Sei sulla pagina 1di 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land
Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC


CORSAN CORVIAM JV
Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

CONTRACT NO.: 95/2012

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2

INSPECTION AND TEST PLAN

CLEARING AND GRUBBING


DOCUMENT No.: KAS-CC JV/BS2P2/ITP/QA/001

Prepared

Approved

Date: 18/08/14

Date: 18/08/14

Antonio Toms Gonzlez Losa

Miguel Angel Lorente Snchez

QA/QC Manager

Project Director

RECORD OF MODIFICATIONS
Rev. Section Modified
00

INITIAL ISSUE

Description of the modification


FOR ENGINEER APPROVAL

Date

18/08/2014

EMPLOYER

ENGINEER

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

INSPECTION CODE:

BS2P2 - Dualization of Bibbid-Sur Roa


INSPECTION AND TEST PLAN

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

W Witness Point

CLEARING AND GRUBBING

S - Surveillance

NIR No Inspection Requeste

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.

STANDARDS

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

Indust
Park

Subcont Product

Survey

Quality Engineer Frequency

NOTES/
ACCEPTANCE CRITERIA

FIRST PART _ ICL001.1

0.

ITP SCOPE

1.

Setting Out

2.

Equipment

INSPECTION CODE:

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
KAS-CC
JV/BS2P2/MS/Q
A/002
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
KAS-CC
JV/BS2P2/MS/Q
A/002

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

This Sub-section describes removal and satisfactory


disposal of all vegetation, surface debris and scattered
stones and rocks within the limits of the actual road width
(including the toes of fill and cut slopes and an additional
5m wide band from both sides), easement areas and
borrow pits.

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Survey report

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Daily report

W Witness Point

S - Surveillance

100%

Right of way (ROW) properly marked as per drawings.

100%

In accordance to Method Statement and Planning

NIR No Inspection Requested


Page 3 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

3.

3.1

3.2

Vegetation
removal

Engineer
communication for
designation

Clearance

INSPECTION CODE:

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.

STANDARDS

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
KAS-CC
JV/BS2P2/MS/Q
A/002
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
KAS-CC
JV/BS2P2/MS/Q
A/002
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
KAS-CC
JV/BS2P2/MS/Q
A/002

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Work Inspection
Request

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Daily report

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

Quality Engineer Frequency

NOTES/
ACCEPTANCE CRITERIA

100%

Engineer will designate all trees, shrubs, plants,


vegetation, etc and other items that are to remain within
the right-of-way (ROW). JV shall carefully preserve all
such items from damage or defacement. Trees to be
removed and delivered for replanting shall be carefully
handled.

100%

All surface objects, trees, stumps, roots, stones and rocks


(up to 0.2 cu.m. or 500 kg individual size or weight), and
other protruding obstructions not designated to be
retained shall be cleared or grubbed to ground level.
Nonperishable solid objects (such as boulders, rocks,
concrete blocks, etc.) which will be a minimum of 2m
below the sub-grade or finished ground level may be left
undisturbed at the Engineers discretion. If such
nonperishable objects are encountered within 2m below
the sub-grade or finished ground level, they will be
removed and considered as unsuitable material.

NIR No Inspection Requested


Page 4 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

3.3

4.

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.

Disposal of historic
artefacts

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-section 2.1
KAS-CC
JV/BS2P2/MS/Q
A/002

Hole backfilling
and compaction

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

INSPECTION CODE:

STANDARDS

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Daily report

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

Quality Engineer Frequency

100%

NOTES/
ACCEPTANCE CRITERIA
Certain materials arising from the site clearance and
excavation are to remain the property of the Employer. All
fossils, antiquities and other objects of interest or value
which may be found or uncovered on the site shall remain
or become the property of the Employer and upon
discovery at such an object the Contractor shall forthwith:
i. Endeavour not to disturb or damage the object
ii. Cease work which would endanger the object or
prevent or impede its removal
iii. Inform the Engineer immediately of the discovery and
precise location of the object.

