Thermofluids Lab-MEC 554/ LS 2/ Rev.

02-20012

TITLE : Variation In Refrigeration Coefficient Of Performance At Various


Operating Condition
1.0 INTRODUCTION
Heat flows in the direction of decreasing the temperature which is from high
temperature regions to low temperature regions. This heat transfer process occurs in nature
without requiring any devices. But the reverse process cannot occur by itself. The transfer
of heat from a low temperature region to a high temperature one requires special devices
called refrigerators. Refrigerators are cyclic devices and the working fluid used in the
refrigeration is called refrigerants.

Another device that transfers heat from a low temperature medium to a high
temperature one is the heat pump. Refrigerators and heat pumps are essentially the same
device but differ in terms of objectives. The objective of the refrigerator is to maintain the
refrigerated space at a low temperature by removing heat from it. Discharging this heat to
higher temperature medium is merely necessary part of the operation, not the purpose. The
objective of a heat pump is to maintain a heated space at a high temperature. This is
accomplished by absorbing heat from a low temperature source, such as well water or cold
outside air in winter, and supplying this heat to a warmer medium such as a house.

Refrigeration is used widely in various applications from industrial to domestic


situations, mainly for the storage and transport of perishable foodstuffs and chemical
substances. It has the prime function to remove heat from a low temperature region, and it
can also be applied as a heat pump for supplying heat to a region of high temperature.

2.0 OBJECTIVE
To investigate the variation of Coefficient of Performance (COPR) of a vapor compression
refrigeration system at different cooling load.

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

3.0 THEORY
The Carnot cycle is a totally reversible cycle that consists of two reversible
isothermal and two isentropic processes. It has the maximum thermal efficiency for given
temperature limits and it serves as a standard against which actual power cycles can be
compared. The reversed Carnot cycle is the most efficient refrigeration cycle operating
between two specified temperature levels. But however, this cycle cannot be approximated
in the actual devices and is not a realistic model for refrigeration cycles due to difficulty in
maintaining isothermal condition during the heat absorption and heat rejection processes.

A refrigeration cycle works to lower and maintain the temperature of a controlled space by
heat transfer from a low to a high temperature region.
High Temperature Reservoir, TH

QH

Wnet

QL
Low Temperature Reservoir, TL

Refrigeration duty is another term for the cooling effect of the refrigeration system,
which is the rate of heat being removed from the low temperature region with specified
evaporation and condensation temperatures. The unit for duty measurements is in Watts
(for 1 ton of refrigeration = 3517W).

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

3.1

The Vapor Compression Cycle

An ideal refrigeration system follows the theoretical Reversed Carnot Cycle


process. In practical refrigerators, compression and expansion of a gas and vapor mixture
presents practical problems in the compressor and expander. Therefore, in practical
refrigeration, compression usually takes place in the superheated condition and a throttling
process is substituted for the isentropic expansion.

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

In an ideal vapor-compression refrigeration cycle, The refrigerant enters the


condenser as superheated vapor at state 1 and leaves as saturated liquid at state 2 as a result
of heat rejection to the surroundings. The temperature of the refrigerant at this state is still
above the temperature of the surroundings. The saturated liquid refrigerant at state 2 is
throttled to the evaporator pressure by passing it through an expansion valve or capillary
tube. The temperature of the refrigerant drops below the temperature of the refrigerated
space during this process.
The refrigerant enters the evaporator at state 3 as a low quality saturated mixture,
and it completely evaporates by absorbing heat from the refrigerated space. The refrigerant
leaves the evaporator as saturated vapor. Then the refrigerant enters the compressor at state
4 as saturated vapor and is compressed isentropically back to the condenser pressure. The
temperature of the refrigerant increases during this isentropic compression process to well
above the temperature of the surrounding medium.
The cycle :
1 2 Condensation of the high pressure vapour during which heat is transferred to the
high temperature region.
2 3 Adiabatic throttling of the condensed vapour from the condensing to the
evaporating pressure.
3 4 Evaporation of the low pressure liquid during which heat is absorbed from the low
temperature source.
4 1 Isentropic compression of the vapour, from the evaporating to the condensing
pressures.

