Preface

The grooming of an engineering student is incomplete without proper


exposure to the industry.we are completing our Bachelors degree in
Electrical Engineering at Rachna College of Engineering and Technology,

Gujranwala. We are students of final year in specialization of Power


engineering therefore, we have to conduct an internship for learning
purposes.
This report documents the work done and learning during the
summer internship at National Dispatch and Transmission Company Ltd.
220/132 kV grid station Gakkhar. The internship report contains and
overview of the internship company and the activities, tasks that we have
worked on during our internship. This report shall give and overview of tasks
completed and technical details we have learnt during the period of
internship and the discussions and overview of lectures taken.

We have tried our best to write the complete knowledge we gain during this
internship in report.

ACKNOWLEDGMENTS

The work culture in grid station really motivates.we could not have done this
work without the lots of help we received cheerfully from whole NTDCL.
Everybody is such a friendly and cheerful companion here that work stress is
never comes in way.Special thanks to Sir Akbar Ali and Sir Mansor for providing
the nice ideas to work upon. Their lectures were very informative and made
clear a lot of our concepts about field work and related to our Electrical
Engineering perspective.

Contents:

Why there is a need of Grid Stations?


An introduction to NTDCL Gakkhar Grid Station
Single line diagram
Explanation of Equipment used
Transmission line
Isolators
Terminal Tower
Wave Trap
CCVT
Earthing Switch
Current Transformer (CT)
Potential Transformer (PT)
Circuit Breaker (CB)
Auto Transformer
Operation
Limitations
Parallel Operation of transformer
Vector group of transformer
PROTECTION OF GRID
Transformer
DC Protection

Why there is a need of Grid Stations?


An electrical grid (also referred to as an electricity grid or electric grid) is an
interconnected network for delivering electricity from suppliers to consumers. It
consists of generating stations that produce electrical power, high-voltage transmission
lines that carry power from distant sources to demand centers, and distribution lines
that connect individual customers.
Power stations may be located near a fuel source, at a dam site, or to take advantage of
renewable energy sources, and are often located away from heavily populated areas.
They are usually quite large to take advantage of the economies of scale. The electric
power which is generated is stepped up to a higher voltage-at which it connects to the
transmission network.
When voltage level of a power is increased, the electric current of the power is reduced
which causes reduction in ohmic or 2 losses in the system, reduction in cross sectional
area of the conductor i.e. reduction in capital cost of the system and it also improves the
voltage regulation of the system(as low I results in low voltage drop in the line). Because
of these, low level power must be stepped up for efficient electrical power transmission.
The transmission network will move the power long distances, sometimes across
international boundaries, until it reaches its wholesale customer (usually the company
that owns the local distribution network).
On arrival at a substation, the power will be stepped down from a transmission level
voltage to a distribution level voltage. As it exits the substation, it enters the distribution
wiring. Finally, upon arrival at the service location, the power is stepped down again from
the distribution voltage to the required service voltage(s).

Candle light dinners are most enjoyable when they are not forced. In todays modern
world of electrical home appliances we realize that poor maintenance of the electricity
supply may mean a loss of a few expensive appliances alongside added inconvenience.
Thus in order to keep your passionately light decorated houses glimmering there are
grid stations to ensure high reliability power supply.
There are different kinds of Grid stations such as:
66 KV Grid Station
132KV Grid Station
220 KV Grid Station
500 KV Grid Station

In this report only 220 KV Grid Station is discussed.

GRID STATION GAKHAR


132kv Ghakhar G/Stn. which was commissioned during 01/77 was upgraded to
220KV level with commissioning on 11.06.1982. 220KV Ghakhar G/Stn. has 04Nos.
160MV, 220/132KV Power T/Fs and 02 Nos. 26 MVA, 132/11KV Power T/Fs
installed at the G/Stn. The G/Stn. is being fed from Mangla Power House through 02
Nos. 220KV D/C T/Lines. This G/S is also connected with 220KV G/S Sialkot through
Single Circuit and 500KV Nokhar and Mangla Power House through IN Out
arrangement.

