Updating nanoLC and

nanoNavigator
Firmware and software updates to the nanoLC

AUTOMATION
Technical Note
2630_en_A
1

PHOENIX CONTACT - 10/2008

Description

From time to time Phoenix Contact will have updates


available for the nanoLine products. To determine if an
update is available for either the nanoNavigator software or
the nanoLC firmware, go to www.PhoenixContact.com and
download the update(s).

4.

From the nanoNavigator Startup dialog box, click the


Run Connection Wizard button. The nanoLC
Connection Wizard dialog box displays the version of
the connected device (nanoLC) and any applicable
options installed.

nanoNavigator Software Update

nanoNavigator software updates are self-extracting


installation files. To install the update, double-click on the file
and install the new nanoNavigator.
1. Download the desired nanoNavigator release from
www.PhoenixContact.com and save the file on the PC
hard drive.
2. Double-click on the file to run the installation file. Follow
any instructions that appear on the screen.

nanoLC Firmware Update

nanoLC firmware updates are *.exe files that can only be


used within the nanoNavigator software. To update the
nanoLC, perform the following:
1. Download the nanoLC firmware from
www.PhoenixContact.com and save the file on the PC
hard drive.
2. Connect the nanoLC to the PC.
3. Start the nanoNavigator software.

Figure 1

nanoLC Connection Wizard dialog box


If the file is executing outside of nanoNavigator,
the files will be extracted but they will not update
the nanoLC.

Updating nanoLC and nanoNavigator

5.

Click the nanoLC Utilities button to open the nanoLC


Utilities dialog box.

Figure 2
6.

8.

With the selected file displayed in the Update package


field, click the Start button to begin downloading the
file to the nanoLC.

Update Firmware button

Click the Update Firmware button. A dialog box opens


that allows browsing to the downloaded file.

Figure 5

9.

Figure 3
7.

Update nanoLC Firmware dialog box with file


selected

After clicking the Start button, a message box asks the


user if an update to the display firmware used in the
Operator Panel is desired. This message also displays
the current firmware version of the Operator Panel and
the firmware version available in the downloaded file.

Update nanoLC Firmware dialog box

Enter the path and file name in the Update package


field or click the Browse button to navigate to the file.
Highlight the file, and click the Open button to return to
the Update nanoLC Firmware dialog box.

Figure 6

Update nanoLC Firmware message box

To update the display (Operator Panel) firmware and


base unit firmware, click the Yes button.
To update only the base unit firmware, click the No
button.
To continue, follow either Display and Base Unit
Update procedure or the Base Unit Update Only
procedure listed on the next page.
Display and Base Unit Update
1.

Figure 4

2630_en_A

If the Yes button is clicked at the update display


firmware prompt, the display firmware begins the
update. After the display update is complete, a
message box appears prompting the user to cycle

Open dialog box

PHOENIX CONTACT

Updating nanoLC and nanoNavigator

power to the nanoLC (see Figure 7). Cycle the power on


the nanoLC now, and then click the OK button to
continue, or click the Cancel button to exit the
process.

2.

When the update is complete, a message box appears


to inform the user the update was successful. Turn the
power to the nanoLC off and back on to use the new,
updated firmware in the controller.

Figure 10
Figure 7

3.
2.
3.

After the run light on the nanoLC stops blinking, press


the OK button to update the nanoLC base firmware.
When the update is complete, a message box appears
stating that the update was successful. Turn the power
to the nanoLC off and back on to use the new, updated
firmware in the controller and Operator Panel.

Figure 8
4.

Update successful message box

Cycle power message prompt

Update successful message box

Click the OK button when power is restored and to


resume normal operation of nanoNavigator.

Clearing the Project from the


nanoLC.

Normally it is not necessary to clear a project from the


nanoLC because when a new project is downloaded, the
existing project is overwritten. However, a project can be
manually cleared by performing the following:
1. Connect the nanoLC to the PC.
2. Start the nanoNavigator software.
3. From the nanoNavigator Startup dialog box, click the
Run Connection Wizard button.

Click the OK button when power is restored and to


resume normal operation of nanoNavigator.

Base Unit Update Only


1.

If the No button is clicked at the update display


firmware prompt (see Figure 6), a message box asks
the user if an update to the base firmware is desired.
This message also displays the current firmware
version of the base unit and the firmware version
available in the downloaded file. Click the Yes button
to load the update or the No button to exit the process.

Figure 9

Update the base firmware prompt

Figure 11

2630_en_A

nanoLC Connection Wizard dialog box

PHOENIX CONTACT

Updating nanoLC and nanoNavigator

4.

Click the nanoLC Utilities button.

Figure 12
5.

Clear Project button

Click the Yes button to clear the project from the


nanoLC or click the Cancel button to exit.

Figure 13

2630_en_A

Clear the project message box

PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany Phone: +49-(0) 5235-3-00
PHOENIX CONTACT P.O.Box 4100 Harrisburg PA 17111-0100 USA Phone: +717-944-1300
www.phoenixcontact.com