PSS-Range
Error List
Item No. 19 715
This manual is intended for instruction and should be retained for future reference.
All rights to this manual are reserved by Pilz GmbH & Co. Copies may be made for internal
purposes.
While every effort has been made to ensure that the information in this manual is accurate,
no responsibility can be accepted for errors or omissions contained within it. We reserve the
right to amend specifications without notice. We are grateful for any feedback on the contents
of this manual.
The names of products, goods and technologies used in this manual are trademarks of the
respective companies.
V, 02/02
Contents
Introduction
1-1
FS Error Messages
2-1
2-1
2-2
2-3
2-4
2-5
2-6
2-14
2-15
2-27
2-28
2-29
2-30
2-31
2-33
2-34
Contents
2-38
2-39
2-43
2-46
2-47
2-48
2-49
2-50
2-53
2-54
2-55
2-56
2-60
2-61
2-62
2-64
2-65
2-66
2-67
2-68
2-78
2-79
2-80
2-81
2-82
2-83
2-84
2-85
2-89
2-90
2-92
2-93
2-94
2-95
2-96
2-97
2-98
2-99
2-100
2-101
Contents
ST Error Messages
Error class S-01
Hardware error
Error class S-04
Battery error
Error class S-05
Configuration error
Error class S-06
Module error
Error class S-07
User program error
Error class S-08
Program cartridge error
Error class S-0B
Power failure
Error class S-0C
Scan time exceeded
Error class S-0F
Addressable module error
2-105
2-106
2-108
2-109
2-110
2-111
2-112
2-113
3-1
3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8
3-9
3-10
3-11
3-12
3-13
3-18
3-19
3-24
3-27
3-28
3-29
3-30
3-31
3-35
3-36
3-37
3-38
Contents
4-1
4-2
4-3
4-5
4-6
4-12
5-1
5-2
5-3
5-4
5-5
5-6
5-7
5-8
5-9
5-10
5-11
5-12
5-14
5-15
5-16
5-17
5-19
5-21
5-22
5-23
5-24
5-25
5-26
5-27
5-28
5-29
5-30
5-31
5-33
5-34
5-35
5-36
5-37
5-38
5-39
5-40
5-41
5-42
5-44
5-45
5-46
5-48
5-50
5-51
5-52
5-53
5-54
5-55
5-57
5-58
5-59
5-60
5-61
5-63
6-1
Contents
Introduction
1-1
Introduction
Notes
1-2
FS Error Messages
F-01
11
.
.
.
15
16
17
.
.
.
1A
Description
Remedy
Hardware error
Hardware error
Hardware error
2-1
FS Error Messages
F-02
0A
.
.
.
0C
0D
0E
.
.
.
11
2-2
Description
Remedy
Hardware error
Faulty user
program
Hardware error
Hardware error
F-03
05
.
.
.
0F
10
11
.
.
.
28
Description
Hardware error
Remedy
Change PSS CPU
Faulty user
program
Hardware error
Hardware error
2-3
FS Error Messages
F-04
2-4
Description
Battery is depleted
Remedy
Change battery. Leave voltage
applied until the battery has been
changed.
F-05
Description
Configuration error
Slot
Remedy
Compare the registered hardware
set up with the actual configuration.
Adjust configuration in configurator
or insert the correct module.
2-5
FS Error Messages
F-06
Error no.
01
.
.
Description
Error on
PSS (1) DIO Z
.
16
17
18
2-6
Error on
PSS (1) DIF
Error on
PSS (1) DIO T
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check alarm conditions e.g. the
alarm must appear for min. 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
F-06
Error no.
19
.
Description
Error on
PSS (1) DO/DOS/DIO T
.
1A
1B
.
.
Error on
PSS (1) DIO T
.
22
23
.
.
.
29
2A
2B
Error on
PSS (1) DO/DOS
Error on PSS (1) DIF
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Short circuits at the inputs
or test pulse wiring?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check alarm conditions e.g. the
alarm must appear for min. 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
2-7
FS Error Messages
Error no.
2C
2D
Description
Error on
PSS (1) DIO T
2E
.
.
Error on
PSS (1) DIF
.
3E
3F
.
.
42
43
2-8
Error on
PSS (1) DI/DI 2
Error on
PSS (1) DIO T
F-06
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator ?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit atthe outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
F-06
Error no.
44
Description
.
.
Error on
PSS (1) DIF/DIO T
46
47
48
.
.
.
51
52
.
.
Error on
PSS (1) DI/DI 2/DIO T
Error on
PSS (1) DOR
Remedy
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
3.) Does the test pulse wiring
match the allocation in the
configurator?
4.) Short circuits at the inputs
or test pulse wiring?
5.) Short circuit at the outputs
or to 0 V or 24 V (DIO T)?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
4.) Short circuit at the outputs
or to 0 V or 24 V (DIO T)?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read?
If no remedy helps: change module.
Check the supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
2-9
FS Error Messages
Error no.
61
Description
Error on PSS (1) DIO T
62
63
64
2-10
F-06
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
5.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
If no remedy helps: change module.
Application program attempts to write
to test pulse outputs; remove error
from the application program
F-06
Error no.
65
Description
Error on PSS (1) DOR
66
67
68
.
.
.
70
71
72
.
.
.
.
74
Remedy
Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
2-11
FS Error Messages
Error no.
75
76
Description
Not assigned
Error at the inputs
77
78
79
7B
2-12
F-06
Remedy
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs or test
pulse wiring
If no remedy helps: change PSS.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs or test
pulse wiring
If no remedy helps: change PSS.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 s
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check alarm inputs for interference
2.) On modular PSS: check contacts
between the alarm module, bus back
plane and CPU module?
If no remedy helps: contact Pilz.
Check stated outputs for short
circuits and shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.
F-06
Error no.
7C
Description
Error at stated output (DOT)
7D
7E
Remedy
Check stated outputs for short
circuits and shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.
Check outputs for short circuits and
shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.
Check stated outputs for short
circuits and shorts across contacts;
check load supply voltage.
If no remedy helps: change module/
compact PSS.
2-13
FS Error Messages
F-07
2-14
Description
User program
Remedy
Clear user program and
reload into PSS ;
.
If no remedy helps: change CPU.
F-08
Error no.
00
Description
Error on an output module
01
02
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
2-15
FS Error Messages
Error no.
03
Description
Error on CPU
or on all output modules
04
Error on an
output module
05
Module error
06
Error on a word
module
2-16
F-08
Remedy
Check supply voltage to the
modules (voltage interrupt?)
If no remedy helps: if there is only
one output module, change it;
if there are several output modules,
change CPU
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
F-08
Error no.
07
Description
Error on PSS (1) DIO T module
08
09
0A
Remedy
1.) Check the supply voltage to
the module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator ?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 s
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module
2-17
FS Error Messages
Error no.
0B
Description
Error on the PSS (1) DOS module
0C
0D
0E
0F
2-18
F-08
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
(voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
F-08
Error no.
F-08
10
11
Description
Remedy
12
13
14
15
2-19
FS Error Messages
Error no.
16
Description
Error on an output module or
on the CPU
17
18
19
2-20
F-08
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Does test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change output
module or CPU.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Does test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
F-08
Error No.
1A
Description
Error on PSS (1) DIF module
1B
1C
1D
1E
1F
20
Remedy
1.) Check alarm conditions e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
1.) Check alarm conditions e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
Check user program
and reload into the PSS (SB 255)
Check user progam
and reload into the PSS (SB 255)
2-21
FS Error Messages
Error No.
21
.
Description
28
29
2A
2B
2C
2D
2-22
F-08
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
1.) Does the test pulse wiring
match the allocation in the
configurator?
2.) Short circuits at the inputs
or the signal wiring?
If no remedy helps: change module.
Change CPU module
1.) Check the supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
Change CPU module
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
Change CPU module
F-08
Error no.
2E
Description
.
Error on an ouput module
.
.
31
34
35
36
37
.
.
.
3C
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
2-23
FS Error Messages
Error no.
3D
.
.
.
Description
Error on a word module
3F
40
41
.
.
44
45
46
48
.
.
.
4C
2-24
F-08
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read
(by AI)?
If no remedy helps: change module.
Change CPU module
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 s
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the inputs?
3.) Test value sent and read
(by AI)?
If no remedy helps: change module
1.) Check alarm conditions, e.g. the
alarm must appear for min. of 1.5 ms
2.) Does the test pulse wiring
match the allocation in the
configurator
3.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module
F-08
Error no.
4D
Description
Error on PSS (1) DIO Z module
4E
4F
50
51
52
53
54
Remedy
1.) Check supply voltage to the
module (voltage interrupt?
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator ?
If no remedy helps: change module.
Check supply voltage to the
module (voltage interrupt?)
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuits at the outputs
or to 0 V or 24 V?
3.) Load break?
4.) Does the test pulse wiring
match the allocation in the
configurator?
If no remedy helps: change module.
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
2-25
FS Error Messages
Error no.
55
56
57
58
59
Description
Configuration error
60
61
62
2-26
F-08
Remedy
Compare true layout with set layout
and either adapt configuration or
change layout
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Short circuit at the outputs
or to 0 V or 24 V?
If no remedy helps: change module.
Change CPU module
Rectify fault at stated inputs.
F-09
Error no.
01
.
.
.
0E
0F
Description
Remedy
1.) Tolerance set is too low
2.) Incorrect match algorithm
(e.g. match instead of min.- max.)
if no error is present in the
configuration: change the module
Check application program
and change if necessary
2-27
FS Error Messages
F-0C
Description
Block run time exceeded
02
2-28
Remedy
Increase the block run time in the
configurator or optimise the
user program
Scan time is the same as the
block run times for the FS and ST
user program and the processing
time for the operating system;
optimise user program, e.g. reduce
alarm load
F-12
Alarm-OB
Description
Too many alarms
(Alarm queue overflow)
Remedy
1.) Reduce alarm load
2.) Make the segments shorter
3.) Optimise user program
2-29
FS Error Messages
F-14
02
03
2-30
Description
Alarm triggered although
no module with alarm
capabilities installed
Alarm source cannot
be determined
Alarm reaction time
exceeded
Remedy
Remove sources of interference
from the working environment.