NIR No Inspection Requested


Page 5 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

4.1

4.2

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.

Material for backfill

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

Layer execution

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

STANDARDS

AASHTO M145

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Daily report
Test reports

KAS-CC
JV/BS2P2/ICL/QA/0
01.1
Daily report
Test reports

Indust
Park

Subcont Product

Survey

Quality Engineer Frequency

NOTES/
ACCEPTANCE CRITERIA

100%

Material fulfilling the following general requirements and


previously approved (ICL001.2 signed and material
submittal approved):
AASHTO M145 types A-1, A-2-4, A-2-5 or A3, if this kind
of material is not available soil types A-2-6, A-2-7, A-4, A5 are accepted.
In addition to both cases, soils shall comply with:
Maximum dry density not less than 1.7 (AASHTO T-180
Method D).
Organic matter not more than 5% (AASHTO T-267)
Gypsum content not more than 5%.
Maximum size not more than 1/2 of the layer thickness
Plasticity Index (P.I.) less than 20%
4-day soaked C.B.R. should not be less than 8% (AASHTO
T-193) when compacted at 100% maximum dry density in
accordance with AASHTO T-180 Method D.

100%

Material shall be placed in horizontal layers not exceeding


200 mm compacted thickness, compacted to at least
90% modified maximum density for the full depth of
embankment; except for the 600 mm of embankment
material immediately below the sub-grade layer that shall
be compacted to at least 95% modified maximum density.
Moisture content shall be within plus or minus 2% of
optimum at the time of compaction. Layer shall be
approved prior to placing the next one.

SECOND PART _ ICL001.2

INSPECTION CODE:

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

W Witness Point

S - Surveillance

NIR No Inspection Requested


Page 6 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

5.

5.1

Identification
Tests

Identification tests.
GRADATION.

INSPECTION CODE:

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.

STANDARDS

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

AASHTO M145
AASHTO T146
AASHTO T27
AASHTO T11
AASHTO T89
AASHTO T90
AASHTO T180
Method D
AASHTO T193

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

AASHTO M145
AASHTO T146
AASHTO T27
AASHTO T11

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.2

KAS-CC
JV/BS2P2/ICL/QA/0
01.2
Test reports

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

Quality Engineer Frequency

NOTES/
ACCEPTANCE CRITERIA

1 per
source
Prior to use
and 5000
3
m

Type A1 soil: Passing 0.425 mm (No.40) sieve, 50% max;


passing 0.075 mm (No. 200) sieve, 25% max.
Type A3 soil: Passing 0.425 mm (No.40) sieve, 51% min;
passing 0.075 mm (No. 200) sieve, 10% max.
Type A2-4 soil: Passing 0.075 mm (No. 200) sieve, 35%
max.
Type A2-5 soil: Passing 0.075 mm (No. 200) sieve, 35%
1 per
max.
source
Type A2-6 soil: Passing 0.075 mm (No. 200) sieve, 35%
and 5000 max.
m3.
Type A2-7 soil: Passing 0.075 mm (No. 200) sieve, 35%
max.
Type A4 soil: Passing 0.075 mm (No. 200) sieve, 36%
min.
Type A5 soil: Passing 0.075 mm (No. 200) sieve, 36%
min.
Maximum size for all types described avobe not more than
1/2 of the layer thickness

NIR No Inspection Requested


Page 7 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

5.2

5.3

Identification tests.
LIQUID LIMIT

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

Special
Specification.
Clause 2.2.2.10.
Page 27
Identification tests.
Standard
PLASTIC LIMIT AND Specifications.
PLASTICITY INDEX
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

INSPECTION CODE:

STANDARDS

AASHTO M145
AASHTO T146
AASHTO T89

AASHTO M145
AASHTO T146
AASHTO T90

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.2
Test reports

KAS-CC
JV/BS2P2/ICL/QA/0
01.2
Test reports

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

NOTES/
ACCEPTANCE CRITERIA

Quality Engineer Frequency

Type
Type
Type
Type
Type
Type

A1 soil: Nil
A3 soil: Nil
A2-4 soil: 40
A2-5 soil: 41
A2-6 soil: 40
A2-7 soil: 41

1 per
source
and 5000
m3.