An introduction to 220/132 kV NTDCL Grid Station (Gakkhar)


This is 220/132 kV grid station, located at Gakkhar (near Gujranwala), under NTDCL (National
Transmission and Dispatch Company Ltd.). The lines coming from MANGLA-I, MANGLA-II and
NOKHAR (500/220 kV grid) and outgoing to SIALKOT. (Although, any of lines can be used to
send or receive power so, dont confuse yourself with the direction of arrows in single line diagramas shown in fig (1) below). It uses double bus scheme on both of its 220 and 132 kV sides with
sectionalizing scheme on 132 kV side. Which will be discussed below in single line diagram.
Single line diagram:In power engineering, a one-line diagram or single-line diagram (SLD) is a
simplified notation for representing a three-phase power system. Electrical elements,
such as circuit breakers, transformers, capacitors, bus bars, and conductors are
shown by standardized schematic symbols. Instead of representing each of three
phases with a separate line or terminal, only one conductor is represented. It is a
form of block diagram graphically depicting the paths for power flow between entities
of the system. Elements on the diagram do not represent the physical size or location
of the electrical equipment.

Fig (1) single line diagram of grid station

There are some conventions and symbols for single line diagram, such as: the
colour of different potential lines are different. Which are given below:
500kV

Brown

220kV

Green

132kV

Red

11kV

Blue

Same like, there are symbols for equipment to show on single line diagram for
complete understanding. Some of them are shown below:
The equipment in single line diagram are denoted by some of symbols which
are given in LEGEND with it. Here, the circuit breakers are represented by Q and
for understanding its potential and position, there are also keywords, like:
132kV

EnQn

220kV

DnQn

500kV

BnQn

Where, n=1, 2, 3.
Which represent the location and exact name of the circuit breaker and make ease
in communication.
Some other key words are:
L.A

Lightning Arresters

W.T

Wave Trap

C.T

Current Transformer

P.T

Potential Transformer

Others are represented by their symbols. Shown in fig.


The single line diagram of this grid station is shown below. According to which
there are total four lines, coming form MANGLA-I, MANGLA-II and NOKHAR and going
to SIALKOT. On each of line (entering or leaving) there are some common equipment
installed such as: Instrument Transformers (C.T & P.T), Wave Trap, CCVT,
Isolators, Grounding Switches, Lighting Arresters.
Bus bars:
There is double bus bar scheme in grid station. The advantage of this is that,
when there is any fault or any maintenance issue, we can convert whole load on any
one bus bar without any interruption in supply of power. Also there is a bus coupler,
which couples both of the buses. In normal conditions, the load is distributed on both
of the buses, using this bus coupler. Although, each of bus has capacity to handle the
complete load. During maintenance or any fault on any of the bus, the isolator of bus
coupler is set such that the load is transferred on the healthy bus.
Sectionalizer:On 132kV side, the two buses are sectionalized in two section each by using
the SECTIONALIZER. These sections are made to increase the reliability of the buses
and the transformers. This is also used for parallel operation of transformer (which
will be discussed later) and coupling the transformers for the power to transformer,
of same rating, percentage impedance and ratio. The buses are divided in many
sections, if there is fault in any of the sections, this section can be isolated from the
system without interruption in other sections.