If no remedy helps: change CPU.
1.) Increase alarm pulse
2.) Remove sources of interference
from the working environment
1.) Increase alarm reaction time in
the configurator
2.) Reduce alarm load
3.) Optimise user program
F-20
Description
Cold start: FS program
starting up
Remedy
---
03
STOP: FS program
switched to STOP
STOP: FS program
switched to "No FS"
---
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
System error
System error
Faulty user program
11
12
13
AS-command in
Alarm-OB
AF-command in
Alarm-OB
14
2-31
FS Error Messages
Error no.
15
16
Description
Deactivation data
cleared
1D
1E
1F
20
22
Start reactivation
Acknowledge reactivation error
Acknowledge reactivation
Reactivation through operator
Maximum scan time
exceeded on start-up
Maximum scan time
exceeded in STOP
Reactivation completed
successfully
23
24
2-32
F-20
Remedy
Replace the battery.
Leave the voltage applied until the
battery is replaced!
---------------
F-21
Timer number
Block in which the error occurred
Description
Command SE: timer was
started with a negative value
Byte division by 0
Byte division overflow
Word division overflow
Periphery word access
to pulsed input in alarm-OB
Remedy
Enter positive value for
time value
Change user program
Reduce dividend
Reduce dividend
No periphery accesses permitted
in alarm-OBs
2-33
FS Error Messages
F-22
2-34
Description
Command "L DR":
DW lies outside the current DB
Command "L DL":
DW lies outside the current DB
Command "T DR":
DW lies outside the current DB
Command "T DL":
DW lies outside the current DB
Command "AND DR":
DW lies outside the current DB
Command "AND DL":
DW lies outside the current DB
Command "OR DR":
DW lies outside the current DB
Command "OR DL":
DW lies outside the current DB
Command "XOR DR":
DW lies outside the current DB
Command "XOR DL":
DW lies outside the current DB
Command "+ DR":
DW lies outside the current DB
Command "+ DL":
DW lies outside the current DB
Command "- DR":
DW lies outside the current DB
Command "- DL":
DW lies outside the current DB
Remedy
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
F-22
Error no.
13
14
15
16
17
18
19
1A
1B
1C
1F
20
23
24
30
31
Description
Command "* DR":
DW lies outside the current DB
Command "* DL":
DW lies outside the current DB
Command ": DR":
DW lies outside the current DB
Command ": DL":
DW lies outside the current DB
Command "I DR":
DW lies outside the current DB
Command "I DL":
DW lies outside the current DB
Command "D DR":
DW lies outside the current DB
Command "D DL":
DW lies outside the current DB
Command "> DR":
DW lies outside the current DB
Command "> DL":
DW lies outside the current DB
Command "!= DR":
DW lies outside the current DB
Command "!= DL":
DW lies outside the current DB
Command "< DR":
DW lies outside the current DB
Command "< DL":
DW lies outside the current DB
Command "L DW":
DW lies outside the current DB
Command "T DW":
DW lies outside the current DB
Remedy
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
2-35
FS Error Messages
Error no.
32
34
36
37
38
39
3A
3B
3C
3D
3F
41
51
52
53
54
2-36
Description
Command "AND DW":
DW lies outside the current DB
Command "OR DW":
DW lies outside the current DB
Command "XOR DW":
DW lies outside the current DB
Command "+ DW":
DW lies outside the current DB
Command "- DW":
DW lies outside the current DB
Command "* DW":
DW lies outside the current DB
Command ": DW":
DW lies outside the current DB
Command "I DW":
DW lies outside the current DB
Command "D DW":
DW lies outside the current DB
Command "> DW":
DW lies outside the current DB
Command "!= DW":
DW lies outside the current DB
Command "< DW":
DW lies outside the current DB
Actual parameter for
DR is invalid
Actual parameter for
DL is invalid
Command "T =para":
DR lies outside the current DB
Command "T =para":
DL lies outside the current DB
F-22
Remedy
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
Check actual parameter,
rectify program
Check actual parameter,
rectify program
Check the length of the DB,
rectify program
Check the length of the DB,
rectify program
F-22
Error no.
61
62
63
64
65
Description
Command "L =para":
DW lies outside the current DB
Command "T =para":
DW lies outside the current DB
Remedy
Check length of the DB,
rectify program
Check length of the DB,
rectify program
2-37
FS Error Messages
F-23
2-38
Description
Command "T DR":
transferring to read-only DB
Command "T DL":
transferring to read-only DB
Command "T DW":
transferring to read-only DB
Command "I DW":
transferring to read-only DB
Command "D DW":
transferring to read-only DB
Command "T =para":
transferring DL to read-only DB
Command "T =para":
transferring DR to read-only DB
Command "T =para":
transferring DW to read-only DB
Command "I =para":
transferring DW to read-only DB
Command "D =para":
transferring DW to read-only DB
Remedy
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
Remove read-only or
select correct DB
F-24
Error class F-24 - Error setting parameters for FBs and SBs
Error parameter:
Error location:
Error no.
01
02
03
13
16
18
19
1A
21
22
23
Call up block
Block called up
Description
Actual parameter (bit)
lies outside the permitted range
Actual parameter (byte)
lies outside the permitted range
Actual parameter (word)
lies outside the permitted range
Command "SE =para":
Actual parameter lies
outside the permitted range
Command "ZV =para":
Actual parameter lies
outside the permitted range
Command "R =para":
Actual parameter lies
outside the permitted range
Command "R =para":
Timer address is incorrect
Command "R =para":
Counter address is incorrect
Command "T =para":
Byte-actual parameter
lies outside the permitted range
Command "I =para":
Byte-actual parameter
lies outside the permitted range
Command "D =para":
Byte-actual parameter
lies outside the permitted range
Remedy
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
2-39
FS Error Messages
Error no.
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
2-40
Description
Command "T =para":
Word-actual parameter
lies outside the permitted range
Command "I =para":
Word-actual parameter
lies outside the permitted range
Command "D =para":
Word-actual parameter
lies outside the permitted range
Command "A =para":
Actual parameter DB lies
outside the permitted range
Command "T =para":
Actual parameter ZW lies
outside the permitted range
Command "S =para":
Bit-write access to
flag range above the special flag
Command "S =para":
Write access to read-only flags
Command "S =para":
Input bit set is not permitted
Command "R =para":
Bit-write access to flag range
above the special flag
Command "R =para":
Bit-write access to read-only flag
Command "R =para":
Resetting of input bit is not permitted
Command "T =para":
Byte-write access to
flag range above the special flag
Command "T =para":
Byte-write access to read-only flags
F-24
Remedy
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Check and rectify actual
parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify actual parameter
Only output bit can be set;
rectify parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
F-24
Error no.
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
4B
Description
Command "T =para":
Word-write access to
flag range above the special flags
Command "T =para":
Word write access to read-only flags
Command "I =para":
Byte-write access to
flag range above the special flags
Command "I =para":
Byte write access to read-only flags
Command "I =para":
Incrementing input byte is not
permitted
Command "D =para":
Byte-write access to
flag range above the special flags
Command "D =para":
Byte-write access to read-only flags
Command "D =para":
Decrementing input byte
is not permitted
Command "I =para":
Word-write access to
flag range above the special flag
Command"I =para":
Word-write access to read-only flags
Command "I =para":
Incrementing input word
is not permitted
Command "D =para":
Word-write access to
flag range above the special flag
Command "D =para":
Word write-access to read-only flags
Command "D =para":
Decrementing input word
is not permitted
Remedy
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
Flag range > do not use last special
flag in the user program;
rectify parameter
Check and rectify parameter
Check and rectify parameter
2-41
FS Error Messages
Error no.
4C
4D
4F
50
51
52
53
54
55
56
57
58
59
2-42
Description
Command "S =para", "!= =para",
"=N =para": Actual parameter lies
outside the permitted range
Command "R =para", Actual
parameter lies outside the
permitted range
Command "L =para",
XW-address on word module lies
outside the permitted range
Command "T =para",
XW-address on word module lies
outside the permitted range
Command "SE =para": Incorrect
timer address as actual parameter
Command "ZR =para": Incorrect
counter address as actual parameter
Command "ZV =para":
Incorrect counter address
as actual parameter
Command "L =para":
Bit-actual parameter lies outside
the permitted range
Command "L =para":
Timer address lies outside the
permitted range
Command "L =para":
Counter address lies outside the
permitted range
Command "L =para": Byte actual
parameter lies outside
the permitted range
Command "L =para": Word actual
parameter lies outside the
permitted range
Command "L =para":
Counter address lies outside the
permitted range
F-24
Remedy
Check and rectify parameter
F-25
16
17
18
19
1A
Description
Indirect address of the flag bit lies
outside the permitted range
Indirect address of the input bit lies
outside the permitted range
Indirect address of the output bit lies
outside the permitted range
Indirect address of the timer bit lies
outside the permitted range
Indirect address of the counter bit
lies outside the permitted range
Command "SE T(...)":
Indirect address of the timer lies
outside the permitted range
Command "ZV Z(...)":
Indirect address of the counter lies
outside the permitted range
Command "ZR Z(...)":
Indirect address of the counter lies
outside the permitted range
Command "R T(...)":
Indirect address of the timer lies
outside the permitted range
Command "R Z(...)":
Indirect address of the counter lies
outside the permitted range
Command "SE T(...)":
Indirect address of the timer lies
outside the permitted range
Remedy
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
2-43
F-25
FS Error Messages
Error no.