Material under 600 mm below subgrade layer:


Type A1 soil: Plasticity index, 6 max
Type A3 soil: Plasticity index, non plastic (NP).
Type A2-4 soil: Plasticity index, 10 max.
Type A2-5 soil: Plasticity index, 10 max.
1 per
Type A2-6 soil: Plasticity index, 11 min. and 20 max.
source
Type A2-7 soil: Plasticity index, 11 min. and 20 max.
and 5000 Material within 600 mm below subgrade:
m3.
Type A1 soil: Plasticity index, 6 max
Type A3 soil: Plasticity index, non plastic (NP).
Type A2-4 soil: Plasticity index, 10 max.
Type A2-5 soil: Plasticity index, 10 max.
Type A2-6 soil: Plasticity index, 11 min. and 5 max.
Type A2-7 soil: Plasticity index, 11 min. and 5 max.

max.
min.
max.
min.

NIR No Inspection Requested


Page 8 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

5.4

Identification tests.
MAXIMUM DRY
DENSITY AND
OPTIMUM
MOISTURE

5.5

Identification tests.
GYPSUM CONTENT

5.6

Identification tests.
C.B.R. (4 day
soaked)

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
BS2P2-MS-KCC
JV-001
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

STANDARDS

AASHTO T146
AASHTO T180
Method D

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.2
Test reports

KAS-CC
JV/BS2P2/ICL/QA/0
01.2
Test reports

AASHTO T146
AASHTO T180
Method D
AASHTO T193

CLEARING AND GRUBBING

KAS-CC
JV/BS2P2/ICL/QA/0
01.2
Test reports

Indust
Park

Subcont Product

Survey

Quality Engineer Frequency

NOTES/
ACCEPTANCE CRITERIA

1 per
source
1.7 min.
and 5000
3
m

1 per
source
5% max.
and 5000
m3

1 per
source
and 5000
m3

Material under 600 mm below subgrade layer: 8 min.


when compacted at 100% MDD.
Material within 600 mm below subgrade: 15 min when
compacted to 95% MDD. If rockfill is used for the bottom
400 mm depth then these requirements shall apply to the
top 200 mm depth below the sub-grade layer.

THIRD PART _ ICL001.3

INSPECTION CODE:

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

W Witness Point

S - Surveillance

NIR No Inspection Requested


Page 9 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

6.

6.1

Control Tests

Control tests.
GRADATION.

INSPECTION CODE:

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.

STANDARDS

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

AASHTO M145
AASHTO T146
AASHTO T27
AASHTO T11
AASHTO T89
AASHTO T90

Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

AASHTO M145
AASHTO T146
AASHTO T27
AASHTO T11

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.3
Test reports

KAS-CC
JV/BS2P2/ICL/QA/0
01.3
Test reports

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

Quality Engineer Frequency

NOTES/
ACCEPTANCE CRITERIA

1 every
3000 m3

1 every
3000 m3

Type A1 soil: Passing 0.425 mm (No.40) sieve, 50% max;


passing 0.075 mm (No. 200) sieve, 25% max.
Type A3 soil: Passing 0.425 mm (No.40) sieve, 51% min;
passing 0.075 mm (No. 200) sieve, 10% max.
Type A2-4 soil: Passing 0.075 mm (No. 200) sieve, 35%
max.
Type A2-5 soil: Passing 0.075 mm (No. 200) sieve, 35%
max.
Type A2-6 soil: Passing 0.075 mm (No. 200) sieve, 35%
max.
Type A2-7 soil: Passing 0.075 mm (No. 200) sieve, 35%
max.
Type A4 soil: Passing 0.075 mm (No. 200) sieve, 36%
min.
Type A5 soil: Passing 0.075 mm (No. 200) sieve, 36%
min.
Maximum size for all types described avobe not more than
1/2 of the layer thickness