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

Energy Transfers Analysis


Compressor
q4-1 = h4 h1 + w4-1
If compression is adiabatic, q4-1 = 0, and w4-1 = h1 h4 = wcomp
Power requirement, P = (h1 h4), where is the flow rate of working fluid per unit
time.
Condenser
q1-2 = h2 h1 + w
w = 0, therefore q1-2 = h2 h1 and rate of heat rejection Q1-2 = ( h2 h1 )

Expansion Valve
q2-3 = h3 h2 + w
w = 0, therefore q 2-3 = h2 h3 and process is assumed adiabatic q 0
therefore h2 = h3

Evaporator
q34 = h4 h3 + w
w = 0 therefore q34 = h4 h3 and rate of heat absorbed Q34 = ( h4 h3 )
Coefficient of Perfomance, COPref:
COPref =

h h3
q3 4
= 4
h1 h4
w

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

4.0 EQUIPMENT
TH Series Computer Linked Refrigeration Unit (Edibon).

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

5.0 PROCEDURES
6a) Condenser-water and evaporator-water
a. Water is selected as a heat source by opening valves AVS-4 and AVS-5.Then
START is clicked
b. The water flow rate is adjusted at the condenser to 5 L/m and 3 L/m at the
evaporator (evaporator load).
c. Then COMPRESSOR is clicked
d. When the system is stabilized, the data is recorded by click START SAVING
e. The sampling rate is set at 120 second per sample.
f. The data for six minutes is recorded (3 samples @ 360 second). STOP
SAVING
g. Then evaporator load is increased to 5 L/m and step (c) to step (f) is repeated.
6b) Condenser-water and evaporator-air
a. Air is selected as a heat source by opening valves AVS-3 and AVS-5.Then
START is clicked.
b. The water flow rate is adjusted at the condenser to 5 L/m and the air flow of the
evaporator is adjusted until 50% of the maximal flow (evaporator load).
c. Then COMPRESSOR is clicked.
d. When the system is stabilized, the data is recorded by click START SAVING
e. The sampling rate is set at 120 second per sample.
f. The data for six minutes is recorded (3 samples @ 360 second). STOP
SAVING
g. Then evaporator load is increased to 100% and step (c) to step (f) is repeated.
6c) Condenser-air and evaporator-air
a. Air is selected as a heat source by opening valves AVS-3 and AVS-6. Then
START is clicked
b. The air flow of the condenser is adjusted to maximum flow (100%) and 50% of
the maximal flow at the evaporator (evaporator load).
c. Then COMPRESSOR is clicked.
d. When the system is stabilized, the data is recorded by click START SAVING
e. The sampling rate is set at 120 second per sample.
f. The data is recorded for six minutes (3 samples @ 360 second). STOP
SAVING
g. Then the evaporator load is increased to 100% and step (c) to step (f) is
recorded.
6d) Condenser-air and evaporator-water
a. Water is selected as a heat source by opening valves AVS-4 and AVS-6.Then
START is clicked.
b. The air flow of the condenser is adjusted to maximum flow (100%) and the
water flow rate is adjusted at the evaporator to 3 L/m (evaporator load).
c. Then COMPRESSOR is clicked.
d. When the system is stabilized, the data is reorded by click START SAVING
e. The sampling rate is set at 120 second per sample.
f. The data is recorded for six minutes (3 samples @ 360 second). STOP
SAVING
g. Then the evaporator load is increased to 5 L/m and step (c) to step (f) is
repeated.
7

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

6.0 DATA AND RESULTS

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

table

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

Result summary table


Time (s)

Exp #

Vref
(m3/s)

v2 (table)
(m3/kg)

mref (kg/s)
= Vref/v2

h3 (kJ/kg)

h4 (kJ/kg)