21
22
23
24
31
32
33
34
36
50
51
52
2-44
Description
Indirect address of the flag byte lies
outside the permitted range
Indirect addressed of the input byte
ies outside the permitted range
Indirect address of the output byte
lies outside the permitted range
Indirect address of the data
byte-word lies outside the
permitted range
Indirect address of the flag word
lies outside the permitted range
Indirect address of the input word
lies outside the permitted range
Indirect addressed output word
lies outside the permitted range
Indirect address of the counter
word lies outside the
permitted range
Command "L XW(...)":
Indirect address of XW
(word module) lies outside the
permitted range
Command "I MW(...)":
Indirect address of the flag word
lies outside the permitted range
Command "I AW(...)":
Indirect addres of the output word
lies outside the permitted range
Command "D MW(...)":
Indirect address of the flag word
lies outside the permitted range
Remedy
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
Rectify flag where the indirect
address is incorrect
F-25
Error no.
53
54
55
56
57
58
59
5A
Description
Command "D AW(...)":
Indirect address of the output word
lies outside the permitted range
Command "A DB(...)":
Indirect address of the DB lies
outside the permitted range
Command "D MW(...)":
Word-write access to read-only flags
Command "I MW(...)":
Word-write access to read-only flag
Indirect bit-write access
to read-only flags
Indirect byte write access
to read-only flags
Indirect word write access to
read-only flags
Command "T XW(...)":
Indirect address of XW
(word module) lies outside the
permitted range
Remedy
Rectify output word in the
decrement command where
the indirect address is incorrect
Rectify data block call up where
the indirect address is incorrect
Check and rectify parameter
Check and rectify parameter
Check and rectify parameter
Check and rectify parameter
Check and rectify parameter
Rectify access to word module
where the indirect address is
incorrect
2-45
FS Error Messages
F-26
2-46
Description
F-27
Call-up block
Block called up
Description
Remedy
Formal and actual parameters do
Adjust the call-ups to suit the
not match (type, number, sequence) block header.
2-47
FS Error Messages
F-28
2-48
Description
Nesting level exceeded
by starting an OB (CAL OB)
Nesting level exceeded
by starting a PB (CAL PB)
Nesting level exceeded
by starting a FB (CAL FB)
Nesting level exceeded
by starting a SB (CAL SB)
Remedy
Check block nesting levels
and reduce the level
Check block nesting levels
and reduce the level
Check block nesting levels
and reduce the level
Check block nesting levels
and reduce the level
F-29
Remedy
01
02
03
04
05
06
07
08
09
0A
2-49
FS Error Messages
F-70
0F
.
.
.
13
14
15
.
.
.
18
19
1A
.
.
.
1F
20
21
22
23
2-50
Description
Remedy
Please contact Pilz
Restart system
If no remedy helps: change CPU
Please contact Pilz
CRC is incorrect
Error in the
programming device
Major system error
F-70
Error no.
24
25
26
.
.
.
32
33
40
.
.
.
42
43
Description
Major system error
Remedy
Please contact Pilz
Message for internal purposes
Please contact Pilz
Incorrect CRC
Transfer program
If no remedy helps: change CPU
Please contact Pilz
44
46
Transfer program
If no remedy helps: change CPU
Message for internal purposes
Please contact Pilz
47
48
.
.
.
63
64
65
.
.
.
71
2-51
FS Error Messages
Error no.
72
73
.
.
.
7F
2-52
F-70
Description
Too many errors simultaneously
Remedy
Restart PSS
F-71
Description
Major system error
Synchronisation location
Remedy
Please contact Pilz
2-53
FS Error Messages
F-72
2-54
Description
Remedy
Please contact Pilz
Defective CPU
Change CPU
F-73
Description
PII cannot be determined
05
06
07
Remedy
Increase the number of read
attempts;
If no remedy helps: change input
module
Increase the number of read
attempts; reduce interrupt load;
If no remedy helps: change DIF
module
Increase the number of read
attempts;
If no remedy helps: change input
module
2-55
FS Error Messages
F-74
0A
0B
0C
0D
0E
0F
10
12
2-56
Description
Error in the operating
system or programming device
Entry in the configurator
is invalid
Invalid slot entered in the configurator for the test pulse module
Slot entered in configurator as the
slot for test pulse module contains
no pulsed outputs
FS user program
is not loaded
Max. number of test pulses in the
configurator does not match the
number used
Two adjacent inputs are being
tested with the same test pulse
Highest test pulse number used is
not permitted
Alarm-OBs configuration
is not consecutive
Alarm-OB loaded, which
is not configured
Invalid slot number configured for
alarm configuration
Invalid edge configuration, process
alarm-OB must be activated with a
rising and falling pulse edge
Remedy
Check contents of the configurator,
If no remedy helps: use a new
programming device (use latest
PG version)
Rectify basic data in the
configurator
Enter valid slot in the configurator
Check PSS configuration and adjust,
or adjust the entry in the configurator
to the layout
Download FS user program
into PSS
Rectify the number of test pulses
in the configurator
Re-enter the test pulse allocation
in the configurator
Re-enter the number of test pulses
in the configurator
Re-enter alarm-OBs in the
configurator
Check user program
Check PSS configuration and check
the details in the configurator for the
slot for the DIF module
Check alarm-OB configuration
F-74
Error no.
13
14
.
.
.
17
18
19
1A
1B
Description
Edge configuration is
invalid
Error in alarm
configuration or the
programming device
Min. scan time is greater than the
max. permitted scan time
Error in the operating
system or programming device
1D
1E
1F
1C
20
21
22
Remedy
Check alarm-OB configuration
Check contents of configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device
Re-enter the minimum scan time in
the configurator
Check contents of configurator,
If no remedy helps: contact Pilz;
possibly use new programming
device
Check the read/write segments in
the configurator
Check the read segments for the
word module in the configurator
Check the read segments for the
word module in the configurator
Check the read segments for that
word module in the configurator
Check the read segments for that
word module in the configurator
Check alignment algorithm for that
word module in the configurator
Check the read segments for that
word module in the configurator
Enter word modules in the
configurator in ascending order
2-57
FS Error Messages
Error no.
23
Description
Alignment point is invalid
24
25
28
29
30
26
27
31
32
33
34
35
36
37
2-58
F-74
Remedy
Check alignment point for the word
module in the configurator
Check configuration, check read and
write segments in the configurator
Check read and write segments in
the configurator
Check read and write segments in
the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Check output segments for word
module in the configurator
Enter the word modules in
configurator in ascending order
Check output point for the word
module in the configurator
Check test pulse allocation
in the configurator
Check configuration, change the
configuration in the configurator
Check configuration or test pulse
allocation in the configurator
Use correct CPU module
F-74
Error no.
38
.
.
47
48
49
.
.
4B
Description
Selective shutdown
configuration error
A module is not supported by the
operating system
Selective shutdown
configuration error
Remedy
Please contact Pilz;
possibly use new programming
device (use latest version)
Change CPU module
Please contact Pilz;
possibly use new programming
device (use latest version)
2-59
FS Error Messages
F-75
2-60
Description
Remedy
Please contact Pilz;
possibly use new programming
device (use latest version)
F-76
Line number
Block
Description
Programming device error
Remedy
Please contact Pilz;
possibly use new programming
device (use latest version)
2-61
FS Error Messages
F-77
04
05
06
07
08
09
0A
2-62
Description
Remedy
Too many blocks have been loaded Reduce blocks to a maximum of 511
PG communication error
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
User program damaged
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
PG communication error
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
Message for internal purposes
Memory for the
Clear memory (Flash-EPROM),
application program is full
reload the user program into
the PSS. If no remedy helps: reduce
the size of the application program
PSS program has not
Only load the program created
been loaded
using the programming device for
the PSS
PG communication error
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
F-77
Error no.
0B
0C
0D
Description
Approved block is defective
DB 002 does not have
write-protection
Remedy
Obtain block from original disk,
re-link program and transfer
Reload the user program into the
PSS, remove the communication
error: If no remedy helps: contact
Pilz; possibly use new programming
device
2-63
FS Error Messages
F-78
Error no.
01
.
.
.
Description
Link error
.
Block
Remedy
Clear user program,
Re-load user program into the
PSS. If no remedy helps, contact
Pilz; change CPU or programming
device
03
2-64
F-79
Error class F-79 - Error in the process image of outputs system error
(processor A)
Error no.
01
.
.
.
04
Description
Remedy
Please contact Pilz.
2-65
FS Error Messages
F-7A
2-66
Description
Remedy
Please contact Pilz
Major system
error
F-80
Description
2-67
FS Error Messages
F-81
Description
Too many test slices set
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
2-68
Remedy
Enter max. 99 test slices in DB 003,
DW 220
Correct the slot number in DB 003
Check configuration;
Correct the slot number in DB 003
Correct match segment number
in DB 003
Correct alignment algorithm number
in DB 003
Correct match segment number
in DB 003
Check function number
Correct read segment number in
DB 003
Correct match segment number
in DB 003
Correct read segment number in
DB 003
Correct slot number in DB003
Correct write segment number in
DB 003
Correct write segment number in
DB 003
Correct slot number in DB 003
Correct slot number in DB 003
F-81
Error no.
18
19
1A
1D
1E
1F
20
21
22
23
24
25
27
28
29
Description
Invalid start address for CRCcalculation in SB 001
Invalid end address for CRCcalculation in SB 001
ID-Number for CRC-calculation
is invalid
Call SB 255, FUNK 100, but
selective shutdown is not defined
Call SB 255, FUNK 100:
Selected signal group not available
Call SB 255, FUNK 100:
Selected signal group
not deactivated yet
Call SB 255, FUNK 100: Run time
for deadman timer is too long
Call SB 255, FUNK 101, but
selective shutdown is not defined
Call SB 255, FUNK 101:
Selected signal group not available
Call SB 255, FUNK 102, but
selective shutdown is not defined
Call SB 255, FUNK 102:
Selected signal group not available
Call SB 255, FUNK 102:
Selected signal group
not yet deactivated
Call SB 255, FUNK 103, but
selective shutdown is not defined
Call SB 255, FUNK 103:
No module on slot entered
Call SB 255, FUNK 104, but
selective shutdown is not defined
Remedy
Correct input parameter STRT
Choose the address range for CRCchecksum so that the last value is in
the permitted address range
2-69
FS Error Messages
Error no.