NIR No Inspection Requested


Page 10 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

6.2

6.3

Control tests.
LIQUID LIMIT

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

Special
Specification.
Clause 2.2.2.10.
Page 27
Control tests.
Standard
PLASTIC LIMIT AND Specifications.
PLASTICITY INEDX
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

INSPECTION CODE:

STANDARDS

AASHTO M145
AASHTO T146
AASHTO T89

AASHTO M145
AASHTO T146
AASHTO T90

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.3
Test reports

KAS-CC
JV/BS2P2/ICL/QA/0
01.3
Test reports

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

NOTES/
ACCEPTANCE CRITERIA

Quality Engineer Frequency

1 every
3000 m3

Type
Type
Type
Type
Type
Type

A1 soil: Nil
A3 soil: Nil
A2-4 soil: 40
A2-5 soil: 41
A2-6 soil: 40
A2-7 soil: 41

1 every
3000 m3

Material under 600 mm below subgrade layer:


Type A1 soil: Plasticity index, 6 max
Type A3 soil: Plasticity index, non plastic (NP).
Type A2-4 soil: Plasticity index, 10 max.
Type A2-5 soil: Plasticity index, 10 max.
Type A2-6 soil: Plasticity index, 11 min. and 20 max.
Type A2-7 soil: Plasticity index, 11 min. and 20 max.
Material within 600 mm below subgrade:
Type A1 soil: Plasticity index, 6 max
Type A3 soil: Plasticity index, non plastic (NP).
Type A2-4 soil: Plasticity index, 10 max.
Type A2-5 soil: Plasticity index, 10 max.
Type A2-6 soil: Plasticity index, 11 min. and 5 max.
Type A2-7 soil: Plasticity index, 11 min. and 5 max.

max.
min.
max.
min.

NIR No Inspection Requested


Page 11 of 12

EMPLOYER

ENGINEER

CONTRACTOR

Ministry of Transport & Communications


Directorate General of Roads & Land Transport
P.O.Box27, P.C.114
Sultanate of Oman

COWI & Partners LLC


P.O.Box2115, P.C.112
Sultanate of Oman

Khalid Bin Ahmed & Sons LLC CORSAN CORVIAM JV


Al Azaiba
P.O. Box723, P.C.130
Sultanate of Oman

Contract No.: 95/2012


DOC No: KAS-CC
JV/SB2P2/ITP/QA/001 Rev.00

ITEM OF
INSPECTION

6.4

Control tests.
FIELD DENSITY
AND MOISTURE

INSPECTION CODE:

BS2P2 - Dualization of Bibbid-Sur Road, Section 2, Part 2


INSPECTION AND TEST PLAN

REFERENCE DOCUMENTS
SPEC.
Special
Specification.
Clause 2.2.2.10.
Page 27
Standard
Specifications.
Sub-sections
2.1 and 2.5
KAS-CC
JV/BS2P2/MS/Q
A/002

STANDARDS

ASTM D
1556 or
ASTM D 2167 or
BS 1377 Part 9.

H Hold Point

Form No.: KAS-CC/SB2P2/OP/QA/01.06

CLEARING AND GRUBBING

Date: 18/08/2014

TYPE OF INSPECTION AND FREQUENCY / INSPECTION PARTY


FOLLOW-UP
DOCUMENTS

KAS-CC
JV/BS2P2/ICL/QA/0
01.3
Test reports

W Witness Point

Indust
Park

Subcont Product

S - Surveillance

Survey

Quality Engineer Frequency

Every
1500 m2
or 100 m,
whichever
is less.

NOTES/
ACCEPTANCE CRITERIA

Soil type materials shall be compacted to at least 90%


modified maximum density for the full depth of
embankment; except for the 600 mm of embankment
material immediately below the sub-grade layer that shall
be compacted to at least 95% modified maximum density.
Moisture content shall be within plus or minus 2% of
optimum at the time of compaction.

NIR No Inspection Requested


Page 12 of 12