Explanation of Equipment used:


Transmission line:
There are three types of transmission line:

Short Transmission Line (up to 80 Km)


Medium Transmission Line
(80-240 Km)
Long Transmission Line (above 240 Km)

Effects on the transmission line:


The transmission lines have following three major effects:Ferranti effect:
When the voltage at the receiving end is increased as compared to
sending end voltage at normal load, called as Ferranti Effect. This is due to the
capacitance between line to line and line to ground. As with increase in length
of transmission line, the capacitance of line increases and inductance reduces,
so due to this capacitance the Ferranti effect is more in Long and transmission
lines as compared to Short transmission line as capacitance is negligible in
short transmission lines.
Skin Effect:
Due to frequency in alternating current, current starts to flow on the
surface of conductor instead of using whole conductor area. Due to this used
area of conductor is reduced and resistance faced by current is increased. So
due to this effect our conductor is wasted as it is not fully utilized.
To eliminate this effect we use stranded conductors.
Corona Effect:
Electric power transmission practically deals in the bulk transfer of
electrical energy, from generating stations situated many kilometers away from
the main consumption centers or the cities. For this reason the long distance
transmission cables are of utmost necessity for effective power transfer, which
in-evidently results in huge losses across the system. Minimizing those has
been a major challenge for power engineers of late and to do that one should
have a clear understanding of the type and nature of losses. One of them being
the corona effect in power system.
For corona effect to occur effectively, two factors here are of prime importance as
mentioned below:1) Alternating electrical potential difference must be supplied across the line.

2) The spacing of the conductors, must be large enough compared to the line
diameter.

Insulators:
The overhead line conductors should be supported on the poles or towers in
such a way that currents from conductors do not flow to earth through supports i.e.
line conductors must be properly insulated from supports. The insulator provides
necessary insulation between line conductors and supports and thus prevent any
leakage current form conductor to earth.
The insulators are made up of Porcelain, Glass, Steatite and special types of
materials.
Types:

Pin type
(up to 33kV)
Suspension type
(above 33kV)
Strain Type insulator
Shackle type insulator

Terminal Tower:
The tower at the end of transmission line i.e. at the start of the grid station is
known as the terminal tower. This tower carry the power line entering the grid station
having strain insulators on it. Its a double circuit tower having two parallel power
lines on it with a SKY WIRE or EARTHED WIRE or OPGW (optical ground wire)
which is used for the protection of the transmission system from lightning strokes and
any of lightning falls on the transmission system, is grounded through this wire as
this wire is on the top of the tower.
The insulators used for insulation of line with ground (tower) and with each
other, depend upon the potential in the line. The string of insulator discs (made of
porcelain, glass or such type of insulating material) are made for this purpose,
according to the potential of the lines. For a rough estimate of the voltage of line
passing can be made by counting the number of plates of the insulator on the tower,
as they are designed and installed according to voltage level. The rough estimate is
like- if you multiply the number of discs with number 15, the answer will provide the
voltage in kV.

Wave Trap:
For the communication between two grid station and between the main head
office and the grid station, NTDCL has its own communication system on the
transmission
line.
As
the
communication requires
very
high
frequency
signals
(>500kHz) so, to separate these
signals from the power signals
(low frequency) we need an
equipment known as Wave Trap,
which is a high pass filter and
allows to pass high frequency
signals
only
to
the
communication equipment. The
equipment or the system used for
it is called as POWER LINE
CARRIER (PLC).

CCVT:
This is Capacitor Coupling Transformer. As the power signal is of low frequency
(50 Hz) so to pass this CCVT is used which is a low pass filter and always gives output
110 volts. Its working is same as the Potential Transformer with addition of low pass
filter circuit.

Isolator:
Isolators are provided for isolation from live parts for the purpose of maintenance.
Isolators are located at either side of the circuit breaker. Isolators are operated
under no load. If it is operated under load, there will be arc between the contacts
of the isolator. Isolator does not have any rating for current breaking or current
making. Isolators are interlocked with circuit breakers
Types of Isolators
are
1. Central rotating,
horizontal swing
2. Centre-Break
3. Vertical swing
4. Pantograph type

Earthing
Switch:
Earthing switches are mounted on the base of mainly line side isolator. Earthing
switches are normally vertically break switches. Earthing arms (contact arm of
earthing switch) are normally aligned horizontally at off condition. During
switching on operation, these earthing arms
rotate and move to vertical
position
and
make
contact
with
earth female contacts fitted at
the top of the post insulator
stack of isolator at its outgoing
side. The earthing arms are so
interlocked with main isolator
moving contacts that it can be
closed only when the main
contacts of isolator are in open
position. Similarly the main
isolator contacts can be closed
only when the earthing arms
are in open position.