2A
2B
2C
2D
2E
2F
31
32
33
34
35
36
37
2-70
Description
Call SB 255, FUNK 104:
No module on slot entered
Call SB 255, FUNK 104:
Word module not on slot entered
Call SB 255, FUNK 104:
Segment has not been defined
Call SB 255, FUNK 105, but
selective shutdown is not defined
Call SB 255, FUNK 105,
called up in alarm-OB
Call SB 255, FUNK 106, but
selective shutdown is not defined
Call SB 255, FUNK 106,
Called up in alarm-OB
Call SB 255, FUNK 106:
Called up in OB 120
Call SB 255, FUNK 106, although
reactivation is already active
Call SB 255, FUNK 106:
Selected signal group not available
Call SB 255, FUNK 106:
Selected signal group has not
been deactivated
Call SB 255, FUNK 106:
Reactivation although signal group
type 0 is not to be reactivated
Call SB 255, FUNK 106:
Reactivating a module that
has been shut down, pulsed
inputs, signal group type 1 or
type 2 on faulty module
F-81
Remedy
Check configuration or correct entry
in DB 003
Check configuration or correct entry
in DB 003
Check configuration or read/write
segment in DB 003
Set selective shutdown in the
configurator or correct the function
Do not carry out reactivation
with FUNK 105 in alarm-OB
Set selective shutdown in the
configurator or correct the function
Do not carry out reactivation
with FUNK 106 in alarm-OB
Remove call up from OB120
Correct user program
Check signal groups
Only deactivated signal groups can
be reactivated, check signal
groups
Check user program,
and if required reactivate all
signal groups simultaneously
Check user program,
and if required reactivate all
signal groups simultaneously
F-81
Error no.
39
Error class
F-81
3A
Description
Call SB 255, FUNK 107: but
selective shutdown is not defined
Error no. Description
Remedy
Set selective shutdown in the
configurator or correct the function
Remedy
3B
3C
3E
3F
40
41
42
44
45
46
2-71
FS Error Messages
Error no.
47
49
4A
4B
4C
4D
4E
4F
50
52
53
2-72
Description
Call SB 255, FUNK 109:
Deactivation interrupted
as the reaction type
is too large
User interface:
Config. DB too short
User interface:
Send DB too short
User interface:
Receive DB too short
Call SB 255, FUNK 103:
Word module is on the
slot entered
Call SB 255, FUNK 104:
Call-up is invalid
Reactivation prevents self-check,
reactivation is not acknowledged
Error in stated block:
Call SB 255, FUNK 111, invalid
I/O-Group entered
Error in stated block:
Call SB 255, FUNK 111, but
previous call not yet processed
Error in stated block:
Call SB 255, FUNK 115, invalid
I/O-Group entered
Error in stated block:
Call SB 255, FUNK 115, but
previous call not yet processed
F-81
Remedy
Reaction type of the signal group
for the 2nd deactivation must be
smaller than that for the 1st,
change reaction type in DB 003
Check configuration DB
(DB no. must appear in DB 003)
Check send DB
(DB no. must appear in DB 003)
Check receive DB
(DB no. must appear in DB 003)
Check configuration, adjust
parameters; FUNK 103 only for bit
modules
Check user program, only
call-up parameters 0 ... 5 are
permitted (see DB 003/DW 201)
Once reactivation is complete,
acknowledge using FUNK 108
Correct enable parameters
F-81
Remedy
55
56
57
58
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB119, source DB too short
number
2.) Check length of DB
59
Error in stated block: Call SB255, FUNK 1.) Check enable parameter Device
119, Master-LD has no write access to address
the stated device
2.) Check the configuration; the MasterLD must have write access to the I/OGroup containing the stated device
5A
Error in stated block: Call SB255, FUNK Correct enable parameters stated in
122, invalid enable parameters
code
0 = DB-Number (source)
1 = Device Address (target)
The code is shown on the error stack
display on the PG.
2-73
FS Error Messages
F-81
Remedy
5B
Error in stated block: Call SB255, FUNK Correct enable parameters stated in
123, invalid enable parameters
code
0 = DB-Number (source)
1 = Device Adresse (source)
2 = DB-Number (target)
3 = Start-DW (target)
4 = Number of DWs
The code is shown on the error stack
display on the PG.
5C
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB123, target DB not available
number (target)
2.) Check whether DB is available in the
project
5D
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB123, target DB too short
number (target)
2.) Check length of DB
5E
Error in stated block: Call SB255, FUNK Lift write protection on target DB
123, target DB is Read-Only
5F
Error in stated block: Call SB255, FUNK 1.) Check enable parameter Device
123, Master-LD has no read access to address
the stated device
2.) Check the configuration; the MasterLD must have read access to the I/OGroup containing the stated device
60
Error in stated block: Call SB255, FUNK Correct enable parameters stated in
124, invalid enable parameters
code
0 = Domain Number (source)
1 = Device Adresse (source)
The code is shown on the error stack
display on the PG.
2-74
F-81
Remedy
61
Error in stated block: Call SB255, FUNK Correct enable parameters stated in
127, invalid enable parameters
code
0 = DB-Number (source)
2 = DB-Number (target)
3 = Start-DW (target)
4 = Number of DWs
The code is shown on the error stack
display on the PG.
62
Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
127 not permitted
127 may only be called in OB131 of the
Slave-LD
63
Error in stated block: Call SB255, FUNK Check enable parameter DB-number
127, DB-Number (source) does not
(source)
match the DB received
64
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB127, target DB not available
number (target)
2.) Check whether DB is available in the
project
65
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB127, target DB too short
number (target)
2.) Check length of DB
66
Error in stated block: Call SB255, FUNK Lift write protection on target DB
127, target DB is Read-Only
68
69
Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
131 not permitted
131 may only be called in OB131 of the
Slave-LD
6A
Error in stated block: Call SB255, FUNK Check enable parameter DB-number
131, DB-Number (source) does not
(source)
match the DB received
2-75
FS Error Messages
F-81
Remedy
6B
6C
Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
135 not permitted
135 may only be called in OB131 of the
Slave-LD
6D
Error in stated block: Call SB255, FUNK Check enable parameter DB-number
135, DB-Number (source) does not
(source)
match the DB received
6E
Error in stated block: Call SB255, FUNK Correct enable parameters stated in
139, invalid enable parameters
code
0 = DB-Number (source)
3 = Start-DW (source)
4 = Number of DWs
The code is shown on the error stack
display on the PG.
6F
Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
139 not permitted
139 may only be called in OB132 of the
Slave-LD
70
Error in stated block: Call SB255, FUNK Check enable parameter DB-number
139, DB-Number (source) does not
(source)
match the DB received
71
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB139, source DB not available
number (source)
2.) Check whether DB is available in the
project
72
Error in stated block: Call SB255, FUNK 1.) Check enable parameter DB139, source DB too short
number (source)
2.) Check length of DB
74
2-76
F-81
Remedy
75
Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
143 not permitted
143 may only be called in OB132 of the
Slave-LD
76
Error in stated block: Call SB255, FUNK Check enable parameter DB-number
143, DB-Number (source) does not
(source)
match the DB received
77
78
Error in stated block: Call SB255, FUNK Amend programming; SB255, FUNK
147 not permitted
147 may only be called in OB132 of the
Slave-LD
79
Error in stated block: Call SB255, FUNK Check enable parameter DB-number
147, DB-Number (source) does not
(source)
match the DB received
7A
7B
Error in stated block: Call SB255, FUNK 1.) Check enable parameters
02, slot is unoccupied
2.) Amend configuration
7C
Error in stated block: Call SB255, FUNK In the enable parameters, a slot has
02, power-up test cannot be deactivated been entered that contains no outputs
on which the power-up test can be
deactivated.
2-77
FS Error Messages
F-82
Error no.
01
.
Description
.
03
2-78
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the output
or to 0 V or 24 V?
4.) Short circuits at the inputs
or test pulse wiring?
If no remedy helps: change module.
F-83
Description
Remedy
Please contact Pilz
Debug error
2-79
FS Error Messages
F-84
Error no.
01
.
.
.
0E
2-80
Description
Error on word module
Remedy
1.) Tolerance set is too low
2.) Incorrect alignment algorithm
(e.g. match instead of min.- max.)
if there is no error in the
configuration: change module
F-90
12
.
.
.
20
21
22
25
.
.
.
33
34
35
.
.
.
37
38
.
.
.
7C
Description
Remedy
Please contact Pilz
Restart system
If no remedy helps: change CPU
Please contact Pilz
2-81
FS Error Messages
F-91
2-82
Synchronisation location
Description
Error within the operating
system
Remedy
Please contact Pilz
F-92
Description
Remedy
Please contact Pilz
2-83
FS Error Messages
F-93
Description
PII cannot be
determined
01
04
05
PII cannot be
determined
06
2-84
Remedy
Increase number of read attempts
If no remedy helps: change input
module
Increase number of read attempts;
reduce interrupt load
If no remedy helps: change DIF
module
Increase number of read attempts
If no remedy helps: change input
module
Increase number of read attempts;
reduce interrupt load
If no remedy helps: change DIF
module
F-94
07
08
09
0A
0B
0C
0D
Description
Programming device error
Remedy
Check contents of the configurator
If no remedy helps: contact Pilz.
possibly use new programming
device (use latest PG version)
Reduce the number of read/write
data blocks
Check contents of the configurator
If no remedy helps: contact Pilz.
possibly use new programming
device (use latest PG version)
Enter valid slot in the
configurator
Check PSS configuration and
adjust or amend the entry in the
configurator to suit the configuration
Download user program into
PSS
Correct the number of test pulses
in the configurator
Correct the test pulse allocation in
the configurator
Correct the test pulse allocation in
the configurator
Enter alarm-OBs in the configurator
consecutively
2-85
FS Error Messages
Error no.
0E
Description
Alarm-OB has been loaded
which has not been configured
0F
10
11
12
F-94
Remedy
Check user program
If no remedy helps: contact Pilz;
possibly use new programming
device
Check PSS configuration,
check the slot for the PSS DIF
in the configurator
Check PSS configuration,
check the slot for the PSS DIF
in the configurator
Check the configuration for the
alarm OBs
13
.
