid

Check application program,


use SB 105

04 ... 09

Match error

Increase tolerance, if this does


not help: change the module

0A

Parameter is invalid

Check application program,


use SB 105

0B

Module is defective

Change module

0C ... 17

Match error

Increase tolerance, if this does


not rectify the error: change
the module

18

Configuration change during


minimum value formation

Check application program,


use SB 105

19

Not assigned

1A

Match error

1B

Not assigned

1C

External voltage supply is


missing

Apply supply voltage

1D, 1E

System error

Change module

1F

Start/Stop of a function which


was not started/selected

Check application program,


use SB 105

20

System error

Change module

21

Not assigned

22

Parameter is invalid

23 ... 7F

Not assigned

80 ... A1

System error

FE

Message for internal purposes

FF

System error

Increase tolerance, if this does


rectify the error: change the
module

Check application program,


use SB 105
Change module
Change module

PSS-Range: Error List

AUS

B
L

BR

CH

DK

Pilz Ges.m.b.H.
Modecenterstrae 14
1030 Wien
Austria
Telephone (01) 7 98 62 63-0
Telefax
(01) 7 98 62 64
E-Mail:
pilz@pilz.at
Pilz Australia
Industrial Automation LP.
9/475 Blackburn Road
Mt. Waverley, Melbourne VIC 3149
Australia
Telephone (03) 95 44 63 00
Telefax
(03) 95 44 63 11
E-Mail:
safety@pilz.com.au
Pilz Belgium
BC Building
lndustriezone lII
lndustrielaan 4
9320 Erembodegem
Belgium
Telephone (0 53) 83 66 70
Telefax
(0 53) 83 89 58
E-Mail:
info@pilz.be
Pilz do Brasil Sistemas Eletrnicos
Industriais Ltda.
Rua rtico, 123 - Jd. do Mar
09726-300
So Bernardo do Campo - SP
Brazil
Telephone (11) 43 37-12 41
Telefax
(11) 43 37-12 42
E-Mail:
pilz@pilzbr.com.br
Pilz lndustrieelektronik GmbH
Gewerbepark Hintermttli
Postfach 6
5506 Mgenwil
Switzerland
Telephone (0 62) 8 89 79 30
Telefax
(0 62) 8 89 79 40
E-Mail:
pilz@pilz.ch
Headquarters:
Pilz GmbH & Co.
Felix-Wankel-Strae 2
73760 Ostfildern
Germany
Telephone (07 11) 34 09-0
Telefax
(07 11) 34 09-1 33
E-Mail:
pilz.gmbh@pilz.de
Pilz Skandinavien KS
Ellegaardvej 25 L
6400 Sonderborg
Denmark
Telephone 74 43 63 32
Telefax
74 43 63 42
E-Mail:
pilz@pilz.dk
Pilz lndustrieelektronik S.L.
Edificio Tilma
Avda. Sant Juli 1
08400 Granollers
Spain
Telephone (93) 8 49 74 33
Telefax
(93) 8 49 75 44
E-Mail:
central@pilzspain.com

Pilz France Electronic


1, rue Jacob Mayer
BP 12
67037 Strasbourg Cedex
France
Telephone 03 88 10 40 00
Telefax
03 88 10 80 00
E-Mail:
siege@pilz-france.fr

FIN

Pilz Skandinavien KS
Pakilantie 61
00660 Helsinki
Finland
Telephone (09) 27 09 37 00
Telefax
(09) 27 09 37 09
E-Mail:
pilz.sk@kolumbus.fi

GB

Pilz Automation Technology


Willow House, Medlicott Close
Oakley Hay Business Park
Corby
Northants NN18 9NF
United Kingdom
Telephone (0 15 36) 46 07 66
Telefax
(0 15 36) 46 08 66
E-Mail:
sales@pilz.co.uk

IRL

MEX

...

www

Pilz ltalia Srl


Via Meda 2/A
22060 Novedrate (CO)
Italy
Telephone (0 31) 78 95 11
Telefax
(0 31) 78 95 55
E-Mail:
info@pilz.it
Pilz Ireland Industrial Automation
Cork Business and Technology Park
Model Farm Road
Cork
Ireland
Telephone (0 21) 4 34 65 35
Telefax
(0 21) 4 80 49 94
E-Mail:
sales@pilz.ie
Pilz Japan Co., Ltd.
Three One Building 701
3-20-5 Shin-Yokohama
Kohoku-ku
Yokohama 222-0033
Japan
Telephone (0 45) 4 71-22 81
Telefax
(0 45) 4 71-22 83
E-Mail:
pilz@pilz.co.jp

NL

Pilz Nederland
Postbus 186
4130 ED Vianen
Netherlands
Telephone (03 47) 32 04 77
Telefax
(03 47) 32 04 85
E-Mail:
info@pilz.nl
Pilz Industrieelektronik S.L.
Apartado 2028
2706-909 Colares
Portugal
Telephone (21) 9 28 91 09
Telefax
(21) 9 28 91 13
E-Mail:
pilz@esoterica.pt

PRC

Pilz China Representative Office


Flat F9/F Huijing Building
134 Siyou Xin Malu
Dongshan District
Guangzhou 510600
China
Telephone (0 20) 87 37 16 18
Telefax
(0 20) 87 37 35 55
E-Mail:
pilzchn@public.guangzhou.gd.cn

ROK

Pilz Korea Liaison Office


102-1402 Ilsung apt
767, Kyomun-Dong, Kuri-Si
Kyungki-Do 417-715
Korea
Telephone (31) 5 54 12 80
Telefax
(31) 5 54 12 80
E-Mail:
pilzkr@hotmail.com

Pilz Skandinavien KS
Energigatan 10 B
43437 Kungsbacka
Sweden
Telephone (03 00) 1 39 90
Telefax
(03 00) 3 07 40
E-Mail:
pilz@tripnet.se

SGP

Pilz Industrial Automation Pte Ltd.


61, Kaki Bukit Ave 1, #05-01
Shun Li Industrial Park
Singapore 417943
Singapore
Telephone 8 44 44 40
Telefax
8 44 44 41
E-Mail:
sales@pilz.com.sg

USA

Pilz LP
7150 Commerce Boulevard
Canton
Michigan 48187
USA
Telephone (7 34) 3 54-02 72
Telefax
(7 34) 3 54-33 55
E-Mail:
info@pilzusa.com

Pilz de Mexico S. de R.L. de C.V.


Av. San Ignacio 1079
Col. Jardines de San Ignacio
C.P. 45000
Guadalajara, Jalisco
Mexico
Telephone (0 13) 1 22 16 81
Telefax
(0 13) 6 47 81 85
E-Mail:
pilz_msolis@infosel.net.mx

In many countries we are represented by sales partners. Please refer to our


Homepage for further details or contact our headquarters.
www.pilz.com
Internet enquiries and orders: www.pilz.com

Pilz GmbH & Co.


Felix-Wankel-Strae 2, 73760 Ostfildern, Germany
Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33

19 715-02/02 Printed in Germany

Potrebbero piacerti anche