Current Transformer:
For the measurement of the current in the line, the
current transformer (C.T) is used. It is an Instrument
transformer which brings current in the range to be
measured. It comes in different primary to secondary ratio
(800/1 or 800/5).
For the safety precaution, the secondary of C.T must
not be opened as on the secondary side there are a large
amount of voltage as current is very low, so due to high
potential arc will produce and CT will burst out. Care must
be taken that the secondary of a current transformer is not
disconnected from its load while current is in the primary,
as the transformer secondary will attempt to continue
driving current across the effectively infinite impedance up
to its core saturation voltage. This may produce a high
voltage across the open secondary into the range of several
kilovolts, causing arcing, compromising operator and
equipment safety, or permanently affect the accuracy of the
transformer.
The accuracy of a CT is directly related to a number of factors including:

Burden

Burden class/saturation class

Rating factor

Load

External electromagnetic fields

Temperature and Physical configuration.

The selected tap, for multi-ratio CTs

Phase change

Maintenance Test:
For the maintenance of the current transformer, two tests are performed,

Capacitance test
The capacitance between HV and LV side of transformer is checked. From
the reading of the instrument we multiply it with the place of knob reading
to get the capacitance. Then percentage depreciation factor is
measured according to the temperature. If the temperature is different form
the ambient (20 degree C) then multiplied by the correction factor provide
in table with the instrument manual.

The DF must be below 1 (or may be up to 1.2) for the best operation.

Insulation test:
Insulation of transformer is checked using MEGGAR (mega ohm-meter).
The MEGGAR is connected between HV side and ground and the resistance
is measured.
Generally, for one kV, 1Mohm is suitable resistance. i.e. for 132kV the
insulation must be about 132 mega ohm.
The calculations were taken at atm temperature and after correction factor
for 20 degree Celsius were applied and result was 5000 MOHM. Which is
suitable for working.

Potential transformer (PT):Voltage transformers are used to step down the voltage for measurement,
protection and control. Voltage transformers are of two types.
1. Electromagnetic type
2. Capacitive VT located on the feeder side
of the Circuit Breaker.
The primary of potential transformer must not
be short as it is connected in parallel and there
will be a burst and PT could be damaged.
A voltage transformer theory or potential
transformer theory is just like a theory of
general purpose step down transformer.
Primary of this transformer is connected across
the phase and ground. Just like the transformer
used for stepping down purpose, potential
transformer i.e. PT has lower turns winding at
its secondary. The system voltage is applied
across the terminals of primary winding of that
transformer, and then proportionate secondary
voltage appears across
the
secondary
terminals of the PT.

The secondary voltage of the PT is generally 110 V. In an ideal potential transformer


or voltage transformer, when rated burden gets connected across the secondary;
the ratio of primary and secondary voltages of transformer is equal to the turn ratio
and furthermore, the two terminal voltages are in precise phase opposite to each other.
But in actual transformer, there must be an error in the voltage ratio as well as in the
phase angle between primary and secondary voltages.

Circuit Breaker:
Circuit breaker is device used to break the circuit in case of excess amount of
current passing (due to any fault or other). It is protective device for the protection
of all equipment in case of fault that can damage the other devices. Here, the circuit
breakers used are SF6 circuit
breakers.
Sulfur Hexafluoride is an
excellent gaseous dielectric for
high voltage power applications.
It has been used extensively in
high voltage circuit breakers and
other switchgears employed by
the power industry. Application
for SF6 include gas insulated
transmission lines and gas
insulated power distributions.
The
combined
electrical,
physical, chemical and thermal
properties
offer
many
advantages when used in power
switchgears.
Some
of
the
outstanding properties of this
are below:

Very
high
dielectric
strength.
Very unique arc-quenching ability.
Very excellent thermal stability.
Very good thermal conductivity.