.
.
16
17
18
19
1A
1B
2-86
F-94
Error no.
1C
Description
Read segments overlap
1D
1E
1F
20
21
22
23
27
28
29
24
25
26
2A
Remedy
Check read segment for the word
module in the configurator
Check read segment for the word
module in the configurator
Check read segment for the word
module in the configurator
Check alignment algorithm for the
word module in the configurator
Check read segments for
word modules
Enter word modules in ascending
order in the configurator
Check alignment point for the
word module in the configurator
Check configuration, check read and
write segments in the configurator
Check write segments in the
configurator
Check write segments in the
configurator
Check write segments for the word
module in the configurator
Check write segments for the word
module in the configurator
Check write segments for the word
module in the configurator
Check write segments for the word
modules in the configurator
Check write segment for the word
module in the configurator
2-87
FS Error Messages
Error no.
2B
2C
2D
2E
2F
30
31
.
.
.
Description
Word modules have not
been entered in ascending order
Output time point is invalid
The same pulse is testing
the DI and DIF inputs
More than 2 DIF in the
set layout
Pulse module entered,
but pulse number = FF
Operating system
version is invalid
Error in selective
shutdown configuration
F-94
Remedy
Enter the word modules in the
configurator in ascending order
Check output time point for the word
module in the configurator
Check test pulse allocation in the
configurator
Check configuration, amend set
layout in the configurator
Check configuration or test pulse
allocation in the configurator
Use correct PSS CPU,
program cannot be executed using
this PSS.
Check configuration
If no remedy helps: contact Pilz
support; possibly use new
programming device
(use latest PG version)
49
2-88
F-96
Description
Line number
Block
Remedy
Please contact Pilz; possibly
use new programming device
(use latest PG version)
2-89
FS Error Messages
F-97
Description
Programming device error
03
04
05
Faults/interference
affecting the download
cable
06
07
08
09
Configuration error
0A
0B
Program error
2-90
Remedy
Please contact Pilz; possibly
use new programming device
(use latest PG version)
Reduce the number of blocks to a
maximum of 511
Clear the memory (Flash-EPROM),
Transfer user program again
If no remedy helps: reduce the
size of the user program
Reload user program into
the PSS, rectify error
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
To program the PSS only use a
programming device suitable for
the PSS (not a P10 PG)
Please contact Pilz; possibly
use a new programming device
(use latest PG version)
See additional error messages in the
error stack
Please contact Pilz; possibly
use a new programming device
(use latest PG version)
See error stack
F-97
Error no.
0C
0D
Description
Major system error
0E
10
11
Program error
An approved block
is defective
12
0D
Remedy
Please contact Pilz; possibly use
new programming device
(use latest PG version)
See error stack
Obtain the block from the original,
disk, relink the program and
transfer to PSS
Please contact Pilz; possibly use
new programming device
(use latest PG version)
2-91
FS Error Messages
F-98
Description
Link error
Block
Remedy
Clear user program,
Reload user program into the PSS
If no remedy helps: contact Pilz;
possibly use new CPU module
or new programming device
.
03
2-92
F-99
Description
Remedy
Please contact Pilz
2-93
FS Error Messages
F-A2
Description
.
Error on PSS (1) DIO T
.
.
03
2-94
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs or
the test pulse wiring?
If no remedy helps: change module
F-A3
Description
Debug error
Remedy
Please contact Pilz.
2-95
FS Error Messages
F-A4
Error no.
01
.
.
.
0D
2-96
Description
Error on word module
Remedy
1.) Tolerance set is too low
2.) Incorrect alignment algorithm
(e.g. match instead of min.- max.)
if there is no error in the
configuration: change module
F-B0
19
.
.
.
1C
1D
1E
.
.
.
26
27
28
.
.
.
30
31
32
.
.
.
5D
Description
Remedy
Please contact Pilz
Restart system
If no remedy helps: change CPU
Please contact Pilz
2-97
FS Error Messages
F-B1
2-98
Description
Synchronisation location
Remedy
Please contact Pilz.
F-B2
Description
Remedy
Please contact Pilz.
2-99
FS Error Messages
F-B3
Description
PII cannot be determined
02
05
06
0B
32
33
34
2-100
Remedy
Increase number of read attempts;
If no remedy helps: change input
module
Increase number of read attempts;
If no remedy helps: change DIF
module
Increase test time in the configurator;
If no remedy helps: contact Pilz
Please contact Pilz.
Increase rnumber of read attempts;
If no remedy helps: change input
module
Increase number of read attempts;
If no remedy helps: change DIF
module
F-B4
Description
Major system error
Remedy
Please contact Pilz.
Programming device
error
0A
Programming device
error
0B
0C
0D
.
.
.
17
18
19
2-101
FS Error Messages
Error no.
1A
1B
1C
1D
1E
Description
DIF has been
configured incorrectly
Alarm-OB has been configured for a
slot that contains no DIF
More alarm-OBs configured than
inputs on DIF
Edge configuration is invalid
1F
20
21
22
23
24
25
26
27
28
2-102
F-B4
Remedy
Check contents of the configurator,
check user program
Check the configuration for the
alarm-OBs and the layout
Check the configuration for the
alarm-OBs
Check the configuration for the
alarm-OBs
Enter the slots for alarm processing
in the configurator in ascending
order
Check the PSS configuration, check
the slots defined for the DIF in the
configurator
Enter alarm-OBs in the configurator
consecutively
Check user program
Enter a slot in the configurator that
is valid
Check the PSS configuration and
adjust or amend the entry in the
configurator to match the
configuration
Correct the number of the test pulse
in the configurator
Correct the entry for the test pulse
number in the configurator
Correct the test pulse allocation in
the configurator
Check configuration and enter the
slot number correctly in the
configurator
F-B4
Error no.
29
Description
Slot number for the word module
is invalid
Remedy
Enter the slot number correctly in
the configurator
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
2-103
FS Error Messages
Error no.
39
Description
Output point is invalid
3B
3C
3D
FS application program
is not loaded
A pulse is testing DI and
DIF inputs configurator
More than 2 DIF modules
in the set layout
Pulse module entered,
but pulse number = FF
Operating system
version is invalid
3E
3F
40
41
42
.
.
.
4E
4F
50
51
2-104
Selective shutdown DB
is not read-only
F-B4
Remedy
Correct the output point in the
configurator
Reload the FS user program
Check the test pulse allocation
Check configurator, amend the set
configuration in the configurator
Check configuration or test pulse
allocation in the configurator
Use correct CPU-module,
program cannot be run on this PSS
Check configuration,
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Change PSS CPU
Check configuration
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Check configuration
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
F-B6
Line number
Block
Description
Programming device error
Remedy
Please contact Pilz.
Possibly use new programming
device (use latest PG version)
2-105
FS Error Messages
F-B7
Description
Communication/transfer
error on the programming
device or system error
Remedy
Reload user program and
transfer to the PSS
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Communication/transfer
error on the programming
device
06
07
08
09
2-106
F-B7
Error no.
0A
.
.
.
0E
0F
10
11
12
13
Description
PG transfer error
Remedy
Reload user program and
transfer to the PSS
If no remedy helps: contact Pilz;
possibly use new programming
device (use latest PG version)
Adjacent CPU has detected an error See error stack
Memory range for user program
Clear memory (Flash-EPROM) ,
is full
reload user program
If no remedy helps: reduce the size of
the user program
Approved block is defective
Obtain the block from the original
disk, relink and transfer to the PSS
DB002 is not read only
Ensure DB 002 is read only
2-107
FS Error Messages
F-B9
2-108
Description
Remedy
Please contact Pilz
F-C2
Error no.
01
Description
.
.
03
Remedy
1.) Check supply voltage to the
module (voltage interrupt?)
2.) Does the test pulse wiring
match the allocation in the
configurator?
3.) Short circuit at the outputs
or to 0 V or 24 V?
4.) Short circuits at the inputs
or the test pulse wiring?
If no remedy helps: change module
2-109
FS Error Messages
F-C4
Error no.
01
.
.
.
0D
2-110
Description
Word module error
F-D0
Description
Signal group deactivated,
error or deadman timer has elapsed
Deadman timer has elapsed
Error timer elapsed
Signal group has been
deactivated by the user
Signal group is to be deactivated
with the same reaction type
Signal group has been
deactivated by the user
Error timer for signal
group is disabled
Remedy
For infomation only
For infomation only
For infomation only
For infomation only
For infomation only
For infomation only
For infomation only
2-111
FS Error Messages
F-D1
2-112
Description
Acknowledgement error
during deactivation
F-D6
Remedy
00
Restart PSS
If message appears regularly: increase
FS and/or ST block run time, reduce
bus load.
If no remedy helps: contact Pilz.
01
02
Restart PSS
If message appears regularly: increase
FS and/or ST block run time, reduce
bus load.
If no remedy helps: contact Pilz.
03
04
2-113
FS Error Messages
F-D6
Remedy
05
06
07
08
09
0B
0C
0E
0F
10
11
12
.
.
15
18
19
1A
1B
2-114
F-D6
Remedy
1C
.
.
1E
1F
20
21
22
23
.
.
29
2A
2-115
FS Error Messages
Notes
2-116
ST Error Messages
S-01
Description
Error has occurred while
clearing the program cartridge
02
03
04
Remedy
Clear user program
If no remedy helps: if present, change
program cartridge, otherwise change
CPU module or PSS.
Clear user program
If no remedy helps: if present, change
program cartridge, otherwise change
CPU module or PSS.
Change CPU module
3-1
ST Error Messages
S-04
3-2
Description
Battery is depleted
Remedy
Replace battery.
When replacing the battery, ensure
data is not lost. The PSS-CPU may
be powered down for a max. 5 min.,
before data is lost.
S-05
Slot
Description
Module configuration error
Remedy
1.) Is the correct module inserted?
2.) Using the programming device,
check the set/true configuration and
either change the module or adjust
the set layout to the true layout
If no remedy helps: change module.