Qevap (kW)
= mref (h4 h3)

COP =
Qevap/ (SW1/1000)

120

0.003

1.006*10-3

2.982

54.688

2451.0

7145.802

14.55

240

0.003

1.008*10-3

2.976

54.688
29.303

2470.1

7263.812

15.03

360

0.003

1.008*10-3

2.976

29.303

2470.1

7263.812

15.29
14.96

Average COP
a
120

0.005

1.008*10-3

4.960

`29.303

2470.1

12106.353

25.27

240

0.005

1.008*10-3

4.960

29.303

2470.1

12106.353

25.43

360

0.005

1.008*10-3

4.960

29.303

2470.1

12106.353

25.48

Average COP

25.39

120

0.0015

0.0199

0.075

225.94

2345.5

158.967

0.33

240

0.0015

0.0199

0.075

225.94

2357.5

159.867

0.33

360

0.0015

0.0199

0.075

225.94

2357.5

159.867

0.33
0.33

Average COP
b
120

0.003

0.0199

0.151

251.42

2354.5

317.565

0.66

240

0.003

0.0173

0.173

251.42

2345.5

363.832

0.75

360

0.003

0.0173

0.173

251.42

2345.5

363.832

0.75

Average COP

0.72

120

0.0015

0.0199

0.075

251.42

2345.5

157.056

0.35

240

0.0015

0.0199

0.075

251.42

2357.5

157.956

0.33

360

0.0015

0.0173

0.085

251.42

2357.5

179.017

0.37
0.35

Average COP
c
120

0.003

0.0199

0.151

251.42

2354.5

317.565

0.65

240

0.003

0.0173

0.173

251.42

2345.5

363.833

0.74

360

0.003

0.0173

0.173

251.42

2345.5

363.833

0.73
0.71

Average COP
120

0.003

1.008*10-3

2.976

54.688

2459.5

7156.721

14.91

240

0.003

1.010*10-3

2.970

54.688

2459.5

7156.721

14.97

360

0.003

1.010*10-3

2.970

54.688

2459.5

7156.721

14.91
14.931

Average COP

d
120

0.005

1.008*10-3

4.960

54.688

2459.5

7156.721

14.91

240

0.005

1.010*10-3

4.950

54.688

2459.5

7156.721

14.97

360

0.005

1.010*10-3

4.950

54.688

2459.5

7156.721

14.91

Average COP

10

14.93

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

7. RESULTS
Sample Calculations
a) Refrigerant mass flow rate,
From the experiment we can get the Volume flow rate, which is 3L/s and converted to
0.003 m/s. From the table, we can indicate the v2 which is 1/density. At 40oC v2 is equal to
1.006x10-3.
Mref = Vref/v2
= 0.003/1.006x10-3 = 2.982 kg/s
b) Evaporator cooling load
By using the table, we can find h3= 54.688 KJ/kg and from evaporated h4= 2451.0 KJ/kg.
Qevap = Mref (H4-H3)
= 2.982 (2451.0 54.688) = 7145.802 KW
c) Coefficient of performance
Referring to the data obtain, SW = 491
COPref = Qevap/ SW(1-1000)
= 7145.802 / 491(1-1000) = 14.55
d) Average COPref
To get the average COPref, we need use COP from 120, 240,360s for accuracy
Average COPref = (14.55+15.03+15.29)/3 = 14.96

11

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

7.0 DISCUSSIONS
From the result summary table obtained, as cooling load increase, the COPref
increases. This is the effect from the mass flow rate is increase or the value of h3 decrease.
When we increase the amount of cooling load definitely the mass flow rate is increase.
Furthermore according from reference, a rule of thumb is that the COP improves by 2 to 4
percent for each C the evaporating temperature is raised or condensing temperature is
lowered. But however, when we change the working fluid of condenser with air and the
working fluid of condenser with water (experiment d) the COPref is constant. If we look
closely at this state, the mass flow rate and h3 is remain constant at any time and so does h4,
that is why the COPref also does not change and remain constant. Along the experiment was
done, there might have some error such as before saving, the system maybe does not 100%
stabilized. The graph shown on the screen which shows the stabilization cannot be 100%
accurate as same as the actual system.