There is a tank of SF6 having specific pressure for the operation of circuit breaker
below which CB is unable to operate and there is pressure gauge for it showing and
monitoring the pressure in tank. When the pressure goes down, it causes a specific
relay to operate for alarm purposes.

MAINTAINANCE TEST:
For the checking the health of circuit breakers, three following tests are
performed annually:1. SF6 purity test
For the best working of circuit breaker the gas should be pure. For this
purpose, test is performed at regular intervals to check the purity.
2. Contact resistance test :
Due to operation of circuit breaker, contacts of breaker become rough
due to arc between them. So, the resistance of contacts increases above limit
resulting very increase in I2R losses. So, the resistance of contacts are checked
annually and it must be in micro ohms and if exceed, these must be replaced.
This is off load test.
3. Timing test.
The opening and closing the contacts of circuit breaker matters a lot. So,
there must be a little time for circuit breaker to sense and break the circuit.
For this timing test is performed using a test set model number TM1600. This
test is off load test i.e. the circuit breaker is disconnected from the circuit and
then test is performed. For the best operation of circuit breaker, following must
be full filled:
Opening time must be between 28-30 msec.
Closing time must be about 60 msec.

AUTO-TRANSFORMER:An autotransformer is an electrical transformer with only one winding. The


"auto" (Greek for "self") prefix refers to the single coil acting on itself and not to any
kind of automatic mechanism. In an autotransformer, portions of the same winding
act as both the primary and secondary sides
of the transformer. The winding has at least
three taps where electrical connections are
made.
Autotransformers
have
the
advantages of often being smaller, lighter,
and cheaper than typical dual-winding
transformers, but the disadvantage of not
providing
electrical
isolation.
Other
advantages of autotransformers include
lower leakage reactance, lower losses, lower
excitation current, and increased KVA rating.

Autotransformers are often used to step up or step down voltages in the 110115120 V range and voltages in the 220-230-240 volt rangefor example. Providing
110
V or 120 V (with taps) from 230 V input, allowing equipment designed for 100 or
120 volts to be used with a 230 volt supply.

OPERATION:An autotransformer has a single winding with two end terminals, and one or more
terminals at intermediate tap points, or a transformer in which the primary and
secondary coils have part or all of their turns in common. The primary voltage is
applied across two of the terminals, and the secondary voltage taken from two
terminals, almost always having one terminal in common with the primary voltage.
The primary and secondary circuits therefore have a number of windings turns in
common. Since the volts-per-turn is the same in both windings, each develops a
voltage in proportion to its number of turns. In an autotransformer part of the current
flows directly from the input to the output, and only part is transferred inductively,
allowing a smaller, lighter, cheaper core to be used as well as requiring only a single
winding. However the voltage and current ratio of autotransformers can be
formulated the same as other two-winding transformers.

As in a two-winding transformer, the ratio of secondary to primary voltages is equal