3-3
ST Error Messages
S-06
3-4
Slot
Description
Error on expansion module
Remedy
Check supply voltage to the
expansion rack
If no remedy helps: change module.
S-07
Block ID
Error no.
01
Description
Error detected in at
least one block
02
03
04
05
06
Remedy
Clear defective block(s) and
reload: start program
If error message continues:
clear program cartridge and
download all blocks again
Clear all blocks and transfer again
Clear all blocks and transfer again
Clear all blocks and transfer again
Clear all blocks and transfer again
09
0A
07/08
3-5
ST Error Messages
S-08
Description
Program cartridge was removed
05
Incorrect programming
adapter plugged in
Incorrect program
cartridge type plugged in
No flash-program cartridge in
PSS programming adapter
PSS program cartridge is not valid
06
07
08
09
3-6
Remedy
Insert program cartridge and
restart standard section
Use programming adapter
suitable for PSS
Use correct program cartridge
type
Insert flash-program cartridge into
PSS programming adapter
Program cartridge has been
formatted due to clearing
Program cartridge has been
formatted due to clearing
S-0B
Description
Power supply(s) for expansion
rack not ready for operation in time
for the start of the program
03
Remedy
1.) Check power-LEDs for all power
supplies and switch on those that
are switched off
2.) Check mains voltage
If no remedy helps: change the PSS
standard power supply(s) on the
the expansion rack
1.) Check power-LEDs for all power
supplies and switch on those that
are switched off
2.) Check mains voltage
If no remedy helps: change the PSS
standard power supply(s) on the
the expansion rack
3-7
ST Error Messages
S-0C
Description
Scan time for the ST application
program has been exceeded
03
3-8
Remedy
Search the ST application program
section which has caused the error
and optimise or accelerate the
program. The application program
may be caught in a loop
Optimise or accelerate the ST
application program
S-0F
Error no.
01
Description
There is no XW-module
at the given XW-address
04
05
06
07
09
0A
Remedy
Check the configuration of XW
module with the configuration error
and correct if required or
check the ST user program
for incorrect access address and
corrrect if necessary.
If no remedy helps: change module
Please contact Pilz;
Possibly change the module
Check base address of the module
and correct in DB 005
Limit number of addressable
modules
Check base address of the module
and correct in DB 005
Check the base address for the
modules and correct in DB 005
Check base address of the modules
and correct in DB 005
3-9
S-10
ST Error Messages
3-10
Description
Program cartridge is missing
Remedy
Insert program cartridge
S-20
Description
ST application program was started
ST application program was
stopped
Non-volatile data is invalid
14
Remedy
For information only
For information only
PSS carries out a general reset and
all non-voltatile data is cleared
Change battery in power supply
For infomation only
3-11
S-21
ST Error Messages
3-12
Description
Invalid operand with DEF-command
Invalid operand with DUF-command
Division by 0 during a byte
operation
Dividend too high during a byte
division command
Division by 0 during a word division
command
Dividend too high during a word
division command
Remedy
Rectify ST application program
Rectify ST application program
Rectify ST application program
Reduce dividend
Rectify ST application program
Reduce dividend
S-22
Error no.
01
02
03
04
05
06
09
0A
0D
Description
Command "L DR": Data word lies
outside the current DB
Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Command "L DL": Data word lies
Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "T DR": Data word lies
Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "T DL": Data word lies
Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "AND DR": Data word
Check the length of the current DB,
lies outside the current DB
rectify ST application program
or set correct DB
Command "AND DL": Data word
Check the length of the current DB,
lies outside the current DB
rectify ST application program
or set correct DB
Command "OR DR": Data word lies Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "OR DL": Data word lies Check the length of the current DB,
outside the current DB
rectify ST application program
or set correct DB
Command "XOR DR": Data word
Check the length of the current DB,
lies outside the current DB
rectify ST application program
or set correct DB
3-13
ST Error Messages
Error no.
0E
Description
Command "XOR DL": Data word
lies outside the current DB
0F
10
11
12
13
14
15
16
17
18
3-14
S-22
Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
S-22
Error no.
19
Description
Command "D DR": Data word
lies outside the current DB
1A
1B
1C
1F
20
23
24
30
31
32
Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
3-15
ST Error Messages
Error no.
34
Description
Command "OR DW": Data word
lies outside the current DB
36
37
38
39
3A
3B
3C
3D
3F
41
3-16
S-22
Remedy
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
Check the length of the current DB,
rectify ST application program
or set correct DB
S-22
Error no.
51
52
53
Description
Actual parameter for DR
is invalid
Actual parameter for DL
is invalid
Command "T =para":
DR lies outside the current DB
54
61
62
63
64
65
Remedy
Check actual parameter
rectify ST application program
Check actual parameter
rectify ST application program
Check length of current DB,
rectify ST application program
or set correct DB
Check length of current DB,
rectify ST application program
or set correct DB
Check the length of current DB,
rectify ST application program
or set correct DB
Check the length of current DB,
rectify ST user program
or set correct DB
Check the length of current DB,
rectify ST application program
or set correct DB
Check the length of current DB,
rectify ST application program
or set correct DB
Always select a DB with "A DB"
before the first data word access;
rectify ST application program
3-17
ST Error Messages
S-23
Error no.
01
02
03
04
05
06
11
12
13
21
31
32
33
3-18
Description
Command "T DR":
transferring to read-only DB
Command "T DL":
transferring to read-only DB
Command "I DR":
access to read-only DB
Command "I DL":
access to read-only DB
Command "D DR":
access to read-only DB
Command "D DL":
access to read-only DB
Command "T DW":
access to read-only DB
Command "I DW":
access to read-only DB
Command "D DW":
access to read-only DB
Command "T =para":
byte access to read-only DB
Command "T =para":
word access to read-only DB
Command "I =para":
word access to read-only DB
Command "D =para":
word access to read-only DB
Remedy
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
Remove read-only or select
the correct DB
S-24
Error no.
01
02
03
13
16
17
18
21
22
23
Description
Actual parameter (bit)
lies outside the permitted range
Actual parameter (byte)
lies outside the permitted range
Actual parameter (word)
lies outside the permitted range
Command "SE =para":
Actual parameter lies outside
the permitted range
Command "ZV =para":
Actual parameter lies outside
the permitted range
Command "ZR =para":
Actual parameter lies outside
the permitted range
Command "R =para":
Actual parameter lies outside
the permitted range
Command "T =para":
Byte-actual parameter lies outside
the permitted range
Command "I =para":
Byte-actual parameter lies outside
the permitted range
Command "D =para":
Byte-actual parameter lies outside
the permitted range
Remedy
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
3-19
ST Error Messages
Error no.
31
32
33
34
40
41
42
43
44
45
46
47
48
3-20
Description
Command "T =para":
Word-actual parameter lies outside
the permitted range
Command "I =para":
Word-actual parameter lies outside
the permitted range
Command "D =para":
Word-actual parameter lies outside
the permitted range
Command "A =para":
Actual parameter lies outside
the permitted range
Command "R =para":
Timer number lies outside
the permitted range
Command "R =para":
Counter number lies outside
the permitted range
Command "T =para":
Word-actual parameter lies outside
the permitted range
Command "S =para":
Bit-write access to a reserved range
Command "S =para":
Bit-write access to a
write-protected flag
Command "S =para":
Setting input bit is not permitted
S-24
Remedy
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
S-24
Error no.
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
Description
Command "T =para": Byte
write access to a reserved range
Command "T =para": Byte
write access to a read-only range
Command "T =para": Word
write access to a reserved range
Remedy
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
3-21
ST Error Messages
Error no.
55
Description
Command "I =para":
Incrementing input word
is not permitted
56
57
58
59
5A
5B
5C
5D
5E
5F
3-22
S-24
Remedy
Only an output word can be
decremented, check actual
parameter and rectify
ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Only an output word can be
decremented, check actual
parameter and rectify ST application
program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
Check actual parameter and
rectify ST application program
S-24
Error no.
60
61
62
63
64
65
Description
Command "L =para":
Bit-actual address lies outside
the permitted range
Command "L =para":
Timer address lies outside
the permitted range
Command "L =para":
Counter address lies outside
the permitted range
Command "L =para":
Byte-actual address lies outside
the permitted range
Command "L =para":
Word-actual address lies outside
the permitted range
Command "L =para":
Counter address lies outside
the permitted range
Remedy
Check bit-parameter and
rectify ST application program
Check bit actual parameter and
rectify ST application program
Check bit actual parameter for
rectify ST application program
Check byte parameter and
rectify ST application program
Check word parameter and
rectify ST application program
Check word actual parameter for
rectify ST application program
3-23
S-25
ST Error Messages
Error no.
01
02
03
04
05
13
16
17
18
3-24
Description
An indirect address of
a flag bit lies outside
the permitted range
An indirect address of
a input bit lies outside
the permitted range
An indirect address of
a output bit lies outside
the permitted range
An indirect address of
a timer bit lies outside
the permitted range
An indirect address of
a counter bit lies outside
the permitted range
Command "SE T(...)":
Indirect address of a timer lies
outside the permitted range
Command "ZV Z(...)":
Indirect address of a counter
lies outside the permitted range
Command "ZR Z(...)":
Indirect address of a counter
lies outside the permitted range
Command "R T(...)":
Indirect address of a timer
lies outside the permitted range
Remedy
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
S-25
Error no.
19
20
22
23
31
32
33
35
50
51
Description
Command "R Z(...)":
Indirect address of the counter
lies outside the permitted range
An indirect address of a flag byte
lies outside the permitted range
Remedy
Check which indirect address is
incorrect and rectify the
ST application program
Check which indirect address is
incorrect and rectify the
ST application program
An indirect address of an input byte Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of an output byte Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of a flag word
Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of an input word Check which indirect address is
lies outside the permitted range
incorrect and rectify the
ST application program
An indirect address of an output
Check which indirect address is
word lies outside the permitted
incorrect and rectify the
range
ST application program
An indirect address for a counter
Check which indirect address
word lies outside the permitted
is incorrect for the counter word and
range
rectify the ST application program
Command "I MW(...)":
Check which indirect address
Indirect address for a flag
is incorrect for the flag word in the
word lies outside the permitted
increment command and rectify the
range
ST application program
Command "I AW(...)":
Check which indirect address
Indirect address for an output
is incorrect for the flag word in the
word lies outside the permitted
increment command and rectify the
range
ST application program
3-25
ST Error Messages
Error no.