We look forward to the cooling medium effect, there is two types of medium used
which is water (experiment a) and air (experiment b). When water is used as the cooling
medium, the COP is much higher compare to air. The higher the COP equate to lower
operating cost. This shows that liquid/water cooling is a better cooling medium. This is
because air is not an outstanding thermal conductor (air has a thermal conductivity of 0.026
W/mK). A more effective method of cooling than air cooling is liquid/water cooling as the
heat transferring medium. One way of increasing the thermal efficiency of a water cooling
system is by placing coils inside the cooling channel to induce a turbulent flow of the
cooling liquid.
Load is the amount of heat energy to be removed from refrigerators by the HVAC
equipment to maintain the design temperature. In domestic fridge, the refrigeration cycle
for the fresh food compartment could be used directly subcool the condensate for the
freezer cycle, thereby shifting some of the cooling load from the freezer to the fresh food
cycle. Comparing the COP of a dual-cycle system to single-cycle system, in a related study
found a 23% improvement in overall COP for a dual cycle system using refrigerants R-142
and R-152 when the total cabinet loads are evenly distributed between the freezer and the
fresh food compartment.

12

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

Figure 1 : Refrigeration System Operating Characteristics

The refrigeration practice (with actual loads) in a factory. The refrigeration process
begins with the compressor. The process start when Ammonia gas is compressed until it
becomes very hot from the increased pressure. This heated gas flows through the coils
behind the refrigerator, which allow excess heat to be released into the surrounding air.
This is why users sometimes feel warm air circulating around the fridge. Eventually the
ammonia cools down to the point where it becomes a liquid. This liquid form of ammonia
is then forced through a device called an expansion valve. Essentially, the expansion valve
has such a small opening that the liquid ammonia is turned into a very cold, fast-moving
mist, evaporating as it travels through the coils in the freezer. Since this evaporation occurs
at -27 degrees F (-32 degrees Celsius), the ammonia draws heat from the surrounding area.
This is the Second Law of Thermodynamics in effect. Cold material, such as the
evaporating ammonia gas, tends to take heat from warmer materials, such as the water in
the ice cube tray.
As the evaporating ammonia gas absorbs more heat, its temperature rises. Coils
surrounding the lower refrigerator compartment are not as compact. The cool ammonia still
draws heat from the warmer objects in the fridge, but not as much as the freezer section.
The ammonia gas is drawn back into the compressor, where the entire cycle of
pressurization, cooling and evaporation begins anew

13

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

Figure 2: Batch-continuous air blast freezer with counter flow air circulation

Figure 3: Batch continuous air blast freezer with cross flow

14

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

8.0 CONCLUSION
As the conclusion, refrigerator consists with two compartments - one for frozen
items and the other for items requiring refrigeration but not freezing. The objective of this
experiment have been completely achieved by understanding the relation of various
condition with Coefficient of Performance, all the parameters required to be solved have
been calculated and solved accordingly. In addition, all of the experiments have eventually
being done according to the procedures given systematically and appropriately.

15

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

9.0 REFERENCES

1) Cengel, Ghajar., Heat and Mass Transfer : Fundamentals and Applications, 4th
edition in SI Units.
2) Cengel, Boles .,Thermodynamics : An Engineering Approach, 7th edition in SI
units
3) UiTM, Faculty of Mechanical Engineering ., MEC551 Thermal Engineering,
2013.

4) Welty, James R., et al. Fundamentals of momentum, heat, and mass transfer.
John Wiley & sons, 2009.
5) http://www.fridgesolutions.com/terms-considerations.html. Retrieved 4 April
2014

16

Thermofluids Lab-MEC 554/ LS 2/ Rev. 02-20012

10.0 APPENDICES