to the ratio of the number of turns of the winding they connect to. For example,
connecting the load between the middle and bottom of the autotransformer will
reduce the voltage by 50%. Depending on the application, that portion of the winding
used solely in the higher-voltage (lower current) portion may be wound with wire of
a smaller gauge, though the entire winding is directly connected.
LIMITAION:An autotransformer does not provide electrical isolation between its windings as an
ordinary transformer does; if the neutral side of the input is not at ground voltage,
the neutral side of the output will not be either. A failure of the insulation of the
windings of an autotransformer can result in full input voltage applied to the output.
Also, a break in the part of the winding that is used as both primary and secondary
will result in the transformer acting as an inductor in series with the load (which under
light load conditions may result in near full input voltage being applied to the output).
These are important safety considerations when deciding to use an autotransformer
in a given application.
Because it requires both fewer windings and a smaller core, an autotransformer for
power applications is typically lighter and less costly than a two-winding transformer,
up to a voltage ratio of about 3:1; beyond that range, a two-winding transformer is
usually more economical.
In three phase power transmission applications, autotransformers have the limitations
of not suppressing harmonic currents and as acting as another source of ground
fault currents. A large three-phase autotransformer may have a "buried" delta
winding, not connected to the outside of the tank, to absorb some harmonic currents.
In practice, losses mean that both standard transformers and autotransformers are
not perfectly reversible; one designed for stepping down a voltage will deliver slightly
less voltage than required if it is used to step up. The difference is usually slight
enough to allow reversal where the actual voltage level is not critical.
Like multiple-winding transformers, autotransformers use time-varying magnetic
fields to transfer power. They require alternating currents to operate properly and will
not function on direct current.

Parallel Operation of transformer


To connect two or more transformers with each other, the operation is followed
is called as the parallel operation of transformer. Parallel operation is carried out to
increase the reliability of the system in such a way that the total load on both is equal
to the maximum rating of one transformer. That is, in case one transformer goes
down for some reason, the one can handle the load without interruption. In normal

conditions, both transformers are sharing the load and hence the reliability increases
and the life of transformer.
For the parallel operation of transformers, three following conditions must be
satisfied:
All transformers should have
1. Same impedance drops.
2. Same turn ratios.
3. Same ratings.
Transformers connected in parallel have the same voltage on each primary and
the same voltage on each secondary. The difference in the voltage between the
primary and secondary windings is the turn ratios. For these terminal voltages to be
the same for the paralleled transformers, their impedance drops must be identical.
Therefore, under any condition of load, the current will be divided such that the
product of impedance and current in one transformer is equal to the product of
impedance and current in the other. Also, if the turn ratios of the transformers are
different, but the primary and secondary terminal voltages are the same in both
transformers, then circulating currents must flow between the transformers, even at
no load.

Typically, transformers should not be operated in parallel when:


The division of load is such that, with the total load current equal to the combined
kVA rating of the transformers, one of the transformers is overloaded.
The no-load circulating currents in any transformer exceed 10% of the full load
rating
The combination of the circulating currents and full load current exceed the full load
rating of either transformer.
Following table (1) shows conditions for transformers under which we can use
transformers in parallel operation:-

Vector group of transformer:In electrical engineering, a vector group is the International Electro technical
Commission (IEC) method of categorizing the high voltage (HV) windings and low
voltage (LV) winding configurations of three-phase transformers. The vector group
designation also indicates the windings configurations and the difference in phase
angle between them.

Symbol designation:-

Y = HV side connected in star


y= LV side connected in star
D= HV side connected in delta
d= LV side connected in delta
N= neutral connected to HV side
n= neural connected to LV side

17

At the end there may be integers like 1, 2, 3 12 for phase displacement between
LV and HV side. E.g.
1=300 , 2=600

,3=900, 12=3600or 00

For example the vector group of auto transformer is Yyan0


This shows that this transformer is connected in star in HV and LV side and a for
auto transformer and n shows that neutral grounded to LV side and 0 shows that
phase difference between HV and LV is zero degree.

PROTECTION OF GRID:Transformer protection:Transformer protection mainly divided into two major groups:
1. Mechanical Protection
2. Electrical Protection
Mechanical Protection:
Mechanically operated protection is called as mechanical protection which do
not have any concern with electric signal to operate. Some are following:
A) MAIN BUCHHOLZ RELAY:
It is gas operated, gas actuated relay. When there is any fault with the
windings of transformer. i.e. it is short from any part, spark will be produced
and it will decompose the oil in the transformer due to which gases will
produced and goes upward to the conservator tank where, there is buchholz
relay main and conservator tank and due to pressure of gases, relay operated.
B) Pressure relief relay:
This relay is operated due to sudden change of pressure of gases within
the tank. When winding is short from more than one place and more arc is
produced and large pressure is created in the tank.
C) ON LOAD TAP CHANGER RELAY:
This is for the protection of the tap changer. If there is any short circuit
or any fault in tap changer this relay operated.