52
Description
Command "D MW(...)":
Indirect address for a flag word
lies outside the permitted range
53
54
55
56
57
58
59
60
3-26
S-25
Remedy
Check which indirect address
is incorrect for the flag word in the
decrement command and rectify
the ST application program
Check which indirect address
is incorrect for the flag word in the
decrement command and rectify
the ST application program
Check which indirect address
is incorrect for the flag word in the
decrement command and rectify
the ST application program
Check which indirect address
is incorrect for the flag word in the
increment command and rectify
the ST application program
Check which indirect address is
incorrect and rectify ST application
program
Check which indirect address is
incorrect and rectify ST
application program
Check which indirect address is
incorrect and rectify ST
application program
Check which indirect address is
incorrect for the XW-module and
rectify the ST application program
Check which indirect address is
incorrect for the XW-module and
rectify the ST application program
S-26
Error no.
01
Description
OB to be called up is not loaded.
03
05
07
11
12
A DB selected through
parameters does not exist.
An DB selected indirectly
does not exist.
13
Remedy
Reload the OB or
remove the block call-up
Reload the PB or
remove the block call-up
Reload the FB or
remove the block call-up
Reload SB or
remove the block call-up
Reload DB or
remove block call-up
Reload DB or
remove block call-up
Reload DB or
remove block call-up
3-27
S-27
ST Error Messages
06
3-28
Call up block
Block called up
Description
When "CAL FB" was called up,
the formal and actual parameters
do not match (type, number,
sequence)
When "CAL SB" was called up,
the formal and actual parameters
do not match (type, number,
sequence)
Remedy
Adapt call ups to suit the amended
block header
S-28
Description
Nesting level exceeded
by starting an OB (CAL OB)
Nesting level exceeded
by stating a PB (CAL PB)
Nesting level exceeded
by starting an FB (CAL FB)
Nesting level exceeded
by starting an SB (CAL SB)
Remedy
Check the block nesting levels
Reduce the block nesting levels
Check the block nesting levels
Reduce the block nesting levels
Check the block nesting levels
Reduce the block nesting levels
Check the block nesting levels
Reduce the block nesting levels
3-29
ST Error Messages
S-2A
Error no.
01
3-30
Timer number
Block in which the timer is used
Low byte: Block number
High byte: Block type
Description
A timer was started with a
negative value entered in the
accumulator
Remedy
Load a positive value into the
accumulator before the SEcommand
S-76
Line number
BLock ID
Low byte: Block number
High byte: Block type
Error no.
01
Description
Undefinedcode
02
Undefined parameters
03
04
05
06
07
Remedy
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
3-31
ST Error Messages
Error no.
08
Description
Flag byte address is invalid
09
0A
0B
PW address is invalid
0C
0D
0E
0F
11
3-32
S-76
Remedy
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
S-76
Error no.
12
Description
Data block is invalid
13
Undefined parameters
14
16
17
18
19
1A
BE-command is missing
15
Remedy
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
3-33
ST Error Messages
Error no.
1B
1C
1D
1E
1F
Description
Undefined operating
system call up
Link table overflow
Overflow of the execite code
buffer for the ST processor
Too many jumps in the block
24
7F
20
21
22
23
3-34
S-76
Remedy
Remove operating system call-up
from the application program
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Reduce number of jumps
Reduce number of bracket
commands "("
Remove ")"-command
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
Clear all blocks and transfer again
If no remedy helps: contact Pilz
S-77
03
04
Block ID
Description
Too many blocks have been loaded
into the program cartridge
Block length in the block header
does not match the number in the
the data transferred
Block is not an ST block
07
08
09
OB, FB or PB created
in assembler code
Read/Write DB-range is full
05
06
0A
Remedy
Reduce the number of blocks in
the program
Transfer the block again
If no remedy helps: contact Pilz
Create block with ST programming
device and re-send
Rename DB,
create block with ST programming
device and re-send
Set DB to correct length
Remove the interferences from the
transfer cable and re-send
Clear program cartridge and transfer
project once more; possibly reduce
the application program or use
a larger program cartridge
Please contact Pilz.
Create block in PSS code
Reduce the number of read/write
DBs
3-35
ST Error Messages
S-80
3-36
Description
ST section has detected a fatal
error in the operating system
Remedy
Please contact Pilz
S-81
Remedy
ST application program
transferred an invalid parameter to
SB 254
3-37
ST Error Messages
S-83
02
03
3-38
Description
A module called up by the start-up
the start-up manager never issues
ready signal
A module called up by the start-up
manager does not keep to the
time conditions
The start-up manager was offset
to an invalid status
Remedy
Increase ST-block run time
If no remedy helps: contact Pilz
Increase ST block run time
If no remedy helps: contact Pilz
Please contact Pilz
4-1
F-30
Description
Remedy
00
I/O-GroupNo.Device-Adr.
01
4-2
F-31
Description
Remedy
00
I/O-Group-No.
Device-Adr.
01
I/O-Group-No.
Device-Adr.
Error in the LD (PSS caused all Display PSS error stack, see
assigned I/O-Groups to STOP) PSS FS error messages for
error description
02
03
04
05
06
Not assigned
07
Not assigned
08
Item No.* 1
Device-Adr.
09
0A
0B
.
.
0C
*1
Not assigned
Change PSS or PSS CPU
0: I/OD A, 1: I/OD B
4-3
F-31
Description
Remedy
0D
Error in LD (PSS)
4-4
F-32
Description
Remedy
00
I/O-Group-No.
Device-Adr.
4-5
F-33
Description
Remedy
00
I/O-Group-No.
Device-Adr.
01
Device-Adr.
02
Device-Adr.
03
Device-Adr.
04
Device-Adr.
05
Device-Adr
06
Item No.* 1
Device-Adr.
07
Device-Adr.
*1
4-6
0: I/OD A, : I/OD B
F-33
Description
08
I/O-Group-No.
Device-Adr.
09
I/O-Group-No.
Device-Adr.
0A
Domain No.
Device-Adr.
0B
Domain No.
Device-Adr.
0C
Device-Adr
Error in the LD
0D
Device-Adr
Error in the MD
0E
Device-Adr
0F
-Device-Adr
10
Device-Adr
Remedy
4-7
F-33
Description
Remedy
11
Device-Adr.
12
Device-Adr.
Domain-Timeout of the MD
(PSS) too short or an error in
the MD (PSS)
Increase Domain-Timeout in
the configurator or display the
PSS error stack, see PSS
FS-error messages
13
Device-Adr.
Device-Adr.
Change PSS.
21
Not assigned
22
Device-Adr.
Device-Adr.
14
.
.
.
20
23
.
.
.
25
26
4-8
Device-Adr.
Change PSS
F-33
Description
Remedy
27
.
.
.
29
2A
2B
.
.
.
30
Device-Adr.
Device-Adr.
Device-Adr.
31
Device-Adr.
32
Device-Adr.
I/O-Group configuration is
incorrect or the LD is defective
33
Device-Adr.
34
Not assigned
35
Device-Adr.
36
Not assigned
37
Not assigned
38
Device-Adr.
4-9
Description
F-33
Remedy
39
Device-Adr.
3A
Device-Adr.
3B
Device-Adr.
3C
.
.
.
44
Device-Adr.
45
Device-Adr.
46
.
.
.
4C
Device-Adr.
MD configured incorrectly or is
defective
4D
I/O-Group-No.
Device-Adr.
Error in the MD
4E
4F
I/O-Group-No.
Device Adr.
Several devices are on the bus Remove all the devices from
without a device addresss
the bus, connect one device
and establish the address;
then connect the next one,
establish the address etc.
4-10
F-33
Domain-No.
Device-Adr.
Error parameter
Remedy
4-11
Description
00
Not assigned
01
.
.
.
03
04
Not assigned
05
06
Not assigned
07
.
.
.
0D
0E
.
.
.
0F
10
Not assigned
11
4-12
Remedy
F-34
Description
12
.
.
.
1C
Not assigned
1D
1E
.
.
.
2F
30
.
.
.
35
Remedy
46
.
.
.
48
49
36
.
.
.
45
4-13
F-34
Description
4A
.
.
.
4B
4C
.
.
.
4F
50
Remedy
51
52
.
.
.
5B
5C
5D
Device-Adr.
Bus version no.
4-14
5-1
F-01
Remedy
00
.
.
.
04
Internal error
0A
Internal error
0C
.
.
.
10
Internal error
12
.
.
.
14
Internal error
5-2
F-02
Remedy
00
.
.
.
05
Internal error
09
.
.
.
18
Internal error
5-3
F-03
Remedy
00
.
.
.
05
Internal error
06
Internal error
Change device.
07
Internal error
08
.
.
.
0A
Internal error
Change device.
0B
Internal error
0D
.
.
.
0E
Internal error
5-4
F-04
Remedy
00
Memory defective
03
Internal error
Change device.
04
EEPROM defective
Change device.
05
Internal error
Change device.
0A
Internal error
Change device.
0B
EEPROM defective
Change device.
5-5
F-05
Remedy
00
.
.
.
01
Internal error
03
:
.
.
04
Internal error
5-6
F-06
Remedy
00
Internal error
Change device
01
Internal error
02
.
.
.
03
Internal error
Change device.
04
05
Internal error
5-7
F-07
Remedy
01
Internal error
Change device.
0D
.
.
.
0E
Internal error
Change device.
5-8
F-08
Remedy
00
Device switched on
01
Internal error
Change device.
05
Internal error
Change device.
06
Internal error
09
Device switched on
5-9
F-10
Remedy
01
.
.
.
02
Internal error
04
.
.
.
06
Internal error
07
Unable to establish the current Check bus cabling: all specifications in the
transmission rate
SafetyBUS p Installation Manual must be
fulfilled.
