Sei sulla pagina 1di 12

ASHIDA Electronics Pvt. Ltd.

Plot no. A-308, Road no. 21, Wagle Industrial Estate, Thane (W) 400604.INDIA.

0091-22-6597 1076/77/78, 2582 7524/25/26

Fax: 0091-22-2580 4262. E-mail: ashida@vsnl.com

ASHIDA RELAY TESTING


UNIT
TYPE: ARTU/S

REV

DESCRIPTION

DATE

CHK. BY

APPD. BY

01

Ashida Relay Testing Unit ARTU/S

19.12.11

jtd

SMK

User Notice
Ashida Electronics (P) Ltd. Reserve all right to make improvements in the
products described in this manual at any time and without notice. All rights are
reserved. No part of this manual may be reproduce, copied, translated or
transmitted in any form or by any means without the prior written permission of
Ashida Electronics (p.) Ltd. Information in this manual is intended to be accurate
and reliable. However Ashida assumes no responsibility for its use; or for any
infringements of rights of third parties which may result from its use.

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 2 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

INDEX
No

Topic

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
9.0
10.0

General
Features
Technical Specification
Front Plate
Details of Front Plate
V / I / Meter
Drawing - Test Set up For Current Relay
Testing Procedure for IDMT type Current Relay
Pickup Test
Time Test
Mechanical Details
Revision Note

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page No
4
4
4
6
7
8
9
10
10
10
11
12

Page 3 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

1.0 General :
The ARTU/S unit is specially designed to suit relay-testing requirements of
power station testing engineers. The ARTU/S is designed to give maximum
numbers of functional units in single cabinet. The unit is having modern hi-tech
digital indicating instrument which give high stability and accuracy The
ARTU/S is a complete relay testing unit for testing of traction TSS relays. It
has all necessary functions for relay testing viz. auxiliary power supply,
variable current source up to 100A, Variable voltage source, Time Interval
Meter up to 1ms resolution etc.
2.0 Features:

Variable AC current: - 0-100 AMP with 150VA.

Variable AC voltage: - 0-230VAC.

In- built auxiliary power supply: - 30 / 110 / 220 V DC.

Micro- controller based time measuring unit with 1ms resolution.

Combine Digital AC Voltmeter (For V1), AC Ameter (For I1).

Specially designed for testing off all types of IDMT Over Current
Relay/ Under - Over Voltage Relay / Auxiliary relay.

3.0 Technical Specification:


Input Main: Normal 220V AC mains. Three terminal instrument socket on
back side.
OUTPUTS:
1.

Variable AC current SOURCE (I1): 0 - 100Amps. Adjustable. VA Burden:


150 VA.

Low Range : 0 10 Amp.

High Range : 0 100 Amp.

2.

Variable AC Voltage SOURCE (V1): 0 - 230 Volts. AC / 2A

3.

Fixed DC Voltage SOURCE : 30V DC/2A; 110VDC/0.6A; 220V DC / 0.3A

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 4 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

MEASUREMENT:
1.

2.

On V / I / Meter:

AC Current: 0 - 100 A. (Multiplication Factor of 10 For HIGH Range)


[Measuring I/Ps I1].

AC Voltage: 0 - 230 VAC [Measuring I/Ps V1].

On Ashida Relay Time Measuring Unit:

3.

Time Measurement :- 0-99999 sec with resolution of 1ms auto


range accuracy:- +/- 1ms

Dimensions: 390x 264 x 325 mm (L x W x H)

Note: All Meters are calibrated against 0.1 % accuracy basic standard
instrument.
AC variable output voltage or current (Adjustable) can not be used
simultaneously. Both are varied by same Variac- control

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 5 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

5.0 Details of Front Plate:


Details of Front Plate along with description & Function of each Push
button/ indicator/knob/Meters.
Sr. No.

Functions

Description

1.

MAINS SWITCH

Power ON switch for Relay testing unit.

2.

V-I CONTROL

Variac for controlling AC voltage and


Current

3.

V / I / METER

AC Current meter 0-20 A for 10A range.


For 100A range reading X10 (I1).
AC Volt meter 0 230 V (V1).

4.

COM / 10A / 100A (I1)

COM - 10A
COM - 100A

5.

A.C VOLTAGE (V1)

Terminal for AC Voltage O/P.

6.

TIMER

Time Measuring Counter 1ms to 99999


Seconds Auto range selection.

7.

RESET

Reset Switch For Time Measuring unit.

8.

TIMER SWITCH

ON /OFF Switch For Time Measuring unit


section.

9.

START

Start Push Button for Time Measuring unit.

10.

STOP

Stop Push Button for Time Measuring unit.

11.

NO/NC SELECT
(Start)

Select the relay contact condition for


START. Accordingly Normally open /
Normally closed position are selected.

12.

NO/NC SELECT
(Stop)

Select the relay contact condition for STOP.


Accordingly Normally open / Normally
closed position are selected.

13.

START TERMINAL

Terminal to start the Time Measuring


Counter

14.

STOP TERMINAL

Terminal to stop the Time Measuring


Counter

15.

FIXED DC SWITCH

Voltage selector Switch for DC Fixed


Voltage Output.

16.

30 / 110 / 220V

Fixed DC Voltage outputs.

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 7 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

6.0 V / I / Meter: CONT.

I1

V1

V/I/

METER

I1 = 00.00 V1 = 000.0
I2 = 00.00 V2 = 000.0
Angle = 000.0 Lead

I2

V2

I1 = Measured Current of Variable AC current section (I1).


V1 = Measured AC Voltage of Variable AC current section (V1).

Calibration Of meter: Cont.: -For adjusting the intensity of the font background.
I1 & V1 to be use for calibration of respective Measurements.

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 8 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

8.0 Testing Procedure for IDMT type Current Relay


8.1 Pickup Test:

Connect the Relay to ARTU/S unit as shown in Diagram.


Connect appropriate DC supply to Relay from Fixed DC Voltage O/P
terminals (30).

Connect Mains to ATRU/S unit.

Switch ON Mains Switch (2) Timer ON switch

Start the Timer and start increasing the current using V-I Control (2)
and observe the PKP indication of the relay.

Note down the reading for I1 on V/I/ Meter.

Repeat procedure for other I/Ps and other settings.

8.2 Time Test:


Keep relay on desired setting.

Connect Alarm contact of the relay to STOP terminal (14).


Adjust current to required value using V-I control (2) by setting the
timer.

Switch ON Timer Switch (8) and press START push button (9), this
will automatically inject the current to the relay.

Timer will start counting the time delay.

Timer will stop counting as soon as relay gets the trip command.

Note down the time value.

Repeat the procedure for different settings.

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 10 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11

10.0 Revision Note


Revision No.

Date

Revision Note

01

20.12.11

Original Revision

ASHIDA Electronics Pvt. Ltd.


Ashida Relay Testing Unit ARTU/S

Page 12 of 12
Ref.: ARTU/S_01
Rev: 01 Dt.: 20.12.11