18

D) WINDING TEMPERATURE RELAY:


This relay is used to maintain the temperature of winding of transformer
at safe level. When more current passes from the winding, it causes to increase
the temperature of winding hence, this current is used to maintain the
temperature of winding. From the current, we can find the voltage drop of it:
V=IR
This voltage is applied to the relay and used to operate it. When the voltage
drop increase form set level it will operate.
This relay has four taps during working. At first step when temperature
rises to about 60 percent of total it activate FAN group 1 if temperature further
rises, it activate FAN GROUP 2 on further increase in temperature, alarm will
be activated and at last relay is operated to trip circuit breakers of both sides.
E) OIL TEMERATURE AND OIL LEVEL RELAY:
These relays are used to check and maintain the temperature and level
of in transformer. These relays use some kind of sensors to sense the
temperature and oil level of main tank of transformer and operate after a set
level.
Electrical Protection:
A) Main Differential Relay:
Differential relay takes the difference of currents between primary and
secondary side of transformer- through the CT of both sides. If there is some
kind of difference between them, it operates the circuit breaker taking it as
fault. As when fault occur on either side of transformer, current increases and
hence the difference of current increases so relay will operate the circuit
breakers.

Ispill = IHV - ILV


To make zero the difference between them, Matching CTs are also placed after
them which make both currents equal for difference. When about 0.1A
difference occurs, main differential relay trip the circuit.
B) HV and LV Over Current Relay:
These relays are used to protect the HV and LV side of transformer in
case of high current. By the use of CT on both sides, it senses the current and
operates accordingly.

19

C) Tertiary Over Current Relay:


This relay is for the protection of the tertiary windings of transformerwhich is used to remove the harmonics in windings. When there is over current
flows in tertiary winding of transformer, this operates the circuit breakers of
transformer.
D) Breaker Failure Relay:
This relay operates when there is fault in breaker or when breaker is not
working properly. This checks the connection of circuit breaker and in case of
fault there, it operates.
E) Pole Discrepancy Relay:
For circuit breaker to be operated properly, it is necessary condition that
all the three poles must be operated at the same time. If all the three poles
fail to cut off or come to circuit at same time, fault occurs. This relay ensures
that, all the poles are operating, during circuit breaker operation. It operates
with the time delay of less than 300msec. This relay avoid that only one or two
phases are open during steady state operation.
F) Over Excitation Relay:
Over excitation of transformer can occur whenever ratio of per unit
voltage to per unit frequency at secondary terminals exceeds its rating. That
is, as we know that the core of transformer is excited and de-excited on each
cycle and due to the voltage applied. This excitation is given by formula
E =4.44 f N
From this, it can be seen that is directly related to the ratio of (V/f). So, to
avoid to exceed this ratio for specific transformer, a relay is set at point above
which it operates and trips the circuit.

DC Protection:The protection of grid is done by the DC source. The 220kV protection


is done at 220 volts while 132kV protection is carried out at 110 volts. For these
voltages, there is a battery room where batteries are placed. Each cell is of
2volts and each plate of cell has capacity of 300Ah. So, for 220 volts, 110 such
cells are placed in series and for 110 volts, 55 such cells are placed. These are
lead-acid batteries and use electrolyte in them.

20

For the maintenance of these batteries, the specific gravity of electrolyte


is checked regularly by the instrument called as Hydrometer. Another thing
for their maintenance is that they are charged properly from a panel providing
suitable voltage for charging. Normally, float charging is done in normal days
but once a week, boast charging also applied on these batteries for their good
health.