If no remedy helps: contact Pilz.
08
Internal error
5-10
F-11
Remedy
00
.
.
.
01
Internal error
5-11
F-12
Remedy
00
Domain-Timeout
01
02
.
.
.
03
04
05
Bus error
06
.
.
.
07
I/O-Group was stopped via the Evaluate error stack of the stated device.
stated Device
5-12
F-12
Remedy
08
09
Bus error
0A
Domain-Timeout
0B
Event-Timeout
0C
0D
Bus error
0E
0F
10
Bus error
5-13
F-13
Remedy
00
5-14
Internal error
F-14
Remedy
00
01
5-15
F-15
Remedy
00
Change device.
01
.
.
.
05
06
5-16
Internal error
F-50
Remedy
01
.
.
.
06
Internal error
07
.
.
.
08
0A
.
.
.
0B
Internal error
0D
Internal error
0F
Internal error
16
Internal error
18
.
.
.
19
Internal error
1C
1D
.
.
.
20
Internal error
5-17
F-50
Remedy
21
Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.
22
.
.
.
.
23
24
Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.
5-18
F-51
Remedy
01
02
04
05
.
.
.
06
08
.
.
.
09
0C
10
.
.
.
.
11
12
.
.
.
1B
5-19
F-51
Remedy
1C
1D
.
.
.
1E
1F
Internal error
20
.
.
.
22
24
25
.
.
.
26
27
28
.
.
.
2A
5-20
5-21
F-55
Remedy
00
01
Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.
02
Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.
03
Internal error
5-22
Change device
F-60
Remedy
00
.
.
.
06
Internal error
5-23
F-61
Remedy
00
.
.
.
01
Change device.
5-24
Internal error
F-62
Remedy
00
.
.
.
03
Internal error
5-25
F-63
Remedy
00
02
03
04
05
06
Internal error
07
Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.
08
Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.
5-26
F-64
Remedy
00
01
02
03
04
05
06
5-27
F-65
Remedy
00
.
.
.
12
Change device.
5-28
Internal error
F-66
Remedy
00
.
.
.
03
Internal error
04
Internal error
Change device.
05
.
.
.
07
Internal error
0A
.
.
.
0D
Internal error
5-29
F-67
5-30
Remedy
F-68
Remedy
00
.
.
.
01
02
03
5-31
F-68
Remedy
04
5-32
F-69
Remedy
00
01
02
Internal error
Change device
03
04
05
Value for Event Timeout is too Amend the time entered for the Event-Timeout
in the configuration to > 10 ms, clear the
low.
program memory and reload the application
program.
06
Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.
5-33
F-81
Remedy
00
.
.
.
09
Internal error
13
.
.
.
14
Internal error
5-34
F-82
Remedy
00
.
.
.
08
Internal error
15
Internal error
19
.
.
.
1A
Internal error
5-35
F-83
Remedy
00
.
.
.
05
Internal error
06
Internal error
Change device.
0C
.
.
.
10
Internal error
5-36
F-84
Remedy
00
Memory defective
01
.
.
.
02
Internal error
Change device.
05
Internal error
Change device.
5-37
F-85
Remedy
00
.
.
.
02
5-38
Internal error
F-88
Remedy
05
Change device.
Internal error
5-39
F-90
Remedy
01
.
.
.
02
Internal error
04
.
.
.
06
Internal error
5-40
F-91
Remedy
00
.
.
.
01
Internal error
5-41
F-92
Remedy
00
Domain-Timeout
01
02
.
.
.
03
04
05
Bus error
06
.
.
.
07
I/O-Group was stopped via the Evaluate error stack of the stated device.
stated Device
5-42
F-92
Remedy
08
09
Bus error
0A
Domain-Timeout
0B
Event-Timeout
0D
Bus error
0E
0F
10
Bus error
5-43
F-93
Remedy
00
5-44
Internal error
F-95
Remedy
If this message appears frequently, even
though the Device-Address has not been
changed manually: Change device.
5-45
F-D0
Remedy
01
.
.
.
06
Internal error
07
.
.
.
08
0A
.
.
.
0B
Internal error
0D
Internal error
0F
Internal error
16
Internal error
18
.
.
.
19
Internal error
1C
1D
.
.
.
20
Internal error
5-46
F-D0
Remedy
21
Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.
22
.
.
.
.
23
24
Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.
5-47
F-D1
Remedy
01
02
04
05
.
.
.
06
08
.
.
.
09
0C
10
.
.
.
.
11
12
.
.
.
1B
5-48
F-D1
Remedy
1C
1D
.
.
.
1E
1F
Internal error
23
24
25
.
.
.
26
27
28
.
.
2A
20
.
.
22
5-49
5-50
F-D5
Remedy
03
Change device
Internal error
5-51
F-E0
Remedy
00
.
.
.
01
Internal error
03
.
.
.
07
Internal error
5-52
F-E1
Remedy
00
.
.
.
01
Change device.
Internal error
5-53
F-E2
Remedy
00
Internal error
02
.
.
.
04
Internal error
5-54
F-E3
Remedy
00
01
Internal error
02
03
04
05
06
Internal error
07
Value for Event Timeout is too Amend the time entered for the Event-Timeout
low.
in the configuration to > 10 ms, clear the
program memory and reload the application
program.
5-55
F-E3
Remedy
08
Value for Event Timeout is too Amend the time entered for the Event-Timeout
high.
in the configuration to < 500 ms, clear the
program memory and reload the application
program.
5-56
F-E4
Remedy
00
01
02
03
04
05
06
5-57
F-E5
Remedy
00
Internal error
Change device.
02
.
.
.
12
Internal error
Change device.
5-58
F-E6
Remedy
00
.
.
.
03
Internal error
04
Internal error
Change device.
05
.
.
.
0D
Internal error
5-59
F-E7
5-60
Remedy
F-E8
Remedy
01
02
03
5-61
F-E8
Remedy
04
5-62
F-E9
Remedy
01
02
Internal error
Change Device
03
5-63
Notes
5-64
An error on the module PSS(1) AI U5I1 is displayed (as with all module
errors) using the error class 06. The error numbers 48 ... 51 in this error class
relate to the AI module (see also PSS FS error messages).
If an error occurs, an additional parameter is given for the PSS(1) AI U5I1
that describes the error in more detail. The meaning of these parameters is
described in this chapter.
6-1
Error class 06
Error
no.
48
.
.
.
51
6-2
Error parameter
Description
Remedy
01... 03
Parameter is invalid
04 ... 09
Match error
0A
Parameter is invalid
0B
Module is defective
Change module
0C ... 17
Match error
18
19
Not assigned
1A
Match error
1B
Not assigned
1C
1D, 1E
System error
Change module
1F
20
System error
Change module
21
Not assigned
22
Parameter is invalid
23 ... 7F
Not assigned
80 ... A1
System error
FE
FF
System error
AUS
B
L
BR
CH
DK
Pilz Ges.m.b.H.
Modecenterstrae 14
1030 Wien
Austria
Telephone (01) 7 98 62 63-0
Telefax
(01) 7 98 62 64
E-Mail:
pilz@pilz.at
Pilz Australia
Industrial Automation LP.
9/475 Blackburn Road
Mt. Waverley, Melbourne VIC 3149
Australia
Telephone (03) 95 44 63 00
Telefax
(03) 95 44 63 11
E-Mail:
safety@pilz.com.au
Pilz Belgium
BC Building
lndustriezone lII
lndustrielaan 4
9320 Erembodegem
Belgium
Telephone (0 53) 83 66 70
Telefax
(0 53) 83 89 58
E-Mail:
info@pilz.be
Pilz do Brasil Sistemas Eletrnicos
Industriais Ltda.
Rua rtico, 123 - Jd. do Mar
09726-300
So Bernardo do Campo - SP
Brazil
Telephone (11) 43 37-12 41
Telefax
(11) 43 37-12 42
E-Mail:
pilz@pilzbr.com.br
Pilz lndustrieelektronik GmbH
Gewerbepark Hintermttli
Postfach 6
5506 Mgenwil
Switzerland
Telephone (0 62) 8 89 79 30
Telefax
(0 62) 8 89 79 40
E-Mail:
pilz@pilz.ch
Headquarters:
Pilz GmbH & Co.
Felix-Wankel-Strae 2
73760 Ostfildern
Germany
Telephone (07 11) 34 09-0
Telefax
(07 11) 34 09-1 33
E-Mail:
pilz.gmbh@pilz.de
Pilz Skandinavien KS
Ellegaardvej 25 L
6400 Sonderborg
Denmark
Telephone 74 43 63 32
Telefax
74 43 63 42
E-Mail:
pilz@pilz.dk
Pilz lndustrieelektronik S.L.
Edificio Tilma
Avda. Sant Juli 1
08400 Granollers
Spain
Telephone (93) 8 49 74 33
Telefax
(93) 8 49 75 44
E-Mail:
central@pilzspain.com
FIN
Pilz Skandinavien KS
Pakilantie 61
00660 Helsinki
Finland
Telephone (09) 27 09 37 00
Telefax
(09) 27 09 37 09
E-Mail:
pilz.sk@kolumbus.fi
GB
IRL
MEX
...
www
NL
Pilz Nederland
Postbus 186
4130 ED Vianen
Netherlands
Telephone (03 47) 32 04 77
Telefax
(03 47) 32 04 85
E-Mail:
info@pilz.nl
Pilz Industrieelektronik S.L.
Apartado 2028
2706-909 Colares
Portugal
Telephone (21) 9 28 91 09
Telefax
(21) 9 28 91 13
E-Mail:
pilz@esoterica.pt
PRC
ROK
Pilz Skandinavien KS
Energigatan 10 B
43437 Kungsbacka
Sweden
Telephone (03 00) 1 39 90
Telefax
(03 00) 3 07 40
E-Mail:
pilz@tripnet.se
SGP
USA
Pilz LP
7150 Commerce Boulevard
Canton
Michigan 48187
USA
Telephone (7 34) 3 54-02 72
Telefax
(7 34) 3 54-33 55
E-Mail:
info@pilzusa.com